Plan Review Details - Permit 18100795
| Plan Review Stops For Permit 18100795 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
P |
Date |
2019-02-20 |
|
|
Cont ID |
|
| Sent By |
dbattles |
Date |
2019-02-20 |
Time |
14:57 |
Rev Time |
0.00 |
| Received By |
dbattles |
Date |
2019-02-20 |
Time |
14:50 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2018-12-05 |
|
|
Cont ID |
|
| Sent By |
dbattles |
Date |
2018-12-05 |
Time |
15:02 |
Rev Time |
0.00 |
| Received By |
dbattles |
Date |
2018-12-05 |
Time |
13:26 |
Sent To |
|
|
| Notes |
| 2018-12-05 15:02:58 | ****CORRECTIONS**** | | | W.P.B. PERMIT: 18100795 | | | REVIEWED: DECEMBER 5, 2018 | | | | | | DYLAN BATTLES | | | BUILDING PLANS EXAMINER I | | | [email protected] | | | 561-805-6718 | | | | | | FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) | | | FBC B = FBC BUILDING | | | FBC EB = FBC EXISTING BUILDING | | | FBC A = FBC ACCESSIBILITY | | | FBC ENERGY = FBC ENERGY CONSERVATION | | | FBC R = FBC RESIDENTIAL | | | | | | 1. [FBC R301.2.1.2]INDICATE MODEL OF CASEMENT WINDOW | | | AND IMPACT LEVEL BY UPLOADING FLORIDA PRODUCT APPROVAL. | | | LOOK IN FL-13145 AND SELECT THE APPLICABLE ONE FOR YOUR | | | WINDOWS. | | | | | | 2. [FBC AMENDED 107.3.4.1]PROVIDE PRODUCT APPROVALS FOR | | | FIXED WINDOWS, AND FRENCH DOORS, OR INDICATE THAT YOU | | | WOULD LIKE THEM DEFERED. | | | THE CCL THAT IS UPLOADED DOESN'T PROVIDE IMPACT | | | INFORMATION. | | | PLEASE UPLOAD ALL PRODUCT APPROVALS SPECIFIED ON A4.01 | | | DOOR AND WOINDOW SCHEDULE. | | | | | | 3. [FBC R308.3]HUMAN IMPACT LOADS. | | | PROVIDE CATEGORY AND LOADS FOR GLASS GUARD TO COMPLY | | | WITH ON SHEET A3.05, OR INDICATE THAT IT WILL BE A | | | DEFERRED SUBMITTAL. | | | | | | NOTE: | | | -PLEASE PROVIDE COMMENT RESPONSE SHEET TO EXPLAIN HOW | | | EACH COMMENT IS BEING ADDRESSED. | | | -ADDITIONAL COMMENTS MAY BE FORTHCOMING PENDING REVIEW | | | OF MATERIALS REQUESTED. | | | -WHEN RESUBMITTING, PROVIDE TWO IDENTICAL COLLATED SETS | | | OF DOCUMENTS FOR ISSUANCE. OLD SHEETS (BOTH SETS) | | | SHOULD BE RETAINED IN THE PACKAGE; PLEASE DO NOT | | | DISCARD ANY DOCUMENTS. THEY SHOULD BE BOUND TOGETHER | | | SEPARATELY FROM THE TWO ISSUANCE SETS AND MARKED "VOID" | | | OR "OLD SHEETS". PLEASE DO NOT STAMP THE PLANS VOID AS | | | APPLICANTS ARE INADVERTENTLY STAMPING SHEETS THAT WE | | | NEED "VOID", RENDERING THEM NOT USABLE. | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
4 |
Status |
P |
Date |
2019-04-23 |
|
|
Cont ID |
|
| Sent By |
jpearson |
Date |
2019-04-23 |
Time |
10:45 |
Rev Time |
0.00 |
| Received By |
jpearson |
Date |
2019-04-23 |
Time |
10:45 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
F |
Date |
2019-04-01 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2019-04-01 |
Time |
12:50 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2019-04-01 |
Time |
09:50 |
Sent To |
|
|
| Notes |
| 2019-04-01 13:19:14 | ELECTRICAL PLAN REVIEW | | | 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST | | | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, | | | CHAPTER 1 ADMINISTRATION | | | | | | CHRISTOPHER S. THROOP, C.B.O. | | | BUILDING PLANS EXAMINER, PX3169 | | | 1&2 FAMILY PLANS EXAMINER, SFP306 | | | CONSTRUCTION SERVICES DIVISION | | | TEL: 561-805-6726 | | | FAX: 561-805-6676 | | | E-MAIL: [email protected] | | | | | | 2ND REVIEW | | | RESULTS: DENIED | | | YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED | | | BELOW. | | | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT | | | | | | 1. SMOKE DETECTORS ARE RECIEVING POWER FROM TWO | | | SEPERATE SERVICE PANELS, CIRCUT 36 ON PANEL (N) K AND | | | CIRCUT 5 ON PANEL (E) NP. | | | R314.4 INTERCONNECTION. | | | WHERE MORE THAN ONE SMOKE ALARM IS REQUIRED TO BE | | | INSTALLED WITHIN AN INDIVIDUAL DWELLING UNIT IN | | | ACCORDANCE WITH SECTION R314.3, THE ALARM DEVICES SHALL | | | BE INTERCONNECTED IN SUCH A MANNER THAT THE ACTUATION | | | OF ONE ALARM WILL ACTIVATE ALL OF THE ALARMS IN THE | | | INDIVIDUAL DWELLING UNIT. PHYSICAL INTERCONNECTION OF | | | SMOKE ALARMS SHALL NOT BE REQUIRED WHERE LISTED | | | WIRELESS ALARMS ARE INSTALLED AND ALL ALARMS SOUND UPON | | | ACTIVATION OF ONE ALARM. | | | | | | 2. IT APPEARS SOME SMALL APPLIANCES ARE NOT INCLUDED IN | | | LOAD CALCULATION. | | | PROVIDE ACCURATE LOAD CALCULATION INCLUDING ALL LOADS. | | | NEC 220; FBC RE E3602.2. | | | | | | 3. COMPACTOR ON PANEL K IS NOT INCLUDED IN LOAD | | | CALCULATION. LOADS NOT INCLUDED IN SQ. FTG. CALC. SHALL | | | BE LISTED ON PANEL SCHEDULE. | | | PROVIDE LOAD CALCULATION FOR SERVICE, INCLUDE EXISTING | | | AND NEW LOADS TO CONFIRM CAPACITY OF SERVICE IS | | | ADEQUATE. NEC 215.2, 220, 408.30; FBC RE E3602.2. | | | | | | 4. WALL OVEN IS NOT INCLUDED IN LOAD CALC. | | | PROVIDE ACCURATE LOAD CALCULATION INCLUDING ALL LOADS. | | | NEC 220; FBC RE E3602.2. | | | | | | 5. PROVIDE PANEL LOAD CALCULATIONS FOR NEW PANEL K. | | | PROVIDE ACCURATE LOAD CALCULATION INCLUDING ALL LOADS. | | | NEC 220; FBC RE E3602.2. | | | | | | 6. PROVIDE REVISED LOAD CALCULATIONS FOR MAIN SERVICE | | | PANEL H BASED ON THE ADJUSTMENTS MADE, (SEE ABOVE). | | | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT | | | CORRECTED PAGES INTO SUBMITTAL AND LEAVE THE PREVIOUSLY | | | REVIEWED SHEETS DETACHED. | | | | | | | | | | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2019-02-26 |
|
|
Cont ID |
|
| Sent By |
jpearson |
Date |
2019-02-26 |
Time |
13:16 |
Rev Time |
0.00 |
| Received By |
fmittner |
Date |
2019-02-28 |
Time |
10:25 |
Sent To |
|
|
| Notes |
| 2019-04-01 09:51:13 | THIS REVIEW WAS PASSED BY MISTAKE BY FMITTNER (ZONING). | | | CT |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2018-11-05 |
|
|
Cont ID |
|
| Sent By |
jpearson |
Date |
2018-11-05 |
Time |
14:08 |
Rev Time |
0.00 |
| Received By |
jpearson |
Date |
2018-11-05 |
Time |
12:51 |
Sent To |
|
|
| Notes |
| 2018-11-05 14:08:30 | CODES IN EFFECT: | | | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION | | | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 | | | 6TH ED, CHAPTER 1. | | | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 | | | 6TH EDITION | | | FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017 | | | 6TH EDITION | | | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION | | | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE | | | FS = FLORIDA STATUTES | | | | | | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | | | 1. PROVIDE PANEL SCHEDULE INDICATING ANY NEW OR ALTERED | | | CIRCUITS, THE WIRE AND BREAKER SIZE FOR THESE CIRCUITS, | | | AND AFCI OR GFCI PROTECTION WHERE APPLICABLE TO COMPLY | | | WITH CODE. NEC 210.8, 210.12, 210.19, 210.20, 215.5, | | | 408.4; WPB FBC 107.3.5; FBC RE E3706.2, E3902 | | | 2. AFCI PROTECTION SHOWN IN NOT CODE COMPLIANT. ALL | | | BRANCH CIRCUITS THAT SUPPLY 120-VOLT, SINGLE-PHASE, 15- | | | AND 20-AMPERE OUTLETS INSTALLED IN KITCHENS, FAMILY | | | ROOMS, DINING ROOMS, LIVING ROOMS, PARLORS, LIBRARIES, | | | DENS, BEDROOMS, SUN-ROOMS, RECREATIONS ROOMS, CLOSETS, | | | HALLWAYS, LAUNDRY AREAS AND SIMILAR ROOMS OR AREAS | | | SHALL BE AFCI PROTECTED. THIS INCLUDES LIGHTING AND | | | POWER OUTLETS AND RECEPTACLES. SOME AREAS REQUIRE BOTH | | | AFCI AND GFCI PROTECTION. PROVIDE CORRECTION. NEC | | | 210.8, 210.12; FBC RE E3902; FBC EX 607.1.1 OR 801.1, | | | 801.2, OR 901.2 AS APPLICABLE. | | | 3. PROVIDE SMOKE/CO ALARMS IN EACH LOCATION REQUIRED | | | PER CODE. PROVIDE FULL FLOOR PLAN SHOWING ALL EXISTING | | | ALARMS. IF NONE ARE EXISTING OR NOT TO CODE, SHOW AS | | | NEW INSTALLATIONS. FBC RE R314.3, R315.1; WPB FBC | | | 107.2.1 | | | 4. PROVIDE RISER DIAGRAM, SHOWING ALL DETAILS OF | | | SERVICE EQUIPMENT, UNDERGROUND OR OVERHEAD SERVICE, | | | WIRE AND BREAKER SIZES FOR SERVICE AND FEED TO ANY | | | SUB-PANEL(S). SHOW GEC SIZE AND SYSTEM, SHOW | | | INTERSYSTEM BONDING TERMINATION POINT. NEC 215.5, 230, | | | 250.50, 250.94, 408.30; FBC RE E3706.1, E3608.1, | | | E3609.3; WPB FBC 107.2.1 | | | 5. IF ANY LOAD IS BEING ADDED, PROVIDE LOAD CALCULATION | | | FOR SERVICE, INCLUDE EXISTING AND NEW LOADS TO CONFIRM | | | CAPACITY OF SERVICE IS ADEQUATE. NEC 215.2, 220, | | | 408.30; FBC RE E3602.2 | | | 6. PROVIDE GFCI PROTECTION FOR DISHWASHER. NEC | | | 210.8(D); FBC RE E3902.10 | | | | | | END OF COMMENTS. | | | | | | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN | | | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES | | | INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY | | | REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED | | | SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD | | | SHEETS. | | | | | | SINCERELY, | | | | | | JOHN PEARSON | | | ELECTRICAL PLANS EXAMINER | | | 561-805-6746 | | | [email protected] | | | |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
4 |
Status |
P |
Date |
2019-04-16 |
|
|
Cont ID |
|
| Sent By |
thunt |
Date |
2019-04-16 |
Time |
07:54 |
Rev Time |
0.00 |
| Received By |
thunt |
Date |
2019-04-16 |
Time |
07:19 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
3 |
Status |
F |
Date |
2019-03-26 |
|
|
Cont ID |
|
| Sent By |
thunt |
Date |
2019-03-26 |
Time |
14:32 |
Rev Time |
0.00 |
| Received By |
thunt |
Date |
2019-03-26 |
Time |
14:32 |
Sent To |
|
|
| Notes |
| 2019-03-26 14:32:01 | GAS 3RD REVIEW**DENIED**? | | | | | | WITH RESPECT TO EVALUATION OF DESIGN PROFESSIONALS & | | | DOCUMENTS, IF A LOCAL GOVERNMENT FINDS IT NECESSARY, IN | | | ORDER TO ENFORCE COMPLIANCE WITH THE FLORIDA BUILDING | | | CODE AND ISSUE A PERMIT, TO REJECT DESIGN DOCUMENTS | | | REQUIRED BY THE CODE THREE OR MORE TIMES FOR FAILURE TO | | | CORRECT A CODE VIOLATION SPECIFICALLY AND CONTINUOUSLY | | | NOTED IN EACH REJECTION, INCLUDING, BUT NOT LIMITED TO, | | | EGRESS, FIRE PROTECTION, STRUCTURAL STABILITY, ENERGY, | | | ACCESSIBILITY, LIGHTING, VENTILATION, ELECTRICAL, | | | MECHANICAL, PLUMBING, AND GAS SYSTEMS, OR OTHER | | | REQUIREMENTS IDENTIFIED BY RULE OF THE FLORIDA BUILDING | | | COMMISSION ADOPTED PURSUANT TO CHAPTER 120, THE LOCAL | | | GOVERNMENT SHALL IMPOSE, EACH TIME AFTER THE THIRD SUCH | | | REVIEW THE PLANS ARE REJECTED FOR THAT CODE VIOLATION, | | | A FEE OF FOUR TIMES THE AMOUNT OF THE PROPORTION OF THE | | | PERMIT FEE ATTRIBUTED TO PLANS REVIEW. | | | | | | 1) SHT. P1.01 AND P1.02 ARE STILL NOT SIGNED | | | ELECTRONICALLY AS PER F.A.C RULE 61G1-16.005 | | | | | | 2) PROVIDE A GAS ISOMETRIC DRAWING. FBC 107.3.5.SUBMIT | | | AN ISOMETRIC DRAWING THAT CLEARLY SHOWS THE LENGTH OF | | | ALL CUT SECTIONS OF PIPE PER 2017 FBC-FUEL GAS, SECS. | | | 402.4.1, 402.4.2. OR 2017 FBC-RES SEC. G2413.4.1, | | | G2413.4.2. | | | | | | 3) PROVIDE SIZING CHART FOR GAS PIPING AFTER THE | | | PRESSURE REGULATOR FOR THE 1/2LB SYSTEM AND SHOW | | | DISTANCE.) SUBMIT TWO COPIES OF THE APPLICABLE SIZING | | | TABLES USED TO SIZE THE GAS SYSTEM OR PLACE A NOTE ON | | | THE PLANS/DRAWINGS SPECIFYING WHICH SIZING TABLE(S) | | | FROM THE GAS CODE OR OTHER STANDARD THAT WERE USED IN | | | THE DESIGN OF THIS GAS SYSTEM. REFER TO THE 2017 | | | FBC-FUEL GAS SECS. 401.4, 401.8, 402.3, AND TABLES | | | 402.4 (1) THRU 402.4 (37) OR 2017 FBC-RES. SEC. | | | G2413.3, G2412.8, G2413.1, G2413.2, & G2413.3 | | | | | | 4) SUBMIT MANUFACTURER?S SPECIFICATIONS FOR THE | | | PRESSURE REGULATORS. REGULATORS INSTALLED ON THE | | | EXTERIOR OF THE BUILDING SHALL BE APPROVED FOR OUTDOOR | | | INSTALLATION. 2014 FGC SEC.410.1, 2017 FBC-RES. SEC. | | | G2421.1. | | | | | | 5) PROVIDE GAS COOK TOP MANUFACTURE INSTALLATION MANUAL | | | SHOWING IT IS LISTED AND LABELED. FBC-R G2404.3 | | | | | | 6) GAS FLAT DRAWING SHOW'S GAS METER AS HAVING 3 OULET | | | PORTS. PER GAS PROVIDER THERE IS NOT SUCH METER ON THE | | | MARKET AND IT ONLY HAS 1 INLET AND 1 OUTLET. PROVIDE A | | | CORRECT FLAT DRAWING SHOWING CORRECT PIPING | | | ORIENTATIONS AND PIPE SIZE'S AND MATERIAL FROM THE | | | METER TO THE NEW GAS COOK TOP. 2017 FBC-FUEL GAS, SECS. | | | 402.4.1, 402.4.2. OR 2017 FBC-RES SEC. G2413.4.1, | | | G2413.4.2. | | | | | | | | | PLEASE FEEL FREE TO CONTRACT THIS PLAN REVIEW SO THAT I | | | CAN ASSIST YOU IN COMPLYING | | | | | | TIM HUNT | | | PLUMBING PLANS EXAMINER | | | BUILDING DIVISION | | | CITY OF WEST PALM BEACH | | | 401 CLEMATIS STREET, 1ST FLOOR | | | WEST PALM BEACH, FL 33401 | | | 561-248-2703 | | | [email protected] | | | | | | |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
2 |
Status |
F |
Date |
2019-02-21 |
|
|
Cont ID |
|
| Sent By |
jesmith |
Date |
2019-02-21 |
Time |
15:29 |
Rev Time |
0.00 |
| Received By |
jesmith |
Date |
2019-02-21 |
Time |
15:31 |
Sent To |
|
|
| Notes |
| 2019-02-21 15:29:32 | CODES IN EFFECT: | | | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION | | | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 | | | 6TH ED, CHAPTER 1. | | | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 | | | 6TH EDITION | | | FBC RES = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION | | | FBC ACC = FLORIDA ACCESSIBILITY CODE 2017 6TH EDITION | | | FBC EX = FLORIDA EXISTING BUILDING CODE 2017 6TH | | | EDITION | | | FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION | | | FBC FG = FLORIDA FUEL GAS CODE 2017 6TH EDITION | | | FAC= FLORIDA ADMINISTRATIVE CODE | | | FS = FLORIDA STATUTES | | | | | | | | | 2ND REVIEW:DENIED | | | DIGITAL SIGNATURE REQUIRED ON THE PLUMBING PLAN P1.01 | | | IS REQUIRED | | | ADDITIONAL COMMENTS | | | RE: P1.01 DETAIL 6-GAS RISER DIAGRAM | | | 1. YOU ARE REFERENCING TWO (2) DIFFERENT TABLES FBC FG | | | 402.4(1) INLET PRESSURE LESS THAN 2PSI AND | | | INTERNATIONAL FG TABLE 402.4(5) INLET PRESSURE 2 PSI. | | | PLEASE CLARIFY. ALSO NOTE THAT THE INTERNATIONAL FUEL | | | GAS CODE IS NOT RECOGNIZED BY WPB FBC AND THE | | | APPROPRIATE TABLE MUST BE NOTED AS FBC FUEL GAS CODE. | | | 2. DO EACH OF THE RUNOUTS CONNECT INDEPENDENTLY TO THE | | | GAS METER AS SHOWN OR IS THE NEW GAS RANGE SUPPLY | | | PIPING CONNECTED TO THE EXISTING PIPING? PLEASE | | | CLARIFY. | | | 3. A PREVIOUS PERMITTED PROJECT PLAN SHOWS THE GAS | | | METER, THE POOL HEATER AND THE NEW TANKLESS HEATER AND | | | NO OVEN. I CANNOT RECONCILE THE FOOT PRINT OF THE THE | | | NEW FLOOR PLAN WITH THE EXISTING. PER WPB FBC 107.2.1 | | | PROVIDE A FOOTPRINT (IE. SITE PLAN SHOWING LOCATION OF | | | NEW WORK AS WELL AS EXISTING GAS METER, POOL HEATER, | | | ETC.) THAT WILL ALLOW THE NEW WORK TO BE MATCHED TO THE | | | EXISTING PER WPB FBC 107.2.1. FYI REFERENCE WPB PERMIT | | | 17010488. | | | | | | | | | | | | SUBMITTAL OF ADDITIONAL AND/OR REVISED MATERIALS, | | | ESPECIALLY AS A RESULT OF RESPONSE TO BUILDING REVIEW | | | COMMENTS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN | | | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES | | | INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY | | | REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED | | | SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED "VOID". | | | | | | JERALD SMITH | | | PLUMBING PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | EMAIL [email protected] | | | PHONE 561-805-6715 |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
1 |
Status |
F |
Date |
2018-12-06 |
|
|
Cont ID |
|
| Sent By |
jesmith |
Date |
2018-12-06 |
Time |
14:40 |
Rev Time |
0.00 |
| Received By |
jesmith |
Date |
2018-12-06 |
Time |
13:41 |
Sent To |
|
|
| Notes |
| 2018-12-06 14:40:24 | CODES IN EFFECT: | | | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION | | | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 | | | 6TH ED, CHAPTER 1. | | | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 | | | 6TH EDITION | | | FBC RES = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION | | | FBC ACC = FLORIDA ACCESSIBILITY CODE 2017 6TH EDITION | | | FBC EX = FLORIDA EXISTING BUILDING CODE 2017 6TH | | | EDITION | | | FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION | | | FAC= FLORIDA ADMINISTRATIVE CODE | | | FS = FLORIDA STATUTES | | | | | | 1ST REVIEW: DENIED | | | GAS COMMENTS | | | 1. SUBMIT THE FOLLOWING PER WPB FBC 107.2.1 | | | A) SUBMIT AN ISOMETRIC DRAWING THAT CLEARLY SHOWS THE | | | LENGTH OF ALL CUT SECTIONS OF PIPE PER FBC RES | | | G2413.4.1 AND G2413.4.2. | | | B) LIST THE BTU LOAD OF EACH APPLIANCE AND THE TOTAL | | | BTU LOAD ON THE SYSTEM FBC RES G2413.3, G2413.4 AND | | | TABLES G2413.4 (1) THROUGH G2413.4 (21). | | | C) SHOW THE DISTANCE FROM THE POINT OF DELIVERY TO THE | | | MOST REMOTE OUTLET IN THE BUILDING AND / OR SYSTEM PER | | | FBC RES G2413.4.1, G2413.4.2. | | | D) SUBMIT MANUFACTURER?S SPECIFICATION SHEETS / | | | INSTALLATION MANUAL FOR ALL GAS EQUIPMENT TO VERIFY | | | COMPLIANCE WITH STANDARDS NFPA 54, NFPA 58 AND FBC RES | | | G2404.3. GAS APPLIANCES SHALL BE LISTED AND LABELED. | | | THE INSTALLATION MANUALS FOR ALL GAS APPLIANCES / | | | EQUIPMENT SHALL BE ONSITE AT THE TIME OF INSPECTION PER | | | FBC RES G2408.1. | | | E) SUBMIT MANUFACTURER?S SPECIFICATIONS FOR THE | | | PRESSURE REGULATORS AT THE RANGE. FBC RES G2421.1. | | | F) SUBMIT COMBUSTION AIR CALCULATIONS FOR THE GAS | | | APPLIANCE. WHERE COMBUSTION AIR IS PROVIDED BY THE | | | BUILDING?S MECHANICAL VENTILATION SYSTEM, THE SYSTEM | | | SHALL PROVIDE THE SPECIFIED COMBUSTION AIR RATE IN | | | ADDITION TO THE REQUIRED VENTILATION AIR. 2017 FBC-FUEL | | | GAS SEC.304.9.3 OR FBCR G2407.9.3. | | | | | | JERALD SMITH | | | PLUMBING PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | EMAIL [email protected] | | | PHONE 561-805-6715 | | | |
|
|
| Review Stop |
HIST |
HISTORICAL |
| Rev No |
1 |
Status |
P |
Date |
2018-10-23 |
|
|
Cont ID |
|
| Sent By |
fmittner |
Date |
2018-10-23 |
Time |
12:30 |
Rev Time |
0.00 |
| Received By |
fmittner |
Date |
2018-10-23 |
Time |
12:30 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
4 |
Status |
N |
Date |
2019-04-24 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2019-04-24 |
Time |
11:45 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2019-04-08 |
Time |
09:28 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2019-04-01 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2019-04-01 |
Time |
13:25 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2019-03-15 |
Time |
15:35 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2019-03-04 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2019-02-28 |
Time |
06:33 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2019-02-13 |
Time |
16:04 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2018-12-06 |
|
|
Cont ID |
|
| Sent By |
lmarchan |
Date |
2018-12-06 |
Time |
15:23 |
Rev Time |
0.00 |
| Received By |
lmarchan |
Date |
2018-10-18 |
Time |
16:39 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
P |
Date |
2018-11-06 |
|
|
Cont ID |
|
| Sent By |
cmontell |
Date |
2018-11-06 |
Time |
10:12 |
Rev Time |
0.00 |
| Received By |
cmontell |
Date |
2018-11-06 |
Time |
10:01 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
4 |
Status |
P |
Date |
2019-04-16 |
|
|
Cont ID |
|
| Sent By |
thunt |
Date |
2019-04-16 |
Time |
07:43 |
Rev Time |
0.00 |
| Received By |
thunt |
Date |
2019-04-16 |
Time |
07:19 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
3 |
Status |
F |
Date |
2019-03-26 |
|
|
Cont ID |
|
| Sent By |
thunt |
Date |
2019-03-26 |
Time |
14:39 |
Rev Time |
0.00 |
| Received By |
thunt |
Date |
2019-03-26 |
Time |
13:32 |
Sent To |
|
|
| Notes |
| 2019-03-26 14:39:44 | PLUMBING 3RD REVIEW**DENIED** | | | | | | WITH RESPECT TO EVALUATION OF DESIGN PROFESSIONALS & | | | DOCUMENTS, IF A LOCAL GOVERNMENT FINDS IT NECESSARY, IN | | | ORDER TO ENFORCE COMPLIANCE WITH THE FLORIDA BUILDING | | | CODE AND ISSUE A PERMIT, TO REJECT DESIGN DOCUMENTS | | | REQUIRED BY THE CODE THREE OR MORE TIMES FOR FAILURE TO | | | CORRECT A CODE VIOLATION SPECIFICALLY AND CONTINUOUSLY | | | NOTED IN EACH REJECTION, INCLUDING, BUT NOT LIMITED TO, | | | EGRESS, FIRE PROTECTION, STRUCTURAL STABILITY, ENERGY, | | | ACCESSIBILITY, LIGHTING, VENTILATION, ELECTRICAL, | | | MECHANICAL, PLUMBING, AND GAS SYSTEMS, OR OTHER | | | REQUIREMENTS IDENTIFIED BY RULE OF THE FLORIDA BUILDING | | | COMMISSION ADOPTED PURSUANT TO CHAPTER 120, THE LOCAL | | | GOVERNMENT SHALL IMPOSE, EACH TIME AFTER THE THIRD SUCH | | | REVIEW THE PLANS ARE REJECTED FOR THAT CODE VIOLATION, | | | A FEE OF FOUR TIMES THE AMOUNT OF THE PROPORTION OF THE | | | PERMIT FEE ATTRIBUTED TO PLANS REVIEW. | | | | | | | | | 1) PLUMBING SHEETS P1.01 AND P1.02 ARE STILL NOT SIGNED | | | DIIGITALLY SIGNED AS STATED IN F.A.C RULE 61G1-16.005 | | | | | | 2) POWER BATHROOM FITTING APPEAR TO BE BACKWARDS. | | | FITTING MUST BE INSTALLED IN DIRECTION OF FLOW. FBC | | | 706.3 | | | | | | 3) THE POWER BATH TOILET IS NOT PERMITTED TO BE WET | | | VENTED INTO THE BUILDING DRAIN. ONLY OTHER BATHROOM | | | FIXTURES UP TO 2 AND ON THE SAME SAME FLOOR ARE | | | PERMITTED TO DRAIN INTO THE BATHROOM WET VENT | | | | | | | | | TIM HUNT | | | PLUMBING PLANS EXAMINER | | | BUILDING DIVISION | | | CITY OF WEST PALM BEACH | | | 401 CLEMATIS STREET, 1ST FLOOR | | | WEST PALM BEACH, FL 33401 | | | 561-248-2703 | | | [email protected] | | | | | | |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
F |
Date |
2019-02-21 |
|
|
Cont ID |
|
| Sent By |
jesmith |
Date |
2019-02-21 |
Time |
14:17 |
Rev Time |
0.00 |
| Received By |
jesmith |
Date |
2019-02-21 |
Time |
14:06 |
Sent To |
|
|
| Notes |
| 2019-02-21 14:17:04 | CODES IN EFFECT: | | | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION | | | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 | | | 6TH ED, CHAPTER 1. | | | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 | | | 6TH EDITION | | | FBC RES = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION | | | FBC ACC = FLORIDA ACCESSIBILITY CODE 2017 6TH EDITION | | | FBC EX = FLORIDA EXISTING BUILDING CODE 2017 6TH | | | EDITION | | | FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION | | | FBC FG = FLORIDA FUEL GAS CODE 2017 6TH EDITION | | | FAC= FLORIDA ADMINISTRATIVE CODE | | | FS = FLORIDA STATUTES | | | | | | | | | 2ND REVIEW:DENIED | | | DIGITAL SIGNATURE REQUIRED ON THE PLUMBING PLAN P1.01 | | | IS REQUIRED | | | 1. PLUMBING DRAWINGS ARE CODE COMPLIANT AND UPON | | | RECEIPT OF DIGITALLY SIGNED PLAN WILL BE APPROVED. | | | 2. ALL WORK PER CITY CODES SUBJECT TO FIELD INSPECTOR'S | | | APPROVAL | | | | | | | | | SUBMITTAL OF ADDITIONAL AND/OR REVISED MATERIALS, | | | ESPECIALLY AS A RESULT OF RESPONSE TO BUILDING REVIEW | | | COMMENTS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN | | | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES | | | INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY | | | REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED | | | SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED "VOID". | | | | | | JERALD SMITH | | | PLUMBING PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | EMAIL [email protected] | | | PHONE 561-805-6715 |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2018-12-06 |
|
|
Cont ID |
|
| Sent By |
jesmith |
Date |
2018-12-06 |
Time |
14:42 |
Rev Time |
0.00 |
| Received By |
jesmith |
Date |
2018-12-06 |
Time |
13:40 |
Sent To |
|
|
| Notes |
| 2018-12-06 13:41:10 | CODES IN EFFECT: | | | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION | | | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 | | | 6TH ED, CHAPTER 1. | | | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 | | | 6TH EDITION | | | FBC RES = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION | | | FBC ACC = FLORIDA ACCESSIBILITY CODE 2017 6TH EDITION | | | FBC EX = FLORIDA EXISTING BUILDING CODE 2017 6TH | | | EDITION | | | FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION | | | FAC= FLORIDA ADMINISTRATIVE CODE | | | FS = FLORIDA STATUTES | | | | | | 1ST REVIEW: DENIED | | | 1. THE DISHWASHER DISCHARGE PIPE OR TUBING SHALL RISE | | | TO THE UNDERSIDE OF THE COUNTER AND BE FASTENED OR | | | OTHERWISE HELD IN THAT POSITION BEFORE CONNECTING TO | | | THE HEAD OF THE FOOD-WASTE DISPOSER OR TO A WYE FITTING | | | IN THE SINK TAILPIECE NOT DOWNSTREAM OF THE TRAP PER | | | FBC RES P2717.2. | | | 2. ICE MAKER AND REFRIGERATOR/FREEZER DISCHARGES SHALL | | | NOT BE CONNECTED DIRECTLY TO THE SANITARY. PROVIDE | | | INDIRECT WASTE THROUGH AN AIR GAP TO A TRAPPED AND | | | VENTED WASTE RECEPTOR SUCH AS A HUB DRAIN OR FLOOR SINK | | | IN ACCORDANCE WITH FBC RES P2706 AND FBC PL 802.2. | | | | | | JERALD SMITH | | | PLUMBING PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | EMAIL [email protected] | | | PHONE 561-805-6715 | | | |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
4 |
Status |
P |
Date |
2019-04-16 |
|
|
Cont ID |
|
| Sent By |
thunt |
Date |
2019-04-16 |
Time |
07:55 |
Rev Time |
0.00 |
| Received By |
thunt |
Date |
2019-04-16 |
Time |
07:55 |
Sent To |
|
|
| Notes |
| 2019-04-16 07:56:02 | ALL SHEETS OK | | | |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
3 |
Status |
F |
Date |
2019-04-01 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2019-04-01 |
Time |
13:26 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2019-04-01 |
Time |
09:50 |
Sent To |
|
|
| Notes |
| 2019-04-01 13:29:04 | BUILDING PLAN REVIEW - DIGITAL SIGNATURE | | | 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST | | | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, | | | CHAPTER 1 ADMINISTRATION | | | | | | CHRISTOPHER S. THROOP, C.B.O. | | | BUILDING PLANS EXAMINER, PX3169 | | | 1&2 FAMILY PLANS EXAMINER, SFP306 | | | CONSTRUCTION SERVICES DIVISION | | | TEL: 561-805-6726 | | | FAX: 561-805-6676 | | | E-MAIL: [email protected] | | | | | | 1ST REVIEW | | | RESULTS: DENIED | | | YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED | | | BELOW. | | | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT | | | | | | CANNOT VERIFY DIGITAL SIGNATURE AND SEAL ON PLAN PAGES | | | E3.01, E6.01 AND E7.01. | | | | | | 1. DIGITAL SIGNATURES/SEALS ARE NOT IN ACCORDANCE WITH | | | FS 471, FS 481 AS NOTED. NEW SHEETS SUBMITTED IN THE | | | NEXT REVIEW CYCLE REQUIRE REVIEW. | | | | | | 2. UPLOAD VIA THE PROJECTDOX PORTAL WITH DIGITAL | | | SIGNATURES OF DESIGN PROFESSIONALS AS APPLICABLE; USE | | | THE REQUIRED NAMING CONVENTION FOR EACH DOCUMENT. | | | | | | ALSO SEE COMMENTS UNDER PLUMBING REVIEW FOR PLAN PAGES | | | P1.01 AND P1.02. | | | | | | |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
2 |
Status |
F |
Date |
2019-02-20 |
|
|
Cont ID |
|
| Sent By |
dbattles |
Date |
2019-02-20 |
Time |
15:05 |
Rev Time |
0.00 |
| Received By |
dbattles |
Date |
2019-02-20 |
Time |
14:50 |
Sent To |
|
|
| Notes |
| 2019-02-20 15:06:15 | 2ND REVIEW SHEETS NOT DIGITALLY SIGNED | | | E3.01 | | | E6.01 | | | E-7.01 | | | P1.01 | | | | | | IF THIRD REVIEW IS NEEDED, ANY NEW SHEETS WILL NEED TO | | | BE DIGITALLY SIGNED. |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
1 |
Status |
F |
Date |
2019-02-26 |
|
|
Cont ID |
|
| Sent By |
jpearson |
Date |
2018-11-05 |
Time |
13:57 |
Rev Time |
0.00 |
| Received By |
jpearson |
Date |
2018-11-05 |
Time |
13:57 |
Sent To |
|
|
| Notes |
| 2019-02-26 13:13:34 | CHANGED STATUS TO REFLECT NEW SUBMISSION. |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
P |
Date |
2019-02-28 |
|
|
Cont ID |
|
| Sent By |
fmittner |
Date |
2019-02-28 |
Time |
10:26 |
Rev Time |
0.00 |
| Received By |
fmittner |
Date |
2019-02-28 |
Time |
10:26 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
P |
Date |
2018-10-23 |
|
|
Cont ID |
|
| Sent By |
fmittner |
Date |
2018-10-23 |
Time |
12:30 |
Rev Time |
0.00 |
| Received By |
fmittner |
Date |
2018-10-23 |
Time |
12:30 |
Sent To |
|
|
| Notes |
|
|
|