Plan Review Details - Permit 18100951
Plan Review Stops For Permit 18100951
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2018-11-21 Cont ID  
Sent By jduprey Date 2018-11-21 Time 13:49 Rev Time 0.00
Received By shill Date 2018-11-21 Time 13:42 Sent To E
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2019-01-02 Cont ID  
Sent By fgiaquin Date 2019-01-02 Time 05:56 Rev Time 0.00
Received By fgiaquin Date 2019-01-02 Time 05:22 Sent To I
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2018-11-26 Cont ID  
Sent By fgiaquin Date 2018-11-26 Time 06:45 Rev Time 0.00
Received By fgiaquin Date 2018-11-26 Time 06:27 Sent To I
Notes
2018-11-26 06:38:21ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. PROVIDE UL OR OTHER NRTL LISTINGS OF NEW EQUIPMENT
 AND MATERIALS. FBC 107.2.1 NEC 90.7,110.2,110.3B
  
 2. VALUE SEEMS LOW. PROVIDE COPY OF CONTRACT SIGNED BY
 BOTH OWNER AND CONTRACTOR. FBC 109.3 BUILDING PERMIT
 VALUATION. FOR PERMITTING PURPOSES, VALUATION OF
 BUILDINGS AND SYSTEMS SHALL BE TOTAL REPLACEMENT VALUE
 TO INCLUDE STRUCTURAL, ELECTRIC, PLUMBING, MECHANICAL,
 INTERIOR FINISH, RELATIVE SITE WORK, ARCHITECTURAL AND
 DESIGN FEES, MARKETING COSTS, OVERHEAD AND PROFIT;
 EXCLUDING ONLY LAND VALUE. VALUATION REFERENCES MAY
 INCLUDE THE LATEST PUBLISHED DATA OF NATIONAL
 CONSTRUCTION COST ANALYSIS SERVICES (MARSHALL-SWIFT,
 MEANS, ETC.), AS PUBLISHED BY INTERNATIONAL CODE
 CONGRESS. FINAL BUILDING PERMIT VALUATION SHALL BE SET
 BY THE BUILDING OFFICIAL.
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
 CODES IN EFFECT:
  
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2017 6TH ED.
 FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 V/R,
  
 FRANK GIAQUINTO III
 ELECTRICAL INSPECTOR
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 [email protected]
 CELL: 561-657-1653
  
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-11-26 Cont ID  
Sent By fgiaquin Date 2018-11-26 Time 06:45 Rev Time 0.00
Received By fgiaquin Date 2018-10-19 Time 13:37 Sent To  
Notes
2018-10-22 13:37:19ROUTED TO ZONING INBOX

Review Stop Z ZONING
Rev No 2 Status P Date 2019-01-07 Cont ID  
Sent By eschneid Date 2019-01-07 Time 17:06 Rev Time 0.25
Received By eschneid Date 2019-01-07 Time 17:06 Sent To PC
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2018-11-09 Cont ID  
Sent By eschneid Date 2018-11-09 Time 11:40 Rev Time 0.25
Received By eschneid Date 2018-11-09 Time 11:40 Sent To B
Notes
2018-11-09 11:41:18FAILED
  
 THE WIRELESS COMMUNICATION FACILITY APPLICATION
 REQUIRES APPROVAL BY CITYSCAPE PRIOR TO ZONING APPROVAL
 OF THE APPLICATION.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446
 [email protected]