Plan Review Details - Permit 18100795
Plan Review Stops For Permit 18100795
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2019-02-20 Cont ID  
Sent By dbattles Date 2019-02-20 Time 14:57 Rev Time 0.00
Received By dbattles Date 2019-02-20 Time 14:50 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2018-12-05 Cont ID  
Sent By dbattles Date 2018-12-05 Time 15:02 Rev Time 0.00
Received By dbattles Date 2018-12-05 Time 13:26 Sent To  
Notes
2018-12-05 15:02:58****CORRECTIONS****
 W.P.B. PERMIT: 18100795
 REVIEWED: DECEMBER 5, 2018
  
 DYLAN BATTLES
 BUILDING PLANS EXAMINER I
 [email protected]
 561-805-6718
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC ENERGY = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 1. [FBC R301.2.1.2]INDICATE MODEL OF CASEMENT WINDOW
 AND IMPACT LEVEL BY UPLOADING FLORIDA PRODUCT APPROVAL.
 LOOK IN FL-13145 AND SELECT THE APPLICABLE ONE FOR YOUR
 WINDOWS.
  
 2. [FBC AMENDED 107.3.4.1]PROVIDE PRODUCT APPROVALS FOR
 FIXED WINDOWS, AND FRENCH DOORS, OR INDICATE THAT YOU
 WOULD LIKE THEM DEFERED.
 THE CCL THAT IS UPLOADED DOESN'T PROVIDE IMPACT
 INFORMATION.
 PLEASE UPLOAD ALL PRODUCT APPROVALS SPECIFIED ON A4.01
 DOOR AND WOINDOW SCHEDULE.
  
 3. [FBC R308.3]HUMAN IMPACT LOADS.
 PROVIDE CATEGORY AND LOADS FOR GLASS GUARD TO COMPLY
 WITH ON SHEET A3.05, OR INDICATE THAT IT WILL BE A
 DEFERRED SUBMITTAL.
  
 NOTE:
 -PLEASE PROVIDE COMMENT RESPONSE SHEET TO EXPLAIN HOW
 EACH COMMENT IS BEING ADDRESSED.
 -ADDITIONAL COMMENTS MAY BE FORTHCOMING PENDING REVIEW
 OF MATERIALS REQUESTED.
 -WHEN RESUBMITTING, PROVIDE TWO IDENTICAL COLLATED SETS
 OF DOCUMENTS FOR ISSUANCE. OLD SHEETS (BOTH SETS)
 SHOULD BE RETAINED IN THE PACKAGE; PLEASE DO NOT
 DISCARD ANY DOCUMENTS. THEY SHOULD BE BOUND TOGETHER
 SEPARATELY FROM THE TWO ISSUANCE SETS AND MARKED "VOID"
 OR "OLD SHEETS". PLEASE DO NOT STAMP THE PLANS VOID AS
 APPLICANTS ARE INADVERTENTLY STAMPING SHEETS THAT WE
 NEED "VOID", RENDERING THEM NOT USABLE.
  

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2019-04-23 Cont ID  
Sent By jpearson Date 2019-04-23 Time 10:45 Rev Time 0.00
Received By jpearson Date 2019-04-23 Time 10:45 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2019-04-01 Cont ID  
Sent By cthroop Date 2019-04-01 Time 12:50 Rev Time 0.00
Received By cthroop Date 2019-04-01 Time 09:50 Sent To  
Notes
2019-04-01 13:19:14ELECTRICAL PLAN REVIEW
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 BUILDING PLANS EXAMINER, PX3169
 1&2 FAMILY PLANS EXAMINER, SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 2ND REVIEW
 RESULTS: DENIED
 YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED
 BELOW.
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. SMOKE DETECTORS ARE RECIEVING POWER FROM TWO
 SEPERATE SERVICE PANELS, CIRCUT 36 ON PANEL (N) K AND
 CIRCUT 5 ON PANEL (E) NP.
 R314.4 INTERCONNECTION.
 WHERE MORE THAN ONE SMOKE ALARM IS REQUIRED TO BE
 INSTALLED WITHIN AN INDIVIDUAL DWELLING UNIT IN
 ACCORDANCE WITH SECTION R314.3, THE ALARM DEVICES SHALL
 BE INTERCONNECTED IN SUCH A MANNER THAT THE ACTUATION
 OF ONE ALARM WILL ACTIVATE ALL OF THE ALARMS IN THE
 INDIVIDUAL DWELLING UNIT. PHYSICAL INTERCONNECTION OF
 SMOKE ALARMS SHALL NOT BE REQUIRED WHERE LISTED
 WIRELESS ALARMS ARE INSTALLED AND ALL ALARMS SOUND UPON
 ACTIVATION OF ONE ALARM.
  
 2. IT APPEARS SOME SMALL APPLIANCES ARE NOT INCLUDED IN
 LOAD CALCULATION.
 PROVIDE ACCURATE LOAD CALCULATION INCLUDING ALL LOADS.
 NEC 220; FBC RE E3602.2.
  
 3. COMPACTOR ON PANEL K IS NOT INCLUDED IN LOAD
 CALCULATION. LOADS NOT INCLUDED IN SQ. FTG. CALC. SHALL
 BE LISTED ON PANEL SCHEDULE.
 PROVIDE LOAD CALCULATION FOR SERVICE, INCLUDE EXISTING
 AND NEW LOADS TO CONFIRM CAPACITY OF SERVICE IS
 ADEQUATE. NEC 215.2, 220, 408.30; FBC RE E3602.2.
  
 4. WALL OVEN IS NOT INCLUDED IN LOAD CALC.
 PROVIDE ACCURATE LOAD CALCULATION INCLUDING ALL LOADS.
 NEC 220; FBC RE E3602.2.
  
 5. PROVIDE PANEL LOAD CALCULATIONS FOR NEW PANEL K.
 PROVIDE ACCURATE LOAD CALCULATION INCLUDING ALL LOADS.
 NEC 220; FBC RE E3602.2.
  
 6. PROVIDE REVISED LOAD CALCULATIONS FOR MAIN SERVICE
 PANEL H BASED ON THE ADJUSTMENTS MADE, (SEE ABOVE).
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO SUBMITTAL AND LEAVE THE PREVIOUSLY
 REVIEWED SHEETS DETACHED.
  
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2019-02-26 Cont ID  
Sent By jpearson Date 2019-02-26 Time 13:16 Rev Time 0.00
Received By fmittner Date 2019-02-28 Time 10:25 Sent To  
Notes
2019-04-01 09:51:13THIS REVIEW WAS PASSED BY MISTAKE BY FMITTNER (ZONING).
 CT

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2018-11-05 Cont ID  
Sent By jpearson Date 2018-11-05 Time 14:08 Rev Time 0.00
Received By jpearson Date 2018-11-05 Time 12:51 Sent To  
Notes
2018-11-05 14:08:30CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. PROVIDE PANEL SCHEDULE INDICATING ANY NEW OR ALTERED
 CIRCUITS, THE WIRE AND BREAKER SIZE FOR THESE CIRCUITS,
 AND AFCI OR GFCI PROTECTION WHERE APPLICABLE TO COMPLY
 WITH CODE. NEC 210.8, 210.12, 210.19, 210.20, 215.5,
 408.4; WPB FBC 107.3.5; FBC RE E3706.2, E3902
 2. AFCI PROTECTION SHOWN IN NOT CODE COMPLIANT. ALL
 BRANCH CIRCUITS THAT SUPPLY 120-VOLT, SINGLE-PHASE, 15-
 AND 20-AMPERE OUTLETS INSTALLED IN KITCHENS, FAMILY
 ROOMS, DINING ROOMS, LIVING ROOMS, PARLORS, LIBRARIES,
 DENS, BEDROOMS, SUN-ROOMS, RECREATIONS ROOMS, CLOSETS,
 HALLWAYS, LAUNDRY AREAS AND SIMILAR ROOMS OR AREAS
 SHALL BE AFCI PROTECTED. THIS INCLUDES LIGHTING AND
 POWER OUTLETS AND RECEPTACLES. SOME AREAS REQUIRE BOTH
 AFCI AND GFCI PROTECTION. PROVIDE CORRECTION. NEC
 210.8, 210.12; FBC RE E3902; FBC EX 607.1.1 OR 801.1,
 801.2, OR 901.2 AS APPLICABLE.
 3. PROVIDE SMOKE/CO ALARMS IN EACH LOCATION REQUIRED
 PER CODE. PROVIDE FULL FLOOR PLAN SHOWING ALL EXISTING
 ALARMS. IF NONE ARE EXISTING OR NOT TO CODE, SHOW AS
 NEW INSTALLATIONS. FBC RE R314.3, R315.1; WPB FBC
 107.2.1
 4. PROVIDE RISER DIAGRAM, SHOWING ALL DETAILS OF
 SERVICE EQUIPMENT, UNDERGROUND OR OVERHEAD SERVICE,
 WIRE AND BREAKER SIZES FOR SERVICE AND FEED TO ANY
 SUB-PANEL(S). SHOW GEC SIZE AND SYSTEM, SHOW
 INTERSYSTEM BONDING TERMINATION POINT. NEC 215.5, 230,
 250.50, 250.94, 408.30; FBC RE E3706.1, E3608.1,
 E3609.3; WPB FBC 107.2.1
 5. IF ANY LOAD IS BEING ADDED, PROVIDE LOAD CALCULATION
 FOR SERVICE, INCLUDE EXISTING AND NEW LOADS TO CONFIRM
 CAPACITY OF SERVICE IS ADEQUATE. NEC 215.2, 220,
 408.30; FBC RE E3602.2
 6. PROVIDE GFCI PROTECTION FOR DISHWASHER. NEC
 210.8(D); FBC RE E3902.10
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD
 SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop G GAS REVIEW
Rev No 4 Status P Date 2019-04-16 Cont ID  
Sent By thunt Date 2019-04-16 Time 07:54 Rev Time 0.00
Received By thunt Date 2019-04-16 Time 07:19 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 3 Status F Date 2019-03-26 Cont ID  
Sent By thunt Date 2019-03-26 Time 14:32 Rev Time 0.00
Received By thunt Date 2019-03-26 Time 14:32 Sent To  
Notes
2019-03-26 14:32:01GAS 3RD REVIEW**DENIED**?
  
 WITH RESPECT TO EVALUATION OF DESIGN PROFESSIONALS &
 DOCUMENTS, IF A LOCAL GOVERNMENT FINDS IT NECESSARY, IN
 ORDER TO ENFORCE COMPLIANCE WITH THE FLORIDA BUILDING
 CODE AND ISSUE A PERMIT, TO REJECT DESIGN DOCUMENTS
 REQUIRED BY THE CODE THREE OR MORE TIMES FOR FAILURE TO
 CORRECT A CODE VIOLATION SPECIFICALLY AND CONTINUOUSLY
 NOTED IN EACH REJECTION, INCLUDING, BUT NOT LIMITED TO,
 EGRESS, FIRE PROTECTION, STRUCTURAL STABILITY, ENERGY,
 ACCESSIBILITY, LIGHTING, VENTILATION, ELECTRICAL,
 MECHANICAL, PLUMBING, AND GAS SYSTEMS, OR OTHER
 REQUIREMENTS IDENTIFIED BY RULE OF THE FLORIDA BUILDING
 COMMISSION ADOPTED PURSUANT TO CHAPTER 120, THE LOCAL
 GOVERNMENT SHALL IMPOSE, EACH TIME AFTER THE THIRD SUCH
 REVIEW THE PLANS ARE REJECTED FOR THAT CODE VIOLATION,
 A FEE OF FOUR TIMES THE AMOUNT OF THE PROPORTION OF THE
 PERMIT FEE ATTRIBUTED TO PLANS REVIEW.
  
 1) SHT. P1.01 AND P1.02 ARE STILL NOT SIGNED
 ELECTRONICALLY AS PER F.A.C RULE 61G1-16.005
  
 2) PROVIDE A GAS ISOMETRIC DRAWING. FBC 107.3.5.SUBMIT
 AN ISOMETRIC DRAWING THAT CLEARLY SHOWS THE LENGTH OF
 ALL CUT SECTIONS OF PIPE PER 2017 FBC-FUEL GAS, SECS.
 402.4.1, 402.4.2. OR 2017 FBC-RES SEC. G2413.4.1,
 G2413.4.2.
  
 3) PROVIDE SIZING CHART FOR GAS PIPING AFTER THE
 PRESSURE REGULATOR FOR THE 1/2LB SYSTEM AND SHOW
 DISTANCE.) SUBMIT TWO COPIES OF THE APPLICABLE SIZING
 TABLES USED TO SIZE THE GAS SYSTEM OR PLACE A NOTE ON
 THE PLANS/DRAWINGS SPECIFYING WHICH SIZING TABLE(S)
 FROM THE GAS CODE OR OTHER STANDARD THAT WERE USED IN
 THE DESIGN OF THIS GAS SYSTEM. REFER TO THE 2017
 FBC-FUEL GAS SECS. 401.4, 401.8, 402.3, AND TABLES
 402.4 (1) THRU 402.4 (37) OR 2017 FBC-RES. SEC.
 G2413.3, G2412.8, G2413.1, G2413.2, & G2413.3
  
 4) SUBMIT MANUFACTURER?S SPECIFICATIONS FOR THE
 PRESSURE REGULATORS. REGULATORS INSTALLED ON THE
 EXTERIOR OF THE BUILDING SHALL BE APPROVED FOR OUTDOOR
 INSTALLATION. 2014 FGC SEC.410.1, 2017 FBC-RES. SEC.
 G2421.1.
  
 5) PROVIDE GAS COOK TOP MANUFACTURE INSTALLATION MANUAL
 SHOWING IT IS LISTED AND LABELED. FBC-R G2404.3
  
 6) GAS FLAT DRAWING SHOW'S GAS METER AS HAVING 3 OULET
 PORTS. PER GAS PROVIDER THERE IS NOT SUCH METER ON THE
 MARKET AND IT ONLY HAS 1 INLET AND 1 OUTLET. PROVIDE A
 CORRECT FLAT DRAWING SHOWING CORRECT PIPING
 ORIENTATIONS AND PIPE SIZE'S AND MATERIAL FROM THE
 METER TO THE NEW GAS COOK TOP. 2017 FBC-FUEL GAS, SECS.
 402.4.1, 402.4.2. OR 2017 FBC-RES SEC. G2413.4.1,
 G2413.4.2.
  
  
 PLEASE FEEL FREE TO CONTRACT THIS PLAN REVIEW SO THAT I
 CAN ASSIST YOU IN COMPLYING
  
 TIM HUNT
 PLUMBING PLANS EXAMINER
 BUILDING DIVISION
 CITY OF WEST PALM BEACH
 401 CLEMATIS STREET, 1ST FLOOR
 WEST PALM BEACH, FL 33401
 561-248-2703
 [email protected]
  
  

Review Stop G GAS REVIEW
Rev No 2 Status F Date 2019-02-21 Cont ID  
Sent By jesmith Date 2019-02-21 Time 15:29 Rev Time 0.00
Received By jesmith Date 2019-02-21 Time 15:31 Sent To  
Notes
2019-02-21 15:29:32CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RES = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 FBC ACC = FLORIDA ACCESSIBILITY CODE 2017 6TH EDITION
 FBC EX = FLORIDA EXISTING BUILDING CODE 2017 6TH
 EDITION
 FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION
 FBC FG = FLORIDA FUEL GAS CODE 2017 6TH EDITION
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
  
 2ND REVIEW:DENIED
 DIGITAL SIGNATURE REQUIRED ON THE PLUMBING PLAN P1.01
 IS REQUIRED
 ADDITIONAL COMMENTS
 RE: P1.01 DETAIL 6-GAS RISER DIAGRAM
 1. YOU ARE REFERENCING TWO (2) DIFFERENT TABLES FBC FG
 402.4(1) INLET PRESSURE LESS THAN 2PSI AND
 INTERNATIONAL FG TABLE 402.4(5) INLET PRESSURE 2 PSI.
 PLEASE CLARIFY. ALSO NOTE THAT THE INTERNATIONAL FUEL
 GAS CODE IS NOT RECOGNIZED BY WPB FBC AND THE
 APPROPRIATE TABLE MUST BE NOTED AS FBC FUEL GAS CODE.
 2. DO EACH OF THE RUNOUTS CONNECT INDEPENDENTLY TO THE
 GAS METER AS SHOWN OR IS THE NEW GAS RANGE SUPPLY
 PIPING CONNECTED TO THE EXISTING PIPING? PLEASE
 CLARIFY.
 3. A PREVIOUS PERMITTED PROJECT PLAN SHOWS THE GAS
 METER, THE POOL HEATER AND THE NEW TANKLESS HEATER AND
 NO OVEN. I CANNOT RECONCILE THE FOOT PRINT OF THE THE
 NEW FLOOR PLAN WITH THE EXISTING. PER WPB FBC 107.2.1
 PROVIDE A FOOTPRINT (IE. SITE PLAN SHOWING LOCATION OF
 NEW WORK AS WELL AS EXISTING GAS METER, POOL HEATER,
 ETC.) THAT WILL ALLOW THE NEW WORK TO BE MATCHED TO THE
 EXISTING PER WPB FBC 107.2.1. FYI REFERENCE WPB PERMIT
 17010488.
  
  
  
 SUBMITTAL OF ADDITIONAL AND/OR REVISED MATERIALS,
 ESPECIALLY AS A RESULT OF RESPONSE TO BUILDING REVIEW
 COMMENTS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED "VOID".
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 PHONE 561-805-6715

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2018-12-06 Cont ID  
Sent By jesmith Date 2018-12-06 Time 14:40 Rev Time 0.00
Received By jesmith Date 2018-12-06 Time 13:41 Sent To  
Notes
2018-12-06 14:40:24CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RES = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 FBC ACC = FLORIDA ACCESSIBILITY CODE 2017 6TH EDITION
 FBC EX = FLORIDA EXISTING BUILDING CODE 2017 6TH
 EDITION
 FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
 1ST REVIEW: DENIED
 GAS COMMENTS
 1. SUBMIT THE FOLLOWING PER WPB FBC 107.2.1
 A) SUBMIT AN ISOMETRIC DRAWING THAT CLEARLY SHOWS THE
 LENGTH OF ALL CUT SECTIONS OF PIPE PER FBC RES
 G2413.4.1 AND G2413.4.2.
 B) LIST THE BTU LOAD OF EACH APPLIANCE AND THE TOTAL
 BTU LOAD ON THE SYSTEM FBC RES G2413.3, G2413.4 AND
 TABLES G2413.4 (1) THROUGH G2413.4 (21).
 C) SHOW THE DISTANCE FROM THE POINT OF DELIVERY TO THE
 MOST REMOTE OUTLET IN THE BUILDING AND / OR SYSTEM PER
 FBC RES G2413.4.1, G2413.4.2.
 D) SUBMIT MANUFACTURER?S SPECIFICATION SHEETS /
 INSTALLATION MANUAL FOR ALL GAS EQUIPMENT TO VERIFY
 COMPLIANCE WITH STANDARDS NFPA 54, NFPA 58 AND FBC RES
 G2404.3. GAS APPLIANCES SHALL BE LISTED AND LABELED.
 THE INSTALLATION MANUALS FOR ALL GAS APPLIANCES /
 EQUIPMENT SHALL BE ONSITE AT THE TIME OF INSPECTION PER
 FBC RES G2408.1.
 E) SUBMIT MANUFACTURER?S SPECIFICATIONS FOR THE
 PRESSURE REGULATORS AT THE RANGE. FBC RES G2421.1.
 F) SUBMIT COMBUSTION AIR CALCULATIONS FOR THE GAS
 APPLIANCE. WHERE COMBUSTION AIR IS PROVIDED BY THE
 BUILDING?S MECHANICAL VENTILATION SYSTEM, THE SYSTEM
 SHALL PROVIDE THE SPECIFIED COMBUSTION AIR RATE IN
 ADDITION TO THE REQUIRED VENTILATION AIR. 2017 FBC-FUEL
 GAS SEC.304.9.3 OR FBCR G2407.9.3.
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 PHONE 561-805-6715
  

Review Stop HIST HISTORICAL
Rev No 1 Status P Date 2018-10-23 Cont ID  
Sent By fmittner Date 2018-10-23 Time 12:30 Rev Time 0.00
Received By fmittner Date 2018-10-23 Time 12:30 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2019-04-24 Cont ID  
Sent By cthroop Date 2019-04-24 Time 11:45 Rev Time 0.00
Received By cthroop Date 2019-04-08 Time 09:28 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2019-04-01 Cont ID  
Sent By cthroop Date 2019-04-01 Time 13:25 Rev Time 0.00
Received By cthroop Date 2019-03-15 Time 15:35 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2019-03-04 Cont ID  
Sent By shill Date 2019-02-28 Time 06:33 Rev Time 0.00
Received By shill Date 2019-02-13 Time 16:04 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-12-06 Cont ID  
Sent By lmarchan Date 2018-12-06 Time 15:23 Rev Time 0.00
Received By lmarchan Date 2018-10-18 Time 16:39 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2018-11-06 Cont ID  
Sent By cmontell Date 2018-11-06 Time 10:12 Rev Time 0.00
Received By cmontell Date 2018-11-06 Time 10:01 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 4 Status P Date 2019-04-16 Cont ID  
Sent By thunt Date 2019-04-16 Time 07:43 Rev Time 0.00
Received By thunt Date 2019-04-16 Time 07:19 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status F Date 2019-03-26 Cont ID  
Sent By thunt Date 2019-03-26 Time 14:39 Rev Time 0.00
Received By thunt Date 2019-03-26 Time 13:32 Sent To  
Notes
2019-03-26 14:39:44PLUMBING 3RD REVIEW**DENIED**
  
 WITH RESPECT TO EVALUATION OF DESIGN PROFESSIONALS &
 DOCUMENTS, IF A LOCAL GOVERNMENT FINDS IT NECESSARY, IN
 ORDER TO ENFORCE COMPLIANCE WITH THE FLORIDA BUILDING
 CODE AND ISSUE A PERMIT, TO REJECT DESIGN DOCUMENTS
 REQUIRED BY THE CODE THREE OR MORE TIMES FOR FAILURE TO
 CORRECT A CODE VIOLATION SPECIFICALLY AND CONTINUOUSLY
 NOTED IN EACH REJECTION, INCLUDING, BUT NOT LIMITED TO,
 EGRESS, FIRE PROTECTION, STRUCTURAL STABILITY, ENERGY,
 ACCESSIBILITY, LIGHTING, VENTILATION, ELECTRICAL,
 MECHANICAL, PLUMBING, AND GAS SYSTEMS, OR OTHER
 REQUIREMENTS IDENTIFIED BY RULE OF THE FLORIDA BUILDING
 COMMISSION ADOPTED PURSUANT TO CHAPTER 120, THE LOCAL
 GOVERNMENT SHALL IMPOSE, EACH TIME AFTER THE THIRD SUCH
 REVIEW THE PLANS ARE REJECTED FOR THAT CODE VIOLATION,
 A FEE OF FOUR TIMES THE AMOUNT OF THE PROPORTION OF THE
 PERMIT FEE ATTRIBUTED TO PLANS REVIEW.
  
  
 1) PLUMBING SHEETS P1.01 AND P1.02 ARE STILL NOT SIGNED
 DIIGITALLY SIGNED AS STATED IN F.A.C RULE 61G1-16.005
  
 2) POWER BATHROOM FITTING APPEAR TO BE BACKWARDS.
 FITTING MUST BE INSTALLED IN DIRECTION OF FLOW. FBC
 706.3
  
 3) THE POWER BATH TOILET IS NOT PERMITTED TO BE WET
 VENTED INTO THE BUILDING DRAIN. ONLY OTHER BATHROOM
 FIXTURES UP TO 2 AND ON THE SAME SAME FLOOR ARE
 PERMITTED TO DRAIN INTO THE BATHROOM WET VENT
  
  
 TIM HUNT
 PLUMBING PLANS EXAMINER
 BUILDING DIVISION
 CITY OF WEST PALM BEACH
 401 CLEMATIS STREET, 1ST FLOOR
 WEST PALM BEACH, FL 33401
 561-248-2703
 [email protected]
  
  

Review Stop P PLUMBING
Rev No 2 Status F Date 2019-02-21 Cont ID  
Sent By jesmith Date 2019-02-21 Time 14:17 Rev Time 0.00
Received By jesmith Date 2019-02-21 Time 14:06 Sent To  
Notes
2019-02-21 14:17:04CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RES = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 FBC ACC = FLORIDA ACCESSIBILITY CODE 2017 6TH EDITION
 FBC EX = FLORIDA EXISTING BUILDING CODE 2017 6TH
 EDITION
 FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION
 FBC FG = FLORIDA FUEL GAS CODE 2017 6TH EDITION
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
  
 2ND REVIEW:DENIED
 DIGITAL SIGNATURE REQUIRED ON THE PLUMBING PLAN P1.01
 IS REQUIRED
 1. PLUMBING DRAWINGS ARE CODE COMPLIANT AND UPON
 RECEIPT OF DIGITALLY SIGNED PLAN WILL BE APPROVED.
 2. ALL WORK PER CITY CODES SUBJECT TO FIELD INSPECTOR'S
 APPROVAL
  
  
 SUBMITTAL OF ADDITIONAL AND/OR REVISED MATERIALS,
 ESPECIALLY AS A RESULT OF RESPONSE TO BUILDING REVIEW
 COMMENTS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED "VOID".
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 PHONE 561-805-6715

Review Stop P PLUMBING
Rev No 1 Status F Date 2018-12-06 Cont ID  
Sent By jesmith Date 2018-12-06 Time 14:42 Rev Time 0.00
Received By jesmith Date 2018-12-06 Time 13:40 Sent To  
Notes
2018-12-06 13:41:10CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RES = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 FBC ACC = FLORIDA ACCESSIBILITY CODE 2017 6TH EDITION
 FBC EX = FLORIDA EXISTING BUILDING CODE 2017 6TH
 EDITION
 FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
 1ST REVIEW: DENIED
 1. THE DISHWASHER DISCHARGE PIPE OR TUBING SHALL RISE
 TO THE UNDERSIDE OF THE COUNTER AND BE FASTENED OR
 OTHERWISE HELD IN THAT POSITION BEFORE CONNECTING TO
 THE HEAD OF THE FOOD-WASTE DISPOSER OR TO A WYE FITTING
 IN THE SINK TAILPIECE NOT DOWNSTREAM OF THE TRAP PER
 FBC RES P2717.2.
 2. ICE MAKER AND REFRIGERATOR/FREEZER DISCHARGES SHALL
 NOT BE CONNECTED DIRECTLY TO THE SANITARY. PROVIDE
 INDIRECT WASTE THROUGH AN AIR GAP TO A TRAPPED AND
 VENTED WASTE RECEPTOR SUCH AS A HUB DRAIN OR FLOOR SINK
 IN ACCORDANCE WITH FBC RES P2706 AND FBC PL 802.2.
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 PHONE 561-805-6715
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 4 Status P Date 2019-04-16 Cont ID  
Sent By thunt Date 2019-04-16 Time 07:55 Rev Time 0.00
Received By thunt Date 2019-04-16 Time 07:55 Sent To  
Notes
2019-04-16 07:56:02ALL SHEETS OK
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status F Date 2019-04-01 Cont ID  
Sent By cthroop Date 2019-04-01 Time 13:26 Rev Time 0.00
Received By cthroop Date 2019-04-01 Time 09:50 Sent To  
Notes
2019-04-01 13:29:04BUILDING PLAN REVIEW - DIGITAL SIGNATURE
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 BUILDING PLANS EXAMINER, PX3169
 1&2 FAMILY PLANS EXAMINER, SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 1ST REVIEW
 RESULTS: DENIED
 YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED
 BELOW.
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 CANNOT VERIFY DIGITAL SIGNATURE AND SEAL ON PLAN PAGES
 E3.01, E6.01 AND E7.01.
  
 1. DIGITAL SIGNATURES/SEALS ARE NOT IN ACCORDANCE WITH
 FS 471, FS 481 AS NOTED. NEW SHEETS SUBMITTED IN THE
 NEXT REVIEW CYCLE REQUIRE REVIEW.
  
 2. UPLOAD VIA THE PROJECTDOX PORTAL WITH DIGITAL
 SIGNATURES OF DESIGN PROFESSIONALS AS APPLICABLE; USE
 THE REQUIRED NAMING CONVENTION FOR EACH DOCUMENT.
  
 ALSO SEE COMMENTS UNDER PLUMBING REVIEW FOR PLAN PAGES
 P1.01 AND P1.02.
  
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status F Date 2019-02-20 Cont ID  
Sent By dbattles Date 2019-02-20 Time 15:05 Rev Time 0.00
Received By dbattles Date 2019-02-20 Time 14:50 Sent To  
Notes
2019-02-20 15:06:152ND REVIEW SHEETS NOT DIGITALLY SIGNED
 E3.01
 E6.01
 E-7.01
 P1.01
  
 IF THIRD REVIEW IS NEEDED, ANY NEW SHEETS WILL NEED TO
 BE DIGITALLY SIGNED.

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2019-02-26 Cont ID  
Sent By jpearson Date 2018-11-05 Time 13:57 Rev Time 0.00
Received By jpearson Date 2018-11-05 Time 13:57 Sent To  
Notes
2019-02-26 13:13:34CHANGED STATUS TO REFLECT NEW SUBMISSION.

Review Stop Z ZONING
Rev No 2 Status P Date 2019-02-28 Cont ID  
Sent By fmittner Date 2019-02-28 Time 10:26 Rev Time 0.00
Received By fmittner Date 2019-02-28 Time 10:26 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2018-10-23 Cont ID  
Sent By fmittner Date 2018-10-23 Time 12:30 Rev Time 0.00
Received By fmittner Date 2018-10-23 Time 12:30 Sent To  
Notes
***NONE***