Plan Review Details - Permit 18100648
Plan Review Stops For Permit 18100648
Review Stop AD ADDRESSING
Rev No 1 Status P Date 2019-10-21 Cont ID  
Sent By jgomez Date 2019-10-21 Time 18:34 Rev Time 0.00
Received By jgomez Date 2019-10-21 Time 18:34 Sent To  
Notes
2019-10-21 18:35:37HELLO EVERYONE,
  
 IN THE ON GOING EFFORT TO BRING ADDRESSES TO A COMMON
 STANDARD I AM UPDATING THE ADDRESS SEQUENCE AND UNIT
 IDENTIFIERS FOR THE PROPERTY WITH THE PCN:
 74434321060240130.
  
 THERE ARE TWO STRUCTURES ON THIS PROPERTY AND THE
 ADDRESS SEQUENCE IS CHANGING THE LOWER NUMBER OF 803
 FROM THE REAR TO THE FRONT WHICH WILL NOW BE THE
 PRIMARY ADDRESS.
  
 FRONT: NEW ADDRESS OF 803 3RD ST CHANGED FROM THE OLD
 ADDRESS OF 805 3RD ST
 REAR: NEW ADDRESS OF 805 3RD ST UNIT 1 CHANGED FROM THE
 OLD ADDRESS OF 803 3RD ST UNIT 1. FIRST FLOOR
 NEW ADDRESS OF 805 3RD ST UNIT 2 CHANGED FROM THE OLD
 ADDRESS OF 803 ? 3RD ST UNIT 2. SECOND FLOOR
  
 I HAVE UPDATED THE WPB AND THE PBC EPZB ADDRESS
 DATABASES.
  
 REGARDS
  
 MICHAEL ORIO
 GIS SUPPORT SPECIALIST
  
 CITY OF WEST PALM BEACH
 INFORMATION TECHNOLOGY DEPARTMENT
 401 CLEMATIS STREET ? WEST PALM BEACH ? FLORIDA 33401
 P: 561.494.1080 | WWW.WPB.ORG

Review Stop B BUILDING (STRUCTURAL)
Rev No 7 Status P Date 2020-02-10 Cont ID  
Sent By pvalenti Date 2020-02-10 Time 08:44 Rev Time 0.00
Received By pvalenti Date 2020-02-10 Time 06:32 Sent To  
Notes
2020-02-10 08:56:13PETER E VALENTI
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6673
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
 FBC M = FBC MECHANICAL
  
 BUILDING REVIEW APPROVED WITH PROVISO:
  
 SEE THE SUBMITTED AND APPROVED SUBMITTALS FOR DETAILS
 ON SIMPSON STRONG TIE ROOF CONNECTORS.

Review Stop B BUILDING (STRUCTURAL)
Rev No 6 Status F Date 2019-10-28 Cont ID  
Sent By jgomez Date 2019-10-28 Time 18:13 Rev Time 0.00
Received By jgomez Date 2019-10-28 Time 15:05 Sent To  
Notes
2019-10-28 18:14:27 
 *****NOTE:
 01/15/2020 MEETING W/ SAMANTHA HILL, JORGE GONZALEZ
 (ENG'R) AND DANIEL ACEVEDO (CONTR) TO GO OVER COMMENTS.
 JG.
  
  
  
 RESIDENTIAL (R3) SIXTH BUILDING REVIEW COMMENTS
 CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS.
  
 1- SHEET S-01:
 PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR ONE
 HOUR FIRE RATED FLOOR ASSEMBLY SEPARATING DUPLEX A AND
 B.
 SEC. 801.3 FBC-EXISTING BUILDING AND SEC. R302.3
 FBC-RESIDENTIALL.
  
 RESPONSE:
 REPEAT COMMENT (SIX TIMES). REVISED DRAWING SUBMITTED
 THIS TIME ON SHEET S-01 DOESN'T PROVIDE ANY DETAIL OR
 SPECIFICATIONS FOR AN APPROVED ONE HOUR FIRE RATED
 FLOOR /CEILING ASSEMBLY COMPLYING WITH THE REQUIREMENTS
 OF SEC. R302.3 FBC-RESIDENTIAL. THE PREVIOUS PLANS
 SPECIFIED APPROVED ASSEMBLY NO L501 BUT IT WAS NOT
 COORDINATED WITH THE BUILDING SECTION ON SAME SHEET.
 THE COMMENT WAS FOR ENGINEER TO COORDINATE THE
 INFORMATION. NOW ENGINEER PROVIDES A NEW DRAWING THAT
 DOESN'T PROVIDE ANY ONE HOUR APPROVED FIRE RATED
 ASSEMBLY. NEED TO PROVIDE DETAIL/SPECIFICATIONS FOR AN
 APPROVED 1 HOUR FLOOR/CEILING ASSEMBLY THAT IS TESTED
 IN ACCORDANCE WITH ASTM E119 OR UL 263 AS REQUIRED BY
 SEC. R302.3 FRBC-RESIDENTIAL.
  
 THIS PLAN REVIEW HAVE BEEN DENIED SIX TIMES FOR THIS
 SAME ITEM. ENGINEER OF RECORD TO PAY FOUR TIMES THE
 PLAN REVIEW FEE ($1630.72) AS REQUIRED BY FLORIDA
 STATUTE 553.80(2)(B).
  
 ARCHITECTS-ENGINEERS
 FLORIDA STATUTE 553.80(2)(B):
 WITH RESPECT TO EVALUATION OF DESIGN PROFESSIONALS
 DOCUMENTS, IF A LOCAL GOVERNMENT FINDS IT NECESSARY, IN
 ORDER TO ENFORCE COMPLIANCE WITH THE FLORIDA BUILDING
 CODE AND ISSUE A PERMIT, TO REJECT DESIGN DOCUMENTS
 REQUIRED BY THE CODE THREE OR MORE TIMES FOR FAILURE TO
 CORRECT A CODE VIOLATION SPECIFICALLY AND CONTINUOUSLY
 NOTED IN EACH REJECTION, INCLUDING, BUT NOT LIMITED TO,
 EGRESS, FIRE PROTECTION, STRUCTURAL STABILITY, ENERGY,
 ACCESSIBILITY, LIGHTING, VENTILATION, ELECTRICAL,
 MECHANICAL, PLUMBING, AND GAS SYSTEMS, OR OTHER
 REQUIREMENTS IDENTIFIED BY RULE OF THE FLORIDA BUILDING
 COMMISSION ADOPTED PURSUANT TO CHAPTER 120, THE LOCAL
 GOVERNMENT SHALL IMPOSE, EACH TIME AFTER THE THIRD SUCH
 REVIEW THE PLANS ARE REJECTED FOR THAT CODE VIOLATION,
 A FEE OF FOUR TIMES THE AMOUNT OF THE PROPORTION OF THE
 PERMIT FEE ATTRIBUTED TO PLANS REVIEW
  
  
 2- WINDOW REPLACEMENT:
 A) CLEARLY SPECIFY TYPE AND SIZE OF EXISTING WINDOWS
 AND TYPE AND SIZE OF PROPOSED WINDOWS TO VERIFY
 COMPLIANCE WITH THE EGRESS REQUIREMENTS OF SEC. 702.5
 FBC-EXISTING BUILDING.
  
 RESPONSE:
 REPEAT COMMENT (SIX TIMES). EGRESS NOTE ON SHEET A-01
 DOESN'T ADDRESS THE COMMENT. THIS NOTE DOESN'T ANSWER
 WHAT IT WAS REQUESTED. PLEASE READ THE COMMENT AGAIN
 AND PROVIDE THE REQUIRED INFORMATION. ALSO, IT LOOKS
 LIKE THE CODE SECTION IS TAKING FROM ANOTHER CODE OTHER
 THAN THE 2017 FBC-RESIDENTIAL. IN ADDITION, THE WINDOW
 SIZES SHOWN ON THE PROPOSED WINDOW SCHEDULE DON'T
 COMPLY.
  
 ARCHITECTS-ENGINEERS
 FLORIDA STATUTE 553.80(2)(B):
 WITH RESPECT TO EVALUATION OF DESIGN PROFESSIONALS
 DOCUMENTS, IF A LOCAL GOVERNMENT FINDS IT NECESSARY, IN
 ORDER TO ENFORCE COMPLIANCE WITH THE FLORIDA BUILDING
 CODE AND ISSUE A PERMIT, TO REJECT DESIGN DOCUMENTS
 REQUIRED BY THE CODE THREE OR MORE TIMES FOR FAILURE TO
 CORRECT A CODE VIOLATION SPECIFICALLY AND CONTINUOUSLY
 NOTED IN EACH REJECTION, INCLUDING, BUT NOT LIMITED TO,
 EGRESS, FIRE PROTECTION, STRUCTURAL STABILITY, ENERGY,
 ACCESSIBILITY, LIGHTING, VENTILATION, ELECTRICAL,
 MECHANICAL, PLUMBING, AND GAS SYSTEMS, OR OTHER
 REQUIREMENTS IDENTIFIED BY RULE OF THE FLORIDA BUILDING
 COMMISSION ADOPTED PURSUANT TO CHAPTER 120, THE LOCAL
 GOVERNMENT SHALL IMPOSE, EACH TIME AFTER THE THIRD SUCH
 REVIEW THE PLANS ARE REJECTED FOR THAT CODE VIOLATION,
 A FEE OF FOUR TIMES THE AMOUNT OF THE PROPORTION OF THE
 PERMIT FEE ATTRIBUTED TO PLANS REVIEW
  
  
  
 3- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 FAC 61G20-3.001 FOR:
 A) EXTERIOR DOORS AS SHOWN ON PLANS. NOTE: PROVIDE
 FLORIDA PRODUCT APPROVAL COVER PAGE THAT CORRESPOND TO
 DRAWINGS MA-FL0211-17 SUBMITTED.
  
 RESPONSE:
 REPEAT COMMENT (SIX TIMES). FLORIDA PRODUCT APPROVAL
 COVER PAGE WAS NOT PROVIDED. NEED TO PROVIDE COMPLETE
 FLORIDA PRODUCT APPROVAL, INCLUDING THE FLORIDA PRODUCT
 APPROVAL COVER PAGE THAT CORRESPONDS TO THE DRAWINGS
 SUBMITTED. THE FLORIDA PRODUCT APPROVAL IS REQUIRED
 BECAUSE IT SHOWS IF PRODUCT IS APPROVED AND CURRENT
 CODE IN EFFECT.
 NOTE: IF THERE IS NOT CURRENT FLORIDA PRODUCT APPROVAL,
 THEN MANUFACTURER MAY APPLY FOR LOCAL PRODUCT APPROVAL.
 2 COPIES OF COMPLETE ENGINEERED PACKAGE WITH ORIGINAL
 SEAL/SIGNATURE ALONG WITH APPLICATION FOR PRODUCT
 APPROVAL WILL BE REQUIRED FOR BUILDING OFFICIAL
 REVIEW/APPROVAL PROCESS.
  
 4- RAFTER CONNECTION DETAIL ON SHEET S-01. ENGINEER TO
 PROVIDE ENGINEERING CALCULATIONS SHOWING THAT THE
 SPECIFIED CONNECTION IS ADEQUATE FOR THE SUPPORT OF
 SECOND FLOOR JOISTS. ENGINEER TO SHOW THAT 1/4" X
 3-1/4" TAPCONS SPACED AT 24" O.C ARE ADEQUATE TO CARRY
 ALL LIVE AND DEAD LOADS. SEC. 107.2.1.2 CITY
 AMENDMENTS.
  
 RESPONSE:
 SCOPE OF WORK IS NO CLEAR NOW. SEC. 107.2.1 CITY
 AMENDMENTS. NEW STRUCTURAL DRAWING S-01 SHOWS WHAT
 LOOKS LIKE A SECOND FLOOR FRAMING PLAN (THERE IS NO
 NAME FOR THIS PLAN). IN ADDITION IT DOESN'T SPECIFY
 WHAT IS THE SCOPE OF WORK ON THIS PLAN. PREVIOUS FLOOR
 FRAMING PLAN WAS FOR THE REPAIR ON ONE CORNER OF THE
 FLOOR. NOW, THE SCOPE OF WORK IS NOT CLEAR.
 ALSO, PREVIOUS SET OF PLANS SHOWED A ROOF FRAMING PLAN
 FOR REPAIR AT ONE CORNER ALSO. THE STRUCTURAL PLAN
 SUBMITTED (S-01) IS NOT CLEAR ON THE SCOPE OF WORK.
  
 ON THE OTHER HAND, WALL SECTIONS ON THE RIGHT HAND SIDE
 OF THE SHEET SHOWS THE SECOND FLOOR CONCRETE BLOCK WALL
 BEING SUPPORTED BY WOOD FLOOR JOISTS. THIS DOESN'T SEEM
 TO BE RIGHT. ( MASONRY SHALL NOT BE SUPPORTED ON WOOD.
 SEC. 2104.1.1 FBC-BUILDING). PREVIOUS DRAWINGS SHOWED A
 CONTINUOUS CONCRETE BLOCK WALL ALL THE WAY UP TO THE
 SECOND FLOOR. AND, FLOOR JOISTS WERE SUPPORTED ON
 STRUCTURAL WOOD LEDGERS. CLARIFY/REVISE AS REQUIRED.
 ALSO, THE HURRICANE TIES (SIMPSON H3) SPECIFIED FOR THE
 FIRST FLOOR FRAMING PLAN AND ROOF FRAMING PLAN ARE WOOD
 TO WOOD CONNECTORS. ACCORDING TO WALL SECTIONS
 SUBMITTED THERE ARE WOOD JOISTS ATTACHED TO THE
 CONCRETE BLOCK WALL. REVISE AS REQUIRED. SPECIFY
 CONNECTORS FOR MASONRY CONSTRUCTION.
 AND, THERE IS NOT INFORMATION ABOUT THE ROOF VENTS.
 PREVIOUS DRAWINGS SHOWED CONTINUATIONS ROOF VENTS.
  
 ARCHITECTS-ENGINEERS
 FLORIDA STATUTE 553.80(2)(B):
 WITH RESPECT TO EVALUATION OF DESIGN PROFESSIONALS
 DOCUMENTS, IF A LOCAL GOVERNMENT FINDS IT NECESSARY, IN
 ORDER TO ENFORCE COMPLIANCE WITH THE FLORIDA BUILDING
 CODE AND ISSUE A PERMIT, TO REJECT DESIGN DOCUMENTS
 REQUIRED BY THE CODE THREE OR MORE TIMES FOR FAILURE TO
 CORRECT A CODE VIOLATION SPECIFICALLY AND CONTINUOUSLY
 NOTED IN EACH REJECTION, INCLUDING, BUT NOT LIMITED TO,
 EGRESS, FIRE PROTECTION, STRUCTURAL STABILITY, ENERGY,
 ACCESSIBILITY, LIGHTING, VENTILATION, ELECTRICAL,
 MECHANICAL, PLUMBING, AND GAS SYSTEMS, OR OTHER
 REQUIREMENTS IDENTIFIED BY RULE OF THE FLORIDA BUILDING
 COMMISSION ADOPTED PURSUANT TO CHAPTER 120, THE LOCAL
 GOVERNMENT SHALL IMPOSE, EACH TIME AFTER THE THIRD SUCH
 REVIEW THE PLANS ARE REJECTED FOR THAT CODE VIOLATION,
 A FEE OF FOUR TIMES THE AMOUNT OF THE PROPORTION OF THE
 PERMIT FEE ATTRIBUTED TO PLANS REVIEW
  
  
  
 5- ALL PLANS SUBMITTED HAVE A COPY OF THE SEAL AND
 SIGNATURE OF THE ENGINEER OF RECORD. NEED TO PROVIDE
 PLANS WITH ORIGINAL SEAL AND SIGNATURE AS REQUIRED BY
 61G15-23.001 FAC.
  
  
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 ENGINEER OF RECORD TO CALL IF THERE ARE ANY QUESTIONS
 REGARDING THE COMMENTS AND PROVIDE A RESPONSE LETTER
 ADDRESSING EACH COMMENT TO AVOID ANY PLAN REVIEW FEES
 AND TO HELP EXPEDITE THE REVIEW PROCESS.
 ADDITIONALLY, PLEASE INSERT CORRECTED PAGES INTO THE
 SUBMITTAL AND REMOVE/VOID THE PREVIOUSLY REVIEWED
 SHEETS. PLEASE DON'T STAPLE OLD DRAWINGS. SUBMIT OLD
 DRAWINGS FOR REFERENCE.
  
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status F Date 2019-10-21 Cont ID  
Sent By jgomez Date 2019-10-21 Time 18:49 Rev Time 0.00
Received By jgomez Date 2019-10-21 Time 17:08 Sent To  
Notes
2019-10-21 18:31:45BUILDING REVIEW CAN NOT BE COMPLETED AT THIS TIME.
 PLANS SUBMITTED ARE FOR THE MAIN HOUSE ONLY. THERE ARE
 TWO STRUCTURES IN THIS PARCEL. IT WAS REQUESTED ON
 09/18/19 MEETING WITH CONTRACTOR AND OWNER TO HAVE A
 SEPARATE PERMIT APPLICATION FOR EACH STRUCTURE.
  
 NOTE:
 DRAWINGS SUBMITTED DON'T HAVE AN ORIGINAL SIGNATURE AS
 REQUIRED BY CHAPTER 471 FLORIDA STATUES WHEN SUBMITTING
 PLANS /DOCUMENTS FOR PUBLIC RECORDS.
  
  
  
 09/18/19 MET WITH RONEN HAZAN (OWNER),DANIEL ACEVEDO
 (CONTRACTOR), JOHN FRASCA (CODE ENFORCEMENT) TO GO OVER
 COMMENTS. JG.
  
  
  
 RESIDENTIAL (R3) FIFTH BUILDING REVIEW COMMENTS
 CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS.
  
 NOTE:
 ARCHITECTS-ENGINEERS
 FLORIDA STATUTE 553.80(2)(B):
 WITH RESPECT TO EVALUATION OF DESIGN PROFESSIONALS
 DOCUMENTS, IF A LOCAL GOVERNMENT FINDS IT NECESSARY, IN
 ORDER TO ENFORCE COMPLIANCE WITH THE FLORIDA BUILDING
 CODE AND ISSUE A PERMIT, TO REJECT DESIGN DOCUMENTS
 REQUIRED BY THE CODE THREE OR MORE TIMES FOR FAILURE TO
 CORRECT A CODE VIOLATION SPECIFICALLY AND CONTINUOUSLY
 NOTED IN EACH REJECTION, INCLUDING, BUT NOT LIMITED TO,
 EGRESS, FIRE PROTECTION, STRUCTURAL STABILITY, ENERGY,
 ACCESSIBILITY, LIGHTING, VENTILATION, ELECTRICAL,
 MECHANICAL, PLUMBING, AND GAS SYSTEMS, OR OTHER
 REQUIREMENTS IDENTIFIED BY RULE OF THE FLORIDA BUILDING
 COMMISSION ADOPTED PURSUANT TO CHAPTER 120, THE LOCAL
 GOVERNMENT SHALL IMPOSE, EACH TIME AFTER THE THIRD SUCH
 REVIEW THE PLANS ARE REJECTED FOR THAT CODE VIOLATION,
 A FEE OF FOUR TIMES THE AMOUNT OF THE PROPORTION OF THE
 PERMIT FEE ATTRIBUTED TO PLANS REVIEW
  
  
 1- SHEET S-01:
 PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR ONE
 HOUR FIRE RATED FLOOR ASSEMBLY SEPARATING DUPLEX A AND
 B.
 SEC. 801.3 EXISTING BUILDING AND SEC. R302.3
 FBC-RESIDENTIAL.
  
 RESPONSE:
 REPEAT COMMENT. DETAIL FOR 1 HOUR FLOOR ASSEMBLY AND
 INFORMATION SHOWN ON THE BUILDING SECTION FOR THE
 FLOOR/CEILING ASSEMBLY ON SAME SHEET DON'T MATCH.
 REVISE AS REQUIRED TO MATCH.
 SEC. 107.2.1 CITY AMENDMENTS. THERE IS NO COORDINATION
 BETWEEN 1 HOUR FLOOR ASSEMBLY NO L501 AND INFORMATION
 SHOWN ON THE WALL SECTION ON SAME SHEET.
  
 PROVIDE COMPLETE DETAIL/SPECIFICATIONS FOR THE APPROVED
 FLOOR /CEILING FIRE RATED ASSEMBLY. SPECIFY ALL
 FINISHES, INCLUDING THE FINISH FLOOR. SEC. 107.2.1 CITY
 AMENDMENTS.
 ENGINEER IS NOT PROVIDING A COMPLETE DRAWING OF THE 1
 HOUR APPROVED FLOOR/CEILING FIRE RATED ASSEMBLY.
 PROVIDE COMPLETE UL L501 APPROVED ASSEMBLY DETAIL THAT
 MATCHES PROPOSED INSTALLATION. SPECIFY THICKNESS OF
 MATERIALS, FASTENING SPECIFICATIONS, ETC. TYPICALLY
 THIS IS DONE BY COPYING THE DETAILS FROM THE UL
 WEBSITE.
  
 2- WINDOW REPLACEMENT :
 A) CLEARLY SPECIFY TYPE AND SIZE OF EXISTING WINDOWS
 AND TYPE AND SIZE OF PROPOSED WINDOWS TO VERIFY
 COMPLIANCE WITH THE EGRESS REQUIREMENTS OF SEC. 702.5
 FBC-EXISTING BUILDING.
  
 RESPONSE:
 REPEAT COMMENT. EGRESS NOTE ON SHEET A-01 DOESN'T
 ADDRESS THE COMMENT. THIS NOTE DOESN'T ANSWER WHAT IT
 WAS REQUESTED. PLEASE READ THE COMMENT AGAIN AND
 PROVIDE THE REQUIRED INFORMATION. ALSO, IT LOOKS LIKE
 THE CODE SECTION IS TAKING FROM ANOTHER CODE OTHER THAN
 THE 2017 FBC-RESIDENTIAL. IN ADDITION, THE WINDOW SIZES
 SHOWN ON THE PROPOSED WINDOW SCHEDULE DON'T COMPLY.
  
 3- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 FAC 61G20-3.001 FOR:
 A) EXTERIOR DOORS AS SHOWN ON PLANS. NOTE: PROVIDE
 FLORIDA PRODUCT APPROVAL COVER PAGE THAT CORRESPOND TO
 DRAWINGS MA-FL0211-17 SUBMITTED.
  
 RESPONSE:
 REPEAT COMMENT. FLORIDA PRODUCT APPROVAL COVER PAGE WAS
 NOT PROVIDED. NEED TO PROVIDE COMPLETE FLORIDA PRODUCT
 APPROVAL, INCLUDING THE FLORIDA PRODUCT APPROVAL COVER
 PAGE THAT CORRESPONDS TO THE DRAWINGS SUBMITTED. THE
 FLORIDA PRODUCT APPROVAL IS REQUIRED BECAUSE IT SHOWS
 IF PRODUCT IS APPROVED AND CURRENT CODE IN EFFECT.
 NOTE: IF THERE IS NOT CURRENT FLORIDA PRODUCT APPROVAL,
 THEN MANUFACTURER MAY APPLY FOR LOCAL PRODUCT APPROVAL.
 2 COPIES OF COMPLETE ENGINEERED PACKAGE WITH ORIGINAL
 SEAL/SIGNATURE ALONG WITH APPLICATION FOR PRODUCT
 APPROVAL WILL BE REQUIRED FOR BUILDING OFFICIAL
 REVIEW/APPROVAL PROCESS.
  
 4- RAFTER CONNECTION DETAIL ON SHEET S-01. ENGINEER TO
 PROVIDE ENGINEERING CALCULATIONS SHOWING THAT THE
 SPECIFIED CONNECTION IS ADEQUATE FOR THE SUPPORT OF
 SECOND FLOOR JOISTS. ENGINEER TO SHOW THAT 1/4" X
 3-1/4" TAPCONS SPACED AT 24" O.C ARE ADEQUATE TO CARRY
 ALL LIVE AND DEAD LOADS. SEC. 107.2.1.2 CITY
 AMENDMENTS.
  
 5- SPECIFICATIONS SUBMITTED ON A SEPARATE LETTER BY THE
 ENGINEER OF RECORD FOR THE REPAIR OF RAFTERS IN MAIN
 HOUSE DON'T MATCH DETAILS SHOWN ON THE STRUCTURAL
 DRAWINGS. ENGINEER TO COORDINATE AND PROVIDE ALL THE
 SPECIFICATIONS ON THE STRUCTURAL PLANS TO AVOID
 CONFLICTS. SEC. 107.2.1 CITY AMENDMENTS.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 ENGINEER OF RECORD TO CALL IF THERE ARE ANY QUESTIONS
 REGARDING THE COMMENTS AND PROVIDE A RESPONSE LETTER
 ADDRESSING EACH COMMENT TO AVOID ANY PLAN REVIEW FEES
 AND TO HELP EXPEDITE THE REVIEW PROCESS.
 ADDITIONALLY, PLEASE INSERT CORRECTED PAGES INTO THE
 SUBMITTAL AND REMOVE/VOID THE PREVIOUSLY REVIEWED
 SHEETS. PLEASE DON'T STAPLE OLD DRAWINGS. SUBMIT OLD
 DRAWINGS FOR REFERENCE.
  
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  
  
  
  
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2019-06-26 Cont ID  
Sent By jgomez Date 2019-06-26 Time 09:46 Rev Time 0.00
Received By jgomez Date 2019-06-25 Time 17:46 Sent To  
Notes
2019-06-26 09:46:2509/18/19 MET WITH RONEN HAZAN (OWNER),DANIEL ACEVEDO
 (CONTRACTOR), JOHN FRASCA (CODE ENFORCEMENT) TO GO OVER
 COMMENTS. JG.
  
  
  
 RESIDENTIAL (R3) FOURTH BUILDING REVIEW COMMENTS
 CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS.
  
 NOTE:
 ARCHITECTS-ENGINEERS
 FLORIDA STATUTE 553.80(2)(B):
 WITH RESPECT TO EVALUATION OF DESIGN PROFESSIONALS
 DOCUMENTS, IF A LOCAL GOVERNMENT FINDS IT NECESSARY, IN
 ORDER TO ENFORCE COMPLIANCE WITH THE FLORIDA BUILDING
 CODE AND ISSUE A PERMIT, TO REJECT DESIGN DOCUMENTS
 REQUIRED BY THE CODE THREE OR MORE TIMES FOR FAILURE TO
 CORRECT A CODE VIOLATION SPECIFICALLY AND CONTINUOUSLY
 NOTED IN EACH REJECTION, INCLUDING, BUT NOT LIMITED TO,
 EGRESS, FIRE PROTECTION, STRUCTURAL STABILITY, ENERGY,
 ACCESSIBILITY, LIGHTING, VENTILATION, ELECTRICAL,
 MECHANICAL, PLUMBING, AND GAS SYSTEMS, OR OTHER
 REQUIREMENTS IDENTIFIED BY RULE OF THE FLORIDA BUILDING
 COMMISSION ADOPTED PURSUANT TO CHAPTER 120, THE LOCAL
 GOVERNMENT SHALL IMPOSE, EACH TIME AFTER THE THIRD SUCH
 REVIEW THE PLANS ARE REJECTED FOR THAT CODE VIOLATION,
 A FEE OF FOUR TIMES THE AMOUNT OF THE PROPORTION OF THE
 PERMIT FEE ATTRIBUTED TO PLANS REVIEW
  
  
 1- SHEET S-01:
 PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR ONE
 HOUR FIRE RATED FLOOR ASSEMBLY SEPARATING DUPLEX A AND
 B.
 SEC. 801.3 FBC-EXISTING BUILDING AND SEC. R302.3
 FBC-RESIDENTIAL.
  
 RESPONSE:
 REPEAT COMMENT. DETAIL FOR 1 HOUR FLOOR ASSEMBLY AND
 INFORMATION SHOWN ON THE BUILDING SECTION FOR THE
 FLOOR/CEILING ASSEMBLY ON SAME SHEET DON'T MATCH.
 REVISE AS REQUIRED TO MATCH.
 SEC. 107.2.1 CITY AMENDMENTS. THERE IS NO COORDINATION
 BETWEEN 1 HOUR FLOOR ASSEMBLY NO L501 AND INFORMATION
 SHOWN ON THE WALL SECTION ON SAME SHEET.
  
 PROVIDE COMPLETE DETAIL/SPECIFICATIONS FOR THE APPROVED
 FLOOR /CEILING FIRE RATED ASSEMBLY. SPECIFY ALL
 FINISHES, INCLUDING THE FINISH FLOOR. SEC. 107.2.1 CITY
 AMENDMENTS.
 ENGINEER IS NOT PROVIDING A COMPLETE DRAWING OF THE 1
 HOUR APPROVED FLOOR/CEILING FIRE RATED ASSEMBLY.
 PROVIDE COMPLETE UL L501 APPROVED ASSEMBLY DETAIL THAT
 MATCHES PROPOSED INSTALLATION. SPECIFY THICKNESS OF
 MATERIALS, FASTENING SPECIFICATIONS, ETC. TYPICALLY
 THIS IS DONE BY COPYING THE DETAILS FROM THE UL
 WEBSITE.
  
 2- WINDOW REPLACEMENT :
 A) CLEARLY SPECIFY TYPE AND SIZE OF EXISTING WINDOWS
 AND TYPE AND SIZE OF PROPOSED WINDOWS TO VERIFY
 COMPLIANCE WITH THE EGRESS REQUIREMENTS OF SEC. 702.5
 FBC-EXISTING BUILDING.
  
 RESPONSE:
 REPEAT COMMENT. EGRESS NOTE ON SHEET A-01 DOESN'T
 ADDRESS THE COMMENT. THIS NOTE DOESN'T ANSWER WHAT IT
 WAS REQUESTED. PLEASE READ THE COMMENT AGAIN AND
 PROVIDE THE REQUIRED INFORMATION. ALSO, IT LOOKS LIKE
 THE CODE SECTION IS TAKING FROM ANOTHER CODE OTHER THAN
 THE 2017 FBC-RESIDENTIAL. IN ADDITION, THE WINDOW SIZES
 SHOWN ON THE PROPOSED WINDOW SCHEDULE DON'T COMPLY.
  
 3- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 FAC 61G20-3.001 FOR:
 A) EXTERIOR DOORS AS SHOWN ON PLANS. NOTE: PROVIDE
 FLORIDA PRODUCT APPROVAL COVER PAGE THAT CORRESPOND TO
 DRAWINGS MA-FL0211-17 SUBMITTEDD.
  
 RESPONSE:
 REPEAT COMMENT. FLORIDA PRODUCT APPROVAL COVER PAGE WAS
 NOT PROVIDED. NEED TO PROVIDE COMPLETE FLORIDA PRODUCT
 APPROVAL, INCLUDING THE FLORIDA PRODUCT APPROVAL COVER
 PAGE THAT CORRESPONDS TO THE DRAWINGS SUBMITTED. THE
 FLORIDA PRODUCT APPROVAL IS REQUIRED BECAUSE IT SHOWS
 IF PRODUCT IS APPROVED AND CURRENT CODE IN EFFECT.
 NOTE: IF THERE IS NOT CURRENT FLORIDA PRODUCT APPROVAL,
 THEN MANUFACTURER MAY APPLY FOR LOCAL PRODUCT APPROVAL.
 2 COPIES OF COMPLETE ENGINEERED PACKAGE WITH ORIGINAL
 SEAL/SIGNATURE ALONG WITH APPLICATION FOR PRODUCT
 APPROVAL WILL BE REQUIRED FOR BUILDING OFFICIAL
 REVIEW/APPROVAL PROCESS.
  
 4- RAFTER CONNECTION DETAIL ON SHEET S-01. ENGINEER TO
 PROVIDE ENGINEERING CALCULATIONS SHOWING THAT THE
 SPECIFIED CONNECTION IS ADEQUATE FOR THE SUPPORT OF
 SECOND FLOOR JOISTS. ENGINEER TO SHOW THAT 1/4" X
 3-1/4" TAPCONS SPACED AT 24" O.C ARE ADEQUATE TO CARRY
 ALL LIVE AND DEAD LOADS. SEC. 107.2.1.2 CITY
 AMENDMENTS.
  
 5- SPECIFICATIONS SUBMITTED ON A SEPARATE LETTER BY THE
 ENGINEER OF RECORD FOR THE REPAIR OF RAFTERS IN MAIN
 HOUSE DON'T MATCH DETAILS SHOWN ON THE STRUCTURAL
 DRAWINGS. ENGINEER TO COORDINATE AND PROVIDE ALL THE
 SPECIFICATIONS ON THE STRUCTURAL PLANS TO AVOID
 CONFLICTS. SEC. 107.2.1 CITY AMENDMENTS.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 ENGINEER OF RECORD TO CALL IF THERE ARE ANY QUESTIONS
 REGARDING THE COMMENTS AND PROVIDE A RESPONSE LETTER
 ADDRESSING EACH COMMENT TO AVOID ANY PLAN REVIEW FEES
 AND TO HELP EXPEDITE THE REVIEW PROCESS.
 ADDITIONALLY, PLEASE INSERT CORRECTED PAGES INTO THE
 SUBMITTAL AND REMOVE/VOID THE PREVIOUSLY REVIEWED
 SHEETS. PLEASE DON'T STAPLE OLD DRAWINGS. SUBMIT OLD
 DRAWINGS FOR REFERENCE.
  
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  
  
  
  
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2019-05-10 Cont ID  
Sent By jgomez Date 2019-05-10 Time 16:07 Rev Time 0.00
Received By jgomez Date 2019-05-09 Time 18:18 Sent To  
Notes
2019-05-09 18:27:22RESIDENTIAL (R3) THIRD BUILDING REVIEW COMMENTS
 CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS.
  
 NOTE:
 ARCHITECTS-ENGINEERS
 FLORIDA STATUTE 553.80(2)(B):
 WITH RESPECT TO EVALUATION OF DESIGN PROFESSIONALS
 DOCUMENTS, IF A LOCAL GOVERNMENT FINDS IT NECESSARY, IN
 ORDER TO ENFORCE COMPLIANCE WITH THE FLORIDA BUILDING
 CODE AND ISSUE A PERMIT, TO REJECT DESIGN DOCUMENTS
 REQUIRED BY THE CODE THREE OR MORE TIMES FOR FAILURE TO
 CORRECT A CODE VIOLATION SPECIFICALLY AND CONTINUOUSLY
 NOTED IN EACH REJECTION, INCLUDING, BUT NOT LIMITED TO,
 EGRESS, FIRE PROTECTION, STRUCTURAL STABILITY, ENERGY,
 ACCESSIBILITY, LIGHTING, VENTILATION, ELECTRICAL,
 MECHANICAL, PLUMBING, AND GAS SYSTEMS, OR OTHER
 REQUIREMENTS IDENTIFIED BY RULE OF THE FLORIDA BUILDING
 COMMISSION ADOPTED PURSUANT TO CHAPTER 120, THE LOCAL
 GOVERNMENT SHALL IMPOSE, EACH TIME AFTER THE THIRD SUCH
 REVIEW THE PLANS ARE REJECTED FOR THAT CODE VIOLATION,
 A FEE OF FOUR TIMES THE AMOUNT OF THE PROPORTION OF THE
 PERMIT FEE ATTRIBUTED TO PLANS REVIEW
  
  
  
  
 1- SHEET S-01:
  
 ORIGINAL COMMENT:
 PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR ONE
 HOUR FIRE RATED FLOOR ASSEMBLY SEPARATING DUPLEX A AND
 B.
 SEC. 801.3 FBC-EXISTING BUILDING AND SEC. R302.3
 FBC-RESIDENTIAL.
  
 RESPONSE:
 A) DETAIL FOR 1 HOUR FLOOR ASSEMBLY DESIGN NO. L501
 DON'T SEEM TO WORK. THIS ASSEMBLY REQUIRES 2X10 MIN.
 WOOD JOISTS. PLANS SUBMITTED SHOW 2X8 WOOD JOISTS.
 REVISE AS REQUIRED. SEC. 107.2.1 CITY AMENDMENTS.
  
 B)DETAIL FOR 1 HOUR FLOOR ASSEMBLY AND INFORMATION
 SHOWN ON THE BUILDING SECTION FOR THE FLOOR/CEILING
 ASSEMBLY ON SAME SHEET DON'T MATCH. REVISE AS REQUIRED
 TO MATCH.
 SEC. 107.2.1 CITY AMENDMENTS.
  
 C) PROVIDE COMPLETE DETAIL/SPECIFICATIONS FOR THE
 APPROVED FLOOR /CEILING FIRE RATED ASSEMBLY. SPECIFY
 ALL FINISHES, INCLUDING THE FINISH FLOOR. SEC. 107.2.1
 CITY AMENDMENTS.
  
  
 2- OK.
  
 3- OK.
  
 4- OK.
  
 ORIGINAL COMMENT:
 5- WINDOW REPLACEMENT :
 CLEARLY SPECIFY TYPE AND SIZE OF EXISTING WINDOWS AND
 TYPE AND SIZE OF PROPOSED WINDOWS TO VERIFY COMPLIANCE
 WITH THE EGRESS REQUIREMENTS OF SEC. 702.5 FBC-EXISTING
 BUILDING.
 NOTE: NEED TO VERIFY MANUFACTURER'S LARGEST STANDARD
 SIZE WINDOW THAT WILL FIT WITHIN THE EXISTING FRAME OR
 EXISTING ROUGH OPENING AND THAT WILL NOT REDUCE THE
 EGRESS SIZE OPENING OF EXISTING WINDOW AS REQUIRED BY
 SEC. 702.5.
  
 RESPONSE:
 REPEAT COMMENT. NOT PROPERLY ADDRESSED. ENGINEER
 RESPONSE LETTER STATES "EGRESS WINDOW NOTES AND DETAIL
 ADDED TO SHEET A-01". BASED ON THE TYPE AND SIZE OF
 WINDOWS SHOWN ON THE WINDOW/DOOR SCHEDULES ON SHEET
 A-01, THE BEDROOM WINDOWS DON'T COMPLY WITH THE EGRESS
 WINDOW NOTES PROVIDED. REVISE AS REQUIRED TO COMPLY.
  
  
 6- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 FAC 61G20-3.001 FOR:
  
 ORIGINAL COMMENT:
 A) EXTERIOR DOORS AS SHOWN ON PLANS. NOTE: PROVIDE
 FLORIDA PRODUCT APPROVAL COVER PAGE THAT CORRESPOND TO
 DRAWINGS MA-FL0211-17 SUBMITTED.
  
 RESPONSE:
 REPEAT COMMENT. FLORIDA PRODUCT APPROVAL COVER PAGE WAS
 NOT PROVIDED.
  
 B) OK.
  
 ORIGINAL COMMENT:
 C) FLAT ROOF NOA 16-0517.08. PROVIDE SIGNED AND SEALED
 RAS 117 CALCULATIONS AS REQUIRED BY GENERAL LIMITATION
 #7 ON LAST PAGE OF NOA TO MEET THE DESIGN PRESSURES AT
 ALL ROOF ZONES.
 SEC. R301.1 FBC-RESIDENTIAL.
  
 RESPONSE:
 REPEAT COMMENT. NOT ADDRESSED.
  
 7- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS
 REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS.
  
 RESPONSE:
 REPEAT COMMENT.
  
  
 8- PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR
 REVISED MATERIALS MAY RESULT IN NEW PLAN REVIEW
 COMMENTS.
 ENGINEER OF RECORD TO CALL IF THERE ARE ANY QUESTIONS
 REGARDING THE COMMENTS AND PROVIDE A RESPONSE LETTER
 ADDRESSING EACH COMMENT TO AVOID ANY PLAN REVIEW FEES
 AND TO HELP EXPEDITE THE REVIEW PROCESS.
 ADDITIONALLY, PLEASE INSERT CORRECTED PAGES INTO THE
 SUBMITTAL AND REMOVE/VOID THE PREVIOUSLY REVIEWED
 SHEETS. PLEASE DON'T STAPLE OLD DRAWINGS. SUBMIT OLD
 DRAWINGS FOR REFERENCE.
  
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  
  
  
  
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2019-02-21 Cont ID  
Sent By jgomez Date 2019-02-21 Time 18:04 Rev Time 0.00
Received By jgomez Date 2019-02-21 Time 13:11 Sent To  
Notes
2019-02-21 18:12:18RESIDENTIAL (R3) SECOND BUILDING REVIEW COMMENTS
 CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS.
  
 NOTE:
 ARCHITECTS-ENGINEERS
 FLORIDA STATUTE 553.80(2)(B):
 WITH RESPECT TO EVALUATION OF DESIGN PROFESSIONALS
 DOCUMENTS, IF A LOCAL GOVERNMENT FINDS IT NECESSARY, IN
 ORDER TO ENFORCE COMPLIANCE WITH THE FLORIDA BUILDING
 CODE AND ISSUE A PERMIT, TO REJECT DESIGN DOCUMENTS
 REQUIRED BY THE CODE THREE OR MORE TIMES FOR FAILURE TO
 CORRECT A CODE VIOLATION SPECIFICALLY AND CONTINUOUSLY
 NOTED IN EACH REJECTION, INCLUDING, BUT NOT LIMITED TO,
 EGRESS, FIRE PROTECTION, STRUCTURAL STABILITY, ENERGY,
 ACCESSIBILITY, LIGHTING, VENTILATION, ELECTRICAL,
 MECHANICAL, PLUMBING, AND GAS SYSTEMS, OR OTHER
 REQUIREMENTS IDENTIFIED BY RULE OF THE FLORIDA BUILDING
 COMMISSION ADOPTED PURSUANT TO CHAPTER 120, THE LOCAL
 GOVERNMENT SHALL IMPOSE, EACH TIME AFTER THE THIRD SUCH
 REVIEW THE PLANS ARE REJECTED FOR THAT CODE VIOLATION,
 A FEE OF FOUR TIMES THE AMOUNT OF THE PROPORTION OF THE
 PERMIT FEE ATTRIBUTED TO PLANS REVIEW
  
  
  
  
 1- SHEET S-01:
  
 ORIGINAL COMMENT:
 A) PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR ONE
 HOUR FIRE RATED FLOOR ASSEMBLY SEPARATING DUPLEX A AND
 B.
 SEC. 801.3 FBC-EXISTING BUILDING AND SEC. R302.3
 FBC-RESIDENTIAL.
  
 RESPONSE:
 REPEAT COMMENT. NOT ADDRESSED.
  
 ORIGINAL COMMENT:
 B) CLARIFY WHY PROVIDING ONE HOUR FIRE RATED DEMISING
 PARTITION ON THESE SHEET. THERE ARE NO DEMISING
 PARTITIONS BETWEEN DWELLING UNITS. THE REQUIRED FIRE
 RATING SEPARATION IS LOCATED ON THE FLOOR/CEILING
 ASSEMBLY. COORDINATE WITH ITEM #1(A) ABOVE. PROVIDE
 WALL DETAIL/SPECIFICATIONS THAT SHOW COMPLIANCE WITH
 THE FLOOR/CEILING ASSEMBLY PENETRATIONS AS REQUIRED BY
 SEC. R302.4 FBC-RESIDENTIAL.
  
 RESPONSE:
 REPEAT COMMENT. NOT ADDRESSED.
  
 ORIGINAL COMMENT.
 2- ROOF TRUSS REPAIR DETAILS ON SHEET S-02 ARE
 INCOMPLETE. SEC. 107.2.1 CITY AMENDMENTS.
 A)SPECIFY NAIL TYPE AND HOW LONG ARE THE 2X4'S THAT ARE
 SISTERED TO THE TRUSSES.
  
 RESPONSE:
 REPEAT COMMENT. NOT ADDRESSED.
  
 ORIGINAL COMMENT:
 B) SPECIFY WHICH CONNECTOR IS GOING TO BE USED FOR THE
 ROOF TO WALL CONNECTIONS.
  
 RESPONSE:
 REPEAT COMMENT. DETAILS ARE KEYED WITH SOME CONNECTORS,
 BUT THERE IS NOT CONNECTOR SCHEDULE. REVISE AS
 REQUIRED.
  
 C) NEW SHEET S-02 WAS NOT SIGNED AND SEALED BY THE
 ENGINEER OF RECORD AS REQUIRED BY SEC. 471. F.S.
  
 ORIGINAL COMMENT:
 3- FLAT ROOF REPAIR DETAIL ON SHEET S-02 IS NOT CLEAR
 AND DOESN'T MATCH FRAMING PLAN SHOWN ON SAME SHEET.
 REVISE AS REQUIRED TO MATCH. ALSO, WHERE IS DETAIL 3
 S-01? SEC. 107.2.1 CITY AMENDMENTS.
  
 RESPONSE:
 A)REPEAT COMMENT. THIS DETAIL WAS REDUCED AND PLACED
 UNDER THE ROOF TRUSS REPAIR DETAIL BOX BELOW. NOW THERE
 IS MORE CONFUSION OF WHAT DETAIL APPLIES TO. ALSO, IT'
 TOO SMALL AND IS NOT LEGIBLE. REVISE AS REQUIRED.
 PROVIDE COMPLETE DETAILS ANS SPECIFICATIONS THAT APPLY
 TO THIS JOB. SEC. 107.2.1 CITY AMENDMENTS.
  
 NEW COMMENT:
 B) NEW FLAT ROOF SECTION DETAIL DOESN'T MATCH FLAT ROOF
 PLAN. AND, (1)ROOF SHEATHING NAILING SPECIFICATIONS IS
 NOT CLEAR. (2)PLYWOOD PANEL SIZE AND NAILING PATTERN
 DON'T SEEM TO MATCH LOCATION OF ROOF STRUCTURAL FRAMING
 MEMBERS. (3)SPECIFY ROOF SHEATHING NAIL TYPE.
 (4)CLARIFY HOW 4" X 20" @ 4' ROOF VENTS WILL PROVIDE
 CROSS VENTILATION ON A FLAT ROOF IF THERE IS NOT AIR
 SPACE IN BETWEEN THE ROOFING JOISTS TO ALLOW FOR CROSS
 VENTILATION?. SEC. 107.2.1 CITY AMENDMENTS.
  
 ORIGINAL COMMENT:
 4- DOORS AND WINDOWS CALCULATED DESIGN PRESSURES SHOWN
 ON SHEET A-01 ARE THE SAME FOR ALL OPENINGS. DESIGN
 PRESSURES SEEM TOO LOW FOR SOME OPENINGS. BASED ON THE
 ACTUAL OPENING EFFECTIVE AREA, WALL ZONE AND MEAN ROOF
 HEIGHT. PROVIDE THE ACTUAL DESIGN PRESSURES FOR EACH
 OPENING OR PROVIDE CALCULATIONS FOR WORST CASED
 SCENARIO THAT WILL COVER ALL OPENINGS. SEC. R301.1
 FBC-RESIDENTIAL.
  
 RESPONSE:
 REPEAT COMMENT. NOT ADDRESSED.
  
 4(A)- REVISED SHEET A-01 WAS NOT SIGNED AND SEALED BY
 THE ENGINEER OF RECORD AS REQUIRED BY SEC. 471. F.S.
  
 ORIGINAL COMMENT:
 5- WINDOW REPLACEMENT :
 A)CLEARLY SPECIFY TYPE AND SIZE OF EXISTING WINDOWS AND
 TYPE AND SIZE OF PROPOSED WINDOWS TO VERIFY COMPLIANCE
 WITH THE EGRESS REQUIREMENTS OF SEC. 702.5 FBC-EXISTING
 BUILDING.
 NOTE: NEED TO VERIFY MANUFACTURER'S LARGEST STANDARD
 SIZE WINDOW THAT WILL FIT WITHIN THE EXISTING FRAME OR
 EXISTING ROUGH OPENING AND THAT WILL NOT REDUCE THE
 EGRESS SIZE OPENING OF EXISTING WINDOW AS REQUIRED BY
 SEC. 702.5.
  
 RESPONSE:
 REPEAT COMMENT. NOT ADDRESSED.
  
  
 B) OK.
  
 6- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 FAC 61G20-3.001 FOR:
  
 ORIGINAL COMMENT:
 A) EXTERIOR DOORS AS SHOWN ON PLANS. NOTE: PROVIDE
 FLORIDA PRODUCT APPROVAL COVER PAGE THAT CORRESPOND TO
 DRAWINGS MA-FL0211-17 SUBMITTED.
  
 RESPONSE:
 REPEAT COMMENT. NOT ADDRESSED.
  
 ORIGINAL COMMENT:
 B) WINDOW MULLIONS AS SHOWN ON PLANS. REQUIRED: CLEARLY
 SPECIFY MULLION SIZE TO BE USED TO VERIFY COMPLIANCE
 WITH THE CALCULATED DESIGN PRESSURES.
  
 RESPONSE:
 REPEAT COMMENT. NOT ADDRESSED.
  
  
 ORIGINAL COMMENT:
 C) FLAT ROOF NOA 16-0517.08. PROVIDE SIGNED AND SEALED
 RAS 117 CALCULATIONS AS REQUIRED BY GENERAL LIMITATION
 #7 ON LAST PAGE OF NOA TO MEET THE DESIGN PRESSURES AT
 ALL ROOF ZONES.
 SEC. R301.1 FBC-RESIDENTIAL.
  
 RESPONSE:
 REPEAT COMMENT. NOT ADDRESSED.
  
 7- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS
 REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS
  
  
 8- PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR
 REVISED MATERIALS MAY RESULT IN NEW PLAN REVIEW
 COMMENTS.
 ENGINEER OF RECORD TO CALL IF THERE ARE ANY QUESTIONS
 REGARDING THE COMMENTS AND PROVIDE A RESPONSE LETTER
 ADDRESSING EACH COMMENT TO AVOID ANY PLAN REVIEW FEES
 AND TO HELP EXPEDITE THE REVIEW PROCESS.
 ADDITIONALLY, PLEASE INSERT CORRECTED PAGES INTO THE
 SUBMITTAL AND REMOVE/VOID THE PREVIOUSLY REVIEWED
 SHEETS. PLEASE DON'T STAPLE OLD DRAWINGS. SUBMIT OLD
 DRAWINGS FOR REFERENCE.
  
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  
  
  
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2018-11-27 Cont ID  
Sent By jgomez Date 2018-11-27 Time 10:47 Rev Time 0.00
Received By jgomez Date 2018-11-27 Time 10:45 Sent To  
Notes
2018-11-27 10:47:59RESIDENTIAL (R3) BUILDING REVIEW COMMENTS
 CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS.
  
 NOTE: SEC. 801.3 FBC-EXISTING BUILDING. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1- SHEET S-01:
 A) PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR ONE
 HOUR FIRE RATED FLOOR ASSEMBLY SEPARATING DUPLEX A AND
 B.
 SEC. 801.3 FBC-EXISTING BUILDING AND SEC. R302.3
 FBC-RESIDENTIAL.
  
 B) CLARIFY WHY PROVIDING ONE HOUR FIRE RATED DEMISING
 PARTITION ON THESE SHEET. THERE ARE NO DEMISING
 PARTITIONS BETWEEN DWELLING UNITS. THE REQUIRED FIRE
 RATING SEPARATION IS LOCATED ON THE FLOOR/CEILING
 ASSEMBLY. COORDINATE WITH ITEM #1(A) ABOVE. PROVIDE
 WALL DETAIL/SPECIFICATIONS THAT SHOW COMPLIANCE WITH
 THE FLOOR/CEILING ASSEMBLY PENETRATIONS AS REQUIRED BY
 SEC. R302.4 FBC_RESIDENTIAL.
  
 2- ROOF TRUSS REPAIR DETAILS ON SHEET S-02 ARE
 INCOMPLETE. SEC. 107.2.1 CITY AMENDMENTS.
 A)SPECIFY NAIL TYPE AND HOW LONG ARE THE 2X4'S THAT ARE
 SISTERED TO THE TRUSSES.
 B) SPECIFY WHICH CONNECTOR IS GOING TO BE USED FOR THE
 ROOF TO WALL CONNECTION.
  
 3- FLAT ROOF REPAIR DETAIL ON SHEET S-02 IS NOT CLEAR
 AND DOESN'T MATCH FRAMING PLAN SHOWN ON SAME SHEET.
 REVISE AS REQUIRED TO MATCH. ALSO, WHERE IS DETAIL 3
 S-01? SEC. 107.2.1 CITY AMENDMENTS.
  
 4- DOORS AND WINDOWS CALCULATED DESIGN PRESSURES SHOWN
 ON SHEET A-01 ARE THE SAME FOR ALL OPENINGS. DESIGN
 PRESSURES SEEM TOO LOW FOR SOME OPENINGS. BASED ON THE
 ACTUAL OPENING EFFECTIVE AREA, WALL ZONE AND MEAN ROOF
 HEIGHT. PROVIDE THE ACTUAL DESIGN PRESSURES FOR EACH
 OPENING OR PROVIDE CALCULATIONS FOR WORST CASED
 SCENARIO THAT WILL COVER ALL OPENINGS.
 SEC. R301.1 FBC-RESIDENTIAL.
  
 5- WINDOW REPLACEMENT :
 A)CLEARLY SPECIFY TYPE AND SIZE OF EXISTING WINDOWS AND
 TYPE AND SIZE OF PROPOSED WINDOWS TO VERIFY COMPLIANCE
 WITH THE EGRESS REQUIREMENTS OF SEC. 702.5 FBC-EXISTING
 BUILDING.
 NOTE: NEED TO VERIFY MANUFACTURER'S LARGEST STANDARD
 SIZE WINDOW THAT WILL FIT WITHIN THE EXISTING FRAME OR
 EXISTING ROUGH OPENING AND THAT WILL NOT REDUCE THE
 EGRESS SIZE OPENING OF EXISTING WINDOW AS REQUIRED BY
 SEC. 702.5.
  
 B) SECOND FLOOR WINDOW OPENING CONTROL DEVICES: WINDOW
 OPENING CONTROL DEVICES IN WINDOW REPLACEMENT ARE
 REQUIRED WHEN THE TOP SILL OF THE WINDOW OPENING IS AT
 A HEIGHT LESS THAN 24 INCHES (610 MM) ABOVE THE
 FINISHED FLOOR. CLEARLY SPECIFY IF THERE ARE ANY
 WINDOWS WHERE THE WINDOW SILL IS LESS THAN 24" ABOVE
 THE FINISH FLOOR.
 SEC. 702.4 FBC-EXISTING BUILDING.
  
 6- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 FAC 61G20-3.001 FOR:
 (NOTE: THIS MAY BE SUBMITTED LATER AS A DEFERRED
 SUBMITTAL)
  
 A) EXTERIOR DOORS AS SHOWN ON PLANS. NOTE: PROVIDE
 FLORIDA PRODUCT APPROVAL COVER PAGE THAT CORRESPOND TO
 DRAWINGS MA-FL0211-17 SUBMITTED.
  
 B) WINDOW MULLIONS AS SHOWN ON PLANS. REQUIRED: CLEARLY
 SPECIFY MULLION SIZE TO BE USED TO VERIFY COMPLIANCE
 WITH THE CALCULATED DESIGN PRESSURES.
  
 C) FLAT ROOF NOA 16-0517.08. PROVIDE SIGNED AND SEALED
 RAS 117 CALCULATIONS AS REQUIRED BY GENERAL LIMITATION
 #7 ON LAST PAGE OF NOA TO MEET THE DESIGN PRESSURES AT
 ALL ROOF ZONES.
 SEC. R301.1 FBC-RESIDENTIAL.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE/VOID THE
 PREVIOUSLY REVIEWED SHEETS.
 PLEASE DON'T STAPLE OLD DRAWINGS. SUBMIT OLD DRAWINGS
 FOR REFERENCE.
  
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  
  
 ************NOTE:
 SEE E-MAIL FROM JOHN FRASCA REGARDING WORK WITHOUT
 PERMITS DATED 12/19/18.
  
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2020-02-24 Cont ID  
Sent By jpearson Date 2020-02-24 Time 13:29 Rev Time 0.00
Received By jpearson Date 2020-02-24 Time 11:03 Sent To I
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2019-11-12 Cont ID  
Sent By jpearson Date 2019-11-12 Time 13:19 Rev Time 0.00
Received By jpearson Date 2019-11-12 Time 13:19 Sent To M
Notes
2019-11-12 13:18:41CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
 FAC = FLORIDA ADMINISTRATIVE CODE
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 PREVIOUS COMMENTS THAT HAVE BEEN ADDRESSED
 SATISFACTORILY ARE MARKED AS CORRECTED. PREVIOUS
 COMMENTS THAT HAVE NOT BEEN ADDRESSED SATISFACTORILY
 HAVE ADDITIONAL COMMENTS IN PARENTHESES. ANY NEW
 COMMENTS WILL BE LISTED AFTER PREVIOUS COMMENTS.
  
 1. CORRECTED.
 2. SMOKE ALARMS MUST BE INSTALLED AT LEAST 3 FEET FROM
 BATHROOM DOOR, 3 FEET FROM CEILING FANS, AND 3 FEET
 FROM ANY MECHANICAL DUCT. PROVIDE CORRECTIONS. FBC RE
 R314.3(4), NFPA 72:29.8.3.4 (SMOKE ALARM NOT PERMITTED
 IN BATHROOM, ALL OTHER LOCATIONS NEED TO BE CORRECTED.)
 3. PROVIDE GFCI PROTECTED RECEPTACLE OUTLET FOR
 SERVICING OF A/C EQUIPMENT WITHIN 25 FEET OF THE
 EQUIPMENT PER CODE. NEC 210.63; FBC RE E3901.12 (NOT
 PROVIDED.)
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD
 SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2019-10-18 Cont ID  
Sent By jpearson Date 2019-10-18 Time 07:55 Rev Time 0.00
Received By jpearson Date 2019-10-18 Time 07:38 Sent To  
Notes
2019-10-18 07:54:38CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
 FAC = FLORIDA ADMINISTRATIVE CODE
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. NEW PLAN SUBMISSION IS MISSING SHEET E-02. PROVIDE
 FULL SET OF PLANS FOR REVIEW. WPB FBC 107.2.1
 2. SMOKE ALARMS MUST BE INSTALLED AT LEAST 3 FEET FROM
 BATHROOM DOOR, 3 FEET FROM CEILING FANS, AND 3 FEET
 FROM ANY MECHANICAL DUCT. PROVIDE CORRECTIONS. FBC RE
 R314.3(4), NFPA 72:29.8.3.4
 3. PROVIDE GFCI PROTECTED RECEPTACLE OUTLET FOR
 SERVICING OF A/C EQUIPMENT WITHIN 25 FEET OF THE
 EQUIPMENT PER CODE. NEC 210.63; FBC RE E3901.12
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD
 SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2019-10-18 Cont ID  
Sent By jpearson Date 2018-11-19 Time 12:43 Rev Time 0.00
Received By jpearson Date 2018-11-19 Time 08:17 Sent To  
Notes
2019-10-18 07:52:06CHANGES STATUS TO REFLECT FAIL DUE TO 10-18-19 REVIEW.

Review Stop HIST HISTORICAL
Rev No 4 Status P Date 2020-02-10 Cont ID  
Sent By fmittner Date 2020-02-10 Time 15:13 Rev Time 0.00
Received By fmittner Date 2020-02-10 Time 15:13 Sent To  
Notes
***NONE***

Review Stop HIST HISTORICAL
Rev No 3 Status P Date 2019-11-13 Cont ID  
Sent By fmittner Date 2019-11-13 Time 13:48 Rev Time 0.00
Received By fmittner Date 2019-11-13 Time 13:48 Sent To  
Notes
***NONE***

Review Stop HIST HISTORICAL
Rev No 2 Status P Date 2019-10-11 Cont ID  
Sent By fmittner Date 2019-10-11 Time 12:13 Rev Time 0.00
Received By fmittner Date 2019-10-11 Time 12:13 Sent To  
Notes
***NONE***

Review Stop HIST HISTORICAL
Rev No 1 Status P Date 2018-11-14 Cont ID  
Sent By fmittner Date 2018-11-14 Time 08:16 Rev Time 0.00
Received By fmittner Date 2018-11-14 Time 08:16 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date   Cont ID  
Sent By   Date 2020-02-24 Time   Rev Time 0.00
Received By lmarchan Date 2020-02-03 Time 13:27 Sent To  
Notes
2020-02-21 16:23:56ROUTED FROM ZONING TO PERMIT LIBRARIAN 2/24/20 EL
2020-02-04 13:27:48R31

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2019-11-19 Cont ID  
Sent By shill Date 2019-11-19 Time 06:12 Rev Time 0.00
Received By shill Date 2019-10-24 Time 13:48 Sent To  
Notes
2019-11-18 16:02:53ROUTED FROM ZONING TO HISTORIC EL
2019-11-12 12:56:54TO JP DESK
  
2019-11-07 14:54:34ROUTED TO DESK OF SHILL PER HER REQUEST ALONG WITH
 #19101417
2019-10-28 13:48:50R21

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2019-10-21 Cont ID  
Sent By jgomez Date 2019-10-21 Time 19:02 Rev Time 0.00
Received By jgomez Date 2019-10-04 Time 14:59 Sent To  
Notes
2019-10-18 16:37:01TO HM DESK
  
2019-10-10 16:26:28NEW COMMENTS FROM ZONING
  
 ROUTED FROM ZONING TO PERMIT LIBRARIAN
 EL
2019-10-07 14:59:56R32

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2019-06-26 Cont ID  
Sent By jgomez Date 2019-06-26 Time 09:46 Rev Time 0.00
Received By jgomez Date 2019-06-20 Time 14:58 Sent To I
Notes
2019-06-20 14:58:36RESUB ROUTED TO JGOMEZ

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2019-05-10 Cont ID  
Sent By jgomez Date 2019-05-10 Time 16:07 Rev Time 0.00
Received By jgomez Date 2019-04-25 Time 15:48 Sent To I
Notes
2019-05-02 11:36:09ROUTED FROM ZONING TO PERMIT LIBRARIAN 5/2/19 EL
  
2019-04-26 15:48:13RESUB ROUTED TO ZONING INBOX

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2019-02-21 Cont ID  
Sent By jgomez Date 2019-02-21 Time 18:12 Rev Time 0.00
Received By jgomez Date 2019-02-05 Time 14:06 Sent To I
Notes
2019-02-13 16:48:00ROUTED FROM ZONING TO PERMIT LIBRARIAN 2/13/2019 EL
2019-02-06 14:06:26RESUB ROUTED TO ZONING INBOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-11-29 Cont ID  
Sent By jesmith Date 2018-11-29 Time 12:48 Rev Time 0.00
Received By jesmith Date 2018-11-29 Time 12:48 Sent To  
Notes
2018-11-14 10:09:57R32
2018-10-23 16:26:43ROUTED FROM ZONING (EL) TO HISTORIC (FM) 10/23/18
2018-10-16 11:14:02LIBRARY

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2020-02-10 Cont ID  
Sent By pvalenti Date 2020-02-10 Time 08:50 Rev Time 0.00
Received By pvalenti Date 2020-02-10 Time 06:32 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2019-11-12 Cont ID  
Sent By cmontell Date 2019-11-12 Time 14:31 Rev Time 0.00
Received By cmontell Date 2019-11-12 Time 14:31 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2019-10-21 Cont ID  
Sent By cmontell Date 2019-10-21 Time 06:11 Rev Time 0.00
Received By cmontell Date 2019-10-21 Time 06:11 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2018-11-15 Cont ID  
Sent By cmontell Date 2018-11-15 Time 13:27 Rev Time 0.00
Received By cmontell Date 2018-11-15 Time 13:12 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status P Date 2019-11-07 Cont ID  
Sent By jesmith Date 2019-11-07 Time 14:39 Rev Time 0.00
Received By jesmith Date 2019-11-07 Time 14:38 Sent To  
Notes
2019-11-07 14:39:1418100648 805 3RD ST
 PLUMBING COMMENTS: APPROVED
 ALL WORK PER STATE AND CITY CODES SUBJECT TO FIELD
 INSPECTOR'S APPROVAL
 SCOPE OF WORK IS LIMITED TO CHANGE OUT OF BATH AND
 KITCHEN FIXTURES ONLY

Review Stop P PLUMBING
Rev No 2 Status P Date 2019-10-17 Cont ID  
Sent By gjohnson Date 2019-10-17 Time 08:36 Rev Time 0.00
Received By gjohnson Date 2019-10-17 Time 08:36 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2018-11-29 Cont ID  
Sent By jesmith Date 2018-11-29 Time 12:47 Rev Time 0.00
Received By jesmith Date 2018-11-29 Time 12:18 Sent To  
Notes
2018-11-29 12:46:15APPROVED
 PLUMBING PROVISO
 1. ALL WORK PER CITY CODES SUBJECT TO FIELD INSPECTOR'S
 APPROVAL
 2. SCOPE OF WORK IS LIMITED TO CHANGE OUT OF BATH AND
 KITCHEN FIXTURES ONLY. CONNECT TO EXISTING PLUMBING
 CONNECTIONS.
 3. SHOWER FLOOR(S) AS DETAILED ON PLAN PAGE A-04
 4. TUB/SHOWER CONTROL VALVE(S) SHALL BE PRESSURE
 BALANCED PB, THERMOSTATIC MIXING (TM) OR COMBINATION
 PB/TM VALVE TYPES WITH HIGH TEMPERATURE LIMITING STOP.
 FBC RES P2708.4
 5. PROVIDE WATER HAMMER ARRESTORS AT WATER SUPPLIES TO
 NEW ICE LINE AND NEW DISHWASHER. FBC RES P2903.5
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 PHONE 561-805-6715

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2020-02-10 Cont ID  
Sent By pvalenti Date 2020-02-10 Time 08:57 Rev Time 0.00
Received By pvalenti Date 2020-02-10 Time 08:57 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2019-11-19 Cont ID  
Sent By shill Date 2019-11-19 Time 17:55 Rev Time 0.00
Received By shill Date 2019-11-19 Time 17:55 Sent To  
Notes
2019-11-19 17:55:47****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 1. THE PLANS SUBMITTED HAVE A PHOTOCOPY SIGNATURE.
 FS471, ORIGINAL REQUIRED. A MEETING WITH THE DESIGN
 PROFESSIONAL IS REQUESTED; HE CAN SIGN THE PLANS AT
 THAT TIME, OR PROVIDE ORIGINALS WHEN RESUBMITTING.
  
  

Review Stop Z ZONING
Rev No 6 Status P Date 2020-02-21 Cont ID  
Sent By elevesqu Date 2020-02-21 Time 16:22 Rev Time 0.00
Received By elevesqu Date 2020-02-21 Time 16:22 Sent To  
Notes
2020-02-21 16:23:39PER EMAIL FROM RAY CARANCI TO RONEN HAZAN OF YAKUT TEAM
 SENT ON 2/21/2020 :
 HOLD IS PUT ON PERMIT FOR CO UNTIL LANDSCAPE PERMIT IS
 SUBMITTED AND APPROVED
  
 LIZ LEVESQUE, URBAN DESIGN PLANNER
 [email protected]
 561 822 1426

Review Stop Z ZONING
Rev No 5 Status F Date 2019-11-18 Cont ID  
Sent By elevesqu Date 2019-11-18 Time 15:20 Rev Time 0.00
Received By elevesqu Date 2019-11-18 Time 15:19 Sent To  
Notes
2019-11-18 15:20:36REPEAT COMMENT:
  
 NEW COMMENTS AS PLANS HAVE CHANGED AND IT HAVE BEEN SO
 LONG SINCE LAST SUMITTAL:
  
  
 STAFF HAS RECOGNIZED THAT THE PROPERTY MUST MEET
 ADDITIONAL LANDSCAPE CRITERIA. PERMITS FOR SINGLE
 FAMILY RESIDENCES, WHERE THE PERMIT VALUE IS OVER 50%
 OF THE IMPROVED LAND VALUE (PER PAPA), MUST BE ABLE TO
 SHOW THAT THEY ARE MEETING THE CRITERIA FOR LANDSCAPING
 FOR SINGLE FAMILY RESIDENCES. THIS PERMIT VALUE MEETS
 THIS REQUIREMENT.
 PLEASE PROVIDE THE FOLLOWING INFORMATION TO RAY
 CARANCI, LANDSCAPE PLANNER:
 PROVIDE A LIST OF THE NUMBER AND SPECIES OF TREES ON
 SITE
 PROVIDE A LIST OF THE AMOUNT (LENGTH) AND SPECIES OF
 SHRUBS ON SITE
  
 IF CURRENT LANDSCAPING DOES NOT MEET CURRENT CODE, A
 LANDSCAPE PERMIT WILL BE REQUIRED. ZONING CANNOT PASS
 PERMIT UNTIL IT IS VERIFIED THAT THE SITE MEETS
 LANDSCAPE CODE, OR UNTIL A LANDSCAPE PERMIT IS SUMITTED
 (IF NEEDED)
  
 LANDSCAPE CODE FOR SINGLE FAMILY DWELLING UNITS IS AS
 FOLLOWS:
  
 (2)GENERAL LANDSCAPING STANDARDS FOR SINGLE-FAMILY
 DWELLING UNITS AND ALL OTHER DEVELOPMENTS . GENERAL
 LANDSCAPING STANDARDS FOR SINGLE-FAMILY DWELLING UNITS
 AND ALL OTHER DEVELOPMENTS SHALL BE AS
 FOLLOWS:A.SINGLE-FAMILY DWELLING UNITS . FOR
 SINGLE-FAMILY AND DUPLEX DWELLING UNITS, AT LEAST ONE
 SHADE OR FLOWERING TREE SHALL BE PLANTED FOR EACH 1,000
 SQUARE FEET OF OPEN SPACE OR PORTION THEREOF. AT LEAST
 ONE SHRUB SHALL BE PLANTED FOR EACH 500 SQUARE FEET OF
 OPEN SPACE OR PORTION THEREOF. FRONT YARDS SHALL BE
 LANDSCAPED TO MEET THE REQUIREMENTS OF SECTION
 94-482(A).
 94-482(A): LOCATION AND SURFACE. REQUIRED OFF-STREET
 PARKING SPACES FOR LESS THAN THREE RESIDENTIAL DWELLING
 UNITS SHALL BE PROVIDED ON THE PROPERTY ON WHICH THE
 UNITS ARE LOCATED. REQUIRED PARKING MAY BE LOCATED IN A
 FRONT YARD; HOWEVER, THE LESSER OF 1,000 SQUARE FEET OR
 75 PERCENT OF THE FRONT YARD AREA SHALL BE LANDSCAPED
 WITH LIVING PLANT MATERIAL (SUCH AS GRASS, GROUND
 COVER, SHRUBS, HEDGES, VINES OR TREES).
  
 PLEASE CONTACT RAY CARANCI AT [email protected] OR AT
 561-822-1462
  
  
  
 LIZ LEVESQUE, URBAN DESIGN PLANNER
 [email protected]
 561 822 1426

Review Stop Z ZONING
Rev No 4 Status F Date 2019-10-10 Cont ID  
Sent By elevesqu Date 2019-10-10 Time 15:59 Rev Time 0.00
Received By elevesqu Date 2019-10-10 Time 15:59 Sent To  
Notes
2019-10-10 16:26:02NEW COMMENTS AS PLANS HAVE CHANGED AND IT HAVE BEEN SO
 LONG SINCE LAST SUMITTAL:
  
  
 1. SCOPE OF WORK HAS NOT CHANGED - STILL MODIFICATIONS
 TO DUPLEX BUT ALL PLANS FOR THE DUPLEX HAVE BEEN
 REMOVED.
 ARE RENOVATIONS ONLY OCCURING TO THE MAIN HOUSE? IF
 RENOVATIONS STILL OCCURING TO DUPLEX, FULL PLANS NEED
 TO BE SUBMITTED.
  
 2. THE ADDRESS FOR THIS PROJECT IS 805 3RD STREET, NOT
 803 3RD STREET. PLEASE FIX ON ALL PLANS THAT SAY "803
 3RD STREET"
  
 3. STAFF HAS RECOGNIZED THAT THE PROPERTY MUST MEET
 ADDITIONAL LANDSCAPE CRITERIA. PERMITS FOR SINGLE
 FAMILY RESIDENCES, WHERE THE PERMIT VALUE IS OVER 50%
 OF THE IMPROVED LAND VALUE (PER PAPA), MUST BE ABLE TO
 SHOW THAT THEY ARE MEETING THE CRITERIA FOR LANDSCAPING
 FOR SINGLE FAMILY RESIDENCES. THIS PERMIT VALUE MEETS
 THIS REQUIREMENT.
 PLEASE PROVIDE THE FOLLOWING INFORMATION TO RAY
 CARANCI, LANDSCAPE PLANNER:
 PROVIDE A LIST OF THE NUMBER AND SPECIES OF TREES ON
 SITE
 PROVIDE A LIST OF THE AMOUNT (LENGTH) AND SPECIES OF
 SHRUBS ON SITE
  
 IF CURRENT LANDSCAPING DOES NOT MEET CURRENT CODE, A
 LANDSCAPE PERMIT WILL BE REQUIRED. ZONING CANNOT PASS
 PERMIT UNTIL IT IS VERIFIED THAT THE SITE MEETS
 LANDSCAPE CODE, OR UNTIL A LANDSCAPE PERMIT IS SUMITTED
 (IF NEEDED)
  
 LANDSCAPE CODE FOR SINGLE FAMILY DWELLING UNITS IS AS
 FOLLOWS:
  
 (2)GENERAL LANDSCAPING STANDARDS FOR SINGLE-FAMILY
 DWELLING UNITS AND ALL OTHER DEVELOPMENTS . GENERAL
 LANDSCAPING STANDARDS FOR SINGLE-FAMILY DWELLING UNITS
 AND ALL OTHER DEVELOPMENTS SHALL BE AS
 FOLLOWS:A.SINGLE-FAMILY DWELLING UNITS . FOR
 SINGLE-FAMILY AND DUPLEX DWELLING UNITS, AT LEAST ONE
 SHADE OR FLOWERING TREE SHALL BE PLANTED FOR EACH 1,000
 SQUARE FEET OF OPEN SPACE OR PORTION THEREOF. AT LEAST
 ONE SHRUB SHALL BE PLANTED FOR EACH 500 SQUARE FEET OF
 OPEN SPACE OR PORTION THEREOF. FRONT YARDS SHALL BE
 LANDSCAPED TO MEET THE REQUIREMENTS OF SECTION
 94-482(A).
 94-482(A): LOCATION AND SURFACE. REQUIRED OFF-STREET
 PARKING SPACES FOR LESS THAN THREE RESIDENTIAL DWELLING
 UNITS SHALL BE PROVIDED ON THE PROPERTY ON WHICH THE
 UNITS ARE LOCATED. REQUIRED PARKING MAY BE LOCATED IN A
 FRONT YARD; HOWEVER, THE LESSER OF 1,000 SQUARE FEET OR
 75 PERCENT OF THE FRONT YARD AREA SHALL BE LANDSCAPED
 WITH LIVING PLANT MATERIAL (SUCH AS GRASS, GROUND
 COVER, SHRUBS, HEDGES, VINES OR TREES).
  
 PLEASE CONTACT RAY CARANCI AT [email protected] OR AT
 561-822-1462
  
  
  
 LIZ LEVESQUE, URBAN DESIGN PLANNER
 [email protected]
 561 822 1426

Review Stop Z ZONING
Rev No 3 Status P Date 2019-05-02 Cont ID  
Sent By elevesqu Date 2019-05-02 Time 11:36 Rev Time 0.00
Received By elevesqu Date 2019-05-02 Time 11:36 Sent To B
Notes
2019-05-02 11:35:51PROVISO: MECHANICAL EQUIPMENT SHALL BE OUTSIDE OF 5'
 SIDE SETBACK
  
 LIZ LEVESQUE, URBAN DESIGN PLANNER
 [email protected]
 561 822 1426

Review Stop Z ZONING
Rev No 2 Status P Date 2019-02-13 Cont ID  
Sent By elevesqu Date 2019-02-13 Time 16:46 Rev Time 0.00
Received By elevesqu Date 2019-02-13 Time 16:46 Sent To B
Notes
2019-02-13 16:47:13PROVISO: MECHANICAL EQUIPMENT TO BE LOCATED OUTSIDE OF
 5' SIDE SETBACK
  
 LIZ LEVESQUE, URBAN DESIGN PLANNER
 561 822 1426
 [email protected]

Review Stop Z ZONING
Rev No 1 Status F Date 2018-10-23 Cont ID  
Sent By elevesqu Date 2018-10-23 Time 16:22 Rev Time 0.00
Received By elevesqu Date 2018-10-23 Time 16:22 Sent To  
Notes
2018-10-23 16:22:46PLEASE PROVIDE SITE PLAN SHOWING PROPERTY BOUNDARIES
 WITH EXISTING/PROPOSED STRUCTURES.
  
 PLEASE INDICATE SETBACK OF MECHANICAL EQUIPMENT FROM
 PROPERTY LINES. MECHANICAL EQUIPMENT CAN ENCROACH NO
 MORE THAN FOUR FEET INTO REQUIRED SETBACKS.
 THE REQUIRED SIDE SETBACK FOR THIS PROPERTY IS MINIMUM
 5 FEET, SO THE MECHANICAL EQUIPMENT MUST BE AT LEAST
 ONE FOOT AWAY FROM THE SIDE PROPERTY LINE.
  
 PLEASE INDICATE WHAT THE RED HATCHED AREA ALONG THE
 WEST SIDE OF THE ONE STORY RESIDENCE IS.
  
 PLEASE REFER TO HISTORICAL REVIEW STOP FOR ANY OTHER
 ZONING COMMENTS.
  
 LIZ LEVESQUE, URBAN DESIGN PLANNER
 [email protected]
  
  
 561 822 1426


Account Summary | Usage Policy | Privacy Policy