Plan Review Details - Permit 18100841
Plan Review Stops For Permit 18100841
Review Stop E ELECTRICAL
Rev No 1 Status P Date 2018-10-25 Cont ID  
Sent By jleahy Date 2018-10-25 Time 16:10 Rev Time 0.00
Received By jleahy Date 2018-10-19 Time 16:10 Sent To  
Notes
2018-10-19 17:19:27FLORIDA BUILDING CODE 2017 6TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED
 NFPA 70 2014 EDITION
  
 JAKE LEAHY
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 CONTRACTOR NOT LICENSED FOR THIS TYPE OF WORK CVC FOR
 SOLAR WORK ONLY NOT TO CHANGE A SERVICE AND ADD
 BATTERIES TO A SERVICE.
  
 61G4-15.021 CERTIFICATION OF SOLAR CONTRACTORS.
  
 (A) ELECTRICAL WORK. THE BRANCH CIRCUIT SUPPLYING THE
 ELECTRIC WATER HEATER, THE RECEPTACLE OUTLET FOR A
 CORD-AND-PLUG-CONNECTED SOLAR CONTROLLER, THE SWIMMING
 POOL PUMP MOTOR, AND THE
 PREMISES WIRING ON THE LOAD SIDE OF THE PREMISES
 SERVICE DISCONNECTING MEANS SHALL BE IN ACCORDANCE WITH
 THE NATIONAL ELECTRIC CODE. IF INSTALLATION,
 ALTERATION, REMOVAL, REPLACEMENT,
 OR UPGRADING OF THIS CIRCUIT IS NECESSARY, THE WORK
 SHALL BE PERFORMED BY LICENSED ELECTRICAL CONTRACTORS
 ONLY.
  
 BATTERIES FOR SYSTEM ARE THEY LOCATED IN THE ECO 10
 CABINET 690.71
  
 GROUNDING OF SERVICE SHOWN WRONG ON PLAN FIRST MEANS OF
 DICONNECT IS THE ECO 10 UNIT. NEUTRAL BONDING AND
 GROUNDING ELECTRODE SHOULD OCCUR IN THE ECO 10 CABINET.
 250.24(C)
  
 PANELBOARD INSIDE SHALL ALL NEUTRALS AND GROUNDS
 SEPARATED.
  
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-10-19 Cont ID  
Sent By jleahy Date 2018-10-19 Time 16:12 Rev Time 0.00
Received By jleahy Date 2018-10-17 Time 14:51 Sent To  
Notes
2018-10-18 14:52:01ROUTED TO JLEAHY


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved