Plan Review Details - Permit 18100882
Plan Review Stops For Permit 18100882
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2018-12-20 Cont ID  
Sent By dbattles Date 2018-12-20 Time 15:31 Rev Time 0.00
Received By dbattles Date 2018-12-20 Time 15:31 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2018-12-05 Cont ID  
Sent By dbattles Date 2018-12-05 Time 11:09 Rev Time 0.00
Received By dbattles Date 2018-12-04 Time 14:19 Sent To  
Notes
2018-12-05 11:09:41****CORRECTIONS****
 W.P.B. PERMIT: 18100882
 REVIEWED: DECEMBER 5, 2018
  
 DYLAN BATTLES
 BUILDING PLANS EXAMINER I
 [email protected]
 561-805-6718
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC AMENDED = FLORIDA BUILDING CODE,6TH EDITION (2017)
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC ENERGY = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 1. [FBC 107.2.1]ALL INFORMATION, DRAWINGS,
 SPECIFICATIONS AND ACCOMPANYING DATA SHALL BEAR THE
 NAME AND SIGNATURE OF THE PERSON RESPONSIBLE FOR THE
 DESIGN.
 PLEASE ADD NAME AND SIGNATURE OF DESIGNER TO THE PLANS.
  
 2. [FBC TABLE R602.3(3)NAIL SHEATHING TO MEET CURRENT
 SPACING PER TABLE WHERE REPLACING.
 WHAT EXISTING SUBSTRATE IS NEW SIDING BEING NAILED
 INTO? WHAT THICKNESS?
 A) VERTICAL SPACING OF SUPPORTING MEMBERS THAT
 SHEATHING ATTACHES TO?
 B) HOW MUCH AREA OF SIDING IS BEING REPLACED?
 C) WHAT IS BEING INSTALLED FOR VAPOR BARRIER?
 D) WHAT TYPE, SIZE AND AMOUNT OF CONNECTOR OF PER PIECE
 OF NEW SIDING?
  
 NOTE:
 -ADDITIONAL COMMENTS MAY BE FORTHCOMING PENDING REVIEW
 OF MATERIALS REQUESTED.
 -WHEN RESUBMITTING, PROVIDE TWO IDENTICAL COLLATED SETS
 OF DOCUMENTS FOR ISSUANCE. OLD SHEETS (BOTH SETS)
 SHOULD BE RETAINED IN THE PACKAGE; PLEASE DO NOT
 DISCARD ANY DOCUMENTS. THEY SHOULD BE BOUND TOGETHER
 SEPARATELY FROM THE TWO ISSUANCE SETS AND MARKED "VOID"
 OR "OLD SHEETS". PLEASE DO NOT STAMP THE PLANS VOID AS
 APPLICANTS ARE INADVERTENTLY STAMPING SHEETS THAT WE
 NEED "VOID", RENDERING THEM NOT USABLE.
  

Review Stop E ELECTRICAL
Rev No 1 Status N Date 2018-11-05 Cont ID  
Sent By jpearson Date 2018-11-05 Time 08:51 Rev Time 0.00
Received By jpearson Date 2018-11-05 Time 07:28 Sent To  
Notes
2018-11-05 08:51:55NO ELECTRICAL WORK REVIEWED OR APPROVED.

Review Stop HIST HISTORICAL
Rev No 1 Status P Date 2018-11-21 Cont ID  
Sent By fmittner Date 2018-11-21 Time 10:59 Rev Time 0.00
Received By fmittner Date 2018-11-21 Time 10:59 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2018-12-20 Cont ID  
Sent By dbattles Date 2018-12-20 Time 15:32 Rev Time 0.00
Received By dbattles Date 2018-12-18 Time 13:16 Sent To  
Notes
2018-12-20 14:03:56RESUB ROUTED TO DBATTLES' DESK 12/20/18
2018-12-19 13:16:52RESUB ROUTED TO JESMITH'S DESK

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-12-05 Cont ID  
Sent By dbattles Date 2018-12-05 Time 11:10 Rev Time 0.00
Received By dbattles Date 2018-10-18 Time 16:39 Sent To  
Notes
2018-10-19 16:39:13R01

Review Stop P PLUMBING
Rev No 2 Status P Date 2018-12-20 Cont ID  
Sent By jesmith Date 2018-12-20 Time 13:58 Rev Time 0.00
Received By jesmith Date 2018-12-20 Time 13:57 Sent To  
Notes
2018-12-20 13:57:43REVIEWED FOR CODE COMPLIANCE
 PLUMBING PROVISO
 1. ALL WORK PER CITY CODES SUBJECT TO FIELD INSPECTOR'S
 APPROVAL
 2. EXACT FIXTURE CHANGE OUT
 3. NEW SHOWER PANS AND ANTISCALD SHOWER VALVES ARE
 REQUIRED
  
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2018-12-04 Cont ID  
Sent By jesmith Date 2018-12-04 Time 15:00 Rev Time 0.00
Received By jesmith Date 2018-12-04 Time 14:59 Sent To  
Notes
2018-12-04 15:00:101ST REVIEW
 COMMENTS: DENIED
  
 1. DOES THE REMODELING OF THE BATHROOMS REQUIRE FIXTURE
 RECONFIGURATION? PLEASE CLARIFY PER WPB FBC 107.2.1.
 2. IF BATHROOM FIXTURES ARE RECONFIGURED THEN PROVIDE
 THE FOLLOWING:
 A. A SANITARY RISER DIAGRAM IS REQUIRED PER WPB FBC
 107.2.1.
 B. PROVIDE DETAILED FLOOR PLAN SHOWING ANY REQUIRED
 PARTITIONING FOR THE SHOWER AND PROVIDE SHOWER
 DIMENSIONS CONFORMING TO FBC RES 2708.1; SHOW MINIMUM
 COMPARTMENT CLEAR AND UNOBSTRUCTED ACCESS AND EGRESS
 OPENING AS REQUIRED BY FBC RES P2708.1.1. INDICATE
 WHETHER OR NOT THERE IS TO BE A SHOWER DOOR (IF SO, IT
 MUST CONFORM TO FBC RES 2708.1). PROVIDE THE LOCATION
 OF THE CONTROL VALVE PER WPB FBC 107.2.1.
 C. PROVIDE DETAILED FLOOR PLAN SHOWING COMPLIANCE WITH
 MINIMUM SPACE REQUIREMENTS IN ACCORDANCE WITH FBC RES
 P2705.1.5 WATER CLOSETS AND LAVATORIES. A WATER CLOSET,
 LAVATORY OR BIDET SHALL NOT BE SET CLOSER THAN 15
 INCHES (381 MM) FROM ITS CENTER TO ANY SIDE WALL,
 PARTITION OR VANITY OR CLOSER THAN 30 INCHES (762 MM)
 CENTER-TO-CENTER BETWEEN ADJACENT FIXTURES. THERE SHALL
 BE A CLEARANCE OF NOT LESS THAN 21 INCHES (533 MM) IN
 FRONT OF A WATER CLOSET, LAVATORY OR BIDET TO ANY WALL,
 FIXTURE OR DOOR.
 3. PROVIDE FULL PERMIT VALUATION INCLUDING PLUMBING
 COST PER WPB FBC 109.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 PHONE 561-805-6715
  
 CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RES = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 FBC ACC = FLORIDA ACCESSIBILITY CODE 2017 6TH EDITION
 FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION
 FBC FG = FLORIDA FUEL GAS CODE 2017 6TH EDITION
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES