Plan Review Details - Permit 18100677
Plan Review Stops For Permit 18100677
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2019-02-22 Cont ID  
Sent By jduprey Date 2019-02-22 Time 14:41 Rev Time 0.00
Received By jduprey Date 2019-02-22 Time 14:28 Sent To  
Notes
2019-02-22 14:41:16PROVISO
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 PROVIDE THE WIND DESIGN CRITERIA AND INFORMATION ALONG
 WITH DOOR PRODUCT APPROVAL AS A REVISION PRIOR TO
 INSTALLATION.
  
 107.3.4.1 DEFERRED SUBMITTALS. FOR THE PURPOSES OF THIS
 SECTION, DEFERRED SUBMITTALS ARE DEFINED AS THOSE
 PORTIONS OF THE DESIGN THAT ARE NOT SUBMITTED AT THE
 TIME OF THE APPLICATION AND THAT ARE TO BE SUBMITTED TO
 THE BUILDING OFFICIAL WITHIN A SPECIFIED PERIOD.
 DEFERRAL OF ANY SUBMITTAL ITEMS SHALL HAVE THE PRIOR
 APPROVAL OF THE BUILDING OFFICIAL. THE REGISTERED
 DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE SHALL LIST
 THE DEFERRED SUBMITTALS ON THE CONSTRUCTION DOCUMENTS
 FOR REVIEW BY THE BUILDING OFFICIAL. DOCUMENTS FOR
 DEFERRED SUBMITTAL ITEMS SHALL BE SUBMITTED TO THE
 REGISTERED DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE
 WHO SHALL REVIEW THEM AND FORWARD THEM TO THE BUILDING
 OFFICIAL WITH A NOTATION INDICATING THAT THE DEFERRED
 SUBMITTAL DOCUMENTS HAVE BEEN REVIEWED AND FOUND TO BE
 IN GENERAL CONFORMANCE TO THE DESIGN OF THE BUILDING.
 THE DEFERRED SUBMITTAL ITEMS SHALL NOT BE INSTALLED
 UNTIL THE DEFERRED SUBMITTAL DOCUMENTS HAVE BEEN
 APPROVED BY THE BUILDING OFFICIAL.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2019-02-16 Cont ID  
Sent By shill Date 2019-02-16 Time 11:40 Rev Time 0.00
Received By shill Date 2019-02-16 Time 11:40 Sent To  
Notes
2019-02-16 11:42:23****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 1. SEE PREVIOUS LIST. THIS APPEARS TO BE LOCATED IN
 EXPOSURE D, REVISE OR HAVE ENGINEER SEND AN EMAIL TO
 EXPLAIN RATIONALE FOR EXPOSURE C, FBC B 1609.
  
 2. THE PRODUCT APPROVAL IS TO BE REVIEWED BY DESIGNER
 OF RECORD, FBC 107. IT IS EXPIRED (2014 RATHER THAN
 2017 CODE), FBC B 1609.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2018-11-21 Cont ID  
Sent By jwitmer Date 2018-11-21 Time 09:10 Rev Time 0.00
Received By jwitmer Date 2018-11-21 Time 06:51 Sent To  
Notes
2018-11-21 09:10:232017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 18100677
 ADD: 3901 S FLAGLER DR. SUITE: 401
 CONT: PM WRIGHT CONSTRUCTION (CBC058843)
 TEL: 561-863-5088
 E-MAIL: [email protected]
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: WED. NOV. 21/2018
 ACTION: DENIED
  
 1) THE PERMIT APPLICATION AND FLOOR PLAN A-1 BOTH
 INDICATE THE REMOVAL AND INSTALLATION OF A NEW EXTERIOR
 DOOR AND FRAME. THE PLANS ARE SILENT AS TO THE BUILDING
 HEIGHT, NOR DOES THE PLANS SHOW THIS UNIT IN REGARDS TO
 THE OVERALL FLOOR PLAN FOR THE BUILDING. THIS BUILDING
 IS A 10 STORY HIGH-RISE AND THE BUILDING (TENANT UNIT)
 MAYBE LOCATED IN EXPOSURE D. WE NEED THE FLOORPLAN OF
 THE BUILDING IDENTIFYING THE UNIT TO SEE IF THE
 LOCATION WILL BE EXPOSURE D AND TO SEE IF THE DOOR IS
 LOCATED IN A WALL ZONE 5.
  
 SINCE THIS IS A 10 STORY HIGH-RISE THE WIND LOADS ON
 EVERY BUILDING SHALL BE DETERMINED IN ACCORDANCE WITH
 CHAPTER 30 OF ASCE7-10. THE PRESSURES WILL NEED TO BE
 CALCULATED BY A STRUCTURAL ENGINEER, NOT THE
 CONTRACTOR.
  
 PLEASE SHOW COMPLIANCE WITH: 2017 FBC-B 1603.1.4 WIND
 DESIGN DATA.
 THE FOLLOWING INFORMATION RELATED TO WIND LOADS SHALL
 BE SHOWN, REGARDLESS OF WHETHER WIND LOADS GOVERN THE
 DESIGN OF THE LATERAL FORCE-RESISTING SYSTEM OF THE
 STRUCTURE:
  
 1.1. ULTIMATE DESIGN WIND SPEED, VULT, (3-SECOND GUST),
 MILES PER HOUR AND NOMINAL DESIGN WIND SPEED, VASD, AS
 DETERMINED IN ACCORDANCE WITH SECTION 1609.3.1.
  
 1.2. RISK CATEGORY.
  
 1.3. WIND EXPOSURE. APPLICABLE WIND DIRECTION IF MORE
 THAN ONE WIND EXPOSURE IS UTILIZED. TABLE 1609.7.2.
 HEIGHT AND EXPOSURE.
  
 1.4. APPLICABLE INTERNAL PRESSURE COEFFICIENT.
  
 1.5. DESIGN WIND PRESSURES TO BE USED FOR EXTERIOR
 COMPONENTS AND CLADDING MATERIALS NOT SPECIFICALLY
 DESIGNED BY THE REGISTERED DESIGN PROFESSIONAL
 RESPONSIBLE FOR THE DESIGN OF THE STRUCTURE, PSF.
  
 TABLE 1609.7(2) ADJUSTMENT FACTORS FOR HEIGHT &
 EXPOSURE. PROVIDE THE MEAN ROOF HEIGHT FOR THE
 BUILDING.
  
 1609.3.1 WIND SPEED CONVERSION VULT TO VASD.
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 A THOROUGH REVIEW OF THE PLANS COULD NOT HAPPEN SINCE
 THERE WAS A GREAT DEFICIENCY IN PLANS AND REQUIRED
 DOCUMENTATION. WITH THE NEXT PLAN REVIEW CYCLE THERE
 MAYBE ADDITIONAL REVIEW COMMENTS BECAUSE OF NEW PLANS
 AND INFORMATION LACKING UNDER THE PRIOR REVIEW.
  
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 DEVELOPMENT SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2019-02-07 Cont ID  
Sent By jpearson Date 2019-02-07 Time 13:52 Rev Time 0.00
Received By jpearson Date 2019-02-07 Time 13:52 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2018-10-30 Cont ID  
Sent By jpearson Date 2018-10-30 Time 15:08 Rev Time 0.00
Received By jpearson Date 2018-10-30 Time 15:07 Sent To  
Notes
2018-10-30 15:07:57CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. PER THE WPB AMENDMENTS TO THE FBC, ELECTRICAL PLAN
 (EACH SHEET OF BOTH COPIES) IS REQUIRED TO BEAR THE
 NAME AND BE SIGNED AND SEALED BY THE PERSON RESPONSIBLE
 FOR THE DESIGN. THIS PERSON MUST BE A LICENSED DESIGN
 PROFESSIONAL OR THE ELECTRICAL CONTRACTOR QUALIFIER.
 PROVIDE CORRECTION. WPB FBC 107.1, 107.2; FS 471, 481
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD
 SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2019-01-28 Cont ID  
Sent By scaldero Date 2019-01-28 Time 11:22 Rev Time 0.00
Received By scaldero Date 2019-01-28 Time 11:21 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2018-10-17 Cont ID  
Sent By scaldero Date 2018-10-17 Time 10:02 Rev Time 0.00
Received By scaldero Date 2018-10-17 Time 09:57 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2019-02-16 Cont ID  
Sent By shill Date 2019-02-16 Time 11:42 Rev Time 0.00
Received By shill Date 2019-01-22 Time 13:29 Sent To  
Notes
2019-01-23 13:29:53B05

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-12-06 Cont ID  
Sent By jesmith Date 2018-12-06 Time 10:59 Rev Time 0.00
Received By jesmith Date 2018-12-06 Time 10:59 Sent To  
Notes
2018-10-16 14:46:17B02

Review Stop P PLUMBING
Rev No 2 Status P Date 2019-01-29 Cont ID  
Sent By jesmith Date 2019-01-29 Time 15:53 Rev Time 0.00
Received By jesmith Date 2019-01-29 Time 15:53 Sent To  
Notes
2019-01-29 15:53:17APPROVED
 ALL WORK PER CITY CODES SUBJECT TO FIELD INSPECTOR'S
 APPROVAL
  

Review Stop P PLUMBING
Rev No 1 Status P Date 2018-12-06 Cont ID  
Sent By jesmith Date 2018-12-06 Time 10:24 Rev Time 0.00
Received By jesmith Date 2018-12-06 Time 10:23 Sent To  
Notes
2018-12-06 10:24:03APPROVED
 PROVISO:
 1. ALL WORK PER CITY CODES SUBJECT TO FIELD INSPECTOR'S
 APPROVAL
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 PHONE 561-805-6715
  