Plan Review Details - Permit 18100540
Plan Review Stops For Permit 18100540
Review Stop AD ADDRESSING
Rev No 6 Status P Date 2021-09-08 Cont ID  
Sent By cpuell Date 2021-09-08 Time 08:56 Rev Time 0.00
Received By cpuell Date 2021-09-08 Time 08:56 Sent To  
Notes
2021-09-08 08:59:29ADDRESS APPROVED AS FOLLOWS:
  
 500 N QUADRILLE BLVD - PRIMARY ADDRESS
 550 N QUADRILLE BLVD - OFFICE BLDG MAIN ENTRANCE
 570 N QUADRILLE BLVD - DAYCARE
 415 4TH ST - RETAIL
 445 4TH ST - EVENT AREA
 455 4TH ST - EVENT AREA
 465 4TH ST - HOTEL MAIN ENTRANCE
 525 N DIXIE HWY - RETAIL
 551 N DIXIE HWY - TENNIS LOBBY
 555 N DIXIE HWY - CONDOS MAIN ENTRANCE

Review Stop AD ADDRESSING
Rev No 5 Status F Date 2021-08-13 Cont ID  
Sent By cpuell Date 2021-08-13 Time 08:28 Rev Time 0.00
Received By cpuell Date 2021-08-13 Time 08:28 Sent To  
Notes
2021-08-13 08:29:47EMAILED CUSTOMER, EXPLAINED THAT ADDRESSES NEED TO BE
 ASSIGNED FOR THE DIFFERENT SPACES, ASKED THEM TO CONTAT
 ME SO WE CAN WORK THROUGH IT. PLEASE CONTACT
 [email protected] OR CALL 561-805-6659

Review Stop AD ADDRESSING
Rev No 4 Status F Date 2021-05-18 Cont ID  
Sent By cpuell Date 2021-05-18 Time 10:14 Rev Time 0.00
Received By cpuell Date 2021-05-18 Time 10:14 Sent To  
Notes
2021-05-18 10:14:56CONTACTED CUSTOMER, WAITING ON RESPONCE. PLEASE EMAIL
 [email protected]

Review Stop AD ADDRESSING
Rev No 3 Status F Date 2021-01-26 Cont ID  
Sent By cpuell Date 2021-01-26 Time 10:02 Rev Time 0.00
Received By cpuell Date 2021-01-26 Time 10:02 Sent To  
Notes
2021-01-26 10:06:18REACHED OUT TO APPLICANT ON 2/19/20 ASKING FOR THEM TO
 PROVIDE A PLAN SHOWING THE DIFFERENT ENTRANCES TO THE
 PROPERTY AND IF THEY ARE FOR INDIVIDUAL UNITS. ALL THE
 OFFICES, HOTEL, APARTMENTS AND RETAIL WILL NEED TO BE
 ALLOCATED AN ADDRESS, I WOULD LIKE TO COMMENCE WORKING
 ON THEM BEFORE THE PERMIT IS ISSUED, SO THAT THE PERMIT
 IS ISSUED WITH THE CORRECT ADDRESS. PLEASE CONTACT
 [email protected] AND EMAIL REQUIRED DOCUMENTATION.

Review Stop AD ADDRESSING
Rev No 2 Status F Date 2020-03-19 Cont ID  
Sent By cpuell Date 2020-03-19 Time 10:23 Rev Time 0.00
Received By cpuell Date 2020-02-19 Time 11:19 Sent To  
Notes
2020-02-19 11:20:02CONTACTED CUSTOMER, WAITING ON RESPONCE. PLEASE EMAIL
 [email protected]

Review Stop AD ADDRESSING
Rev No 1 Status F Date 2019-04-04 Cont ID  
Sent By shill Date 2019-04-04 Time 05:04 Rev Time 0.00
Received By shill Date 2019-04-04 Time 05:04 Sent To  
Notes
2019-04-04 05:04:47FOR ADDRESSING, PLEASE CONTACT (PREFERABLY VIA EMAIL):
  
 MICHAEL ORIO
 GIS SUPPORT SPECIALIST
 [email protected]
 CITY OF WEST PALM BEACH
 INFORMATION TECHNOLOGY DEPARTMENT
 401 CLEMATIS STREET, WEST PALM BEACH, FLORIDA 33401
 P: 561.494.1080
  
  

Review Stop AIPP ART IN PUBLIC PLACES
Rev No 1 Status P Date   Cont ID  
Sent By   Date 2021-09-08 Time   Rev Time 0.00
Received By   Date 2021-09-08 Time   Sent To  
Notes
2021-09-08 15:11:17**PROVISO** PROVIDED TO MY ATTENTION WITHIN 10 BUSINESS
 DAYS.
  
 MISSING:
  
 1. ARTIST'S QUALIFICATIONS- THIS IS FOR THE RECORD ?
 CV/BIO/WEBSITE
  
 2. DETAILED DESCRIPTION AND DEPICTION OF THE ARTWORK,
 INCLUDING CONCEPTUAL APPROACH AND RELEVANT DESIGN
 INFORMATION.
  
 3. DRAWINGS AND RENDERINGS OF THE PROPOSED ARTWORK, IN
 TERMS OF SIZE, SCALE, COLOR, SHAPE, AND MATERIALS IN
 SUFFICIENT DETAIL TO PROVIDE A CLEAR UNDERSTANDING OF
 THE ART OR ELEMENTS PROPOSED.
 4. DRAWINGS AND RENDERINGS SHALL BE TO SCALE, AT THE
 PROPOSED LOCATION(S) ON SITE PLAN - SHOW SURROUNDING
 LANDSCAPING, BUILDINGS, LIGHTING, PUBLIC RIGHT-OF-WAY,
 PLAQUE PLACEMENT, PARKING, FRONTAGE, AND ANY OTHER
 INFORMATION RELEVANT TO THE SITE AND PLACEMENT.
  
 5. MATERIALS AND METHOD DESCRIPTION INCLUDING ALL
 PROPOSED MATERIALS AND INSTALLATION
  
 6. SCHEDULE. PROPOSED PROJECT SCHEDULE AND PROJECT
 DEVELOPMENT TIMELINES, INCLUDING CITY REVIEWS AND
 ARTWORK INSTALLATION SCHEDULE.
  
 BY CITY CODE THE ARTWORK MUST BE REVIEWED BY THE
 ARTLIFE (PUBLIC ART) COMMITTEE AND BE RECOMMENDED TO
 CITY COMMISSION BEFORE ARTIST MAY BEGIN PRODUCTION.
  
 ALLOW TWO MONTHS FOR REVIEW PROCESS. ALLOW 15 TO 18
 MONTHS FOR PRODUCTION/FABRICATION FROM AN ARTIST
 STUDIO.
  
 CALL ME WITH ANY QUESTIONS.
  
 SYBILLE
  
 SYBILLE WELTER
 ADMINISTRATOR OF PUBLIC ART AND CULTURE
 CITY OF WEST PALM BEACH
  
 PUBLIC ART FOR AN INSPIRED CITY
 401 CLEMATIS STREET
 WEST PALM BEACH, FL 33401
 DIRECT: 561.822.1521
 [email protected]
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 6 Status P Date 2021-09-03 Cont ID  
Sent By rmcdouga Date 2021-09-03 Time 17:14 Rev Time 0.00
Received By rmcdouga Date 2021-09-03 Time 15:36 Sent To  
Notes
2021-09-03 17:14:26DEFERRED SUBMITTALS
 SEE SHEET A0.001 FOR LIST OF DEFERRED ITEMS.
 PER THE DESIGNER THE SALES AND SERVICE COUNTERS
 DRAWINGS AND DETAILS WILL BE PROVIDED FOR APPROVAL AT A
 LATER DATE.
  
 NOTE: SEPARATE PERMITS (APPLICATIONS, PLANS, AND FEES)
 ARE REQUIRED FOR:
 LIGHT POLES/SITE LIGHTING
 FIRE ALARM
 FIRE SPRINKLER
 LOW VOLTAGE
 ACCESS
 LANDSCAPING
 IRRIGATION
 PARKING LOT
 SWIMMING POOLS AND SPAS - THE POOL DRAWINGS
 13.001-SP.001 THRU 13.033-SP.750 ARE NOT LISTED IN THE
 INDEX OF PLANS. SEPARATE POOL/SPA PERMITS WILL BE
 REQUIRED FOR THE (3) POOLS/SPAS.
 GENERATORS
 ALL OTHER ITEMS OTHER THAN BMEP
  
  
  
  
  
  
  
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status F Date 2021-08-24 Cont ID  
Sent By rmcdouga Date 2021-08-24 Time 17:09 Rev Time 0.00
Received By rmcdouga Date 2021-08-23 Time 15:50 Sent To  
Notes
2021-08-24 17:08:58BUILDING REVIEW COMMENTS:
  
 W.P.B. PERMIT: 18100540
 550 N. QUADRILLE BLVD.
 BUILDING PERMIT 30 STORY BLDG W/ TWO TOWERS
 CONSTRUCTION TYPE: 1A, SPRINKLERED
 MIXED OCCUPANCY: B, R-1, R-2, A-2, A4, S-2, M, E
  
 1 ST REVIEW: APRIL 18, 2019 - DYLAN BATTLES
 2 ND REVIEW: MARCH 2, 2020 - DYLAN BATTLES
 3 RD REVIEW: JANUARY 13, 2021 - ROBERT MCDOUGAL
 4 TH REVIEW: JUNE 10, 2021 - ROBERT MCDOUGAL
 5 TH REVIEW: AUGUST 23, 2021 - ROBERT MCDOUGAL
  
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 FLORIDA BUILDING CODE,5TH EDITION (2014)
 FBC[AMENDED] = 2014 CHAPTER 1 WPB AMENDMENTS (SEE LINK
 BELOW)
 HTTPS://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/
 BUILDING-PERMIT-FORMS
 FBC[B] = FBC BUILDING
 FBC[A] = FBC ACCESSIBILITY
 FBC[E] = FBC ENERGY CONSERVATION
  
  
 BUILDING REVIEW COMMENTS:
  
 1) RESOLVED.
  
 A) RESOLVED.
  
 B) RESOLVED.
  
 C) RESOLVED.
  
 D) RESOLVED.
  
 E) RESOLVED.
  
 F) RESOLVED.
  
 G) RESOLVED.
  
 H) RESOLVED.
  
 2) RESOLVED.
  
 3) RESOLVED.
  
 4) RESOLVED.
  
 5) RESOLVED.
  
 6) RESOLVED.
  
 FAIRHOUSING REVIEW:
  
 7) RESOLVED.
  
 A) RESOLVED.
  
 B) RESOLVED.
  
 C) RESOLVED.
  
 D) RESOLVED.
  
 E) RESOLVED.
  
 F) RESOLVED.
  
 LIFE SAFETY:
  
 8) RESOLVED.
  
 9) RESOLVED.
  
 10) RESOLVED.
  
 11) RESOLVED.
  
 12) RESOLVED.
  
 13) RESOLVED.
  
 14) RESOLVED.
  
 15) RESOLVED.
  
 16) NOT COMPLETELY RESOLVED. [RAMP 4 STILL DOES NOT
 COMPLY.] [ RAMP 4 ON A1.228 IS REQUIRED TO HAVE A
 LANDING WITH 60" X 60" CLEAR SPACE AT THE CHANGE IN
 DIRECTION. RAMP 8 ON 5.123 REQUIRES A 60" (5') CLEAR
 LANDING AND THE DRAWING HAS 59" (4'-11"). FBC-A 405.7]
 THERE ARE SEVERAL RAMPS SHOWN ON THE PLANS. PLEASE
 IDENTIFY EACH WITH AN ID TAG AND PROVIDE DETAILS FOR
 EACH OF THEM TO SHOW THAT THEY MEET THE ACCESSIBILITY
 REQUIREMENTS FOR RAMPS. FBC ACCESSIBILITY 405. 1003.5
 FBC[B] ELEVATION CHANGE. DOES EXIT FROM RESIDENT LOBBY
 TO STAIR 2 HAVE STEPS? PLEASE REVIEW
 -HOW DO STEPS WORK AT EGRESS FROM RESIDENT LOUNGE TO
 STAIR ST2? PLEASE REVIEW 1003.5 FOR CHANGE IN ELEVATION
 IN PATH OF EGRESS.
  
 17) RESOLVED.
  
 18) RESOLVED.
  
 19) RESOLVED.
  
 20) RESOLVED.
  
 DEFERRED SUBMITTALS
 21) RESOLVED. SEE SHEET A0.001 FOR LIST OF DEFERRED
 ITEMS.
  
 22) DEFERRED.
  
 23) RESOLVED.
  
 ACCESSIBILITY REVIEW:
  
 24) RESOLVED.
  
 25) RESOLVED.
  
 26) RESOLVED. THE POOL DRAWINGS 13.001-SP.001 THRU
 13.033-SP.750 ARE NOT LISTED IN THE INDEX OF PLANS.
 SEPARATE POOL/SPA PERMITS WILL BE REQUIRED FOR THE (3)
 POOLS/SPAS.
  
 27) RESOLVED.
  
 CHAPTER 4 - HIGHRISE:
  
 28) RESOLVED.
  
 29) RESOLVED.
  
 30) RESOLVED. BUILDING IS LESS THAN 420 FEET IN HEIGHT.
  
 NEW COMMENTS:
  
 31) RESOLVED.
  
 32) RESOLVED.
  
 33) RESOLVED.
  
 34) RESOLVED.
  
 35) NOT RESOLVED. [THE EXITS STILL DO NOT COMPLY.] [
 BASED ON THE NUMBERS THAT YOU HAVE PROVIDED (487 OCC.)
 THE CAPACITY OF THE TWO EXISTS THAT ARE PROVIDED ARE
 NOT ADEQUATE FOR THE OCCUPANT LOAD OF THIS AREA. SEE
 FBC SECTIONS 1004, 1005 AND 1006. FBC 1005.5
 DISTRIBUTION OF EGRESS CAPACITY WHERE MORE THAN ONE
 EXIT, OR ACCESS TO MORE THAN ONE EXIT, IS REQUIRED, THE
 MEANS OF EGRESS SHALL BE CONFIGURED SUCH THAT THE LOSS
 OF ANY ONE EXIT, OR ACCESS TO ONE EXIT, SHALL NOT
 REDUCE THE AVAILABLE CAPACITY TO LESS THAN 50 PERCENT
 OF THE REQUIRED CAPACITY. CHECK THE AREA AND OCCUPANT
 LOAD AND PROVIDE CODE COMPLIANT EGRESS. ]
 ON PAGE 04.024 -ALS1.109, SHOW THE TOTAL OCCUPANT LOAD
 OF THE TERRACE AND PICKLE BALL COURTS, THE LOADS AT
 EACH EXIT DOOR AND THE COMBINED LOADS AT THE HOTEL AND
 RESIDENT EXIT STAIRWAYS. FBC 1004
  
 36) RESOLVED.
  
 37) RESOLVED.
  
 38) RESOLVED.
  
 39) RESOLVED.
  
 40) RESOLVED.
  
 41) RESOLVED.
  
 42) RESOLVED.
  
 43) DEFERRED. PER THE DESIGNER THE SALES AND SERVICE
 COUNTERS DRAWINGS AND DETAILS WILL BE PROVIDED FOR
 APPROVAL AT A LATER DATE. NOT RESOLVED. [THE ONLY PLAN
 SHEET I SAW WAS ID7.010 SUBMITTED AS AN ATTACHED
 SUPPLEMENTAL DOCUMENT. IT ONLY HAS THE RECEPTION DESKS
 FOR THE HOTEL AND THE RESIDENTIAL UNITS. SALES AND
 SERVICE COUNTERS ARE REQUIRED TO COMPLY WITH
 FBC-ACCESSIBILITY 904.4 SALES COUNTERS AND SERVICE
 COUNTERS SHALL COMPLY WITH 904.4.1 OR 904.4.2. THE
 ACCESSIBLE PORTION OF THE COUNTER TOP SHALL EXTEND THE
 SAME DEPTH AS THE SALES OR SERVICE COUNTER TOP. THE
 SHEET IS NOT SIGNED AND SEALED. WHAT ABOUT THE OTHER
 COMMON AREA ITEMS?] I DID NOT SEE THE
 DETAILS/ELEVATIONS OF BUILT-IN ITEMS IN THE COMMON USE
 AREAS, SUCH AS RECEPTION DESKS, SERVICE COUNTERS, BREAK
 ROOM KITCHENS, ETC. THAT ARE REQUIRED TO BE ACCESSIBLE
 PER FBC ACCESSIBILITY CHAPTERS 8 AND 9. PLEASE INDICATE
 SHEETS THEY ARE ON OR PROVIDE SHEETS WITH DETAILS AND
 ELEVATIONS FOR THESE ITEMS.
  
 44) NOTE: ADDITIONAL COMMENTS MAY RESULT FROM THE
 RESPONSES TO THESE PLAN REVIEW COMMENTS.
  
 -PROVIDE COMMENT RESPONSE SHEET TO EXPLAIN HOW EACH
 COMMENT IS BEING ADDRESSED.
 -FEEL FREE TO CONTACT ME AT 561-805-6714 (M-F 8-5) TO
 DISCUSS COMMENTS, OR E-MAIL ANYTIME [email protected]
  
 NOTE: SEPARATE PERMITS (APPLICATIONS, PLANS, AND FEES)
 ARE REQUIRED FOR:
 LIGHT POLES/SITE LIGHTING
 FIRE ALARM
 FIRE SPRINKLER
 LOW VOLTAGE
 ACCESS
 LANDSCAPING
 IRRIGATION
 PARKING LOT
 SWIMMING POOLS AND SPAS
 GENERATORS
 ALL OTHER ITEMS OTHER THAN BMEP
  
  
  
  
  
  
  
  
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2021-06-21 Cont ID  
Sent By rmcdouga Date 2021-06-21 Time 11:51 Rev Time 0.00
Received By rmcdouga Date 2021-06-10 Time 10:01 Sent To  
Notes
2021-06-10 10:09:35BUILDING REVIEW COMMENTS:
  
 W.P.B. PERMIT: 18100540
 550 N. QUADRILLE BLVD.
 BUILDING PERMIT 30 STORY BLDG W/ TWO TOWERS
 CONSTRUCTION TYPE: 1A, SPRINKLERED
 MIXED OCCUPANCY: B, R-1, R-2, A-2, A4, S-2, M, E
  
 1 ST REVIEW: APRIL 18, 2019 - DYLAN BATTLES
 2 ND REVIEW: MARCH 2, 2020 - DYLAN BATTLES
 3 RD REVIEW: JANUARY 13, 2021 - ROBERT MCDOUGAL
 4 TH REVIEW: JUNE 10, 2021 - ROBERT MCDOUGAL
  
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 FLORIDA BUILDING CODE,5TH EDITION (2014)
 FBC[AMENDED] = 2014 CHAPTER 1 WPB AMENDMENTS (SEE LINK
 BELOW)
 HTTPS://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/
 BUILDING-PERMIT-FORMS
 FBC[B] = FBC BUILDING
 FBC[A] = FBC ACCESSIBILITY
 FBC[E] = FBC ENERGY CONSERVATION
  
  
 BUILDING REVIEW COMMENTS:
  
 1) RESOLVED.
  
 A) RESOLVED.
  
 B) RESOLVED.
  
 C) RESOLVED.
  
 D) RESOLVED.
  
 E) RESOLVED.
  
 F) RESOLVED.
  
 G) RESOLVED.
  
 H) RESOLVED.
  
 2) RESOLVED.
  
 3) RESOLVED.
  
 4) RESOLVED.
  
 5) RESOLVED.
  
 6) RESOLVED.
  
 FAIRHOUSING REVIEW:
  
 7) RESOLVED.
  
 A) PARTIALLY RESOLVED. [ UNIT B-1 ON SHEET A1.524, DOES
 NOT APPEAR TO COMPLY WITH FAIR HOUSING SPECIFICATION B
 BATHROOMS. THE ACCESS TO THE BATHTUB CONTROLS CAN NOT
 BE OBSTRUCTED BY THE TOILET OR VANITY IN ONE OF THE
 BATHROOMS IN ORDER TO BE A SPECIFICATION B. ] THE TUBS
 PAGE 03.097(A1.519) THE MASTER BATH TOILET IN
 RESIDENTIAL UNIT S8 DOES NOT APPEAR TO COMPLY WITH A
 TYPE B BATHROOM. ON PAGE 03.102(A1.524) RESIDENTIAL
 UNIT B1 HAS ONE BATH ROOM MARKED AS TYPE A AND THE
 OTHER AS TYPE B. THE UNIT CAN ONLY BE ONE TYPE. ON PAGE
 03.104(A1.526) SHOW THE REQUIRED CLEAR FLOOR SPACE AT
 THE TOILET IN UNIT B3.1. IT WOULD BE HELPFUL TO ADD A
 MATRIX OF ROOMS ON SHEET A1.500 WHICH BATHROOM SPEC IS
 BEING USED AND APPLY THE FOLLOWING FOR SPEC A AND B
  
 SPECIFICATION A:
 IF SPECIFICATION A IS USED IT APPLIES TO ALL BATHROOMS,
 AND ALL FIXTURES IN THOSE BATHROOMS MUST BE USABLE. ALL
 BATHROOMS IN THAT UNIT ARE REQUIRED TO MEET THE
 SPECIFICATION A REQUIREMENTS.
 SPECIFICATION B:
 IF SPECIFICATION B IS USED, IT APPLIES TO ONE BATHROOM,
 AND ONLY ONE OF EACH TYPE OF FIXTURE MUST BE USABLE;
 ADDITIONAL BATHROOMS IN THE UNIT ARE EXEMPT ONLY FROM
 MANEUVERING AND CLEAR FLOOR SPACE REQUIREMENTS AT
 FIXTURES.
  
 B) RESOLVED.
  
 C) RESOLVED.
  
 D) RESOLVED.
  
 E) RESOLVED.
  
 F) RESOLVED.
  
 LIFE SAFETY:
  
 8) RESOLVED.
  
 9) RESOLVED.
  
 10) RESOLVED.
  
 11) RESOLVED.
  
 12) RESOLVED.
  
 13) RESOLVED.
  
 14) RESOLVED.
  
 15) RESOLVED.
  
 16) NOT COMPLETELY RESOLVED. [ RAMP 4 ON A1.228 IS
 REQUIRED TO HAVE A LANDING WITH 60" X 60" CLEAR SPACE
 AT THE CHANGE IN DIRECTION. RAMP 8 ON 5.123 REQUIRES A
 60" (5') CLEAR LANDING AND THE DRAWING HAS 59"
 (4'-11"). FBC-A 405.7] THERE ARE SEVERAL RAMPS SHOWN ON
 THE PLANS. PLEASE IDENTIFY EACH WITH AN ID TAG AND
 PROVIDE DETAILS FOR EACH OF THEM TO SHOW THAT THEY MEET
 THE ACCESSIBILITY REQUIREMENTS FOR RAMPS. FBC
 ACCESSIBILITY 405. 1003.5 FBC[B] ELEVATION CHANGE. DOES
 EXIT FROM RESIDENT LOBBY TO STAIR 2 HAVE STEPS? PLEASE
 REVIEW
 -HOW DO STEPS WORK AT EGRESS FROM RESIDENT LOUNGE TO
 STAIR ST2? PLEASE REVIEW 1003.5 FOR CHANGE IN ELEVATION
 IN PATH OF EGRESS.
  
 17) RESOLVED.
  
 18) RESOLVED.
  
 19) RESOLVED.
  
 20) RESOLVED.
  
 DEFERRED SUBMITTALS
 21) RESOLVED. SEE SHEET A0.001 FOR LIST OF DEFERRED
 ITEMS.
  
 22) DEFERRED.
  
 23) RESOLVED.
  
 ACCESSIBILITY REVIEW:
  
 24) RESOLVED.
  
 25) RESOLVED.
  
 26) RESOLVED. THE POOL DRAWINGS 13.001-SP.001 THRU
 13.033-SP.750 ARE NOT LISTED IN THE INDEX OF PLANS.
 SEPARATE POOL/SPA PERMITS WILL BE REQUIRED FOR THE (3)
 POOLS/SPAS.
  
 27) RESOLVED.
  
 CHAPTER 4 - HIGHRISE:
  
 28) RESOLVED.
  
 29) RESOLVED.
  
 30) NOT RESOLVED. [ RESPONSE TO COMMENT STATES THAT IT
 HAS BEEN DETERMINED THAT NEITHER BUILDING EXCEEDS 420'
 IN HEIGHT THUS THE REQUIREMENTS OF FBC 403.3.1 ARE NOT
 APPLICABLE. PLEASE PROVIDE DETAILS OF HOW THIS WAS
 DETERMINED. THE FBC DEFINES BUILDING HEIGHT AS THE
 VERTICAL DISTANCE FROM GRADE PLAIN TO THE AVERAGE
 HEIGHT OF THE HIGHEST ROOF SURFACE. THE DEFINITION OF
 GRADE PLANE IS A REFERENCE PLANE REPRESENTING THE
 AVERAGE OF FINISHED GROUND LEVEL ADJOINING THE BUILDING
 AT THE EXTERIOR WALLS. THE PLAN ELEVATIONS SHOW THAT
 THE HIGH ROOF OF THE OFFICE BUILDING IS 437'-0"NAVD AND
 THE AVERAGE GRADE AT THE BUILDING IS AROUND 15' NAVD.
 THIS WOULD MEAN THAT THE BUILDING HEIGHT IS 437' - 15'
 OR 422'. ] ADD NOTES TO PAGE 10.001 SHEET FR.001 THAT
 SPECIFY THAT A MINIMUM OF TWO RISERS WILL BE PROVIDED
 AND THAT EACH RISER SHALL SUPPLY SPRINKLERS ON
 ALTERNATE FLOORS. 403.3.1 FBC[B]NUMBER OF SPRINKLER
 RISERS AND SYSTEM DESIGN. EACH SPRINKLER SYSTEM ZONE IN
 BUILDINGS THAT ARE MORE THAN 420 FEET (128 000 MM) IN
 BUILDING HEIGHT SHALL BE SUPPLIED BY NO FEWER THAN TWO
 RISERS. EACH RISER SHALL SUPPLY SPRINKLERS ON ALTERNATE
 FLOORS. IF MORE THAN TWO RISERS ARE PROVIDED FOR A
 ZONE, SPRINKLERS ON ADJACENT FLOORS SHALL NOT BE
 SUPPLIED FROM THE SAME RISER.
 -PLEASE SEE HOW THIS APPLIES TO OFFICE TOWER ONLY AND
 UPDATE FS DRAWINGS AS APPLICABLE.
  
 NEW COMMENTS:
  
 31) RESOLVED.
  
 32) RESOLVED.
  
 33) RESOLVED.
  
 34) RESOLVED.
  
 35) NOT RESOLVED. [ BASED ON THE NUMBERS THAT YOU HAVE
 PROVIDED (487 OCC.) THE CAPACITY OF THE TWO EXISTS THAT
 ARE PROVIDED ARE NOT ADEQUATE FOR THE OCCUPANT LOAD OF
 THIS AREA. SEE FBC SECTIONS 1004, 1005 AND 1006. FBC
 1005.5 DISTRIBUTION OF EGRESS CAPACITY WHERE MORE THAN
 ONE EXIT, OR ACCESS TO MORE THAN ONE EXIT, IS REQUIRED,
 THE MEANS OF EGRESS SHALL BE CONFIGURED SUCH THAT THE
 LOSS OF ANY ONE EXIT, OR ACCESS TO ONE EXIT, SHALL NOT
 REDUCE THE AVAILABLE CAPACITY TO LESS THAN 50 PERCENT
 OF THE REQUIRED CAPACITY. CHECK THE AREA AND OCCUPANT
 LOAD AND PROVIDE CODE COMPLIANT EGRESS. ]
 ON PAGE 04.024 -ALS1.109, SHOW THE TOTAL OCCUPANT LOAD
 OF THE TERRACE AND PICKLE BALL COURTS, THE LOADS AT
 EACH EXIT DOOR AND THE COMBINED LOADS AT THE HOTEL AND
 RESIDENT EXIT STAIRWAYS. FBC 1004
  
 36) RESOLVED.
  
 37) RESOLVED.
  
 38) RESOLVED.
  
 39) RESOLVED.
  
 40) RESOLVED.
  
 41) RESOLVED.
  
 42) RESOLVED.
  
 43) NOT RESOLVED. [THE ONLY PLAN SHEET I SAW WAS
 ID7.010 SUBMITTED AS AN ATTACHED SUPPLEMENTAL DOCUMENT.
 IT ONLY HAS THE RECEPTION DESKS FOR THE HOTEL AND THE
 RESIDENTIAL UNITS. SALES AND SERVICE COUNTERS ARE
 REQUIRED TO COMPLY WITH FBC-ACCESSIBILITY 904.4 SALES
 COUNTERS AND SERVICE COUNTERS SHALL COMPLY WITH 904.4.1
 OR 904.4.2. THE ACCESSIBLE PORTION OF THE COUNTER TOP
 SHALL EXTEND THE SAME DEPTH AS THE SALES OR SERVICE
 COUNTER TOP. THE SHEET IS NOT SIGNED AND SEALED. WHAT
 ABOUT THE OTHER COMMON AREA ITEMS?] I DID NOT SEE THE
 DETAILS/ELEVATIONS OF BUILT-IN ITEMS IN THE COMMON USE
 AREAS, SUCH AS RECEPTION DESKS, SERVICE COUNTERS, BREAK
 ROOM KITCHENS, ETC. THAT ARE REQUIRED TO BE ACCESSIBLE
 PER FBC ACCESSIBILITY CHAPTERS 8 AND 9. PLEASE INDICATE
 SHEETS THEY ARE ON OR PROVIDE SHEETS WITH DETAILS AND
 ELEVATIONS FOR THESE ITEMS.
  
 44) NOTE: ADDITIONAL COMMENTS MAY RESULT FROM THE
 RESPONSES TO THESE PLAN REVIEW COMMENTS.
  
 -PROVIDE COMMENT RESPONSE SHEET TO EXPLAIN HOW EACH
 COMMENT IS BEING ADDRESSED.
 -FEEL FREE TO CONTACT ME AT 561-805-6714 (M-F 8-5) TO
 DISCUSS COMMENTS, OR E-MAIL ANYTIME [email protected]
  
 NOTE: SEPARATE PERMITS (APPLICATIONS, PLANS, AND FEES)
 ARE REQUIRED FOR:
 LIGHT POLES/SITE LIGHTING
 FIRE ALARM
 FIRE SPRINKLER
 LOW VOLTAGE
 ACCESS
 LANDSCAPING
 IRRIGATION
 PARKING LOT
 SWIMMING POOLS AND SPAS
 GENERATORS
 ALL OTHER ITEMS OTHER THAN BMEP
  
  
  
  
  
  
  
  
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2021-02-03 Cont ID  
Sent By rmcdouga Date 2021-02-03 Time 12:33 Rev Time 0.00
Received By rmcdouga Date 2021-01-13 Time 13:48 Sent To  
Notes
2021-01-29 10:39:57BUILDING REVIEW COMMENTS:
  
 W.P.B. PERMIT: 18100540
 550 N. QUADRILLE BLVD.
 BUILDING PERMIT 30 STORY BLDG W/ TWO TOWERS
 CONSTRUCTION TYPE: 1A, SPRINKLERED
 MIXED OCCUPANCY: B, R-1, R-2, A-2, A4, S-2, M, E
  
 1 ST REVIEW: APRIL 18, 2019 - DYLAN BATTLES
 2 ND REVIEW: MARCH 2, 2020 - DYLAN BATTLES
 3 RD REVIEW: JANUARY 13, 2021 - ROBERT MCDOUGAL
  
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 FLORIDA BUILDING CODE,5TH EDITION (2014)
 FBC[AMENDED] = 2014 CHAPTER 1 WPB AMENDMENTS (SEE LINK
 BELOW)
 HTTPS://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/
 BUILDING-PERMIT-FORMS
 FBC[B] = FBC BUILDING
 FBC[A] = FBC ACCESSIBILITY
 FBC[E] = FBC ENERGY CONSERVATION
  
 1) NOT RESOLVED. THERE ARE STILL SOME ERRORS AND THE
 PAGE DID NOT LOAD PROPERLY. THE BOTTOM OF THE SHEET IS
 CUT OFF AND THERE IS A PARTIAL SHEET AT THE TOP.
 107.5.3 FBC[AMENDED]PLEASE UPDATE SHEET A0.102 SITE
 DATA. THE DIAGRAM IN THE UPPER RIGHT CORNER DOESN'T
 REFLECT THE CHANGES IN ROOMS SHOWN IN THE PLANS.
 COMPARE SHEET A1.500 FOR SUITE AND UNIT COUNTS.
  
 A) NOT RESOLVED. THERE ARE SEVERAL PAGES OF THE SAME
 SHEETS. RATHER THAN BEING THE SAME SHEET VERSION-ED,
 THERE IS A PAGE WITH THE OLD PLAN SHEET AND A PAGE WITH
 THE REVISED PLAN SHEET. AS A GENERAL COMMENT, PLEASE
 LOOK IN PROJECTDOX AND NOTE IF SOME SHEETS MAY NOT HAVE
 BEEN REPLACED FOR SECOND REVIEW. EITHER UPLOAD REVISED
 SHEETS, LEAVE IT DIDN'T CHANGE OR REQUEST IT TO BE
 DELETED.
  
 B) NOT RESOLVED COMPLETELY. A PORTION OF THE WALL IS
 MISSING BETWEEN UNIT B-1 AND THE UNIT ABOVE IT THAT IS
 NOT LABELED. THE WOMENS BATHROOM AT THE PREFUNCTION
 AREA IS MISSING DETAILS. SEE MARKUPS ON SHEET A1.260.
 LEVEL 8 - SHEET A1.260. IS THE COLUMN LAYER TURNED OFF?
 ALSO, MISSING UNIT NUMBER ABOVE UNIT B1 08-22
 THIS SHEET WAS NOT REVISED FROM FIRST REVIEW SO I THINK
 IT REFLECTS OLD LAYOUT. PLEASE UPLOAD NEW LEVEL 8
 RESIDENTIAL SHEET.
  
 C) NOT RESOLVED. SEE SHEETS PAGES 03.071(A1.265) AND
 03.072(A1.266) FOR REDUNDANT AND CONFLICTING
 INFORMATION. LEVEL 13-14 - 08 UNITS EACH FLOOR . SHEET
 A1.265 SAYS LEVEL 13-14, BUT THEN THE NEXT SHEET IS
 LEVEL 14. PLEASE ADJUST TITLE BLOCK TO STATE LEVEL 13
 ONLY.
  
 D) NOT RESOLVED. PAGE 03.072(A1.266) IS STILL IN THE
 PLANS. LEVEL 14 - 08 UNITS. SHEET A1.266 IS THE COLUMN
 LAYER TURNED OFF? ALSO, MISSING UNIT NUMBERS.
  
 E) RESOLVED. LEVEL 3 - MISSING SUITE NUMBER NEXT TO
 SUITE 7.1 ON SHEET A1.103. LOOKS LIKE IT SHOULD BE
 SUITE 8.
  
 F) RESOLVED. LEVEL 9 - MISSING SUITE NUMBER NEXT
 BETWEEN SUITE 1.3B AND 1.3D ON SHEET A1.109
  
 G) RESOLVED. LEVEL 16 - SUITE 2B ADA LOOKS LIKE WALL
 WAS LEFT BETWEEN ENTRY AND SLEEPING AREA.
  
 H) RESOLVED. LEVEL 17, I CAN'T FIND OFFICE LEVEL FLOOR
 PLAN. I DO SEE RCP AND LIFE SAFETY. PLEASE CHECK IF IT
 WAS LOADED INTO PROJECT DOX.
  
 2) NOT RESOLVED. PAGE 03.052 (A1.240) WAS NOT UPDATED
 AND IS STILL IN THE PLANS. 107.5.3 FBC[AMENDED]SHEET
 03.052 - A1.240 - HOTEL TOWER FLOOR PLAN - LEVEL 8 HAS
 NOT BEEN UPDATED. PLEASE UPLOAD A NEW VERSION, OR
 REQUEST IT BE DELETED FROM THE FOLDER. LEVEL EIGHT IS
 SHOWN ON PODIUM LEVEL 8 DRAWING 03.014 - A1.108 -
 PODIUM FLOOR PLAN AND IN QUADRANT PAGES AS WELL.
  
 3) NOT RESOLVED. THERE ARE STILL SOME ISSUES WITH THE
 ADA REQUIREMENTS. THE GUEST ROOM MATRIX ON PAGE 03.082
 (A1.500) HAS THE REQUIRED ADA ROOMS WITH MOBILITY
 FEATURES AS (5) ROOMS WITHOUT ROLL-IN SHOWERS, (2)
 ROOMS WITH ROLL-IN SHOWERS. THE 2010 ADA TABLE 224.2
 REQUIRES (6) ROOMS WITHOUT ROLL-IN SHOWERS, (2) ROOMS
 WITH ROLL-IN SHOWERS FOR A TOTAL OF (8) ROOMS. THE ADA
 REQUIREMENTS FOR GUEST ROOMS WITH COMMUNICATION
 FEATURES IN TABLE 224.4 IS 14 ROOMS WHEN 200 GUEST
 ROOMS ARE PROVIDED. AT LEAST ONE GUEST ROOM REQUIRED TO
 PROVIDE MOBILITY FEATURES COMPLYING WITH 806.2 SHALL
 ALSO PROVIDE COMMUNICATION FEATURES COMPLYING WITH
 806.3. NOT MORE THAN 10 PERCENT OF GUEST ROOMS REQUIRED
 TO PROVIDE MOBILITY FEATURES COMPLYING WITH 806.2 SHALL
 BE USED TO SATISFY THE MINIMUM NUMBER OF GUEST ROOMS
 REQUIRED TO PROVIDE COMMUNICATION FEATURES COMPLYING
 WITH 806.3. REVISE THE ROOM MATRIX TO CLEARLY SHOW
 COMPLIANCE OF SPECIFIC ROOMS. ALSO REVISE THE PLANS TO
 COMPLY.
 107.5.3 FBC[AMENDED]PLEASE ADD COMMUNICATION SYMBOL TO
 SUITE 4.2B ON SHEET A1.243 ROOM SUMMARY SHEET STATES
 LEVEL 12-15 AS COMMUNICATION. PLEASE ADD SYMBOL TO
 THOSE ROOMS AS WELL. ADD BOTH SYMBOLS TO SUITE 2.B ON
 SHEET A1.246
 PLEASE LOOK AT MOBILITY FEATURES DATA LAST LINE WHERE
 IT SAYS LEVEL 8-16 SUITE 4.2B. I DO SEE THAT THERE IS
 ADA ON LEVEL 16. ADD SYMBOLS AND CORRECT WHERE IT
 STATES 8-16 OR SHOW THAT LEVEL 8-15 SUITE 4.2B ARE ADA
 SUITES.
  
 4) NOT RESOLVED. PROVIDE A ROOM MATRIX THAT SHOWS WHICH
 SPECIFIC HOTEL ROOMS WILL MEET THE ACCESSIBILITY
 REQUIREMENTS FOR MOBILITY AND COMMUNICATION FEATURES.
 SEE FBC ACCESSIBILITY SECTIONS 224 AND 806. NOT MORE
 THAN 10 PERCENT OF GUEST ROOMS REQUIRED TO PROVIDE
 MOBILITY FEATURES COMPLYING WITH 806.2 SHALL BE USED TO
 SATISFY THE MINIMUM NUMBER OF GUEST ROOMS REQUIRED TO
 PROVIDE COMMUNICATION FEATURES COMPLYING WITH 806.3.
 SPECIFY THE LOCATION AND ACCESSIBILITY TYPE OT HOTEL
 ROOMS WITH THE APPROPRIATE SYMBOLS ON THE PLANS. 224.5
 FBC[A]DISPERSION. GUEST ROOMS REQUIRED TO PROVIDE
 MOBILITY FEATURES COMPLYING WITH 806.2 AND GUEST ROOMS
 REQUIRED TO PROVIDE COMMUNICATION FEATURES COMPLYING
 WITH 806.3 SHALL BE DISPERSED AMONG THE VARIOUS CLASSES
 OF GUEST ROOMS, AND SHALL PROVIDE CHOICES OF TYPES OF
 GUEST ROOMS, NUMBER OF BEDS, AND OTHER AMENITIES
 COMPARABLE TO THE CHOICES PROVIDED TO OTHER
 GUESTS.WHERE THE MINIMUM NUMBER OF GUEST ROOMS REQUIRED
 TO COMPLY WITH 806 IS NOT SUFFICIENT TO ALLOW FOR
 COMPLETE DISPERSION, GUEST ROOMS SHALL BE DISPERSED IN
 THE FOLLOWING PRIORITY: GUEST ROOM TYPE, NUMBER OF
 BEDS, AND AMENITIES. AT LEAST ONE GUEST ROOM REQUIRED
 TO PROVIDE MOBILITY FEATURES COMPLYING WITH 806.2 SHALL
 ALSO PROVIDE COMMUNICATION FEATURES COMPLYING WITH
 806.3. NOT MORE THAN 10 PERCENT OF GUEST ROOMS REQUIRED
 TO PROVIDE MOBILITY FEATURES COMPLYING WITH 806.2 SHALL
 BE USED TO SATISFY THE MINIMUM NUMBER OF GUEST ROOMS
 REQUIRED TO PROVIDE COMMUNICATION FEATURES COMPLYING
 WITH 806.3.
 -ONLY 10 PERCENT OF REQUIRED ROOMS CAN SHARE
 COMMUNICATION AND MOBILITY. PLEASE SHOW COMMUNICATION
 ROOMS ONLY SHARE IN ONE SUITE.
 -PLEASE VERIFY THAT ROOMS ARE EVENLY DISTRIBUTED FOR
 ROOM TYPES AND PRICE RANGE.
  
 5) NOT RESOLVED. PROVIDE A ROOM MATRIX TO SHOW WHICH
 SPECIFIC HOTEL ROOMS WILL MEET THIS REQUIREMENT. 806.4
 FBC[A]HOTEL,MOTEL AND CONDOMINIUM SPECIAL ACCESSIBILITY
 FEATURES. THIS SECTION DOES NOT RELIEVE THE OWNER OF
 THE RESPONSIBILITY OF PROVIDING ACCESSIBLE ROOMS IN
 CONFORMANCE WITH SECTION 224 AND 806 OF THIS CODE. IN
 ALL BUILDINGS, STRUCTURES AND FACILITIES LICENSED AS A
 HOTEL, MOTEL OR RESORT CONDOMINIUM PURSUANT TO CHAPTER
 509, F.S., A NUMBER OF ROOMS EQUALING AT LEAST 5
 PERCENT OF THE GUEST ROOMS MINUS THE TOTAL NUMBER OF
 REQUIRED (ACCESSIBLE) ROOMS REQUIRED BY TABLE 224.2
 SHALL PROVIDE THE FOLLOWING ADDITIONAL SPECIAL
 ACCESSIBILITY FEATURES:
 (I) GRAB RAILS IN BATHROOMS AND TOILET ROOMS WHICH
 COMPLY WITH SECTION 604.5.
 (II) ALL BEDS IN DESIGNED ACCESSIBLE GUEST ROOMS SHALL
 BE OPEN-FRAME TYPE THAT ALLOWS THE PASSAGE OF LIFT
 DEVICES.
 (III)WATER CLOSETS THAT COMPLY WITH SECTION 604.4.
 -SHOW WHICH ROOMS COMPLY WITH 806.4
  
 6) NOT RESOLVED. THERE ARE HOTEL ROOMS THAT APPEAR TO
 BE EQUIPPED WITH COOKING APPLIANCES. YOUR RESPONSE
 STATES THAT NOTE 26 ON SHEET A0.201 ADDRESSES THIS
 COMMENT. IT STATES THAT SERVICE APARTMENTS DESIGNED FOR
 STAYS OF MORE THAN 30 DAYS ARE REQUIRED TO COMPLY WITH
 FAIRHOUSING RATHER THAN ADA ACCESSIBILITY REQUIREMENTS.
 THIS IS NOT ACCURATE. BECAUSE THESE ARE HOTEL ROOMS
 THEY ARE NOT APARTMENTS AND ARE REQUIRED TO COMPLY WITH
 THE FLORIDA ACCESSIBILITY CODE AS WELL AS FAIRHOUSING
 GUIDELINES IF THEY ARE USED FOR STAYS OF MORE THAN 30
 DAYS. YOU WILL NEED TO IDENTIFY THESE ROOMS AND SHOW
 THAT THEY MEET THE MOST RESTRICTIVE REQUIREMENTS OF THE
 TWO. 224.1 ADVISORY FBC[A]ARE THERE NON-TRANSIENT ROOMS
 (MORE THAN 30 DAY STAY)?
 IF SO, THOSE ROOMS MAY FALL UNDER THE FAIRHOUSING
 GUIDELINES IN ADDITION TO ACCESSIBILITY FBC 2017 6 TH
 EDITION.
  
 FAIRHOUSING REVIEW:
 7) RESOLVED. 1986 ANSI [A117.1] IF A DESIGNER OR
 BUILDER CHOOSES TO FOLLOW AN ACCESSIBILITY STANDARD
 OTHER THAN THE 1986 ANSI A117.1 STANDARD, OR A MORE
 RECENT VERSION OF THE ANSI A117.1, SUCH AS THE 1992
 CABO/ANSI, THAT CARE BE TAKEN TO ENSURE THE STANDARD
 USED IS AT LEAST EQUIVALENT TO OR STRICTER THAN THE
 1986 ANSI A117.1 STANDARD.
 -WHAT STANDARD IS BEING APPLIED FOR COMPLIANCE WITH
 FAIR HOUSING? YOU CAN USE GUIDELINES THAT FALL WITHIN
 THE SAFE HARBOR FOR COMPLIANCE?
  
 A) PARTIALLY RESOLVED. PAGE 03.097(A1.519) THE MASTER
 BATH TOILET IN RESIDENTIAL UNIT S8 DOES NOT APPEAR TO
 COMPLY WITH A TYPE B BATHROOM. ON PAGE 03.102(A1.524)
 RESIDENTIAL UNIT B1 HAS ONE BATH ROOM MARKED AS TYPE A
 AND THE OTHER AS TYPE B. THE UNIT CAN ONLY BE ONE TYPE.
 ON PAGE 03.104(A1.526) SHOW THE REQUIRED CLEAR FLOOR
 SPACE AT THE TOILET IN UNIT B3.1. IT WOULD BE HELPFUL
 TO ADD A MATRIX OF ROOMS ON SHEET A1.500 WHICH BATHROOM
 SPEC IS BEING USED AND APPLY THE FOLLOWING FOR SPEC A
 AND B
  
 SPECIFICATION A:
 IF SPECIFICATION A IS USED IT APPLIES TO ALL BATHROOMS,
 AND ALL FIXTURES IN THOSE BATHROOMS MUST BE USABLE.
 SPECIFICATION B:
 IF SPECIFICATION B IS USED, IT APPLIES TO ONE BATHROOM,
 AND ONLY ONE OF EACH TYPE OF FIXTURE MUST BE USABLE;
 ADDITIONAL BATHROOMS IN THE UNIT ARE EXEMPT ONLY FROM
 MANEUVERING AND CLEAR FLOOR SPACE REQUIREMENTS AT
 FIXTURES.
  
 B) RESOLVED. PLEASE ADD TO FAIRHOUSING NOTES ON SHEET
 A1.528. THIS SAYS ALL BATHROOMS TO BE SPEC A. PLEASE
 ADJUST NOTE SINCE BOTH SPEC ARE BEING USED.
  
 C) RESOLVED. ADD NOTE FOR USABLE HARDWARE.
 REQUIREMENT 3 - USABLE DOORS. THE DOORS IN COMMON
 SPACES AND THE SIDE ENTERING INTO DWELLING UNITS NEED
 TO HAVE USABLE HARDWARE THAT CAN BE USED WITHOUT TIGHT
 GRASPING OR TWISTING.
 -TYPICALLY THE HARDWARE WOULD BE A LEVER TYPE. THIS
 TYPE OF HARDWARE WOULD NOT BE REQUIRED ONCE INSIDE THE
 UNIT. YOU MAY WANT TO CLARIFY HARDWARE ON THE DOOR
 SCHEDULE.
  
 D) NOT RESOLVED. DOOR SCHEDULES ON PAGES 03.242(A6.104)
 AND 03.243(A6.105) NEED TO BE CLEANED UP AND MADE
 LEGIBLE. DOOR SCHEDULE ON SHEET A6.104 IS DISTORTED AND
 INFORMATION IS NOT LEGIBLE. PLEASE ADJUST AND POPULATE
 AS NEEDED.
  
 E) RESOLVED. SHOW ACCESSIBLE ROUTES FOR EACH UNIT TYPE.
  
 F) RESOLVED. ADD DETAIL OF HOW ACCESS IS GAINED AT
 RESIDENTIAL BALCONY. IS THERE ELEVATION CHANGE TO MEET
 FAIRHOUSING MAX OF 4 INCHES TOP OF THRESHOLD?
  
 LIFE SAFETY:
  
 8) PARTIALLY RESOLVED. SPECIFY THE REQUIRED FIRE
 RATINGS FOR THE EXIT STAIR DOORS AND THE FIRE SERVICE
 ACCESS LOBBY DOORS IN THE DOOR SCHEDULES. 3006.2
 FBC[B]SHEET A1.107 SHOWS NO ELEVATOR LOBBY ON LEVEL 7
 AT ELEVATORS 8, 9 AND 10. IF REQUIRED PLEASE SHOW THE
 DOORS.
 1024.4 FBC[B]TERMINATION. EXIT PASSAGEWAYS ON THE LEVEL
 OF EXIT DISCHARGE SHALL TERMINATE AT AN EXIT DISCHARGE.
 EXIT PASSAGEWAYS
 ON OTHER LEVELS SHALL TERMINATE AT AN EXIT.
 EXIT DISCHARGE. THAT PORTION OF A MEANS OF EGRESS
 SYSTEM BETWEEN THE TERMINATION OF AN EXIT AND A PUBLIC
 WAY.
  
 9) RESOLVED. 3005.5 FBC[B] SHUNT TRIP. WHERE ELEVATOR
 HOISTWAYS, ELEVATOR MACHINE ROOMS, CONTROL ROOMS AND
 CONTROL SPACES CONTAINING ELEVATOR CONTROL EQUIPMENT
 ARE PROTECTED WITH AUTOMATIC SPRINKLERS, A MEANS
 INSTALLED IN ACCORDANCE WITH SECTION 21.4 OF NFPA 72
 SHALL BE PROVIDED TO DISCONNECT AUTOMATICALLY THE MAIN
 LINE POWER SUPPLY TO THE AFFECTED ELEVATOR PRIOR TO THE
 APPLICATION OF WATER. THIS MEANS SHALL NOT BE
 SELF-RESETTING. THE ACTIVATION OF AUTOMATIC SPRINKLERS
 OUTSIDE THE HOISTWAY, MACHINE ROOM, MACHINERY SPACE,
 CONTROL ROOM OR CONTROL SPACE SHALL NOT DISCONNECT THE
 MAIN LINE POWER SUPPLY.
  
 10) RESOLVED. 3006.2 FBC[B] HOISTWAY OPENING PROTECTION
 REQUIRED. ELEVATOR HOISTWAY DOOR OPENINGS SHALL BE
 PROTECTED IN ACCORDANCE WITH SECTION 3006.3 WHERE AN
 ELEVATOR HOISTWAY CONNECTS MORE THAN THREE STORIES, IS
 REQUIRED TO BE ENCLOSED WITHIN A SHAFT ENCLOSURE IN
 ACCORDANCE WITH SECTION 712.1.1 AND ANY OF THE
 FOLLOWING CONDITIONS APPLY:
 5. THE BUILDING IS A HIGH RISE AND THE ELEVATOR
 HOISTWAY IS MORE THAN 75 FEET (22 860 MM) IN HEIGHT.
 THE HEIGHT OF THE HOISTWAY SHALL BE MEASURED FROM THE
 LOWEST FLOOR TO THE HIGHEST FLOOR OF THE FLOORS SERVED
 BY THE HOISTWAY.
 -IS THE PRE FUNCTION AREA OPEN AIR? IT IS HARD TO TELL
 BUT IT APPREARS TO BE COVERED BY RESIDENTIAL ABOVE.
 -FREIGHT ELEVATOR DOES NOT HAVE ELEVATOR LOBBY ON THE 8
 TH FLOOR. PLEASE REVIEW 3006.2 FOR OPENING PROTECTION
 ON SHAFT MORE THAN 75 FEET.
  
 11) NOT RESOLVED. YOUR RESPONSE STATES THAT A LIFE
 SAFETY PLAN FOR THE PARK WAS ADDED ON SHEET ALS1.109.
 THERE IS NO SUCH SHEET IN THE PLANS OR THE PLAN INDEX.
 PLEASE CLARIFY. 107.5.3 FBC[AMENDED]ADD SCALE TO LIFE
 SAFETY PLANS. I THINK IT IS 1/16 SCALE.
 ALSO, IS THERE A LIFE SAFETY SHEET FOR THE PARK ABOVE
 THE TENNIS PAVILION? PLEASE PROVIDE OR LET ME KNOW
 WHICH SHEET I CAN FIND IT.
  
 12) NOT RESOLVED. THERE ARE EXIT DOORS AT GRADE LEVEL
 THAT DO NOT HAVE EGRESS LOAD TAGS. 1004 FBC[B]PLEASE
 PROVIDE TOTAL OCCUPANT LOAD FOR EACH EGRESS DOOR AT
 GRADE WHERE THE DOOR PROVIDES EGRESS FROM MULTIPLE
 AREAS. FOR EXAMPLE EGRESS DOORS IN HOTEL LOBBY PICKUP
 THE STAIRS AND OTHER AREAS FROM FIRST LEVEL USES. I AM
 LOOKING FOR DATA TAG LIKE WAS USED AT STAIRWAY DOORS.
  
 13) RESOLVED. 1025.1 FBC[B]GENERAL. APPROVED LUMINOUS
 EGRESS PATH MARKINGS DELINEATING THE EXIT PATH SHALL BE
 PROVIDED IN HIGH-RISE BUILDINGS OF GROUP A, B, E, I, M,
 AND R-1 OCCUPANCIES IN ACCORDANCE WITH SECTIONS 1025.1
 THROUGH 1025.5.
 -ST4 AND ST3 FROM R-1 LEVELS TO MEET 1025.1 FOR
 LUMINOUS MARKINGS.
  
 14) RESOLVED. 1013.2 FBC[B] FLOOR-LEVEL EXIT SIGNS IN
 GROUP R-1. WHERE EXIT SIGNS ARE REQUIRED IN GROUP R-1
 OCCUPANCIES BY SECTION 1013.1, ADDITIONAL LOW-LEVEL
 EXIT SIGNS SHALL BE PROVIDED IN ALL AREAS SERVING GUEST
 ROOMS IN GROUP R-1 OCCUPANCIES AND SHALL COMPLY WITH
 SECTION 1013.5.
 -ADD LOW LEVEL EXIT SIGNS AS REQUIRED, OR STATE WHICH
 PAGE THIS INFORMATION CAN BE FOUND.
  
 15) NOT RESOLVED. THE EXIT ACCESS TRAVEL DISTANCE FOR
 SPRINKLERED TYPE M OCCUPANCIES IS 250' IN 2014 FBC
 TABLE 1016.2 AND THE TABLE ON SHEET ALS1.101 HAS 400'.
 THE EGRESS TRAVEL DISTANCE FOR SPRINKLERED RESIDENTIAL
 OCCUPANCIES IS 250' IN FBC TABLE 1016.2 AND THE TABLE
 ON THE LIFE SAFETY PLANS SHEETS WITH RESIDENTIAL UNITS
 HAS 325'. YOU ARE REQUIRED TO MEET THE MOST RESTRICTIVE
 REQUIREMENT BETWEEN THE F.F.P.C. AND THE FBC BUILDING.
 SOME DESIGNERS LIST THE REQUIREMENTS OF BOTH CODES IN
 THEIR TABLES WITH A NOTE TO USE THE MOST RESTRICTIVE
 REQUIREMENT. PLEASE REVIEW ALL LIFE SAFETY PLANS FOR
 REQUESTED DATA. THE RESIDENTS LOUNGE AREA (0161) HAS AN
 OCCUPANT LOAD OF MORE THAN 49 AND REQUIRES TWO EXITS
 PER TABLE 1015.1. BE SURE TO SHOW EXIT ROUTES FOR ALL
 AREAS. 107.3.5 FBC[AMENDED] MINIMUM REVIEW CRITERIA.
 THIS IS FOR ALL LIFE SAFETY SHEETS
 A. ADD MAX COMMON PATH AND MAX TRAVEL DISTANCE FOR R-1
 AND R-2 TO ALS1.100 COMPLIANCE SUMMARY FOR FLORIDA
 BUILDING CODE IN ADDITION TO THE PROVIDED NFPA. THE
 MORE RESTRICTIVE CODE WILL APPLY.
 B. SHOW MAXIMUM PATH OF TRAVEL ON ALL L.S. PLANS.
 CURRENTLY, L.S. SHEETS SHOW PATH OF TRAVEL DISTANCE OR
 TOTAL DISTANCE. PLANS SHOULD SHOW BOTH COMMON PATH OF
 TRAVEL AND EXIT ACCESS TRAVEL DISTANCE. THIS SHOULD BE
 DONE FOR WORST CASE IN EACH GENERAL AREA.
  
 16) NOT COMPLETELY RESOLVED. THERE ARE SEVERAL RAMPS
 SHOWN ON THE PLANS. PLEASE IDENTIFY EACH WITH AN ID TAG
 AND PROVIDE DETAILS FOR EACH OF THEM TO SHOW THAT THEY
 MEET THE ACCESSIBILITY REQUIREMENTS FOR RAMPS. FBC
 ACCESSIBILITY 405. 1003.5 FBC[B] ELEVATION CHANGE. DOES
 EXIT FROM RESIDENT LOBBY TO STAIR 2 HAVE STEPS? PLEASE
 REVIEW
 -HOW DO STEPS WORK AT EGRESS FROM RESIDENT LOUNGE TO
 STAIR ST2? PLEASE REVIEW 1003.5 FOR CHANGE IN ELEVATION
 IN PATH OF EGRESS.
  
 17) RESOLVED. 1012.9 FBC[B] INTERMEDIATE HANDRAILS.
 STAIRWAYS SHALL HAVE INTERMEDIATE HANDRAILS LOCATED IN
 SUCH A MANNER THAT ALL PORTIONS OF THE STAIRWAY MINIMUM
 WIDTH OR REQUIRED CAPACITY ARE WITHIN 30 INCHES (762
 MM) OF A HANDRAIL. ON MONUMENTAL STAIRS, HANDRAILS
 SHALL BE LOCATED ALONG THE MOST DIRECT PATH OF EGRESS
 TRAVEL.
 -CHECK COMPLIANCE WITH 1012.9 AT BALLROOM STEPS.
  
 18) RESOLVED. 713.13.4 CHUTE DISCHARGE ROOM. WASTE OR
 LINEN CHUTES SHALL DISCHARGE INTO AN ENCLOSED ROOM
 SEPARATED BY FIRE BARRIERS WITH A FIRE RESISTANCE
 RATING NOT LESS THAN THE REQUIRED FIRE RATING OF THE
 SHAFT ENCLOSURE AND CONSTRUCTED IN ACCORDANCE WITH
 SECTION 707 OR HORIZONTAL ASSEMBLIES CONSTRUCTED IN
 ACCORDANCE WITH SECTION 711, OR BOTH. OPENINGS INTO THE
 DISCHARGE ROOM FROM THE REMAINDER OF THE BUILDING SHALL
 BE PROTECTED BY OPENING PROTECTIVES HAVING A FIRE
 PROTECTION RATING EQUAL TO THE PROTECTION REQUIRED FOR
 THE SHAFT ENCLOSURE. DOORS SHALL BE SELF- OR
 AUTOMATICCLOSING UPON THE DETECTION OF SMOKE IN
 ACCORDANCE WITH SECTION 716.5.9.3. WASTE CHUTES SHALL
 NOT TERMINATE IN AN INCINERATOR ROOM. WASTE AND LINEN
 ROOMS THAT ARE NOT PROVIDED WITH CHUTES NEED ONLY
 COMPLY WITH TABLE 509.
 -DOUBLE DOORS TO TRASH ROOM AT BASE LEVEL SHOW 90
 MINUTE RATING, BUT 713.13.4 REQUIRES SAME LEVEL OF
 PROTECTION FOR OPENINGS IN DISCHARGE ROOM EQUAL TO THE
 SHAFT ENCLOSURE (2 HOURS).
  
 19) RESOLVED. 420.3 FBC[B]HORIZONTAL SEPARATION AND
 FBC[B] 602 FLOOR ASSEMBLIES SEPARATING DWELLING UNITS
 IN THE SAME BUILDINGS, FLOOR ASSEMBLIES SEPARATING
 SLEEPING UNITS IN THE SAME BUILDING AND FLOOR
 ASSEMBLIES SEPARATING DWELLING OR SLEEPING UNITS FROM
 OTHER OCCUPANCIES CONTIGUOUS TO THEM IN THE SAME
 BUILDING SHALL BE CONSTRUCTED AS HORIZONTAL ASSEMBLIES
 IN ACCORDANCE WITH SECTION 711.
 -602 FBC[B]SHEET A7.310 HAS CEILING ASSEMBLIES. PLEASE
 SHOW THE RATED ASSEMBLY FOR CEILINGS SEPARATING
 DWELLING AND SLEEPING UNITS AS STATED IN LIFE SAFETY
 COMPLIANCE SUMMARY ALS1.100.
  
 20) NOT RESOLVED. THE TAG ON THE WASTE CHUTE ACCESS
 DOORS FROM THE CORRIDORS STILL HAVE NR INSTEAD OF 45
 MIN. ON THE LIFE SAFETY PLANS.713.13.3 FBC[B]CHUTE
 ACCESS ROOMS. ACCESS OPENINGS FOR WASTE OR LINEN CHUTES
 SHALL BE LOCATED IN ROOMS OR COMPARTMENTS ENCLOSED BY
 NOT LESS THAN 1-HOUR FIRE BARRIERS CONSTRUCTED IN
 ACCORDANCE WITH SECTION 707 OR HORIZONTAL ASSEMBLIES
 CONSTRUCTED IN ACCORDANCE WITH SECTION 711, OR BOTH.
 OPENINGS INTO THE ACCESS ROOMS SHALL BE PROTECTED BY
 OPENING PROTECTIVES HAVING A FIRE PROTECTION RATING OF
 NOT LESS THAN 3/4 HOUR. DOORS SHALL BE SELF- OR
 AUTOMATIC-CLOSING UPON THE DETECTION OF SMOKE IN
 ACCORDANCE WITH SECTION 716.5.9.3.
 -LIFE SAFETY SHEETS SHOW CHUTE ACCESS DOORS AS NOT
 RATED (NR). THESE ACCESS DOORS ARE REQUIRED TO HAVE A
 3/4 HOUR RATING PER 713.13.3.
 - ADD DOOR TAG TO THE DOORS LEADING TO THE TRASH CHUTE
 OR TELL ME WHAT SHEETS THER ARE ON. I WAS LOOKING ON
 QUADRANT SHEETS WHERE THE OTHER TAGS FOR COMMON SPACE
 DOORS WERE LOCATED.
  
 DEFERRED SUBMITTALS
 21) NOT COMPLETELY RESOLVED. PLEASE LABEL GENERAL NOTE
 16 ON SHEET A0.001 AS "DEFERRED SUBMITTALS" AND NOTE
 THAT THE ITEMS BEING DEFERRED ARE REQUIRED TO BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORDED AND SUBMITTED AND APPROVED BY THE CITY OF WEST
 PALM BEACH BUILDING DEPARTMENT PRIOR TO BEING
 INSTALLED. ANY ITEMS NOT LISTED WILL HAVE TO BE
 APPROVED BEFORE THE PERMIT CAN BE ISSUED. 107.3.4.1
 FBC[AMENDED] PLEASE PROVIDE A LIST OF DEFERRED
 SUBMITTALS ON PLANS SO THAT I WILL NOT ASK FOR ITEMS
 THAT WILL BE SUPPLIED AT A LATER DATE, OR INDICATE
 WHICH PAGE A LIST CAN BE FOUND.
 THESE ARE THE ONES I BELIEVE WE WILL NEED, BUT THIS IS
 NOT A COMPLETE LIST.
 A) COMPONENT & CLADDING PRODUCT APPROVALS (COMPLY WITH
 PRESSURES SHOWN ON SHEET S0.0.5)
 B) CURTAIN WALL SUBMITTAL (COMPLY WITH PRESSURES SHOWN
 ON SHEET S0.0.5)
 C) FENESTRATION SHOP DRAWINGS TO INCLUDE ALL WINDOWS,
 DOORS, TRANSOMS, SLIDERS, LOUVERS AND MULL BARS.
 D) FLOORING UNDERLAYMENT WITH THREE REPORTS:
 1. 1207.2 FBC[B] AIR-BORNE SOUND. WALLS, PARTITIONS AND
 FLOOR/CEILING ASSEMBLIES SEPARATING DWELLING UNITS AND
 SLEEPING UNITS FROM EACH OTHER OR FROM PUBLIC OR
 SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS OF
 NOT LESS THAN 50, OR NOT LESS THAN 45 IF FIELD TESTED,
 FOR AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM
 E90.
 2. 1207.3 FBC[B] STRUCTURE-BORNE SOUND. FLOOR/CEILING
 ASSEMBLIES BETWEEN DWELLING UNITS AND SLEEPING UNITS OR
 BETWEEN A DWELLING UNIT OR SLEEPING UNIT AND A PUBLIC
 OR SERVICE AREA WITHIN THE STRUCTURE SHALL HAVE AN
 IMPACT INSULATION CLASS RATING OF NOT LESS THAN 50, OR
 NOT LESS THAN 45 IF FIELD TESTED, WHEN TESTED IN
 ACCORDANCE WITH ASTM E492.
 3. 603.1 FBC[B] ALLOWABLE MATERIALS IN NON COMBUSTIBLE
 BUILDINGS, SEE ITEM 2, EXCEPTION 2, ACOUSTICAL
 INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID
 DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED
 TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200. SEE
 803.1.1, PROVIDE TEST DATA IN ACCORDANCE WITH ASTM E 84
 OR UL 723.
 E) RAILINGS AND GUARDRAILS. INCLUDES BALCONIES, STAIRS
 AND COMMON SPACES.
 F) PARKING GARAGE VEHICLE BARRIER PER 406.4.2 FBC[B]
 G) FIRE SPRAY
 H) 806.1 FBC[B] GENERAL REQUIREMENTS. CURTAINS,
 DRAPERIES, HANGINGS AND OTHER DECORATIVE MATERIALS
 SUSPENDED FROM WALLS OR CEILINGS SHALL MEET THE FLAME
 PROPAGATION PERFORMANCE CRITERIA OF NFPA 701 IN
 ACCORDANCE WITH SECTION 806.2 OR BE NONCOMBUSTIBLE.
 I) LIGHTWIEGHT CONCRETE.
 J) WINDOW WASHING EQUIPMENT ATTACHMENTS/LOCATIONS AT
 ROOF.
 K) E.F.I.S. IF APPLICABLE
 L) LIGHTING CONTROLS PER ENERGY CODE C405.2 LIGHTING
 CONTROLS (MANDATORY) C405.5 EXTERIOR LIGHTING
 (MANDATORY)
 M) FINAL GYM EQUIPMENT LAYOUT WITH ACCESSIBILTY
 REQUIREMENTS PROVIDED.
 PRODUCT APPROVALS FOR ROOFING ARE PROVIDED, BUT NO
 SELECTIONS ARE MADE AND IT IS NOT CLEAR WHICH AREA OF
 ROOF RECEIVE.
 ROOFING CAN BE ADDED TO DEFERRED SUBMITTAL LIST.
  
 22) NOT RESOLVED. THE PRODUCT APPROVALS THAT WERE
 SUBMITTED ARE REQUIRED TO BE REVIEWED AND APPROVED IN
 WRITING BY THE DESIGNER OF RECORD. IF YOU ARE NOT SURE
 WHICH PRODUCTS WILL BE USED, YOU CAN SPECIFY ON THE
 PLANS THAT THEY WILL BE SUBMITTED LATER. ALSO, PROVIDE
 PRODUCT APPROVAL FOR ROOF INSULATION AND ATTACHMENT.
 OTHER PRODUCT APPROVALS WERE SUBMITTED FOR DOORS, BUT
 THEY WERE NOT STAMPED AS REVIEWED. AS PART OF
 FENESTRATION PACKAGE PROVIDE ALL PRODUCT APPROVALS WITH
 INDICATION THAT THEY WERE REVIEWED BY THE DESIGNER OF
 RECORD.
  
 23) RESOLVED. ENERGY CODE REVIEW:
 A) THIS BUILDING WAS BROUGHT IN UNDER 2014 CODE CYCLE.
 PLEASE REVISE TO THAT CODE DATE, OR PROVIDE LETTER OF
 COMPLIANCE THAT CURRENT CODES ARE EQUIVALENT.
 B) C407.2.1 ROOF/CEILING THERMAL ENVELOPE. SECTIONS FOR
 ROOFING AND DOORS SHOW NO DATA. PLEASE INCLUDE THOSE
 VALUES IN THE ENERGY CALCULATIONS.
 C) IN SECTION FOR WALLS THE ASSEMBLY STATES 6 INCH
 INSULATION. WHERE IS THAT ASSEMBLY BEING USED ON THE
 BUILDING?
  
 ACCESSIBILITY REVIEW:
  
 24) PROVIDE DETAILS TO SHOW THAT THE BUILT IN LOCKER
 ROOM BENCHES ARE ADA COMPLIANT. 803.1 FBC[A] GENERAL.
 DRESSING, FITTING, AND LOCKER ROOMS SHALL COMPLY WITH
 803.
 803.2 FBC[A] TURNING SPACE. TURNING SPACE COMPLYING
 WITH 304 SHALL BE PROVIDED WITHIN THE ROOM.
 803.3 FBC[A] DOOR SWING. DOORS SHALL NOT SWING INTO THE
 ROOM UNLESS A CLEAR FLOOR OR GROUND SPACE COMPLYING
 WITH 305.3 IS PROVIDED BEYOND THE ARC OF THE DOOR
 SWING.
 803.4 FBC[A] BENCHES. A BENCH COMPLYING WITH 903 SHALL
 BE PROVIDED WITHIN THE ROOM.
 903.4 FBC[A] BACK SUPPORT. THE BENCH SHALL PROVIDE FOR
 BACK SUPPORT OR SHALL BE AFFIXED TO A WALL. BACK
 SUPPORT SHALL BE 42 INCHES LONG MINIMUM AND SHALL
 EXTEND FROM A POINT 2 INCHES MAXIMUM ABOVE THE SEAT
 SURFACE TO A POINT 18 INCHES MINIMUM ABOVE THE SEAT
 SURFACE. BACK SUPPORT SHALL BE 21/2 INCHES MAXIMUM FROM
 THE REAR EDGE OF THE SEAT MEASURED HORIZONTALLY.
  
 25) NOT COMPLETELY RESOLVED. THE ADA INFORMATION, CLEAR
 FLOOR SPACE WAS NOT PROVIDED FOR THE EXERCISE EQUIPMENT
 IN THE MENS GYM. 236.1 FBC[A]GENERAL. AT LEAST ONE OF
 EACH TYPE OF EXERCISE MACHINE AND EQUIPMENT SHALL
 COMPLY WITH 1004.
 1004.1 FBC[A]CLEAR FLOOR SPACE. EXERCISE MACHINES AND
 EQUIPMENT SHALL HAVE A CLEAR FLOOR SPACE COMPLYING WITH
 305 POSITIONED FOR TRANSFER OR FOR USE BY AN INDIVIDUAL
 SEATED IN A WHEELCHAIR. CLEAR FLOOR OR GROUND SPACES
 REQUIRED AT EXERCISE MACHINES AND EQUIPMENT SHALL BE
 PERMITTED TO OVERLAP.
  
 ADVISORY 1004.1 FBC[A]CLEAR FLOOR SPACE. ONE CLEAR
 FLOOR OR GROUND SPACE IS PERMITTED TO BE SHARED BETWEEN
 TWO PIECES OF EXERCISE EQUIPMENT.TO OPTIMIZE SPACE USE,
 DESIGNERS SHOULD CAREFULLY CONSIDER LAYOUT OPTIONS SUCH
 AS CONNECTING ENDS OF THE ROW AND CENTER AISLE SPACES.
 THE POSITION OF THE CLEAR FLOOR SPACE MAY VARY GREATLY
 DEPENDING ON THE USE OF THE EQUIPMENT OR MACHINE. FOR
 EXAMPLE, TO PROVIDE ACCESS TO A SHOULDER PRESS MACHINE,
 CLEAR FLOOR SPACE NEXT TO THE SEAT WOULD BE APPROPRIATE
 TO ALLOW FOR TRANSFER. CLEAR FLOOR SPACE FOR A BENCH
 PRESS MACHINE DESIGNED FOR USE BY AN INDIVIDUAL SEATED
 IN A WHEELCHAIR, HOWEVER, WILL MOST LIKELY BE CENTERED
 ON THE OPERATING MECHANISMS.
  
 26) NOT RESOLVED. THE NOTES ON THE POOLS STATE TO REFER
 TO SHEETS SP.001, SP.002 AND SP.003. I WAS NOT ABLE TO
 FIND THESE SHEETS. SHOW HOW THE POOLS WILL COMPLY WITH
 FBC ACCESSIBILITY SECTION 242.2 SWIMMING POOLS. AT
 LEAST TWO ACCESSIBLE MEANS OF ENTRY SHALL BE PROVIDED
 FOR SWIMMING POOLS. (SEE EXCEPTIONS) ACCESSIBLE MEANS
 OF ENTRY SHALL BE SWIMMING POOL LIFTS COMPLYING WITH
 1009.2; SLOPED ENTRIES COMPLYING WITH 1009.3; TRANSFER
 WALLS COMPLYING WITH 1009.4; TRANSFER SYSTEMS COMPLYING
 WITH 1009.5; AND POOL STAIRS COMPLYING WITH 1009.6. AT
 LEAST ONE ACCESSIBLE MEANS OF ENTRY PROVIDED SHALL
 COMPLY WITH 1009.2 OR 1009.3. ADVISORY 242.2 SWIMMING
 POOLS. WHERE MORE THAN ONE MEANS OF ACCESS IS PROVIDED
 INTO THE WATER, IT IS RECOMMENDED THAT THE MEANS BE
 DIFFERENT. PROVIDING DIFFERENT MEANS OF ACCESS WILL
 BETTER SERVE THE VARYING NEEDS OF PEOPLE WITH
 DISABILITIES IN GETTING INTO AND OUT OF A SWIMMING
 POOL. IT IS ALSO RECOMMENDED THAT WHERE TWO OR MORE
 MEANS OF ACCESS ARE PROVIDED, THEY NOT BE PROVIDED IN
 THE SAME LOCATION IN THE POOL. DIFFERENT LOCATIONS WILL
 PROVIDE INCREASED OPTIONS FOR ENTRY AND EXIT,
 ESPECIALLY IN LARGER POOLS. ADVISORY 242.2 SWIMMING
 POOLS EXCEPTION 1. POOL WALLS AT DIVING AREAS AND AREAS
 ALONG POOL WALLS WHERE THERE IS NO POOL ENTRY BECAUSE
 OF LANDSCAPING OR ADJACENT STRUCTURES ARE TO BE COUNTED
 WHEN DETERMINING THE NUMBER OF ACCESSIBLE MEANS OF
 ENTRY REQUIRED.
 COMMUNITY POOLS THAT ARE ASSOCIATED WITH A PRIVATE
 RESIDENTIAL COMMUNITY THAT DO NOT RECEIVE GOVERNMENTAL
 FINANCIAL ASSISTANCE OR SPONSORSHIP AND ARE LIMITED TO
 THE EXCLUSIVE OF RESIDENTS AND THEIR GUESTS ARE NOT
 COVERED BY THE ADA ACCESSIBILITY REQUIREMENTS,
 INCLUDING PROVISIONS FOR POOL LIFTS OR SLOPED ENTRIES.
 IF A SWIMMING POOL LOCATED IN A RESIDENTIAL COMMUNITY
 IS MADE AVAILABLE TO THE PUBLIC FOR RENTAL OR USE IT IS
 REQUIRED TO COMPLY WITH TITLE II OF THE ADA. SPECIFY ON
 THE PLANS THE FORMER OR SHOW COMPLIANCE WITH THE LATTER
 STATEMENTS. SEE DECLARATORY STATEMENT, DS 2013-011.
  
 1009.1 GENERAL. WHERE PROVIDED, POOL LIFTS, SLOPED
 ENTRIES, TRANSFER WALLS, TRANSFER SYSTEMS, AND POOL
 STAIRS SHALL COMPLY WITH 1009.
 -IF POOL LIFTS ARE PROVIDED PLEASE ADD DETAILS TO THE
 ADA DETAIL SHEET.
 ALSO, ADD ANY ADDITIONAL DETAILS IF APPLICABLE TO ADA
 DETAILS FOR THE POOLS.
  
 27) NOT RESOLVED. PROVIDE DETAILS OF ALL RAMPS TO SHOW
 COMPLIANCE WITH ACCESSIBILITY REQUIREMENTS. THE MAXIMUM
 RAMP SLOPE IS 1:12 (8%). FBC ACCESSIBILITY SECTION 405.
 405.8 FBC[A]HANDRAILS.RAMP RUNS WITH A RISE GREATER
 THAN 6 INCHES (150 MM) SHALL HAVE HANDRAILS COMPLYING
 WITH 505.
 -SHEET ALS1.107 SHOWS RAMP FROM PRE-FUNCTION UP TO
 ELEVATORS AND STAIR ST8. WILL THERE BE RAILS PROVIDE
 THE RAMP AS REQUIRED? ALSO, IS THE WALKWAY FROM RAMP TO
 STAIR 8 GOING TO HAVE RAIL OR IS IT OPEN FROM ABOVE TO
 PRE-FUNCTION?
  
 CHAPTER 4 - HIGHRISE:
  
 28) RESOLVED. 403.5.3.1 FBC[B]STAIRWAY COMMUNICATION
 SYSTEM. A TELEPHONE OR OTHER TWO-WAY COMMUNICATIONS
 SYSTEM CONNECTED TO AN APPROVED CONSTANTLY ATTENDED
 STATION SHALL BE PROVIDED AT NOT LESS THAN EVERY FIFTH
 FLOOR IN EACH STAIRWAY WHERE THE DOORS TO THE STAIRWAY
 ARE LOCKED.
 -WILL THE DOORS BE LOCKED FROM THE STAIRWAY SIDE? IF SO
 PLEASE ADD COMMUNICATION SYSTEM AS REQUIRED IN
 403.5.3.1
  
 29) NOT RESOLVED. THERE ARE SEVERAL EXIT STAIRWAYS THAT
 ARE NOT CONTINUOUS FROM THE UPPER FLOORS TO THE LEVEL
 OF EXIT DISCHARGE AT THE GROUND FLOOR. THE PLANS SHOW
 THAT THE STAIRWAYS TRANSFER THROUGH A FIRE RATED
 "TRANSFER" CORRIDOR (EXIT PASSAGEWAY) TO ANOTHER
 STAIRWAY IN ORDER TO TRAVEL TO THE EXIT DISCHARGE.
 THERE ARE OPENINGS INTO THE CORRIDOR (EXIT PASSAGEWAY)
 TO AN AHU ROOM AND TWO MAINTENANCE/ACCESS ROOMS. PLEASE
 KEEP IN MIND THAT ONCE AN OCCUPANT ENTERS AN EXIT
 STAIRWAY THE EXPECTATION IS THAT THE OCCUPANT WILL HAVE
 THE SAME PROTECTION AS PROVIDED BY THE EXIT STAIRWAY
 UNTIL THEY REACH THE EXIT DISCHARGE. THE SAME
 REQUIREMENTS FOR THE STAIRWAY WILL APPLY TO THE
 TRANSFER CORRIDOR. NO OPENINGS, PENETRATIONS OR SYSTEMS
 OTHER THAN THOSE REQUIRED AS A PART OF THE EMERGENCY
 EGRESS SYSTEM AND THOSE THAT SERVICE THE STAIRWAY ARE
 ALLOWED. THERE IS ALSO A CONCERN THAT A DOUBLE DOOR
 THAT OPENS DIRECTLY TO THE PARKING GARAGE. PLEASE
 PROVIDE A NARRATIVE THAT EXPLAINS THE RATIONALE AND
 INTENTIONS FOR THE EXIT STAIRS THAT HAVE THIS DESIGN.
 FBC 1009 THE1022.8 FBC[B] DISCHARGE IDENTIFICATION. AN
 INTERIOR EXIT STAIRWAY AND RAMP SHALL NOT CONTINUE
 BELOW ITS LEVEL OF EXIT DISCHARGE UNLESS AN APPROVED
 BARRIER IS PROVIDED AT THE LEVEL OF EXIT DISCHARGE TO
 PREVENT PERSONS FROM UNINTENTIONALLY CONTINUING INTO
 LEVELS BELOW. DIRECTIONAL EXIT SIGNS SHALL BE PROVIDED
 AS SPECIFIED IN SECTION 1011.
 -IF STAIRWAY 4 AT 2 ND LEVEL TRANSFERS TO STAIRWAY 11
 THAN 1022.8 APPLIES.
  
 30) NOT RESOLVED. ADD NOTES TO PAGE 10.001 SHEET FR.001
 THAT SPECIFY THAT A MINIMUM OF TWO RISERS WILL BE
 PROVIDED AND THAT EACH RISER SHALL SUPPLY SPRINKLERS ON
 ALTERNATE FLOORS. 403.3.1 FBC[B]NUMBER OF SPRINKLER
 RISERS AND SYSTEM DESIGN. EACH SPRINKLER SYSTEM ZONE IN
 BUILDINGS THAT ARE MORE THAN 420 FEET (128 000 MM) IN
 BUILDING HEIGHT SHALL BE SUPPLIED BY NO FEWER THAN TWO
 RISERS. EACH RISER SHALL SUPPLY SPRINKLERS ON ALTERNATE
 FLOORS. IF MORE THAN TWO RISERS ARE PROVIDED FOR A
 ZONE, SPRINKLERS ON ADJACENT FLOORS SHALL NOT BE
 SUPPLIED FROM THE SAME RISER.
 -PLEASE SEE HOW THIS APPLIES TO OFFICE TOWER ONLY AND
 UPDATE FS DRAWINGS AS APPLICABLE.
  
 NEW COMMENTS:
  
 31) THERE ARE SOME SHEETS THAT ARE DUPLICATED AND THEY
 ARE NOT LISTED AS PREVIOUS VERSIONS OF THE SHEET. I AM
 NOT SURE WHY THIS HAPPENED. PERHAPS THEY WERE NAMED
 DIFFERENTLY WHEN RESUBMITTING. PLEASE REMOVE THE
 DUPLICATED SHEETS THAT ARE NOT VERSION-ED. CONTACT THE
 PERMIT LIBRARIAN IF YOU REQUIRE ASSISTANCE. FBC
 AMENDMENTS 107
  
 32) SHOW COMPLIANCE WITH FBC 403.4.5 EMERGENCY
 RESPONDER RADIO COVERAGE SHALL BE PROVIDED IN
 ACCORDANCE WITH THE FLORIDA FIRE PREVENTION CODE. THIS
 TYPICALLY REQUIRES A BI-DIRECTIONAL ANTENNA (BDA
 SYSTEM) OR SOME OTHER APPROVED METHOD.
  
 33) NOTE #4 ON SHEET ALS1.100 IS APPARENTLY FOR ANOTHER
 PROJECT. IT SPECIFIES OCEAN DRIVE AND HEATHER DRIVE AS
 EMERGENCY STAGING AREAS. PLEASE CORRECT. FBC AMENDMENTS
 107.2.1
  
 34) ON PAGE 04.016 - ALS1.116, THE RESIDENTIAL ELEVATOR
 MACHINE ROOM LIFE SAFETY PLAN IS NOT CLEAR. IT APPEARS
 THAT THE PATH OF TRAVEL IS GOING THROUGH WALLS. PLEASE
 CLARIFY. FBC AMENDMENTS 107.2.1
  
 35) ON PAGE 04.024 -ALS1.109, SHOW THE TOTAL OCCUPANT
 LOAD OF THE TERRACE AND PICKLE BALL COURTS, THE LOADS
 AT EACH EXIT DOOR AND THE COMBINED LOADS AT THE HOTEL
 AND RESIDENT EXIT STAIRWAYS. FBC 1004
  
 36) ON SHEET A7.700 THERE APPEARS TO BE A WALL SHOWN IN
 THE CENTER OF THE SCREEN ROOM THAT IS RUNNING THROUGH
 SOME OF THE SEATING. PLEASE CLARIFY. FBC 107.2.1
  
 37) ON SHEET A0.001, GENERAL NOTES 6-10 ARE MISSING.
 PLEASE CLARIFY. FBC AMENDMENTS 107.2.1
  
 38) ALSO ON SHEET A0.001, GENERAL NOTE 15 SHOULD
 REFERENCE ASCE 7-10, RATHER THAN ASCE 7-88. FBC CHAPTER
 35.
  
 39) FBC ACCESSIBILITY 505.10.3 REQUIRES THE HANDRAIL
 EXTENSIONS AT THE BOTTOM OF STAIRS TO EXTEND AT THE
 SLOPE OF THE STAIRFLIGHT FOR THE LENGTH OF A STAIR
 TREAD BEFORE RETURNING TO THE WALL, FLOOR OR POST.
  
 40) THE STAIR DETAIL DRAWINGS THAT START ON PG
 03.208-A5.101 APPEAR TO HAVE SOME ISSUES. PLEASE REVIEW
 THE MINIMUM 44" STAIRWAY WIDTH REQUIRED BY FBC 1009.4.
 THE 3'-8" RADIUS AT THE STAIR LANDINGS IN SOME OF THE
 DETAILS ARE INCORRECT.
  
 41) ON PAGE 04.002 - ALS1.101, EXIT PASSAGEWAY 0158 IS
 SHOWN WITH A ONE HOUR FIRE RATED WALL AND A 45 MINUTE
 FIRE RATED DOOR. FBC 1023 REQUIRES EXIT PASSAGEWAY
 ENCLOSURES TO HAVE WALLS, FLOORS AND CEILINGS OF NOT
 LESS THAN THAT REQUIRED FOR ANY CONNECTING INTERIOR
 EXIT STAIRWAY OR RAMP. SINCE THE CONNECTING STAIRWAY
 HAS A TWO HOUR FIRE RATING, THIS PASSAGEWAY IS ALSO
 REQUIRED TO HAVE A TWO HOUR FIRE RATING AND A 90 MINUTE
 FIRE RATED DOOR.
  
 42) THE BUILDING OFFICIAL HAS DETERMINED THAT WHEN CAR
 CHARGING STATIONS ARE PROVIDED, AT LEAST ONE ACCESSIBLE
 EV CHARGING STATION IS TO BE PROVIDED FOR EVERY 25
 TOTAL EV CHARGING STATIONS. THE ACCESSIBLE EV CHARGING
 STATIONS CAN BE LOCATED WITH THE OTHERS.
  
 43) I DID NOT SEE THE DETAILS/ELEVATIONS OF BUILT-IN
 ITEMS IN THE COMMON USE AREAS, SUCH AS RECEPTION DESKS,
 SERVICE COUNTERS, BREAK ROOM KITCHENS, ETC. THAT ARE
 REQUIRED TO BE ACCESSIBLE PER FBC ACCESSIBILITY
 CHAPTERS 8 AND 9. PLEASE INDICATE SHEETS THEY ARE ON OR
 PROVIDE SHEETS WITH DETAILS AND ELEVATIONS FOR THESE
 ITEMS.
  
 44) NOTE: ADDITIONAL COMMENTS MAY RESULT FROM THE
 RESPONSES TO THESE PLAN REVIEW COMMENTS.
  
 -PROVIDE COMMENT RESPONSE SHEET TO EXPLAIN HOW EACH
 COMMENT IS BEING ADDRESSED.
 -FEEL FREE TO CONTACT ME AT 561-805-6714 (M-F 8-5) TO
 DISCUSS COMMENTS, OR E-MAIL ANYTIME [email protected]
  
 NOTE: SEPARATE PERMITS (APPLICATIONS, PLANS, AND FEES)
 ARE REQUIRED FOR:
 LIGHT POLES/SITE LIGHTING
 FIRE ALARM
 FIRE SPRINKLER
 LOW VOLTAGE
 ACCESS
 LANDSCAPING
 IRRIGATION
 PARKING LOT
 SWIMMING POOLS AND SPAS
 GENERATORS
 ALL OTHER ITEMS OTHER THAN BMEP
  
  
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2020-03-11 Cont ID  
Sent By dbattles Date 2020-03-11 Time 09:12 Rev Time 0.00
Received By dbattles Date 2020-02-18 Time 07:38 Sent To  
Notes
2020-03-11 09:14:02BUILDING REVIEW COMMENTS:
  
 W.P.B. PERMIT: 18100540
 BUILDING PERMIT 30 STORY BLDG W/ TWO TOWERS
 1 ST REVIEW: APRIL 18, 2019
 2 ND REVIEW: MARCH 2, 2020
  
 DYLAN BATTLES
 BUILDING PLANS EXAMINER PX4191
 [email protected]
 561-805-6718
  
 FLORIDA BUILDING CODE,5TH EDITION (2014)
 FBC[AMENDED] = 2014 CHAPTER 1 WPB AMENDMENTS (SEE LINK
 BELOW)
 HTTPS://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/
 BUILDING-PERMIT-FORMS
 FBC[B] = FBC BUILDING
 FBC[EXISTING] = FBC EXISTING BUILDING
 FBC[A] = FBC ACCESSIBILITY
 FBC[E] = FBC ENERGY CONSERVATION
 FBC[R] = FBC RESIDENTIAL
  
 1) 107.5.3 FBC[AMENDED]PLEASE UPDATE SHEET A0.102 SITE
 DATA. THE DIAGRAM IN THE UPPER RIGHT CORNER DOESN'T
 REFLECT THE CHANGES IN ROOMS SHOWN IN THE PLANS.
 COMPARE SHEET A1.500 FOR SUITE AND UNIT COUNTS.
  
 A) AS A GENERAL COMMENT, PLEASE LOOK IN PROJECTDOX AND
 NOTE IF SOME SHEETS MAY NOT HAVE BEEN REPLACED FOR
 SECOND REVIEW. EITHER UPLOAD REVISED SHEETS, LEAVE IT
 DIDN'T CHANGE OR REQUEST IT TO BE DELETED.
  
 B) LEVEL 8 - SHEET A1.260. IS THE COLUMN LAYER TURNED
 OFF? ALSO, MISSING UNIT NUMBER ABOVE UNIT B1 08-22
 THIS SHEET WAS NOT REVISED FROM FIRST REVIEW SO I THINK
 IT REFLECTS OLD LAYOUT. PLEASE UPLOAD NEW LEVEL 8
 RESIDENTIAL SHEET.
  
 C) LEVEL 13-14 - 08 UNITS EACH FLOOR . SHEET A1.265
 SAYS LEVEL 13-14, BUT THEN THE NEXT SHEET IS LEVEL 14.
 PLEASE ADJUST TITLE BLOCK TO STATE LEVEL 13 ONLY.
  
 D) LEVEL 14 - 08 UNITS. SHEET A1.266 IS THE COLUMN
 LAYER TURNED OFF? ALSO, MISSING UNIT NUMBERS.
  
 E) LEVEL 3 - MISSING SUITE NUMBER NEXT TO SUITE 7.1 ON
 SHEET A1.103. LOOKS LIKE IT SHOULD BE SUITE 8.
  
 F) LEVEL 9 - MISSING SUITE NUMBER NEXT BETWEEN SUITE
 1.3B AND 1.3D ON SHEET A1.109
  
 G) LEVEL 16 - SUITE 2B ADA LOOKS LIKE WALL WAS LEFT
 BETWEEN ENTRY AND SLEEPING AREA.
  
 H) LEVEL 17, I CAN'T FIND OFFICE LEVEL FLOOR PLAN. I DO
 SEE RCP AND LIFE SAFETY. PLEASE CHECK IF IT WAS LOADED
 INTO PROJECT DOX.
  
 2) 107.5.3 FBC[AMENDED]SHEET 03.052 - A1.240 - HOTEL
 TOWER FLOOR PLAN - LEVEL 8 HAS NOT BEEN UPDATED. PLEASE
 UPLOAD A NEW VERSION, OR REQUEST IT BE DELETED FROM THE
 FOLDER. LEVEL EIGHT IS SHOWN ON PODIUM LEVEL 8 DRAWING
 03.014 - A1.108 - PODIUM FLOOR PLAN AND IN QUADRANT
 PAGES AS WELL.
 3) 107.5.3 FBC[AMENDED]PLEASE ADD COMMUNICATION SYMBOL
 TO SUITE 4.2B ON SHEET A1.243
 ROOM SUMMARY SHEET STATES LEVEL 12-15 AS COMMUNICATION.
 PLEASE ADD SYMBOL TO THOSE ROOMS AS WELL.
 ADD BOTH SYMBOLS TO SUITE 2.B ON SHEET A1.246
 PLEASE LOOK AT MOBILITY FEATURES DATA LAST LINE WHERE
 IT SAYS LEVEL 8-16 SUITE 4.2B. I DO SEE THAT THERE IS
 ADA ON LEVEL 16. ADD SYMBOLS AND CORRECT WHERE IT
 STATES 8-16 OR SHOW THAT LEVEL 8-15 SUITE 4.2B ARE ADA
 SUITES.
  
 4) 224.5 FBC[A]DISPERSION. GUEST ROOMS REQUIRED TO
 PROVIDE MOBILITY FEATURES COMPLYING WITH 806.2 AND
 GUEST ROOMS REQUIRED TO PROVIDE COMMUNICATION FEATURES
 COMPLYING WITH 806.3 SHALL BE DISPERSED AMONG THE
 VARIOUS CLASSES OF GUEST ROOMS, AND SHALL PROVIDE
 CHOICES OF TYPES OF GUEST ROOMS, NUMBER OF BEDS, AND
 OTHER AMENITIES COMPARABLE TO THE CHOICES PROVIDED TO
 OTHER GUESTS.WHERE THE MINIMUM NUMBER OF GUEST ROOMS
 REQUIRED TO COMPLY WITH 806 IS NOT SUFFICIENT TO ALLOW
 FOR COMPLETE DISPERSION, GUEST ROOMS SHALL BE DISPERSED
 IN THE FOLLOWING PRIORITY: GUEST ROOM TYPE, NUMBER OF
 BEDS, AND AMENITIES. AT LEAST ONE GUEST ROOM REQUIRED
 TO PROVIDE MOBILITY FEATURES COMPLYING WITH 806.2 SHALL
 ALSO PROVIDE COMMUNICATION FEATURES COMPLYING WITH
 806.3. NOT MORE THAN 10 PERCENT OF GUEST ROOMS REQUIRED
 TO PROVIDE MOBILITY FEATURES COMPLYING WITH 806.2 SHALL
 BE USED TO SATISFY THE MINIMUM NUMBER OF GUEST ROOMS
 REQUIRED TO PROVIDE COMMUNICATION FEATURES COMPLYING
 WITH 806.3.
 -ONLY 10 PERCENT OF REQUIRED ROOMS CAN SHARE
 COMMUNICATION AND MOBILITY. PLEASE SHOW COMMUNICATION
 ROOMS ONLY SHARE IN ONE SUITE.
 -PLEASE VERIFY THAT ROOMS ARE EVENLY DISTRIBUTED FOR
 ROOM TYPES AND PRICE RANGE.
  
 5) 806.4 FBC[A]HOTEL,MOTEL AND CONDOMINIUM SPECIAL
 ACCESSIBILITY FEATURES. THIS SECTION DOES NOT RELIEVE
 THE OWNER OF THE RESPONSIBILITY OF PROVIDING ACCESSIBLE
 ROOMS IN CONFORMANCE WITH SECTION 224 AND 806 OF THIS
 CODE. IN ALL BUILDINGS, STRUCTURES AND FACILITIES
 LICENSED AS A HOTEL, MOTEL OR RESORT CONDOMINIUM
 PURSUANT TO CHAPTER 509, F.S., A NUMBER OF ROOMS
 EQUALING AT LEAST 5 PERCENT OF THE GUEST ROOMS MINUS
 THE TOTAL NUMBER OF REQUIRED (ACCESSIBLE) ROOMS
 REQUIRED BY TABLE 224.2 SHALL PROVIDE THE FOLLOWING
 ADDITIONAL SPECIAL ACCESSIBILITY FEATURES:
 (I) GRAB RAILS IN BATHROOMS AND TOILET ROOMS WHICH
 COMPLY WITH SECTION 604.5.
 (II) ALL BEDS IN DESIGNED ACCESSIBLE GUEST ROOMS SHALL
 BE OPEN-FRAME TYPE THAT ALLOWS THE PASSAGE OF LIFT
 DEVICES.
 (III)WATER CLOSETS THAT COMPLY WITH SECTION 604.4.
 -SHOW WHICH ROOMS COMPLY WITH 806.4
  
 6) 224.1 ADVISORY FBC[A]ARE THERE NON-TRANSIENT ROOMS
 (MORE THAN 30 DAY STAY)?
 IF SO, THOSE ROOMS MAY FALL UNDER THE FAIRHOUSING
 GUIDELINES IN ADDITION TO ACCESSIBILITY FBC 2017 6 TH
 EDITION.
  
 FAIRHOUSING REVIEW:
 7) 1986 ANSI [A117.1] IF A DESIGNER OR BUILDER CHOOSES
 TO FOLLOW AN ACCESSIBILITY STANDARD OTHER THAN THE 1986
 ANSI A117.1 STANDARD, OR A MORE RECENT VERSION OF THE
 ANSI A117.1, SUCH AS THE 1992 CABO/ANSI, THAT CARE BE
 TAKEN TO ENSURE THE STANDARD USED IS AT LEAST
 EQUIVALENT TO OR STRICTER THAN THE 1986 ANSI A117.1
 STANDARD.
 -WHAT STANDARD IS BEING APPLIED FOR COMPLIANCE WITH
 FAIR HOUSING? YOU CAN USE GUIDELINES THAT FALL WITHIN
 THE SAFE HARBOR FOR COMPLIANCE?
  
 A) IT WOULD BE HELPFUL TO ADD A MATRIX OF ROOMS ON
 SHEET A1.500 WHICH BATHROOM SPEC IS BEING USED AND
 APPLY THE FOLLOWING FOR SPEC A AND B
  
 SPECIFICATION A:
 IF SPECIFICATION A IS USED IT APPLIES TO ALL BATHROOMS,
 AND ALL FIXTURES IN THOSE BATHROOMS MUST BE USABLE.
 SPECIFICATION B:
 IF SPECIFICATION B IS USED, IT APPLIES TO ONE BATHROOM,
 AND ONLY ONE OF EACH TYPE OF FIXTURE MUST BE USABLE;
 ADDITIONAL BATHROOMS IN THE UNIT ARE EXEMPT ONLY FROM
 MANEUVERING AND CLEAR FLOOR SPACE REQUIREMENTS AT
 FIXTURES.
  
 B) PLEASE ADD TO FAIRHOUSING NOTES ON SHEET A1.528.
 THIS SAYS ALL BATHROOMS TO BE SPEC A. PLEASE ADJUST
 NOTE SINCE BOTH SPEC ARE BEING USED.
  
 C) ADD NOTE FOR USABLE HARDWARE.
 REQUIREMENT 3 - USABLE DOORS. THE DOORS IN COMMON
 SPACES AND THE SIDE ENTERING INTO DWELLING UNITS NEED
 TO HAVE USABLE HARDWARE THAT CAN BE USED WITHOUT TIGHT
 GRASPING OR TWISTING.
 -TYPICALLY THE HARDWARE WOULD BE A LEVER TYPE. THIS
 TYPE OF HARDWARE WOULD NOT BE REQUIRED ONCE INSIDE THE
 UNIT. YOU MAY WANT TO CLARIFY HARDWARE ON THE DOOR
 SCHEDULE.
  
 D) DOOR SCHEDULE ON SHEET A6.104 IS DISTORTED AND
 INFORMATION IS NOT LEGIBLE. PLEASE ADJUST AND POPULATE
 AS NEEDED.
  
 E) SHOW ACCESSIBLE ROUTES FOR EACH UNIT TYPE.
  
 F) ADD DETAIL OF HOW ACCESS IS GAINED AT RESIDENTIAL
 BALCONY. IS THERE ELEVATION CHANGE TO MEET FAIRHOUSING
 MAX OF 4 INCHES TOP OF THRESHOLD?
  
 LIFE SAFETY:
  
 8) 3006.2 FBC[B]SHEET A1.107 SHOWS NO ELEVATOR LOBBY ON
 LEVEL 7 AT ELEVATORS 8, 9 AND 10. IF REQUIRED PLEASE
 SHOW THE DOORS.
 1024.4 FBC[B]TERMINATION. EXIT PASSAGEWAYS ON THE LEVEL
 OF EXIT DISCHARGE SHALL TERMINATE AT AN EXIT DISCHARGE.
 EXIT PASSAGEWAYS
 ON OTHER LEVELS SHALL TERMINATE AT AN EXIT.
 EXIT DISCHARGE. THAT PORTION OF A MEANS OF EGRESS
 SYSTEM BETWEEN THE TERMINATION OF AN EXIT AND A PUBLIC
 WAY.
  
 9) 3005.5 FBC[B]SHUNT TRIP. WHERE ELEVATOR HOISTWAYS,
 ELEVATOR MACHINE ROOMS, CONTROL ROOMS AND CONTROL
 SPACES CONTAINING ELEVATOR CONTROL EQUIPMENT ARE
 PROTECTED WITH AUTOMATIC SPRINKLERS, A MEANS INSTALLED
 IN ACCORDANCE WITH SECTION 21.4 OF NFPA 72 SHALL BE
 PROVIDED TO DISCONNECT AUTOMATICALLY THE MAIN LINE
 POWER SUPPLY TO THE AFFECTED ELEVATOR PRIOR TO THE
 APPLICATION OF WATER. THIS MEANS SHALL NOT BE
 SELF-RESETTING. THE ACTIVATION OF AUTOMATIC SPRINKLERS
 OUTSIDE THE HOISTWAY, MACHINE ROOM, MACHINERY SPACE,
 CONTROL ROOM OR CONTROL SPACE SHALL NOT DISCONNECT THE
 MAIN LINE POWER SUPPLY.
  
 10) 3006.2 FBC[B]HOISTWAY OPENING PROTECTION REQUIRED.
 ELEVATOR HOISTWAY DOOR OPENINGS SHALL BE PROTECTED IN
 ACCORDANCE WITH SECTION 3006.3 WHERE AN ELEVATOR
 HOISTWAY CONNECTS MORE THAN THREE STORIES, IS REQUIRED
 TO BE ENCLOSED WITHIN A SHAFT ENCLOSURE IN ACCORDANCE
 WITH SECTION 712.1.1 AND ANY OF THE FOLLOWING
 CONDITIONS APPLY:
 5. THE BUILDING IS A HIGH RISE AND THE ELEVATOR
 HOISTWAY IS MORE THAN 75 FEET (22 860 MM) IN HEIGHT.
 THE HEIGHT OF THE HOISTWAY SHALL BE MEASURED FROM THE
 LOWEST FLOOR TO THE HIGHEST FLOOR OF THE FLOORS SERVED
 BY THE HOISTWAY.
 -IS THE PRE FUNCTION AREA OPEN AIR? IT IS HARD TO TELL
 BUT IT APPREARS TO BE COVERED BY RESIDENTIAL ABOVE.
 -FREIGHT ELEVATOR DOES NOT HAVE ELEVATOR LOBBY ON THE 8
 TH FLOOR. PLEASE REVIEW 3006.2 FOR OPENING PROTECTION
 ON SHAFT MORE THAN 75 FEET.
  
 11) 107.5.3 FBC[AMENDED]ADD SCALE TO LIFE SAFETY PLANS.
 I THINK IT IS 1/16 SCALE.
 ALSO, IS THERE A LIFE SAFETY SHEET FOR THE PARK ABOVE
 THE TENNIS PAVILION? PLEASE PROVIDE OR LET ME KNOW
 WHICH SHEET I CAN FIND IT.
  
 12) 1004 FBC[B]PLEASE PROVIDE TOTAL OCCUPANT LOAD FOR
 EACH EGRESS DOOR AT GRADE WHERE THE DOOR PROVIDES
 EGRESS FROM MULTIPLE AREAS. FOR EXAMPLE EGRESS DOORS IN
 HOTEL LOBBY PICKUP THE STAIRS AND OTHER AREAS FROM
 FIRST LEVEL USES. I AM LOOKING FOR DATA TAG LIKE WAS
 USED AT STAIRWAY DOORS.
  
 13) 1025.1 FBC[B]GENERAL. APPROVED LUMINOUS EGRESS PATH
 MARKINGS DELINEATING THE EXIT PATH SHALL BE PROVIDED IN
 HIGH-RISE BUILDINGS OF GROUP A, B, E, I, M, AND R-1
 OCCUPANCIES IN ACCORDANCE WITH SECTIONS 1025.1 THROUGH
 1025.5.
 -ST4 AND ST3 FROM R-1 LEVELS TO MEET 1025.1 FOR
 LUMINOUS MARKINGS.
  
 14) 1013.2 FBC[B] FLOOR-LEVEL EXIT SIGNS IN GROUP R-1.
 WHERE EXIT SIGNS ARE REQUIRED IN GROUP R-1 OCCUPANCIES
 BY SECTION 1013.1, ADDITIONAL LOW-LEVEL EXIT SIGNS
 SHALL BE PROVIDED IN ALL AREAS SERVING GUEST ROOMS IN
 GROUP R-1 OCCUPANCIES AND SHALL COMPLY WITH SECTION
 1013.5.
 -ADD LOW LEVEL EXIT SIGNS AS REQUIRED, OR STATE WHICH
 PAGE THIS INFORMATION CAN BE FOUND.
  
 15) 107.3.5 FBC[AMENDED] MINIMUM REVIEW CRITERIA. THIS
 IS FOR ALL LIFE SAFETY SHEETS
 A. ADD MAX COMMON PATH AND MAX TRAVEL DISTANCE FOR R-1
 AND R-2 TO ALS1.100 COMPLIANCE SUMMARY FOR FLORIDA
 BUILDING CODE IN ADDITION TO THE PROVIDED NFPA. THE
 MORE RESTRICTIVE CODE WILL APPLY.
 B. SHOW MAXIMUM PATH OF TRAVEL ON ALL L.S. PLANS.
 CURRENTLY, L.S. SHEETS SHOW PATH OF TRAVEL DISTANCE OR
 TOTAL DISTANCE. PLANS SHOULD SHOW BOTH COMMON PATH OF
 TRAVEL AND EXIT ACCESS TRAVEL DISTANCE. THIS SHOULD BE
 DONE FOR WORST CASE IN EACH GENERAL AREA.
  
 16) 1003.5 FBC[B] ELEVATION CHANGE. DOES EXIT FROM
 RESIDENT LOBBY TO STAIR 2 HAVE STEPS? PLEASE REVIEW
 -HOW DO STEPS WORK AT EGRESS FROM RESIDENT LOUNGE TO
 STAIR ST2? PLEASE REVIEW 1003.5 FOR CHANGE IN ELEVATION
 IN PATH OF EGRESS.
  
 17) 1012.9 FBC[B] INTERMEDIATE HANDRAILS. STAIRWAYS
 SHALL HAVE INTERMEDIATE HANDRAILS LOCATED IN SUCH A
 MANNER THAT ALL PORTIONS OF THE STAIRWAY MINIMUM WIDTH
 OR REQUIRED CAPACITY ARE WITHIN 30 INCHES (762 MM) OF A
 HANDRAIL. ON MONUMENTAL STAIRS, HANDRAILS SHALL BE
 LOCATED ALONG THE MOST DIRECT PATH OF EGRESS TRAVEL.
 -CHECK COMPLIANCE WITH 1012.9 AT BALLROOM STEPS.
  
 18) 713.13.4 CHUTE DISCHARGE ROOM. WASTE OR LINEN
 CHUTES SHALL DISCHARGE INTO AN ENCLOSED ROOM SEPARATED
 BY FIRE BARRIERS WITH A FIRE RESISTANCE RATING NOT LESS
 THAN THE REQUIRED FIRE RATING OF THE SHAFT ENCLOSURE
 AND CONSTRUCTED IN ACCORDANCE WITH SECTION 707 OR
 HORIZONTAL ASSEMBLIES CONSTRUCTED IN ACCORDANCE WITH
 SECTION 711, OR BOTH. OPENINGS INTO THE DISCHARGE ROOM
 FROM THE REMAINDER OF THE BUILDING SHALL BE PROTECTED
 BY OPENING PROTECTIVES HAVING A FIRE PROTECTION RATING
 EQUAL TO THE PROTECTION REQUIRED FOR THE SHAFT
 ENCLOSURE. DOORS SHALL BE SELF- OR AUTOMATICCLOSING
 UPON THE DETECTION OF SMOKE IN ACCORDANCE WITH SECTION
 716.5.9.3. WASTE CHUTES SHALL NOT TERMINATE IN AN
 INCINERATOR ROOM. WASTE AND LINEN ROOMS THAT ARE NOT
 PROVIDED WITH CHUTES NEED ONLY COMPLY WITH TABLE 509.
 -DOUBLE DOORS TO TRASH ROOM AT BASE LEVEL SHOW 90
 MINUTE RATING, BUT 713.13.4 REQUIRES SAME LEVEL OF
 PROTECTION FOR OPENINGS IN DISCHARGE ROOM EQUAL TO THE
 SHAFT ENCLOSURE (2 HOURS).
  
 19) 420.3 FBC[B]HORIZONTAL SEPARATION AND FBC[B] 602
 FLOOR ASSEMBLIES SEPARATING DWELLING UNITS IN THE SAME
 BUILDINGS, FLOOR ASSEMBLIES SEPARATING SLEEPING UNITS
 IN THE SAME BUILDING AND FLOOR ASSEMBLIES SEPARATING
 DWELLING OR SLEEPING UNITS FROM OTHER OCCUPANCIES
 CONTIGUOUS TO THEM IN THE SAME BUILDING SHALL BE
 CONSTRUCTED AS HORIZONTAL ASSEMBLIES IN ACCORDANCE WITH
 SECTION 711.
 -602 FBC[B]SHEET A7.310 HAS CEILING ASSEMBLIES. PLEASE
 SHOW THE RATED ASSEMBLY FOR CEILINGS SEPARATING
 DWELLING AND SLEEPING UNITS AS STATED IN LIFE SAFETY
 COMPLIANCE SUMMARY ALS1.100.
  
 20) 713.13.3 FBC[B]CHUTE ACCESS ROOMS. ACCESS OPENINGS
 FOR WASTE OR LINEN CHUTES SHALL BE LOCATED IN ROOMS OR
 COMPARTMENTS ENCLOSED BY NOT LESS THAN 1-HOUR FIRE
 BARRIERS CONSTRUCTED IN ACCORDANCE WITH SECTION 707 OR
 HORIZONTAL ASSEMBLIES CONSTRUCTED IN ACCORDANCE WITH
 SECTION 711, OR BOTH. OPENINGS INTO THE ACCESS ROOMS
 SHALL BE PROTECTED BY OPENING PROTECTIVES HAVING A FIRE
 PROTECTION RATING OF NOT LESS THAN 3/4 HOUR. DOORS
 SHALL BE SELF- OR AUTOMATIC-CLOSING UPON THE DETECTION
 OF SMOKE IN ACCORDANCE WITH SECTION 716.5.9.3.
 -LIFE SAFETY SHEETS SHOW CHUTE ACCESS DOORS AS NOT
 RATED (NR). THESE ACCESS DOORS ARE REQUIRED TO HAVE A
 3/4 HOUR RATING PER 713.13.3.
 - ADD DOOR TAG TO THE DOORS LEADING TO THE TRASH CHUTE
 OR TELL ME WHAT SHEETS THER ARE ON. I WAS LOOKING ON
 QUADRANT SHEETS WHERE THE OTHER TAGS FOR COMMON SPACE
 DOORS WERE LOCATED.
  
 DEFERRED SUBMITTALS
 21) 107.3.4.1 FBC[AMENDED]PLEASE PROVIDE A LIST OF
 DEFERRED SUBMITTALS ON PLANS SO THAT I WILL NOT ASK FOR
 ITEMS THAT WILL BE SUPPLIED AT A LATER DATE, OR
 INDICATE WHICH PAGE A LIST CAN BE FOUND.
 THESE ARE THE ONES I BELIEVE WE WILL NEED, BUT THIS IS
 NOT A COMPLETE LIST.
 A) COMPONENT & CLADDING PRODUCT APPROVALS (COMPLY WITH
 PRESSURES SHOWN ON SHEET S0.0.5)
 B) CURTAIN WALL SUBMITTAL (COMPLY WITH PRESSURES SHOWN
 ON SHEET S0.0.5)
 C) FENESTRATION SHOP DRAWINGS TO INCLUDE ALL WINDOWS,
 DOORS, TRANSOMS, SLIDERS, LOUVERS AND MULL BARS.
 D) FLOORING UNDERLAYMENT WITH THREE REPORTS:
 1. 1207.2 FBC[B] AIR-BORNE SOUND. WALLS, PARTITIONS AND
 FLOOR/CEILING ASSEMBLIES SEPARATING DWELLING UNITS AND
 SLEEPING UNITS FROM EACH OTHER OR FROM PUBLIC OR
 SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS OF
 NOT LESS THAN 50, OR NOT LESS THAN 45 IF FIELD TESTED,
 FOR AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM
 E90.
 2. 1207.3 FBC[B] STRUCTURE-BORNE SOUND. FLOOR/CEILING
 ASSEMBLIES BETWEEN DWELLING UNITS AND SLEEPING UNITS OR
 BETWEEN A DWELLING UNIT OR SLEEPING UNIT AND A PUBLIC
 OR SERVICE AREA WITHIN THE STRUCTURE SHALL HAVE AN
 IMPACT INSULATION CLASS RATING OF NOT LESS THAN 50, OR
 NOT LESS THAN 45 IF FIELD TESTED, WHEN TESTED IN
 ACCORDANCE WITH ASTM E492.
 3. 603.1 FBC[B] ALLOWABLE MATERIALS IN NON COMBUSTIBLE
 BUILDINGS, SEE ITEM 2, EXCEPTION 2, ACOUSTICAL
 INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID
 DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED
 TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200. SEE
 803.1.1, PROVIDE TEST DATA IN ACCORDANCE WITH ASTM E 84
 OR UL 723.
 E) RAILINGS AND GUARDRAILS. INCLUDES BALCONIES, STAIRS
 AND COMMON SPACES.
 F) PARKING GARAGE VEHICLE BARRIER PER 406.4.2 FBC[B]
 G) FIRE SPRAY
 H) 806.1 FBC[B] GENERAL REQUIREMENTS. CURTAINS,
 DRAPERIES, HANGINGS AND OTHER DECORATIVE MATERIALS
 SUSPENDED FROM WALLS OR CEILINGS SHALL MEET THE FLAME
 PROPAGATION PERFORMANCE CRITERIA OF NFPA 701 IN
 ACCORDANCE WITH SECTION 806.2 OR BE NONCOMBUSTIBLE.
 I) LIGHTWIEGHT CONCRETE.
 J) WINDOW WASHING EQUIPMENT ATTACHMENTS/LOCATIONS AT
 ROOF.
 K) E.F.I.S. IF APPLICABLE
 L) LIGHTING CONTROLS PER ENERGY CODE C405.2 LIGHTING
 CONTROLS (MANDATORY) C405.5 EXTERIOR LIGHTING
 (MANDATORY)
 M) FINAL GYM EQUIPMENT LAYOUT WITH ACCESSIBILTY
 REQUIREMENTS PROVIDED.
 PRODUCT APPROVALS FOR ROOFING ARE PROVIDED, BUT NO
 SELECTIONS ARE MADE AND IT IS NOT CLEAR WHICH AREA OF
 ROOF RECEIVE.
 ROOFING CAN BE ADDED TO DEFERRED SUBMITTAL LIST.
  
 22) ALSO, PROVIDE PRODUCT APPROVAL FOR ROOF INSULATION
 AND ATTACHMENT.
 OTHER PRODUCT APPROVALS WERE SUBMITTED FOR DOORS, BUT
 THEY WERE NOT STAMPED AS REVIEWED. AS PART OF
 FENESTRATION PACKAGE PROVIDE ALL PRODUCT APPROVALS WITH
 INDICATION THAT THEY WERE REVIEWED BY THE DESIGNER OF
 RECORD.
  
 23) ENERGY CODE REVIEW:
 A) THIS BUILDING WAS BROUGHT IN UNDER 2014 CODE CYCLE.
 PLEASE REVISE TO THAT CODE DATE, OR PROVIDE LETTER OF
 COMPLIANCE THAT CURRENT CODES ARE EQUIVALENT.
 B) C407.2.1 ROOF/CEILING THERMAL ENVELOPE. SECTIONS FOR
 ROOFING AND DOORS SHOW NO DATA. PLEASE INCLUDE THOSE
 VALUES IN THE ENERGY CALCULATIONS.
 C) IN SECTION FOR WALLS THE ASSEMBLY STATES 6 INCH
 INSULATION. WHERE IS THAT ASSEMBLY BEING USED ON THE
 BUILING?
  
 ACCESSIBILITY REVIEW:
 24) 803.1 FBC[A] GENERAL. DRESSING, FITTING, AND LOCKER
 ROOMS SHALL COMPLY WITH 803.
 803.2 FBC[A] TURNING SPACE. TURNING SPACE COMPLYING
 WITH 304 SHALL BE PROVIDED WITHIN THE ROOM.
 803.3 FBC[A] DOOR SWING. DOORS SHALL NOT SWING INTO THE
 ROOM UNLESS A CLEAR FLOOR OR GROUND SPACE COMPLYING
 WITH 305.3 IS PROVIDED BEYOND THE ARC OF THE DOOR
 SWING.
 803.4 FBC[A] BENCHES. A BENCH COMPLYING WITH 903 SHALL
 BE PROVIDED WITHIN THE ROOM.
 903.4 FBC[A] BACK SUPPORT. THE BENCH SHALL PROVIDE FOR
 BACK SUPPORT OR SHALL BE AFFIXED TO A WALL. BACK
 SUPPORT SHALL BE 42 INCHES LONG MINIMUM AND SHALL
 EXTEND FROM A POINT 2 INCHES MAXIMUM ABOVE THE SEAT
 SURFACE TO A POINT 18 INCHES MINIMUM ABOVE THE SEAT
 SURFACE. BACK SUPPORT SHALL BE 21/2 INCHES MAXIMUM FROM
 THE REAR EDGE OF THE SEAT MEASURED HORIZONTALLY.
  
 25) 236.1 FBC[A]GENERAL. AT LEAST ONE OF EACH TYPE OF
 EXERCISE MACHINE AND EQUIPMENT SHALL COMPLY WITH 1004.
  
 1004.1 FBC[A]CLEAR FLOOR SPACE. EXERCISE MACHINES AND
 EQUIPMENT SHALL HAVE A CLEAR FLOOR SPACE COMPLYING WITH
 305 POSITIONED FOR TRANSFER OR FOR USE BY AN INDIVIDUAL
 SEATED IN A WHEELCHAIR. CLEAR FLOOR OR GROUND SPACES
 REQUIRED AT EXERCISE MACHINES AND EQUIPMENT SHALL BE
 PERMITTED TO OVERLAP.
  
 ADVISORY 1004.1 FBC[A]CLEAR FLOOR SPACE. ONE CLEAR
 FLOOR OR GROUND SPACE IS PERMITTED TO BE SHARED BETWEEN
 TWO PIECES OF EXERCISE EQUIPMENT.TO OPTIMIZE SPACE USE,
 DESIGNERS SHOULD CAREFULLY CONSIDER LAYOUT OPTIONS SUCH
 AS CONNECTING ENDS OF THE ROW AND CENTER AISLE SPACES.
 THE POSITION OF THE CLEAR FLOOR SPACE MAY VARY GREATLY
 DEPENDING ON THE USE OF THE EQUIPMENT OR MACHINE. FOR
 EXAMPLE, TO PROVIDE ACCESS TO A SHOULDER PRESS MACHINE,
 CLEAR FLOOR SPACE NEXT TO THE SEAT WOULD BE APPROPRIATE
 TO ALLOW FOR TRANSFER. CLEAR FLOOR SPACE FOR A BENCH
 PRESS MACHINE DESIGNED FOR USE BY AN INDIVIDUAL SEATED
 IN A WHEELCHAIR, HOWEVER, WILL MOST LIKELY BE CENTERED
 ON THE OPERATING MECHANISMS.
  
 26) 1009.1 GENERAL. WHERE PROVIDED, POOL LIFTS, SLOPED
 ENTRIES, TRANSFER WALLS, TRANSFER SYSTEMS, AND POOL
 STAIRS SHALL COMPLY WITH 1009.
 -IF POOL LIFTS ARE PRVIDED PLEASE ADD DETAILS TO THE
 ADA DETAIL SHEET.
 ALSO, ADD ANY ADDITIONAL DETAILS IF APPLICABLE TO ADA
 DETAILS FOR THE POOLS.
  
 27) 405.8 FBC[A]HANDRAILS.RAMP RUNS WITH A RISE GREATER
 THAN 6 INCHES (150 MM) SHALL HAVE HANDRAILS COMPLYING
 WITH 505.
 -SHEET ALS1.107 SHOWS RAMP FROM PRE-FUNCTION UP TO
 ELEVATORS AND STAIR ST8. WILL THERE BE RAILS PROVIDE
 THE RAMP AS REQUIRED? ALSO, IS THE WALKWAY FROM RAMP TO
 STAIR 8 GOING TO HAVE RAIL OR IS IT OPEN FROM ABOVE TO
 PRE-FUNCTION?
  
 CHAPTER 4 ? HIGHRISE
 28) 403.5.3.1 FBC[B]STAIRWAY COMMUNICATION SYSTEM. A
 TELEPHONE OR OTHER TWO-WAY COMMUNICATIONS SYSTEM
 CONNECTED TO AN APPROVED CONSTANTLY ATTENDED STATION
 SHALL BE PROVIDED AT NOT LESS THAN EVERY FIFTH FLOOR IN
 EACH STAIRWAY WHERE THE DOORS TO THE STAIRWAY ARE
 LOCKED.
 -WILL THE DOORS BE LOCKED FROM THE STAIRWAY SIDE? IF SO
 PLEASE ADD COMMUNICATION SYSTEM AS REQUIRED IN
 403.5.3.1
  
 29) 1022.8 FBC[B] DISCHARGE IDENTIFICATION. AN INTERIOR
 EXIT STAIRWAY AND RAMP SHALL NOT CONTINUE BELOW ITS
 LEVEL OF EXIT DISCHARGE UNLESS AN APPROVED BARRIER IS
 PROVIDED AT THE LEVEL OF EXIT DISCHARGE TO PREVENT
 PERSONS FROM UNINTENTIONALLY CONTINUING INTO LEVELS
 BELOW. DIRECTIONAL EXIT SIGNS SHALL BE PROVIDED AS
 SPECIFIED IN SECTION 1011.
 -IF STAIRWAY 4 AT 2 ND LEVEL TRANSFERS TO STAIRWAY 11
 THAN 1022.8 APPLIES.
  
 30) 403.3.1 FBC[B]NUMBER OF SPRINKLER RISERS AND SYSTEM
 DESIGN. EACH SPRINKLER SYSTEM ZONE IN BUILDINGS THAT
 ARE MORE THAN 420 FEET (128 000 MM) IN BUILDING HEIGHT
 SHALL BE SUPPLIED BY NO FEWER THAN TWO RISERS. EACH
 RISER SHALL SUPPLY SPRINKLERS ON ALTERNATE FLOORS. IF
 MORE THAN TWO RISERS ARE PROVIDED FOR A ZONE,
 SPRINKLERS ON ADJACENT FLOORS SHALL NOT BE SUPPLIED
 FROM THE SAME RISER.
 -PLEASE SEE HOW THIS APPLIES TO OFFICE TOWER ONLY AND
 UPDATE FS DRAWINGS AS APPLICABLE.
  
 -PROVIDE COMMENT RESPONSE SHEET TO EXPLAIN HOW EACH
 COMMENT IS BEING ADDRESSED.
 -FEEL FREE TO CONTACT ME AT 561-805-6718 (M-F 8-5) TO
 DISCUSS COMMENTS, OR E-MAIL ANYTIME [email protected]
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2019-04-18 Cont ID  
Sent By dbattles Date 2019-04-18 Time 15:07 Rev Time 0.00
Received By dbattles Date 2019-03-26 Time 08:47 Sent To  
Notes
2019-04-18 15:07:33****CORRECTIONS****
 W.P.B. PERMIT: 18100540
 REVIEWED: APRIL 18, 2019
  
 DYLAN BATTLES
 BUILDING PLANS EXAMINER PX4191
 [email protected]
 561-805-6718
  
 FBC[AMENDED] = FLORIDA BUILDING CODE,5TH EDITION (2014)
 FBC[B] = FBC BUILDING
 FBC[A] = FBC ACCESSIBILITY
 FBC[E] = FBC ENERGY CONSERVATION
 FBC[R] = FBC RESIDENTIAL
  
 1) 107.2.1 FBC[B]DRAWINGS STATE THAT THEY ARE AT 80
 PERCENT.
  -A FULL REVIEW CANNOT BE PROVIDED UNTIL 100% PLANS ARE
 PROVIDED. THIS REVIEW IS BASED ON THE 80 PERCENT PLANS
 PROVIDED. WHEN RE-UPLOADING PLEASE ADD DIGITAL
 REPRESENTATION OF SEAL AND REMOVE 80% DESIGNATION.
  
 2) 107.2.1 FBC[AMENDED] PLACE A DIGITALLY CREATED IMAGE
 OF YOUR SEAL AND THE FOLLOWING SENTENCES WHERE AN
 ORIGINAL SIGNATURE WOULD APPEAR IF THE ITEM WERE BEING
 PHYSICALLY SIGNED DATED AND SEALED. THE SENTENCES CAN
 BE PART OF THE DIGITAL SIGNATURE CUSTOM APPEARANCE
 AVAILABLE IN THE SIGNING TOOL, OR THEY CAN BE PLACED ON
 THE DOCUMENT OUTSIDE OF THE DIGITAL SIGNATURE BLOCK.
 THIS ITEM HAS BEEN ELECTRONICALLY SIGNED AND SEALED BY
 [LICENSEE, RA, OR LS] ON THE DATE AND/OR TIME STAMP
 SHOWN USING A DIGITAL SIGNATURE.
  -SEE SIGNATURE REVIEW. CONTACT PERMIT LIBRARIAN OR
 BUILDING PLANS EXAMINER FOR OPTIONS TO SATISFY 107.2.1.
  
 3) 107.3.4.1 FBC[AMENDED] DEFERRED SUBMITTALS. FOR THE
 PURPOSES OF THIS SECTION, DEFERRED SUBMITTALS ARE
 DEFINED AS THOSE PORTIONS OF THE DESIGN THAT ARE NOT
 SUBMITTED AT THE TIME OF THE APPLICATION AND THAT ARE
 TO BE SUBMITTED TO THE BUILDING OFFICIAL WITHIN A
 SPECIFIED PERIOD. DEFERRAL OF ANY SUBMITTAL ITEMS SHALL
 HAVE THE PRIOR APPROVAL OF THE BUILDING OFFICIAL. THE
 REGISTERED DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE
 SHALL LIST THE DEFERRED SUBMITTALS ON THE CONSTRUCTION
 DOCUMENTS FOR REVIEW BY THE BUILDING OFFICIAL.
 DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE
 SUBMITTED TO THE REGISTERED DESIGN PROFESSIONAL IN
 RESPONSIBLE CHARGE WHO SHALL REVIEW THEM AND FORWARD
 THEM TO THE BUILDING OFFICIAL WITH A NOTATION
 INDICATING THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE
 BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO
 THE DESIGN OF THE BUILDING. THE DEFERRED SUBMITTAL
 ITEMS SHALL NOT BE INSTALLED UNTIL THE DEFERRED
 SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE BUILDING
 OFFICIAL.
  -PLEASE PROVIDE A LIST OF DEFERRED SUBMITTALS SO THAT
 I WILL NOT ASK FOR ITEMS THAT WILL BE SUPPLIED AT A
 LATER DATE, OR INDICATE WHICH PAGE A LIST CAN BE FOUND.
  
 4) 107.3.4.1 FBC[AMENDED] PRODUCT APPROVALS. PRODUCT
 APPROVALS ARE PROVIDED FOR WINDOWS, DOORS AND ROOFING.
  A. PLEASE INCULDE ON WINDOW AND DOOR SCHEDULES WHICH
 APPROVAL APPLIES TO EACH OPENING.
  B. NOTE ON ROOFING PLANS WHAT ROOF TYPE EACH AREA WILL
 RECEIVE. IF THESE APPROVALS WILL LIKELY CHANGE YOU MAY
 WANT TO DO ROOFING AS A DEFERRED SUBMITTAL. CHANGING
 ROOF SYSTEMS LATER MAY REQUIRE REVISION IF NOT
 SPECIFIED UP FRONT AS A DEFERRED SUBMITTAL.
  
 5) 107.3.5 FBC[AMENDED] MIN REVIEW CRITERIA. FLOOR
 PLANS FOR ALL RESIDENTIAL LEVELS ARE INCOMPLETE
 (ESPECIALLY ABOVE PODIUM LEVELS). MISSING WALL TYPES,
 DIMENSIONS, DOOR TYPES, OPENING SCHEDULES FINISHES AND
 DETAILS AS APPLICABLE.
  
 6) 107.3.5 FBC[AMENDED] MIN REVIEW CRITERIA.COMPLETE
 ADDING WALL TYPES FOR SOUND CONTROL BETWEEN PUBLIC
 AREAS AND OTHER WALLS AS APPLICABLE.
  
 7) 107.3.5 FBC[AMENDED]ARE BALCONIES SEPARATED? IF SO
 PROVIDE DETAILS.
  
 8) 107.3.5 FBC[AMENDED]SHEET A1.602 ENLARGED
 BATHROOMS.
  -TOILETS DO NOT SHOW UP ON THIS SHEET AND I THINK
 COLUMNS ARE TURNED OFF AS WELL. IS THIS SHEET GOING TO
 BE DIMENSIONED AND CLEAR SPACES SHOWN FOR ADA
 CLEARANCES?
  
 9) 107.3.5 FBC[AMENDED] GEOMETRY PLANS RESIDENTIAL WILL
 NEED TO BE COMPLETE BEFORE REVIEWING. A10.212 TO
 A10.255. OTHER GEOMETRY SHEETS MAT NEED TO BE COMPLETES
 AS WELL.
  
 10) 107.3.5 FBC[AMENDED] MEANS OF EGRESS
  -SHEETS A1.101, A1.202 AND ALS1.101 LOOKING AT
 REVOLVING DOORS IT APPEARS THAT A SMALL REVOLVING DOOR
 IS ON TOP OF LARGER REVOLVING DOOR IN TWO DOORS INTO
 HOTEL LOBBY. ALSO , THIS SMALLER REVOLVE APPEARS OVER
 DOUBLE DOORS NEAR VALET DROP OFF.
  
 11) 107.3.5 FBC[AMENDED] WHERE IS SAYS VALET DROP-OFF
 THERE IS A DIRECTION ARROW THAT MAKES IT APPERAR TO BE
 A ROADWAY. I DON'T SEE THE ARROW ON OTHER SHEETS, SO
 CHECK IF IT SHOULD BE REMOVED.
  
 12) 107.3.5 FBC[AMENDED]SOME DOORS HAVE NUMBERS LIKE
 267, 262 AND OTHERS ARE NOT NUMBERED. THE NUMBERS DO
 NOT CORESPOND TO NUMBERING SYSTEM ON THE DOOR
 SCHEDULE.
  -PLEASE TELL ME HOW THE DOORS CORESPOND TO THE DOOR
 SCHEDULE.
  
 13) ON ALL LIFE SAFETY SHEETS THE COLUMN LAYER DOESN'T
 SHOW UP ON DRAWINGS. IT MAKES THE PLANS TO APPEAR AS IF
 THERE ARE SPACES BETWEEN AREAS.
  A. PLEASE SHOW COLUMNS ON ALL LIFE SAFETY SHEET. ALSO,
 SHEET ALS1.114 AT ELEVATOR LOBBY IN RESIDENTIAL SIDE
 WITH THREE ELEVATOR BANKS LOOKS LIKE WALLS INSTEAD OF
 DOORS.
  B. SAME COMMENT FOR PLAN SHEETS A1.240 - A1.255 AND
 A1.260 - A1.272. PLEASE SHOW COLUMNS ON ALL SHEETS.
  
 14) 107.3.5 FBC[AMENDED] SHEET ALS1.114 CHECK UNIT A4
 OCCUPANCY SIZE AND COUNT
  A. ADJUST SQ. FOOTAGE OF UNIT AS 5,205 SF IS NOT
 CORRECT FOR THE UNIT.
  B. ADJUST OCCUPANCY COUNT TOTALS AS NEEDED.
  
 15) 107.3.5 FBC[AMENDED] SHEET A1.602SHOW DIMENSIONS ON
 ENLARGED BATHROOM PLANS.
  
  
 16) 107.3.5 FBC[AMENDED] MINIMUM REVIEW CRITERIA. THIS
 IS FOR ALL LIFE SAFETY SHEETS
  A. ADD MAX COMMON PATH AND MAX TRAVEL DISTANCE FOR R-1
 AND R-2 TO ALS1.100 COMPLIANCE SUMMARY
  ADD STAIR 10 AND 12 DATA TO EXIT CAPACITY TABLE. IS
 THERE A STAIRWAY 11?
  B. STAIR 12 MERGES WITH STAIR 6. STAIR DATA SHOULD
 INCLUDE ACTUAL LOAD AT EACH STAIR AND ANY MERGING
 SHOULD BE INCLUDED IN THE TOTAL.
  C. CHECK ALL EXIT CAPACITY TABLES FOR DOOR CAPACITY
 BASED ON .2 INCHES PER OCCUPANT AND THE DOOR WIDTH
 NEEDS TO BE CLEAR WIDTH.
  D. COLUMNS DON?T SHOW ON THE PLAN LIFE SAFETY PLANS.
 PLEASE SHOW COLUMNS ON ALL PLANS.
  E. IT?S NOT CLEAR WHAT THE COMMON PATH OF TRAVEL IS
 AND WHAT THE MAX TRAVEL DISTANCE WILL BE FOR THE
 RESIDENTIAL. COMMON PATH OF TRAVEL WOULD BE FROM MOST
 REMOTE POINT IN UNIT TO THE COORIDOR WHERE 2 EXIT
 OPTIONS ARE PROVIDED.
  F. PROVIDE OCCUPANT LOAD FOR SEPARATE OCCUPANCIES (R-2
 AND S-2), EXITS REQUIRED, EXITS PROVIDED AND OCCUPANT
 LOAD AT EACH EXIT IN ADDITION TO THE LIMITING CAPACITY
 PROVIDED.
  G. ALL LIFE SAFETY SHEETS AND ALL FP SHEETS NEED TO BE
 COORDINATED. STANDPIPES APPEAR TO BLOCK PATH OF EGRESS
 AT GROUND FLOORS AND EGRESS DOORS DON?T LINE UP WITH
 EXTENDED WALLS AT CURTAIN WALL.
  
 17) 107.3.5 FBC[AMENDED] MINIMUM REVIEW CRITERIA.
 ALS1.101
  A. REVIEW PLACEMENT EXIT SIGN .WHERE DOES THE EXIT
 SIGN NEXT TO TRUCKS EGRESS?
  B. TOILETS DON?T SHOW ON THE PLAN, THEN THEY DON?T
 SHOW ON THE ENLARGED A1602
  C. REVOLVING DOORS OVERLAPPING AND DIFFERENT SIZES.
  D. STAIRWAY 11 SAYS 6IN. STANDPIPE, BUT IT IS 8 IN. ON
 FP.201.B
  E. LABEL FPL VAULT. ALSO LABEL FPL ON OTHER APPLICABLE
 SHEETS.
  F. WHAT ARE THE 2 WALL AREAS THAT LOOK LIKE OPENINGS
 IN FPL VAULT? LOUVERS?
  
 18) 107.3.5 FBC[AMENDED] MINIMUM REVIEW CRITERIA.
 ALS1.102
  A. ROOM TAG MISSING ON SHEET ALS1.102, A1.102 AND
 A1.208 (PLUS OTHER APPLICABLE SHEETS)
  B. ADD EXIT SIGN TO STAIR 6 FROM GARAGE TO EXIT STAIR.
  
 19) 107.3.5 FBC[AMENDED] MINIMUM REVIEW CRITERIA.
 ALS1.103
  A. ADD EXIT SIGN TO STAIR 6 FROM GARAGE TO EXIT STAIR.
  B. REVIEW DATA TAG ON UNITS S1.3 (TWO UNITS SHOW
 SAME). SAYS NOT ENCLOSED AND 0 OCCUPANTS.
  
 20) 107.3.5 FBC[AMENDED] MINIMUM REVIEW CRITERIA.
 ALS1.104
  -REVIEW DATA TAG ON UNIT S1.2. SAYS NOT ENCLOSED AND 0
 OCCUPANTS.
  
 21) 107.3.5 FBC[AMENDED] MINIMUM REVIEW CRITERIA.
 ALS1.105
  -REVIEW DATA TAG ON UNIT S1.2. SAYS NOT ENCLOSED AND 0
 OCCUPANTS.
  
 22) 107.3.5 FBC[AMENDED] MINIMUM REVIEW CRITERIA.
 ALS1.106
  -UPDATE PER TYPICAL COMMENTS.
  
 23) 107.3.5 FBC[AMENDED] MINIMUM REVIEW CRITERIA.
 ALS1.107
  A. IS LEVEL 7 SHARED BY HOTEL AND RESIDENTIAL?
  B. POOL DECK OCCUPANT LOAD SHOWS ZERO.
  C. 1011.6 FBC[B] STAIRWAY LANDINGS. CHECK EGRESS DOOR
 SWING FROM POOL DECK INTO STAIR 5 IS IT TOO FAR INTO
 STAIRWAY PATH OF EGRESS?
  D.1003.5 FBC[B] ELEVATION CHANGE. DOES EXIT FROM
 RESIDENT LOBBY TO STAIR 2 HAVE STEPS? PLEASE REVIEW
  E. HOW DO STEPS WORK AT 2 ND EGRESS FROM RESIDENT
 LOUNGE? (SEE SECTION A4.200)
  F. 1003.5 FBC[B] REVIEW EGRESS AT BALLROOM TO STAIR 8.
 DOES THIS EGRESS USE STAIRS FOR EGRESS?
  G. CHECK EGRESS FROM BALLROOM TERRACE. THE BALLROOM
 ELEVATION IS 2 FEET LOWER THAN RESIDENTIAL DECK. HOW
 DOES EGRESS FROM BALLROOM TO STAIR 7 WORK WITH
 ELEVATION DIFFERENCE?
  H. SHEET A5.104 CHECK DOOR ELEVATION FOR STAIR 2 AT
 7TH LEVEL. THE DOOR IS POSITIONED TWO FEET HIGHER
 BECAUSE THERE ARE STEPS DOWN TO GET TO STAIR 2 AND IT
 LOOKS TO BE SET AT ELEVATION OF POOL DECK AND
 RESIDENTIAL LOUNGE.
  I. CAPACITY SHOWN IN TABLE DOESN?T EXCEED THE AMOUNT
 OF OCCUPANTS ON LEVEL AND IT ISN?T CLEAR WHICH EXITS
 SERVE WHICH OCCUPANTS.
  J. PROVIDE EGRESS BASED ON OCCUPANCY REQUIRED WIDTH
 AND PROVIDED. THE TABLES PROVIDED ARE BASED ON
 CAPACITY, BUT OCCUPANCY NEEDS TO BE LOOKED AT BY AREA
 SERVED.
  K. REVIEW EGRESS FROM TENNIS AND TERRACE AREAS. TENNIS
 COURTS AND TERRACES REQUIRES 292 INCHES OF EGRESS FOR
 1457 OCCUPANTS. STAIR 5 AND 9 STATE (2) 40 INCH DOORS
 FOR 160 INCHES AND STAIRWAY 10 MAY PROVIDE ADDITIONAL
 80 (ADD DATA TO CHART AND THE LOAD FROM LEVEL 8 GETS
 ADDED INTO LEVEL 7 FOR 1005.6 FBC[B] CONVERGENCE).
 TOTAL IS NOW 240, SO 52 INCHES WOULD STILL NEED TO BE
 SUPPLIED WITHIN THE MAX TRAVEL DISTANCE. THERE IS PATH
 GOING TO RESIDENTIAL STAIR, BUT THE DOOR IS 32 INCHES
 AND THE DOOR WOULD NEED TO BE UNLOCKED FROM EGRESS
 SIDE. STAIR 2 ALSO HAS RESIDENTIAL AND POOL AREA
 APPLIED TO THE EGRESS WIDTH OF STAIR 2.
  
 24) 107.3.5 FBC[AMENDED] PLEASE REVIEW HOW MANY
 OCCUPANTS CONTRIBUTE TO EACH EXIT AND CALCULATE TOTAL
 FOR EACH EXIT. CURRENT LIFE SAFETY SEEMS TO LOOK AT
 ENTIRE FLOOR AND BASED ON CAPACITY, BUT EACH FLOOR
 NEEDS MORE DETAIL AS TO HOW MANY OCCUPANTS, NUMBER OF
 EXITS REQUIRED AND CONVERGENCE.
  -SHOW HOW CONVERGENCE IS HANDLED FROM STAIR 10 LEVEL 8
 TO LEVEL 7.
  
 25) 107.3.5 FBC[AMENDED] SHEET ALS1.110 SUITE 12-10
 DOESN?T SHOW OCCUPANT LOAD. PLEASE ADD TO FLOOR COUNT.
  
 26) 107.3.5 FBC[AMENDED] THE REFLECTED CEILING PLANS
 (RCP) DO NOT APPEAR TO BE COMPLETE. PLEASE SUBMIT
 COMPLETED RCP PLANS FOR SECOND REVIEW.
  
 27) 107.3.5 FBC[B] MISSING LS FOR RESIDENTIAL FLOORS 8,
 9, 10 AND 11. THEY HAVE A DIFFERENT CONFIGURATION THAN
 FLOORS 13-30.
  -PROVIDE LIFE SAFTY SHEET FOR EACH FLOOR
 CONFIGURATION.
  
 28) 107.3.5 FBC[AMENDED] SHEET ALS1.111 REMOVE WALL AT
 EGRESS 90 MINUTE DOOR.
  
 29) 107.3.5 FBC[AMENDED] SHEET ALS1.112 OCCUPANT
 SCHEDULE LOAD EXCEEDS EXIT CAPACITY TABLE, AND ROOM
 LABELS DO NOT MATCH SCHEDULE LOADS.
  
 30) 107.3.5 FBC[AMENDED] SHEET ALS1.112 PLANTERS APPEAR
 TO BLOCK ROOF DRAINS.
  
 31) 107.3.5 FBC[B] THE HOTEL LEVEL , AND BUSINESS
 ABOVE, RELY ON TWO INTERIOR STAIRWAYS FOR EGRESS.
  A. BOTH INTERIOR STAIRWAY DOORS ON THE LEVEL OF EXIT
 DISCHARGE ARE SWINGING IN. PLEASE REVIEW THIS AS EACH
 EXIT WILL SERVE MORE THAN 50 PERSONS.
  B. IS THE INTENT TO EGRESS FROM STAIRWAY 4 AT 2ND
 LEVEL AND TRANSFER TO STAIRWAY 11?
  
 32) 107.3.5 FBC[A] COVERED MULTIFAMILY DWELLINGS FOR
 FIRST OCCUPANCY AFTER MARCH 13, 1991, SHALL BE DESIGNED
 AND CONSTRUCTED TO HAVE AT LEAST ONE BUILDING ENTRANCE
 ON AN ACCESSIBLE ROUTE UNLESS IT IS IMPRACTICAL TO DO
 SO BECAUSE OF THE SITE.
  A. SHOW ACCESSIBLE PATH FOR RESIDENTIAL UNITS.
  
 1986 ANSI [A117.1] IF A DESIGNER OR BUILDER CHOOSES TO
 FOLLOW AN ACCESSIBILITY STANDARD OTHER THAN THE 1986
 ANSI A117.1 STANDARD, OR A MORE RECENT VERSION OF THE
 ANSI A117.1, SUCH AS THE 1992 CABO/ANSI, THAT CARE BE
 TAKEN TO ENSURE THE STANDARD USED IS AT LEAST
 EQUIVALENT TO OR STRICTER THAN THE 1986 ANSI A117.1
 STANDARD.
 FHA AND ADA ARE BEING USED, BUT IT IS NOT CLEAR WHICH
 CODE APPLIES TO MIXED USE OCCUPANCIES. PLEASE PROVIDE A
 SUMMARY OF EACH OCCUPANCY AND IF ADA OR FHA IS BEING
 APPLIED.
  -WHAT STANDARD IS BEING USED TO INCORPORATE FAIR
 HOUSING GUIDELINES?
  
 WALKS THAT ARE PART OF ACCESSIBLE ROUTES BECOME RAMPS
 WHEN THEIR SLOPE EXCEEDS 5% (1 IN 20). HANDRAILS ARE
 NOT REQUIRED ON WALKS WITH SLOPES BETWEEN 0% AND 5%,
 BUT THEY ARE REQUIRED ON THOSE STEEPER THAN 5% AND UP
 TO 8.33% (1 IN 12)
  B. CLEARLY INDICATE ANY RAMPS ON PLANS. LEVEL 7 FOR
 EXAMPLE HAS 2 FOOT DIFFERENCE BETWEEN POOL DECK AND
 BALLROOM. RAMPS WILL AFFECT EGRESS AND PATH OF TRAVEL.
  
 IN DWELLING UNITS CONTAINING MORE THAN ONE BATHROOM, IF
 SPECIFICATION A IS SELECTED AS THE BASIS FOR DESIGNING
 A BATHROOM, ALL BATHROOMS IN THE DWELLING UNIT ALSO
 MUST COMPLY WITH THE A SPECIFICATIONS. IF SPECIFICATION
 B IS SELECTED, ONLY ONE BATHROOM IN THE DWELLING UNIT
 MUST MEET THOSE REQUIREMENTS ALL BATHROOMS AS DEFINED
 IN THE GUIDELINES MUST:
 1. BE ON AN ACCESSIBLE ROUTE (REQUIREMENT 4),
 2. HAVE 32-INCH NOMINAL CLEAR WIDTH DOORWAYS
 (REQUIREMENT 3)
 3. HAVE SWITCHES, OUTLETS, AND CONTROLS IN ACCESSIBLE
 LOCATIONS (REQUIREMENT 5)
 4. HAVE REINFORCING AROUND TOILETS, TUBS, AND SHOWERS
 (REQUIREMENT 6)
 5. MEET REQUIREMENT 7, SPECIFICATION A OR B:
 POWDER ROOMS MUST:
 1. BE ON AN ACCESSIBLE ROUTE (REQUIREMENT 4),
 2. HAVE 32-INCH NOMINAL CLEAR WIDTH DOOR-WAYS
 (REQUIREMENT 3), AND
 3. HAVE SWITCHES, OUTLETS, AND CONTROLS IN ACCESSIBLE
 LOCATIONS (REQUIREMENT 5). EXCEPTION WHEN THE POWDER
 ROOM IS THE ONLY TOILET FACILITY ON THE ENTRY LEVEL OF
 A MULTI-STORY UNIT IN A BUILDING WITH ONE OR MORE
 ELEVATORS, IT MUST, IN ADDITION TO REQUIREMENTS 3, 4,
 AND 5, MEET THE REINFORCING SPECIFICATIONS OF
 REQUIREMENT 6 AND THE MANEUVERING AND CLEAR FLOOR
 SPECIFICATIONS OF REQUIREMENT 7.
 101.4.1 FBC[CE] MIXED OCCUPANCY. WHERE A BUILDING
 INCLUDES BOTH RESIDENTIAL AND COMMERCIAL OCCUPANCIES,
 EACH OCCUPANCY SHALL BE SEPARATELY CONSIDERED AND MEET
 THE APPLICABLE PROVISIONS OF FLORIDA BUILDING CODE,
 ENERGY CONSERVATION?COMMERCIAL PROVISIONS OR FLORIDA
 BUILD.
  C. PROVIDE DOCUMENTS TO SHOW COMPLIANCE WITH FBC
 ENERGY FOR EACH OCCUPANCY.
  
 33) 208.1 FBC[A] SHEET A0.102 PARKING. PLEASE INDICATE
 ON THE PLANS WHICH PARKING SPOTS ARE SHARED. IF ANY
 SPOTS ARE NOT TO BE SHARED THEN THEY SHOULD NOT BE
 INCLUDED IN THE SHARED PARKING TABLE.
  A. IF ALL SPOTS ARE SHARED AS INDICATED, PROVIDE
 DETAILS OF HOW TANDEM AND LIFT SPOTS ARE USABLE BY ALL
 OCCUPANCIES.
  B. WHICH OCCUPANCIES ARE SERVED BY VALET AND WHERE DO
 THEY PARK?
  
 34) 206.1 FBC[A] GENERAL. ACCESSIBLE ROUTES SHALL BE
 PROVIDED IN ACCORDANCE WITH 206 AND SHALL COMPLY WITH
 CHAPTER 4.
 208.3.1 FBC[A] LOCATION. WHERE PARKING SERVES MORE THAN
 ONE ACCESSIBLE ENTRANCE, PARKING SPACES COMPLYING WITH
 502 SHALL BE DISPERSED AND LOCATED ON THE SHORTEST
 ACCESSIBLE ROUTE TO THE ACCESSIBLE ENTRANCES.IF THERE
 ARE MULTIPLE ENTRANCES FOR MULTIPLE RETAIL STORES THE
 PARKING SPACES MUST BE DISPERSED TO PROVIDE PARKING AT
 THE NEAREST ACCESSIBLE ENTRANCE. IN PARKING FACILITIES
 THAT DO NOT SERVE A PARTICULAR BUILDING OR FACILITY,
 PARKING SPACES COMPLYING WITH 502 SHALL BE LOCATED ON
 THE SHORTEST ACCESSIBLE ROUTE TO AN ACCESSIBLE
 PEDESTRIAN ENTRANCE OF THE PARKING FACILITY.
  -CURRENT PARKING DOES NOT MEET FBC[A] 208.2.3.1.
 PLEASE PROVIDE REVISED PARKING AND SHOW ACCESSIBLE PATH
 FROM EACH SPACE TO OCCUPANCY SERVED. EACH OCCUPANCY
 SHOULD HAVE REQUIRED NUMBER SPACES AND ACCESSIBLE PATH
 LEADING TO THEM.
  
 35) 224.1.2 FBC[A] GUEST ROOM DOORS AND
 DOORWAYS.ENTRANCES, DOORS, AND DOORWAYS PROVIDING USER
 PASSAGE INTO AND WITHIN GUEST ROOMS THAT ARE NOT
 REQUIRED TO PROVIDE MOBILITY FEATURES COMPLYING WITH
 806.2 SHALL COMPLY WITH 404.2.3.
 A. 224.2, 224.3, 224.4, 224.5 AND 224.6.3 TRANSIENT
 LODGING GUEST ROOMS. THIS IS ISN?T READY FOR REVIEW, SO
 PLEASE LOOK AT ALL SECTIONS OF CODE. FOR INSTANCE,
 GENERAL FLOOR PLAN A1.244 SHOWING FLOORS 12-16 DOESN?T
 PROVIDE ENOUGH INFO THE SATISFY DISPERSION. THAT IS
 WHERE A MATRIX WOULD HELP TO SEE THAT THE ROOMS ARE
 BEING DISPERSED AND THAT ALL ROOMS ARE ACCOUNTED FOR.
  B. ADD MATRIX TO SHOW COMPLIANCE WITH FBC [A] 224.2,
 224.3, 224.4, 224.5 AND 224.6.3 ACCORDING TO THE AMOUNT
 OF ROOMS ON SHEET A0.102 THERE SHOULD BE 11 ROOMS WITH
 MOBILITY FBC[A] 806.2, 17 ROOMS WITH COMMUNICATION
 FBC[A]806.3 AND 10 ADDITIONAL ROOMS WITH SPECIAL
 ACCESSIBLE FEATURES FBC[A] 806.4. AT LEAST ONE, BUT NO
 MORE THAN 10% OF THE ROOMS TO COMPLY WITH MOBILITY CAN
 ALSO BE USED TO COMPLY WITH COMMUNICATION FEATURES.
 THAT WOULD MEAN THAT ONE ROOM CAN BE USED TO SATISFY
 BOTH.
  
 36) 401.2 FBC[CE] APPLICATION. COMMERCIAL BUILDINGS
 SHALL COMPLY WITH ONE OF THE FOLLOWING:
 1. THE REQUIREMENTS OF ANSI/ASHRAE/IESNA 90.1,
 EXCLUDING SECTION 9.4.1.1(G) OF THE STANDARD.
 2. THE REQUIREMENTS OF SECTIONS C402 THROUGH C405. IN
 ADDITION, COMMERCIAL BUILDINGS SHALL COMPLY WITH
 SECTION C406 AND TENANT SPACES SHALL COMPLY WITH
 SECTION C406.1.1.
 3. THE REQUIREMENTS OF SECTIONS C402.5, C403.2, C404,
 C405.2, C405.3, C405.5, C405.6 AND C407. THE BUILDING
 ENERGY COST SHALL BE EQUAL TO OR LESS THAN 85 PERCENT
 OF THE STANDARD REFERENCE DESIGN BUILDING.
  
 37) 402.1 FBC[A] PROVIDE ACCESSIBLE ROUTE FROM PARKING
 LOT. IN ADDITION TO ACCESSIBLE ENTRANCES REQUIRED BY
 SECTIONS 1105.1.1 THROUGH 1105.1.7 (PARKING GARAGE
 ENTRANCES, ENTRANCES FROM TUNNELS OR ELEVATED WALKWAYS,
 RESTRICTED ENTRANCES, ENTRANCES FOR INMATES OR
 DETAINEES, SERVICE ENTRANCES AND ENTRANCES TO TENANT
 SPACES, DWELLING UNITS AND SLEEPING UNITS), AT LEAST 60
 PERCENT OF ALL PUBLIC ENTRANCES SHALL BE ACCESSIBLE.
 SEE THE EXCEPTIONS FOR ENTRANCES TO AREAS NOT REQUIRED
 TO BE ACCESSIBLE AND LOADING/SERVICE ENTRANCES THAT ARE
 NOT THE ONLY TENANT SPACE ENTRANCE.
  -PROVIDE DETAILS ON PLANS TO SHOW HOW DROP OFF AREAS
 MEET FBC[A] 502 FOR PASSENGER LOADING ZONES AT HOTEL
 AND RESIDENTIAL LOBBY. LENGTH, WIDTH AND MARKINGS.
  
 38) 403.3.2 FBC[B] WATER SUPPLY TO REQUIRED FIRE PUMPS.
 REQUIRED FIRE PUMPS SHALL BE SUPPLIED BY CONNECTIONS TO
 NO FEWER THAN TWO WATER MAINS LOCATED IN DIFFERENT
 STREETS. SEPARATE SUPPLY PIPING SHALL BE PROVIDED
 BETWEEN EACH CONNECTION TO THE WATER MAIN AND THE
 PUMPS. EACH CONNECTION AND THE SUPPLY PIPING BETWEEN
 THE CONNECTION AND THE PUMPS SHALL BE SIZED TO SUPPLY
 THE FLOW AND PRESSURE REQUIRED FOR THE PUMPS TO
 OPERATE.
  -IS THIS ACCOUNTED FOR ON CIVIL AND PLUMBING PLANS?
 PLEASE STATE WHICH SHEETS.
  
 39) 403.5.4 FBC[B] SMOKEPROOF ENCLOSURES. EVERY
 REQUIRED EXIT STAIRWAY SERVING FLOORS MORE THAN 75 FEET
 (22 860 MM) ABOVE THE LOWEST LEVEL OF FIRE DEPARTMENT
 VEHICLE ACCESS SHALL BE A SMOKEPROOF ENCLOSURE IN
 ACCORDANCE WITH SECTIONS 909.20 AND 1022.10.
  
 40) 407.4.1 FBC[A] CAR DIMENSIONS. INSIDE DIMENSIONS OF
 ELEVATOR CARS AND CLEAR WIDTH OF ELEVATOR DOORS SHALL
 COMPLY WITH TABLE 407.4.1.
  -PLEASE ADD CAB DIMENSIONS ON PLANS.
  
 41) 704.9 FBC[B] IMPACT PROTECTION. WHERE THE FIRE
 PROTECTIVE COVERING OF A STRUCTURAL MEMBER IS SUBJECT
 TO IMPACT DAMAGE FROM MOVING VEHICLES, THE HANDLING OF
 MERCHANDISE OR OTHER ACTIVITY, THE FIRE PROTECTIVE
 COVERING SHALL BE PROTECTED BY CORNER GUARDS OR BY A
 SUBSTANTIAL JACKET OF METAL OR OTHER NONCOMBUSTIBLE
 MATERIAL TO A HEIGHT ADEQUATE TO PROVIDE FULL
 PROTECTION, BUT NOT LESS THAN 5 FEET FROM THE FINISHED
 FLOOR. EXCEPTION: CORNER PROTECTION IS NOT REQUIRED ON
 CONCRETE COLUMNS IN OPEN OR ENCLOSED PARKING GARAGES.
  -VERIFY IF COLUMNS IN PARKING GARAGE ARE SUBJECT TO
 704.9 IMPACT PROTECTION.
  
 42) 803.1 GENERAL. PROVIDE INTERIOR FINISH SCHEDULES.
  A. SUPPLY MORE DEVELOPED PLANS TO SHOW BUILT INS AND
 FURNITURE LAYOUTS.
  B. ADD FURNITURE PLAN TO ROOMS TO VERIFY ADA AND
 EGRESS COMPLIANCE.
  
 43) 806.1 FBC[B] GENERAL REQUIREMENTS. IN OCCUPANCIES
 IN GROUPS A, E, I AND R-1 AND DORMITORIES IN GROUP R-2,
 CURTAINS, DRAPERIES, HANGINGS AND OTHER DECORATIVE
 MATERIALS SUSPENDED FROM WALLS OR CEILINGS SHALL MEET
 THE FLAME PROPAGATION PERFORMANCE CRITERIA OF NFPA 701
 IN ACCORDANCE WITH SECTION 806.2 OR BE NONCOMBUSTIBLE.
  -ADD TO DEFERRED SUBMITTAL LIST IF APPLICABLE.
  
 44) 909.3 FBC[B] SPECIAL INSPECTION AND TEST
 REQUIREMENTS. IN ADDITION TO THE ORDINARY INSPECTION
 AND TEST REQUIREMENTS WHICH BUILDINGS, STRUCTURES AND
 PARTS THEREOF ARE REQUIRED TO UNDERGO, SMOKE CONTROL
 SYSTEMS SUBJECT TO THE PROVISIONS OF SECTION 909 SHALL
 UNDERGO SPECIAL INSPECTIONS AND TESTS SUFFICIENT TO
 VERIFY THE PROPER COMMISSIONING OF THE SMOKE CONTROL
 DESIGN IN ITS FINAL INSTALLED CONDITION. THE DESIGN
 SUBMISSION ACCOMPANYING THE CONSTRUCTION DOCUMENTS
 SHALL CLEARLY DETAIL PROCEDURES AND METHODS TO BE USED
 AND THE ITEMS SUBJECT TO SUCH INSPECTIONS AND TESTS.
 SUCH COMMISSIONING SHALL BE IN ACCORDANCE WITH
 GENERALLY ACCEPTED ENGINEERING PRACTICE AND, WHERE
 POSSIBLE, BASED ON PUBLISHED STANDARDS FOR THE
 PARTICULAR TESTING INVOLVED.
  
 45) 909.4 FBC[B] ANALYSIS. A RATIONAL ANALYSIS
 SUPPORTING THE TYPES OF SMOKE CONTROL SYSTEMS TO BE
 EMPLOYED, THEIR METHODS OF OPERATION, THE SYSTEMS
 SUPPORTING THEM AND THE METHODS OF CONSTRUCTION TO BE
 UTILIZED SHALL ACCOMPANY THE SUBMITTED CONSTRUCTION
 DOCUMENTS AND SHALL INCLUDE, BUT NOT BE LIMITED TO, THE
 ITEMS INDICATED IN SECTIONS 909.4.1 THROUGH 909.4.6.
  
 46) 909.20.5 FBC[B] STAIR PRESSURIZATION ALTERNATIVE.
 WHERE THE BUILDING IS EQUIPPED THROUGHOUT WITH AN
 AUTOMATIC SPRINKLER SYSTEM IN ACCORDANCE WITH SECTION
 903.3.1.1, THE VESTIBULE IS NOT REQUIRED, PROVIDED THAT
 INTERIOR EXIT STAIRWAYS ARE PRESSURIZED TO A MINIMUM OF
 0.10 INCHES OF WATER (25 PA) AND A MAXIMUM OF 0.35
 INCHES OF WATER (87 PA) IN THE SHAFT RELATIVE TO THE
 BUILDING MEASURED WITH ALL STAIRWAY DOORS CLOSED UNDER
 MAXIMUM ANTICIPATED CONDITIONS OF STACK EFFECT AND WIND
 EFFECT.
  -PLEASE PROVIDE RATIONAL ANALYSIS FOR ALL SMOKE
 CONTROL SYSTEMS STATING HOW HOISTWAYS AND STAIRWAYS
 WILL MEET THE CODE REQUIREMENTS.
  
 47) 1006.2.1 FBC TABLE[B] MAXIMUM COMMON PATH OF EGRESS
 TRAVEL DISTANCE.
  -ADD ROWS TO SHEET ALS1.100 TABLE A7.6 TO SHOW DATA
 FOR R OCCUPANCIES.
  
 48) 1006.2.1 FBC TABLE[B] HOW MANY EXITS ARE PROVIDED
 ON RESIDENTIAL (R-2) FLOORS? LIFE SAFETY SHEETS APPEAR
 TO USE ONE EXIT WITH ELEVATOR LOBBY CONNECTING TWO
 SIDES.
  -ADJUST LIFE SAFETY TO STATE HOW MANY EXITS ARE
 REQUIRED, HOW MANY PROVIDED AND MARK EXIT SIGNS AND
 EGRESS PATHS FOR THE REQUIRED NUMBER OF EXITS.
  
 49) 1006.1 ILLUMINATION REQUIRED. THE MEANS OF EGRESS,
 INCLUDING THE EXIT DISCHARGE, SHALL BE ILLUMINATED AT
 ALL TIMES THE BUILDING SPACE SERVED BY THE MEANS OF
 EGRESS IS OCCUPIED.
  -SEE 1006.1 FOR EXCEPTIONS
  
 50) 1006.3 EMERGENCY POWER FOR ILLUMINATION. THE POWER
 SUPPLY FOR MEANS OF EGRESS ILLUMINATION SHALL NORMALLY
 BE PROVIDED BY THE PREMISES? ELECTRICAL SUPPLY. IN THE
 EVENT OF POWER SUPPLY FAILURE, AN EMERGENCY ELECTRICAL
 SYSTEM SHALL AUTOMATICALLY ILLUMINATE ALL OF THE
 FOLLOWING AREAS: (SEE 1006.3 FOR AREAS)
  -PLEASE PROVIDE ELECTRICAL SHEET NUMBERS THAT SHOW THE
 INFORMATION TO MEET 1006.1 AND 1006.3
  
 51) 1010.1.2.1 FBC[B] DIRECTION OF SWING. PIVOT OR
 SIDE-HINGED SWINGING DOORS SHALL SWING IN THE DIRECTION
 OF EGRESS TRAVEL WHERE SERVING A ROOM OR AREA
 CONTAINING AN OCCUPANT LOAD OF 50 OR MORE PERSONS OR A
 GROUP H OCCUPANCY.
  A. SHEET A1.201 THE DOOR LEADING OUT OF STAIR 3
 BETWEEN 267 AND 262. IS THIS DOOR SUPPOSE TO SWING IN.
 PLEASE VERIFY THE DIRECTION OF EGRESS AND IT ALSO NEEDS
 A DOOR NUMBER.
  B. SHEET A1.202 THE DOOR LEADING OUT OF STAIR 4
 LABELED 267 . IS THIS DOOR SUPPOSE TO SWING IN. PLEASE
 VERIFY THE DIRECTION OF EGRESS AND IS IT SUPPOSED TO
 HAVE THE SAME DOOR NUMBER AS A DOOR IN STAIR 3?
  C. SHEET A1.204 THE DOOR LEADING OUT OF STAIR 2
 LABELED 262 SWINGS OUT INTO CORRIDOR 01-40. THEN EGRESS
 CONTINUES OUT TO DOOR 291 WHICH IN TURN SWINGS IN.
 PLEASE REVIEW DIRECTION OF EGRESS. ALSO, DOORS IN A
 SERIES WOULD NEED 48 INCHES BETWEEN THEM FROM OPEN
 POSITION (FBC ACCESSIBILITY 404.2.6)
  
 52) 1013.2 FBC[B] FLOOR-LEVEL EXIT SIGNS IN GROUP R-1.
 WHERE EXIT SIGNS ARE REQUIRED IN GROUP R-1 OCCUPANCIES
 BY SECTION 1013.1, ADDITIONAL LOW-LEVEL EXIT SIGNS
 SHALL BE PROVIDED IN ALL AREAS SERVING GUEST ROOMS IN
 GROUP R-1 OCCUPANCIES AND SHALL COMPLY WITH SECTION
 1013.5.
  -ADD FLOOR-LEVEL SIGNS TO LIFE SAFTEY PLANS FOR HOTEL
 FLOORS WITH R-1 UNITS (LEVELS 9-16)
  
 53) 1014.6 FBC[B] HANDRAIL EXTENSIONS. HANDRAILS SHALL
 RETURN TO A WALL, GUARD OR THE WALKING SURFACE OR SHALL
 BE CONTINUOUS TO THE HANDRAIL OF AN ADJACENT FLIGHT OF
 STAIRS OR RAMP RUN. WHERE HANDRAILS ARE NOT CONTINUOUS
 BETWEEN FLIGHTS, THE HANDRAILS SHALL EXTEND
 HORIZONTALLY NOT LESS THAN 12 INCHES BEYOND THE TOP
 RISER AND CONTINUE TO SLOPE FOR THE DEPTH OF ONE TREAD
 BEYOND THE BOTTOM RISER. AT RAMPS WHERE HANDRAILS ARE
 NOT CONTINUOUS BETWEEN RUNS, THE HANDRAILS SHALL EXTEND
 HORIZONTALLY ABOVE THE LANDING 12 INCHES MINIMUM BEYOND
 THE TOP AND BOTTOM OF RAMP RUNS. THE EXTENSIONS OF
 HANDRAILS SHALL BE IN THE SAME DIRECTION OF THE FLIGHTS
 OF STAIRS AT STAIRWAYS AND THE RAMP RUNS AT RAMPS.
  -DETAIL 1/A5.121 AND 1/A5.122 SHOW HOW RAILING
 EXTENSIONS WORK. ALL STAIR SECTIONSA5.101 TO A5.118
 SHOW 12 INCH HORIZONTAL PROJECTION FROM FIRST TREAD
 HEIGHT. PLEASE HAVE DETAIL AND SECTION MATCH SO WE CAN
 SEE HOW THIS AFFECTS WHERE BOTTOM HANDRAILS MEET DOOR
 FRAMES.
  
 54) 1015.6 DAY CARE MEANS OF EGRESS. DAY CARE
 FACILITIES, ROOMS OR SPACES WHERE CARE IS PROVIDED FOR
 MORE THAN 10 CHILDREN THAT ARE 2 1/2 YEARS OF AGE OR
 LESS, SHALL HAVE ACCESS TO NOT LESS THAN TWO EXITS OR
 EXIT ACCESS DOORWAYS.
  -DAYCARE 2 EXITS NEEDED? PLEASE STATE THE AGE AND
 AMOUNT OF CHILDREN ANTICIPATED AT THE DAYCARE.
  
 55) 1022.5 PENETRATIONS. PENETRATIONS INTO AND OPENINGS
 THROUGH INTERIOR EXIT STAIRWAYS AND RAMPS ARE
 PROHIBITED EXCEPT FOR REQUIRED EXIT DOORS, EQUIPMENT
 AND DUCTWORK NECESSARY FOR INDEPENDENT VENTILATION OR
 PRESSURIZATION, SPRINKLER PIPING, STANDPIPES,
 ELECTRICAL RACEWAY FOR FIRE DEPARTMENT COMMUNICATION
 SYSTEMS AND ELECTRICAL RACEWAY SERVING THE INTERIOR
 EXIT STAIRWAY AND RAMP AND TERMINATING AT A STEEL BOX
 NOT EXCEEDING 16 SQUARE INCHES (0.010 M2). SUCH
 PENETRATIONS SHALL BE PROTECTED IN ACCORDANCE WITH
 SECTION 714. THERE SHALL BE NO PENETRATIONS OR
 COMMUNICATING OPENINGS, WHETHER PROTECTED OR NOT,
 BETWEEN ADJACENT INTERIOR EXIT STAIRWAYS AND RAMPS.
  -HVAC COMMON FEEDING STAIRS FROM MAIN (SEE STAIRS AT
 VAV-2)-INDEPENDENT SYSTEMS TO FEED STAIRWAYS? PLEASE
 REVIEW PENETRATIONS INTO INTERIOR STAIRWAYS AND PROVIDE
 INDEPENDENT SYSTEMS AS REQUIRED IN 1022.5.
  
 56) 1022.8 FBC[B] DISCHARGE IDENTIFICATION. AN INTERIOR
 EXIT STAIRWAY AND RAMP SHALL NOT CONTINUE BELOW ITS
 LEVEL OF EXIT DISCHARGE UNLESS AN APPROVED BARRIER IS
 PROVIDED AT THE LEVEL OF EXIT DISCHARGE TO PREVENT
 PERSONS FROM UNINTENTIONALLY CONTINUING INTO LEVELS
 BELOW. DIRECTIONAL EXIT SIGNS SHALL BE PROVIDED AS
 SPECIFIED IN SECTION 1011.
  A. IF STAIRWAY 4 AT 2 ND LEVEL TRANSFERS TO STAIRWAY
 11 THAN 1022.8 APPLIES.
  B. REVIEW EGRESS PATH TO STAIR 11. DOUBLE DOORS
 SWINGING INTO PATH AND WIDTH OF 90 DEGREE TURN.
  
 57) 1022.9 FBC[B] SIGNAGE. GENERAL COMMENT.
  A. 1022.9 FBC[B] STAIRWAY IDENTIFICATION SIGNS.
  B. 1022.9.1 FBC[B] SIGNAGE REQUIREMENTS.
  
 58) 1022.10.2 FBC[B] ENCLOSURE ACCESS. ACCESS TO THE
 STAIRWAY WITHIN A SMOKEPROOF ENCLOSURE SHALL BE BY WAY
 OF A VESTIBULE OR AN OPEN EXTERIOR BALCONY.
 EXCEPTION: FBC[B] ACCESS IS NOT REQUIRED BY WAY OF A
 VESTIBULE OR EXTERIOR BALCONY FOR STAIRWAYS USING THE
 PRESSURIZATION ALTERNATIVE COMPLYING WITH SECTION
 909.20.5.
  
 59) 1022.10 FBC[B] SMOKEPROOF ENCLOSURES AND
 PRESSURIZED STAIRWAYS AND RAMPS. WHERE REQUIRED BY
 SECTION 403.5.4 OR 405.7.2, INTERIOR EXIT STAIRWAYS AND
 RAMPS SHALL BE SMOKEPROOF ENCLOSURES OR PRESSURIZED
 STAIRWAYS OR RAMPS IN ACCORDANCE WITH SECTION 909.20.
 1022.10.1 FBC[B] TERMINATION AND EXTENSION. A
 SMOKEPROOF ENCLOSURE OR PRESSURIZED STAIRWAY SHALL
 TERMINATE AT AN EXIT DISCHARGE OR A PUBLIC WAY. THE
 SMOKEPROOF ENCLOSURE OR PRESSURIZED STAIRWAY SHALL BE
 PERMITTED TO BE EXTENDED BY AN EXIT PASSAGEWAY IN
 ACCORDANCE WITH SECTION 1022.3. THE EXIT PASSAGEWAY
 SHALL BE WITHOUT OPENINGS OTHER THAN THE FIRE DOOR
 ASSEMBLY REQUIRED BY SECTION 1022.3.1 AND THOSE
 NECESSARY FOR EGRESS FROM THE EXIT PASSAGEWAY. THE EXIT
 PASSAGEWAY SHALL BE SEPARATED FROM THE REMAINDER OF THE
 BUILDING BY 2-HOUR FIRE BARRIERS CONSTRUCTED IN
 ACCORDANCE WITH SECTION 707 OR HORIZONTAL ASSEMBLIES
 CONSTRUCTED IN ACCORDANCE WITH SECTION 711, OR BOTH.
  -SEE 1022.10.1 FOR EXCEPTIONS
  
 60) 1024.1 FBC[B] GENERAL. APPROVED LUMINOUS EGRESS
 PATH MARKINGS DELINEATING THE EXIT PATH SHALL BE
 PROVIDED IN HIGH-RISE BUILDINGS OF GROUP A, B, E, I, M,
 AND R-1 OCCUPANCIES IN ACCORDANCE WITH SECTIONS 1024.1
 THROUGH 1024.5.
 EXCEPTION: LUMINOUS EGRESS PATH MARKINGS SHALL NOT BE
 REQUIRED ON THE LEVEL OF EXIT DISCHARGE IN LOBBIES THAT
 SERVE AS PART OF THE EXIT PATH IN ACCORDANCE WITH
 SECTION 1027.1, EXCEPTION 1
  
 61) 1024.2 FBC[B] MARKINGS WITHIN EXIT COMPONENTS.
 EGRESS PATH MARKINGS SHALL BE PROVIDED IN INTERIOR EXIT
 STAIRWAYS, INTERIOR EXIT RAMPS AND EXIT PASSAGEWAYS, IN
 ACCORDANCE WITH SECTIONS 1024.2.1 THROUGH 1024.2.6.
  -ADD DETAILS TO SHOW COMPLIANCE WITH 1024.2.1 THROUGH
 1024.2.6
  
 62) 1207 FBC[B] PROVIDE FLOORING SUBMITTAL FOR SOUND
 CONTROL, OR ADD TO THE DEFERRED SUBMITTAL LIST.
  -PLEASE ADVISE, WHAT FLOORING AND UNDERLAYMENT ARE
 PROPOSED? PLEASE ADVISE VIA EMAIL. IF THE UNDERLAYMENT
 PRODUCT PROPOSED IS NOT ONE FOR WHICH WE HAVE TEST
 REPORTS ON FILE, THE FOLLOWING REPORTS ARE REQUIRED:
 1207.2 FBC[B] AIR-BORNE SOUND. WALLS, PARTITIONS AND
 FLOOR/CEILING ASSEMBLIES SEPARATING DWELLING UNITS FROM
 EACH OTHER OR FROM PUBLIC OR SERVICE AREAS SHALL HAVE A
 SOUND TRANSMISSION CLASS (STC) OF NOT LESS THAN 50 (45
 IF FIELD TESTED) FOR AIR-BORNE NOISE WHEN TESTED IN
 ACCORDANCE WITH ASTM E 90. PENETRATIONS OR OPENINGS IN
 CONSTRUCTION ASSEMBLIES FOR PIPING; ELECTRICAL DEVICES;
 RECESSED CABINETS; BATHTUBS; SOFFITS; OR HEATING,
 VENTILATING OR EXHAUST DUCTS SHALL BE SEALED, LINED,
 INSULATED OR OTHERWISE TREATED TO MAINTAIN THE REQUIRED
 RATINGS. THIS REQUIREMENT SHALL NOT APPLY TO DWELLING
 UNIT ENTRANCE DOORS; HOWEVER, SUCH DOORS SHALL BE TIGHT
 FITTING TO THE FRAME AND SILL.
 1207.3 FBC[B] STRUCTURE-BORNE SOUND. FLOOR/CEILING
 ASSEMBLIES BETWEEN DWELLING UNITS OR BETWEEN A DWELLING
 UNIT AND A PUBLIC OR SERVICE AREA WITHIN THE STRUCTURE
 SHALL HAVE AN IMPACT INSULATION CLASS (IIC) RATING OF
 NOT LESS THAN 50 (45 IF FIELD TESTED) WHEN TESTED IN
 ACCORDANCE WITH ASTM E 492.
 FBC 603.1, ALLOWABLE MATERIALS IN NON COMBUSTIBLE
 BUILDINGS, SEE ITEM 2, EXCEPTION 2, ACOUSTICAL
 INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID
 DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED
 TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200. SEE
 803.1.1, PROVIDE TEST DATA IN ACCORDANCE WITH ASTM E 84
 OR UL 723.
  -MANUFACTURER SPEC SHEETS ARE NOT ACCEPTABLE DUE TO
 DISCREPANCIES BETWEEN SPEC SHEETS/BROCHURES AND TEST
 REPORTS FOR SOME MANUFACTURERS (NOT NECESSARILY THE
 MANUFACTURER SELECTED; THIS IS A GENERAL COMMENT)
  
 63) 1012.9 FBC[B] INTERMEDIATE HANDRAILS. STAIRWAYS
 SHALL HAVE INTERMEDIATE HANDRAILS LOCATED IN SUCH A
 MANNER THAT ALL PORTIONS OF THE STAIRWAY MINIMUM WIDTH
 OR REQUIRED CAPACITY ARE WITHIN 30 INCHES (762 MM) OF A
 HANDRAIL. ON MONUMENTAL STAIRS, HANDRAILS SHALL BE
 LOCATED ALONG THE MOST DIRECT PATH OF EGRESS TRAVEL.
  -CHECK COMPLIANCE WITH 1012.9 AT BALLROOM STEPS.
  
 64) 1210.2 FBC[B] FINISH MATERIALS. WALLS, FLOORS AND
 PARTITIONS IN TOILET AND BATHROOMS SHALL COMPLY WITH
 SECTIONS 1210.2.1 THROUGH 1210.2.4.
  
 65) 1210.2.1 FBC[B] FLOORS AND WALL BASES. IN OTHER
 THAN DWELLING UNITS, TOILET, BATHING AND SHOWER ROOM
 FLOOR FINISH MATERIALS SHALL HAVE A SMOOTH, HARD,
 NONABSORBENT SURFACE. THE INTERSECTIONS OF SUCH FLOORS
 WITH WALLS SHALL HAVE A SMOOTH, HARD, NONABSORBENT
 VERTICAL BASE THAT EXTENDS UPWARD ONTO THE WALLS NOT
 LESS THAN 4 INCHES (102 MM).
  
 66) 1210.2.2 FBC[B] WALLS AND PARTITIONS. WALLS AND
 PARTITIONS WITHIN 2 FEET (610 MM) OF SERVICE SINKS,
 URINALS AND WATER CLOSETS SHALL HAVE A SMOOTH, HARD,
 NONABSORBENT SURFACE, TO A HEIGHT OF NOT LESS THAN 4
 FEET (1219 MM) ABOVE THE FLOOR, AND EXCEPT FOR
 STRUCTURAL ELEMENTS, THE MATERIALS USED IN SUCH WALLS
 SHALL BE OF A TYPE THAT IS NOT ADVERSELY AFFECTED BY
 MOISTURE. EXCEPTION: THIS SECTION DOES NOT APPLY TO THE
 FOLLOWING BUILDINGS AND SPACES: SEE 1210.2.2 FOR
 EXCEPTIONS.
  
 67) 3006.3 FBC[B] HOISTWAY OPENING PROTECTION. WHERE
 SECTION 3006.2 REQUIRES PROTECTION OF THE ELEVATOR
 HOISTWAY DOOR OPENING, THE PROTECTION SHALL BE PROVIDED
 BY ONE OF THE FOLLOWING:
  -(SEE OPTIONS 1-4 FROM FBC 3007.6.4) HOW IS PROTECTION
 PROVIDED FOR ELEVATORS 8, 9 AND 10? ALSO, P-15, P-16,
 P-06 AND P-07
  
 68) 3001 FBC[B] PROVIDE DETAILS OF FREIGHT ELEVATOR.
 A. TYPE OF ELEVATOR AND REFERRENCED STANDARDS.
  B. HOW IS MACHINE ROOM ACCESSED?
  
 69) 3006.3 FBC[B] PRESSURIZATION. THE ELEVATOR MACHINE
 ROOM, CONTROL ROOMS OR CONTROL SPACE WITH OPENINGS INTO
 A PRESSURIZED ELEVATOR HOISTWAY SHALL BE PRESSURIZED
 UPON ACTIVATION OF A HEAT OR SMOKE DETECTOR LOCATED IN
 THE ELEVATOR MACHINE ROOM, CONTROL ROOM OR CONTROL
 SPACE.
  -PROVIDE PRESSURIZATION ANALYSIS.
  
 70) 3005.1 FBC[B] ACCESS. AN APPROVED MEANS OF ACCESS
 SHALL BE PROVIDED TO ELEVATOR MACHINE ROOMS, CONTROL
 ROOMS, CONTROL SPACES AND MACHINERY SPACES.
  -HOW ARE MACHINE ROOMS ACCESSED FOR P-06, P-07, P-16,
 P-17 AND FREIGHT ELEVATORS?
  
 71) 3005.3 FBC[B] PRESSURIZATION. THE ELEVATOR MACHINE
 ROOM, CONTROL ROOMS OR CONTROL SPACE WITH OPENINGS INTO
 A PRESSURIZED ELEVATOR HOISTWAY SHALL BE PRESSURIZED
 UPON ACTIVATION OF A HEAT OR SMOKE DETECTOR LOCATED IN
 THE ELEVATOR MACHINE ROOM, CONTROL ROOM OR CONTROL
 SPACE.
  
 72) 3006 FBC[B] GENERAL COMMENT. THIS COMMENT APPLIES
 TO ALL OTHER ELEVATOR DRAWINGS. AT THIS STAGE THEY MAY
 LACK COMPLETION, SO FURTHER REVIEW WILL BE REQUIRED
 UPON RESUBMITTAL.
  -ELEVATORS P-06 AND 07. HOW DO YOU ACCESS MACHINE
 ROOMS?
  
 73) 3306.1 FBC[B] PROTECTION REQUIRED. PEDESTRIANS
 SHALL BE PROTECTED DURING CONSTRUCTION, REMODELING AND
 DEMOLITION ACTIVITIES AS REQUIRED BY THIS CHAPTER AND
 TABLE 3306.1. SIGNS SHALL BE PROVIDED TO DIRECT
 PEDESTRIAN TRAFFIC.
  -AS THE BUILDING CONSTRUCTION INCREASES THE SIDEWALK
 PROTECTION WILL NEED TO MEET REQUIREMENTS BELOW.
  -SEE 3306.1 TO 3306.9 FOR REQUIREMENTS TO PROVIDE
 WALKWAYS, BARRIERS AND COVERED WALKWAYS.
  
 74) 3007.7.4 FBC[B] LOBBY SIZE. EACH ENCLOSED FIRE
 SERVICE ACCESS ELEVATOR LOBBY SHALL BE NOT LESS THAN
 150 SQUARE FEET (14 M2) IN AN AREA WITH A MINIMUM
 DIMENSION OF 8 FEET (2440 MM).
  -ALS1.114 FIRE LOBBY ON FLOORS 12-30 IS UNDERSIZED.
 CORRIDOR 01-40 ON ALS1.101. GROUND LEVEL FIRE SERVICE
 AND FREIGHT ARE SHOWING ELEVATOR LOBBIES. THIS ARE NOT
 REQUIRED AT EXIT LEVEL AND THE FIRE SERVICE WOULD NOT
 PROVIDE 150 SQ. FT. PLEASE REVIEW THIS AND COORDINATE
 IF FREIGHT IS PRESSURIZED, OR IF LOBBY REQUIRED AT
 LEVEL 7.
  
 75) 3007.7.1 ACCESS. DOOR CONFIGURATION TWO 90 SWINGING
 INTO EXIT STAIR FROM FIRE SERVICE LOBBY.
  -EXIT DOOR FROM FIRE LOBBY WOULD BLOCK EXIT DOOR FROM
 CORRIDOR. PLEASE REVIEW CONFIGURATION AND POSSIBLE. CAN
 SWING FROM FIRE LOBBY BE CHANGED BASED ON 1010.1.2.1
 FBC[B] DIRECTION OF SWING?
  
 76) 3007.7.4 FBC[B] LOBBY SIZE. REGARDLESS OF THE
 NUMBER OF FIRE SERVICE ACCESS ELEVATORS SERVED BY THE
 SAME ELEVATOR LOBBY, THE ENCLOSED FIRE SERVICE ACCESS
 ELEVATOR LOBBY SHALL BE NOT LESS THAN 150 SQUARE FEET
 (14 M2) IN AN AREA WITH A DIMENSION OF NOT LESS THAN 8
 FEET (2440 MM).
  A. FIRE LOBBIES THAT SERVE RESIDENTIAL FIRE SERVICE
 ACCESS ELEVATORS DO NOT MEET THE MINIMUM SIZE REQUIRED
 IN 3007.7.4. PLEASE REVIEW AND ADJUST ACCORDINGLY.
  B. FIRE LOBBY S1 AT EXIT LEVEL IS UNDER SIZED AND FIRE
 LOBBY ISN'T REQUIRED ON EXIT LEVEL. PLEASE REVIEW AND
 ADJUST.
  PLEASE REVIEW TO MEET 3007.7.4
  
 77) 3006.2 FBC[B] HOISTWAY OPENING PROTECTION REQUIRED
 . PROTECTION OF ELEVATOR HOISTWAY DOOR OPENINGS IS NOT
 REQUIRED AT THE LEVEL(S) OF EXIT DISCHARGE, PROVIDED
 THE LEVEL(S) OF EXIT DISCHARGE IS EQUIPPED WITH AN
 AUTOMATIC SPRINKLER SYSTEM IN ACCORDANCE WITH SECTION
 903.3.1.1.
  
 78) 3007.6.2 LOBBY ENCLOSURE. THE FIRE SERVICE ACCESS
 ELEVATOR LOBBY SHALL BE ENCLOSED WITH A SMOKE BARRIER
 HAVING A FIRE-RESISTANCE RATING OF NOT LESS THAN 1
 HOUR, EXCEPT THAT LOBBY DOORWAYS SHALL COMPLY WITH
 SECTION 3007.6.3. EXCEPTION: ENCLOSED FIRE SERVICE
 ACCESS ELEVATOR LOBBIES ARE NOT REQUIRED AT THE LEVELS
 OF EXIT DISCHARGE.
  
 NOTES:
  
 -PLEASE PROVIDE COMMENT RESPONSE SHEET TO EXPLAIN HOW
 EACH COMMENT IS BEING ADDRESSED.
  
 -COMMENTS ARE A BRIEF OVERVIEW OF CODE SECTIONS.
 FURTHER REVIEW OF THE REFERENCED CODE SECTIONS WILL BE
 REQUIRED.
  
 -ADDITIONAL COMMENTS MAY BE FORTHCOMING PENDING REVIEW
 OF MATERIALS REQUESTED.
  
 PLEASE FEEL FREE TO CONTACT ME AT 561-805-6718 (M-F
 8-5) TO DISCUSS COMMENTS, OR E-MAIL ANYTIME
 [email protected]
  
  
  

Review Stop E ELECTRICAL
Rev No 5 Status P Date 2021-06-14 Cont ID  
Sent By jleahy Date 2021-06-14 Time 14:16 Rev Time 0.00
Received By jleahy Date 2021-06-04 Time 16:03 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 4 Status F Date 2021-01-27 Cont ID  
Sent By jleahy Date 2021-01-27 Time 08:34 Rev Time 0.00
Received By jleahy Date 2021-01-11 Time 08:33 Sent To  
Notes
2021-01-27 08:36:20ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 FLORIDA BUILDING CODE 2017 6TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED
 NFPA 70 2014 EDITION
  
 JAKE LEAHY BN, BU, PX
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 PAGE E.502A
 1) NO SIZES OF CONDUCTORS FROM THE PANELS TO THE
 TRANSFORMERS AND THEN AGAIN ON THE SECONDARY SIDE.
  
 2) GROUNDING SHOWN AT TRANSFORMERS PLEASE INDICATE WHAT
 THEY ARE TO TIE INTO FOR GROUNDING.
  
 3) FEEDERS TO THE FOLLOWING SHOW NOT SIZES AS WELL
 N2A1, SWB3, SWBC, SWBH4, SWBH1, SWBH3, KITCHEN PANEL,
 POOL PANEL, HOTEL POOL PANEL, GYM PANEL, AND N4H8B.
  
 PAGE E.502B
 1) NO SIZES OF CONDUCTORS FROM THE PANELS TO THE
 TRANSFORMERS AND THEN AGAIN ON THE SECONDARY SIDE.
  
 2) NO FEEDER SIZES TO CH, CWH
  
 PAGE E503
 1) GENERATOR 1 HAS 800A FEEDER WITH OVERCURRENT
 PROTECTION GOING TO FIRE PUMP, BUT IT HAS A 1600A
 FEEDER WITH NO OVER CURRENT PROTECTION AT THE GENERATOR
 WHAT SECTION ALLOWS THIS AND IF IT DOES THE CONDUCTORS
 WILL HAVE TO BE 115% PER 445.13
  
 2) PANEL DQ4H5 SHOWS NO OVERCURRENT PROTECTION SIZES
 AND APPEARS TO HAVE 3 SPARES?
  
 3) PANEL DE4H5 SAME AS ABOVE
  
 4) PANEL DQ4HRB NO WIRE SIZES FROM PANEL TO TRANSFORMER
 AND THEN AGAIN ON THE SECONDARY SIDE OF THE
 TRANSFORMER.
  
 PAGE E504
 1) WIRE SIZES FROM PANELS TO TRANSFORMER AND THEN AGAIN
 ON THE SECONDARY SIDE.
  
 2) SWBNRR NO SIZES ON OVERCURRENT PROTECTION 5 SPARES?
  
 3) DN4PR1 NO OVERCURRENT SIZES ON BREAKERS.
  
  
 PAGE E505
 1) PANELS DQ4RRA, DE4RR, AND DQ4RRB HAVE NO OVERCURRENT
 PROTECTION SHOWN ON BREAKERS AND IF THERE ARE SPARES.
  
 2) WIRE SIZES FROM PANELS TO TRANSFORMERS AND ON THE
 SECONDARY SIDE ARE NOT SHOWN.
  
 PLANS ARE GENERALY GOOD PLANS BUT THE RISER HAS YOU
 LOOKING IN SEVERAL PLACES TO COME UP WITH THE SIZES OF
 CONDUCTORS AND OVERCURRENT PROTECTION ON PRIMARIES AND
 SECONDARIES OF THE TRANSFORMERS. IT WOULD BE A BENEFIT
 TO HAVE THE WIRE SIZES AND OVERCURRENT PROTECTION ON
 THE RISER MAYBE WITH A TABLE SHOWING THE WIRES AND
 OCPS.
  
 SMOKE ALARMS IN RESIDENTIAL UNITS NEEDS TO BE LOOKED AT
 IN REFERENCE TO LOCATIONS OF THE SMOKE ALARMS OR
 DETECTORS. NFPA 72 GIVES LOCATIONS FOR SMOKE ALARMS
 NEAR BATHROOM DOORS AND COOKING APPLIANCES THAT SEEMED
 TO HAVE BEEN OVERLOOKED. SEE NFPA 72 SECTIONS
 29.8.3.4(4), AND (6) FOR COOKING APPLIABCES AND
 BATHROOM LOCATIONS.

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2021-01-27 Cont ID  
Sent By jleahy Date 2021-01-27 Time 07:37 Rev Time 0.00
Received By jleahy Date 2021-01-11 Time 16:40 Sent To  
Notes
2021-02-03 07:39:15ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 FLORIDA BUILDING CODE 2017 6TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED
 NFPA 70 2014 EDITION
  
 JAKE LEAHY BN, BU, PX
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 PAGE E.502A
 1) NO SIZES OF CONDUCTORS FROM THE PANELS TO THE
 TRANSFORMERS AND THEN AGAIN ON THE SECONDARY SIDE.
  
 2) GROUNDING SHOWN AT TRANSFORMERS PLEASE INDICATE WHAT
 THEY ARE TO TIE INTO FOR GROUNDING.
  
 3) FEEDERS TO THE FOLLOWING SHOW NOT SIZES AS WELL
 N2A1, SWB3, SWBC, SWBH4, SWBH1, SWBH3, KITCHEN PANEL,
 POOL PANEL, HOTEL POOL PANEL, GYM PANEL, AND N4H8B.
  
 PAGE E.502B
 1) NO SIZES OF CONDUCTORS FROM THE PANELS TO THE
 TRANSFORMERS AND THEN AGAIN ON THE SECONDARY SIDE.
  
 2) NO FEEDER SIZES TO CH, CWH
  
 PAGE E503
 1) GENERATOR 1 HAS 800A FEEDER WITH OVERCURRENT
 PROTECTION GOING TO FIRE PUMP, BUT IT HAS A 1600A
 FEEDER WITH NO OVER CURRENT PROTECTION AT THE GENERATOR
 WHAT SECTION ALLOWS THIS AND IF IT DOES THE CONDUCTORS
 WILL HAVE TO BE 115% PER 445.13
  
 2) PANEL DQ4H5 SHOWS NO OVERCURRENT PROTECTION SIZES
 AND APPEARS TO HAVE 3 SPARES?
  
 3) PANEL DE4H5 SAME AS ABOVE
  
 4) PANEL DQ4HRB NO WIRE SIZES FROM PANEL TO TRANSFORMER
 AND THEN AGAIN ON THE SECONDARY SIDE OF THE
 TRANSFORMER.
  
 PAGE E504
 1) WIRE SIZES FROM PANELS TO TRANSFORMER AND THEN AGAIN
 ON THE SECONDARY SIDE.
  
 2) SWBNRR NO SIZES ON OVERCURRENT PROTECTION 5 SPARES?
  
 3) DN4PR1 NO OVERCURRENT SIZES ON BREAKERS.
  
  
 PAGE E505
 1) PANELS DQ4RRA, DE4RR, AND DQ4RRB HAVE NO OVERCURRENT
 PROTECTION SHOWN ON BREAKERS AND IF THERE ARE SPARES.
  
 2) WIRE SIZES FROM PANELS TO TRANSFORMERS AND ON THE
 SECONDARY SIDE ARE NOT SHOWN.
  
 PLANS ARE GENERALY GOOD PLANS BUT THE RISER HAS YOU
 LOOKING IN SEVERAL PLACES TO COME UP WITH THE SIZES OF
 CONDUCTORS AND OVERCURRENT PROTECTION ON PRIMARIES AND
 SECONDARIES OF THE TRANSFORMERS. IT WOULD BE A BENEFIT
 TO HAVE THE WIRE SIZES AND OVERCURRENT PROTECTION ON
 THE RISER MAYBE WITH A TABLE SHOWING THE WIRES AND
 OCPS.
  
 SMOKE ALARMS IN RESIDENTIAL UNITS NEEDS TO BE LOOKED AT
 IN REFERENCE TO LOCATIONS OF THE SMOKE ALARMS OR
 DETECTORS. NFPA 72 GIVES LOCATIONS FOR SMOKE ALARMS
 NEAR BATHROOM DOORS AND COOKING APPLIANCES THAT SEEMED
 TO HAVE BEEN OVERLOOKED. SEE NFPA 72 SECTIONS
 29.8.3.4(4), AND (6) FOR COOKING APPLIABCES AND
 BATHROOM LOCATIONS.

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2020-03-04 Cont ID  
Sent By jpearson Date 2020-03-04 Time 15:48 Rev Time 0.00
Received By jpearson Date 2020-03-01 Time 15:09 Sent To  
Notes
2020-03-04 11:09:38CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 PREVIOUS COMMENTS THAT HAVE BEEN ADDRESSED
 SATISFACTORILY ARE MARKED AS CORRECTED. PREVIOUS
 COMMENTS THAT HAVE NOT BEEN ADDRESSED SATISFACTORILY
 HAVE ADDITIONAL COMMENTS IN PARENTHESES. ANY NEW
 COMMENTS WILL BE LISTED AFTER PREVIOUS COMMENTS.
  
 1. CORRECTED.
 2. CORRECTED.
 3. CORRECTED.
 4. CORRECTED.
 5. CORRECTED.
 6. CORRECTED.
 7. CORRECTED.
 8. CORRECTED.
 9. CORRECTED.
 10. CORRECTED.
 11. CORRECTED.
 12. CORRECTED.
 13. CORRECTED.
 14. CORRECTED.
 15. CORRECTED.
 16. CORRECTED.
 17. CORRECTED.
 18. SHEETS E.506 AND E.803, SPECIFY WIRES SIZES FOR
 GROUNDING SYSTEM TO CONFIRM CODE COMPLIANCE. NEC 250;
 WPB FBC 107.2.1 (THESE SHEETS SEEM TO BE A AN EXACT
 DUPLICATE, WHY ARE BOTH SHEETS NEEDED? SHEET E.506 IS
 NOT SHOWN IN THE LEGEND OF SHEETS ON E.603. ALSO, THE
 MAIN BONDING JUMPER SHOULD BE SIZED AT 12.5% OF TOTAL
 FEEDER SIZE WHEN USING PARALLEL FEEDS. PROVIDE
 CORRECTION. NEC 250.102(C)(1))
 19. PROVIDE ACCURATE LOAD CALCULATION FOR ALL SERVICES.
 NEC 220; WPB FBC 107.2.1 (LOAD CALCULATION FOR HOTEL /
 GUEST ROOMS INCLUDES 166,588 VA FOR UNITS WITHOUT
 COOKING. I ADDED THE LOAD FOR ALL OF THESE UNITS AND
 CAME UP WITH 845,034 VA. PROVIDE CLARIFICATION AND/OR
 CORRECTION.)
 20. CORRECTED.
 21. CORRECTED.
 22. CORRECTED.
 23. PROVIDE COMPLETED PANEL SCHEDULE FOR EACH PANEL,
 INDICATING ANY NEW OR ALTERED CIRCUITS, THE WIRE AND
 BREAKER SIZE FOR THESE CIRCUITS, AND AFCI OR GFCI
 PROTECTION WHERE APPLICABLE TO COMPLY WITH CODE. MANY
 PANELS SCHEDULES PROVIDED ARE BLANK OR HAVE LIMITED
 INFORMATION. NEC 210.8, 210.12, 210.19, 210.20, 215.5,
 408.4 (SHHET E.616, 3 PANELS SHOWS CIRCUITS BEING FED,
 BUT NO LOAD FOR THOSE CIRCUITS. PANELS N2H8, N2H9, AND
 N2H12. PROVIDE CORRECTION.)
 24. CORRECTED.
 25. CORRECTED.
 26. CORRECTED.
 27. CORRECTED.
  
 NEW COMMENTS:
  
 28. SHEET E.207D, RESTROOM 0756 AND 0757, THE
 RECEPTACLE OUTLET IS NOT GFCI PROTECTED. PROVIDE
 CORRECTION. NEC 210.8
 29. SHEET E.107D AND E.108D, THERE SHOULD BE A MINUMUM
 OF 3 FOOT CANDLES OF LIGHT AT THE POOL WATER SURFACE
 AND THE POOL WET DECK SURFACE FOR OUTDOOR POOLS, AND 10
 FOOT CANDLES FOR INDOOR POOLS. PROVIDE COMPLIANCE. FBC
 454.1.4.2
 30. SHEET E.301 AND E.303, KEYNOTE 1 SHOWS A RECEPTACLE
 OUTLET FOR A TV IN A WATERPROOF ENCLOSURE. A RECEPTACLE
 OUTLET IS NOT PERMITTED IN THE TUB OR SHOWER SPACE.
 PROVIDE CORRECTION. NEC 406.9(C)
 31. SHEETS E.306, 307, 308, 309, 310, AND 311 ALL SHOW
 INCORRECT WIRING OF BATHROOM CIRCUITS IN MODELS C1, D2,
 B3.1, D3, D1, E1, B5, D4, AND B6. THERE MAY BE SOME
 THAT I MISSED. A MINIMUM OF ONE 20 AMPERE BRANCH
 CIRCUIT SHALL BE PROVIDED TO SUPPLY BATHROOM RECEPTACLE
 OUTLET(S). SUCH CIRCUITS SHALL HAVE NO OTHER OUTLETS.
 WHEN AN INDIVIDUAL CIRCUIT IS RAN TO A BATHROOM AND
 THIS CIRCUIT IS USED FOR LIGHTING AND RECEPTACLE
 OUTLETS, THIS CIRCUIT CANNOT BE USED IN ANOTHER
 BATHROOM. IF THE CIRCUIT IS USED ONLY FOR THE
 RECEPTACLE OUTLETS, IT CAN BE USED TO FEED OTHER
 RECEPTACLE OUTLETS IN A DIFFERENT BATHROOM. SEVERAL
 LOCATIONS SHOW CIRCUIT 14 OR 26, SOMETIMES BOTH, BEING
 USED FOR LIGHTING AND RECEPTACLE OUTLETS IN MULTILPLE
 BATHROOMS. PROVIDE CORRECTION. NEC 210.11(C)(3)
 32. SHEET E.501 SHOWS A 1200 AMP SERVICE FOR FUTURE
 RETAIL USE. THIS DOES NOT HAVE A DESIGNATION THE SAME
 AS OTHER MAINS DO. PLEASE CLARIFY THE NAME OF THIS
 MAIN. WPB FBC 107.2.1
 33. SHEET E.502A, BUSWAY RISER HA, 11TH FLOOR
 DISCONNECT IS SHOWN AS A 300 AMP BREAKER WITH A 200 AMP
 FEEDER TO THE DOWNSTREAM PANEL. PROVIDE CLARIFICATION
 AND/OR CORRECTION. NEC 215.2, 240.4, 310.15(B)(16); WPB
 FBC 107.2.1
 34. SHEET E.603, PANEL SCHEDULE LEGEND. THE LEGEND FOR
 SHEETS E.604, E.606, E.607, E.610, E.611, E.616, AND
 E.622 DO NOT MATCH WHAT IS ON THOSE PAGES. SHEET E.506
 IS NOT IN THE LEGEND. PROVIDE CORRECTIONS. WPB FBC
 107.2.1
 35. SHEET E.614, PANEL SWBNRR IS SHOWN AS A 1000 AMP
 PANEL. THE RISER DIAGRAM SHOWS THIS AS A 2500 AMP
 PANEL. THE LOADS SPECIFIED IN PANEL SCHEDULE ARE
 DIFFERENT THAN WHAT IS SHOWN ON RISER. PROVIDE
 CLARIFICATION AND/OR CORRECTION. WPB FBC 107.2.1; NEC
 215.2, 240.4, 310.15(B)(16)
 36. SHEET E.615, PANEL DN4H1 IS SHOWN AS AN 800 AMP
 PANEL WITH A LOAD OF 945 AMPS. PROVIDE CLARIFICATION
 AND/OR CORRECTION. WPB FBC 107.2.1; NEC 215.2, 240.4,
 310.15(B)(16)
 37. SHEET E.615, PANEL N2H1 IS SHOWN AS AN 400 AMP
 PANEL WITH A LOAD OF 1959 AMPS. PROVIDE CLARIFICATION
 AND/OR CORRECTION. WPB FBC 107.2.1; NEC 215.2, 240.4,
 310.15(B)(16)
 38. SHEET E.622, PANEL N4H7E IS SHOWN AS AN 225 AMP
 PANEL WITH A LOAD OF 277 AMPS. PROVIDE CLARIFICATION
 AND/OR CORRECTION. WPB FBC 107.2.1; NEC 215.2, 240.4,
 310.15(B)(16)
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD
 SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2019-03-29 Cont ID  
Sent By jpearson Date 2019-03-29 Time 10:23 Rev Time 0.00
Received By jpearson Date 2019-03-25 Time 14:18 Sent To  
Notes
2019-03-29 10:23:07CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 BE ADVISED THAT A COMPLETE REVIEW WAS NOT POSSIBLE AT
 THIS TIME. THE PLANS PROVIDED STATE THEY ARE 80%
 DOCUMENTS, BUT IT APPEARS THE ELECTRICAL PORTION IS
 LESS THAN THAT. SOME PAGES, SUCH AS E.502A, E.502B,
 E.503, E.504A, AND E.504B ARE BLANK. OTHER PAGES THAT
 STATE THEY ARE FOR LIGHTING AND POWER ARE MISSING
 LIGHTING IN KEY AREAS, NOT EVEN SHOWING THE REQUIRED
 MEANS OF EGRESS ILLUMINATION PER FBC 1008.2.1, AND NOT
 SHOWING CIRCUIT NUMBERS AND KEY INFORMATION ON POWER
 ITEMS. THEREFORE, THE NEXT REVIEW WILL LIKELY CONTAIN
 COMMENTS FOR CORRECTION THAT ARE NOT ADDRESSED IN THIS
 REVIEW.
  
 1. SHEET E.201B, PROVIDE GFCI PROTECTION FOR ALL
 RECEPTACLE OUTLETS IN KITCHEN. NEC 210.8(B)(2)
 2. SHEET E.202A, PROVIDE GFCI PROTECTION FOR ALL
 RECEPTACLE OUTLETS IN BATHROOM. NEC 210.8(B)(1)
 3. PROVIDE AVAILABLE SHORT CIRCUIT CALCULATION FOR
 SERVICE AND DOWNSTREAM PANELS, INCLUDING INFORMATION
 FROM THE POWER COMPANY STATING WHAT THE AVAILABLE SHORT
 CIRCUIT CURRENT IS FOR THE SERVICE TO CONFIRM THE
 STATED AIC RATING OF THE SERVICE EQUIPMENT AND
 DOWNSTREAM PANELS IS ADEQUATE. NEC 110.9, 110.10; FBC
 RE E3606.3
 4. PROVIDE NOTES TO INDICATE THE REQUIRED MARKING OF
 SERVICE EQUIPMENT FOR ARC FLASH HAZARD WARNING AND
 AVAILABLE FAULT CURRENT PER CODE. NEC 110.16, 110.24
 5. PROVIDE CHART OF INTERIOR LIGHTING POWER ALLOWANCES
 EXPRESSED IN WATTAGE PER THE FBC ENERGY CODE IN
 RELATION TO THE WATTAGE OF THE CONNECTED INTERIOR
 LIGHTING PROPOSED TO COMPLY WITH CODE. FOR RESIDENTIAL
 AREAS, A MINIMUM OF 75 PERCENT OF THE LAMPS IN
 PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL BE
 HIGH-EFFICACY LAMPS OR A MINIMUM OF 75 PERCENT OF THE
 PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL CONTAIN
 ONLY HIGH EFFICACY LAMPS. FBC EC C405.1, C405.4.2
 6. PROVIDE THE ADDITIONAL INTERIOR LIGHTING CONTROLS
 STIPULATED IN THE FBC ENERGY CODE. MANY AREAS DO NOT
 SHOW THE AUTOMATIC CONTROL REQUIRED. FBC EC C405.2
 7. PROVIDE VOLTAGE DROP CALCULATIONS TO COMPLY WITH
 CODE. FBC EC C405.6.3
 8. PROVIDE BLOCK NOTE INDICATING COMPLIANCE: ?WITHIN 30
 DAYS AFTER THE DATE OF SYSTEM ACCEPTANCE, RECORD
 DRAWINGS OF THE ACTUAL INSTALLATION SHALL BE PROVIDE TO
 THE BUILDING OWNER, INCLUDING: 1. A SINGLE LINE DIAGRAM
 OF THE BUILDING ELECTRICAL DISTRIBUTION SYSTEM AND 2.
 FLOOR PLANS INDICATING LOCATION AND AREA SERVED FOR ALL
 DISTRIBUTION.? FBC EC C405.6.4.1
 9. PROVIDE RECEPTACLE CONTROL REQUIRED BY ASHREA 90.1:
 8.4.2. PER THIS REQUIREMENT, THE FOLLOWING SHALL BE
 AUTOMATICALLY CONTROLLED: 1) AT LEAST 50% OF ALL
 125-VOLT, 15 AND 20 AMP RECEPTACLES, IN ALL PRIVATE
 OFFICES, CONFERENCE ROOMS, ROOMS USED PRIMARILY FOR
 PRINTING AND/OR COPYING FUNCTIONS, BREAK ROOMS,
 CLASSROOMS, AND INDIVIDUAL WORKSTATIONS. 2) AT LEASE
 25% OF BRANCH CIRCUIT FEEDERS INSTALLED FOR MODULAR
 FURNITURE NOT SHOWN ON THE CONSTRUCTION DOCUMENTS. FBC
 EC C405.6.1
 10. FOR POOL ROOM EQUIPMENT SHOWN ON SHEETS E.205C AND
 E.207A, PROVIDE ENCLOSURE TYPES DESIGNED TO PROTECT
 AGAINST CORROSIVE ENVIRONMENTS. NEC TABLE 110.28
 11. SHEET E.207D, PROVIDE GFCI RECEPTACLE OUTLET FOR
 POOL PER CODE. NEC 680.22(A)
 12. PROVIDE GFCI PROTECTION FOR ALL ELECTRIC WATER
 COOLERS. NEC 422. 5, 422.52
 13. PROVIDE GFCI PROTECTION FOR DISHWASHERS IN DWELLING
 UNITS. NEC 210.8(D)
 14. SHEET E.218 AND E.405, PANEL SWBNHR DOES NOT APPEAR
 TO HAVE THE PROPER CLEARANCE TO ALLOW FOR ONE ENTRANCE
 TO AND EGRESS FROM THIS SPACE. ADDITIONAL INFORMATION
 IS NEEDED TO CONFIRM AS THERE IS NO PANEL SCHEDULE FOR
 THIS PANEL, OR ANY PERTINENT INFORMATION SUPPLIED.
 PROVIDE CLARIFICATION AND/OR CORRECTIONS AS NEEDED. NEC
 110.26(C)
 15. NOTE 5 ON SHEETS E.301, E.302, E.303, AND NOTE 8 ON
 SHEETS E.304, E.305, E.306, E.307, E.308, AND E.309 DO
 NOT PROVIDE AFCI PROTECTION TO CODE. ALL BRANCH
 CIRCUITS THAT SUPPLY 120-VOLT, SINGLE-PHASE, 15- AND
 20-AMPERE OUTLETS INSTALLED IN KITCHENS, FAMILY ROOMS,
 DINING ROOMS, LIVING ROOMS, PARLORS, LIBRARIES, DENS,
 BEDROOMS, SUN-ROOMS, RECREATIONS ROOMS, CLOSETS,
 HALLWAYS, LAUNDRY AREAS AND SIMILAR ROOMS OR AREAS
 SHALL BE AFCI PROTECTED. THIS INCLUDES LIGHTING AND
 POWER OUTLETS AND RECEPTACLES. SOME AREAS REQUIRE BOTH
 AFCI AND GFCI PROTECTION. PROVIDE CORRECTION. NEC
 210.8, 210.12
 16. SHEET E.505, FEEDER FROM GDP-GEN2 TO ATS ER IS
 SHOWN AS A 400 AMP FEEDER. HOWEVER, THIS IS FED FROM A
 600 AMP BREAKER. THE ATS IS ONLY RATED FOR 400 AMPS PER
 DESCRIPTION ON PLAN. PROVIDE CLARIFICATION AND/OR
 CORRECTIONS AS NEEDED. NEC 110.3, 310.15(B)(16), 701.4,
 701.5
 17. PROVIDE GROUND FAULT PROTECTION PER NEC 230.95.
 18. SHEETS E.506 AND E.803, SPECIFY WIRES SIZES FOR
 GROUNDING SYSTEM TO CONFIRM CODE COMPLIANCE. NEC 250;
 WPB FBC 107.2.1
 19. PROVIDE ACCURATE LOAD CALCULATION FOR ALL SERVICES.
 NEC 220; WPB FBC 107.2.1
 20. SHEET E.601, METER CENTER LOAD SUMMARY SHOWS A
 TOTAL LOAD FOR MC-1 AS 1,064,094 VA, WITH A DEMAND LOAD
 OF 330,120 VA. BUT THE FEEDER TO MC-1 SHOWS A LOAD OF
 840,000 VA AND A DEMAND LOAD OF 294,000, WITH A
 DIFFERENT NUMBER OF UNITS SPECIFIED. THERE ARE SIMILAR
 PROBLEMS WITH OTHER FEEDER CALCULATIONS. ALL DATA
 SHOULD BE CONSISTENT. PROVIDE CORRECTION. WPB FBC
 107.2.1 NEC 220
 21. THE LOAD CALCULATION PROVIDED FOR HOTEL GUEST ROOM
 SUITES USES THE LOAD CALCULATION METHOD FROM NEC
 220.82. FOR THE DEMAND FACTORS IN THIS SECTION TO BE
 USED, IT MUST BE A 120/240 OR 120/208 THREE WIRE
 (SINGLE PHASE) FEEDER WITH A MINIMUM AMPACITY OF 100
 AMPS. THE LOAD CALCULATION SHOWS THIS AS THREE PHASE.
 THE PANEL SCHEDULE ON SHEET E.603 SHOWS THE PANELS AS
 SINGLE PHASE. PROVIDE CLARIFICATIONS AND CORRECTIONS AS
 NEEDED. NEC 220; WPB FBC 107.2.1
 22. GUEST ROOM FEEDER DEMAND USES 480 VOLT, 3 PHASE FOR
 TOTAL DEMAND CALCULATIONS WHILE OTHER CALCULATIONS ARE
 AT 208 VOLT, 3 PHASE. PROVIDE CLARIFICATIONS AND/OR
 CORRECTIONS AS NEEDED. NEC 220; WPB FBC 107.2.1
 23. PROVIDE COMPLETED PANEL SCHEDULE FOR EACH PANEL,
 INDICATING ANY NEW OR ALTERED CIRCUITS, THE WIRE AND
 BREAKER SIZE FOR THESE CIRCUITS, AND AFCI OR GFCI
 PROTECTION WHERE APPLICABLE TO COMPLY WITH CODE. MANY
 PANELS SCHEDULES PROVIDED ARE BLANK OR HAVE LIMITED
 INFORMATION. NEC 210.8, 210.12, 210.19, 210.20, 215.5,
 408.4
 24. PROVIDE DETAILS OF SELECTIVE COORDINATION PER NEC
 700.28 AND 701.27.
 25. PROVIDE DETAILS OF ARC ENERGY REDUCTION PER NEC
 240.87
 26. PER NEC 230.72(B), THE DISCONNECTS FOR EMERGENCY
 SYSTEMS SHALL BE LOCATED REMOTELY FROM NORMAL POWER
 SYSTEMS. IT APPEARS FROM THIS DESIGN THAT THE NORMAL
 POWER FEEDERS AND THE EMERGENCY POWER FEEDERS ARE FED
 FROM THE SAME SWITCH BOARDS. PROVIDE CLARIFICATION
 AND/OR CORRECTION AS NEEDED. NEC 230.72(B)
 27. BE ADVISED THAT FIRE ALARM, LOW VOLTAGE SYSTEMS,
 DAS, LIGHTNING PROTECTION, GENERATORS, COMMERCIAL HOOD
 SYSTEMS, WALK IN COOLERS, SIGNS, SITE LIGHTING, AND
 SWIMMING POOLS (WHERE APPLICABLE) ARE NOT INCLUDED IN
 THE SCOPE OF THIS PLAN REVIEW. PROVIDE A BLOCK NOTE
 INDICATING THE REQUIRED SEPARATE PERMITS AND PLAN
 SUBMITTALS FOR ANY OF THESE SYSTEMS PRESENT. WPB FBC
 105.1, 107.2.1
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD
 SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  
  

Review Stop ENG ENGINEERING CSD
Rev No 3 Status P Date 2021-09-08 Cont ID  
Sent By rrossano Date 2021-09-08 Time   Rev Time 0.00
Received By rrossano Date 2021-09-08 Time   Sent To I
Notes
2021-09-08 08:33:01PASSED WITH PROVISO: CHECK WITH ENGINEERING SERVICES
 PRIOR TO ISSUANCE OF CO FOR COMPLETION OF ENGINEERING
 PERMIT (E19010014).

Review Stop ENG ENGINEERING CSD
Rev No 2 Status P Date 2020-02-11 Cont ID  
Sent By rrossano Date 2020-02-11 Time 07:34 Rev Time 0.00
Received By rrossano Date   Time   Sent To I
Notes
2020-02-11 07:34:40PASSED WITH PROVISO: CHECK WITH ENGINEERING SERVICES
 PRIOR TO ISSUANCE OF CO FOR COMPLETION OF ENGINEERING
 PERMIT (E19010014). CONTACT MANNY GONZALEZ, SENIOR
 ENGINEERING PROJECT COORDINATOR, ENGINEERING SERVICES
 DEPARTMENT, 401 CLEMATIS STREET, 4TH FLOOR, WEST PALM
 BEACH, FL 33401, EMAIL: [email protected],
 WWW.WPB.ORG/ENGINEERING
  

Review Stop ENG ENGINEERING CSD
Rev No 1 Status F Date 2019-03-22 Cont ID  
Sent By shill Date 2019-03-22 Time 15:48 Rev Time 0.00
Received By shill Date 2019-03-22 Time 15:48 Sent To  
Notes
2019-03-22 15:49:07CONTACT ENGINEERING DEPARTMENT DIRECTLY AND SUBMIT
 APPLICATION IF REQUIRED
 HTTP://WWW.WPB.ORG/DEPARTMENTS/ENGINEERING-PUBLIC-WORKS
 /FORMS,-PERMITS-APPLICATIONS
  
 ENGINEERING APPROVAL REQUIRED PRIOR TO PERMIT ISSUANCE
  
 MAIN PHONE: (561) 822-1200

Review Stop FIRE FIRE DEPARTMENT
Rev No 5 Status P Date 2021-06-07 Cont ID  
Sent By pleduc Date 2021-06-07 Time   Rev Time 0.00
Received By pleduc Date 2021-05-20 Time 10:02 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status P Date 2021-01-25 Cont ID  
Sent By pleduc Date 2021-01-25 Time   Rev Time 0.00
Received By pleduc Date 2021-01-07 Time 09:35 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2020-03-13 Cont ID  
Sent By pleduc Date 2020-03-13 Time   Rev Time 0.00
Received By pleduc Date 2020-02-21 Time 09:11 Sent To  
Notes
2020-03-12 10:09:50THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 PLEASE CONSIDER THE FOLLOWING AS PROVISO:
  
 THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED
 AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE
 PROVISO COMMENTS WILL RESULT IN A FAILED FIRE
 INSPECTION.
  
  
  
 1) SHEET A 1.108 - PLEASE REVIEW THE REQUIREMENT FOR AN
 ELEVATOR LOBBY AT THE FREIGHT ELEVATOR.
  
 PLEASE REVIEW AND CORRECT, IF APPLICABLE, WITH
 REVISIONS.
  
  
  
 2) STAIR PRESSURIZATION RATIONAL ANALYSIS REPORT -
  
 ON PAGE 13 OF THE STAIR PRESSURIZATION RATIONAL
 ANALYSIS REPORT DOCUMENT SECTION 11. CONCLUSION THERE
 IS AN INDICATION OF A DETAILED SEQUENCE OF OPERATION,
 WHICH DOES NOT APPEAR TO BE SUBMITTED.
  
 PLEASE AND PROVIDE AND CONTINUE TO WORK WITH THE OFFICE
 OF THE FIRE MARSHAL AND THE BUILDING DEPARTMENT'S
 MECHANICAL PLAN REVIEWERS AND INSPECTORS FOR APPROVAL.
  
  
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2019-03-27 Cont ID  
Sent By pleduc Date 2019-03-27 Time   Rev Time 0.00
Received By pleduc Date 2019-03-08 Time 14:17 Sent To  
Notes
2019-03-13 13:43:42THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 1) SHEET ALS 1.00 - THERE ARE INDICATIONS REGARDING THE
 CONTENTS OF THE COMMAND ROOM.
  
 PER NFPA 1 AND 101 THERE ARE ADDITIONAL REQUIRMENTS NOT
 LISTED. FOR CLARIFICATION PURPOSES THE EXACT CODE
 LANGUAGE IS PROVIDED:
  
 THE FIRE COMMAND CENTER SHALL COMPLY WITH NFPA 1,
 CHAPTER 11, BUILDING SERVICES; 11.9 AND SHALL CONTAIN
 THE FOLLOWING FEATURES:
  
 1. SHALL BE A MINIMUM OF 200 FT SQUARED WITH A MINIMUM
 DIMENSION OF 10 FT.
 2. THE FIRE DEPARTMENT COMMUNICATIONS SYSTEM.
 3. A TELEPHONE FOR FIRE DEPARTMENT USE WITH CONTROLLED
 ACCESS TO THE PUBLIC TELEPHONE SYSTEM
 4. SCHEMATIC BUILDING PLANS INDICATING THE TYPICAL
 FLOOR PLAN AND DETAILING THE BUILDING CORE, MEANS OF
 EGRESS, FIRE PROTECTION SYSTEMS, FIRE-FIGHTING
 EQUIPMENT AND FIRE DEPARTMENT ACCESS AND THE LOCATION
 OF FIRE WALLS, FIRE BARRIERS, FIRE PARTITIONS, SMOKE
 BARRIERS AND SMOKE PARTITIONS
 5. A WORK TABLE.
 6. IF APPLICABLE, A HAZARDOUS MATERIAL MANAGEMENT PLAN
 FOR THE BUILDING.
 7. THE EMERGENCY VOICE/ALARM COMMUNICATION SYSTEM
 CONTROL UNIT.
 8. ANNUNCIATOR UNIT VISUALLY INDICATING THE LOCATION OF
 THE ELEVATORS AND WHETHER THEY ARE OPERATIONAL
 9. STATUS INDICATORS AND CONTROLS FOR AIR DISTRIBUTION
 SYSTEMS.
 10. CONTROLS FOR UNLOCKING STAIRWAY DOORS
 SIMULTANEOUSLY
 11. SPRINKLER VALVE AND WATER FLOW DETECTOR DISPLAY
 PANELS
 12. EMERGENCY AND STANDBY POWER STATUS INDICATORS
 13. FIRE PUMP STATUS INDICATORS
 14. GENERATOR SUPERVISION DEVICES AND MANUAL START AND
 TRANSFER FEATURES.
 15. PUBLIC ADDRESS SYSTEM, WHERE SPECIFICALLY REQUIRED
 BY OTHER SECTIONS OF THIS CODE
 16. CONTROLS REQUIRED FOR SMOKE CONTROL
 17. ELEVATOR FIRE RECALL SWITCH IN ACCORDANCE WITH ASME
 A17.1.
 18. ELEVATOR EMERGENCY OR STANDBY POWER SELECTOR
 SWITCH(ES), WHERE EMERGENCY OR STANDBY POWER IS
 PROVIDED
  
 NFPA 101, CHAPTER 11, SPECIAL STRUCTURES AND HIGH RISE
 BUILDINGS
  
 11.8.6* EMERGENCY COMMAND CENTER.
 11.8.6.1 AN EMERGENCY COMMAND CENTER SHALL BE PROVIDED
 IN A LOCATION APPROVED BY THE FIRE DEPARTMENT.
 11.8.6.2 THE EMERGENCY COMMAND CENTER SHALL CONTAIN THE
 FOLLOWING:
 (1) VOICE FIRE ALARM SYSTEM PANELS AND CONTROLS
 (2) FIRE DEPARTMENT TWO-WAY TELEPHONE COMMUNICATION
 SERVICE PANELS AND CONTROLS WHERE REQUIRED BY ANOTHER
 SECTION OF THIS CODE
 (3) FIRE DETECTION AND FIRE ALARM SYSTEM ANNUNCIATION
 PANELS
 (4) ELEVATOR FLOOR LOCATION AND OPERATION ANNUNCIATORS
 (5) ELEVATOR FIRE RECALL SWITCH IN ACCORDANCE WITH ASME
 A17.1/CSA B44, SAFETY CODE FOR ELEVATORS AND ESCALATORS
 (6) ELEVATOR EMERGENCY POWER SELECTOR SWITCH(ES) WHERE
 PROVIDED IN ACCORDANCE WITH ASME A17.1/CSA B44
 (7) SPRINKLER VALVE AND WATERFLOW ANNUNCIATORS
 (8) EMERGENCY GENERATOR STATUS INDICATORS
 (9) CONTROLS FOR ANY AUTOMATIC STAIRWAY DOOR UNLOCKING
 SYSTEM
 (10) FIRE PUMP STATUS INDICATORS
 (11) TELEPHONE FOR FIRE DEPARTMENT USE WITH CONTROLLED
 ACCESS TO THE
 PUBLIC TELEPHONE SYSTEM
 (12) STAIRWAY VIDEO MONITORING EQUIPMENT AS REQUIRED BY
 11.8.8
  
 PLEASE REVIEW AND CORRECT.
  
  
  
 2) SHEET ALS1.102 THRU 1.104 - THE HOTEL SIDE FIRE
 LOBBY DOOR,EAST SIDE, INDICATES A SWING AGAINST THE
 EXIT PATH OF TRAVEL.
  
 PER NFPA 101, CH 7, MEANS OF EGRESS
  
 7.2.1.4.2 DOOR LEAF SWING DIRECTION. DOOR LEAVES
 REQUIRED TO BE
 OF THE SIDE-HINGED OR PIVOTED-SWINGING TYPE SHALL SWING
 IN THE
 DIRECTION OF EGRESS TRAVEL UNDER ANY OF THE FOLLOWING
 CONDITIONS:
 (1) WHERE SERVING A ROOM OR AREA WITH AN OCCUPANT LOAD
 OF 50 OR
 MORE, EXCEPT UNDER ANY OF THE FOLLOWING CONDITIONS:
 (A) DOOR LEAVES IN HORIZONTAL EXITS SHALL NOT BE
 REQUIRED TO
 SWING IN THE DIRECTION OF EGRESS TRAVEL WHERE PERMITTED
 BY 7.2.4.3.8.1 OR 7.2.4.3.8.2.
 (B) DOOR LEAVES IN SMOKE BARRIERS SHALL NOT BE REQUIRED
 TO
 SWING IN THE DIRECTION OF EGRESS TRAVEL IN EXISTING
 HEALTH
 CARE OCCUPANCIES, AS PROVIDED IN CHAPTER 19.
 (2) WHERE THE DOOR ASSEMBLY IS USED IN AN EXIT
 ENCLOSURE, UNLESS
 THE DOOR OPENING SERVES AN INDIVIDUAL LIVING UNIT THAT
 OPENS
 DIRECTLY INTO AN EXIT ENCLOSURE
 (3) WHERE THE DOOR OPENING SERVES A HIGH HAZARD
 CONTENTS AREA
  
 PLEASE REVIEW AND CORRECT OR JUSTIFY WITH SPECIFIC CODE
 REFERENCES.
  
  
  
  
 3) SHEET A 1.102 & A 6.103 - THERE ARE NO CLEAR
 INDICATIONS OF THE TRASH CHUTE ROOM DOOR NUMBER OR TYPE
 ON THIS THESE SHEETS OR ANY OTHER SHEET.
  
 PLEASE REVIEW AND CORRECT OR CLARIFY
  
  
  
 3A) SHEET A 1.102 - THE DOOR TO THE TRASH CHUTE OPENS
 TOO FAR INTO THE EXIT CORRIDOR.
  
 PER NFPA 101, CH 7 MEANS OF EGRESS & CH 9
  
 7.2.1.4.3* DOOR LEAF ENCROACHMENT.
 7.2.1.4.3.1 DURING ITS SWING, ANY DOOR LEAF IN A MEANS
 OF EGRESS
 SHALL LEAVE NOT LESS THAN ONE-HALF OF THE REQUIRED
 WIDTH OF AN AISLE,
 A CORRIDOR, A PASSAGEWAY, OR A LANDING UNOBSTRUCTED,
 UNLESS BOTH
 OF THE FOLLOWING CONDITIONS ARE MET:
 (1) THE DOOR OPENING PROVIDES ACCESS TO A STAIR IN AN
 EXISTING
 BUILDING.
 (2) THE DOOR OPENING MEETS THE REQUIREMENT OF
 7.2.1.4.3.2.
  
  
 9.5 WASTE CHUTES, INCINERATORS, AND LAUNDRY CHUTES.
 9.5.1 ENCLOSURE.
 9.5.1.1 WASTE CHUTES AND LAUNDRY CHUTES SHALL BE
 SEPARATELY
 ENCLOSED BY WALLS OR PARTITIONS IN ACCORDANCE WITH THE
 PROVISIONS
 OF SECTION 8.3.
 9.5.1.2 CHUTE INTAKE OPENINGS SHALL BE PROTECTED IN
 ACCORDANCE
 WITH SECTION 8.3.
 9.5.1.3 THE DOORS OF CHUTES SPECIFIED IN 9.5.1.2 SHALL
 OPEN ONLY TO
 A ROOM THAT IS DESIGNED AND USED EXCLUSIVELY FOR
 ACCESSING THE
 CHUTE OPENING.
 9.5.1.4 CHUTE SERVICE OPENING ROOMS SHALL BE SEPARATED
 FROM OTHER
 SPACES IN ACCORDANCE WITH SECTION 8.7.
  
 PLEASE REVIEW AND CORRECT OR JUSTIFY WITH SPECIFIC CODE
 REFERENCES AND NARRATIVE.
  
  
  
 4) SHEET A1.105 - THERE ARE INDICATIONS OF LIFT IN SOME
 OF THE PARKING GARAGE.
  
 WHAT DOES REPRESENT AND HOW WILL IT EFFECT THE FIRE
 PROTECTION SYSTEMS?
  
 PLEASE REVIEW AND PROVIDE DETAILS WITH SPECIFIC CODE
 REFERENCES.
  
  
  
 5) SHEET A1.108 - THERE IS AN INDICATION OF AN EXIT
 SIGN(TENNIS COURT SIDE) AND EXIT DOOR FIRE RESISTANCE
 CALCULATION(45) LEADING TO THE CORRIDOR BY THE HOTEL
 POOL EQUIPMENT ROOM.
  
 THERE IS NO INDICATION OF A DOOR.
  
 SHEET E108B INDICATES A DOUBLE DOOR AT THE WALL WITH AN
 EXIT SIGN.
  
 PLEASE REVIEW AND CORRECT OR CLARIFY.
  
  
  
  
 6) SHEET A1.109, ALS 1.110 & A1.241- THERE IS AN
 INDICATION OF THE FIRE LOBBY DOOR SWINGING IN THE PATH
 OF TRAVEL ON A1.109 AND AGAINST THE PATH OF TRAVEL ON
 THE OTHER TWO SHEETS.
  
 IT IS REQUIRED TO SWING IN THE PATH OF TRAVEL PER NPA
 101, CH 7 AS NOTED ABOVE.
  
 PLEASE REVIEW,CORRECT AND /OR CLARIFY.
  
  
  
  
 7) ALL APPLICABLE A & ALS SHEETS - THERE IS AN
 INCORRECT TOTAL CALCULATION INDICATED FOR A 44" DOOR
 OPENING. THE CODE REQUIRES THE LOAD CALCULATIONS TO BE
 ROUNDED UP; 146.7 SHOULD BE ROUNDED UP TO 147 ON ALL
 APPLICABLE SHEETS.
  
 7.3.3* EGRESS CAPACITY.
 7.3.3.1 EGRESS CAPACITY FOR APPROVED COMPONENTS OF
 MEANS OF
 EGRESS SHALL BE BASED ON THE CAPACITY FACTORS SHOWN IN
 TABLE
 7.3.3.1, UNLESS OTHERWISE PROVIDED IN 7.3.3.2
  
 PLEASE REVIEW AND CORRECT
  
  
  
 8) ALL APPLICABLE A & ALS SHEETS - THERE IS AN
 INCORRECT TOTAL CALCULATION INDICATED FOR A 60" STAIR
 WIDTH; 218(.2 WAS USED . THE CODE REQUIRES THE LOAD
 CALCULATIONS TO BE .03; 200 SHOULD ON ALL APPLICABLE
 SHEETS.
  
 7.3.3* EGRESS CAPACITY.
 7.3.3.1 EGRESS CAPACITY FOR APPROVED COMPONENTS OF
 MEANS OF
 EGRESS SHALL BE BASED ON THE CAPACITY FACTORS SHOWN IN
 TABLE
 7.3.3.1, UNLESS OTHERWISE PROVIDED IN 7.3.3.2
  
 PLEASE REVIEW AND CORRECT.
  
  
  
 9) SHEET A1.109 , A1.110 & ALS1.110 - THERE ARE
 INDICATIONS OF CONFLICTS WITH THE CORE DOOR FIRE
 RATINGS, DOOR LOCATION AND DOOR SWING.
  
 THE LS SHEET SHOWS TWO DOORS, NR, IN THE H.K. ROOM WITH
 NO RATING ON THE BACK WALL.
  
 THE MECH ROOM DOOR IS 20 MIN IN A 2 HOUR WALL.
  
 THE LS SHEET DOOR SWING ON THE FIRE LOBBY SHOWS IN THE
 PATH OF TRAVEL WHILE OTHER SHEETS SHOW OPPISITE.
  
 PLEASE REVIEW AND CORRECT OR CLARIFY.
  
  
  
 10) SHEET ALS1.111 - THERE IS AN INDICATION OF NR
 DOUBLE DOORS AT THE MECH ROOM. THESE DOORS ARE REQUIRED
 TO BE RATED.
  
 PER NFPA 101, CH 38
  
 38.3.2 PROTECTION FROM HAZARDS.
 38.3.2.1* GENERAL. HAZARDOUS AREAS INCLUDING, BUT NOT
 LIMITED TO,
 AREAS USED FOR GENERAL STORAGE, BOILER OR FURNACE
 ROOMS, AND
 MAINTENANCE SHOPS THAT INCLUDE WOODWORKING AND PAINTING
 AREAS
 SHALL BE PROTECTED IN ACCORDANCE WITH SECTION 8.7.
 38.3.2.2* HIGH HAZARD CONTENTS AREAS. HIGH HAZARD
 CONTENTS
 AREAS, AS CLASSIFIED IN SECTION 6.2, SHALL MEET ALL OF
 THE FOLLOWING
 CRITERIA:
 (1) THE AREA SHALL BE SEPARATED FROM OTHER PARTS OF THE
 BUILDING BY
 FIRE BARRIERS HAVING A MINIMUM 1-HOUR FIRE RESISTANCE
 RATING,
 WITH ALL OPENINGS THEREIN PROTECTED BY SELF-CLOSING
 FIRE DOOR
 ASSEMBLIES HAVING A MINIMUM 3?4-HOUR FIRE PROTECTION
 RATING.
 (2) THE AREA SHALL BE PROTECTED BY AN AUTOMATIC
 EXTINGUISHING
 SYSTEM IN ACCORDANCE WITH 9.7.1.1(1) OR 9.7.1.2.
  
  
 PLEASE REVIEW AND CORRECT OR JUSTIFY WITH SPECIFIC CODE
 REFERENCES.
  
  
  
  
 11) SHEET ALS1.114 - THERE ARE INDICATIONS AT THE FIRE
 LOBBY & STAIR #1 EXIT DOORS OBSTRUCTING EACH OTHER.
  
 PER NFPA 101 CH 7
 7.2.1.4.3* DOOR LEAF ENCROACHMENT.
 7.2.1.4.3.1 DURING ITS SWING, ANY DOOR LEAF IN A MEANS
 OF EGRESS
 SHALL LEAVE NOT LESS THAN ONE-HALF OF THE REQUIRED
 WIDTH OF AN AISLE,
 A CORRIDOR, A PASSAGEWAY, OR A LANDING UNOBSTRUCTED,
 UNLESS BOTH
 OF THE FOLLOWING CONDITIONS ARE MET:
 (1) THE DOOR OPENING PROVIDES ACCESS TO A STAIR IN AN
 EXISTING
 BUILDING.
 (2) THE DOOR OPENING MEETS THE REQUIREMENT OF
 7.2.1.4.3.2.
  
 PLEASE REVIEW AND CORRECT OR JUSTIFY WITH SPECIFIC CODE
 REFERENCES AND NARRATIVE.
  
  
  
 12) SHEET ALS1.114 - THERE ARE INDICATION THAT EACH
 STAIR IS INDICATED AS STAIR # 1. SHEET ALS1.101
 INDICATES THEM DIFFERENTLY.
  
 PLEASE REVIEW AND CORRECT OR JUSTIFY.
  
  
  
  
 13) ENGINEERING DOCUMENTATION - THERE IS NO SPECIFIC
 ENGINEEERING DOCUMENTATION REGARDING THE SMOKE CONTROL
 FOR THIS PROJECT.
  
 PER NFPA 101, CH 9
  
 9.3 SMOKE CONTROL.
 9.3.1 INSTALLATION. WHERE REQUIRED BY ANOTHER SECTION
 OF THIS
 CODE, SMOKE CONTROL SYSTEMS SHALL BE DESIGNED,
 INSTALLED,
 INSPECTED, TESTED, AND MAINTAINED IN ACCORDANCE WITH
 NFPA 92,
 STANDARD FOR SMOKE CONTROL SYSTEMS; NFPA 204, STANDARD
 FOR
 SMOKE AND HEAT VENTING; OR NATIONALLY RECOGNIZED
 STANDARDS,
 ENGINEERING GUIDES, OR RECOMMENDED PRACTICES, AS
 APPROVED BY
 THE AUTHORITY HAVING JURISDICTION.
 9.3.2 SYSTEM DESIGN. THE ENGINEER OF RECORD SHALL
 CLEARLY IDENTIFY
 THE INTENT OF THE SYSTEM, THE DESIGN METHOD USED, THE
 APPROPRIATENESS OF THAT METHOD, AND THE REQUIRED MEANS
 OF
 INSPECTING, TESTING, AND MAINTAINING THE SYSTEM.
  
 PLEASE REVIEW AND PROVIDE THE SPECIFIC DOCUMENTATION.
  
  
  
 14) DOOR SCHEDULES - IT IS DIFFICULT TO CONFIRM WITH
 ANY CERTAINTY THE CORRECT RATING AND HARDWARES OF THE
 DOORS DUE TO NO ONE SHEET OF EACH FLOOR HAS ALL THE
 DOORS NUMBERS MARKED,
  
 PLEASE MARK THE DOORS ON THE ALS SHEETS TO BETTER MARK
 EACH DOOR NUMBER WITH THE RATING THAT CAN BE CLEARLY
 AND ACCURATELY CHECKED AGAINST THE DOOR SCHEDULE.
  
 PLEASE REVIEW AND CORRECT OR HELP TO CLARIFY
 VERIFICATIONS.
  
  
  
  
 15) SHEET ALS1.10 & ALS1.108 - THERE IS AN INDICATION
 OF A LARGE STAIRCASE CONNECTING THESE TO FLOOR LEVELS.
 THERE ARE NO INDICATIONS OF HOW THIS CONVENIENCE
 OPENING WILL BE PROTECTED.
  
 PER NFPA 101, CH 8
  
 8.6.9 CONVENIENCE OPENINGS.
 8.6.9.1 WHERE PERMITTED BY CHAPTERS 11 THROUGH 43,
 UNENCLOSED
 VERTICAL OPENINGS NOT CONCEALED WITHIN THE BUILDING
 CONSTRUCTION SHALL
 BE PERMITTED AS FOLLOWS:
 (1) SUCH OPENINGS SHALL CONNECT NOT MORE THAN TWO
 ADJACENT STORIES
 (ONE FLOOR PIERCED ONLY).
 (2) SUCH OPENINGS SHALL BE SEPARATED FROM UNPROTECTED
 VERTICAL
 OPENINGS SERVING OTHER FLOORS BY A BARRIER COMPLYING
 WITH 8.6.5.
 (3) SUCH OPENINGS SHALL BE SEPARATED FROM CORRIDORS.
 (4) *IN OTHER THAN APPROVED, EXISTING CONVENIENCE
 OPENINGS, SUCH
 OPENINGS SHALL BE SEPARATED FROM OTHER FIRE OR SMOKE
 COMPARTMENTS ON THE SAME FLOOR.
 (5) IN NEW CONSTRUCTION, THE CONVENIENCE OPENING SHALL
 BE SEPARATED
 FROM THE CORRIDOR REFERENCED IN 8.6.9.1(3) BY A SMOKE
 PARTITION,
 UNLESS CHAPTERS 11 THROUGH 43 REQUIRE THE CORRIDOR TO
 HAVE A FIRE
 RESISTANCE RATING.
 (6) *SUCH OPENINGS SHALL NOT SERVE AS A REQUIRED MEANS
 OF EGRESS.
  
 8.6.9.2 WHERE PERMITTED BY CHAPTERS 11 THROUGH 43,
 UNENCLOSED
 VERTICAL OPENINGS CREATED BY CONVENIENCE STAIRWAYS
 SHALL COMPLY WITH
 ALL OF THE FOLLOWING:
 (1) THE CONVENIENCE STAIR OPENINGS SHALL NOT SERVE AS
 REQUIRED
 MEANS OF EGRESS.
 (2) THE BUILDING SHALL BE PROTECTED THROUGHOUT BY AN
 APPROVED,
 SUPERVISED AUTOMATIC SPRINKLER SYSTEM IN ACCORDANCE
 WITH
 SECTION 9.7.
 (3) *THE CONVENIENCE STAIR OPENINGS SHALL BE PROTECTED
 IN
 ACCORDANCE WITH THE METHOD DETAILED FOR THE PROTECTION
 OF
 VERTICAL OPENINGS IN NFPA 13, STANDARD FOR THE
 INSTALLATION OF
 SPRINKLER SYSTEMS.
 (4) IN NEW CONSTRUCTION, THE AREA OF THE FLOOR OPENING
 SHALL NOT
 EXCEED TWICE THE HORIZONTAL PROJECTED AREA OF THE
 STAIRWAY.
 (5) FOR NEW CONSTRUCTION, SUCH OPENINGS SHALL NOT
 CONNECT MORE THAN
 FOUR CONTIGUOUS STORIES, UNLESS OTHERWISE PERMITTED BY
 CHAPTERS
 11 THROUGH 43.
  
 PLEASE REVIEW, CORRECT AND PROVIDE DETAILS.
  
  
  
  
 16) SHEET ALS1.108 - THERE IS AN INDICATION OF AN EXIT
 SIGN AT THE TOP OF THE STAIRWAY NOTED ABOVE; HOWEVER,
 PER 8.6.9.2 (1) THE STAIR SHALL NOT SERVE AS A REQUIRED
 MEANS OF EGRESS.
  
 THIS STAIR APPEARS TO SERVE AS A REQUIRED MEANS OF
 EGRESS.
  
 PLEASE REVIEW AND CORRECT OR JUSTIFY WITH SPECIFIC CODE
 REFERENCES AND NARRATIVE.
  
  
  
  
 17) SHEET FP 301 - THERE ARE INDICATIONS OF TWO PUMPS.
 THE PUMP SCHEDULES INDICATE 750 GPM WITH MAX CHURN
 PRESSURE OF 235.
  
 THOSE THESE ARE NOT SHOP DRAWINGS, THESE FIGURES DO NOT
 APPEAR TO BE ABLE TO SUPPORT FIRE DEMANDS ON UPPER
 FLOORS, NOR SEPARATE FIRE LOCATED IN DIFFERENT TOWERS
 AT THE SAME TIME.
  
 PLEASE REIVEW AND CORRECT OR JUSTIFY WITH THE EOR
 NARRATIVE.
  
  
  
 18) SHEET A1.105 & E - THERE IS AN INDICATION OF A
 GENERATOR ROOM; HOWEVER, THERE ARE NO INDICATIONS OF
 WHAT TYPE, CLASS, ETC.
  
 PER NFPA 110
  
 CHAPTER 4 CLASSIFICATION OF EMERGENCY POWER SUPPLY
 SYSTEMS (EPSSS)
 4.1* GENERAL. THE EPSS SHALL PROVIDE A SOURCE OF
 ELECTRICAL
 POWER OF REQUIRED CAPACITY, RELIABILITY, AND QUALITY TO
 LOADS FOR
 A LENGTH OF TIME AS SPECIFIED IN TABLE 4.1(A) AND
 WITHIN A SPECIFIED
 TIME FOLLOWING LOSS OR FAILURE OF THE NORMAL POWER
 SUPPLY
 AS SPECIFIED IN TABLE 4.1(B).
  
 4.2* CLASS. THE CLASS DEFINES THE MINIMUM TIME, IN
 HOURS, FOR
 WHICH THE EPSS IS DESIGNED TO OPERATE AT ITS RATED LOAD
 WITHOUT
 BEING REFUELED OR RECHARGED. [SEE TABLE 4.1(A).]
 4.3 TYPE. THE TYPE DEFINES THE MAXIMUM TIME, IN
 SECONDS,
 THAT THE EPSS WILL PERMIT THE LOAD TERMINALS OF THE
 TRANSFER
 SWITCH TO BE WITHOUT ACCEPTABLE ELECTRICAL POWER. TABLE
 4.1(B)
 PROVIDES THE TYPES DEFINED BY THIS STANDARD.
 4.4* LEVEL. THIS STANDARD RECOGNIZES TWO LEVELS OF
 EQUIPMENT
 INSTALLATION, PERFORMANCE, AND MAINTENANCE.
 4.4.1* LEVEL 1 SYSTEMS SHALL BE INSTALLED WHERE FAILURE
 OF THE
 EQUIPMENT TO PERFORM COULD RESULT IN LOSS OF HUMAN LIFE
 OR
 SERIOUS INJURIES.
 4.4.2* LEVEL 2 SYSTEMS SHALL BE INSTALLED WHERE FAILURE
 OF THE
 EPSS TO PERFORM IS LESS CRITICAL TO HUMAN LIFE AND
 SAFETY.
 4.4.3 ALL EQUIPMENT SHALL BE PERMANENTLY INSTALLED.
 4.4.4* LEVEL 1 AND LEVEL 2 SYSTEMS SHALL ENSURE THAT
 ALL LOADS
 SERVED BY THE EPSS ARE SUPPLIED WITH ALTERNATE POWER
 THAT
 MEETS ALL THE FOLLOWING CRITERIA:
 (1) OF A QUALITY WITHIN THE OPERATING LIMITS OF THE
 LOAD
 (2) FOR A DURATION SPECIFIED FOR THE CLASS AS DEFINED
 IN TABLE
 4.1(A)
 (3) WITHIN THE TIME SPECIFIED FOR THE TYPE AS DEFINED
 IN TABLE
 4.1(B)
  
 THE GENERATOR SHALL BE INSTALLED UNDER SEPARATE SHOP
 DRAWINGS.
  
 PLEASE REVIEW AND PROVIDE DETAILS AND A NOTE OF
 ACKNOWLEDGEMENT.
  
  
  
 19) SHEET A 1.108 & ALS 1.108 - STAIRWAYS # 5 & 9
 INDICATE EXIT SIGNS AND OPENINGS; HOWEVER, THERE ARE NO
 DOORS INDICATED ON THESE SHEETS OR ANY OTHER SHEET FOR
 THESE OPENINGS.
  
 PER NFPA 101 CH 7, EXIT STAIRWELLS ARE TO BE PROTECTED.
  
 7.2.2.5 ENCLOSURE AND PROTECTION OF STAIRS.
 7.2.2.5.1 ENCLOSURES.
 7.2.2.5.1.1 ALL INSIDE STAIRS SERVING AS AN EXIT OR
 EXIT COMPONENT
 SHALL BE ENCLOSED IN ACCORDANCE WITH 7.1.3.2.
  
 7.1.3.2 EXITS.
 7.1.3.2.1 WHERE THIS CODE REQUIRES AN EXIT TO BE
 SEPARATED FROM OTHER
 PARTS OF THE BUILDING, THE SEPARATING CONSTRUCTION
 SHALL MEET THE
 REQUIREMENTS OF SECTION 8.2 AND THE FOLLOWING:
 (1) *THE SEPARATION SHALL HAVE A MINIMUM 1-HOUR FIRE
 RESISTANCE
 RATING WHERE THE EXIT CONNECTS THREE OR FEWER STORIES.
  
 (8) OPENINGS IN THE SEPARATION SHALL BE PROTECTED BY
 FIRE DOOR
 ASSEMBLIES EQUIPPED WITH DOOR CLOSER COMPLYING WITH
 7.2.1.8.
  
  
 PLEASE REVIEW AND CORRECT OR JUSTIFY.
  
  
  
  
 20) OUTDOOR TERRACE/POOL/ROOFTOP AREAS - THERE DOES NOT
 APPEAR TO BE ANY BBQ'S PROPOSED FOR THIS PROJECT;
 HOWEVER, SHOULD THEY BE A FUTURE INSTALL THEY SHALL
 COMPLY WITH THE ALL APPLICABLE CODES INCLUDING NFPA 1
  
 10.10.6 COOKING EQUIPMENT.
 10.10.6.1 FOR OTHER THAN ONE- AND TWO-FAMILY DWELLINGS,
 NO
 HIBACHI, GRILL, OR OTHER SIMILAR DEVICES USED FOR
 COOKING, HEATING,
 OR ANY OTHER PURPOSE SHALL BE USED OR KINDLED ON ANY
 BALCONY,
 UNDER ANY OVERHANGING PORTION, OR WITHIN 10 FT (3 M) OF
 ANY
 STRUCTURE.
 10.10.6.1.1 LISTED ELECTRIC PORTABLE, TABLETOP GRILLS,
 NOT TO EXCEED
 200 SQUARE INCHES OF COOKING SURFACE, OR OTHER SIMILAR
 APPARATUS
 SHALL BE PERMITTED.
 10.10.6.2 FOR OTHER THAN ONE- AND TWO-FAMILY DWELLINGS,
 NO
 HIBACHI, GRILL, OR OTHER SIMILAR DEVICES USED FOR
 COOKING SHALL BE
 STORED ON A BALCONY.
 10.10.6.3* LISTED EQUIPMENT PERMANENTLY INSTALLED IN
 ACCORDANCE
 WITH ITS LISTING, APPLICABLE CODES, AND MANUFACTURER?S
 INSTRUCTIONS
 SHALL BE PERMITTED.
 10.10.7 INSTALLATION OF PATIO HEATERS. THE INSTALLATION
 OF PATIO
 HEATERS SHALL COMPLY WITH 69.3.11.
  
 SHOULD THERE BE REVISIONS, BBQ'S SHALL BE CLEARLY
 IDENTIFIED, LOCATED PER THE CODE AND ALL MANUFACTURES
 SPECIFICATIONS ATTACHED, AND COMPLY WITH THOSE
 SPECIFICATIONS, PRIOR TO ANY APPROVAL.
  
 PLEASE ENSURE COMPLIANCE.
  
  
  
  
 21) RESIDENTIAL TOWER SHEETS - AT THE FIRE SERVICE
 ELEVATOR EXIT DOOR TO THE STARIWELL THE DOOR OPENS INTO
 THE REQUIRED EGRESS OF THE CORRIDOR DOOR AND VISA A
 VERSA.
  
 PER NFPA 101, CH 7
  
 7.2.1.4.3* DOOR LEAF ENCROACHMENT.
 7.2.1.4.3.1 DURING ITS SWING, ANY DOOR LEAF IN A MEANS
 OF EGRESS
 SHALL LEAVE NOT LESS THAN ONE-HALF OF THE REQUIRED
 WIDTH OF AN AISLE,
 A CORRIDOR, A PASSAGEWAY, OR A LANDING UNOBSTRUCTED,
 UNLESS BOTH
 OF THE FOLLOWING CONDITIONS ARE MET:
 (1) THE DOOR OPENING PROVIDES ACCESS TO A STAIR IN AN
 EXISTING
 BUILDING.
 (2) THE DOOR OPENING MEETS THE REQUIREMENT OF
 7.2.1.4.3.2.
 7.2.1.4.3.2 WHEN FULLY OPEN, ANY DOOR LEAF IN A MEANS
 OF EGRESS
 SHALL NOT PROJECT MORE THAN 7 IN. (180 MM) INTO THE
 REQUIRED WIDTH
 OF AN AISLE, A CORRIDOR, A PASSAGEWAY, OR A LANDING,
 UNLESS THE DOOR
 LEAF IS EQUIPPED WITH AN APPROVED SELF-CLOSING DEVICE
 AND IS NOT
 REQUIRED BY THE PROVISIONS OF 7.2.1.4.2 TO SWING IN THE
 DIRECTION OF
 EGRESS TRAVEL.
  
 PLEASE REVIEW AND CORRECT OT JUSTIFY/CLARIFY WITH
 SPECIFIC CODE REFERENCES.
  
  
  
  
  
 23) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
  
  
 24) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2018-11-27 Cont ID  
Sent By pleduc Date 2018-11-27 Time   Rev Time 0.00
Received By pleduc Date 2018-11-05 Time 09:54 Sent To  
Notes
2018-11-27 16:08:49FIRE REVIEWED THIS SUBMITTAL WITH THE UNDERSTANDING
 THAT IT WOULD BE CURSORY IN SUPPORT OF A FOUNDATION
 ONLY SUBMITTAL.
  
 FIRE APPROVES THIS SUBMITTAL FOR FOUNDATION ONLY AND
 THAT FUTURE COMPLETE PLANS WILL BE SUBMITTED FOR THE
 REMAINDER OF THE PROPOSED PROJECT.
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop G GAS REVIEW
Rev No 5 Status P Date 2021-08-16 Cont ID  
Sent By lcrespo Date 2021-08-16 Time 12:00 Rev Time 0.00
Received By lcrespo Date 2021-08-16 Time 12:00 Sent To  
Notes
2021-08-16 12:31:4608/13/21 REVIEWED FOR CODE COMPLIANCE (GAS)
  
 BY REVIEWING THE PLANS / SPECIFICATIONS FOR CODE
 COMPLIANCE DOES NOT RELIEVE THE OWNER, DESIGN
 PROFESSIONAL, CONTRACTORS, OR THEIR REPRESENTATIVES
 FROM THE RESPONSIBILITY TO COMPLY WITH ALL LOCAL,
 STATE, AND NATIONAL CODES AND STANDARDS IN EFFECT AT
 THE TIME OF PERMIT ISSUANCE. OUR REVIEW IS NOT A CHECK
 OF EVERY ITEM AND DOES NOT PREVENT THIS DEPARTMENT FROM
 REQUIRING CORRECTIONS DURING CONSTRUCTION. ANY CHANGES
 / ALTERATIONS TO APPROVED PLANS SHALL BE APPROVED TO
 AVOID VOIDING OF THE PERMIT.
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER / INSPECTOR
 EMAIL: [email protected] OFFICE: 561 805-6720
  

Review Stop G GAS REVIEW
Rev No 4 Status F Date 2021-06-21 Cont ID  
Sent By lcrespo Date 2021-06-21 Time 15:46 Rev Time 0.00
Received By lcrespo Date 2021-06-14 Time 14:32 Sent To  
Notes
2021-06-21 15:48:1006/21/21 4TH GAS REVIEW**DENIED** WITH COMMENTS
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME, AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
  
 1. DONE.
  
 2. DONE.
  
 3. DONE.
  
 4. DONE.
  
 5. DONE.
  
 6. DONE.
  
 7. DONE.
  
 8. THERE IS CLOUD AND NO INFORMATION, SO PLEASE
 CORRECT. SHEET P.700, KEYNOTE #3 - IDENTIFY THIS FUTURE
 LINE/SYSTEM ON THE GAS RISER PER THE WPB AMENDMENTS TO
 FBC SEC. 107.2.1.
  
 9. DONE.
  
 10. DONE.
  
 11. THIS COMMENT HAS NOT BEEN ADDRESSED, AND BOTH
 SHEETS DO NOT MATCH; SHEET P.700 - KEYNOTE #14 SHOWS
 THE GAS LINE WITH 579 CFH AND SHT. P.700A, DETAIL #2
 SHOWS 500 CFH. CLARIFY.
  
 12. DONE.
  
 13. ON SHEET 700A DETAIL #6, THE LONGEST RUN IS NOT
 CLEAR THE LONGEST RUN. IS TO THE PRV REGULATOR OR THE
 BOILER. THIS NEEDS TO BE KNOWN AS THE LONGEST RUN
 DETERMINE THE SIZE CALCULATION, SO PLEASE CLARIFY PER
 THE WPB AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION
 ON CONSTRUCTION DOCUMENTS.
  
 14. ON SHEET 700A DETAIL #5, SIZE THE SHORT SECTION OF
 THE GAS MAIN LINE BETWEEN THE 4 INCH LINE AND THE 2 ?
 INCH LINE NEEDS A SIZE FIELD CLARIFICATION, PLEASE
 PROVIDE PER THE WPB AMENDMENTS TO THE FBC SEC. 107.2.1
 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 15. DONE.
  
 16. DONE.
  
 17. DONE.
  
 18. DONE.
  
 19. DONE.
  
 WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY NECESSARY PAGES.
 A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND, WILL HELP EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 HTTPS://CODES.ICCSAFE.ORG/CODES/FLORIDA
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER / INSPECTOR
 EMAIL: [email protected] OFFICE: 561 805-6720
  
  

Review Stop G GAS REVIEW
Rev No 3 Status F Date 2021-02-19 Cont ID  
Sent By tklarge Date 2021-02-19 Time 09:48 Rev Time 0.00
Received By tklarge Date 2021-02-18 Time 11:51 Sent To  
Notes
2021-02-18 12:49:051) SHT. P.509 - DETAIL #2 SHOWS A 1 INCH GAS LINE DOWN
 TO AN AHU. WHERE IS THIS AHU LOCATED? THE GAS LINE
 SHOWS A SHUTOFF VALVE ON THE GAS LINE. THE SHUTOFF
 VALVE SHALL BE LOCATED IN THE SAME ROOM AS THE
 APPLIANCE AND WITHIN 6 FEET OF THE APPLIANCE PER
 FBC-FUEL GAS SEC.409.5.1. CLARIFY.
 2) SHT. P.700 - KEYNOTE #7 - PROVIDE A REFERENCE RISER
 TAG FOR THIS LINE OR PROVIDE A SHEET NUMBER AS TO WHERE
 THE CONTINUATION OF THIS LINE CAN BE FOUND AND PROVIDE
 A COMPLETE GAS RISER FOR THIS AREA SHOWING ALL PIPE
 SIZES, BTU LOADS OF APPLIANCES/EQUIPMENT, GAS PRESURE
 OF SYSTEM, VALVES, LONGEST RUN FROM POINT OF DELIVRY,
 ETC. WPB AMEND. TO FBC SEC. 107.2.1,107.3.5.1.5.
 3) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE GAS
 APPLIANCES/EQUIPMENT IN THE RESTAURANT. WPB AMEND. TO
 FBC SEC. 107.2.1.
 4) SHT. P.700 - KEYNOTE #11 - SUBMIT A COMPLETE GAS
 RISER FOR THIS AREA EVEN THOUGH IT IS FOR FUTURE OR THE
 LOAD IS ESTIMATED. WPB AMEND. TO FBC SEC. 107.2.1,
 107.3.5.1.5.
 5) WHERE CONNECTED TO RIGID PIPING, A UNION SHALL BE
 INSTALLED WITHIN 1 FOOT OF EITHER SIDE OF THE
 REGULATORS PER FBC-FUEL GAS SEC.410.2 (7).
 6) THE INSTALLATION OF THE MP REGULATORS SHALL ALSO
 COMPLY WITH FBC-FUEL GAS SEC.410.2 ITEMS #1-#6.
 7) SHT. P.700 - NATURAL GAS SYSTEMS TABLE - SYSTEM #1
 SHOWS THE MAXIMUM BTU LOAD AS 4854 CFH BUT THE GAS
 RISER ON THE SAME PAGE SHOWS THE BTU LOAD AS 3229 CFH.
 CLARIFY.
 8) SHT. P.700 - KEYNOTE #3 - IDENTIFY THIS FUTURE
 LINE/SYSTEM ON THE GAS RISER.WPB AMEND. TO FBC SEC.
 107.2.1.
 9) SHT. P.700 - NATURAL GAS SYSTEMS TABLE - GAS SYSTEM
 #5 - THE TABLE NOTES THE BTU LOAD AS 3,650 CFH BUT THE
 RISER SHOWS 3,500 CFH. CLARIFY..
 10) SHT. P.700 - KEYNOTE #11 - PROVIDE A REFERENCE
 RISER TAG FOR THIS LINE OR PROVIDE A SHEET NUMBER AS TO
 WHERE THE CONTINUATION OF THIS LINE CAN BE FOUND AND
 PROVIDE A COMPLETE GAS RISER FOR THIS AREA SHOWING ALL
 PIPE SIZES, BTU LOADS OF APPLIANCES/EQUIPMENT, GAS
 PRESURE OF SYSTEM, VALVES, LONGEST RUN FROM POINT OF
 DELIVERY, ETC. WPB AMEND. TO FBC SEC. 107.2.1,
 107.3.5.1.5.
 11) SHT. P.700 - KEYNOTE #14 SHOWS THE GAS LINE WITH
 579 CFH AND SHT. P.700A, DETAIL #2 SHOWS 500 CFH.
 CLARIFY.
 12) SHT. P.700 - THERE ARE RISER TAGS AT HE GAS RISER
 ON LEVELS 6,7, & 8 WITH NO DRAWING LOCATIONS/SHEET
 NUMBERS ON THE RISER TAGS. CLARIFY.
 13) SHT. P.700A - DETAIL #6 SHOWS THE THE LONGEST RUN
 AS 550 FEET.THIS LINE IS UNDERSIZED AS DESIGNED. A
 MAXIMUM OF 556,000 BTU'S CAN BE ACCOMMODATED ON A 2 1/2
 INCH LINE AT A DISTANCE OF 550 FEET IN ACCORDANCE WITH
 FBC-FUEL GAS TABLE 402.4(1). CLARIFY.
 14) SHT. P.700A - DETAIL #5 - SIZE THE SHORT SECTION OF
 THE GAS MAIN LINE BETWEEN THE 4 INCH LINE AND THE 2 1/2
 INCH LINE. SIZING SHALL COMPLY WITH FBC-FUEL GAS TABLE
 402.4 (1). 2ND REQUEST. CLARIFY.
 15) SHT. P.700A - DETAILS # 1- #6 - THERE IS A NOTE ON
 ALL THE DETAILS THAT REFER TO DETAIL #10 ON SHT.P.802
 BUT THERE IS NO SUCH DETAIL ON THIS SHEET. 2ND
 REQUEST.CLARIFY. THE RESPONSE NARRATIVE STATES THE
 DETAIL IS ON SHT. P.804, DETAIL #10, BUT THAT DETAIL IS
 FOR A THERMOSTATIC MIXING VALVE AND IS NOT APPLICABLE.
 16) SHT. P.700A - DETAILS #1 & #3 - NOTE #4 STATES TO
 REFER TO SHT. P.802, DETAIL #6 FOR THE WATER HEATER
 DETAIL. DETAIL #6 ON SHT.P.802 IS FOR A CONDENSATE
 DRAIN. 2ND REQUEST. CLARIFY.
 17) SHT. P.700A - PLACE THE SPECIFIC SHEET NUMBER OF
 THE ORIGIN/CONTINUATION OF THE GAS SUPPLY LIINES TO THE
 APPLIANCES/EQUIPMENT ON EACH GAS RISER DETAIL. 2ND
 REQUEST.
 18) SHT. P.804 - SUBMIT THE SPECIFICATIONS/INSTALLATION
 MANUAL FOR THE GAS DETECTION SYSTEM AND REFERENCE THE
 STANDARD ON WHICH THIS SYSTEM IS DESIGNED. 2ND
 REQUEST.WPB AMEEND. TO FBC SEC.107.2.1.
 19) SHT. P.700 - THERE ARE FOUR RISER TAGS ON THIS PAGE
 IDENTIFIED AS G/H1, G/H2, G/H3 AND G/R1 WITH NO DRAWING
 LOCATION ON THESE RISER TAGS. CLARIFY.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  
  

Review Stop G GAS REVIEW
Rev No 2 Status F Date 2020-03-28 Cont ID  
Sent By tklarge Date 2020-03-28 Time 10:06 Rev Time 0.00
Received By tklarge Date 2020-03-28 Time 07:22 Sent To  
Notes
2020-03-28 09:34:431) SHT. P.700A - THERE IS A NOTE ON ALL THE DETAILS
 THAT STATES "REFER TO SHT. P.802, DETAIL #10 FOR
 SEDIMENT TRAP DETAIL." THERE IS NO DETAIL #10 ON SHT.
 P.802 ? CLARIFY.
 2) 2) SHT. P700A - DETAIL #5 - SIZE THE MAIN LINE
 BETWEEN THE 4 INCH AND 2 1/2 INCH SECTIONS OF PIPE THAT
 SUPPLIES WATER HEATERS 1B & 1C.
 3) SHT. P700A - DETAILS #1 & #3 - NOTE #4 - THERE IS
 NOTE ON THESE DETAILS THAT REFERS TO SHT. P.802 FOR
 WATER HEATER DETAIL. THIS DETAIL HAS NOTHING TO DO WITH
 GAS WATER HEATERS. THE CORRECT SHEET IS P.804.PLEASE
 REVISE THE NOTE ON THE PLAN.
 4) SHT. P.803 - THE GAS WATER HEATER SCHEMATICS REFER
 TO THE HVAC DRAWINGS FOR FLUE INFORMATION FOR THE WATER
 HEATERS. PLACE THE SPECIFIC MECHANICAL SHEET NUMBERS ON
 THE DRAWINGS WHERE THE INFORMATION CAN BE FOUND. WPB
 AMEND. TO FBC SEC. 107.2.1.
 5) SHT. P700 - KEYNOTE #8 - SHOWS THE CFH AS 2,012 BUT
 THE GAS RISER SHOWS THE CFH AS 3,075. IF THIS NUMBER OF
 3, 075 IS CORRECT, THEN THE REST OF THE CFH ON THE GAS
 RISER IS WRONG. CLARIFY.
 6) SHT. P700 - THE NUMBERING ON THE GAS TAGS ON THE GAS
 RISER ARE VERY LIGHT AND ALMOST ILLEGIBLE. PLEASE
 REVISE.
 7) SHT. P.804 - SUBMIT ADDITIONAL INFORMATION
 (SPECIFICATIONS/ INSTALLATION MANUAL) FOR THE GAS
 DETECTION SYSTEM AND REFERENCE THE STANDARD ON WHICH
 THIS SYSTEM IS DESIGNED. WPB AMEND. TO FBC SEC.
 107.2.1.
 8) SHT. P.700A - PLACE THE SPECIFIC SHEET NUMBER IN THE
 GAS ISOMETRICS FOR THE ORIGINATING POINTS OF THE GAS
 LINES. WPB AMEND. TO FBC SEC. 107.2.1, 107.3.5.1.5.
 9) ALL GAS EQUIPMENT SHALL BE LISTED AND LABELED PER
 FBC-FUEL GAS SEC.301.3.
 10) SUBMIT CALCULATIONS FOR COMBUSTION AIR. PROVIDE
 VERIFICATION & CALCULATIONS AS TO HOW THE REQUIREMENTS
 ARE BEING MET. PROVIDE THE CODE SECTIONS FROM THE GAS
 CODE THAT YOU ARE USING IN THE DESIGN OF THE COMBUSTION
 AIR REQUIREMENTS PER THE 2014 FBC-FUEL GAS CODE
 SEC.304.1,
 11) SUBMIT DETAILS FOR THE TYPE OF GAS VENT MATERIAL,
 LOCATION, SIZE, TERMINATION POINT, HEIGHT ABOVE ROOF,
 AND ANCHORING DETAILS OF THE GAS VENTS. FBC-FUEL GAS
 SECS.502 THROUGH 505.
 12) THE RESPONSE NARRATIVE STATES THAT A PDF PACKAGE
 HAS BEEN CREATED AND SUBMITTED ALONG WITH REQUESTED
 DRAWINGS TO COMPLY WITH PREVIOUS COMMENT # 4 FROM THE
 GAS REVIEW FROM 4/9/19 REQUESTING TWO COPIES OF
 MANUFACTURER?S SPECIFICATIONS AND INSTALLATION MANUALS
 FOR ALL GAS EQUIPMENT BUT THERE ARE NO SUCH DOCUMENTS
 IN THIS SUBMITTAL. CLARIFY.
 13) SHT. P.509 - DETAIL #2 SHOWS THE SHUTOFF VALVE
 OUTSIDE THE ROOM WHERE THE POOL HEATER IS LOCATED.
 CLARIFY.
 14) SHT. P.105C SHOWS VENT PIPING FROM THE GAS
 REGULATOR RUNNING FOR AN EXTENSIVE DISTANCE TO ITS
 TERMINATION POINT. VENT PIPING SHALL NOT EXCEED THE
 LENGTH SPECIFIED IN THE REGULATOR MANUFACTURER?S
 INSTRUCTIONS. SUBMIT THE VENT INSTALLATION INSTRUCTIONS
 FOR ALL THE REGULATORS TO BE USED. FBC-FUEL GAS SEC.
 410.3.1.
 15) SHOW THE SIZE OF THE GAS REGULATOR VENTS ON THE
 PLANS. WPB AMEND. TO FBC SEC. 107.2.1.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  
  
  
  

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2019-04-09 Cont ID  
Sent By gjohnson Date 2019-04-09 Time 10:28 Rev Time 0.00
Received By gjohnson Date 2019-04-09 Time 10:28 Sent To  
Notes
2019-04-09 10:28:301ST REVIEW: 18100540
 2017 FLORIDA BUILDING CODE 6TH EDITION
 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH
 EDITION
  
 GAS COMMENTS:
  
 1. SHT. P-700 SHOW ON THE ISOMETRIC DRAWING THE PIPING
 UP TO THE CONNECTION OF EVERY GAS APPLIANCE INCLUDING
 VALVES, REGULATOR AND DRIP LEG OR PROVIDE A DETAIL FOR
 EACH APPLIANCE OR GROUP WITH A CORRESPONDING TAG TO THE
 OVERALL ISOMETRIC. PER WPB AMEND TO FBC 107.2.1
 2. SUBMIT TWO COPIES OF A DETAIL SHOWING THE TYPE OF
 VENT, LOCATION, SIZE, TERMINATION POINT, HEIGHT ABOVE
 THE ROOF AND ANCHORING DETAILS OF THE GAS VENT(S) PER
 2017 FBC-FUEL GAS SECS. 502 THRU 505 OR 2017 FBC-RES.
 SEC.G2426 THROUGH G2439.
 3. SUBMIT CALCULATIONS FOR COMBUSTION AIR PER THE 2017
 FBC-FUEL GAS CODE SEC.304.1, 614.6 (CLOTHES DRYERS) OR
 2017 FBC-RES. SEC.G 2407.1 AND G2439.4 (CLOTHES
 DRYERS).
 4. SUBMIT TWO COPIES OF THE MANUFACTURER?S
 SPECIFICATION SHEETS / INSTALLATION MANUAL FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH STANDARDS NFPA 54,
 NFPA 58, AND FBC-2017 FUEL GAS CODE SEC. 402.2, AND
 301.3 OR 2017 FBC-RES. SEC. G2404.3. GAS APPLIANCES
 SHALL BE LISTED AND LABELED. THE INSTALLATION MANUALS
 FOR ALL GAS APPLIANCES / EQUIPMENT SHALL BE ONSITE AT
 THE TIME OF INSPECTION. FGC SEC.305.1, FBC-RES.
 SEC.G2408.1.
 5. SUBMIT MANUFACTURER?S SPECIFICATIONS AND
 INSTALLATION INSTRUCTIONS FOR THE PRESSURE REGULATORS.
 REGULATORS INSTALLED ON THE EXTERIOR OF THE BUILDING
 SHALL BE APPROVED FOR OUTDOOR INSTALLATION. IDENTIFY ON
 THE SPECIFICATION SHEETS WHICH MODEL REGULATOR IS BEING
 INSTALLED AND THE ORIFICE SIZE TO ENSURE THE REGULATOR
 CAN ACCOMMODATE THE BTU LOAD THROUGH THE REGULATOR.2017
 FGC SEC.410.1, 2017 FBC-RES. SEC. G2421.1.
 6. SHOW DISTANCE BETWEEN 2ND STAGE REGULATOR AND
 APPLIANCE SIZE AND TYPE OF PIPE. PER WPB AMEND TO FBC
 107.2.1
 7. GAS SYSTEM # 3 SHALL BE MARKED FOR REFERENCE ONLY OR
 PROVIDE PIPE SIZE, TYPE, LENGTH OF RUN AND BTU LOAD.
 PER 2017 FBC-FUEL GAS, SECS. 402.4.1, 402.4.2. OR 2017
 FBC-R SEC. G2413.4.1, G2413.4.2.
  
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2021-09-08 Cont ID  
Sent By cpuell Date 2021-09-08 Time 08:59 Rev Time 0.00
Received By cpuell Date 2021-09-02 Time 09:04 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2021-08-30 Cont ID  
Sent By rmcdouga Date 2021-08-30 Time 08:07 Rev Time 0.00
Received By rmcdouga Date 2021-08-11 Time 09:39 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2021-06-22 Cont ID  
Sent By lmarchan Date 2021-06-22 Time 09:01 Rev Time 0.00
Received By lmarchan Date 2021-05-17 Time 15:41 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2021-03-04 Cont ID  
Sent By lmarchan Date 2021-03-04 Time 16:41 Rev Time 0.00
Received By lmarchan Date 2020-12-22 Time 17:06 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2020-03-30 Cont ID  
Sent By lmarchan Date 2020-03-30 Time 10:04 Rev Time 0.00
Received By lmarchan Date 2020-02-10 Time 12:18 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2019-04-29 Cont ID  
Sent By cpuell Date 2019-04-29 Time 12:36 Rev Time 0.00
Received By cpuell Date 2019-02-26 Time 07:42 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-11-29 Cont ID  
Sent By shill Date 2018-11-29 Time 16:01 Rev Time 0.00
Received By shill Date 2018-10-24 Time 08:08 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status P Date 2019-04-30 Cont ID  
Sent By shill Date 2019-04-30 Time 11:00 Rev Time 0.00
Received By shill Date 2019-03-18 Time 12:52 Sent To  
Notes
2019-04-30 11:01:27SEE IMPACT FEE REVIEW UNDER STRUCTURE REVISION 19020102
  
2019-03-18 12:53:083/18/19 SENT EMAIL TO IMPACT FEE OFFICE.

Review Stop M MECHANICAL (A/C)
Rev No 5 Status P Date 2021-08-16 Cont ID  
Sent By medwards Date 2021-08-16 Time 09:10 Rev Time 0.00
Received By medwards Date 2021-08-16 Time 07:54 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 4 Status F Date 2021-06-10 Cont ID  
Sent By medwards Date 2021-06-10 Time 13:12 Rev Time 0.00
Received By medwards Date 2021-06-10 Time 13:12 Sent To  
Notes
2021-06-10 13:12:174TH REVIEW FBC-2020 MECHANICAL
 PERMIT-18100540
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE
 FBC M- FLORIDA MECHANICAL CODE
 FBC EC- FLORIDA ENERGY CONSERVATION
 FBC FG- FLORIDA FUEL GAS
 FBC EX- FLORIDA EXISTING BUILDING CODE
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PLEASE ADDRESS NOTE (3) OF THE PREVIOUS COMMENTS,
 THERE STILL IS NO SHEET MP.002 WHICH IS SUPPOSE TO SHOW
 THE REMOTE FUEL FILL STATION AND FILL PIPE.
  
 2) SHEET M-715: DRYER EXHAUST RISER R3 AND R14 STILL
 APPEAR TO NOT MEET FBC M 504.8 (4)
  
 3) PLEASE SEE NOTE (5) OF THE PREVIOUS COMMENTS: SHEET
 M.715 PLEASE SHOW THAT THE EXHAUST FAN FOR THE DRYER
 EXHAUST SUB DUCT MEETS FBC M 504.8 (5).
  
 4) PLEASE SEE COMMENT (6) OF PREVIOUS COMMENTS: SHEET
 M-715- PLEASE SHOW THAT THE EXHAUST FAN FOR THE DRYER
 SUB DUCT MEETS FBC M 504.8 (8)
  
 5) WITH NO RESPONSE LETTER FROM THE DESIGNER I DO NOT
 SEE THAT COMMENT (10) OF PREVIOUS COMMENTS HAS BEEN
 ADDRESSED: PLEASE PROVIDE THE SPECIFIC DRYER
 SPECIFICATIONS ALONG WITH THE DRYER DUCT LENGTHS. FBC M
 504.6.4
  
 6)
  
 BUILDERS RISK WITH X VENT
  
 THE INSTALLATION OF THE PROPOSED XVENT DRYER EXHAUST
 TERMINATION PROCEEDS ENTIRELY AT THE RISK OF THE
 DEVELOPER. IN ORDER TO SHOW THAT THE PRODUCT IS IN
 COMPLIANCE WITH SECTION 504.4 OF FLORIDA BUILDING CODE,
 MECHANICAL, AT A MEETING BETWEEN CITY OF WEST PALM
 BEACH STAFF AND XVENT ON 5/27/21, XVENT PERSONNEL
 AGREED TO CONDUCT AN AUDIT TO COMPARE LINT BUILD UP ON
 TYPICAL LOUVERED BACKDRAFT DAMPER DRYER VENT
 TERMINATIONS VERSUS BUILD UP ON THE FIXED LOUVERS OF
 THE XVENT PRODUCT WHEN USED AS A DRYER EXHAUST
 TERMINATION. THE PURPOSE OF THE AUDIT IS FOR XVENT TO
 JUSTIFY THE USE OF THEIR PRODUCT BY SHOWING THAT THEIR
 FIXED LOUVER PRODUCT IS NOT MORE SUSCEPTIBLE TO LINT
 BUILD UP THAN A TYPICAL LOUVERED BACKDRAFT DAMPER DRYER
 VENT TERMINATION. CODE COMPLIANCE WILL BE DETERMINED
 BASED ON THE RESULTS OF THE AUDIT.
  
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2021-01-07 Cont ID  
Sent By medwards Date 2021-01-07 Time 09:01 Rev Time 0.00
Received By medwards Date 2021-01-07 Time 09:01 Sent To  
Notes
2021-01-07 09:01:373RD REVIEW FBC-2017 MECHANICAL
 PERMIT-18100540
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH
 EDITION 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET M.201A AND SHEET M.201B: PLEASE SHOW A DETAIL
 OF THE MECHANICAL SYSTEM FOR THE EXIT PASSAGEWAY
 SHOWING HOW IT MEETS FBC M 601.3. THE EXIT PASSAGEWAY
 CANNOT BE SERVED BY A SYSTEM THAT SERVES ANY OTHER
 AREA.
  
 2) SHEET M.201A AND M.201B: PLEASE EXPLAIN THE INTAKE
 DUCT IN ELECTRIC ROOM (E4) FBC 107.2.1
  
 3) PREVIOUS COMMENT #12- THE RESPONSE STATES TO LOOK ON
 SHEET MP.002 FOR THE REMOTE FUEL FILL STATION AND FILL
 PIPE. THERE IS NO MP.002 SHEET SUBMITTED IN THIS
 PACKAGE.
  
 4) SHEET M.715 AND SHEET M.707: THE DRYER EXHAUST
 DIAGRAM SHOWS OFF SETS IN SEVERAL RISERS, PLEASE SHOW
 HOW THIS WOULD MEET FBC M 504.8 (4)
  
 5) SHEET M.715: PLEASE SHOW THAT THE EXHAUST FAN FOR
 THE DRYER EXHAUST SUB DUCT MEETS FBC M 504.8 (5)
  
 6) SHEET M.715: PLEASE SHOW THAT THE EXHAUST FAN FOR
 THE DRYER SUBDUCT MEETS FBC M 504.8 (8)
  
 7) SHEETS M.254- SHEET M.262: PLEASE REMOVE THE DRYER
 BOOSTER FANS AS THERE IS NO REFERENCE OF THESE IN THE
 2014 FBC M.
  
 8) THE DRYER EXHAUST DUCT MUST BE INSTALLED BY THE
 MANUFACTURES INSTALLATION INSTRUCTIONS. THE TYPICAL
 DRYER INSTALLATION MANUAL WILL ALLOW ONLY (4) 90 DEGREE
 FITTINGS IN A SINGLE RUN. I DO SEE SEVERAL DRYER DUCT
 WITH MORE THAN THE 4 90 DEGREE FITTINGS IN A SINGLE
 RUN, PLEASE CORRECT THIS. FBC M 504.6.4.2
  
 9) PLEASE PROVIDE A LETTER FROM THE DRYER MANUFACTURER
 STATING THAT THE X VENT DRYER EXHAUST TERMINATION IS
 ALLOWED WITH EACH SPECIFIC DRYER. THE X VENT IS UNIQUE
 IN THE FACT THAT IT USES BOTH THE BACK-DRAFT DAMPER AND
 THE LOUVER. THE INSTALLATION MANUAL DOES NOT ADDRESS
 THIS KIND OF INSTALLATION. WITH THE X VENT SYSTEM THE
 BOX OF THE X VENT IS MOUNTED INTO THE EXTERIOR OF THE
 WALL AND THE LOUVER IS FLUSH TO THE EXTERIOR WALL. THE
 EXHAUST OF THE DRYER MUST TRAVEL THROUGH THE EXHAUST
 DUCT, OPEN THE BACK-DRAFT DAMPER AND TRAVEL THROUGH THE
 X VENT COVER (LOUVER) BEFORE IT IS EXHAUSTED TO THE
 OUTDOORS. BECAUSE THIS PRODUCT USES BOTH THE BACK-DRAFT
 DAMPER AND THE OUTER COVER OF THE BOX (LOUVER) INSTEAD
 OF EITHER THE BACK-DRAFT DAMPER OR THE LOUVER AS
 TYPICALLY SEEN IN THE MANUFACTURES INSTALLATION MANUAL
 THE OUTER LOUVER IS A RESTRICTION THAT MUST BE
 ADDRESSED. IN LIEU OF THE MANUFACTURES LETTER STATING
 THE MAXIMUM DRYER EXHAUST DUCT TO BE USED WITH THE X
 VENT SYSTEM THE ENGINEER OF RECORD MUST DETERMINE THE
 AMOUNT OF RESTRICTION THIS CREATES AND THE EFFECT TO
 THE DRYER EXHAUST DUCT LENGTH. THE ENGINEER OF RECORD
 MUST SUBMIT THE CALCULATIONS AND PROVIDE MAX. EXHAUST
 DRYER DUCT LENGTHS FOR EACH DRYER USED IN THIS PROJECT.
 FBC M 504.8.4.2
  
 10) PLEASE PROVIDE THE SPECIFIC DRYER SPECIFICATIONS
 ALONG WITH THE DRYER DUCT LENGTHS. FBC M 504.6.4
  
 11) SHEET M.205B; WHAT IS THE WATER HEATER INTAKE AND
 EXHAUST PIPING MATERIAL? PLEASE PROVIDE THE
 SPECIFICATIONS FOR THE MENTIONED FIRE WRAP MATERIAL
 CALLED OUT ON THE DRAWING FOR THE SPECIFIC PIPING
 MATERIAL OF THE INTAKE AND EXHAUST PIPING. FBC 107.2.1
  
 12) SHEET M.701; I DO NOT SEE THE MENTIONED SD?S AT THE
 RETURN DUCT OF THE ERU-3 AND AHU-11 ON EACH LEVEL OF
 OFFICE TOWER. PLEASE CLOUD THE SD?S TO CLEARLY SHOW THE
 CHANGES. FBC 107.2.1
  
 13) SHEETS M.606-M.607; PLEASE IDENTIFY EACH VENT ZONE
 IN THE OUTDOOR AIR CALCULATIONS TO MATCH THE TABLES
 EITHER IN THE 2014 FBC M TABLE 403.3 OR ASHRAE 62.1
 TABLE 6.2.2.1
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD
 SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER
 SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN
 THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS
 PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS
 PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR
 UPDATED.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2020-03-10 Cont ID  
Sent By ccole Date 2020-03-10 Time 18:05 Rev Time 0.00
Received By ccole Date 2020-02-26 Time 13:34 Sent To  
Notes
2020-03-10 18:06:302ND REVIEW FBC-2014 MECHANICAL
 PERMIT #18100540
 550 N QUADRILLE BLVD
 3/2/20
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2014
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2014
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2014
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2014
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 1) ENERGYGAUGE COMPLIANCE REPORT PAGE 47: THE COOLING
 TOWER MUST MEET THE MINIMUM EFFICIENCY REQUIREMENT
 LISTED IN TABLE C403.2.3(8) FBC EC. PLEASE CORRECT THE
 N/A CHECKMARK. A) PLEASE NOTE THAT THE PLANS FOR THE
 PROPOSED PROJECT ARE BEING DESIGNED IN ACCORDANCE WITH
 THE FLORIDA BUILDING CODE- 2014 FIFTH EDITION. AS A
 RESULT THE 2017 VERSION OF THE ENERGYGAUGE COMPLIANCE
 SOFTWARE CANNOT BE USED. PLEASE SUBMIT THE 2014
 ENERGYGAUGE SOFTWARE VERSION.
  
 2) THE STAIR PRESSURIZATION RATIONAL ANALYSIS SHALL BE
 ELECTRONICALLY SIGNED AND SEALED BY THE ENGINEER WHO
 PREPARED THE DOCUMENT- FL. STATUTE 471.025 AND SECTION
 61G15-23.005 FLORIDA ADMINISTRATIVE CODE. IN ADDITION,
 THE ARCHITECT OF RECORD AND THE MECHANICAL ENGINEER OF
 RECORD SHALL EACH PROVIDE A REVIEW AND APPROVAL STAMP
 ON THE DOCUMENT- SECTION 107.2.1 WPB. PLEASE NOTE THAT
 SPECIAL INSPECTION AND COMMISSIONING OF THE SYSTEMS
 SHALL BE CONDUCTED IN ACCORDANCE WITH SECTION 909.18.1
 FBC B, AND A FINAL COMMISSIONING REPORT SHALL BE
 PROVIDED TO THE CITY OF WEST PALM BEACH BUILDING
 DIVISION AND THE WPB FIRE DEPARTMENT AS A CONDITION OF
 RECEIVING A FINAL CERTIFICATE OF OCCUPANCY FOR THE
 BUILDING- SEE SECTIONS 909.3 AND 909.18.8.1- 909.20 FBC
 B. THE ENGINEER OF RECORD AND SMOKE CONTROL ARE ADVISED
 TO LOOK AT THE ISSUES LISTED BELOW.
 A) MISSING FROM THE REPORT IS A DETAILED NARRATIVE
 DESCRIPTION OF HOW THE FIRE ALARM AND PRESSURIZATIONS
 SYSTEMS IN THE TWO TOWERS AND PODIUM WILL COORDINATE
 AND INTERACT TOGETHER UNDER EMERGENCY ALARM CONDITIONS.
 FOR EXAMPLE- WILL ALL THE INTERIOR EXIT STAIRWAYS BE
 PRESSURIZED IN THE TOWERS AND THE PODIUM IF AN ALARM
 OCCURS IN JUST ONE AREA OF THE BUILDING SUCH AS THE
 PODIUM OR ONE OF THE TOWERS, OR WILL JUST THE STAIRWAYS
 IN THE AREA OF THE INCIDENT BE PRESSURIZED?
 B) STAIR 1 HAS AN EXTENSION AT THE GROUND FLOOR THAT IS
 MISLABELED AS A CORRIDOR, AND SHOULD BE LABELED AS AN
 EXIT PASSAGEWAY- SECTION 1022.3.1 FBC B. THE PASSAGEWAY
 SHALL BE PRESSURIZED IN THE SAME MANNER AS THE
 STAIRWAY- SECTION 1022.10.1 FBC B.
 C) ITEM 4.2 OF THE REPORT SPECIES SMOKE DETECTION AT
 THE ENTRANCE TO THE PRESSURIZED STAIRWELLS, AND DUCT
 SMOKE DETECTORS ARE SHOWN ON THE PLANS IN THE
 PRESSURIZATION DUCTS AND FAN HOUSINGS. PLEASE NOTE THAT
 SECTION 606.2.1 FBC M REQUIRES UL LISTED AND LABELED
 DUCT SMOKE DETECTORS IN THE RETURN DUCTS OF AIR
 DISTRIBUTION SYSTEMS, BUT NOT IN PRESSURIZATION SUPPLY
 DUCTS. PLEASE PROVIDE A WRITTEN SEQUENCE OF OPERATION
 FOR THE DETECTORS AND A PRODUCT SUBMITTAL. THE
 SUBMITTAL SHALL INDICATE THE DEVICES ARE LISTED AND
 LABELED FOR USE IN PRESSURIZATION SYSTEMS- SECTION
 107.2.1 WPB.
 D) FIRE WRAPPING AND FLAMEBAR DUCTWORK ARE BEING USED
 THROUGHOUT THE BUILDING TO PROVIDE THE REQUIRED 2-HR.
 FIRE BARRIER ENCLOSURE FOR THE PRESSURIZATION DUCTS
 THAT ARE CONNECTING THE O/A INLETS AND FANS TO THE
 STAIRWAYS. 1) FIRE WRAP: PLEASE VERIFY AND ACKNOWLEDGE
 IN THE ANALYSIS THAT THE WRAPPING HAS THE REQUIRED UL
 LISTING AND LABELING TO PROVIDE THE REQUIRED FIRE
 RESISTANCE PER SECTION 703.2.1 FBC B. 2) FLAMEBAR:
 PROVIDE A COMPLETE FLAMEBAR DUCTWORK SUBMITTAL PACKAGE
 INCLUDING UL LISTED ASSEMBLIES AND JOB-SPECIFIC
 INSTALLATION DETAILS- JOINTS, CONNECTIONS, SUPPORTS.
 PLEASE NOTE THAT THE MECHANICS ASSEMBLING THE DUCTWORK
 SHALL BE CERTIFIED TO DO THE INSTALLATIONS AND THE
 CERTS SHALL BE ONSITE AT TIME OF INSPECTION.
  
 3) SHEETS M.606 & M.607: PLEASE PROVIDE INDIVIDUAL O/A
 CFM TOTALS FOR THE OFFICE TOWER, HOTEL TOWER, AND
 RESIDENTIAL TOWER AND PODIUM.
 A) INDICATE WHAT THE "K" SYMBOL MEANS THAT IS SHOWN IN
 THE ZONE POPULATION COLUMN OF THE SCHEDULES.
 B) THE PROVIDED (ACTUAL OUTDOOR AIRFLOW RATE) CFMS IN
 MANY OF THE ROOMS AND SPACES SHOWN IN THE TABLES IS
 LESS THAN THE REQUIRED CFMS FOR EXAMPLE THE BALLROOM,
 PREFUNCTION, CONFERENCE, RESIDENTIAL LOBBY, TENNIS
 EVENT, MAIL, FITNESS, HOTEL ELEVATOR LOBBY ETC. PLEASE
 CORRECT THE SCHEDULES- TABLE 403.3.1.1 FBC M.
 C) PROVIDE VENTILATION CALCULATIONS FOR THE INDOOR
 TENNIS COURTS AND THE INDOOR POOL- TABLE 403.3.1.1 FBC
 M.
  
 4) PLEASE NOTE THAT THE PLANS FOR THE PROPOSED PROJECT
 ARE BEING DESIGNED IN ACCORDANCE WITH THE FLORIDA
 BUILDING CODE- 2014 FIFTH EDITION. AS A RESULT, ALL
 PREVIOUS REVIEW COMMENTS REQUIRING DUCT SMOKE DETECTORS
 IN THE SUPPLY SYSTEMS OF THE AIR HANDLERS ARE NOT
 APPLICABLE. WHERE REQUIRED, THE DUCT SMOKE DETECTORS
 SHALL BE INSTALLED IN THE RETURN AIR SYSTEMS.
  
 PODIUM
  
 5) M201, 202, 203, 204, 205: THE REVISED PLANS ARE
 MISSING DUCT SIZES, AND LABELS FOR DUCTS, DIFFUSERS
 RETURN GRILLS, VAV'S, AHU'S, SENSORS ETC.- SECTION
 107.2.1 WPB.
  
 6) M201.A & ALSI.101: THE VESTIBULE AT STAIR #3 IS
 NEITHER FIRE-RATED OR VENTILATED- TABLE 1028.1 FBC B
 AND TABLE 403.3.1.1 FBC M.
  
 7) M201.A: PROVIDE CONSTRUCTION DETAILS FOR THE
 FIRE-RATED PRESSURIZATION DUCT ENCLOSURE AT STAIR #3-
 SECTION 703.2.1 & 717.2.1 FBC B.
  
 8) M201.B: SHOW THE FUTURE TERMINATION LOCATIONS AND
 REQUIRED CLEARANCES FOR THE KITCHEN HOOD GREASE EXHAUST
 DUCT, AND ALL OTHER KITCHEN EXHAUST DUCTS- SEE SECTION
 506 FBC M.
  
 9) M201B: FIRE DAMPERS MISSING AT DUCTS PENETRATING THE
 1-HR FIRE RATED WALLS AT THE RECEIVING, LUGGAGE,
 CORRIDOR 0141, OFFICE ROOM WALLS- SECTION 607.5.2 FBC
 M.
  
 10) M201.C: PROVIDE PRODUCT SUBMITTALS FOR THE DIESEL
 FIRE PUMP AND THE PUMP EXHAUST DUCTWORK- SECTIONS 4.2
 AND 11.5.2.5 NFPA 20. PLEASE NOTE THAT THE SUBMITTALS
 MAY BE DEFERRED BY REQUEST. A) SHOW THE LOCATION OF THE
 PUMP IN THE ROOM AND REFER TO SECTION 11.3.2.4.3 NFPA
 20 FOR EXHAUST REQUIREMENTS FOR RADIATOR-COOLED
 ENGINES. A DIRECT DUCT CONNECTION TO THE PUMP VIA A
 FLEXIBLE SECTION MAY BE REQUIRED. B) PLEASE ADD NOTES
 TO INDICATE THE VENTILATION SYSTEM FOR THE PUMP AS
 DESIGNED WILL BE CAPABLE OF MAINTAINING A MAXIMUM
 TEMPERATURE OF 120 DEGREES F IN THE ROOM, WILL PROVIDE
 ADEQUATE COMBUSTION AIR, AND WILL REMOVE ALL HAZARDOUS
 VAPORS- SECTION 11.3.2.1 NFPA 20. PLEASE NOTE THERE IS
 NO AC SYSTEM IN THE ROOM.
  
 11) M201.C: PROVIDE THE SEQUENCE OF OPERATION FOR THE
 GENERATOR FUEL STORAGE TANK ROOM EXHAUST SYSTEM-
 SECTION 502.8.1.1 FBC M.
  
 12) M.301C & M711- DIESEL FIRE PUMP AND FUEL TANK: A)
 PROVIDE FUEL TANK, FILL AND VENT PIPE SPECIFICATIONS,
 PIPE SIZING CALCULATIONS, PIPE INSTALLATION DETAILS-
 JOINTS AND CONNECTIONS, AND PIPE SUPPORT DETAILS-
 SECTION 1302, 1303, 1305 FBC M. B) SHOW THE REMOTE FILL
 PIPING LOCATION AND FILL PIPING RUN- SECTION 1305.6 FBC
 M. C) INDICATE THE REQUIRED CLEARANCES FOR THE VENT
 PIPING TO BUILDING OPENINGS- SECTION 1305.7 FBC M. IT
 APPEARS THE LOCATIONS ARE STILL INSIDE THE BUILDING
 FOOTPRINT WHICH IS NOT ALLOWED.
  
 13) M301.C & M711- GENERATOR FUEL TANK: PROVIDE THE
 FILL AND VENT PIPING SPECIFICATIONS, PIPE SIZING
 CALCULATIONS, PIPE INSTALLATION DETAILS- JOINTS AND
 CONNECTIONS, AND PIPE SUPPORT DETAILS- SECTION 1302,
 1303, 1305 FBC M. B) THE EMERGENCY VENT LINE FROM THE
 TANK SHALL TERMINATE OUTSIDE OF THE BUILDING- SECTION
 1305.7 FBC M & SECTION 27.8.2.6 NFPA 30. C) INDICATE
 HOW THE LINES WILL BE PROTECTED- SECTION 1305.7 FBC M.
 D) INDICATE THE REQUIRED CLEARANCES FOR THE FILL AND
 VENT PIPING TO BUILDING OPENINGS- SECTION 1305.7 FBC M.
 IT APPEARS THE LOCATIONS ARE STILL INSIDE THE BUILDING
 FOOTPRINT WHICH IS NOT ALLOWED.
  
 14) M.711: THE LOCATIONS OF THE 3-HR. FIRE-RATED FUEL
 LINE SHAFTS THROUGHOUT THE BUILDING ARE NOT SHOWN
 CLEARLY AND ACCURATELY ON THE LIFE SAFETY,
 ARCHITECTURAL, AND MECHANICAL AIR DISTRIBUTION PLANS.
 THE LIFE SAFETY PLANS APPEAR TO SHOW THEM IN THE SAME
 SHAFT WITH AN HVAC DUCT WHICH IS NOT ALLOWED. PLEASE
 SHOW THE LOCATIONS, NOTE THEM CLEARLY ON THE PLANS, AND
 PROVIDE CONSTRUCTION DETAILS FOR THE SHAFT- SECTION
 713.1 FBC B. A) PLEASE EMBOLDEN THE KEY NOTES IN THE
 DIAGRAM.
  
 15) M201.C: PROVIDE A SUBMITTAL FOR THE 2-HR FIRE RATED
 EXHAUST DUCT WRAP. PLEASE NOTE THE WRAP SHALL BE LISTED
 AND LABELED FOR USE ON HAZARDOUS EXHAUST DUCTS- SECTION
 510.7.3 FBC M.
  
 16) M201.C NOTE #1: THE 3' CLEARANCE TO OPERABLE
 OPENINGS IS ALLOWABLE FOR EXHAUST DUCTS SERVING A TYPE
 II HOOD ONLY. PLEASE PROVIDE MORE INFORMATION AND
 SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE HOOD,
 EXHAUST DUCT, AND THE COOKING APPLIANCE- SEE SECTIONS
 506.3.13.3 AND 506.4.2 FBC M. PLEASE NOTE THAT SEPARATE
 PERMITS ARE REQUIRED FOR KITCHEN EXHAUST AND FIRE
 SUPPRESSION SYSTEMS- SECTION 107.2.1 WPB.
  
 17) M201C: CU 5 SHALL BE INSTALLED OUTDOORS IN
 ACCORDANCE WITH THE LISTING AND LABELING OF THE
 APPLIANCE AND MANUFACTURER'S GUIDELINES- SECTION 304.1
 FBC M.
  
 18) M201.C: FIRE DAMPERS MISSING AT THE AHU-13 SUPPLY
 AND RETURN DUCT PENETRATIONS- SECTIONS 606.2 AND
 607.6.1 FBC M.22) M202.B: FIRE DAMPER MISSING FOR THE
 8X6 ERU SUPPLY DUCT PENETRATING FIRE-RATED WALL AT THE
 FIRE LOBBY.
  
 19) M202A AND ALL ENCLOSED GARAGE FLOORS: THE PLANS
 SHOW THE GARAGE FANS WILL BE EXHAUSTING THE AIR INTO
 THE SPACE BETWEEN THE EXTERIOR WALLS AND THE GREEN
 SCREEN. PLEASE VERIFY THAT THE EXHAUST AIR WILL BE ABLE
 TO FLOW FREELY OUT OF THE BUILDING AND NOT BE
 OBSTRUCTED BY THE SCREEN.
  
 20) M202.B, C, & D C: NO O/A PROVIDED AT THE ELEVATOR
 OR FIRE LOBBIES- TABLE 403.3.1.1 AND SECTION 404.3 FBC
 M.
  
 21) M202.C: SHOW THE SIZE OF THE SPF/01 PRESSURIZATION
 DUCT- SECTION 107.2.1 WPB.
  
 22) M202.C: FIRE DAMPER MISSING AT THE AHU-13 SUPPLY
 DUCT FLOOR PENETRATION- SECTION 607.6.1 FBC M.
  
 23) M202.C & D - M206.C & D: ACCORDING TO THE SCHEDULE
 AHU-14 SUPPLYING AIR TO THE RESIDENTIAL UNITS (AND ALL
 OTHER AHU'S IN THE SCHEDULE ON SHEET M.602) IS NOT
 BEING EQUIPPED WITH A MOTORIZED OUTSIDE AIR DAMPER
 (NOTE #8 IN THE SCHEDULE). THE PLAN SHOWS AN ACD FOR
 AHU-14, HOWEVER PLEASE NOTE SECTION C403.2.4.4 FBC EC
 REQUIRES OUTDOOR AIR SUPPLY DUCTS TO BE EQUIPPED WITH
 GRAVITY OR MOTORIZED DAMPERS THAT WILL AUTOMATICALLY
 SHUT WHEN THE SYSTEMS OR SPACES ARE NOT IN USE. PROVIDE
 DAMPERS FOR EACH DUCT SUPPLYING O/A TO THE VHP'S.
  
 24) M202 C & D- M206.C & D, M605, M707: REFER TO
 SECTION 504.8 FBC M AND PROVIDE THE FOLLOWING DETAILS
 AND INFORMATION CONCERNING THE CLOTHES DRYER EXHAUST
 SYSTEMS- TYPE OF DUCTWORK, SEQUENCE OF OPERATION FOR
 THE EXHAUST FANS, AND HOW MAKEUP AIR IS BEING PROVIDED.
 A) PROVIDE AIR BALANCE CALCULATIONS FOR THE RESIDENTIAL
 UNITS THAT INCLUDE THE CLOTHES DRYER AND TOILET EXHAUST
 SYSTEMS.
  
 25) M203.B, C, & D C: NO O/A PROVIDED AT THE ELEVATOR
 OR FIRE LOBBIES- TABLE 403.3.1.1 AND SECTION 404.3 FBC
 M.
  
 26) M203.B, 204.B, 205.B, 206.B: IT APPEARS THAT
 FIRE-WRAPPING IS BEING USED TO CREATE CONTINUOUS
 VERTICAL TO HORIZONTAL SHAFTS FOR THE ERU-01 SUPPLY
 DUCTS AND THE RETURN/SMOKE PURGE DUCTS. PLEASE PROVIDE
 A UL LISTED ASSEMBLY SHOWING THE FIRE WRAPPING USED IN
 THIS CONFIGURATION- PLEASE SEE SECTION 703.2.1 FBC B.
  
 27) M203.B- M206.B: SECTION C403.2.4.4 FBC EC REQUIRES
 OUTDOOR AIR SUPPLY DUCTS TO BE EQUIPPED WITH GRAVITY OR
 MOTORIZED DAMPERS THAT WILL AUTOMATICALLY SHUT WHEN THE
 SYSTEMS OR SPACES ARE NOT IN USE. PROVIDE DAMPERS FOR
 EACH DUCT SUPPLYING O/A TO THE FCU'S.
  
 28) M204.C, & D: NO O/A PROVIDED AT THE ELEVATOR OR
 FIRE LOBBIES- TABLE 403.3.1.1 AND SECTION 404.3 FBC M.
  
 29) M205.B: CU-2 SHALL BE INSTALLED OUTDOORS IN
 ACCORDANCE WITH THE LISTING AND LABELING OF THE
 APPLIANCE AND MANUFACTURER'S GUIDELINES- SECTION 304.1
 FBC M.
  
 30) M205.B: SUBMIT MANUFACTURER'S SPECIFICATIONS FOR
 THE WATER HEATER INTAKE VENT AND EXHAUST FLUE
 FIRE-WRAPPING- SECTION 304.1 FBC M. THE SPECS SHALL
 SHOW THE PRODUCT CAN BE USED FOR THIS TYPE OF
 INSTALLATION IN LIEU OF A FIRE-RATED SHAFT
  
 31) M205.D: NO O/A PROVIDED AT THE ELEVATOR OR FIRE
 LOBBIES- TABLE 403.3.1.1 AND SECTION 404.3 FBC M.
  
 32) M205.C & M206.C: IT APPEARS FD'S ARE MISSING AT THE
 AHU-14 SUPPLY AND RETURN DUCT FLOOR/CEILING
 PENETRATIONS.
  
 33) M205.C: PLEASE CLARIFY THE PURPOSE OF THE FSD SHOWN
 IN THE MIDDLE OF THE 24X20 SUPPLY DUCT FROM AHU-14.
  
 34) M205.C & M206.C POOL EQUIPMENT ROOM: A) PROVIDE A
 POOL EQUIPMENT SCHEDULE AND SUBMIT MANUFACTURER'S
 SPECIFICATIONS FOR THE POOL HEATERS AND DIRECT VENT
 EXHAUST AND INTAKE DUCTS- SECTION 301.3 FBC FG. B)
 PROVIDE A GAS PIPING PLAN AND ISOMETRIC DRAWING-
 SECTION 402.1 FBC FG. C) THE AIR INTAKE LOUVER SHALL
 COMMUNICATE DIRECTLY TO THE OUTDOORS AND CANNOT DRAW
 VENTILATION AIR FROM THE ENCLOSED GARAGE SPACE- TABLE
 403.3.1.1 FOOTNOTE B. D) REFER TO SECTION 414.1.3 FBC B
 AND PROVIDE A LIST OF POOL TREATMENT CHEMICALS AND
 THEIR QUANTITIES TO BE USED AND STORED IN THE ROOM. E)
 INDICATE THE SEQUENCE OF OPERATION FOR EF 62 AND THE
 TYPE OF EXHAUST DUCTWORK TO BE INSTALLED- REFER TO
 SECTIONS 510.2- 510.9 FBC M. F) INDICATE THE REQUIRED
 CLEARANCES FOR THE EXHAUST OUTLET- SECTION 501.3.1 FBC
 M. G) SHOW COMPLIANCE WITH SECTION 305.3.2 FBC FG:
 CONNECTION OF A PARKING GARAGE WITH ANY ROOM IN WHICH
 THERE IS A FUEL-FIRED APPLIANCE SHALL BE BY MEANS OF A
 VESTIBULE PROVIDING A TWO-DOORWAY SEPARATION, EXCEPT
 THAT A SINGLE DOOR IS PERMITTED WHERE THE SOURCES OF
 IGNITION IN THE APPLIANCE ARE ELEVATED IN ACCORDANCE
 WITH SECTION 305.3.
  
 35) M206.A, EMERGENCY GENERATOR: THE EXHAUST DUCT FROM
 EF-53 SHALL RUN INDEPENDENTLY AND DIRECTLY TO THE
 EXTERIOR OF THE BUILDING, AND SHALL NOT CONNECT INTO
 THE RADIATOR EXHAUST PLENUM- SECTION 510.6.7 FBC M.
 PLEASE NOTE THAT THE GENERATOR WILL BE UNDER SEPARATE
 PERMIT. A COMPLETE SEPARATE PLAN AND SUBMITTAL PACKAGE
 WILL BE REQUIRED INCLUDING AN ENLARGED DRAWING OF THE
 EPSS (EMERGENCY GENERATOR) ROOM SHOWING THE LOCATIONS
 OF THE GENERATOR AND SUB-BASE TANK, FUEL OIL PIPE AND
 EXHAUST PIPE RUNS AND TERMINATION LOCATIONS, AND ALL
 OTHER ASSOCIATED EQUIPMENT INCLUDING EMERGENCY
 ELECTRICAL PANELS ETC. PLEASE INCLUDE THE REQUIRED
 CLEARANCE DISTANCE MEASUREMENTS FOR ALL EQUIPMENT VENT
 PIPING RUNS AND SPECIFICATIONS INCLUDING FILL PIPING
 LOCATIONS. THE SUBMITTAL PACKAGE SHALL INCLUDE:
 A) MANUFACTURER'S SPECIFICATIONS FOR THE GENERATOR AND
 THE 190-GALLON FUEL TANK, FUEL PIPING, ENGINE EXHAUST
 PIPE, MUFFLER, AND ALL OTHER ASSOCIATED SYSTEM
 COMPONENTS- SECTION 304.1 FBC M
 B) THE UL 2200 CERTIFICATE OF COMPLIANCE FOR THE
 GENERATOR- SECTION 915.1 FBC M.
 C) THE MANUFACTURER'S SPECIFICATIONS AND/OR UL
 CERTIFICATE SHALL INDICATE THE GENERATOR IS COMPLIANT
 WITH THE NFPA 37 AND NFPA 110 STANDARD AND IS
 CLASSIFIED AS A LEVEL 1 EPSS- SECTION 4.4.1 NFPA 110.
 D) PRODUCT CUT SHEET FOR THE FUEL TANK THAT INCLUDES
 THE TANK'S UL LISTING- UL 142 OR UL 2085- SEE SECTION
 21.4.2.1.1 NFPA 30.
 E) GENERATOR EXHAUST PIPE SPECIFICATIONS AND PROVIDE AN
 EXHAUST PIPE DIAGRAM SHOWING THE TOTAL SYSTEM RUN AND
 LENGTH MEASUREMENT, AND TERMINATION LOCATION PLEASE
 INCLUDE ALL COMPONENTS OF THE SYSTEM INCLUDING THE
 SILENCER, AND ANY CONTRACTOR SUPPLIED PIPING- SEE
 SECTIONS 8.1 ? 8.4 NFPA 37, AND SECTION 501.3.1 FBC M.
 F) BACKPRESSURE CALCULATIONS FOR THE GENERATOR EXHAUST
 PIPE RUN- SECTION 304.1 FBC M.
 G) DETAILS AND SPECIFICATIONS FOR NORMAL AND EMERGENCY
 RELIEF VENTING OF THE TANK, INCLUDING VENT PIPING RUNS
 AND TERMINATION LOCATIONS AT THE EXTERIOR OF THE
 BUILDING- SECTION 24.13 NFPA 30.
  
 36) M206.A: REFER TO SECTION 7.7.1 NFPA 110- 2016 AND
 VERIFY THAT THE VENTILATION AIRFLOW IN THE
 GENERATOR/TANK (EPS) ROOM IS DESIGNED TO LIMIT THE
 MAXIMUM AIR TEMPERATURE IN THE ROOM TO THE MAXIMUM
 AMBIENT AIR TEMPERATURE REQUIRED BY THE GENERATOR
 MANUFACTURER. CONSIDERATION SHALL BE GIVEN TO ALL THE
 HEAT EMITTED TO THE ROOM BY THE ENERGY CONVERTER,
 EXHAUST PIPES, AND ALL OTHER HEAT PRODUCING EQUIPMENT-
 SECTION 7.7.1.1. DESIGN OF THE HEATING, COOLING, AND
 VENTILATION SYSTEM SHALL AMONG OTHER THINGS, INCLUDE
 PROVISIONS FOR FACTORS SUCH AS HEAT, COLD, HUMIDITY,
 LOUVERS, ETC.- SECTION
 'S SPECS FOR THE BOILERS AND WATER HEATERS- SECTIONS
 402.1, 503.1, AND 624.1 FBC FG.
  
 38) M206.B: PROVIDE A DUCT SMOKE DETECTOR IN THE RETURN
 AIR SYSTEM OF ERU-01- SECTION 606.2.1 FBC M.
  
 39) M206.C: NOTE THE REQUIRED CLEARANCES FOR THE
 COMBUSTION AIR INTAKE DUCTS PER MANUFACTURER'S
 SPECIFICATIONS, AND PER SECTION 304.1 (8) FBC FG.
  
 40) M206.C: SHOW O/A SUPPLY TO THE RESIDENTIAL UNITS OR
 INDICATE NATURAL VENTILATION IN THE NOTES- SECTION 402
 FBC M.
  
 41) M206.C: PLEASE PLACE NOTES ON THE PLAN TO INDICATE
 THE WHAT TYPE OF HORIZONTAL 2-HR FIRE-RATED ENCLOSURES
 WILL BE INSTALLED FOR THE DRYER AND TOILET EXHAUST
 DUCTS AND INDICATE WHERE THE DETAILS ARE FOUND IN THE
 PLANS- SECTION 107.2.1 WPB.
  
 42) M206.C: THE REVISED PLAN SHOWS SPF-13 PRESSURIZING
 THE CORRIDOR BUT NOT THE STAIRWAY WHICH IS NOW SHOWN
 CLOSED OFF WITH DOORS- SECTION 909.6 FBC B AND 513.6
 FBC M.
  
 43) M207.A: THE VENTILATION CALCULATIONS SHOWN AT THE
 TOP OF THE PAGE ARE NOT IN COMPLIANCE WITH TABLE
 403.3.1.1 FBC M. PLEASE REVISE AND PROVIDE AIR BALANCE
 CALCULATIONS FOR ALL ROOMS AND SPACES USING EXHAUST
 VENTILATION SYSTEMS- SECTION 501.4 FBC M. A) INCLUDE
 THE AHU SERVING THE LAP POOL IN THE CALCULATIONS.
 PLEASE NOTE THAT THIS APPEARS TO BE A SYSTEM OF SUPPLY
 AND RETURN AIR, HOWEVER THE CALCULATION INDICATES
 O/A/EXHAUST. PLEASE CORRECT OR PROVIDE EXHAUST IN THE
 ROOM.
  
 44) M207.A POOL EQUIPMENT ROOM: A) PROVIDE A POOL
 EQUIPMENT SCHEDULE AND SUBMIT MANUFACTURER'S
 SPECIFICATIONS FOR THE POOL HEATERS AND DIRECT VENT
 EXHAUST AND INTAKE DUCTS- SECTION 301.3 FBC FG. B)
 PROVIDE A GAS PIPING PLAN AND ISOMETRIC DRAWING-
 SECTION 402.1 FBC FG. C) REFER TO SECTION 414.1.3 FBC B
 AND PROVIDE A LIST OF POOL TREATMENT CHEMICALS AND
 THEIR QUANTITIES TO BE USED AND STORED IN THE ROOM. D)
 INDICATE THE SEQUENCE OF OPERATION FOR EF 48 AND THE
 TYPE OF EXHAUST DUCTWORK TO BE INSTALLED- REFER TO
 SECTIONS 510.2- 510.9 FBC M. E) INDICATE THE REQUIRED
 CLEARANCES FOR THE EXHAUST OUTLET- SECTION 501.3.1 FBC
 M.36
  
 45) M207.A LAUNDRY: PLACE A NOTE INDICATING UNDER
 SEPARATE PERMIT AS WAS INDICATED IN THE RESPONSE
 NARRATIVE.
  
 46) M207.B: PER THE NOTE, THE KITCHENS ARE UNDER
 SEPARATE PERMIT, HOWEVER IT WILL BE HELPFUL TO SHOW THE
 PROPOSED LOCATIONS OF KITCHEN HOOD EXHAUST DUCT
 TERMINATIONS ON THE PLAN (THERE IS NO NOTE INDICATING A
 SCRUBBER IS TO BE USED PER THE RESPONSE NARRATIVE).
 PLEASE BE ADVISED THAT THE REQUIREMENT FOR KITCHEN
 EXHAUST MAKEUP AIR TEMPERATURE UNDER SECTION 508.1.1
 WILL BE ENFORCED UNDER THE SEPARATE PERMIT.
  
 47) M207.B: LABEL THE ELEVATOR RELIEF VENT- SECTION
 107.2.1 WPB.
  
 48) M208.A & B: THE RR-4 RETURN FROM THE TENNIS COURTS
 APPEARS TO BE CONNECTED TO TWO SUPPLY DIFFUSERS. WHICH
 SYSTEM(S) ARE THESE DUCTS CONNECTED TO?- SECTION
 107.2.1 WPB.
  
 49) M208.B HOTEL POOL EQUIPMENT ROOM: A) PROVIDE A POOL
 EQUIPMENT SCHEDULE AND SUBMIT MANUFACTURER'S
 SPECIFICATIONS FOR THE POOL HEATERS AND DIRECT VENT
 EXHAUST AND INTAKE DUCTS- SECTION 301.3 FBC FG. B)
 PROVIDE A GAS PIPING PLAN AND ISOMETRIC DRAWING-
 SECTION 402.1 FBC FG. C) REFER TO SECTION 414.1.3 FBC B
 AND PROVIDE A LIST OF POOL TREATMENT CHEMICALS AND
 THEIR QUANTITIES TO BE USED AND STORED IN THE ROOM. D)
 INDICATE THE SEQUENCE OF OPERATION FOR EF-52 AND THE
 TYPE OF EXHAUST DUCTWORK TO BE INSTALLED- REFER TO
 SECTIONS 510.2- 510.9 FBC M. E) INDICATE THE REQUIRED
 CLEARANCES FOR THE POOL ROOM EXHAUST OUTLET- SECTION
 501.3.1 FBC M, AND THE POOL HEATER INTAKE OPENINGS AND
 EXHAUST OUTLETS.
  
 50) M208.C: NO VENTILATION PROVIDED TO THE ELEVATOR
 LOBBY.
 HOTEL TOWER
  
 51) M209, 210, 211, 212: PROVIDE A DETAIL SHOWING THE
 FCU INSTALLATION IN THE CLOSET INCLUDING THE RETURN AIR
 SYSTEM, AND REQUIRED CLEARANCE AND ACCESS FOR SERVICE
 AND REPLACEMENT OF THE UNIT- SECTION 306.1 FBC M.
  
 52) M209-M211 TENNIS COURT SYSTEMS: PLEASE CORRECT THE
 REFERENCES TO PLAN SHEETS M.224 AND M.226 WHICH ARE NOT
 RELATED TO THE TENNIS COURT SYSTEMS- SECTION 107.2.1
 WPB.
  
 53) M209 & M210: THE DRYERS APPEAR TO BE REMOVED FROM
 THE HOTEL FLOOR PLANS. PLEASE REMOVE GENERAL NOTE #3
 CONCERNING THE MAKEUP AIR IN THE CLOSETS.
  
 54) M209, M210, M211, & M212: THE KITCHEN EXHAUST SHALL
 RUN INDEPENDENTLY AND NOT BE CONNECTED TO THE TOILET
 EXHAUST DUCT SYSTEM- SECTIONS 501.2 & 505.1 FBC M.
  
 OFFICE TOWER
  
 55) M.701 AND ALL OFFICE FLOOR PLAN SHEETS: PROVIDE
 DUCT SMOKE DETECTORS AT EACH FLOOR LEVEL OF THE ERU-03
 RETURN AIR RISER- SECTION 606.2.3 FBC M. PROVIDE DS
 SYMBOLS ON THE PLANS TO INDICATE THE LOCATIONS.
  
 56) M.218: THE MECHANICAL ROOM VENTILATION CALCULATIONS
 ARE NOT IN COMPLIANCE WITH SECTION 1105.6.3.1 FOR
 NORMAL CONDITIONS, AND SECTION 1105.6.3.2 FOR EMERGENCY
 CONDITIONS. PLEASE CORRECT THE CALCULATIONS AND PROVIDE
 A SEQUENCE OF OPERATION FOR EF-58.
  
 57) M.218 & M.603: PROVIDE THE MISSING PERFORMANCE DATA
 FOR THE COOLING TOWERS IN THE SCHEDULE.
  
 58) M.218: PROVIDE SITE SPECIFIC STRUCTURAL ENGINEERING
 FOR INSTALLATION OF THE COOLING TOWERS, CONDENSER
 UNITS, ROOFTOP AND ALL OTHER EXPOSED MECHANICAL
 EQUIPMENT AND APPLIANCES- SECTION 301.15 FBC M. PLEASE
 NOTE THE ENGINEERING MAY BE DEFERRED AND CAN BE NOTED
 AS SUCH ON THE PLAN SHEET.
  
 59) M.219: IT APPEARS THAT AN AC-4 AND AC-9 ARE TO BE
 INSTALLED INSIDE THE ELEVATOR HOISTWAYS WHICH IS
 PROHIBITED- SECTION 303.8 FBC M.
  
 60) THERE ARE NO COOLING AND HEATING CALCULATIONS FOR
 ERU-03 & OAU-1.
  
 RESIDENTIAL TOWER
  
 61) M.220: PROVIDE A DUCT SMOKE DETECTOR IN THE RETURN
 AIR SYSTEM OF AHU-12- SECTION 606.2.1 FBC M.
  
 62) M.222: CHANGE THE REFERENCE TO SHEET M.228 TO
 M.229- SECTION 107.2.1 WPB.
  
 63) M.222: PROVIDE CONSTRUCTION DETAILS FOR THE 2-HR
 FIRE-RATED ELEVATOR RELIEF DUCT ENCLOSURE- SECTION
 703.2.1 FBC B.
  
 64) M.227: PROVIDE SITE SPECIFIC STRUCTURAL ENGINEERING
 FOR INSTALLATION OF THE COOLING TOWERS, GENERATOR, OAU
 AND ROOFTOP DUCTWORK, CONDENSING UNITS, AND ALL OTHER
 MECHANICAL EQUIPMENT AND APPLIANCES- SECTION 301.15 FBC
 M. PLEASE NOTE THE ENGINEERING MAY BE DEFERRED AND CAN
 BE NOTED AS SUCH ON THE PLAN SHEET.
  
 65) M.228: PROVIDE SITE SPECIFIC STRUCTURAL ENGINEERING
 FOR INSTALLATION OF ROOFTOP CONDENSING UNITS, AND ALL
 OTHER EXPOSED MECHANICAL EQUIPMENT AND APPLIANCES-
 SECTION 301.15 FBC M. PLEASE NOTE THE ENGINEERING MAY
 BE DEFERRED AND CAN BE NOTED AS SUCH ON THE PLAN SHEET.
  
 66) M.228: IT APPEARS THAT AN AC-4 IS TO BE INSTALLED
 INSIDE THE ELEVATOR HOISTWAY WHICH IS PROHIBITED-
 SECTION 303.8 FBC M.
  
 67) M.229: LABEL THE MAIN RETURN AIR GRILL AND OPENING
 SIZE- SECTION 601.5 FBC M.
  
 68) M.229: INDICATE THE HEIGHT OF EF-A10 FROM THE
 FINISHED FLOOR- SEE SECTION 306.5 FBC M.
  
 69) M.229: PROVIDE A MECHANICAL ROOF PLAN FOR THE
 TENNIS COURT STRUCTURE WHICH SHOWS THE LOCATIONS OF THE
 CONDENSING UNITS, GRAVITY INTAKES AND EXHAUST FANS AS
 CALLED OUT ON M.229. A) PROVIDE ENGINEERING FOR ALL
 ROOFTOP MECHANICAL INSTALLATIONS- MAY BE DEFERRED WITH
 A NOTE ON THE PLAN. B) PROVIDE CLEARANCE DISTANCE
 MEASUREMENTS FOR ALL SERVICEABLE MECHANICAL EQUIPMENT
 TO ROOF EDGES- SEE SECTION 304.11 FBC M.
  
 70) M.259- M261 RESIDENTIAL UNITS: PLEASE PROVIDE
 DETAILS OR NOTES ON THE PLAN INDICATING COMPLIANCE WITH
 THE FOLLOWING ITEMS.
 A) IDENTIFY ALL ROOMS ON THE PLANS.
 B) PROVIDE A FRONT VIEW DRAWING OF THE AIR HANDLER IN
 THE CLOSET SHOWING REQUIRED CLEARANCES, CONDENSATE
 DISPOSAL DETAILS, SUPPLY PLENUM AND RETURN AIR
 CONNECTIONS.
 C) INDICATE DIFFUSER AND RETURN GRILL DIMENSIONS OR
 PROVIDE A SCHEDULE ON THE PLAN. PLEASE NOTE BALANCED
 RETURN AIR IS REQUIRED- TRANSFER DUCTS SHALL BE SIZED
 1-1/2 TIMES THE AREA OF THE SUPPLY DUCT TO THE ROOM,
 RETURN GRILLS SHALL BE SIZED AT 50 CFMS PER 100 SQ.
 INCHES, AND ALL AIR SUPPLIED TO MASTER BEDROOMS SHALL
 BE RETURNED- SEE SECTION 601.5 FBC M
 D) PROVIDE COOKING APPLIANCE SCHEDULES AND SUBMIT
 MANUFACTURER?S SPECIFICATIONS FOR EACH COOKING
 APPLIANCE. MAY BE DEFERRED AND NOTED AS SUCH ON THE
 PLANS.
 E) PROVIDE EXHAUST VENTILATION FOR THE KITCHENS AT A
 RATE OF 100 CFM INTERMITTENT OR 25 CFMS CONTINUOUS-
 TABLE 403.3.1.1.
 F) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE CLOTHES
 DRYERS AND THE DRYER EXHAUST BOOSTER FAN. PLEASE NOTE
 THAT THERE IS NO REQUIREMENT FOR BOOSTER FANS IN THE
 FBC-14 MECHANICAL CODE. DRYERS SHALL BE EXHAUSTED IN
 ACCORDANCE WITH MANUFACTURER?S SPECIFICATIONS AND
 INSTALLATION INSTRUCTIONS- SECTION 504.1 FBC M.
 G) PROVIDE A SUBMITTAL FOR THE X-VENT BOXES.
  
 71) M.501: PROVIDE DUCT CONNECTION, SUPPORT AND HANGING
 DETAILS PER THE CURRENT SMACNA HVAC DUCT CONSTRUCTION
 STANDARD- METAL AND FLEXIBLE 2005, AND SMACNA FIBROUS
 GLASS DUCT- 2010.
  
 72) PLEASE PROVIDE COMPLETE CONDENSATE DISPOSAL PLANS
 INCLUDING RISER DRAWINGS FOR THE TOWER AND PODIUM
 SYSTEMS- SECTION 307.2.1 FBC M.
  
 73) PLEASE LABEL ALL ELEVATOR EQUIPMENT ROOMS ON THE
 PLANS AND SHOW THE REQUIRED VENTILATION SYSTEMS-
 SECTION 3006.2 FBC B.
  
 ENERGY COMPLIANCE REPORT
  
 74) THE PROJECT IS BEING DESIGNED UNDER THE 2014
 FLORIDA BUILDING CODES. SUBMIT THE 2014 ENERGYGAUGE
 COMPLIANCE REPORT.
  
 75) M.218 & M.603: THE SYSTEM FULL LOAD AND IPLV
 COMPLIANCE DATA FOR THE CHILLERS IN THE SCHEDULE DOES
 NOT MATCH THE DATA IN THE ENERGY REPORT- SEE TABLE
 C403.2.3(7) FBC EC.
  
 76) NO COMPLIANCE DATA FOR OAU-1, THE WATER HEATERS,
 SERVICE WATER PIPING, AIR COOLED SPLIT SYSTEMS- AC-1-
 9, INDOOR POOL AHU-08, AND THE CAPACITIES FOR FCU?S
 2-18,
  
 77) M.603: THE TOTAL MBH LISTED IN THE SCHEDULE FOR
 AHU-12, 13, & 14 DOES NOT MATCH THE CAPACITIES LISTED
 IN THE REPORT.
  
 78) M.604: THE CAPACITY LISTED FOR FCU-01 IN THE
 SCHEDULE DOES NOT MATCH THE REPORT.
  
 79) M.604 VHP'S: A) MBH IN SCHEDULE FOR VHP- 2, 3 & 4
 DOESN'T MATCH DATA IN THE REPORT. B) PLEASE INDICATE
 THE NUMBER OF EACH VHP (1-7)) TO BE INSTALLED ON THE
 PROJECT.
  
 80) M.604 HHP'S: A) NO DATA IN THE REPORT FOR HHP-2, 5,
 6, 7, 8, & 9. B) PLEASE INDICATE THE NUMBER OF EACH HHP
 (1-9)) TO BE INSTALLED ON THE PROJECT.
  
 HEAT LOAD CALCULATIONS
  
 81) SHEET M.602: THE COOLING CAPACITIES (MBH) SHOWN IN
 THE AHU AND ERU SCHEDULE ARE EITHER UNDER OR OVER THE
 HEAT LOADS SHOWN IN CALCULATIONS- SECTION C403.2.2 FBC
 EC.
  
 A) AHU-01 OFFICE/LOBBY: SCHEDULE- 207 MBH, CALCS- 436
 MBH.
  
 B) AHU-02 LOBBY/CAFE: SCHEDULE- 158 MBH, CALCS- 177
 MBH.
  
 C) AHU-03 HOTEL LOBBY: SCHEDULE- 275 MBH, CALCS- 320
 MBH
  
 D) AHU-04 RETAIL/RESTAURANT: SCHEDULE- 903 MBH, CALCS-
 773 MBH
  
 E) AHU-05 DAYCARE: SCHEDULE- 126 MBH, CALCS- 193 MBH
  
 F) AHU-07A & B: SCHEDULE 1,417 MBH, CALCS- 1,650 MBH.
  
 G) AHU-08 INDOOR POOL: SCHEDULE- 359 MBH, CALCS- 251
 MBH.
  
 H) AHU-09 FITNESS/SPA: SCHEDULE- 265 MBH, CALCS- 667
 MBH.
  
 I) AHU-10A & B TENNIS COURT ASSEMBLY: SCHEDULE- 1,387
 MBH, CALCS- 1,552 MBH. PLEASE NOTE THAT THERE IS
 ANOTHER CALCULATION FOR THE ?TENNIS COURT? INDICATING
 890 MBH. PLEASE CLARIFY.
  
 J) AHU-12 RES/LOUNGE: SCHEDULE- 404 MBH, CALCS- 357
 MBH.
  
 K) AHU-13 RES LOBBY: SCHEDULE- 453 MBH, CALCS
  
 L) ERU-1: SCHEDULE- 761 MBH, CALCS 911 MBH.
  
 M) THERE ARE NO COOLING AND HEATING CALCULATIONS FOR
 ERU-03 & OAU-1.
  
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2019-04-08 Cont ID  
Sent By ccole Date 2019-04-08 Time 17:50 Rev Time 0.00
Received By ccole Date 2019-04-01 Time 14:17 Sent To  
Notes
2019-04-08 17:58:151ST REVIEW FBC-2017 MECHANICAL
 PERMIT #18100540
 550 N QUADRILLE BLVD
 4/2/19
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
 PLAN REVIEW RESULTS: DENIED.
  
 THE MECHANICAL PLANS HAVE FAILED FOR THE DEFICIENCIES
 AND OMISSIONS LISTED BELOW. PLEASE REVIEW ALL COMMENTS,
 INCLUDING THOSE LISTED FOR ADVISORY PURPOSES, AND
 RESUBMIT CORRECTED PLANS AND REQUIRED DOCUMENTS. WHEN
 RESUBMITTING, PLEASE PROVIDE A RESPONSE LETTER
 ADDRESSING EACH ITEM ALONG WITH THE CITY RE-SUBMITTAL
 FORM.
 PRIOR TO MECHANICAL PERMIT ISSUANCE, THE GENERAL
 CONTRACTOR AND MECHANICAL SUB-CONTRACTOR FOR THE
 PROJECT ARE REQUESTED TO ATTEND A MEETING AT THE WPB
 BUILDING DEPARTMENT WITH THE STAFF- CHIEF MECHANICAL
 INSPECTOR, PLANS EXAMINER, AND OTHER OFFICIALS- TO
 DISCUSS TIMELINES AND GUIDELINES FOR INSPECTIONS AND
 THE DOCUMENT SUBMITTAL PROCESS . FURTHER INFORMATION
 WILL FOLLOW ONCE ALL PLANS ARE APPROVED.
  
 1) THE FOLLOWING LIST OF DOCUMENTS WERE NOT SUBMITTED
 BUT ARE REQUIRED TO PERFORM A COMPLETE MECHANICAL
 REVIEW FOR THE PROJECT.
 1A) SMOKE CONTROL RATIONAL ANALYSIS- SECTION 513.4 FBC
 M: A RATIONAL ANALYSIS SUPPORTING THE TYPES OF SMOKE
 CONTROL SYSTEMS TO BE EMPLOYED, THEIR METHODS OF
 OPERATION, THE SYSTEMS SUPPORTING THEM AND THE METHODS
 OF CONSTRUCTION TO BE UTILIZED SHALL ACCOMPANY THE
 SUBMITTED CONSTRUCTION DOCUMENTS AND SHALL INCLUDE, BUT
 NOT BE LIMITED TO, THE ITEMS INDICATED IN SECTIONS
 513.4.1 THROUGH 513.4.7.
 513.4.1 STACK EFFECT: THE SYSTEM SHALL BE DESIGNED SUCH
 THAT THE MAXIMUM PROBABLE NORMAL OR REVERSE STACK
 EFFECTS WILL NOT ADVERSELY INTERFERE WITH THE SYSTEM'S
 CAPABILITIES. IN DETERMINING THE MAXIMUM PROBABLE STACK
 EFFECTS, ALTITUDE, ELEVATION, WEATHER HISTORY AND
 INTERIOR TEMPERATURES SHALL BE USED.
 513.4.2 TEMPERATURE EFFECT OF FIRE: BUOYANCY AND
 EXPANSION CAUSED BY THE DESIGN FIRE IN ACCORDANCE WITH
 SECTION 513.9 SHALL BE ANALYZED. THE SYSTEM SHALL BE
 DESIGNED SUCH THAT THESE EFFECTS DO NOT ADVERSELY
 INTERFERE WITH ITS CAPABILITIES.
 513.4.3 WIND EFFECT: THE DESIGN SHALL CONSIDER THE
 ADVERSE EFFECTS OF WIND. SUCH CONSIDERATION SHALL BE
 CONSISTENT WITH THE WIND-LOADING PROVISIONS OF THE
 FLORIDA BUILDING CODE, BUILDING.
 513.4.4 HVAC SYSTEMS: THE DESIGN SHALL CONSIDER THE
 EFFECTS OF THE HEATING, VENTILATING AND
 AIR-CONDITIONING (HVAC) SYSTEMS ON BOTH SMOKE AND FIRE
 TRANSPORT. THE ANALYSIS SHALL INCLUDE ALL PERMUTATIONS
 OF SYSTEMS STATUS. THE DESIGN SHALL CONSIDER THE
 EFFECTS OF FIRE ON THE HVAC SYSTEMS.
 513.4.5 CLIMATE: THE DESIGN SHALL CONSIDER THE EFFECTS
 OF LOW TEMPERATURES ON SYSTEMS, PROPERTY AND OCCUPANTS.
 AIR INLETS AND EXHAUSTS SHALL BE LOCATED SO AS TO
 PREVENT SNOW OR ICE BLOCKAGE.
 513.4.6 DURATION OF OPERATION: ALL PORTIONS OF ACTIVE
 OR ENGINEERED SMOKE CONTROL SYSTEMS SHALL BE CAPABLE OF
 CONTINUED OPERATION AFTER DETECTION OF THE FIRE EVENT
 FOR A PERIOD OF NOT LESS THAN EITHER 20 MINUTES OR 1.5
 TIMES THE CALCULATED EGRESS TIME, WHICHEVER IS GREATER.
 513.4.7 SMOKE CONTROL SYSTEM INTERACTION: THE DESIGN
 SHALL CONSIDER THE INTERACTION EFFECTS OF THE OPERATION
 OF MULTIPLE SMOKE CONTROL SYSTEMS FOR ALL DESIGN
 SCENARIOS.
 THE SMOKE ANALYSIS SHALL CONTAIN A PROJECT DESCRIPTION
 OF SMOKE CONTROL SYSTEMS, SPRINKLER AND STANDPIPE
 SYSTEMS, FIRE ALARM SYSTEMS, SHAFT VENTING, AND CONTROL
 SYSTEMS. INCLUDED IN THE ANALYSIS SHALL BE SPECIAL
 INSPECTION AND TEST REQUIREMENTS, TESTING PROCEDURES,
 AND FINAL COMMISSIONING REQUIREMENTS FOR THE SYSTEMS.
 IMPORTANT NOTE: ACCEPTANCE TESTING OF THE PROJECT'S
 SMOKE CONTROL SYSTEMS SHALL BE COMPLETED UNDER NORMAL
 AND EMERGENCY POWER. PLEASE PROVIDE A DESCRIPTION OF
 THE EMERGENCY PROCEDURE THAT INCLUDES BOTH EMERGENCY
 GENERATORS AND HOW THE FIRE ALARM AND LIFE SAFETY
 SYSTEMS IN THE TWO TOWERS AND PODIUM WILL COORDINATE
 AND INTERACT TOGETHER.
  
 1B) AC COOLING AND HEATING CALCULATIONS- SECTION
 C403.2.1 FBC EC: DESIGN LOADS ASSOCIATED WITH HEATING,
 VENTILATING AND AIR CONDITIONING OF THE BUILDING SHALL
 BE DETERMINED IN ACCORDANCE WITH ANSI/ASHRAE/ACCA
 STANDARD 183 OR ACCA MANUAL N OR BY AN APPROVED
 EQUIVALENT COMPUTATIONAL PROCEDURE USING THE DESIGN
 PARAMETERS SPECIFIED IN CHAPTER 3. HEATING AND COOLING
 LOADS SHALL BE ADJUSTED TO ACCOUNT FOR LOAD REDUCTIONS
 THAT ARE ACHIEVED WHERE ENERGY RECOVERY SYSTEMS ARE
 UTILIZED IN THE HVAC SYSTEM IN ACCORDANCE WITH THE
 ASHRAE HVAC SYSTEMS AND EQUIPMENT HAND-BOOK BY AN
 APPROVED EQUIVALENT COMPUTATIONAL PROCEDURE. DESIGN
 LOADS SHALL BE ATTACHED TO THE CODE COMPLIANCE FORM
 SUBMITTED TO THE BUILDING DEPARTMENT WHEN THE BUILDING
 IS PERMITTED OR, IN THE EVENT THE MECHANICAL PERMIT IS
 OBTAINED AT A LATER TIME, THE SIZING CALCULATION SHALL
 BE SUBMITTED WITH THE APPLICATION FOR THE MECHANICAL
 PERMIT.
  
 1C) ENERGY EFFICIENCY COMPLIANCE REPORT- SECTION C401.2
 FBC EC.
 COMMERCIAL BUILDINGS SHALL COMPLY WITH ONE OF THE
 FOLLOWING:\]
 1.THE REQUIREMENTS OF ANSI/ASHRAE/IESNA 90.1, EXCLUDING
 SECTION 9.4.1.1(G) OF THE STANDARD.
 2.THE REQUIREMENTS OF SECTIONS C402 THROUGH C405. IN
 ADDITION, COMMERCIAL BUILDINGS SHALL COMPLY WITH
 SECTION C406 AND TENANT SPACES SHALL COMPLY WITH
 SECTION C406.1.1.
 3.THE REQUIREMENTS OF SECTIONS C402.5, C403.2, C404,
 C405.2, C405.3, C405.5, C405.6 AND C407. THE BUILDING
 ENERGY COST SHALL BE EQUAL TO OR LESS THAN 85 PERCENT
 OF THE STANDARD REFERENCE DESIGN BUILDING.
 PLEASE REVIEW SECTION C101.5.1 FBC EC: THE FLORIDA
 BUILDING COMMISSION SHALL APPROVE SPECIFIC COMPUTER
 SOFTWARE. THE CODE OFFICIAL SHALL BE PERMITTED TO
 APPROVE WORKSHEETS, COMPLIANCE MANUALS AND OTHER
 SIMILAR MATERIALS THAT MEET THE INTENT OF THIS CODE.
  
 1D) COMMISSIONING PLAN: COMMISSIONING OF THE MECHANICAL
 SYSTEMS AND SERVICE WATER HEATING SYSTEMS IS REQUIRED
 PER SECTION C408.2 FBC EC. COMMISSIONING PLAN. "PRIOR
 TO THE FINAL MECHANICAL AND PLUMBING INSPECTIONS, THE
 LICENSED DESIGN PROFESSIONAL, ELECTRICAL ENGINEER,
 MECHANICAL ENGINEER, OR APPROVED AGENCY SHALL PROVIDE
 EVIDENCE OF MECHANICAL SYSTEMS COMMISSIONING AND
 COMPLETION IN ACCORDANCE WITH THE PROVISIONS OF THIS
 SECTION".
 A COMMISSIONING PLAN SHALL BE DEVELOPED BY A LICENSED
 DESIGN PROFESSIONAL, ELECTRICAL ENGINEER, MECHANICAL
 ENGINEER OR APPROVED AGENCY AND SHALL INCLUDE THE
 FOLLOWING ITEMS:
 1. A NARRATIVE DESCRIPTION OF THE ACTIVITIES THAT WILL
 BE ACCOMPLISHED DURING EACH PHASE OF COMMISSIONING,
 INCLUDING THE PERSONNEL INTENDED TO ACCOMPLISH EACH OF
 THE ACTIVITIES.
 2. A LISTING OF THE SPECIFIC EQUIPMENT, APPLIANCES OR
 SYSTEMS TO BE TESTED AND A DESCRIPTION OF THE TESTS TO
 BE PERFORMED.
 3. FUNCTIONS TO BE TESTED INCLUDING, BUT NOT LIMITED
 TO, CALIBRATIONS AND ECONOMIZER CONTROLS.
 4. CONDITIONS UNDER WHICH THE TEST WILL BE PERFORMED.
 TESTING SHALL AFFIRM WINTER AND SUMMER DESIGN
 CONDITIONS AND FULL OUTSIDE AIR CONDITIONS.
 5. MEASURABLE CRITERIA FOR PERFORMANCE'
  
 2) SUBMITTALS: REQUIRED SUBMITTALS LISTED BELOW SHALL
 HAVE SHOP DRAWING STAMPS BY THE EOR AND BE IN THE FIELD
 AT TIME OF INSPECTION.
 A) SMOKE CONTROL FANS INCLUDING SMOKE EXHAUST FANS, AND
 STAIRWELL AND ELEVATOR PRESSURIZATION FANS.
 B) FIRE DAMPERS AND FIRE/SMOKE DAMPERS.
 C) MOTORIZED AND GRAVITY DAMPERS
 D) DUCT SMOKE DETECTORS
 E) LOUVERS FOR EXHAUST AND OUTSIDE AIR INTAKES
 INCLUDING MANUFACTURER'S SPECIFICATIONS AND FL. PRODUCT
 APPROVALS AND/OR MIAMI-DADE NOA'S
 F) AC STAND NOA'S OR FL. PRODUCT APPROVALS
 G) C0, N02, & CO2 SENSORS, AND REFRIGERANT LEAK
 DETECTORS.
 H) COOLING TOWERS AND CHILLERS
 I) FACTORY BUILT DUCTWORK
 J) DUCT FIRE WRAPPING
 K) CLOTHES DRYERS
 L) TOILET AND DRYER EXHAUST WALL CAPS
 M) COOKING APPLIANCES
 N) TEST AND BALANCE REPORTS
 O) SMOKE CONTROL TEST REPORTS.
  
 2A) SUBMITTALS TO BE PROVIDED TO THE BUILDING
 DEPARTMENT FOR REVIEW.
 A) SIGNED AND SEALED STRUCTURAL ENGINEERING FOR
 INSTALLATION OF ALL EXTERIOR MECHANICAL EQUIPMENT AND
 APPLIANCES. ALL DELEGATED ENGINEERING SHALL BEAR THE
 SHOP DRAWING STAMP OF THE STRUCTURAL ENGINEER RECORD.
 B) GENERATORS AND FUEL TANKS AND ALL ASSOCIATED
 EQUIPMENT, VENT FLUES, AND FUEL OIL PIPING.
 C) BOILERS AND WATER HEATERS INCLUDING COMBUSTION AIR
 DUCTS AND VENT FLUES.
 D) COMMISSIONING REPORTS
 PLEASE NOTE: ALL SUBMITTALS AND SHOP DRAWINGS SHALL
 BEAR THE APPROVAL STAMP AND SIGNATURE OF THE DESIGN
 PROFESSIONAL OF RECORD. ALL REQUIRED SUBMITTALS MAY BE
 DEFERRED IN ACCORDANCE WITH SECTION 107.3.4.1 WPB. IT
 WILL BE HELPFUL TO UPLOAD A MASTER LIST OF DEFERRED
 SUBMITTALS IN DOCUMENT FORM, OR IN THE FORM OF NOTES ON
 THE MECHANICAL PLANS.
 DEFERRED SUBMITTALS: FOR THE PURPOSES OF THIS SECTION,
 DEFERRED SUBMITTALS ARE DEFINED AS THOSE PORTIONS OF
 THE DESIGN THAT ARE NOT SUBMITTED AT THE TIME OF THE
 APPLICATION AND THAT ARE TO BE SUBMITTED TO THE
 BUILDING OFFICIAL WITHIN A SPECIFIED PERIOD. DEFERRAL
 OF ANY SUBMITTAL ITEMS SHALL HAVE THE PRIOR APPROVAL OF
 THE BUILDING OFFICIAL. THE REGISTERED DESIGN
 PROFESSIONAL IN RESPONSIBLE CHARGE SHALL LIST THE
 DEFERRED SUBMITTALS ON THE CONSTRUCTION DOCUMENTS FOR
 REVIEW BY THE BUILDING OFFICIAL.
 DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE
 SUBMITTED TO THE REGISTERED DESIGN PROFESSIONAL IN
 RESPONSIBLE CHARGE WHO SHALL REVIEW THEM AND FORWARD
 THEM TO THE BUILDING OFFICIAL WITH A NOTATION
 INDICATING THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE
 BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO
 THE DESIGN OF THE BUILDING.
  
 3) SEPARATE PERMITS: SEPARATE PERMITS ARE REQUIRED FOR
 COMMERCIAL KITCHEN EXHAUST HOODS, FIRE SUPPRESSION
 SYSTEMS, AND WALK-IN COOLERS AND FREEZERS. PLEASE PLACE
 NOTES ON THE MAIN BUILDING PLANS ACCORDINGLY AND
 PROVIDE THE FOLLOWING INFORMATION FOR THE KITCHEN
 HOODS.
 A) LOCATIONS OF HOODS, EXHAUST AND MAKEUP AIR FANS AND
 DUCTWORK, EXHAUST AND MAKEUP AIR OUTLETS AND INLETS,
 MUA UNITS IF PROVIDED.
 B) AIR BALANCE CALCULATIONS.
 C) ADVISORY: REFER TO SECTION 508.1.1 FBC M. MAKEUP AIR
 TEMPERATURE: THE TEMPERATURE DIFFERENTIAL BETWEEN
 MAKEUP AIR AND THE AIR IN THE CONDITIONED SPACE SHALL
 NOT EXCEED 10 DEGREES F (6 DEGREES C) EXCEPT WHERE THE
 ADDED HEATING AND COOLING LOADS OF THE MAKEUP AIR DO
 NOT EXCEED THE CAPACITY OF THE HVAC SYSTEM.
  
 4) PROVIDE VENTILATION CALCULATIONS AND A SCHEDULE THAT
 INDICATES THE REQUIRED AND PROVIDED OUTDOOR AND EXHAUST
 AIRFLOW RATES. THE O/A CFMS LISTED IN THE 100% O/A-ERU
 AND AHU EQUIPMENT SCHEDULES SHALL CORRELATE WITH THE
 CALCULATIONS. PLEASE ALSO PROVIDE AIR BALANCE
 CALCULATIONS ? TABLE 403.3.1.1 FBC M & SECTION C403.2.7
 FBC EC.
 5) PROVIDE CALCULATIONS FOR THE POST FIRE SMOKE PURGE
 SYSTEM AND FANS- SEE SECTION 403.4.7 FBC B.
 6) PARKING GARAGE EXHAUST- PODIUM LEVELS 1- 6 (SHEETS
 M201, 202, 203, 204, 205, 206) PROVIDE CALCULATIONS-
 TABLE 403.3.1.1 AND SECTION 404.1 FBC M. A) INDICATE
 THE SEQUENCE OF OPERATION FOR THE EXHAUST SYSTEM-
 SECTION 404.2 FBC M. ADVISORY: PLEASE PROVIDE NOTES AND
 DETAILS ON THE PLANS THAT ARE CONSISTENT WITH THE
 SEQUENCING NOTES ON SHEET M.813. B) SUBMIT
 MANUFACTURER'S SPECIFICATIONS FOR THE CO AND NO2
 SENSORS (MAY BE DEFERRED PER COMMENT #2). C) REFER TO
 SECTION C403.2.6.2 FBC EC FOR ENERGY COMPLIANCE
 REQUIREMENTS.
  
 PODIUM
 7) SHEETS M.201-M.208 A, B, C, & D QUADRANTS: DUCT
 SMOKE DETECTORS ARE REQUIRED IN THE SUPPLY SYSTEMS OF
 THE AHU'S PER SECTION 606.2.1 FBC M. PLEASE PROVIDE DS
 SYMBOLS ON THE PLANS AND RISER DRAWINGS TO SHOW THE
 LOCATIONS.
 8) M.201-M.208 A, B, C, & D QUADRANTS: DUCT SMOKE
 DETECTORS ARE REQUIRED IN THE SUPPLY SYSTEMS OF THE
 100% O/A ERU SYSTEMS, AND AT EACH STORY OF THE RA/EA
 RISER- SECTION 606.2.3. PLEASE PROVIDE DS SYMBOLS ON
 THE PLANS AND RISER DRAWINGS TO SHOW THE LOCATIONS.
 9) M.201-M.208 A, B, C, & D QUADRANTS: SHOW CLEARANCE
 DISTANCE MEASUREMENTS FOR O/A INTAKES AND EXHAUST
 OUTLETS IN COMPLIANCE WITH SECTIONS 401.4 AND 501.3.1
 FBC M OR PROVIDE GENERAL KEYNOTES.
 10) M.201-M.208 A, B, C, & D QUADRANTS: REFER TO
 SECTION 306.1 AND VERIFY ACCESS IS PROVIDED FOR AC AND
 FAN UNITS LOCATED ABOVE HARD CEILING. SHOW AN ACCESS
 PANEL WITH DIMENSIONS ON THE DRAWINGS WHERE REQUIRED-
 SECTION 306.1 FBC M.1
 11) M.201-M.208 A, B, C, & D QUADRANTS: PLACE NOTES TO
 INDICATE LOCATIONS OF ABOVE CEILING PLENUMS AND NO
 COMBUSTIBLE MATERIALS PERMITTED.
 12) SHEETS M.201-M.208 A, B, C, & D QUADRANTS: BRANCH
 AND FLEX DUCT SIZES NOT SHOWN- SECTION 603.1 FBC M.
 13) M.201- M.208 A, B, C, D QUADRANTS WHERE APPLICABLE:
 FIRE DAMPERS MISSING FOR THE O/A BRANCH DUCTS
 PENETRATING THE FIRE-RATED CORRIDOR/SUITE, AND
 CORRIDOR/RESIDENTIAL UNIT WALLS- SECTION 607.5.3 FBC M.
 14) M.201- M.208 A, B, C, D QUADRANTS WHERE APPLICABLE:
 PLACE NOTES TO INDICATE NO COMBUSTIBLE MATERIALS
 PERMITTED IN THE VHP CLOSETS INCLUDING THE DOORS-
 SECTION 602.2.1 FBC M. IT APPEARS THE DOORS WILL BE
 LOUVERED TO ALLOW RETURN AIR TO THE HEAT PUMPS,
 OTHERWISE INDICATE MEANS OF RETURN AIR- SECTION 601.6
 FBC M.
 15) M.201- M.208 A, B, C, D: AUTOMATICALLY OPERATING
 SHUTOFF DAMPERS ARE REQUIRED FOR THE O/A DUCTS SERVING
 THE SUITES AND THE UNITS- SECTION C403.2.4.3 FBC EC.
 16) M.201A: AN AUTOMATIC SHUTOFF DAMPER IS REQUIRED FOR
 THE O/A SUPPLY TO AHU-5- SECTION C403.2.4.3 FBC EC
 17) SHEET ALS1.101 & M.201B: FIRE DAMPERS MISSING FOR
 TOILET EXHAUST DUCT PENETRATING OFFICE/LOBBY &
 VALET/LOBBY WALLS, & 48X20 EXHAUST DUCT PENETRATING
 MENS WC/VALET WALL- SECTION 607.5.2 FBC M.
 18) M.201B: IDENTIFY THE AC SYSTEM CONNECTED TO THE
 SUPPLY AND RETURN DROPS IN THE OFFICE/LOBBY ROOM-
 PROVIDE A NOTE ON THE PLAN- SECTION 107.2.1 WPB. A)
 IDENTIFY WITH A NOTE THE SYSTEM CONNECTED TO THE 40X20
 RETURN DUCT- SECTION 107.2.1 WPB. B) FIRE DAMPERS
 MISSING FOR THE 48X20 EXHAUST DUCT PENETRATING
 FIRE-RATED WALLS AT THE FIRE LOBBY, RECEIVING ROOM, AND
 MENS WC. C) FIRE DAMPER MISSING FOR THE 6X6 SUPPLY
 PENETRATING FIRE-RATED WALL AT THE FIRE LOBBY.
 19) M.201C: LABEL THE SYSTEM CONNECTED TO THE 60X24
 DROPS IN THE SCREENING ROOM- SECTION 107.2.1 WPB.
 20) ALS1.101 & M.201C: THERE ARE NUMEROUS FIRE DAMPERS
 MISSING FOR SUPPLY, RETURN, AND EXHAUST DUCTS RUNNING
 THROUGH THE FIRE-RATED WALLS AT THE TRASH ROOM, OFFICE,
 RESIDENT?S LOUNGE, ETC.- SECTION 607.5.2 FBC M. MANY OF
 THESE ARE BRANCHING OFF THE TWO MAIN 60X24 DUCTS.
 21) M.201C: SHOW THE LOCATION OF MAU-01.
 22) M.201C: SUBMIT MANUFACTURER'S SPECIFICATIONS AND UL
 CERTIFICATE FOR THE 2000-GALLON FUEL TANK.
 23) M.201C: VENTILATION IS REQUIRED FOR THE FUEL TANK
 ROOM AND IT CANNOT BE ACHIEVED NATURALLY BECAUSE OF THE
 ROOM LOCATION. REFER TO SECTION 24.10.2 NFPA 30 AND
 PROVIDE A MECHANICAL VENTILATION SYSTEM THAT INCLUDES
 CALCULATIONS AND SPECIFICATIONS FOR EXHAUST AND MAKEUP
 AIR. A) PROVIDE DETAILS AND SPECIFICATIONS FOR NORM AND
 EMERGENCY RELIEF VENTING OF THE TANK, INCLUDING VENT
 PIPING RUNS AND TERMINATION LOCATIONS AT THE EXTERIOR
 OF THE BUILDING- SECTION 24.13 NFPA 30.
 24) THE EXHAUST SYSTEM FOR THE FIRE PUMP ROOM IS
 INCOMPLETE- PLEASE PROVIDE THE TYPE AND SIZE OF EXHAUST
 DUCT, LOCATION OF EXHAUST FAN, FAN EQUIPMENT SCHEDULE,
 EXHAUST CALCULATIONS AND SEQUENCE OF OPERATION, AND
 SOURCE OF MAKEUP AIR.
 25) M.201D: FIRE DAMPERS MISSING FOR THE DUCTS
 PENETRATING THE FIRE-RATED WALLS AT THE SERVICE
 CORRIDOR AND AHU LOBBY ROOM- SECTION 607.5.2 FBC M.
 26) M202B: THE EXHAUST FROM EF-A01 & EF-A02 SHALL
 DISCHARGE TO THE OUTDOORS AND NOT INTO THE ENCLOSED
 GARAGE- SECTION 501.3 FBC M.
 27) M.202B: DUCTWORK IN THE OPEN AREA IS INCOMPLETE- NO
 DUCT SIZES, AIRFLOWS, SYSTEM IDENTIFICATION ETC.-
 SECTION 107.2.1 WPB.
 28) M.202B: PROVIDE NOTES AT AHU-03 TO INDICATE WHICH
 AREA IS BEING CONDITIONED BY THE SYSTEM, AND HOW O/A IS
 BEING PROVIDED AND AUTOMATICALLY CONTROLLED- SECTION
 C404.2.4.3 FBC EC.
 29) M.202B: FIRE DAMPER MISSING FOR THE 8X8 SUPPLY DUCT
 PENETRATING FIRE-RATED WALL AT THE FIRE LOBBY.
 30) M.202C: PROVIDE A TERMINATION CAP FOR THE PFP SMOKE
 PURGE DUCT, AND INDICATE MINIMUM 10' CLEARANCE TO THE
 O/A INTAKES LOCATED IN PROXIMITY OF THE OUTLET- SECTION
 501.3.1 FBC M.
 31) M.202C: AUTOMATIC SHUTOFF DAMPERS ARE REQUIRED FOR
 THE O/A SUPPLY DUCTS TO AHU-5 AND SPF-01- SECTION
 C403.2.4.3 FBC EC.
 32) M.202C: IDENTIFY THE SOURCE OF THE O/A DUCT TRUCK
 SUPPLYING THE VERTICAL HEAT PUMPS (VHP) IN THE UNITS
 AND PROVIDE AUTOMATIC SHUTOFF DAMPERS AT EACH SUPPLY-
 SECTION 107.2.1 WPB AND SECTION C403.2.4.3 FBC EC.
 33) M.202C: THE 22X22 SPF-01 INTAKE DUCT SHALL BE
 COMPLETELY ENCLOSED IN A FIRE-RATED HORIZONTAL ASSEMBLY
 AS REQUIRED BY SECTION 909.20.6.1 FBC B. SUBMIT
 MANUFACTURER?S SPECIFICATIONS FOR THE 2-HR FIRE
 WRAPPING (MAY BE DEFERRED SUBMITTAL). A FIRE/SMOKE
 DAMPER IS REQUIRED AT SG-3 PENETRATION INTO STAIR-1 -
 SECTION 1023.5 FBC B.
 34) M.202D: PROVIDE NOTES AT AHU-04 TO INDICATE WHICH
 AREA IS BEING CONDITIONED BY THE SYSTEM, AND HOW O/A IS
 BEING PROVIDED AND AUTOMATICALLY CONTROLLED- SECTION
 C404.2.4.3 FBC EC.
 35) M.202D: FIRE DAMPERS MISSING FOR THE O/A BRANCH
 DUCTS PENETRATING THE FIRE-RATED CORRIDOR WALLS.
 36) M.203B: IDENTIFY THE SOURCE OF THE O/A DUCT TRUCK
 SUPPLYING THE FAN COIL UNITS (FCU) IN THE UNITS AND
 PROVIDE AUTOMATIC SHUTOFF DAMPERS FOR THE SUPPLY AT
 EACH UNIT- SECTION 107.2.1 WPB AND SECTION C403.2.4.3
 FBC EC.
 37) M.203B: INDICATE WHAT AIR IS BEING RETURNED VIA THE
 54X24 RA DUCT IN THE SHAFT. THE PLAN SHOWS NO DUCTS
 CONNECTING TO IT.
 38) M.203B: FIRE DAMPER MISSING FOR THE 6X6 SUPPLY DUCT
 PENETRATING FIRE-RATED WALL AT THE FIRE LOBBY.
 39) M.203C: THE SPF-03 INTAKE DUCT SHALL BE COMPLETELY
 ENCLOSED IN A FIRE-RATED HORIZONTAL ASSEMBLY AS
 REQUIRED BY SECTION 909.20.6.1 FBC B. A FIRE/SMOKE
 DAMPER IS REQUIRED AT SG-2 PENETRATION INTO STAIR-2 -
 SECTION 1023.5 FBC B.
 40) M.203C & D: IDENTIFY THE SOURCE OF THE O/A DUCT
 TRUCK SUPPLYING THE VERTICAL HEAT PUMPS (VHP) IN THE
 UNITS AND PROVIDE AUTOMATIC SHUTOFF DAMPERS FOR THE
 SUPPLY AT EACH UNIT- SECTION 107.2.1 WPB AND SECTION
 C403.2.4.3 FBC EC.
 41) M.203C & D: FIRE DAMPERS MISSING FOR THE O/A BRANCH
 DUCTS PENETRATING THE FIRE-RATED CORRIDOR WALLS-
 SECTION 607.5.3 FBC M.
 42) M.203C & D: PLACE NOTES TO INDICATE NO COMBUSTIBLE
 MATERIALS PERMITTED IN THE VHP CLOSETS INCLUDING THE
 DOORS- SECTION 602.2.1 FBC M. IT APPEARS THE DOORS WILL
 BE LOUVERED TO ALLOW RETURN AIR TO THE HEAT PUMPS.,
 OTHERWISE INDICATE MEANS OF RETURN AIR- SECTION 601.6
 FBC M.
 43) M.204B: FIRE DAMPERS MISSING FOR THE O/A BRANCH
 DUCTS PENETRATING THE FIRE-RATED CORRIDOR/SUITE WALLS-
 SECTION 607.5.3 FBC M.
 44) M.204B: INDICATE WHAT AIR IS BEING RETURNED VIA THE
 54X24 RA DUCT IN THE SHAFT. THE PLAN SHOWS NO DUCTS
 CONNECTING TO IT.
 45) M.204B: FIRE DAMPER MISSING FOR THE 6X6 SUPPLY DUCT
 PENETRATING FIRE-RATED WALL AT THE FIRE LOBBY.
 46) M.204C & D: IDENTIFY THE SOURCE OF THE O/A DUCT
 TRUCK SUPPLYING THE VERTICAL HEAT PUMPS (VHP) IN THE
 UNITS AND PROVIDE AUTOMATIC SHUTOFF DAMPERS FOR THE
 SUPPLY AT EACH UNIT- SECTION 107.2.1 WPB AND SECTION
 C403.2.4.3 FBC EC.
 47) M.204C & D: FIRE DAMPERS MISSING FOR THE O/A BRANCH
 DUCTS PENETRATING THE FIRE-RATED CORRIDOR WALLS-
 SECTION 607.5.3 FBC M.
 48) M.205B: SHOW THE O/A AND EXHAUST DUCT RUNS AND
 INLET AND OUTLET LOCATIONS FOR ERU-01- SECTION 107.2.1
 WPB AND SECTIONS 401.4 & 501.3.1 FBC M.
 49) M.205B: FIRE DAMPER MISSING FOR THE 6X6 SUPPLY DUCT
 PENETRATING FIRE-RATED WALL AT THE FIRE LOBBY.
 50) M.205C: SHOW THE O/A AND EXHAUST DUCT RUNS AND
 INLET AND OUTLET LOCATIONS FOR ERU-02- SECTION 107.2.1
 WPB AND SECTIONS 401.4 & 501.3.1 FBC M.
 51) M.205C & D: FIRE DAMPERS MISSING FOR THE O/A BRANCH
 DUCTS PENETRATING THE FIRE-RATED CORRIDOR WALLS-
 SECTION 607.5.3 FBC M.
 52) M.205C & D: IDENTIFY THE SOURCE OF THE O/A DUCT
 TRUCK SUPPLYING THE VERTICAL HEAT PUMPS (VHP) IN THE
 UNITS AND PROVIDE AUTOMATIC SHUTOFF DAMPERS FOR THE
 SUPPLY AT EACH UNIT- SECTION 107.2.1 WPB AND SECTION
 C403.2.4.3 FBC EC.
 53) M.206A: PROVIDE AN ENLARGED DRAWING OF THE EPSS
 (EMERGENCY GENERATOR) ROOM SHOWING THE LOCATIONS OF THE
 GENERATOR AND FUEL TANK, FUEL OIL PIPE AND EXHAUST PIPE
 RUNS AND TERMINATION LOCATIONS, AND ALL OTHER
 ASSOCIATED EQUIPMENT INCLUDING EMERGENCY ELECTRICAL
 PANELS ETC. PLEASE INCLUDE THE REQUIRED CLEARANCE
 DISTANCE MEASUREMENTS FOR ALL EQUIPMENT VENT PIPING
 RUNS AND SPECIFICATIONS INCLUDING FILL PIPING
 LOCATIONS.
 A) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE
 GENERATOR AND THE 190-GALLON FUEL TANK, FUEL PIPING,
 ENGINE EXHAUST PIPE, MUFFLER, AND ALL OTHER ASSOCIATED
 SYSTEM COMPONENTS- SECTION 304.1 FBC M
 B) SUBMIT THE UL 2200 CERTIFICATE OF COMPLIANCE FOR THE
 GENERATOR- SECTION 915.1 FBC M.
 C) THE MANUFACTURER'S SPECIFICATIONS AND/OR UL
 CERTIFICATE SHALL INDICATE THE GENERATOR IS COMPLIANT
 WITH THE NFPA 37 AND NFPA 110 STANDARDS
 D) SUBMIT A CUT SHEET FOR THE FUEL TANK THAT INCLUDES
 THE TANK'S UL LISTING- UL 142 OR UL 2085- SEE SECTION
 21.4.2.1.1 NFPA 30.
 E) REFER TO 4.1 NFPA 110 AND INDICATE THE
 CLASSIFICATION AND LEVEL OF THE EPSS SYSTEM. PLEASE
 INCLUDE THIS INFORMATION IN THE SMOKE CONTROL RATIONAL
 ANALYSIS.
 F) SUBMIT THE GENERATOR EXHAUST PIPE SPECIFICATIONS AND
 PROVIDE AN EXHAUST PIPE DIAGRAM SHOWING THE TOTAL
 SYSTEM RUN AND LENGTH MEASUREMENT, AND TERMINATION
 LOCATION PLEASE INCLUDE ALL COMPONENTS OF THE SYSTEM
 INCLUDING THE SILENCER, AND ANY CONTRACTOR SUPPLIED
 PIPING- SEE SECTION 8.1 ? 8.4 NFPA 37, AND SECTION
 501.3.1 FBC M.
 G) PROVIDE BACKPRESSURE CALCULATIONS FOR THE GENERATOR
 EXHAUST PIPE RUN- SECTION 304.1 FBC M.
 H) REFER TO SECTIONS 7.7.2,1 &, 7.7.2.3 & 7.7.3 NFPA
 110: PER THE ENGINEER'S PLAN AND NARRATIVE, THE
 VENTILATION AIR FOR THE GENERATOR ROOM IS BEING DRAWN
 IN THROUGH A LOUVERED OPENING IN THE 2HR. FIRE-RATED
 WALL GENERATOR ROOM WALL THAT ADJACENT TO THE PARKING
 GARAGE WHICH IS NOT PERMITTED PER SECTION 7.7.2.1 &
 7.7.2.3. THESE SECTIONS STATE THAT VENTILATION AIR MUST
 BE SUPPLIED DIRECTLY FROM A SOURCE OUTSIDE THE
 BUILDING. SECTION 7.7.2.3 PROHIBITS THE USE OF A FIRE
 DAMPER TO PROTECT THE OPENING, THEREFORE THE
 VENTILATION OPENING LOCATION WOULD NOT BE COMPLIANT
 BECAUSE OPENINGS IN FIRE BARRIERS REQUIRE PROTECTION
 ACCORDING TO SECTION 607.5.2 FBC M. INDICATE HOW
 VENTILATION WILL BE PROVIDED FOR THE GENERATOR/FUEL
 TANK ROOM.
 J) PROVIDE DETAILS AND SPECIFICATIONS FOR NORM AND
 EMERGENCY RELIEF VENTING OF THE TANK, INCLUDING VENT
 PIPING RUNS AND TERMINATION LOCATIONS AT THE EXTERIOR
 OF THE BUILDING- SECTION 24.13 NFPA 30.
 K) M-401: REFER TO SECTION 7.7.1 NFPA 110- 2016 AND
 VERIFY THAT THE VENTILATION AIRFLOW IN THE
 GENERATOR/TANK (EPS) ROOM IS DESIGNED TO LIMIT THE
 MAXIMUM AIR TEMPERATURE IN THE ROOM TO THE MAXIMUM
 AMBIENT AIR TEMPERATURE REQUIRED BY THE GENERATOR
 MANUFACTURER. CONSIDERATION SHALL BE GIVEN TO ALL THE
 HEAT EMITTED TO THE ROOM BY THE ENERGY CONVERTER,
 EXHAUST PIPES, AND ALL OTHER HEAT PRODUCING EQUIPMENT-
 SECTION 7.7.1.1. DESIGN OF THE HEATING, COOLING, AND
 VENTILATION SYSTEM SHALL AMONG OTHER THINGS, INCLUDE
 PROVISIONS FOR FACTORS SUCH AS HEAT, COLD, HUMIDITY,
 LOUVERS, ETC.- SECTION 7.7.7. 57) M.205A, B, C, & D:
 SHOW CLEARANCE DISTANCE MEASUREMENTS FOR O/A INTAKES
 AND EXHAUST OUTLETS IN COMPLIANCE WITH SECTIONS 401.4
 AND 501.3.1 FBC M OR PROVIDE GENERAL KEYNOTES.
 54) M.206A & B: INDICATE WHAT APPLIANCES ARE CONNECTED
 TO THE INTAKE VENT AND EXHAUST FLUE PIPES AT THE H.
 AMENITIES ROOM. SHOW THE APPLIANCES IN THE ROOM,
 PROVIDE EQUIPMENT SCHEDULES ON THE PLAN AND SUBMIT
 MANUFACTURER?S SPECIFICATIONS- SECTIONS 503.1 AND 624.1
 FG. ASSUMING THESE APPLIANCES ARE GAS-FIRED PLEASE
 PROVIDE THE GAS PIPING REQUIREMENTS TO THE MAIN GAS
 PLAN- SECTION 402.1 FBC FG.
 55) M.206B: FIRE DAMPERS MISSING FOR THE O/A BRANCH
 DUCTS PENETRATING THE FIRE-RATED CORRIDOR/SUITE WALLS-
 SECTION 607.5.3 FBC M.
 56) M.206B: THE 16X6 O/A DUCT SHALL NOT PENETRATE AND
 RUN THROUGH THE INTERIOR EXIT STAIRWAY- 1023.5 FBC B.
 57) M.206B: THE ERU EXHAUST SHALL TERMINATE OUTDOORS OF
 THE BUILDING. IT APPEARS TO BE EXHAUSTING INTO AN
 INTERSTITIAL SPACE- SECTION 501.3 FBC M.
 58) M.206C: FIRE DAMPERS MISSING FOR THE O/A BRANCH
 DUCTS PENETRATING THE FIRE-RATED CORRIDOR WALLS-
 SECTION 607.5.3 FBC M.
 59) M.206C: DUCT DROPS TO ERU-02 ARE MISLABELED AS
 DROPS TO AHU-02- SECTION 107.2.1 FBC M.
 60) M.206C: IN-LINE EXHAUST FANS ARE SHOWN ON EXHAUST
 DUCTS THAT ARE SPECIFIED TO HAVE FIRE WRAPPING WHICH IS
 NOT IN COMPLIANCE WITH EITHER THE FAN OR THE DUCT WRAP
 LISTING AND INSTALLATION INSTRUCTIONS- SECTION 304.1
 FBC M.
 61) M.206C: THE SPF-13 INTAKE DUCT SHALL BE COMPLETELY
 ENCLOSED IN A FIRE-RATED HORIZONTAL ASSEMBLY AS
 REQUIRED BY SECTION 909.20.6.1 FBC B. A FIRE/SMOKE
 DAMPER IS REQUIRED AT SG-3 PENETRATION INTO STAIR-12 -
 SECTION 1023.5 FBC B.
 62) M.207A: FIRE DAMPERS MISSING FOR SUPPLY AND RETURN
 DUCTS FROM AHU-08 & AHU-09 PENETRATING FIRE-RATED WALLS
 AT POOL EQUIP, POOL DECK, FITNESS STUDIO, AND MENS WC
 WALLS- SECTION 607.5.2 FBC M.
 63) M.207A: FIRE DAMPERS MISSING FOR SUPPLY AND RETURN
 DUCTS FROM AHU-08 & AHU-09 PENETRATING FIRE-RATED WALLS
 AT MENS WC AND PREFUNCTION- SECTION 607.5.2 FBC M. A)
 INDICATE THE DIMENSIONS OF THE AHU-09 SUPPLY DUCT.
 64) M.207A: THE EXHAUST DUCT FROM MENS WC AND WOMENS WC
 SHALL DISCHARGE TO THE OUTDOORS- SECTION 501.3 FBC M.
 65) M.207A: AUTOMATIC DAMPERS ARE REQUIRED FOR THE O/A
 INTAKES AT AHU-08 & 09- SECTION C403.2.4.3 FBC EC.
 66) M.207A: PROVIDE EXHAUST VENTILATION CALCULATIONS
 FOR EF-A07 & EF-A09. IT APPEARS ONE OF FANS IS
 CONNECTED TO THE RA DUCT AT AHU-09.
 67) M.207A: IT APPEARS THE PRESSURIZATION DUCTS FROM
 SPF-07, 10, & 15 ARE ENCLOSED IN FIRE WRAPPING. PLEASE
 CLARIFY BY PLACING A NOTE ON THE PLAN- SECTION
 909.20.6.1 FBC B.
 68) M.207A: SUBMIT MANUFACTURER'S SPECIFICATIONS FOR
 THE 3-HR FIRE WRAP ENCLOSING THE GENERATOR EXHAUST
 DUCT. TERMINATE DUCT AT THE EXTERIOR WITH AN ENDCAP.
 69) M.207A: PROVIDE AN ENLARGED DRAWING OF THE LAUNDRY
 ROOM THAT SHOWS THE LOCATION OF ALL EQUIPMENT, AND THE
 EXHAUST AND MAKEUP AIR SYSTEM DETAILS AND
 SPECIFICATIONS. SUBMIT MANUFACTURER'S SPECIFICATIONS
 FOR THE DRYERS PER SECTION- 504.1 FBC M.
 70) M.207A: INDICATE THE TYPE OF DUCTWORK TO BE USED IN
 THE LAP POOL ROOM- SECTION 603 FBC M.
 71) M.207A: PROVIDE EXHAUST VENTILATION CALCULATIONS
 FOR THE POOL ROOM AND SHOW HOW MAKEUP AIR IS BEING
 PROVIDED- SECTION 501.4 FBC M. CLARIFY IF THE POOL
 EQUIPMENT IS TO BE INSTALLED UNDER SEPARATE PERMIT-
 PLACE A NOTE ON THE PLANS.
 72) M.207B: VERIFY THE EXHAUST AIR LOUVER FOR THE
 FUTURE KITCHEN IS IN COMPLIANCE WITH SECTION 506.3.13.2
 AND 506.3.13.3 FBC M. REFER TO COMMENT #3 FOR MORE
 INFORMATION.
 73) M.207B: FIRE DAMPERS MISSING FOR THE O/A BRANCH
 DUCTS PENETRATING THE FIRE-RATED CORRIDOR WALLS-
 SECTION 607.5.3 FBC M.
 74) M.207B: FIRE/SMOKE DAMPERS REQUIRED AT SG-3
 PRESSURIZATION INLETS AT STAIR-4 AND STAIR-8.
 75) M.207C: FIRE DAMPERS REQUIRED FOR THE AHU-09 SUPPLY
 DUCT AND 36X30 TRANSFER DUCT PENETRATING THE FITNESS
 AND SPA FIRE-RATED WALLS, AND THE 10' DUCT PENETRATING
 THE SPA/FITNESS OFFICE WALL- SECTION 607.5.2 FBC M.
 FIRE WRAPPING OF THE DUCT IN JUST THESE SECTIONS OF THE
 DUCT MUST BE VERIFIED TO BE CONSISTENT WITH THE
 MANUFACTURER'S LISTING AND INSTALLATION INSTRUCTIONS-
 SECTION 304.1 FBC M.
 76) M.207C: NO DIFFUSER IS SHOWN AT THE END OF THE
 16X14 SUPPLY DUCT AT THE SPA- SECTION 603.
 77) M.207C: FIRE DAMPERS MISSING FOR THE LOCKER ROOM
 EXHAUST DUCTS PENETRATING THE FIRE-RATED LOCKER ROOM
 WALLS- SECTION 607.5.3 FBC M.
 79) M.207C: FIRE DAMPERS MISSING FOR THE LOCKER ROOM
 SUPPLY AND RETURN DUCTS PENETRATING THE FIRE-RATED
 LOCKER ROOM WALLS- SECTION 607.5.2 FBC M.
 80) M.207C: IT APPEARS NO O/A HAS BEEN PROVIDED FOR
 UNITS A6, B1, AND S6- TABLE 403.3.1.1. FBC M.
 81) M.207D: FIRE DAMPERS MISSING AT THE DUCTS
 PENETRATING THE CORRIDOR/WOMENSWC/MENSWC FIRE RATED
 WALLS- SECTION 607.5.2 FBC M.
 82) M.208A: LABEL THE PRESSURIZATION FAN SHOWN AT THE
 UNIDENTIFIED INTERIOR EXIT STAIRWAY THE INTAKE DUCT
 SHALL BE COMPLETELY ENCLOSED IN A FIRE-RATED HORIZONTAL
 ASSEMBLY AS REQUIRED BY SECTION 909.20.6.1 FBC B. A
 FIRE/SMOKE DAMPER IS REQUIRED AT THE DIFFUSER
 PENETRATION INTO THE STAIRWAY- SECTION 1023.5 FBC
 83) M.208A: FIRE DAMPERS AND O/A DAMPER MISSING AT THE
 28X28 INTAKE DUCT PENETRATING INTO THE STORAGE ROOM
 84) M.208A: FIRE DAMPERS MISSING FOR THE TENNIS COURTS
 SUPPLY AND RETURN DUCTS PENETRATING INTO THE STORAGE
 ROOM.
 85) M.208AAC SYSTEM FOR THE TENNIS COURTS IN THE
 STORAGE ROOM NOT IDENTIFIED.
 86) M.208C: IT APPEARS NO O/A HAS BEEN PROVIDED FOR
 UNITS B1, B2, B3, & A4- TABLE 403.3.1.1. FBC M.
 87) M.208C: FIRE DAMPERS MISSING FOR THE 18X14 SUPPLY
 AND RETURN DUCTS PENETRATING THROUGH THE FIRE-RATED
 CORRIDOR WALL- SECTION 607.5.3 FBC M.
 88) M.208D: FIRE DAMPERS MISSING FOR THE BRANCH DUCT
 PENETRATING THE FIRE LOBBY WALL, AND ALL OTHER BRANCH
 DUCTS PENETRATING FIRE-RATED CORRIDOR WALLS- SECTION
 607.5.2 & 607.5.3 FBC M.
  
 HOTEL TOWER
 89) SHEETS M.209, M.211, & M.212: DUCT SMOKE DETECTORS
 ARE REQUIRED IN THE SUPPLY SYSTEMS OF THE AHU'S PER
 SECTION 606.2.1 FBC M. PLEASE PROVIDE DS SYMBOLS ON THE
 PLANS AND RISER DRAWINGS TO SHOW THE LOCATIONS.
 91) M.209, M.211, M.212: DUCT SMOKE DETECTORS ARE
 REQUIRED IN THE SUPPLY SYSTEMS OF THE 100% O/A ERU
 SYSTEMS, AND AT EACH STORY OF THE RA/EA RISER- SECTION
 606.2.3. PLEASE PROVIDE DS SYMBOLS ON THE PLANS AND
 RISER DRAWINGS TO SHOW THE LOCATIONS.
 92) M.209, M.211, M.212: PROVIDE A FIRE-RATED ENCLOSURE
 AND ACCESS PANEL FOR THE DEF'S AND SUBMIT SPECS FOR THE
 FAN AND THE EXHAUST DUCT FIRE WRAPPING- SECTIONS 304.1
 & 306.1. A) REFER TO SECTION 504.1 AND SUBMIT
 MANUFACTURER'S SPECIFICATIONS FOR THE CLOTHES DRYERS.
 PROVIDE ON THE PLANS DRYER EXHAUST DUCT DIAGRAMS THAT
 SHOW THE TOTAL RUN LENGTHS OF THE SYSTEMS CONSISTENT
 WITH THE MANUFACTURER'S GUIDELINES. B) REFER TO SECTION
 504.9 AND PROVIDE A SEQUENCE OF OPERATION FOR THE
 DEF?S.
 93) M.209, M.211, M.212: FIRE DAMPERS MISSING FOR THE
 O/A BRANCH DUCTS AND TOILET EXHAUST DUCTS PENETRATING
 THE FIRE-RATED CORRIDOR/SUITE WALLS- SECTION 607.5.3
 FBC M.
 94) M.209, M.211, M.212: SHOW CLEARANCE DISTANCE
 MEASUREMENTS FOR THE EXHAUST OUTLETS IN COMPLIANCE WITH
 SECTIONS 501.3.1 FBC M OR PROVIDE GENERAL KEYNOTES.
 95) M.209, M.211, M.212: REFER TO SECTION 306.1 AND
 VERIFY ACCESS IS PROVIDED FOR AC AND FAN UNITS LOCATED
 ABOVE HARD CEILING. SHOW AN ACCESS PANEL WITH
 DIMENSIONS ON THE DRAWINGS WHERE REQUIRED- SECTION
 306.1 FBC M.
 96) M.209, M.211, M.212: INDICATE LOCATIONS OF ABOVE
 CEILING PLENUMS AND AIR HANDLER CLOSETS AND NOTE NO
 COMBUSTIBLE MATERIALS PERMITTED.
 97) M.209, M.211, M.212: BRANCH DUCT SIZES NOT SHOWN-
 SECTION 603.1 FBC M.
 98) M.209, M.211, M.212: AUTOMATICALLY OPERATING
 SHUTOFF DAMPERS ARE REQUIRED FOR THE O/A DUCTS SERVING
 THE SUITES- SECTION C403.2.4.3 FBC EC.
  
 OFFICE TOWER
 100) SHEETS M.213, M.214, M.215: INCOMPLETE PLANS AND
 DETAILS. IT APPEARS THAT OFFICE SHELL SPACES ARE
 DEPICTED HOWEVER THERE ARE NO NOTES TO CLARIFY. PLEASE
 LABEL ALL THE ROOMS SHOWN ON THE PLAN- SECTION 107.2.1
 WPB.
 101) M.213, M.214, M.215: LABEL THE SYSTEMS IN THE MECH
 RM- SECTION 107.2.1 WPB.102)
 102) M.213, M.214, M.215: FIRE/SMOKE DAMPERS MISSING
 FOR THE 64X28 SUPPLY AND RETURN DUCTS PENETRATING THE
 FIRE-RATED MECH RM WALLS- SECTION 607.5.3 FBC M.
 103) M.213, M.214, M.215: NO O/A OR CONDITIONING HAS
 BEEN PROVIDED IN THE FIRE AND ELEVATOR LOBBIES- SECTION
 107.2.1 WPB.
 104): M.213, M.214, M.215: DUCT SMOKE DETECTORS ARE
 REQUIRED IN THE SUPPLY SYSTEMS OF THE AHU'S PER SECTION
 606.2.1 FBC M. PLEASE PROVIDE DS SYMBOLS ON THE PLANS
 AND RISER DRAWINGS TO SHOW THE LOCATIONS.
 105) M.213, M.214, M.215: DUCT SMOKE DETECTORS ARE
 REQUIRED IN THE SUPPLY SYSTEMS OF THE 100% O/A ERU
 SYSTEMS, AND AT EACH STORY OF THE RA/EA RISER- SECTION
 606.2.3. PLEASE PROVIDE DS SYMBOLS ON THE PLANS AND
 RISER DRAWINGS TO SHOW THE LOCATIONS.
 106) M.216: LABEL ALL ROOMS AND AREAS SHOWN ON THE
 PLANS- SECTION 107.2.1 WPB.
 107) M.216: FIRE DAMPERS MISSING FOR ERU-03 SUPPLY AND
 RETURN DUCTS PENETRATING THE FIRE-RATED MECHANICAL ROOM
 WALLS- SECTION 607.5.3 FBC M.
 108) M.216: NO O/A OR CONDITIONING HAS BEEN PROVIDED IN
 THE FIRE AND ELEVATOR LOBBIES- SECTION 107.2.1 WPB.
 109) M.216: LABEL THE AIR INLET OPENING AT THE ERU-03
 MECHANICAL ROOM- SECTION 107.2.1 WPB.
 110) M.216: IT APPEARS THE SMOKE PURGE EXHAUST AND
 ERU-03 RETURN DUCTS ARE CONNECTED OR IN THE SAME SHAFT-
 PLEASE CLARIFY- SECTION 107.2.1 WPB.
 110) M.216: PROVIDE ENLARGED DRAWINGS OF THE CHILLER
 MECHANICAL ROOMS AND SHOW HOW THE ROOMS ARE BEING
 VENTILATED PER SECTIONS 1105.6 FBC M. A) PROVIDE NORMAL
 AND EMERGENCY VENTILATION CALCULATIONS AND DETAILS-
 SECTIONS 1105.6.3.1 & 1105.6.3.2 FBC M. C) SHOW THE
 LOCATIONS OF REFRIGERANT DETECTORS AND SUBMIT
 MANUFACTURER'S SPECIFICATIONS. D) SHOW HOW THE CHILLERS
 ARE BEING ANCHORED TO THE STRUCTURE. E) LABEL ALL
 EQUIPMENT IN THE ROOM AND PROVIDE AN EQUIPMENT
 SCHEDULE.
 111) M.216: PROVIDE AN ENLARGED DRAWING OF THE COOLING
 TOWER ROOM AND SHOW HOW THE ROOM IS BEING VENTILATED-
 NATURALLY OR MECHANICALLY- PROVIDE CALCULATIONS AND
 DETAILS. A) SHOW VAPOR PLUME DISCHARGE LOCATIONS AND
 REQUIRED CLEARANCE DISTANCES PER SECTION 908.3 FBC M.
 B) SHOW HOW THE TOWERS ARE BEING ANCHORED TO THE
 STRUCTURE- SECTION 908.4 FBC M (ENGINEERING FOR SUPPORT
 AND PLATFORM STRUCTURES MAY BE DEFERRED). C) PROVIDED
 WATER PIPING SUPPLY AND RETURN DIAGRAMS. D) SHOW THE
 WATER FEED LINE PIPE AND BACKFLOW PREVENTER
 CONNECTIONS- SECTION 908.5 FBC M.
 112) M.217: CLARIFY IF THE ELEVATOR HOISTWAYS ARE TO BE
 VENTILATED AND PROVIDE DETAILS- SECTION 909.21.2 FBC B.
 113) M.216 & M.217: SHOW THE LOCATION OF THE ELEVATOR
 CONTROL ROOM AND SHOW COMPLIANCE WITH SECTION 3005.2
 FBC B FOR INDEPENDENT VENTILATION SYSTEMS.
  
 RESIDENTIAL TOWER
 114) SHEETS M.218, M.219, M.220, & M.221: DUCT SMOKE
 DETECTORS ARE REQUIRED IN THE SUPPLY SYSTEMS OF THE
 AHU'S PER SECTION 606.2.1 FBC M. PLEASE PROVIDE DS
 SYMBOLS ON THE PLANS AND RISER DRAWINGS TO SHOW THE
 LOCATIONS.
 115) M.218, M.219, M.220, & M.221: DUCT SMOKE DETECTORS
 ARE REQUIRED IN THE SUPPLY SYSTEMS OF THE 100% O/A ERU
 SYSTEMS, AND AT EACH STORY OF THE RA/EA RISER- SECTION
 606.2.3. PLEASE PROVIDE DS SYMBOLS ON THE PLANS AND
 RISER DRAWINGS TO SHOW THE LOCATIONS.
 116) M.218, M.219, M.220, & M.221: INDICATE HOW O/A IS
 BEING PROVIDED TO THE UNITS AND PROVIDE CALCULATIONS-
 SECTION 401.2 FBC M.
 117) M.218, M.219, M.220, & M.221: SHOW CLEARANCE
 DISTANCE MEASUREMENTS FOR THE TOILET AND DRYER EXHAUST
 OUTLETS IN COMPLIANCE WITH SECTIONS 501.3.1 FBC M OR
 PROVIDE GENERAL KEYNOTES.
 118) M.218, M.219, M.220, & M.221: REFER TO SECTION
 306.1 AND VERIFY ACCESS IS PROVIDED FOR AC AND FAN
 UNITS LOCATED ABOVE HARD CEILING. SHOW AN ACCESS PANEL
 WITH DIMENSIONS ON THE DRAWINGS WHERE REQUIRED- SECTION
 306.1 FBC M.
 119) M.218, M.219, M.220, & M.221: INDICATE LOCATIONS
 OF ABOVE CEILING PLENUMS AND AIR HANDLER CLOSETS AND
 NOTE NO COMBUSTIBLE MATERIALS PERMITTED.120
 120) M.218, M.219, M.220, & M.221: BRANCH DUCT SIZES
 NOT SHOWN- SECTION 603.1 FBC M.
 121) M.218, M.219, M.220, & M.221: AUTOMATICALLY
 OPERATING SHUTOFF DAMPERS WILL BE REQUIRED FOR O/A
 DUCTS SERVING THE UNITS- SECTION C403.2.4.3 FBC EC.
 122) M.218, M.219, M.220, & M.221: PROVIDE VENTILATION
 FOR THE CORRIDORS, ELEVATOR AND FIRE LOBBIES- TABLE
 403.3.1.1 FBC M.
 123) M.220: NO DUCT LAYOUT PLANS PROVIDED- SECTION
 107.2.1 FBC M.
 124) M.218, M.219, M.220, & M.221: REFER TO SECTION
 504.1 AND SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE
 CLOTHES DRYERS. PROVIDE ON THE PLANS DRYER EXHAUST DUCT
 DIAGRAMS THAT SHOW THE TOTAL RUN LENGTHS OF THE SYSTEMS
 CONSISTENT WITH THE MANUFACTURER'S GUIDELINES.
 125) M.222: PROVIDE ENLARGED DRAWINGS OF THE MECHANICAL
 ROOM AND SHOW HOW THE ROOMS IS BEING VENTILATED PER
 SECTIONS 1105.6 FBC M. A) PROVIDE NORMAL AND EMERGENCY
 VENTILATION CALCULATIONS AND DETAILS- SECTIONS
 1105.6.3.1 & 1105.6.3.2 FBC M. C) SHOW THE LOCATIONS OF
 REFRIGERANT DETECTORS AND SUBMIT MANUFACTURER'S
 SPECIFICATIONS. D) SHOW HOW THE CHILLERS ARE BEING
 ANCHORED TO THE STRUCTURE. E) LABEL ALL EQUIPMENT IN
 THE ROOM AND PROVIDE AN EQUIPMENT SCHEDULE. E) PROVIDE
 MANUFACTURER?S SPECIFICATIONS FOR THE BOILERS- SECTION
 631.1 FBC FG. PLEASE NOTE THAT OPEN FAME GAS EQUIPMENT
 SHALL NOT USE COMBUSTION AIR FROM THE MACHINERY ROOM-
 SECTION 1105.5 FBC FG.
 126) M.222: PROVIDE AN ENLARGED DRAWING OF THE COOLING
 TOWER ROOM AND SHOW HOW THE ROOM IS BEING VENTILATED-
 NATURALLY OR MECHANICALLY- PROVIDE CALCULATIONS AND
 DETAILS. A) SHOW VAPOR PLUME DISCHARGE LOCATIONS AND
 REQUIRED CLEARANCE DISTANCES PER SECTION 908.3 FBC M.
 B) SHOW HOW THE TOWERS ARE BEING ANCHORED TO THE
 STRUCTURE- SECTION 908.4 FBC M (ENGINEERING FOR SUPPORT
 AND PLATFORM STRUCTURES MAY BE DEFERRED). C) PROVIDED
 WATER PIPING SUPPLY AND RETURN DIAGRAMS. D) SHOW THE
 WATER FEED LINE PIPE AND BACKFLOW PREVENTER
 CONNECTIONS- SECTION 908.5 FBC M.
 127) M.222: SUBMIT MANUFACTURER'S SPECIFICATIONS FOR
 THE GENERATOR, FUEL PIPING, ENGINE EXHAUST PIPE,
 MUFFLER, AND ALL OTHER ASSOCIATED SYSTEM COMPONENTS-
 SECTION 304.1 FBC M. A) SUBMIT THE UL 2200 CERTIFICATE
 OF COMPLIANCE FOR THE GENERATOR- SECTION 915.1 FBC M.
 THE MANUFACTURER'S SPECIFICATIONS AND/OR UL CERTIFICATE
 SHALL INDICATE THE GENERATOR IS COMPLIANT WITH THE NFPA
 37 AND NFPA 110 STANDARDS. B) SUBMIT MANUFACTURER'S
 SPECIFICATIONS FOR THE FUEL TANK THAT INCLUDES THE
 TANK'S UL LISTING- UL 142 OR UL 2085- SEE SECTION
 21.4.2.1.1 NFPA 30. C) REFER TO 4.1 NFPA 110 AND
 INDICATE THE CLASSIFICATION AND LEVEL OF THE EPSS
 SYSTEM. PLEASE INCLUDE THIS INFORMATION IN THE SMOKE
 CONTROL RATIONAL ANALYSIS. D) SUBMIT THE GENERATOR
 EXHAUST PIPE SPECIFICATIONS AND PROVIDE AN EXHAUST PIPE
 DIAGRAM SHOWING THE TOTAL SYSTEM RUN AND LENGTH
 MEASUREMENT, AND TERMINATION LOCATION PLEASE INCLUDE
 ALL COMPONENTS OF THE SYSTEM INCLUDING THE SILENCER,
 AND ANY CONTRACTOR SUPPLIED PIPING- SEE SECTION 8.1.
 8.4 NFPA 37, AND SECTION 501.3.1 FBC M. E) PROVIDE
 DETAILS AND SPECIFICATIONS FOR NORMAL AND EMERGENCY
 RELIEF VENTING OF THE TANK, INCLUDING VENT PIPING RUNS
 AND TERMINATION LOCATIONS- SECTION 24.13 NFPA 30.
 128) M.222: PROVIDE WIND LOAD ENGINEERING FOR
 ATTACHMENT OF THE GENERATOR TO THE ROOF STRUCTURE-
 SECTION 301.15 FBC M.
 129) M.223: SHOW THE LOCATIONS OF THE ELEVATOR CONTROL
 ROOMS AND SHOW COMPLIANCE WITH SECTION 3005.2 FBC B FOR
 INDEPENDENT VENTILATION SYSTEMS.
  
 HOTEL SUITES:
 130) M.250- M.253: SHOW HOW O/A IS BEING PROVIDED TO
 THE SUITES- SECTION 401.2 FBC M, AND HOW IT IS BEING
 AUTOMATICALLY CONTROLLED- SECTION C403.2.4.3 FBC EC.
 131) M.250- M.253: REFER TO SECTION 306.1 AND VERIFY
 ACCESS IS PROVIDED FOR THE FCU'S LOCATED ABOVE HARD
 CEILINGS OR IN CLOSETS. SHOW AN ACCESS PANEL WITH
 DIMENSIONS ON THE DRAWINGS WHERE REQUIRED- SECTION
 306.1 FBC M.
 132) M.250- M.253: INDICATE LOCATIONS OF ABOVE CEILING
 PLENUMS AND AIR HANDLER PLENUM CLOSETS AND NOTE NO
 COMBUSTIBLE MATERIALS PERMITTED.
  
 RESIDENTIAL UNITS
 133) M.254- M.258: LABEL ALL ROOMS AND SPACES ON THE
 PLANS- SECTION 107.2.1 WPB.
 134) M.254- M.258: SHOW HOW O/A IS BEING PROVIDED TO
 THE UNITS- SECTION 401.2 FBC M, AND HOW IT IS BEING
 AUTOMATICALLY CONTROLLED- SECTION C403.2.4.3 FBC EC.
 135) M.254- M.258: PLACE NOTES TO INDICATE NO
 COMBUSTIBLE MATERIALS PERMITTED IN THE VHP CLOSETS
 INCLUDING THE DOORS- SECTION 602.2.1 FBC M. IT APPEARS
 THE DOORS WILL BE LOUVERED TO ALLOW RETURN AIR TO THE
 HEAT PUMPS, OTHERWISE INDICATE MEANS OF RETURN AIR-
 SECTION 601.6 FBC M.
 136) M.254- M.258: INDICATE HOW AIR IS BEING RETURNED
 FROM THE BEDROOMS- SECTION 601.6.
 137) M.254- M.258: REFER TO SECTION 504.1 AND SUBMIT
 MANUFACTURER'S SPECIFICATIONS FOR THE CLOTHES DRYERS.
 PROVIDE ON THE PLANS DRYER EXHAUST DUCT DIAGRAMS THAT
 SHOW THE TOTAL RUN LENGTHS OF THE SYSTEMS CONSISTENT
 WITH THE MANUFACTURER'S GUIDELINES.
 138) M.254- M.258: PROVIDE AN ENLARGED DRAWING OF THE
 VHP CLOSETS SHOWING REQUIRED CLEARANCES- SECTION
 C403.2.9.3.3 FBC EC, AND PRIMARY AND SECONDARY MEANS OF
 CONDENSATE DISPOSAL- SECTION 307.2.1, 307.2.2, &
 307.2.3 FBC M.
 139) PROVIDE A CONDENSATE DISPOSAL RISER DRAWING- TABLE
 307.2.2 FBC M.
 140) PROVIDE FIRESTOPPING DETAILS FOR CHILLED AND HOT
 WATER PIPES, AND DUCTWORK.
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  

Review Stop P PLUMBING
Rev No 5 Status P Date 2021-08-23 Cont ID  
Sent By lcrespo Date 2021-08-23 Time 18:03 Rev Time 0.00
Received By lcrespo Date 2021-08-23 Time 11:44 Sent To  
Notes
2021-08-23 14:52:1808/23/21 REVIEWED FOR CODE COMPLIANCE (PLUMBING)
  
 BY REVIEWING THE PLANS / SPECIFICATIONS FOR CODE
 COMPLIANCE DOES NOT RELIEVE THE OWNER, DESIGN
 PROFESSIONAL, CONTRACTORS, OR THEIR REPRESENTATIVES
 FROM THE RESPONSIBILITY TO COMPLY WITH ALL LOCAL,
 STATE, AND NATIONAL CODES AND STANDARDS IN EFFECT AT
 THE TIME OF PERMIT ISSUANCE. OUR REVIEW IS NOT A CHECK
 OF EVERY ITEM AND DOES NOT PREVENT THIS DEPARTMENT FROM
 REQUIRING CORRECTIONS DURING CONSTRUCTION. ANY CHANGES
 / ALTERATIONS TO APPROVED PLANS SHALL BE APPROVED TO
 AVOID VOIDING OF THE PERMIT.
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER / INSPECTOR
 EMAIL: [email protected] OFFICE: 561 805-6720
  

Review Stop P PLUMBING
Rev No 4 Status F Date 2021-06-21 Cont ID  
Sent By lcrespo Date 2021-06-21 Time 15:48 Rev Time 0.00
Received By lcrespo Date 2021-06-14 Time 14:32 Sent To  
Notes
2021-06-21 15:54:2406/21/21 1ST PLUMBING REVIEW**DENIED** WITH COMMENTS
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME, AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
 1. NO RESPONSE TO THIS?SHEET C.03 SHOWS A 15-INCH PVC
 RWL NEAR THE PROPERTY'S SOUTHWEST CORNER NEAR THE BUS
 STOP. THE LINE IS NOT SHOWN ON SHT. P100 (NEAR COLUMN
 LINE #1). CLARIFY.
  
 2. DONE.
  
 3. DONE.
  
 4. DONE.
  
 5. DONE.
  
 6. SHEET A1.502A - DETAIL #2 DOES NOT SHOW A SEAT IN
 THE SHOWER, AND DETAIL #3 SHOWS A SEAT. CLARIFY.
  
 THE SEAT DRAWN IN IS A SIDE SEAT, AND THE ONE ON THE
 ADA FUTURE IS THE BACK SEAT. PLEASE CORRECT AS BACKING
 DETAIL IS REQUIRED AND PROVIDED PER THE WPB AMENDMENTS
 TO THE FBC SEC. 107.2.1 INFORMATION ON CONSTRUCTION
 DOCUMENTS.
  
 7. DONE.
  
 8. DONE.
  
 9. DONE.
  
 10. THIS ITEM HAS NOT BEEN ADDRESSED, SHEET A1.600 -
 DETAIL #1 - WOMEN'S RESTROOM - THE PLAN STATES A CLEAR
 FLOOR SPACE OF 60 INCHES WIDE FOR THE ACCESSIBLE STALL,
 BUT THE PLAN ALSO SHOWS THE CLEAR INSIDE WIDTH 4 FEET
 11 1/2 INCHES. IF THIS IS A ROUGH DIMENSION, THEN THIS
 STALL WILL NOT BE WIDE ENOUGH AFTER THE FINISH. COMPLY
 WITH FBC-ACCESS. SEC.604.3.1.2ND REQUEST. CLARIFY.
  
 11. THIS ITEM HAS NOT BEEN ADDRESSED, SHEET A1.600
 DETAIL #1 - MEN'S RESTROOM - ONE OF THE URINALS IS
 SHOWN AS 1 FOOT 2 INCHES FROM A WALL TO THE CENTERLINE
 OF THE URINAL. A MINIMUM OF 15 INCHES FROM A WALL TO
 THE CENTER OF THE URINAL IS REQUIRED. FBC-PLUMBING
 SEC.405.3.1. 2ND REQUEST.
  
 12. THIS ITEM HAS NOT BEEN ADDRESSED, SHEET A1.600 -
 GROUND LEVEL BATHROOM #0132- IS THIS A UNISEX TOILET
 ROOM OR GENDER-SPECIFIC? CLARIFY. 2ND REQUEST, IT SEEMS
 AS THERE SHOULD BE A V3 SHEET.
  
 13. DONE.
  
 14. DONE.
  
 15. DONE.
  
 16. DONE.
  
 17. DONE BUT NEW COMMENT;
  
 ON SHEET 606 FHA;
  
 A. DETAIL #3, DOOR IS SWINGING INTO THE CLEAR FLOOR
 SPACE OF THE LAVE, AND THE CLEAR FLOOR SPACE IS NOT
 SHOWN FOR THE TUB. PLEASE NOTE THAT THE DISTANCE FROM
 THE DOOR OPENING TO THE TUB MAY BE ENCROACHING IN THE
 FLOOR SPACE.
  
 B. DETAIL #9 UNIT D1 SHOWS CLEAR FLOOR SPACE BUT NOT AN
 FHA UNIT; PLEASE REMOVE OR CLARIFY STATUS.
  
 ON SHEET 607 FHA;
 A. DETAIL #2, THE CLEAR FLOOR SPACE FOR TUB AND LAV NOT
 SHOWN.
  
 B. DETAIL # 3 AND #6, MASTER TUB CLEAR FLOOR SPACE NOT
 SHOWN.
  
 C. DETAIL # 7, LAV AND SHOW CLEAR FLOOR SPACE NOT
 SHOWN.
  
 ON SHEET 608 FHA;
  
 A. DETAIL #1, #4, AND 6, THE CLEAR FLOOR SPACE FOR TUB
 NOT SHOWN.
  
 B. DETAIL #3 UNIT B4 SHOWS CLEAR FLOOR SPACE BUT NOT AN
 FHA UNIT; PLEASE REMOVE OR CLARIFY STATUS.
  
 C. DETAIL #10 UNIT C1 SHOWS BACKING ON TUB AND TOILET.
 IS THIS AN FHA UNIT; PLEASE CLARIFY?
  
 ON SHEET 609 FHA;
  
 A. DETAIL #1, #3, AND #8, MASTER TUB CLEAR FLOOR SPACE
 NOT SHOWN.
  
 B. DETAIL #5 UNIT D1 SHOWS BACKING. IS THIS AN FHA
 UNIT; PLEASE CLARIFY?
  
 C. DETAIL #6 UNIT D3, LAV, AND TUB CLEAR FLOOR SPACE
 NOT SHOWN.
  
 D. DETAIL #7 UNIT D3 BATHROOM 2 & 3 SHOWS BACKING AND
 TOILET CLEAR FLOOR SPACE; IS THIS AN FHA? PLEASE
 CLARIFY.
  
 E. DETAIL 9 UNIT D4 SHOWS BACKING. IS THIS AN FHA UNIT;
 PLEASE CLARIFY?
  
 18. DONE.
  
 19. DONE.
  
 20. DONE.
  
 21. DONE.
  
 22. DONE.
  
 23. DONE.
  
 24. DONE.
  
 25. DONE.
  
 26. DONE.
  
 27. DONE.
  
 28. THE PAGE FOR V5 DOES NOT COINCIDE WITH THE PRIOR
 VERSION, SHEET A1.610 - DETAIL # 2 - CLEAN UP THIS
 PLAN. THE LAVATORY IS SHOWN LOCATED PARTIALLY IN THE
 WALL.
  
 29. THE PAGE FOR V5 DOES NOT COINCIDE WITH THE PRIOR
 VERSION, SHEET A1.610 - DETAIL #1 - THE FLOOR PLAN
 SHOWS THE DOOR SWINGING INTO THE SHOWER AND THE TOILET
 COMPARTMENT. THE INSWING DOOR IMPEDES ACCESS TO THE
 SHOWER CONTROLS AND THE TOILET AND DOES NOT COMPLY WITH
 FAIR HOUSING. REVERSE THE SWING OF THE DOOR.
  
 30. THE PAGE FOR V5 DOES NOT COINCIDE WITH THE PRIOR
 VERSION, SHEET A1.610 - DETAIL #3 - THE NOTES AND
 DETAILS FOR THE GRAB BAR REINFORCEMENT DON'T MAKE
 SENSE. CORRECT THE DEFICIENCIES. IF THIS IS SUPPOSED TO
 BE AN FHA-COMPLIANT BATHROOM, SHOW ALL CLEAR FLOOR
 SPACES AND THE FHA BATHROOM TYPE ON THE PLAN. THE
 LAVATORY APPEARS TO ENCROACH INTO THE REQUIRED CLEAR
 FLOOR SPACE FOR THE SHOWER. PLEASE CLARIFY.
  
 31. THE PAGE FOR V5 DOES NOT COINCIDE WITH THE PRIOR
 VERSION, SHEET A1.610 - DETAIL # 6 - IF THIS IS THE
 FHA-COMPLIANT BATHROOM, PLACE THE TYPE OF FHA BATHROOM
 ON THE PLAN AND CORRECT THE OVERLAY OF THE UNIT NUMBER
 ON THE FLOOR PLAN. PLEASE CORRECT THE OVERLAY ON DETAIL
 #5 ALSO.
  
 32. THE PAGE FOR V5 DOES NOT COINCIDE WITH THE PRIOR
 VERSION, SHEET A1.610 - DETAIL #7 - CORRECT THIS
 DETAIL. THE LOCATION OF REINFORCEMENT AND CLEAR FLOOR
 SPACES ARE OUT OF WHACK. CONTROLS ARE CALLED OUT ON THE
 LAVATORY. THE BATHROOM FLOOR PLAN IS CUT OFF AND
 INCOMPLETE. PLEASE CLARIFY.
  
 33. DONE.
  
 34. THIS ITEM SEEMS TO HAVE A PIPE THAT IS NOT CLEAR TO
 WHERE THEY GO OR ARE ON SHEET P100. IF POSSIBLE, EXPAND
 THE PIPING LAYOUT FOR THE SANITARY AND VENT LINES AND
 TAG THE RISERS AT THE TOILET ROOMS BY ELEVATORS P03,
 P04, & P05 ON COLUMN LINE H.
  
 35. DONE.
  
 36. DONE.
  
 38. THIS IS NOT CORRECTED; SHEET P.101B SHOWS AN 8-INCH
 SANITARY LINE WITHIN STAIRWAY # 4 AND A 4 INCH GW LINE
 IN STAIRWAY #10. THE LINE IS NOT PERMITTED WITHIN THE
 STAIRWAY PER FBC-BUILDING SEC.1023.5. THERE IS A CIRCLE
 WITH A LINE IN THIS AND ANOTHER ELEVATOR THAT WILL NEED
 TO BE REMOVED OR RELATED OUT OF THE STAIRWAY TO MOVE
 FORWARD TO A FINAL REVIEW, SO PLEASE DO YOUR BEST TO
 CORRECT THESE ITEMS.
  
 39. DONE.
  
 40. DONE.
  
 41. THE RISER TAGS FOR THE LW R2 P 7XX RISERS ARE
 MISSING THE DRAWING LOCATIONS ON THE RISER TAGS. PLEASE
 CLARIFY PER THE WPB AMENDMENTS TO FBC SEC. 107.2.1.
 PLEASE ALSO CLARIFY ANY ABOVE FLOORS IN POD C AND ANY
 OTHERS ON THIS PLAN TO PREVENT A DELAY IN YOUR REVIEW.
  
 42. NEW COMMENT; ON SHEET 103C UNIT IN GRID J/12, THE
 PIPES FOR SANITARY P702 AND P 7XX ARE IN THE WRONG
 LOCATION, AND THE ARROW IS NOT POINTED TO THEM AND
 PLEASE CORRECT OTHER UNITS BESIDE P709 AND P702A PER
 THE WPB AMEND. TO FBC SEC. 107.2.1, 107.3.5.1.3.
  
 43. NEW COMMENT; ON SHEET 104C UNIT IN GRID J/12, THE
 PIPES FOR SANITARY P702 AND P 7XX ARE IN THE WRONG
 LOCATION, AND THE ARROW IS NOT POINTED TO THEM AND
 PLEASE CORRECT OTHER UNITS BESIDE P709 AND P702A PER
 THE WPB AMEND. TO FBC SEC. 107.2.1, 107.3.5.1.3.
  
 44. NEW COMMENT; ON SHEET 105C UNIT IN GRID J/12, THE
 PIPES FOR SANITARY P702 AND P 7XX ARE IN THE WRONG
 LOCATION, AND THE ARROW IS NOT POINTED TO THEM AND
 PLEASE CORRECT OTHER UNITS BESIDE P709 AND P702A PER
 THE WPB AMEND. TO FBC SEC. 107.2.1, 107.3.5.1.3.
  
 45. NEW COMMENT; ON SHEET 106C UNIT IN GRID J/12, THE
 PIPES FOR SANITARY BELOW TO THE LABELS BELOW ARE NOT
 CLEAR OR ARE MISSED LABELED; PLEASE TRY TO CLARIFY AND
 CORRECT AS THEY ARE TOO MANY TO MENTION PER THE WPB
 AMEND. TO FBC SEC. 107.2.1, 107.3.5.1.3.
  
 46. DONE.
  
 47. DONE.
  
 48. DONE.
  
 49. DONE.
  
 50. DONE.
  
 51. DONE.
  
 52. DONE.
  
 53. DONE.
  
 54. DONE.
  
 55. DONE.
  
 56. DONE.
  
 57. DONE.
  
 58. DONE.
  
 59. DONE.
  
 60. DONE.
  
 61. DONE.
  
 62. DONE.
  
 63. DONE.
  
 64. DONE.
  
 65. DONE.
  
 66. DONE.
  
 67. DONE.
  
 68. DONE.
  
 68 A. NEW COMMENT, ON SHEET 702A AND 702 B, FROM WATER
 SERVICE TO PUMPS, THE CW HAS TOO LIGHT LABELS; PLEASE
 CORRECT BY DARKENING THEM PER THE WPB AMENDMENTS TO THE
 FBC SEC. 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 69. DONE.
  
 70. DONE.
  
 71. DONE.
  
 72. DONE.
  
 73. PARTLY DONE, BUT ON SHEET 704, TAG SS/R8 AND SS/R9
 ARE MISSING PXXX DESTINATION. PLEASE CORRECT PER THE
 WPB AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS. PLEASE NOTE THE SHEET 704 AND
 CONTINUING PAGES HAVE A TABLE THAT REFERS TO THE 2014
 CODE FOR TABLE 710.1(2), AND IT SHOULD BE THE 2017 FBC
 P TABLE 710.2 CODE, SO PLEASE CORRECT ALL PAGES TO
 PREVENT FURTHER DELAYS PER THE WPB AMENDMENTS TO THE
 FBC SEC. 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 74. DONE.
  
 75. THERE ARE TAGS ON LEVELS EIGHT AND ELEVEN THAT ARE
 NOT LABELED ON SHEET. P.704B - RISER TAGS ARE MISSING
 THE DRAWING LOCATION NUMBERS ON THE RISER TAGS. ENSURE
 ALL RISER TAGS ARE COMPLETE.
  
 76. DONE.
  
 76. A. PLEASE NOTE THE SHEET 705, 705 A, 706, AND
 CONTINUING PAGES HAVE A TABLE THAT REFERS TO THE 2014
 CODE FOR TABLE 709.1. IT SHOULD BE THE 2017 FBC P TABLE
 709.1 CODE, SO PLEASE CORRECT ALL PAGES TO PREVENT
 FURTHER DELAYS PER THE WPB AMENDMENTS TO THE FBC SEC.
 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 77. DONE.
  
 78. DONE.
  
 79. DONE.
  
 80. DONE.
  
 81. DONE.
  
 82. DONE.
  
 83. DONE.
  
 84. DONE.
  
 85. DONE.
  
 86. DONE.
  
 87. DONE.
  
 88. DONE.
  
 89. ON SHEET P.711, DETAIL #6, THE RISER TAG
 INFORMATION FOR DOMESTIC WATER RISER IS SO LIGHT IT IS
 ILLEGIBLE. PLEASE CORRECT.
  
 90. DONE.
  
 91. ON SHEET P.712 DETAIL #6 ?
  
 A. THE MEN'S AND WOMEN'S ROOMS REQUIRE SHUT-OFF VALVES
 AT HOSE BIBBS PER THE FBC-PLUMBING SEC. 606.2.
  
 B. THE WATER COOLER REQUIRES A HAMMER ARRESTOR PER THE
 2017 FBC P 604.9 WATER HAMMER.
  
 92. ON SHEET P.712, DETAILS #3, #4 (SS/0#), - THE RISER
 TAGS MISS THE RISER INFORMATION. ENSURE ALL RISER TAGS
 ARE COMPLETE.
  
 93. ON SHEET P.712, THE WATER RISER FOR THE OFFICE
 TOWER-MEN?S OFFICE TOWER MEN?S TOILET ROOM LEVEL 17 IS
 MISSING AIR ARRESTORS AND SHUT-OFF VALES PER THE 2017
 FBC P 604.9 AND 606.1. OFFICE TOWER-MEN?S TOILET IS
 ONLY MISSING AIR ARRESTORS.
  
 94. INCOMPLETE, ON SHEET P.720 ? THE IDENTIFIED RISER
 TAGS INFO FIXTURE UNIT LOADS FOR SS/P60 HAS P7XX;
 PLEASE ADD CORRESPONDING NUMBERS. AND SS/P1 DOES NOT
 HAVE A STACK NUMBER. PLEASE CORRECT PER THE WPB
 AMENDMENTS TO FBC SEC. 107.2.1, 107.3.5.1.3.
  
 95. DONE BUT OVERLAPPING; PLEASE CORRECT. ON SHEET
 P.730 - IDENTIFY ALL RISERS WITH RISER TAGS COMPLETE
 WITH ALL RISER TAG INFO AND THE GPM'S DRAINING INTO
 EACH RISER. WPB AMEND. TO FBC SEC. 107.2.1,
 107.3.5.1.3.
  
 96. ON SHEET P.731 - THE DRAWING HAS A FLOATING FITTING
 AND DRAINS WITH SECTIONS OF PIPE ARE MISSING, PIPE
 SIZES ARE NOT CONNECTED, RISER TAGS ALL OVER THE PLACE
 AND NOT DIRECTED OR POINTED TO A REFERENCE POINT,
 SECTIONS OF THE PIPING SYSTEM ARE CONGESTED AND
 DIFFICULT TO REVIEW ON THE TOP PART. PLEASE CORRECT PER
 THE WPB AMENDMENTS TO FBC SEC. 107.2.1, 107.3.5.1.3.
  
 97. ON SHEET P.732 - THE RISER SHOWS THE SQUARE FOOTAGE
 AREA BEING DRAINED BUT NO GPM'S WITH 2014 FBC-PLUMBING
 SEC. TABLE 1106.3, AND THE CODE THAT SHOULD BE USED AND
 REFERENCED IS 2017 FBC SEC. TABLE 1106.2, SO PLEASE
 CLARIFY AND OR RECALCULATE. THIS IN ALL OTHER SECTION
 OF THIS PLUMBING FOR SANITARY HAS 2014, PLEASE CORRECT
 AND CLARIFY IF NEED BE,
  
 98. ON SHEET. P.733, SECOND REQUEST, SEVERAL RISER TAGS
 ARE MISSING THE DRAWING LOCATION INFORMATION. PLEASE
 ENSURE ALL RISER TAGS ARE COMPLETE.
  
 99. ON SHEET. P.734, SECOND REQUEST, SEVERAL RISER TAGS
 ARE MISSING THE DRAWING LOCATION INFORMATION. PLEASE
 ENSURE ALL RISER TAGS ARE COMPLETE.
  
 100. DONE.
  
 101. ON THE SHEET, P.803 - DETAIL #3 SHOWS JOINTS UNDER
 THE SLAB - PLUMBING SPECIFICATIONS SEC. 22 1110 - PART
 2 - 2.02 STATES THAT "ENTRANCE PIPING TO THE BUILDING
 TO TERMINATE ABOVE GRADE." THE DETAIL ON P.803 SHOWS
 FLANGED FITTINGS UNDER THE SLAB. CLARIFY. IF THIS
 PIPING ARRANGEMENT IS TO REMAIN, SUBMIT DETAILS ON
 FITTING RESTRAINTS AND THRUST BLOCK INFORMATION. WPB
 AMEND. TO FBC SEC. 107.2.1, 107.3.5.1.3. 2ND REQUEST
 AND THE THERE IS NO NEW DRAWING, AND THE RESPONSE SAYS
 DETAIL HAS BEEN UPDATED PLEASE CLARIFY PER THE WPB
 AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS.
  
 102. RIGID SUPPORT SWAY BRACING SHALL BE PROVIDED AT
 CHANGES IN A DIRECTION MORE SIGNIFICANT THAN 45 DEGREES
 FOR PIPE SIZES 4 INCHES AND LARGER PER FBC-PLUMBING
 SEC. 308.6. SUBMIT DETAILS FOR THE BRACING. 2ND
 REQUEST, NO DETAIL FOUND PER RESPOND ?#3 HAS BEEN
 UPDATED. REFER TO REVISED SHEET P803?.
  
 103. DONE.
  
 104. DONE.
  
  
 WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY NECESSARY PAGES.
 A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND, WILL HELP EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 HTTPS://CODES.ICCSAFE.ORG/CODES/FLORIDA
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER / INSPECTOR
 EMAIL: [email protected] OFFICE: 561 805-6720
  

Review Stop P PLUMBING
Rev No 3 Status F Date 2021-02-21 Cont ID  
Sent By tklarge Date 2021-02-21 Time 09:15 Rev Time 0.00
Received By tklarge Date 2021-01-24 Time 03:14 Sent To  
Notes
2021-02-19 11:02:151) SHT. C.03 SHOWS A 15 INCH PVC RWL NEAR THE SOUTHWEST
 CORNER OF THE PROPERTY NEAR THE BUS STOP. THE LINE IS
 NOT SHOWN ON SHT. P100 ( NEAR COLUMN LINE #1). CLARIFY.
 2) SHT.L5-711 - THE POOL DECK SHOWER DOES NOT APPEAR TO
 BE COMPLIANT WITH ANSI A117.1-1986 SEC.4.25.4.FOR FAIR
 HOUSING ACT COMPLIANCE. THE CONTROL RING APPEARS LIKE
 IT MAY REQUIRE GRASPING OR TWISTING OF THE WRIST TO
 OPERATE WHICH WILL VIOLATE THIS SECTION. THE SUBMITTED
 SPECIFICATION SHEET DOES NOT SHOW THAT THIS A HANDICAP
 ACCESSIBLE COMPLIANT UNIT. PROVIDE DOCUMENTATION TO
 SHOW COMPLIANCE.THE RESPONSE NARRATIVE REFERS TO DETAIL
 #8 ON THIS SHEET BUT THE DETAIL SHOWS A PLAN VIEW OF
 THE SHOWER WHICH DOES NOT ADDRESS THIS COMMENT. 2ND
 REQUEST.
 3) SHT. L5-711 - SHOW THE HEIGHT OF THE SHOWER CONTROL
 RING FROM FINISH GRADE TO THE CENTER OF THE CONTROL
 RING IN US CUSTOMARY UNITS.THE SPECIFICATION CURRENTLY
 SHOWS THE MEASUREMENT IN WHAT APPEARS TO BE
 MILLIMETERS. THE HEIGHT OF THE CONTROL RING SHALL
 COMPLY WITH ANSI A117.1-1986 SECS.4.2.5 & 4.2.6.
 4) SHT.A0.203 - ALTERNATIVE ROLL-IN SHOWER W/SEAT - THE
 CONTROLS SHALL BE LOCATED A MAXIMUM OF 15 INCHES FROM
 THE CENTERLIINE OF THE SEAT TO THE CENTERLINE OF THE
 CCONTROLS PER FBC-ACCESS. SEC.608.5.3 AND FIGURE
 608.5.3. THE DRAWING SHOWS THE 15 INCHES TO THE EDGE OF
 THE CONTROL AREA, NOT TO THE CENTER.
 5) SHT. A1.256 - SHT. A1.256 - OFFICE TOWER FLOOR PLAN
 - ROOF LEVEL - SUBMIT INFORMATION FOR THE CHEMICAL
 TREATMENT SYSTEM. SUBMIT MSDS SHEETS FOR THE CHEMICALS
 BEING USED. SUBMIT INFORMATION ON THE AMOUNTS OF EACH
 CHEMICAL BEING USED, WHERE THEY ARE BEING STORED, THE
 TYPES OF CONTAINERS THE CHEMICALS ARE STORED IN, ETC.
 COMPLIANCE WITH SEC. 414 & 415 OF THE 2014 FBC MAY BE
 REQUIRED. THE SUBMITTED RESPONSE NARRATIVE STATES THIS
 SYSTEM IS LIISTED UNDER THE DEFERRED SUBMITTALS ON SHT.
 M.002 BUT IT IS NOT.
 6) SHT.A1.502A - DETAIL #2 DOES NOT SHOW A SEAT IN THE
 SHOWER AND DETAIL #3 SHOWS A SEAT. CLARIFY.
 7) SHT. A1.503 - DETAIL #2 - SHOW THE LOCATION OF THE
 SHOWER CONTROLS. THE LOCATION OF THE CONTROLS SHALL
 COMPLY WITH FBC-ACCESS. SEC.608.5.2.
 8) SHT. A1.532 - MASTER BATH - THE FLOOR PLAN SHOWS THE
 DOOR SWINGING INTO THE SHOWER AND THE TOILET
 COMPARTMENT. THE INSWING DOOR IS IMPEDING ACCESS TO THE
 SHOWER CONTROLS AND THE USE OF THE TOILET AND DOES NOT
 COMPLY WITH FAIR HOUSING. REVERSE THE SWING OF THE
 DOOR.
 9) SHT. A1.532 - SHOW THE REQUIRED CLEAR FLOOR SPACE AT
 ALL THE FIXTURES IN THE FHA ADAPTABLE BATHROOM. WPB
 AMEND. TO FBC SEC. 107.2.1.
 10) SHT.A1.600 - DETAIL #1 - WOMEN'S RESTROOM - THE
 PLAN STATES A CLEAR FLOOR SPACE OF 60 INCHES WIDE FOR
 THE ACCESSIBLE STALL BUT THE PLAN ALSO SHOWS THE INSIDE
 CLEAR WIDTH AS 4 FEET 11 1/2 INCHES. IF THIS IS A ROUGH
 DIMENSION THEN THIS STALL WILL NOT BE WIDE ENOUGH AFTER
 FINISH. COMPLY WITH FBC-ACCESS. SEC.604.3.1.2ND
 REQUEST. CLARIFY.
 11) SHT. A1.600 - SHT.A1.600 - DETAIL #1 - MEN'S
 RESTROOM - ONE OF THE URINALS IS SHOWN AS 1 FOOT 2
 INCHES FROM A WALL TO THE CENTERLINE OF THE URINAL. A
 MINIMUM OF 15 INCHES FROM A WALL TO THE CENTER OF THE
 URINAL IS REQUIRED. FBC-PLUMBING SEC.405.3.1. 2ND
 REQUEST.
 12) SHT. A1.600 - GROUND LEVEL BATHROOM #0132- IS THIS
 A UNISEX TOILET ROOM OR GENDER SPECIFIC? CLARIFY.2ND
 REQUEST.
 13) SHT.A1.601 - DETAIL # 1 - GROUND LEVEL BATHROOM
 #0121 - THE DOOR TO ONE OF THE TOILET ROOMS IS SWINGING
 INTO THE CLEAR FLOOR SPACE FOR THE LAVATORY.
 FBC-ACCESS. SEC. 603.2.3. SEE EXCEPTIONS. SHOW THE
 REQUIRED 30 INCH MINIMUM BY 48 INCH MINIMUM CLEAR FLOOR
 SPACE BEYOND THE ARC OF THE DOOR SWING ON THE PLANS. IT
 IS NOT SHOWN. 2ND REQUEST.
 14) SHT. A1.601 - DETAIL #1 - TOILET ROOM #0121 - THE
 DOOR IS IN FRONT OF THE WATER CLOSET. THE WATER CLOSET
 CANNOT OVERLAP THE REQUIRED MANEUVERING CLEARANCE FOR
 THE DOOR INSIDE THE ROOM. SHOW THE REQUIRED MANEUVERING
 CLEARANCE FOR THE DOOR IN ACCORDANCE WITH FBC-ACCESS.
 404.2.4.
 15) SHT. A1..602 - DETAIL #1 - WOMEN'S RESTROOM #0731-
 SHOW THE INSIDE CLEAR LENGTH OF THE AMBULATORY
 ACCESSIBLE TOILET STALL AND THE STANDARD TOILET STALLS.
 THE DIMENSIONS SHOWN ON THE PLAN ARE NOT CLEAR INSIDE
 DIMENSIONS. FBC-ACCESS. SEC.604.8.2.1,
 604.8.2FBC-PLUMBING SEC.405.3.1.2ND REQUEST.
 16) SHT. A1.603 - DETAILS #1 & #5 - IDENTIFY ON THE
 PLANS THAT THESE BATHROOMS ARE LOCATED IN THE HOTEL.
 2ND REQUEST.
 17) SHT. A1.607 - DETAIL #8 - THERE ARE NOTES ON THE
 PLAN POINTING TO NOTHING AND TO WRONG ITEMS, LOCATION
 OF GRAB BAR REINFORCEMENT IS WRONG,AND THE DOOR SWINGS
 INTO THE SHOWER. A PERSON IN A WHEELCHAIR WOULD NOT BE
 ABLE TO ACCESS THE CONTROLS. REVERSE THE DOOR SWING ON
 THE SHOWER.
 18) SHT. A1.607 - DETAIL #6 - IDENTIFY THE FHA BATHROOM
 TYPE ON THE PLANS.
 19) SHT. A1.608 - DETAIL #5 CALLS OUT A MASTER BATH BUT
 THE FLOOR PLAN SHOWS A KITCHEN. CLARIFY.
 20) SHT. A1.608 - DETAIL #4 - IDENTIFY THE FHA BATHROOM
 TYPE ON THE DETAIL AND PLEASE FIX THE OVERLAY OF THE
 UNIT NUMBER OVER THE COLUMN NUMBER.
 21) SHT. A1.608 - DETAIL #10 - THE LOCATION OF THE GRAB
 BAR REINFORCEMENTS ARE SHOWN IN THE MIDDLE OF THE
 FLOOR. CLARIFY.
 22) SHT. A1.609 - DETAIL #5 - THERE IS AN OVERLAY ON
 THIS DETAIL THAT NEEDS TO BE REMOVED AND ALSO FLOATING
 NOTES. CLEAN UP THIS DETAIL. WPB AMEND. TO FBC SEC.
 107.2.1.
 23) SHT.A1.609 - DETAIL #2 - CLEAN UP THIS DETAIL.
 CLEAR FLOOR SPACE IS SHOWN IN THE CLOSET. IF THIS IS
 SUPPOSED TO BE AN FHA COMPLIANT BATHROOM IT IS NOT. A
 WATER CLOSET CANNOT BE LOCATED NEXT TO THE SHOWER
 BECAUSE THE REQUIRED FLOOOR SPACE FOR THE SHOWER CANNOT
 BE PROVIDED. A NOTE ON THIS DETAIL STATES "BATHROOM 1
 FHA TYPE B." CLARIFY.
 24) SHT. A1.609 - DETAILL # 3 - INDICATE ON THE DETAIL
 IF THIS IS THE FHA COMPLIANT BATHROOM. IF SO, SHOW ALL
 THE REQUUIRED CLEAR FLOOR SPACES, LOCATION OF GRAB BAR
 REINFORCEMENT, AND THE DOORS ON THE SHOWER AND THE
 TOILET CCOMPARTMENT CANNOT SWING IN PER FHA DESIGN
 MANUAL/GUIDELINES.
 25) SHT. A1.609 - DETAIL #4 CALLS OUT BATHROOM 3 BUT
 THERE IS NO BATHROOM PLAN SHOWN. CLARIFY.
 26) SHT. A1.609 - DETAIL #8 - CORRECT THE LOCATION OF
 THE GRAB BAR REINFORCEMENT FOR THE TOILET ON THE PLAN.
 27) SHT. A1.609 - DETAIIL #9 - IF THIS IS SUPPOSED TO
 BE AN FHA COMPLIANT BATHROOM IT IS NOT. A WATER CLOSET
 CANNOT BE LOCATED NEXT TO THE SHOWER BECAUSE THE
 REQUIRED FLOOOR SPACE FOR THE SHOWER CANNOT BE
 PROVIDED. CLARIFY.
 28) SHT. A1.610 - DETAIL # 2 - CLEAN UP THIS PLAN. THE
 LAVATORY IS SHOWN LOCATED PARTIALLY IN THE WALL.
 29) SHT. A1.610 - DETAIL #1 - THE FLOOR PLAN SHOWS THE
 DOOR SWINGING INTO THE SHOWER AND THE TOILET
 COMPARTMENT. THE INSWING DOOR IS IMPEDING ACCESS TO THE
 SHOWER CONTROLS AND THE USE OF THE TOILET AND DOES NOT
 COMPLY WITH FAIR HOUSING. REVERSE THE SWING OF THE
 DOOR.
 30) SHT. A1.610 - DETAIL #3 - THE NOTES AND DETAILS FOR
 THE GRAB BAR REINFORCEMENT DON'T MAKE SENSE. CORRECT
 THE DEFICIENCIES. IF THIS IS SUPPOSED TO BE AN FHA
 OMPLIANT BATHROOM SHOW ALL CLEAR FLOOR FLOOOR SPACES
 AND THE FHA BATHROOM TYPE ON THE PLAN. THE LAVATORY
 APPEARS LIKE ENCROACH INTO THE REQUIRED CLEAR FLOOR
 SPACE FFOR THE SHOWER.CLARIFY.
 31) SHT. A1.610 - DETAIL # 6 - IF THIS IS THE FHA
 COMPLIANT BATHROOM, PLACE THE TYPE OF FHA BATHROOM ON
 THE PLAN AND CORRECT THE OVERLAY OF THE UNIT NUMBER ON
 THE FLOOR PLAN.PLEASE CORRECT THE OVERLAY ON DETAIL #5
 ALSO.
 32) SHT. A1.610 - DETAIL #7 - CORRECT THIS DETAIL.
 LOCATION OF REINFORCEMENT AND CLEAR FLOOR SPACES ARE
 OUT OF WHACK. CONTROLS ARE CALLED OUT ON THE
 LAVATORY.BATHROOM FLOOR PLAN IS CUTOFF AND INCOMPLETE.
 CLARIIFY.
 33) SHT. P1.00 - THERE IS A LINE IDENTIFIED AS "8 INCH
 CWS UP" AND THE ARROW APPEARS TO POINT TO A 10 INCH
 SANITARY LINE. REFER TO COLUMN LINE G-11 NEAR STAIR #1.
 CLARIFY.
 34) SHT. P100 - EXPAND THE PIPING LAYOUT FOR THE
 SANITARY AND VENT LINES AND TAG THE RISERS AT THE
 TOILET ROOMS BY ELEVATORS P03, P04, & P05 ON COLUUMN
 LINE H.
 35) SHT. P100 - ONE OF THE 6 INCH KW LINES BY THE
 GREASE IINTERCEPTORS IS ALSO LABELED AS AN 8 INCH CW
 UP. CLARIFY.
 36) SHT. P100 - THERE ARE A LOT OF DRAIN LINES ON THIS
 PLAN, ESPECIALLY AT THE STAIRS, THAT BEAR NO RISER
 TAGS.CLARIFY.
 38) SHT. P.101 & SHT. P.101B SHOWS AN 8 INCH SANITARY
 LINE WITHIN THE STAIRWAY # 4 AND ALSO A 4 INCH GW LINE
 IN STAIRWAY #10. THE LINE IS NOT PERMITTED WITHIN THE
 STAIRWAY PER FBC-BUILDING SEC.1023.5.
 39) SHTS. P.101A, P.101B, P.101C, & P.101C - THERE ARE
 DRAIN, GAS, RAINWATER, CONDENSATE AND WATER LINES THAT
 HAVE NO RISER TAGS AND SOME RISER TAGS HAVE NO DRAWING
 LOCATIONS ON THEM, RISER TAGS WITH NO ARROWS
 IDENTIFYING THE SPECIFIC LINES, ETC.PROVIDE THE
 REQUESTED INFORMATION ON THESE DRAWINGS. WPB AMEND. TO
 FBC SEC. 107.2.1, 107.3.5.1.3.
 40) IDENTIFY THE STAIR NUMBERS ON THE PLUMBING SHEETS.
 THIS WILL HELP IN DETERMINING THE LOCATION OF PIPE
 SYSTEMS ON THE RE-REVIEW.WPB AMND. TO FBC SEC.
 107.2.1.2ND REQUEST.
 41) SHTS. P.102A, P.102B, P.102C, P.102D - THERE ARE
 DRAIN, RAINWATER, CONDENSATE AND WATER LINES THAT HAVE
 NO RISER TAGS AND SOME RISER TAGS HAVE NO DRAWING
 LOCATIONS ON THEM, RISER TAGS WITH NO ARROWS
 IDENTIFYING THE SPECIFIC LINES, ETC.PROVIDE THE
 REQUESTED INFORMATION ON THESE DRAWINGS. WPB AMEND. TO
 FBC SEC. 107.2.1, 107.3.5.1.3.
 42) SHTS.P.103A, P.103B, P.103C, P.103D - THERE ARE
 DRAIN, RAINWATER, CONDENSATE AND WATER LINES THAT HAVE
 NO RISER TAGS AND SOME RISER TAGS HAVE NO DRAWING
 LOCATIONS ON THEM, RISER TAGS WITH NO ARROWS
 IDENTIFYING THE SPECIFIC LINES, ETC.PROVIDE THE
 REQUESTED INFORMATION ON THESE DRAWINGS. WPB AMEND. TO
 FBC SEC. 107.2.1, 107.3.5.1.3.
 43 - SHTS. P.104A THROUGH SHT. P104D - THERE ARE DRAIN,
 RAINWATER, CONDENSATE AND WATER LINES THAT HAVE NO
 RISER TAGS AND SOME RISER TAGS HAVE NO DRAWING
 LOCATIONS ON THEM, RISER TAGS WITH NO ARROWS
 IDENTIFYING THE SPECIFIC LINES, ETC.PROVIDE THE
 REQUESTED INFORMATION ON THESE DRAWINGS. WPB AMEND. TO
 FBC SEC. 107.2.1, 107.3.5.1.3.
 44) SHTS. P1.05A THROUGH P.105D - THERE ARE DRAIN,
 RAINWATER, CONDENSATE AND WATER LINES THAT HAVE NO
 RISER TAGS AND SOME RISER TAGS HAVE NO DRAWING
 LOCATIONS ON THEM, RISER TAGS WITH NO ARROWS
 IDENTIFYING THE SPECIFIC LINES, ETC.PROVIDE THE
 REQUESTED INFORMATION ON THESE DRAWINGS. WPB AMEND. TO
 FBC SEC. 107.2.1, 107.3.5.1.3.
 45) SHTS. P.106A THROUGH SHT. 106D - THERE ARE DRAIN,
 RAINWATER, CONDENSATE AND WATER LINES THAT HAVE NO
 RISER TAGS AND SOME RISER TAGS HAVE NO DRAWING
 LOCATIONS ON THEM, RISER TAGS WITH NO ARROWS
 IDENTIFYING THE SPECIFIC LINES, ETC.PROVIDE THE
 REQUESTED INFORMATION ON THESE DRAWINGS. WPB AMEND. TO
 FBC SEC. 107.2.1, 107.3.5.1.3.
 46) SHTS. P.107A THROUGH P.107D - THERE ARE DRAIN,
 RAINWATER, CONDENSATE AND WATER LINES THAT HAVE NO
 RISER TAGS AND SOME RISER TAGS HAVE NO DRAWING
 LOCATIONS ON THEM, RISER TAGS WITH NO ARROWS
 IDENTIFYING THE SPECIFIC LINES, ETC.PROVIDE THE
 REQUESTED INFORMATION ON THESE DRAWINGS. WPB AMEND. TO
 FBC SEC. 107.2.1, 107.3.5.1.3.
 47) SHTS. P.108A THROUGH P.108D - THERE ARE DRAIN,
 RAINWATER, CONDENSATE AND WATER LINES THAT HAVE NO
 RISER TAGS AND SOME RISER TAGS HAVE NO DRAWING
 LOCATIONS ON THEM, RISER TAGS WITH NO ARROWS
 IDENTIFYING THE SPECIFIC LINES, ETC.PROVIDE THE
 REQUESTED INFORMATION ON THESE DRAWINGS. WPB AMEND. TO
 FBC SEC. 107.2.1, 107.3.5.1.3.
 48) SHT. P.105D SHOWS 2-4INCH RW LINES WITHIN THE
 STAIRWAY #7. THESE LINES ARE NOT PERMITTED WITHIN THE
 STAIRWAY PER FBC-BUILDING SEC.1023.5.
 49) SHT. P.106D SHOWS FOUR- 4 INCH ROOF DRAINS AND A 4
 INCH RW LINE WITHIN STAIRWAY #7.THE LINES ARE NOT
 PERMITTED WITHIN THE STAIRWAY PER FBC-BUILDING
 SEC.1023.5.
 50) SHTS. P.107A, P.107C & P.107D - THE DRAWINGS SHOW
 RAINWATER DRAIN PIPING AND ROOF DRAINS LOCATED IN
 STAIRWAYS #5, #12, & #7. THESE LINES AND DRAINS ARE NOT
 PERMITTED WITHIN THE STAIRWAY PER FBC-BUILDING
 SEC.1023.5.
 51) SHTS. P.108A, P.108B, P.108C - THE DRAWINGS SHOW
 RAINWATER DRAIN PIPING, DRAINS AND CONDENSATE PIPING IN
 STAIRWAYS #5, 8 & #9. THE LINES AND DRAINS ARE NOT
 PERMITTED WITHIN THE STAIRWAY PER FBC-BUILDING
 SEC.1023.5.
 52) THE OVERALL PIPNG PLANS FOR THE PODIUM LEVELS ARE
 MISSING SECTIONS OF PIPING AND BASICALLY HAVE NO
 INFORMATION ON THEM AND ARE USELESS FOR REVIEW.I
 UNDERSTAND THAT THESE ARE OVERALLL PLANS BUT THE
 DRAWINGS ARE MISSING BASIC ESSENTIAL INFORMATION FOR
 PLAN REVIEW. WPB AMEND. TO FFBC SEC. 107.2.1,
 107.3.5.1.3.
 53) SHTS. P.251 THROUGH 256 - THE RISER TAGS FOR THE LW
 RISERS ARE MISSING THE DRAWING LOCATIONS ON THE RISER
 TAGS. CLARIFY.
 54) SHTS. P. 258 THROUGH P.261 - THE RISER TAGS FOR THE
 LW RISERS ARE MISSING THE DRAWING LOCATIONS ON THE
 RISER TAGS.CLARIFY.
 55) SHT. P.510 - DETAIL #6 - TWO LAVATORIES ARE MISSING
 FROM THE SANITARY RISER. CLARIFY.
 56) SHT. P.510 - DETAIL #3 - A LAVATORY IN THE MEN'S
 AND WOMEN'S HANDICAP STALL IS MISSING FROM SANITARY
 RISER. CLARIFY.
 57) SHT. P.510 - DETAILS #2 & #3 THE DRINKING FOUNTAINS
 ARE MISSING FROM THE SANITARY AND WATER RISERS.
 58) SHT. P.5.11 - DETAIL #4 - ROOMS #0243 & 0245 - THE
 URINAL DOES NOT APPEAR TO BE VENTED. CLARIFY.
 59) SHT. P.511 -DETAIL #4 - THE LAVATORY IN THE
 HANDICAP STALL IN THE WOMEN'S CHANGING FACILITY IS NOT
 SHOWN ON THE SANITARY RISER.
 60) SHT. P.511 - DETAIL #4 - IT APPEARS THERE IS A
 STANDARD WATER CLOSET IN THE WOMEN'S CHANGING FACILITY
 THAT IS NOT SHOWN ON THE SANITARY RISER DIAGRAM.
 61) SHT. P.511 - DETAIL #4 - THE LAVATORY IN THE MEN'S
 HANDICAP STALL IS NOT SHOWN ON THE SANITARY RISER.
 62) SHT. P.511 - DETAIL #4 - THERE IS A LAVATORY ON THE
 RISER DIAGRAM FOR THE MEN'S CHANGING FACILITY THAT IS
 NOT SHOWN ON THE FLOOR PLAN. 61) SHT. P.503 -
 63) SHT. P.513 - DETAIL #1 - REVVISE THIS DETAIL TO
 CLEARLY SHOW THE 3 LAVATORIES IN EACH RESTROOM. THERE
 IS AN OVERLAY THAT CURRENTLY LOOKS LIKE 5 LAVATORIES.
 2ND REQUEST.
 64) SHT. P.514 - DETAI #5 - THE LW RISER TAGS DO NOT
 HAVE DRAWING LOCATIONS ON THE RISER TAGS. CLARIFY.
 65) SHT. P.514 - DETAIL#6 - THE LAVATORY IN THE WOMEN'S
 HANDICAP ACCESSIIBLE STALL IS NOT SHOWN ON THE SANITARY
 RISER. CLARIFY.
 66) SHT. P.701 - THE RISER TAGS AT THE BOTTOM AND TOP
 OF THE HOTEL/OFFICE DOMESTIC WATER RISERS ARE MISSING
 THE DRAWING LOCATIONS. CLARIFY.
 67) SUBMIT A PIPING DETAIL FOR MASTER THERMOSTATIC
 MIXING VALVES TMV-1, TMV-2 & TMV-3. THE PIPING FOR
 RECIRCULATION SYSTEMS HAVING MASTER THERMOSTATIC VALVES
 SHALL CCOMPLY WITH FBC-PLUMBING SEC. 607.2.2. 2ND
 REQUEST.
 68) SHT. P.702 - THERE ARE BRANCHES OFF THE WATER
 RISERS THAT SOME HAVE NO SIZES OR THE AREA THEY SUPPLY.
 REFER TO LEVELS 2-8. SUPPLY THE REQUIRED INFO. WPB
 AMEND. TO FBC SEC. 107.3.5.1.3. 2ND REQUEST.
 69) SHT. P.703 - ALMOST ALL OF THE RISER TAGS ARE
 MISSING DRAWING LOCATION INFORMATION. CLARIFY.
 70) SHT. P.703A & P.703B - THERE ARE DRAWING LOCATION
 NUMBERS MISSING FROM NUMEROUS RISER TAGS ON THESE
 SHEETS.SUPPLY THE APPLICABLE DRAWING LOCATION NUMBERS
 ON THESE TAGS.
 71) SHT. P.703A - THE STACK DESIGNATION TYPE AND RISER
 NUMBERING ON THE RISER TAGS DOES NOT CORRELATE WITH THE
 REFERENCED RISER TAGS ON SHTS. P502 & SHT. P.503.
 CLARIFY.
 72) SHT. P.703B - RISER TAGS ARE MISSING THE DRAWING
 LOCATION NUMBERS ON THE RISER TAGS. ENSURE ALL RISER
 TAGS ARE COMPLETE.
 73) SHT. P.704 - NUMEROUS RISER TAGS ARE MISSING
 DRAWING LOCATION INFORMATION/NUMBERS.
 74) SHT. P.704A - RISER TAGS ARE MISSING THE DRAWING
 LOCATION NUMBERS ON THE RISER TAGS. ENSURE ALL RISER
 TAGS ARE COMPLETE.
 75) SHT. P.704B - RISER TAGS ARE MISSING THE DRAWING
 LOCATION NUMBERS ON THE RISER TAGS. ENSURE ALL RISER
 TAGS ARE COMPLETE.
 76) SHT. P.705A - THE PRINTING ON THE RISER TAGS IS SO
 LIGHT THAT IT IS ILLEGIBLE. PROVIDE LEGIBLE INFO. WPB
 AMEND. TO FBC SEC. 107.2.1.
 77) SHT. SHT. P.706 - DETAILS #7, 8, 10, 11, &12 - ONLY
 4 FIXTURE UNITS ARE ALLOWED ON A 2 INCH WET VENT PER
 FBC-PLUMBING TABLE 912.3. THE HORIZONTAL DRAIN FROM THE
 WATER CLOSET SHALL BE 3 INCHES UP TO THE FIRST
 HORIZONTAL FIXTURE DRAIN (BATHTUB/SHOWER).
 78) SHT. P.706 - DETAIL #9 - THE HORIZONTAL DRAIN FROM
 THE WATER CLOSET UP TO THE FIRST HORIZONTAL BRANCH
 SHALL BE 3 INCHES IN DIAMETER PER FBC-PLUMBING TABLE
 912.3.
 79) SHT. P.706 - DETAIL #10 & #20 - THE BATHTUBS ARE
 NOT VENTED. THEY CANNOT CONNECT DIRECTLY TO THE SHOWER
 OR WATER CLOSET FIXTURE DRAIN. FBC-PLUMBING
 SECS.1002.1, 901.2.
 80) SHT. P.706 - DETAIL #19 - THE DRAIN FROM THE
 WASHING MACHINE BOX TO THE STACK SHALL BE A MINIMUM OF
 3 INCHES IN DIAMETER PERR FBC-PLUMBING SEC.406.2.
 81) SHT. P.707 - DETAILS #1,2,3,4,,& 5 - RISER TAG
 NUMBERS, STACK DESIGNATION AND DRAWING LOCATION
 INFORMATION IS MISSING FROM THE RISER TAGS. ENSURE ALL
 RISER TAGS ARE COMPLETE.
 82) SHT. P.709 - THE DRAIN FROM THE WASHING MACHINE BOX
 TO THE STACK SHALL BE A MINIMUM OF 3 INCHES IN DIAMETER
 PERR FBC-PLUMBING SEC.406.2.
 83) SHT. P.709 - THE DRAWING LOCATION INFORMATION IS
 MISSING FROM ALL OF THE WASTE AN SANITARY STACK RISER
 DIAGRAMS. ENSURE ALL RISER TAGS ARE COMPLETE.
 84) SHT. P.709 - IDENTIFY THE CONTINUATION POINTS OF
 BOTH 6 INCH VERTICAL SANITARY DRAINS THAT TURN DOWN.
 85) SHT. P.710 - DETAIL #5 - THE WATER RISER DIAGRAM
 DOES NOT CORRELATE WITH THE REFERENCED ENLARGED FLOOR
 PLAN DETAIL #5 ON SHT. P.505. THESES ARE TWO DIFFERENT
 UNITS. CLARIFY.
 86) SHT.P.710 - DETAIL #4 - THE WATER CONNECTION FROM
 THE WATER RISER TO THE UNIT IS MISSING. CLARIFY.
 87) SHT. P.711 - DETAIL #2 - THERE IS A BATHTUB MISSING
 ON THE WATER RISER IN ONE OF THE BATHROOMS AND THE
 SHOWER IS LABELED AS A BATHTUB IN THE SAME BATHROOM,
 AND ONLY ONE LAVATORY IS SHOWN ON THE RISER IN THIS
 SAME BATH. CLARIFY.
 88) SHT. P.711 - DETAIL #2 - THERE IS A BATHTUB SHOWN
 ON THE WATER RISER IN THE MASTER BATH BUT IT IS NOT
 SHOWN ON THE FLOOR PLAN AND THE WATER CLOSET AND
 LAVATORY ARE REVRSED ON THE WATER RISER IN THE MASTER
 BATH.. CLARIFFY.
 89) SHT. P.711 - DETAIL #6 -THE LAYOUT OF THE FIXTURES
 ON THE WATER RISER DIAGRAM DOES NOT CORRELATE WITH THE
 LAYOUT OF THE PLUMBING FIXTURES ON REFERENCED SHT.
 P.507, DETAIL #2. ALSO, THE RISER TAG INFORMATION IS SO
 LIGHT IT IS ILLEGIBLE. CLARIFY.
 90) SHT. P.712 - DETAIL #F - THE SANITARY RISER IS
 INCOMPLETE. FIXTURES ARE MISSING. EXPAND THE RIDER SO A
 PROPER REVIEW CAN BE DONE. WPB AMEND. TO FBC SEC.
 107.2.1, 107.3.5.1.3.
 91) SHT. P.712 - THE WATER SUPPLY BRANCHES FROM THE
 RISERS TO THE MEN'S AND WOMEN'S OFFICE TOILET RROOMS
 REQUIRE SHUTOFF VALVES TO RESTROOMS. FBC-PLUMBING SEC.
 606.1.
 92) SHT. P.712 - DETAILS #3, #4, & #6 - THE RISER TAGS
 ARE MISSING THE RISER INFORMATION. ENSURE ALL RISER
 TAGS ARE COMPLETE.
 93) SHT. P.712 - DETAIL #6 - THE DRINKING FOUNTAINS
 SHOWN ON DETAIL #3 ARE NOT SHOWN ON THE WATER RISER ON
 DETAIL #6 OR THE WATER RISER FOR THE OFFICE TOWER -
 WOMEN'S TOILET ROOM. CLARIFY.
 94) SHT. P.720 - IDENTIFY ALL RISERS WITH RISER TAGS
 COMPLETE WITH ALL RISER TAG INFO AND FIXTURE UNIT
 LOADS. THERE ARE STILL RISERS THAT HAVE NO TAGS. WPB
 AMEND. TO FBC SEC. 107.2.1, 107.3.5.1.3.
 95) SHT. P.730 - IDENTIFY ALL RISERS WITH RISER TAGS
 COMPLETE WITH ALL RISER TAG INFO AND THE GPM'S DRAINING
 INTO EACH RISER. WPB AMEND. TO FBC SEC. 107.2.1,
 107.3.5.1.3.
 96) SHT. P.731 - THE DRAWING IS INCOMPLETE.SECTIONS OF
 PIPE ARE MISSING, PIPE SIZES ARE MISSING, NO RISER
 TAGS, SECTIONS OF THE PIPING SYSTEM ARE CONGESTED AND
 DIFICULT TO REVIEW.WPB AMEND. TO FBC SEC. 107.2.1,
 107.3.5.1.3.
 97) SHT. P.732 - THE RISER SHOWS THE SQUARE FOOTAGE
 AREA BEING DRAINED BUT NO GPM'S. COMPLY WITH
 FBC-PLUMBING SEC. 11106.2. CLARIFY.
 98) SHT. P.733- THERE ARE SEVERAL RISER TAGS MISSING
 THE DRAWING LOCATION INFORMATION.ENSURE ALL RISER TAGS
 ARE COMPLETE.
 99) SHT. P.734 - THERE ARE SEVERAL RISER TAGS MISSING
 THE DRAWING LOCATION INFORMATION.ENSURE ALL RISER TAGS
 ARE COMPLETE.
 100) SHT. P.803 - DETAIL #9 - SUBMIT DETAILS AS TO HOW
 THE WOOD BLOCK IS BEING ATTACHED TO THE ROOF. WPB
 AMEND. TO FBC SEC. 107.2.1.2ND REQUEST.
 101) HT. P.803 - DETAIL #3 SHOWS JOINTS UNDER THE SLAB
 - PLUMBING SPECIFICATIONS SEC.221110 - PART 2 - 2.02
 STATES THAT "ENTRANCE PIPING TO THE BUILDING TO
 TERMINATE ABOVE GRADE." THE DETAIL ON P.803 SHOWS
 FLANGED FITTINGS UNDER THE SLAB. CLARIFY. IF THIS
 PIPING ARRANGEMENT IS TO REMAIN, SUBMIT DETAILS ON
 FITTING RESTRAINTS AND THRUST BLOCK INFORMATION. WPB
 AMEND. TO FBC SEC. 107.2.1, 107.3.5.1.3.2ND REQUEST.
 102) RIGID SUPPORT SWAY BRACING SHALL BE PROVIDED AT
 CHANGES IN DIRECTION GREATER THAN 45 DEGREES FOR PIPE
 SIZES 4 INCHES AND LARGER PER FBC-PLUMBING SEC.308.6.
 SUBMIT DETAILS FOR THE BRACING. 2ND REQUEST.
 103) SHT. P.804 - DETAIL #7 - THE REDUCED PRESSURE
 BACKFLOW PREVENTER AT HE TRASH CHUTE REQUIRES A DRAIN
 PIPED TO AN APPROVEDD POINT OF DISPOSAL.M
 104) THE PLUMBING SPECIFICATIONS SECTION 22 1323 - PART
 2 - SECTION 2.01 (GREASE INTERCEPTOR) :TAG # GT-1 -
 SECTION C -ACCESSORIES: CALLS OUT A 4-INCH INFLUENT AND
 EFFLUENT TWO-WAY CLEANOUT, BUT ALSO CALLS OUT A 6-INCH
 SAMPLING PORT. THIS WOULD CREATE AN OBSTRUCTION TO FLOW
 AND VIOLATES FBC-PLUMBING SEC.706.2. THIS SECTION ALSO
 CALLS OUT A SCHIER INTERCEPTOR WITH 6-INCH INLET AND
 OUTLET. CLARIFY. 2ND REQUEST. THE SUBMITTED RESPONSE
 NARRATIVE STATES THE 4 INCH REFERENCE IS INCCORRECT BUT
 THE SPECIFICATION IS STILL WRONG.CORRECT THE
 SPECIFICATION.
 NOTE: WHEN THE REVISED PLANS ARE UPLOADED, ENSURE THEY
 ARE DONE IN SEQUENTIAL ORDER AND THAT ALL PLANS ARE IN
 SEQUENTIAL ORDER. I HAVE WASTED AN INORDINATE AMOUNT OF
 TIME DURING THIS LAST REVIEW SEARCHING THROUGH NUMEROUS
 DRAWINGS TO FIND THE CORRECT PLAN THAT WAS SUPPOSED TO
 HAVE ADDRESSED THE REVIEW COMMENT.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  
  
  
  
  
  
  
  
  
  
  
 .
  

Review Stop P PLUMBING
Rev No 2 Status F Date 2020-03-28 Cont ID  
Sent By tklarge Date 2020-03-28 Time 10:03 Rev Time 0.00
Received By tklarge Date 2020-02-29 Time 05:31 Sent To  
Notes
2020-03-22 04:50:20STEP ADDED BY MISTAKE.
2020-03-22 04:49:29THE FOLLOWING COMMENTS ARE FROM THE PLUMBING PLAN
 REVIEW THAT WAS DONE ON 4/9/2019 THAT HAVE NOT BEEN
 PROPERLY ADDRESSED:
 PLUMBING:
 COMMENT # 2 - PLACE A NOTE ON THE PLANS THAT THE
 RESIDENTIAL TOWER UNITS AND THE COMMON AREAS SHALL
 COMPLY WITH THE FAIR HOUSING ACT REQUIREMENTS AND ANSI
 A117.1 - 1986. THE NOTE THAT WAS PLACED ON THE PLAN
 REFERS TO THE FLORIDA BUILDING CODE ACCESSIBILITY 2014.
 2ND REQUEST.
 COMMENT #32 -ON THE PLUMBING SHEETS, LABEL AND TAG ALL
 RISERS ON ALL FLOOR PLANS. THERE ARE NUMEROUS RISERS
 THAT HAVE NO LABELS OR TAGS AND THERE ARE OTHERS THAT
 HAVE INCOMPLETE INFORMATION ( RISERS ARE LABELED WITH
 NO TAG OR TAGGED WITH NO LABEL). WPB AMEND. TO FBC SEC.
 107.2.1.
 COMMENT #35 - THE PLANS SHOW AIR ADMITTANCE VALVES
 INSTALLED ON SOME OF THE KITCHEN SINKS.WHERE THE
 HORIZONTAL BRANCH IS LOCATED MORE THAN FOUR BRANCH
 INTERVALS FROM THE TOP OF THE STACK, THE HORIZONTAL
 BRANCH SHALL BE PROVIDED WITH A RELIEF VENT THAT SHALL
 CONNECT TO A VENT STACK OR STACK VENT , OR EXTEND
 OUTDOORS TO THE OPEN AIR. I DID NOT SEE WHERE THIS WAS
 DONE. PROVIDE THE SHEET/DRAWING NUMBER(S) THAT WAS
 REVISED TO SHOW COMPLIANCE. WPB AMEND. TO FBC SEC.
 107.2.1, 2014 FBC-PLUMBING SEC. 918.3.1.
 COMMENT # 38 - PROVIDE A COMPLETE SANITARY ISOMETRIC
 DIAGRAM FOR THE UNDERGROUND / UNDERSLAB COLLECTION
 SYSTEM. THE DRAWING SUBMITTED ON SHT. P.720 IS
 INSUFFICIENT AND DEFICIENT IN THE NECESSARY INFORMATION
 TO PERFORM A COMPREHENSIVE REVIEW ON THE DRAWING.WPB
 AMEND. TO FBC SEC. 107.3.5.1.3.
 COMMENT #40 - PLACE A NOTE ON THE PLANS THAT ACCESS
 SHALL BE PROVIDED TO THE WATER SUPPLY SHUTOFF VALVES
 FOR THE STACKABLE WASHING MACHINES IN THE RESIDENTIAL
 UNITS. 2014 FBC-PLUMBING SEC. 606.3. THE RESPONSE
 NARRATIVE FROM THE DESIGN PROFESSIONAL STATES THAT A
 NOTE WAS ADDED TO THE PLANS BUT I COULD NOT LOCATE THIS
 NOTE. PROVIDE THE SHEET/ DRAWING NUMBER WHERE THE NOTE
 CAN BE FOUND. WPB AMEND. TO FBC SEC. 107.2.1.
 COMMENT # 42 - THE ENLARGED PLUMBING FLOOR PLANS APPEAR
 TO HAVE TAGS ON THE STACKS THAT ARE INCOMPLETE.ENSURE
 THAT ALL STACKS/RISERS ARE FULLY LABELED AND TAGGED TO
 MATCH THE ISOMETRIC DRAWING AND FULL FLOOR PLANS.
  
 NEW PLUMBING COMMENTS:
  
 1) PLACE A NOTE ON THE PLANS THAT THE BACKFLOW
 PREVENTERS WILL REQUIRE A SEPARATE PERMIT AND SHALL
 COMPLY WITH 2014 FBC-PLUMBING SEC.605.2.1 AND THE CITY
 OF WEST PALM BEACH CROSS-CONNECTION CONTROL MANUAL.
 2) PLACE A NOTE ON THE PLUMBING PLANS THAT A SEPARATE
 PERMIT IS REQUIRED FOR THE GREASE INTERCEPTORS.
 3) SHT.A1.602 - DETAIL #1 - WOMEN'S RESTROOM - SHOW THE
 INSIDE CLEAR DIMENSIONS (L X W) OF THE HANDICAP
 ACCESSIBLE TOILET COMPARTMENTS AND SHOW THE LENGTH OF
 THE STANDARD TOILET COMPARTMENTS ON THE PLAN. WPB
 AMEND. TO FBC SEC. 107.2.1.
 4) SHT. A1.602 - DETAIL #1 - WOMEN'S RESTROOM - SHOW
 THE LENGTH AND WIDTH DIMENSIONS OF THE AMBULATORY
 ACCESSIBLE TOILET COMPARTMENT ON THE PLANS. COMPLY WITH
 2014 FBC- ACCESS. SECS.604.8.2.1, 604.8.2.2, 604.8.2.3.
 5) SHT. A1.602 - DETAIL #2 - SHOW THE LENGTH OF THE
 AMBULATORY ACCESSIBLE TOILET COMPARTMENT IN THE MEN?S
 RESTROOM. COMPLY WITH 2014 FBC- ACCESS. SECS.604.8.2.1,
 604.8.2.2, 604.8.2.3.
 6) SHT. L5-711 - DETAIL #6 - SUBMIT ADDITIONAL
 DOCUMENTATION FOR THE POOL DECK SHOWER. IF THIS SHOWER
 IS IN THE RESIDENTIAL TOWER POOL AREA, IT SHALL COMPLY
 WITH ANSI A117.1-1986. IF IT IS IN THE HOTEL, THE
 SHOWER CONTROLS SHALL COMPLY WITH THE 2014 FBC-ACCESS.
 SEC. 308 FOR REACH RANGES AND SEC.309 FOR OPERABLE
 PARTS.
 7) SHT. L5-711 - DETAIL #7- SUBMIT ADDITIONAL
 INFORMATION FOR THE WATER FOUNTAIN AT THE POOL DECK. IF
 THIS DRINKING FOUNTAIN IS IN THE RESIDENTIAL TOWER POOL
 AREA, IT SHALL COMPLY WITH ANSI A117.1-1986. IF IT IS
 IN THE HOTEL, THE DRINKING FOUNTAIN SHALL COMPLY WITH
 SECS. 211 AND 602 OF THE 2014 FBC-ACCESS.
 8) SHT. A0.101 - HEADING III - CODE DATA - THERE IS AN
 ITEM STATING, "SWIMMING POOL TABLE NOT REQUIRED PER FBC
 2014 424.1.6.1". THERE IS NO SUCH CODE SECTION IN THE
 2014 FBC. SECTION. 424 IS FOR CHILDREN'S PLAY
 STRUCTURES. CLARIFY.
 9) SHT. A0.101 - APPLICABLE CODES - THE LIST REFERS TO
 THE 2010 EDITION OF THE PLUMBING AND MECHANICAL CODES.
 THIS PROJECT FALLS UNDER THE 2014 EDITIONS OF THE
 PLUMBING AND MECHANICAL CODES. CLARIFY.
 10) SHT. A0.201 - FAIR HOUSING REQUIREMENTS - NOTE #4
 REFERS TO "FBC SECTION 11-4.26.3." THERE IS NO SUCH
 CODE SECTION IN THE 2014 EDITION OF THE FBC. CLARIFY.
 11) SHT. A0.202 - FBC- ACC FIXTURE MOUNTING HEIGHTS AND
 GRAB BAR MOUNTING REQUIREMENTS - GRAB BARS SHALL BE
 MEASURED FROM THE FINISH FLOOR TO THE TOP OF THE
 GRIPPING SURFACE PER 2014 FBC-ACCESS. SEC. 609.4.
 12) SHT. A0.202 - FBC -ACC FIXTURE MOUNTING HEIGHTS -
 SHOW THE HEIGHT OF THE WATER CLOSET ABOVE THE FINISH
 FLOOR. COMPLY WITH 2014 FBC-ACCESS. SEC. 604.4.
 13) SHTS. A0.201, A0.202, & A0.203 - THE DETAILS ARE
 LABELED AS ADA. THESE DETAILS ARE TO BE LABELED AS
 FLORIDA ACCESSIBILITY CODE. THE ADA IS NOT ENFORCED.
 FLORIDA'S ACCESSIBILITY CODE IS A DEPT. OF JUSTICE
 CERTIFIED CODE AS BEING SUBSTANTIALLY EQUIVALENT TO THE
 ADA STANDARDS.
 14) SHT.A0.203 - SHOWER ELEVATIONS - THE SHOWER SPRAY
 UNIT SHALL BE LOCATED NO MORE THAN 48 INCHES ABOVE THE
 SHOWER FLOOR. THE ELEVATION SHOWS 5 FEET. 2014
 FBC-ACCESS. SEC. 608.5.2, 608.5.3.
 15) SHT. A1.107 - MEN'S RESTROOM #0757 & WOMEN'S
 RESTROOM #0756 - THE DOORS FOR THE AMBULATORY
 ACCESSIBLE COMPARTMENTS CANNOT SWING INTO THE MINIMUM
 REQUIRED COMPARTMENT AREA. 2014 FBC-ACCESS.
 SEC.604.8.2.2.
 16) SHT.A1.107 - MEN'S RESTROOM # 0730 - AN AMBULATORY
 ACCESSIBLE TOILET COMPARTMENT IS REQUIRED PER 2014
 FBC-ACCESS. SEC.213.3.1.
 17) SHT. A1.256 - OFFICE TOWER FLOOR PLAN - ROOF LEVEL
 - SUBMIT INFORMATION FOR THE CHEMICAL TREATMENT SYSTEM.
 SUBMIT MSDS SHEETS FOR THE CHEMICALS BEING USED. SUBMIT
 INFORMATION ON THE AMOUNTS OF EACH CHEMICAL BEING USED,
 WHERE THEY ARE BEING STORED, THE TYPES OF CONTAINERS
 THE CHEMICALS ARE STORED IN, ETC. COMPLIANCE WITH SEC.
 414 & 415 OF THE 2014 FBC MAY BE REQUIRED.
 18) SHT. A1-501 - FAIR HOUSING NOTE #3 REFERS TO SEC.
 11-4.26.3. THERE IS NO SUCH SECTION IN THE FAIR HOUSING
 DESIGN MANUAL. CLARIFY.
 19) SHT. A1.503 - DETAIL #2 - HOTEL SUITE 3.1A OR 3.1B
 - THE SEAT IN THE SHOWER SHALL COMPLY WITH FBC-ACCESS.
 SEC. 610.3. AS SHOWN, IT DOES NOT COMPLY.
 20) SHT. A1.600 - DETAIL #1 - WOMEN'S RESTROOM - THE
 PLAN STATES A CLEAR FLOOR SPACE OF 60 INCHES WIDE, BUT
 THE PLAN ALSO SHOWS THE WIDTH OF THIS SPACE AS 4 FEET,
 11 INCHES. CLARIFY. COMPLY WITH FBC-ACCESS.
 SEC.604.3.1.
 21) SHT.A1.600 - DETAIL #1 - MEN'S RESTROOM - ONE OF
 THE URINALS IS SHOWN AS 1 FOOT 2 INCHES FROM A WALL TO
 THE CENTERLINE OF THE URINAL. A MINIMUM OF 15 INCHES
 FROM A WALL TO THE CENTER OF THE URINAL IS REQUIRED.
 FBC-PLUMBING SEC.405.3.1.
 22) SHT.A1.601 - DETAIL # 1 - GROUND LEVEL BATHROOM
 #0121 - THE DOOR TO ONE OF THE TOILET ROOMS IS SWINGING
 INTO THE CLEAR FLOOR SPACE FOR THE LAVATORY.
 FBC-ACCESS. SEC. 603.2.3. SEE EXCEPTIONS.
 23) SHT. A1.601 - THE DOOR IS IN FRONT OF THE WATER
 CLOSET. THE WATER CLOSET CANNOT OVERLAP THE REQUIRED
 MANEUVERING CLEARANCE FOR THE DOOR INSIDE THE ROOM.
 SHOW THE REQUIRED MANEUVERING CLEARANCE FOR THE DOOR IN
 ACCORDANCE WITH FBC-ACCESS. 404.2.4.
 24) SHT. A1.600 - GROUND LEVEL BATHROOM #0132- IS THIS
 A UNISEX TOILET ROOM OR GENDER SPECIFIC? CLARIFY.
 25) SHT. A1.601 - DETAIL #6 -LEVEL 02 BATHROOM 0240 -
 THE BENCHES IN THE MEN'S AND WOMEN'S RESTROOM SHALL
 COMPLY WITH FBC-ACCESS. SEC.903.
 26) SHT. A1.601 - DETAIL #6 - LEVEL 02 BATHROOM 0240 -
 ONE LAVATORY OUTSIDE OF THE STALL IN THE MEN?S AND
 WOMEN?S RESTROOM SHALL COMPLY WITH FBC-ACCESS. SEC.606.
 27) SHT. A1.602 - DETAIL #1 - LEVEL 07 BATHROOM #0759
 -IDENTIFY THE AMBULATORY ACCESSIBLE COMPARTMENT ON THE
 PLANS AND SHOW THE GRAB BARS AND PLACE THE DIMENSIONS
 OF THE STALL ON THE PLANS. COMPLY WITH FBC-ACCESS.
 SEC.604.8.2.
 28) SHOW THE LENGTH OF THE STANDARD TOILET COMPARTMENTS
 ON THE PLANS. COMPLY WITH FBC-PLUMBING SEC.405.3.1.
 29) SHT. A1.602 - DETAIL #1 - LEVEL 07 BATHROOM #0759 -
 ONE LAVATORY OUTSIDE OF THE STALL IN THE WOMEN?S
 RESTROOM SHALL COMPLY WITH FBC-ACCESS. SEC.606.
 30) SHT. A1.602 - DETAIL #2 - LEVEL 8 BATHROOM 08119 -
 IDENTIFY THE HANDICAP ACCESSIBLE URINAL. SHOW THE
 REQUIRED CLEAR FLOOR SPACE ON THE PLAN. FBC-ACCESS.
 SECS. 605, 305.
 31) SHT. A4.300 - DETAIL #2- SUBMIT A DETAIL FOR THE
 OVERFLOW SCUPPER FOR THE OPEN DECK ON LEVEL 6 -PODIUM.
 SHOW THE DIMENSIONS OF THE SCUPPER.
 31) SHT. A5.110 - DETAILS #7 & #8 - THERE ARE SYMBOLS
 IN THESE STAIR ENCLOSURES THAT LOOK LIKE DRAINS.
 CLARIFY. COMPLY WITH FBC-BUILDING SEC. 1022.5.
 32) SHT. A1.118 - DETAILS A & B - DRAINS ARE SHOWN IN
 THE STAIR ENCLOSURE. THESE ARE NOT PERMITTED PER
 FBC-BUILDING SEC. 1022.5.
 33) SANITIZING UNIT FOR THE TRASH CHUTE WILL REQUIRE A
 HIGHER DEGREE OF BACKFLOW PROTECTION OTHER THAN A
 VACUUM BREAKER PER FBC-PLUMBING SEC.608.1, 608.5.
 34) SHT. A7.501 - PROVIDE DETAILS IF THERE ARE SEPARATE
 SHUTOFF VALVES FOR THE TUBS AND IF SO, HOW IS ACCESS
 GOING TO BE PROVIDED TO THE SHUTOFF VALVES?
 FBC-PLUMBING SEC.606.2.
 35) SHT. A7.502 - DETAIL #2 - THE HIGH POINT AT THE
 SHOWER SHALL NOT EXCEED 1/2 OF AN INCH PER FBC-ACCESS.
 SEC. 303, 608.7.
 36) SHT. A0.204 - GROUND LEVEL - MERCANTILE - THE
 PLUMBING FIXTURE TABLE NOTES 1 DRINKING FOUNTAIN AND 1
 WATER COOLER TO BE PROVIDED. A MINIMUM OF TWO DRINKING
 FOUNTAINS ARE REQUIRED PER FBC- PLUMBING SEC. 410.2,
 FBC-ACCESS. SEC. 211.2. A SERVICE SINK IS ALSO REQUIRED
 PER FBC-PLUMBING TABLE 403.1. THE SUBSTITUTION FOR
 WATER COOLERS SHALL COMPLY WITH FBC-PLUMBING SEC.410.3.
 37).37) WHERE ONE DRINKING FOUNTAIN IS LISTED AS BEING
 REQUIRED, A MINIMUM OF TWO DRINKING FOUNTAINS SHALL BE
 PROVIDED IN ACCORDANCE WITH FBC-PLUMBING SEC.410.2 AND
 FBC-ACCESS. SEC. 211.2.
 38) 8TH LEVEL AMENITIES - ASSEMBLY-2-BAR- PROVIDE THE
 OCCUPANT LOAD AND FIXTURE REQUIREMENTS FOR THIS AREA.
 THE PLAN NOTES "PENDING" CLARIFY.
 39) THE SUBSTITUTION FOR WATER COOLERS SHALL COMPLY
 WITH FBC-PLUMBING SEC. 410.3.
 40) THERE IS A FOOTNOTE AT THE BOTTOM OF THE PLUMBING
 FIXTURE CHART ON SHT. A0.204 THAT REFERS TO FBC SEC.
 403.6 FOR THE EXCEPTION OF SANITARY FACILITIES FOR
 PUBLIC SWIMMING POOLS. SECTION 403.6 OF THE
 2014FBC-BUILDING REFERS TO ELEVATORS IN HIGH RISE
 BUILDINGS. THE CORRECT CODE SECTION IS 454.1.6
 EXCEPTION. PLEASE EXPLAIN HOW ALL THE LIVING UNITS CAN
 BE WITHIN A 200 FEET HORIZONTAL RADIUS OF THE NEAREST
 WATER'S EDGE.
 41) SHT. A1.269 A - THE COVERED DWELLING UNITS THAT
 HAVE DOUBLE BASINS SHALL HAVE THE CLEAR FLOOR SPACE
 CENTERED ON ONE OF THE BASINS PER THE FAIR HOUSING
 DESIGN MANUAL.
 42) SHT. A1.502A - THIS SHEET HAS FAIR HOUSING NOTES ON
 IT. THIS SHEET IS FOR THE HOTEL ROOMS. THE FAIR HOUSING
 ACT DOES NOT APPLY. THIS IS THE FBC-ACCESS. DELETE THIS
 FAIR HOUSING NOTE FROM THE PLAN. WPB AMEND. TO FBC SEC.
 107.2.1. SEE SHEETS A1.507 AND A1.508 ALSO.
 43) A1.603 - INDICATE ON THE PLANS IN WHICH BUILDING
 THESE SANITARY FACILITIES ARE LOCATED WPB AMEND. TO FBC
 SEC. 107.2.1.
 44) A1.603 - DETAIL # 1 - LEVEL 07 BATHROOM 0760. -
 SHOW THE REQUIRED AMBULATORY ACCESSIBLE COMPARTMENT ON
 THE PLANS. SHOW THE GRAB BARS AND ALL DIMENSIONS.
 45) A1.603 - SHOW THE LOCATION AND THE CLEAR FLOOR
 SPACE FOR THE ACCESSIBLE URINAL AND THE REQUIRED
 HANDICAP LAVATORY OUTSIDE THE TOILET COMPARTMENT.
 FBC-ACCESS. SEC.213.3.4, 213.3.3.
 46) SHT. A1.603 - DETAIL # 5 - LEVEL 8 BATHROOM 0835 -
 THE DOOR ON THE HANDICAP ACCESSIBLE STALL IS SWINGING
 INTO THE COMPARTMENT. DOORS SHALL NOT SWING INTO THE
 MINIMUM REQUIRED COMPARTMENT AREA. FBC-ACCESS. SEC.
 604.8.1.2.
 47) SHT. A1.604 - DETAIL #1 - LEVEL 07 BATHROOM 0742
 AND 0741 - THE DOOR OF THE AMBULATORY STALL CANNOT
 SWING INTO THE MINIMUM REQUIRED COMPARTMENT AREA.
 FBC-ACCESS. SEC 604.8.2.2.
 48) A1.604 - DETAIL #1 - SHOW THE REQUIRED ACCESSIBLE
 LAVATORY OUTSIDE THE TOILET COMPARTMENT PER FBC-ACCESS.
 SEC.213.3.4 AND SHOW THE REQUIRED CLEAR FLOOR SPACE.
 49) SHT. A1.604 - DETAIL #7 - TWO OF THE TOILET STALLS
 SHOW A WIDTH OF 29 INCHES. THE MINIMUM WIDTH IS 30
 INCHES. FBC-PLUMBING SEC.405.3.1.
 50) SHT. A1.604 - DETAIL #7 - SHOW THE REQUIRED
 ACCESSIBLE LAVATORY AND CLEAR FLOOR SPACE FOR A
 LAVATORY OUTSIDE THE TOILET COMPARTMENT. FBC-ACCESS.
 213.3.4. SHOW THE GRAB BARS FOR THE WATER CLOSET IN THE
 HANDICAP ACCESSIBLE COMPARTMENT.
 51) SHT. A1.605 - SHOW THE LOCATION OF THE COMPARTMENT
 DOOR ON THE FLOOR PLAN. COMPLY WITH FBC-ACCESS.
 SEC.604.8.1.2.
 52) SHT. A1.606 - DETAIL #13 - THE WATER CLOSET SHALL
 BE LOCATED 18 INCHES TO THE CENTERLINE FROM THE EDGE OF
 THE BATHTUB PER THE FHA DESIGN MANUAL.
 53) DIAPER CHANGING STATIONS ARE REQUIRED IN THE
 RESTROOMS SERVING THE POOLS. IDENTIFY THIS ITEM IN THE
 RESTROOMS SERVING THE POOLS. FBC-BUILDING SEC.
 454.1.6.1.
 54) SHT. P100 SHOWS A 12-INCH RAINWATER LINE BY COLUMN
 #6 BUT THIS LINE IS NOT SHOWN ON SHT. C.03. CLARIFY.
 55) SHT. P.100 - THERE IS A 4-INCH CONDENSATE LINE BY
 COLUMN LINE #6, A 6-INCH CONDENSATE LINE BY COLUMN LINE
 8, AND A 4-INCH CONDENSATE LINE BY COLUMN LINE #1 THAT
 STATES "FOR CONTINUATION REFER TO CIVIL DRAWINGS."
 THESE LINES ARE NOT SHOWN ON THE CIVIL DRAWINGS. REFER
 TO THE SPECIFIC CIVIL DRAWING WHERE THESE LINES CAN BE
 FOUND OR SUBMIT THE APPLICABLE DRAWINGS IF THEY ARE NOT
 IN THIS SUBMITTAL. WPB AMEND. TO FBC SEC. 107.2.1.
 56) SHT. P100 - SHOW THE LOCATION OF THE WATER SERVICE
 ON THIS PLAN BY COLUMN LINE #10. WPB AMEND. TO FBC SEC.
 107.2SUBMIT DETAILS FOR THE GAS/OIL SEPARATOR. THE
 SEPARATOR SHALL COMPLY WITH FBC-PLUMBING SEC. 1003.4.2.
 57) SUBMIT DETAILS OF THE ELEVATOR SUMP/ SUMP PIPING.
 WPB AMEND. TO FBC SEC. 107.2.1.
 58) SHT.P101 - THE PIPING SYSTEM IS EXTREMELY DIFFICULT
 TO REVIEW. MOST OF THE PIPING SYSTEMS ARE NOT
 IDENTIFIED, PIPELINES HAVE NO CONTINUATION POINTS, ETC.
 THE SHEET IS NOT COMPLETE ENOUGH FOR REVIEW. WPB AMEND.
 TO FBC SEC. 107.2.1.
 59) IDENTIFY THE STAIR NUMBERS ON THE PLUMBING SHEETS.
 THIS WILL HELP IN DETERMINING THE LOCATION OF PIPE
 SYSTEMS ON THE RE-REVIEW. WPB AMEND. TO FBC- SEC.
 107.2.1.
 60) ON THE MAJORITY OF THE PLUMBING DRAWINGS THERE ARE
 SYMBOLS INDICATING PIPES GOING VERTICAL BUT THERE ARE
 NO PIPES ATTACHED, LINES AND RISERS HAVE NO
 IDENTIFICATION TAGS AS TO WHAT THEY ARE, PIPES GOING
 NOWHERE, NO CONTINUATION LINES, NUMEROUS SYMBOLS
 (CIRCLES) ON THE DRAWINGS WITH NO IDENTIFICATION, PIPE
 LINES SO CONGESTED TOGETHER THEY ARE ILLEGIBLE, AND
 SECTIONS OF PIPE TO NOWHERE. PLEASE CLEAN THESE
 DRAWINGS UP SO A PROPER REVIEW CAN BE DONE. WPB AMEND.
 TO FBC SEC. 107.2.1.
 61) SHT. P102C SHOWS A 1-INCH CD LINE FROM A FCU. FROM
 WHERE? WHERE DOES IT BEGIN AND TERMINATE? INDICATE ON
 THE PLANS.
 62) THE PLUMBING SHEETS SHOULD BE IDENTIFIED AS TO
 BEING FOR THE HOTEL/ OFFICE OR THE RESIDENTIAL TOWER.
 WPB AMEND. TO FBC SEC. 107.2.1.
 63) PLACE A PROPER KEY PLAN ON THE PLAN SHEETS. THE
 SAME KEY PLAN IS ON EVERY SHEET. WPB AMEND. TO FBC SEC.
 107.2.1.
 64) SHT. P1.05 - THIS SHEET NEEDS TO BE REPLACED. AS
 IS, IT IS NOT REVIEWABLE.
 65) SHT. P1.06 - THE PIPELINES AND PIPE SYMBOLS ARE SO
 CONGESTED THIS SHEET CANNOT BE REVIEWED.
 66) SHT. P.223 - THERE ARE GRAY HEART SHAPED DESIGNS ON
 THIS SHEET AND OTHER SHEETS THAT ARE MAKING THE REVIEW
 DIFFICULT. SUBMIT REVISED SHEETS.
 67) SHT. P.233 - PIPELINES ARE SO CONGESTED AT THE
 RESTROOMS THAT THE PLANS CANNOT BE REVIEWED. SUBMIT A
 REVISE PLAN THAT IS LEGIBLE. WPB AMEND. TO FBC SEC.
 107.2.1.
 68) SHT. P.252 - THERE ARE SYMBOLS FOR PIPES GOING UP
 AND NO RISER TAGS, NO IDENTIFICATION, LINES TERMINATING
 NOWHERE, NO RISER TAGS. MOST OF THE SUBMITTED PLANS
 MIRROR THIS CONDITION AND CANNOT BE PROPERLY REVIEWED.
 69) SHT. P.262 SHOWS A 6-INCH ROOF DRAIN FOR THE
 COOLING TOWER BLOWDOWN. COOLING TOWER WATER IS
 PROHIBITED FROM DISCHARGING TO THE STORMWATER SYSTEM
 PER CITY OF WEST PALM BEACH CODE OF ORDINANCES CHAPTER
 90, ARTICLE III, SEC. 90-126 (B) (5).
 70) THE DOMESTIC WATER RISERS FOR THE RESIDENTIAL UNITS
 SHOW INCOMPLETE SECTIONS OF PIPING GOING NOWHERE, PIPE
 LINES ARE NOT IDENTIFIED AS TO USE, SOME PLUMBING
 FIXTURES ARE NOT IDENTIFIED ON THE RISERS, THE WATER
 PIPING FOR SOME OF THE FIXTURES ARE NOT SHOWN ON THE
 WATER RISERS. THIS COMMENT IS TYPICAL FOR MOST OF THE
 WATER RISERS. EACH RISER SHALL BE CHECKED FOR ACCURACY
 AND REVISED AS NECESSARY. WPB AMEND. TO FBC SEC.
 107.2.1, 107.3.5.1.3.
 71) SHT. P.509 - DETAIL #1, #2, #3 SHOWS NPCW TO POOL
 AND SPA FILL SYSTEM. WHAT IS THE SOURCE OF THE
 NON-POTABLE COLD WATER? NON-POTABLE WATER PIPING SHALL
 BE IDENTIFIED IN ACCORDANCE WITH 2014FBC-PLUMBING
 SEC.608.8 ? 608.8.10. SUBMIT DETAILS FOR COMPLIANCE.
 THIS APPLIES TO ANY OTHER PORTIONS OF THE BUILDINGS
 THAT WILL UTILIZE NON-POTABLE WATER.
 72) SHT. P.701 - THE 4-INCH CW-X TO 3-INCH CW-3 OFFICE
 TOWER MAIN SHOWS TYPICAL 1 INCH AND 2-INCH BRANCHES OFF
 THE MAIN. WHAT DO THESE BRANCHES SUPPLY? IF THEY ARE
 FUTURE, THERE SHALL BE A VALVE AND CAP AND DESIGNATED
 AS FUTURE.
 73) SHT. P.701 - THERE SHALL BE A FULL-OPEN VALVE AT
 THE BASE OF THE 4-INCH CW-X RISER FOR THE OFFICE TOWER
 PER FBC-PLUMBING SEC.606.1 (4).
 74) SHT. P.701 - A FULL OPEN VALVE IS REQUIRED ON THE
 TOP OF THE HOT WATER RECIRCULATION LINES PER
 FBC-PLUMBING SEC. 606.1 (5).
 75) SHT. P.702 - THERE IS A 2 - INCH COLD WATER LINE
 LABELED AS CW-1 ON LEVEL 1 THAT TERMINATES TO A TEE
 WITH 2 BRANCHES. THERE ARE NO PIPE SIZES ON THESE
 BRANCHES OR WHAT THEY SUPPLY. CLARIFY.
 76) SHT. P.702 - THERE ARE BRANCHES OFF THE WATER
 RISERS THAT SOME HAVE NO SIZES OR THE AREA THEY SUPPLY.
 REFER TO LEVELS 2-8. SUPPLY THE REQUIRED INFO. WPB
 AMEND. TO FBC SEC. 107.3.5.1.3.
 77) SHT. P.705 & P.705A - SOME OF THE SANITARY
 ISOMETRICS SHOW THE WATER CLOSET AS S-TRAPPED. CLARIFY.
 78) SHT. P.705 - DETAIL #2 - CLARIFY THE VENTING FOR
 THE KITCHEN SINK. THE DETAIL IS CONFUSING. CLARIFY. IF
 AN AIR ADMITTANCE VALVE IS BEING USED, IT MUST HAVE A
 RELIEF IF THE HORIZONTAL BRANCH IS LOCATED MORE THAN
 FOUR BRANCH INTERVALS FROM THE TOP OF THE STACK.
 FBC-PLUMBING SEC. 918.3.1.
 79) SHT. P.705 - DETAIL #3 - THE WASTE STACK IS LABELED
 AS A VENT STACK AND THE VENT STACK IS LABELED AS A
 WASTE STACK. CLARIFY.
 80) SHT. P.705 - DETAIL #7 - CLEARLY SHOW THE WATER
 CLOSET CONNECTION LAVATORY CONNECTION TO THE STACKS.
 THERE IS PIPE MISSING ON THIS RISER.
 80) SHT. P.705 - DETAIL #5 - WHAT ELSE IS CONNECTED TO
 THE SANITARY DRAIN? THERE IS NOTHING SHOWN. IS IT A
 TUB, SHOWER? CLARIFY.
 81) SHT. P7.06 - DETAILS #1, #2, #3 & #5 - CLEAN UP THE
 RISERS. THERE ARE SECTIONS OF PIPE MISSING. THE RISER
 IS INCOMPLETE.
 82) THE SANITARY AND VENT RISER FOR THE HOTEL ONLY GOES
 UP TO THE LEVEL 7 PODIUM. WHAT ABOUT THE REST OF THE
 UPPER FLOORS? SUBMIT A COMPLETE SANITARY VENT AND RISER
 SHEET SHOWING ALL FLOORS. WPB AMEND. TO FBC SEC.
 107.2.1, 107.3.5.1.3.
 83) SHTS. P 7.06 (DETAIL #5), P.707 (DETAILS #1-#5),
 P.708 (DETAILS #4 & #6) P.709 ? (DETAILS #$ & #6) -
 CLARIFY THE PIPING CONNECTIONS TO THE STACK. THE RISERS
 ARE CONGESTED AND VERY DIFFICULT TO REVIEW. THERE ARE
 SECTIONS OF PIPING TO NOWHERE. RISER TAGS ARE MISSING,
 PIPELINES AND SECTIONS OF PIPE ARE MISSING, HOT AND
 COLD-WATER LINES NOT IDENTIFIED ON THE RISERS, WATER
 PIPING MISSING FOR THE WATER CLOSET ON DETAILS #4 & #6.
 84) SHT. P.707 - DETAILS #1,2,3,4 &5 - RISER TAG
 NUMBERS ARE MISSING, IDENTIFICATION ARROWS POINTING TO
 NOTHING, STRAY LINES ON THE RISE. CLEAN UP THE RISERS.
 SHT. P.709 - DETAIL #4 - RISER IS INCOMPLETE.
 85) SHT. P701A - SUBMIT A PIPING DETAIL OF THE TMV AND
 THE PIPING CONNECTED THERETO. THE PIPING SHALL COMPLY
 WITH FBC-PLUMBING SEC.607.2.2.
 86) SHT.P.701B - THE VERTICAL 4-INCH LINE CW-X IS SHOWN
 AS 4 INCHES ON LEVEL 18 AND ALSO SHOWN AS 3 INCHES ON
 LEVEL 19. CLARIFY.
 87) SHT. P702A - THE 6-INCH LINE CW-X IS ALSO SHOWN AS
 3 INCH. CLARIFY,
 88) SHT.P703A - THE RISER TAGS REFER TO SHEETS P.502
 AND P.503. THE RISERS ARE NOT SHOWN ON THESE SHEETS.
 CLARIFY.
 89) SHT. P.709A - RISERS SS/2, SS/3, WS/2 - THE WATER
 CLOSET, BATHTUB AND SHOWER ARE NOT PROPERLY VENTED.
 FBC-PLUMBING SEC. 901.2.1.
 90) SHT. P.710 - DETAILS #1 THROUGH #6 - THERE ARE
 WATER LINES MISSING, HOT AND COLD-WATER LINES CALLED
 OUT AND NOTHING IS SHOWN, FIXTURES MISSING, PARTIAL
 SANITARY LINES SHOWN, THE RISERS ARE INCOMPLETE,
 IDENTIFY ALL FIXTURES ON THE WATER RISERS.
 91) SHT. P.711 - DETAILS #1 THROUGH #5 - THERE ARE
 WATER LINES MISSING, HOT AND COLD-WATER LINES CALLED
 OUT AND NOTHING IS SHOWN, FIXTURES MISSING, PARTIAL
 SANITARY LINES SHOWN, THE RISERS ARE INCOMPLETE,
 IDENTIFY ALL FIXTURES ON THE WATER RISERS.
 92) SHT.P.712 - THE LAVATORY IS MISSING FROM THE
 SANITARY RISER ON DETAIL - "C".
 93) SUBMIT WATER RISER DIAGRAM FOR THE TOILET ROOMS ON
 SHT. P.712. WPB AMEND. TO FBC SEC. 107.3.5.1.3.
 94) SHT. P.720 - SUBMIT A COMPLETE UNDER
 SLAB/UNDERGROUND SANITARY RISER DIAGRAM FOR REVIEW. ALL
 THE RISERS SHALL BE IDENTIFIED BY RISER NUMBER TAGS,
 PIPE SIZES SHALL BE SHOWN, FIXTURE UNIT LOADS, SLOPE OF
 PIPE, REQUIRED CLEANOUTS, GREASE WASTE PIPING AND ALL
 POINTS OF CONNECTION. THE SUBMITTED SHEET P.720 IS
 UNACCEPTABLE, SEVERELY DEFICIENT AND CANNOT BE
 REVIEWED. WPB AMEND. TO FBC-SEC. 107.3.5.1.3.
 95) SHT. P.730 - SUBMIT A COMPLETE UNDER
 SLAB/UNDERGROUND STORM RISER DIAGRAM FOR REVIEW. ALL
 THE RISERS SHALL BE IDENTIFIED BY RISER NUMBER TAGS,
 PIPE SIZES SHALL BE SHOWN, REQUIRED CLEANOUTS AND ALL
 POINTS OF CONNECTION. THE SUBMITTED SHEETT. IS
 UNACCEPTABLE AND DEFICIENT.
 WPB AMEND. TO FBC-SEC. 107.3.5.1.3.
 96) INDICATE ON THE RAINWATER PLANS THE PITCH OF THE
 PIPE USED FOR THE ABOVEGROUND HORIZONTAL STORM DRAIN
 PIPING AND THE RAINFALL RATE USED IN THE DESIGN OF THE
 STORMWATER SYSTEM. FBC-PLUMBING SEC.1106.1.
 97) SHT. P.732 - DETAIL #2 - THE RAINWATER RISER IS
 INCOMPLETE. THERE ARE LINES MISSING AND CONNECTION
 POINTS MISSING.
 98) SHT.P.734 - THERE ARE SECTIONS OF THE RISER DIAGRAM
 MISSING AND PIPE SIZES MISSING ON SOME OF THE LINES.
 PIPING IS NOT IDENTIFIED, PORTIONS OF THE RISER ARE TOO
 CONGESTED AND DIFFICULT TO REVIEW, NP CONTINUATION
 POINTS .SUBMIT A REVISED SHEET FOR REVIEW.
 99) SHT. P.503A - THERE ARE ARROWS CALLING OUT VENT
 PIPES, WASTE STACKS, AND CONDENSATE RISERS AND NOTHING
 IS SHOWN. CLARIFY.
 100) SHT. P.505 - THERE IS A RISER TAG DW/P702A
 POINTING TO A RISER LOCATION BUT THERE IS NOTHING
 THERE. CLARIFY.
 101) CLEANOUTS ARE REQUIRED IN THE BASE OF EACH WASTE
 OR SOIL STACK PER FBC-PLUMBING SEC.708.3.4. BUILDING
 SEWERS SHALL BE PROVIDE WITH CLEANOUTS EVERY 100 FEET
 IN ACCORDANCE WITH FBC-PLUMBING SEC.708.3.2.
 102) SHT. P.511 - DETAIL #1 - ONE OF THE WATER CLOSETS
 IS MISSING ON THE SANITARY RISER.
 103) SHT. P.511 - ALL HOSE BIBBS SHALL BE SEPARATELY
 VALVED PER FBC-PLUMBING SEC. 606.2 (2).
 104) SHT.P.511 - DETAIL #5 - A LAVATORY IN THE MEN'S
 RESTROOM IS MISSING ON THE WATER RISER.
 SHT. P.511 - DETAIL #6 - SHOWS VENTS ON THE FLOOR
 DRAINS. AS DRAWN, THESE VENTS WILL BE IN THE MIDDLE OF
 THE FLOOR OF THE RESTROOM. CLARIFY.
 105) SHT. P.513 - DETAIL #1 - REVISE THE DRAWING TO
 CLEARLY SHOW THE BANK OF LAVATORIES IN EACH RESTROOM.
 THERE IS AN OVERLAY THAT MAKES IT DIFFICULT TO REVIEW.
 THERE IS ALSO A PARTIAL SANITARY DIAGRAM ON THE LEFT
 SIDE OF THE PAGE THAT GOES NOWHERE.
 106) SHT. P.513 - THE WATER RISER FOR THE LEVEL 8
 RESTROOM #0822 IS OVERLAYED ONTO THE SANITARY RISER SO
 A REVIEW COULD NOT BE DONE. SUBMIT A CLEAN PAGE FOR
 REVIEW.
 107) SHT. P.513 - DETAILS #4 & #5 - THE LAYOUT OF THE
 FIXTURES ON THE WATER RISER FOR THE LEVEL 7 TOILET
 ROOMS #07-58/07-59 DOES NOT MATCH THE LAYOUT ON THE
 SANITARY RISER. IT APPEARS THE WATER RISER IS FOR THE
 LEVEL 8 TOILET ROOM. CLARIFY.
 108) SHT. P.514 - DETAILS #3 & #1-THE PLAN VIEW SHOWS 4
 WATER CLOSETS IN A ROW AND THE WATER RISER SHOWS 5.
 CLARIFY.
 109) ) SHT.P.514 - DETAIL #3 - THE HANDICAP WATER
 CLOSET IS NOT SHOWN ON THE WATER RISER. CLARIFY.
 110) SHT. P.514 - DETAIL #5 - SHOW THE CONTINUATION
 POINT OF THE 6-INCH SANITARY RISER ON THE PLANS.
 111) SHT. P.514 -DETAIL #5 - THE FLOOR DRAINS ARE NOT
 SHOWN ON THE SANITARY ISOMETRIC. CLARIFY.
 112) SHT. P.514 - THERE ARE VENTS SHOWN ON THE FLOOR
 DRAINS. AS, DRAWN, THE VENTS WILL BE LOCATED IN THE
 MIDDLE OF THE FLOR. CLARIFY.
 113) SHT. P.514 - DETAIL #3 - THERE ARE 5 WATER CLOSETS
 IN A ROW SHOWN ON THE WATER RISER AND FOUR ON THE FLOOR
 PLAN AND THE ACCESSIBLE WATER CLOSET IN THE MEN?S
 RESTROOM IS NOT SHOWN ON THE WATER RISER. CLARIFY.
 114) SHT. P.514 - DETAIL #6 - THE LAVATORY IN THE
 HANDICAP ACCESSIBLE TOILET COMPARTMENT IS NOT SHOWN ON
 THE SANITARY RISER. CLARIFY.
 115) SHT. P.802 - SHOW PROVISIONS FOR THERMAL EXPANSION
 FOR THE HOT WATER SYSTEM. FBC-PLUMBING SEC. 607.3.
 116) SHT.P8.02 - DETAIL #7 REFERS TO DETAIL #3 OF THIS
 SAME SHEET FOR WATER HEATER INFO. DETAIL #3 IS
 CONDENSATE DRAIN DETAIL. THE CORRECT DETAIL IS # 7.
 REVISE THE NOTE.
 117) SHT. P.803 - DETAIL #1 & #2 - THE BACKFLOW
 PREVENTION DEVICES SHALL BE LEAD FREE AND BE ON THE
 UNIVERSITY OF SOUTHERN CALIFORNIA'S FOUNDATION FOR
 CROSS CONNECTION CONTROL LIST OF APPROVED DEVICES.
 118) SHT. P8.03 - DETAIL #9 - SUBMIT DETAILS AS TO HOW
 THE WOOD BLOCK IS BEING ATTACHED TO THE ROOF. WPB
 AMEND. TO FBC SEC. 107.2.1.
 119) SHT. P.803 - DETAILS #1 & #2 - PLACE A NOTE BY THE
 BACKFLOW DETAILS THAT A SEPARATE PERMIT IS REQUIRED FOR
 THE BACKFLOW PREVENTERS.
 120) SHT. P.804 - DETAIL #3 - THE NOTES ARE BARELY
 LEGIBLE. THERE IS AN OVERLAY OF OTHER NOTES. CLARIFY.
 WPB AMEND. TO FBC-SEC. 107.2.1.
 121) SHT. P.804 - DETAIL #3 - THE OIL SEPARATOR SHALL
 COMPLY WITH FBC-PLUMBING SEC. 1003.4.2, 1003.4.2.1.
 122) SHT. P.510 - DETAIL #6 - THERE IS A LAVATORY
 MISSING FROM THE SANITARY RISER IN THE MEN-S RESTROOM
 #0121.CLARIFY.
 123) SHT. P.510 - DETAIL #6 - TWO LAVATORIES ARE
 MISSING FROM THE SANITARY RISER. CLARIFY.
 124) SHT. P.510 - DETAIL #3 - TOILET ROOMS 01-51 &
 01-52 - THE DRINKING FOUNTAIN IS MISSING ON THE
 SANITARY RISER. CLARIFY.
 125) SHT. P.510 - DETAIL #6 SHOWS A FLAT, DRY VENT ON
 THE FLOOR DRAIN. COMPLY WITH FBC-PLUMBING SEC.905.3.
 126) SUBMIT MANUFACTURER'S SPECIFICATIONS AND
 INSTALLATION INSTRUCTIONS FOR THE MEMBRANE SYSTEM FOR
 THE SHOWERS. THE SYSTEM BEING USED SHALL COMPLY WITH
 THE APPLICABLE CODE SECTIONS IN THE FBC-PLUMBING CODE
 SECS.417.5, 417.5.2, 417.5.2.5, 417.5.2.6.
 127) THE PLUMBING SPECIFICATIONS SECTION 22 1323 - PART
 2 - SECTION 2.01 (GREASE INTERCEPTOR) :TAG # GT-1 -
 SECTION C -ACCESSORIES: CALLS OUT A 4-INCH INFLUENT AND
 EFFLUENT TWO-WAY CLEANOUT, BUT ALSO CALLS OUT A 6-INCH
 SAMPLING PORT. THIS WOULD CREATE AN OBSTRUCTION TO FLOW
 AND VIOLATES FBC-PLUMBING SEC.706.2. THIS SECTION ALSO
 CALLS OUT A SCHIER INTERCEPTOR WITH 6-INCH INLET AND
 OUTLET. CLARIFY.
 128) SHOW THE CAPACITY OF THE GREASE INTERCEPTORS ON
 THE CIVIL AND PLUMBING SHEETS. WPB AMEND TO FBC SEC.
 107.2.1.
 129) SHT. P.802 - DETAIL #4 - A FULL OPEN VALVE SHALL
 BE INSTALLED ON THE DISCHARGE SIDE OF THE CHECK VALVE
 AND SHALL BE INSTALLED IN THE PUMP / EJECTOR DISCHARGE
 PIPING BETWEEN THE PUMP OR EJECTOR AND THE GRAVITY
 DRAINAGE SYSTEM PER FBC-PLUMBING 712.2.
 130)) SHT. P.802 - DETAIL #8 SHOWS A 6-INCH TRAP
 DISCHARGING INTO A 4-INCH LINE. CLARIFY.
 131) SHT.P.803 - DETAILS #1 & #2 - THE BACKFLOW DEVICES
 SHALL BE LEAD FREE AND THE BACKFLOW DEVICES MUST BE ON
 THE UNIVERSITY OF SOUTHERN CALIFORNIA'S (USC) LIST OF
 APPROVED DEVICES. A SEPARATE PERMIT IS REQUIRED FOR THE
 BACKFLOW DEVICES.
 132) RIGID SUPPORT SWAY BRACING SHALL BE PROVIDED AT
 CHANGES IN DIRECTION GREATER THAN 45 DEGREES FOR PIPE
 SIZES 4 INCHES AND LARGER PER FBC-PLUMBING SEC.308.6.
 SUBMIT DETAILS FOR THE BRACING.
 133) FOR PIPE SIZES GREATER THAN 4 INCHES (102 MM),
 RESTRAINTS SHALL BE PROVIDED FOR DRAIN PIPES AT ALL
 CHANGES IN DIRECTION AND AT ALL CHANGES IN DIAMETER
 GREATER THAN TWO PIPE SIZES. BRACES, BLOCKS, RODDING
 AND OTHER SUITABLE METHODS AS SPECIFIED BY THE COUPLING
 MANUFACTURER SHALL BE UTILIZED.
 134) THE PLUMBING SHEETS DO NOT BEAR THE DIGITAL
 SIGNATURE AND SEAL OF THE DESIGN PROFESSIONAL IN
 RESPONSIBLE CHARGE PER WPB AMEND. TO FBC SEC.107.3.4,
 FL. ADMIN. CODE RULE 61G15-23.004, 61G15-23.005.
 135) THE SUPPLY LINES AND FITTINGS FOR THE RESIDENTIAL
 DISHWASHERS SHALL BE INSTALLED SO AS TO PREVENT
 BACKFLOW. PLUMBING FIXTURE FITTINGS SHALL PROVIDE
 BACKFLOW PROTECTION IN ACCORDANCE WITH ASME
 A112.18.1/CSA B125.1.FBC-PLUMBING SEC. 608.2.
 136) SHT. P.803 - DETAIL #3 SHOWS JOINTS UNDER THE SLAB
 - PLUMBING SPECIFICATIONS SEC.221110 - PART 2 - 2.02
 STATES THAT "ENTRANCE PIPING TO THE BUILDING TO
 TERMINATE ABOVE GRADE." THE DETAIL ON P.803 SHOWS
 FLANGED FITTINGS UNDER THE SLAB. CLARIFY. IF THIS
 PIPING ARRANGEMENT IS TO REMAIN, SUBMIT DETAILS ON
 FITTING RESTRAINTS AND THRUST BLOCK INFORMATION. WPB
 AMEND. TO FBC SEC. 107.2.1, 107.3.5.1.3.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  
  
  
  
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2019-04-09 Cont ID  
Sent By gjohnson Date 2019-04-09 Time 10:07 Rev Time 0.00
Received By gjohnson Date 2019-03-28 Time 07:07 Sent To  
Notes
2019-04-09 10:07:161ST REVIEW: 18100540
 2017 FLORIDA BUILDING CODE 6TH EDITION
 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH
 EDITION
  
 PLUMBING COMMENTS: DUE TO THE FACT THAT THESE PLANS ARE
 INCOMPLETE I AM NOT ABLE TO DETERMINE CODE COMPLIANCE
 AT THIS TIME. I HAVE REVIEWED THE INFORMATION PROVIDED
 AND COMMENTED, WHEN A COMPLETE SET OF DESIGN DOCUMENTS
 ARE PROVIDE PLEASE ADDRESS THESE COMMENTS.I WILL THEN
 BE ABLE TO COMPLETE A MORE COMPREHENSIVE REVIEW.
  
 1. PLEASE INDICATE ON THE PLAN WHICH DESIGN DOCUMENT
 WAS USED TO DETERMINE COMPLIANCE TO THE FHA SUCH AS THE
 FHA DESIGN MANUAL OR THE FHA GUIDE LINES FOUND IN THE
 BACK OF THE FBC ACCESSIBILITY BOOK. PER WPB AMEND TO
 FBC 107.2.1
 2. PLEASE CLARIFY ON THE PLAN THAT THE RESIDENTIAL
 UNITS AND AND COMMON AREAS FOR THOSE UNITS SHALL COMPLY
 WITH FHA AND ANSI A117.1-1986.
 3. PLEASE CLARIFY ON THE PLAN THAT ALL OTHER
 OCCUPANCY'S OTHER THAN THE RESIDENTIAL UNITS SHALL
 COMPLY WITH THE 2017 6TH EDITION FLORIDA BUILDING CODE
 ACCESSIBILITY NOT ADA
 4. PLEASE PROVIDE A MATRIX CHART FOR THE RESIDENTIAL
 UNITS SHOWING WHICH BATHROOMS ARE COMPLYING WITH FHA
 AND WHAT DESIGN SPEC IS BEING USED. PER WPB AMENDS TO
 FBC 107.2.1
 5. PLEASE PROVIDE A PLUMBING FIXTURE COUNT BREAK DOWN
 FOR THE BUSINESS, ASSEMBLY AND MERCANTILE OCCUPANCY'S
 PER FBC PL TABLE 403.1
 6. PROVIDE BREAK DOWN OF ACCESSIBLE AND NON ACCESSIBLE
 ROOMS FOR THE HOTEL. PER WPB AMENDS TO FBC 107.2.1
 7. SHT. A0.202 SOME OF THE DETAILS ARE CONFUSING THEY
 ARE COMBINING FHA WITH ADA THESE CODES DO NOT MATCH UP
 AND THE PROJECT SHALL COMPLY WIH THE FBC ACC NOT ADA
 PLEASE CLARIFY. PER WPB AMENDS TO FBC 107.2.1
 8. THE MENS BATHROOM SHALL HAVE URINALS PLEASE PROVIDE
 FIXTURE BREAKDOWN FOR ALL THE POOLS COMPLYING WITH FBC
 PL TABLE 403.6
 9. SHT. A1.505 SUITE 1.2 PROVIDE DIMENSIONS OF THE
 SHOWER. PER WPB AMENDS TO FBC 107.2.1
 10.SHT. A1.510 - A1.528 THE FHA SPEC DESIGNATION IS
 MISSING FROM SOME OF THE BATHROOMS EACH RESIDENTIAL
 UNIT SHALL BE DESIGNATED SPEC A OR B FOR THE BATHROOMS.
 PER FHA
 11.SHT. A1.510 - A1.528 SOME OF THE CLEAR FLOOR SPACE
 AND LOCATION OF GRAB BAR BACKING LOCATION ARE MISSING
 THESE SHALL BE SHOWN ON ALL ENLARGED FLOOR PLANS WHERE
 THEY ARE REQUIRED. PER WPB AMENDS TO FBC 107.2.1
 12. SHT. A1.527 + A1.600 DETAIL 13 THE WING WALL NEXT
 TO THE TOILET SHALL NOT EXTEND MORE THAN 24" FROM REAR
 WALL THIS REQUIREMENT IS FOR ALL FHA COMPLIANT
 BATHROOMS. PER FHADM REQ. #7 PG 7.43
 13. SHOW THE DEPTH OF THE LAVATORY'S IN ALL FHA
 COMPLIANT BATHROOMS. PER FHADM REQ. #7 PG 7.43
 14. SHT. A1.600 DETAIL #11 IS SHOW MULTIPLE SHOWER
 LAYOUTS ON TOP OF EACH OTHER PLEASE CLARIFY AND SHOW
 DIMENSIONS. PER WPB AMEND TO FBC 107.2.1
 15. SHT. A1.600 - A1.602 SHOW ALL DIMENSIONS OF THE
 BATHROOMS. PER WPB AMEND TO FBC 107.2.1
 16. SHT. A1.524 A1.600 DETAIL #7 SHOW CLEAR FLOOR
 SPACE. PER WPB AMEND TO FBC 107.2.1
 17. SHT. A1.600+601 SOME OF THE DETAILS ARE SHOW DOUBLE
 FIXTURE OVERLAPPING PLEASE CLARIFY.
 PER WPB AMEND TO FBC 107.2.1
 18. SHT A1.521 THE CLEAR FLOOR SPACE AT THE KITCHEN IS
 OVERLAPPING THE SINK AND CABINETS PLEASE CLARIFY. PER
 WPB AMEND TO FBC 107.2.1
 19. SHT A1.602 SHOW ALL CLEAR FLOOR SPACE WITH
 DIMENSIONS FOR ACCESSIBLE TOILET, LAVATORY'S, URINALS
 AND SHOWER AND WATER FOUNTAINS. PER WPB AMEND TO FBC
 107.2.1 AND FBC ACC CH6
 20. SHT A1.602 SHOW DIMENSIONS FOR THE STALL AND
 SHOWER. PER WPB AMEND TO FBC 107.2.1
 21. SHT. A1.602 DETAIL #2 IN THE ACCESSIBLE STALL THE
 SHOWER IS ENCROACHING INTO THE CLEAR FLOOR SPACE OF THE
 TOILET SPACE IT SHALL COMPLY WITH FBC ACC 604.3.1
 22. SHT A1.602 THE TRANSFER SHOWER SHALL HAVE A SEAT.
 PER FBC ACC 608.4
 23. IN THE PLUMBING FIXTURE BREAKDOWN PLEASE INDICATE
 COMPLIANCE WITH POTTY PARITY. PER FBC ACC 403.1.3
 24. SHT. A1.602 PLEASE LABEL ALL ENLARGED BATHROOM
 GROUPS WITH THE ROOM NUMBER AND MENS OR WOMENS. PER WPB
 AMEND TO FBC 107.2.1
 25. PROVIDE ENLARGED BATHROOM DETAILS FOR ALL COMMON
 AREA IN ALL THE DIFFERENT OCCUPANCY I FOUND THESE
 MISSING, 07-55, 07-27, 07-61, 07-60, 08-28, 08-21,
 08-38, 08-39, 08-21. PER WPB AMEND TO FBC 107.2.1
 26. PROVIDE DIMENSIONS FOR THE ROOF SCUPPERS MAIN AND
 EMERGENCY SCUPPERS. PER WPB AMEND TO FBC 107.2.1
 27. PROVIDE MANUFACTURE SPECIFICATIONS AND INSTILLATION
 GUIDES FOR THE LIQUID APPLIED WATERPROOF MEMBRANE FOR
 THE SHOWER PANS IT SHALL COMPLY WITH FBC PL 417.5.2.6
 AND ANSI A118.10
 28. SHT. A7.502 ON THE DEPRESSION DETAIL THE HYDRO BAN
 SHALL BE PITCHED TO TH SHOWER DRAIN FLANGE UNDER THE
 MORTAR BED AND SEAL TO THE BOTTOM FLANGE UNDER THE
 CLAMPING RING. PER FBC PL 417.5.2
 29. IN THE RESIDENTIAL COMMON AREA LOUNGE AND SCREENING
 ROOM AND RESIDENTIAL POOL IT DOES NOT APPEAR TO BE ANY
 COMMON BATHROOMS PLEASE CLARIFY. PER WPB AMEND TO FBC
 107.2.1
 30. PLEASE INDICATE ON THE PLAN ALL WORK SHALL COMPLY
 WITH 2017 6TH EDITION FLORIDA BUILDING CODE , PLUMBING,
 FUEL GAS, MECHANICAL, ACCESSIBILITY AND FHA
 31. SHT P-100 WHAT IS THE 2'X 2' SAND PIT LOCATED NEAR
 GRID LINES B+8. PER WPB AMEND TO FBC 107.2.1
 32. SHT. P'S LABEL AND TAG ALL RISERS ON ALL FLOOR
 PLANS. PER WPB AMEND TO FBC 107.3.5.1.3(13)
 33. ON SANITARY FLOOR PLAN SHOW ALL COMMON AREA
 BATHROOMS OR NOTE WHERE ENLARGED PLAN CAN BE FOUND. PER
 WPB AMEND TO FBC 107.2.1
 34. PLEASE IDENTIFY WHAT THE IWS IS SERVING. PER WPB
 AMEND TO FBC 107.2.1
 35. SHT P 107B SHOWS AN AAV THESE TYPE OF VENTS ARE
 ONLY ALLOWED TO SERVE FIXTURES THAT ARE NO MORE THAN 4
 BRANCH INTERVALS FROM THE TOP OF THE VENT STACK UNLESS
 A RELIEF VENT IS PROVIDED PLEASE CLARIFY . PER FBC PL
 918.3.1
 36. SHT. P-109 IF PONDING CAN OCCUR ON THIS LEVEL
 OVERFLOW DRAINS WILL BE REQUIRED FOR THE PD. PER FBC PL
 1108.1
 37. PLEASE PROVIDE MANUFACTURE SPECIFICATIONS FOR ALL
 PUMPS AND VALVES INCLUDING MIXING VALVE AND PRESSURE
 REDUCING.PER WPB AMEND TO FBC 107.2.1
 38. PROVIDE COMPLETE COLLECTION ISOMETRIC DRAWING FOR
 ALL UNDER GROUND PLUMBING PLEASE SEPARATE EACH
 DIFFERENT SYSTEM FOR CLARITY AND INCLUDE SIZING DFU
 LOADS SGFT DRAINED. WPB AMEND TO FBC 107.3.5.1.3(13)
 39. A WYE STAINER IS REQUIRED AT ALL PRESSURE REDUCING
 VALVES PLEASE SHOW ON ALL DETAILS AND ISOMETRIC
 DRAWING. PER FBC PL 604.8
 40. PLACE NOTE ON PLAN SHUT OFF VALVES FOR STACKABLE
 WASHING MACHINES IN THE RESIDENCIAL UNITS SHALL BE
 ACCESSIBLE. PER FBC PL 606.3
 41. IN PUBLIC BATHROOMS TEMPERED WATER SHALL BE
 DELIVERED FROM LAVATORIES AND GROUP WASH FIXTURES
 LOCATED IN PUBLIC TOILET FACILITIES PROVIDED FOR
 CUSTOMERS, PATRONS AND VISITORS. TEMPERED WATER SHALL
 BE DELIVERED THROUGH AN APPROVED WATER-TEMPERATURE
 LIMITING DEVICE THAT CONFORMS TO ASSE 1070 OR CSA
 B125.3. PER FBC PL 416.5
 42. THE ENLARGED PLUMBING FLOOR PLANS APPEAR TO HAVE
 TAGS ON THE STACKS THAT ARE INCOMPLETE PLEASE MAKE SURE
 ALL STACKS ARE LABBELED AND TAGED TO MATHCH THE
 ISOMETRIC DRAWING AND FULL FLOOR PLANS. PER WPB AMEND
 TO FBC 107.2.1
 43. SHT. P-701 I CAN NOT DETERMINE CODE COMPLIANCE ON
 THIS PAGE PLEASE SPLIT RISER AND ORIENT THE DRAWING SO
 THE BOTTOM OF THE BUILDING MATCHES UP TO THE BOTTOM OF
 THE PLAN SHEET.PER WPB AMEND TO FBC 107.2.1
 44. SHT. P-701 PLEASE LABEL THE UNIT BRANCHES .PER WPB
 AMEND TO FBC 107.2.1
 45. PROVIDE COMPLETE STORM ISOMETRIC WITH SQFT AND
 SLOPE OF THE PIPE. PER WPB AMEND TO FBC 107.3.5.1.3(13)
 46. SHT. P-703 ONLY 1 FIXTURE IS ALLOWED UPSTREAM OF
 THE WET VENT ON THE BATHROOM GROUP SS/2 . PER FBC PL
 912.1
  
  
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]

Review Stop P-GREASE GREASE INTERCEPTOR/TRAP REVIEW
Rev No 5 Status N Date 2021-08-16 Cont ID  
Sent By lcrespo Date 2021-08-16 Time 12:03 Rev Time 0.00
Received By lcrespo Date 2021-08-16 Time 12:03 Sent To  
Notes
2021-08-16 12:03:30NOTE: A SEPARATE PERMIT APPLICATION AND REVIEW ARE
 REQUIRED FROM ENGINEERING FOR THE GREASE INTERCEPTOR.

Review Stop P-GREASE GREASE INTERCEPTOR/TRAP REVIEW
Rev No 4 Status F Date 2021-06-21 Cont ID  
Sent By lcrespo Date 2021-06-21 Time 15:54 Rev Time 0.00
Received By lcrespo Date 2021-06-14 Time 14:33 Sent To  
Notes
2021-06-21 15:54:54ON SHEET 804, DETAIL #2 OF NOTE TWO HAS SPECIFIED A
 SCHIER 250 GALLONS. WHY IS THIS SPECIFIED? HOW DID YOU
 DETERMINE THE USAGE OF THE RESTAURANT UNITS WITH
 RESPECT TO THE RESTAURANT CAPACITY? HOW IS THIS
 INFORMATION PROVIDED? IF SCHIER PROVIDED THESE
 CALCULATIONS OR WILL ASSIST IN SIZING, PLEASE NOTE IN
 DETAIL TWO HOW THE ENGINEERED SYSTEM IS TO COMPLY.
 PLEASE PUT A NOTE RESPONSE OF P100 ON P 804 DETAIL 2. I
 SPOKE TO SCHIER'S REP, AND THEY ARE WILLING TO HELP IN
 ALL CALCULATION ASSISTANCE REQUIRED; IF HE NEEDS TO
 CONTACT YOU, MAY LEE @ 561 632-3123, FYI.

Review Stop P-GREASE GREASE INTERCEPTOR/TRAP REVIEW
Rev No 3 Status F Date 2021-02-20 Cont ID  
Sent By tklarge Date 2021-02-19 Time 09:51 Rev Time 0.00
Received By tklarge Date 2021-02-19 Time 09:48 Sent To  
Notes
2021-02-19 09:54:501) SUBMIT FACTORY SIZING CALCULATIONS FROM SCHIER FOR
 THIS INTERCEPTOR PER FBC-PLUMBING SEC. 1003.2. 2ND
 REQUEST.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  

Review Stop P-GREASE GREASE INTERCEPTOR/TRAP REVIEW
Rev No 2 Status F Date 2020-03-28 Cont ID  
Sent By tklarge Date 2020-03-28 Time 10:05 Rev Time 0.00
Received By tklarge Date 2020-03-28 Time 05:00 Sent To  
Notes
2020-03-28 05:16:231) SHOW THE CAPACITY OF THE GREASE INTERCEPTORS ON THE
 CIVIL AND PLUMBING SHEETS. WPB AMEND TO FBC SEC.
 107.2.1.
 2) THE PLUMBING SPECIFICATIONS SECTION 22 1323 - PART 2
 - SECTION 2.01 (GREASE INTERCEPTOR) :
 TAG # GT-1 - SECTION C -ACCESSORIES: CALLS OUT A 4-INCH
 INFLUENT AND EFFLUENT TWO-WAY CLEANOUT, BUT ALSO CALLS
 OUT A 6-INCH SAMPLING PORT. THIS WOULD CREATE AN
 OBSTRUCTION TO FLOW AND VIOLATES FBC-PLUMBING
 SEC.706.2. THIS SECTION ALSO CALLS OUT A SCHIER
 INTERCEPTOR WITH 6-INCH INLET AND OUTLET. CLARIFY.
 3) THE INSTALLATION GUIDE/MANUAL FOR THE GREASE
 INTERCEPTORS SHALL BE ONSITE FOR INSPECTION.
 FBC-PLUMBING SEC. 1003.3.4. FACTORY SIZING CALCULATIONS
 SHALL BE SUBMITTED FOR REVIEW. FBC-PLUMBING SEC.1003.2,
 1003.3.4.
 4) A SEPARATE PERMIT IS REQUIRED FOR THE GREASE
 INTERCEPTORS. PLACE A NOTE ON DRAWING C.06 AND THE
 PLUMBING DRAWINGS.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  
  

Review Stop P-GREASE GREASE INTERCEPTOR/TRAP REVIEW
Rev No 1 Status F Date 2019-04-09 Cont ID  
Sent By gjohnson Date 2019-04-09 Time 10:07 Rev Time 0.00
Received By gjohnson Date 2019-04-09 Time 10:07 Sent To  
Notes
2019-04-09 10:08:181ST REVIEW: 18100540
 2017 FLORIDA BUILDING CODE 6TH EDITION
 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH
 EDITION
  
 GREASE INTERCEPTOR COMMENTS:
  
 1. PROVIDE MANUFACTURE SIZING CALCULATION FOR THE
 GREASE INTERCEPTOR AND THE OIL/SAND INTERCEPTOR. PER
 FBC PL 1003.2 /1003.4.2.2
 2. WHAT IS DISCHARGED THROUGH GARAGE WASTE SYSTEM IF IT
 IS STORM WATER IT SHALL DISCHARGE TO THE STORM SYSTEM
 NOT THE SANITARY SYSTEM. PER CITY OF WEST PALM BEACH
 CODE OF ORDINANCE SEC. 90-126(5)
 3. SHT P-100 WHAT IS THE 2'X 2' SAND PIT LOCATED NEAR
 GRID LINES B+8. PER WPB AMEND TO FBC 107.2.1
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]

Review Stop P-IRRIGATE IRRIGATION REVIEW
Rev No 3 Status P Date 2021-02-19 Cont ID  
Sent By tklarge Date 2021-02-19 Time 09:52 Rev Time 0.00
Received By tklarge Date 2021-02-19 Time 09:52 Sent To  
Notes
2021-02-19 09:55:521) A SEPARATE PERMIT IS REQUIRED FOR THE IRRIGATION
 SYSTEM.
 20 A SEPARATE PERMIT IS REQUIRED FOR THE BACKFLOW
 PREVENTER.

Review Stop P-IRRIGATE IRRIGATION REVIEW
Rev No 2 Status F Date 2020-03-28 Cont ID  
Sent By tklarge Date 2020-03-28 Time 04:58 Rev Time 0.00
Received By tklarge Date 2020-03-28 Time 04:44 Sent To  
Notes
2020-03-28 04:45:451) SHT. LIR5-000 SHOWS A PRESSURE VACUUM BREAKER TYPE
 BACKFLOW PREVENTION DEVICE FOR THE IRRIGATION SYSTEM.
 THIS TYPE OF DEVICE IS NOT APPROVED TO BE INSTALLED ON
 A COMMERCIAL IRRIGATION SYSTEM PER THE CITY OF WEST
 PALM BEACH CROSS CONNECTION CONTROL MANUAL. A REDUCED
 PRESSURE ZONE VALVE IS THE MINIMUM REQUIRED PROTECTION
 ON THIS SYSTEM. A SEPARATE PERMIT IS REQUIRED FOR THE
 INSTALLATION OF THIS DEVICE. THE DEVICE MUST BE LEAD
 FREE AND BE LISTED ON THE UNIVERSITY OF SOUTHERN
 CALIFORNIA'S FOUNDATION FOR CROSS CONNECTION CONTROL
 LIST OF APPROVED DEVICES. THE DEVICE MUST BE TESTED AND
 CERTIFIED BY THE CITY OF WEST PALM BEACH UTILITIES
 DEPARTMENT WHEN IT IS INSTALLED PER THE CITY OF WEST
 PALM BEACH CROSS CONNECTION CONTROL MANUAL.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  
  
  

Review Stop P-IRRIGATE IRRIGATION REVIEW
Rev No 1 Status F Date 2019-04-08 Cont ID  
Sent By gjohnson Date 2019-04-08 Time 08:26 Rev Time 0.00
Received By gjohnson Date 2019-04-08 Time 08:26 Sent To  
Notes
2019-04-08 08:50:251ST REVIEW:
 2017 FLORIDA BUILDING CODE 6TH EDITION
 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH
 EDITION
  
 IRRIGATION COMMENTS:
  
 1. SHT. LIRI - 100 SHOW LOCATION OF RAIN SENSOR . PER
 WPB AMEND TO FBC 107.2.1
  
 2. ALL THE IRRIGATION PAGES SHALL BE DIGITALLY SIGNED
 AND SEALED BY DESIGN PROFESSIONAL RESPONSIBLE FOR
 SYSTEM DESIGN. PER FAC 61G15-23.003 OR FAC 61G1-16.005
  
  
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  

Review Stop R ROOF PLAN REVIEW
Rev No 4 Status N Date 2021-06-18 Cont ID  
Sent By rmcdouga Date 2021-06-18 Time 10:03 Rev Time 0.00
Received By rmcdouga Date 2021-06-18 Time 10:03 Sent To  
Notes
2021-06-18 10:06:00ROOFING PRODUCT MATERIALS HAVE BEEN DEFERRED. SEE NOTES
 ON PLAN SHEET A0.001.

Review Stop R ROOF PLAN REVIEW
Rev No 3 Status F Date 2021-03-01 Cont ID  
Sent By rmcdouga Date 2021-03-01 Time 11:24 Rev Time 0.00
Received By rmcdouga Date 2021-03-01 Time 11:24 Sent To  
Notes
2021-03-01 11:10:09PLAN
 REVIEW COMMENTS
  
 3RD REVIEW: FBC FIFTH EDITION (2014)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 ROOFING MATERIALS DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) THE ROOFING PRODUCT APPROVALS ARE REQUIRED TO BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD FOR THE PROJECT. FBC AMENDMENTS 107.3.4
  
 2) THERE ARE MUTIPLE SYSTEMS WITH DIFFERENT DESIGN
 PRESSURES LISTED IN THE PRODUCT APPROVALS. HI-LIGHT OR
 CIRCLE THE SPECIFIC MEMBRANE TYPE, SYSTEM TYPE AND
 MAXIMUM DESIGN PRESSURES THAT APPLY IN THE PRODUCT
 APPROVALS. FBC AMENDMENTS 107.2.1
  
 3) SEE BUILDING REVIEW COMMENT NUMBER 22.
  
 4) SUBMIT PRODUCT APPROVALS FOR ROOF INSULATION. FBC
 AMENDMENTS 107.3.4
  
 5) ROOFING PRODUCT APPROVALS SUBMITTED.
 NOA NO. 15-0707.08
 NOA NO. 15-0709.14
 NOA NO. 16-0203.02
 NOA NO.16-0229.06
 NOA NO.17-0222.10

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status F Date 2020-03-06 Cont ID  
Sent By dbattles Date 2020-03-06 Time 12:52 Rev Time 0.00
Received By dbattles Date 2020-02-18 Time 07:38 Sent To  
Notes
2020-03-06 12:53:26SEE BUILDING COMMENT #22
  
 DYLAN BATTLES
 BUILDING PLANS EXAMINER PX4191
 [email protected]
 561-805-6718
  

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2019-04-18 Cont ID  
Sent By dbattles Date 2019-04-18 Time 15:08 Rev Time 0.00
Received By dbattles Date 2019-04-08 Time 13:37 Sent To  
Notes
2019-04-18 15:09:10SEE BUILDING COMMENTS.
 PRODUCT APPROVALS WILL BE REVIEWED ON SECOND REVIEW,
 UNLESS DEFERRED SUBMITTAL IS REQUESTED.

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 6 Status P Date 2021-09-08 Cont ID  
Sent By shill Date 2021-09-08 Time 11:41 Rev Time 0.00
Received By shill Date 2021-09-08 Time 11:41 Sent To  
Notes
2021-09-08 11:42:23SIGNATURE ERRORS IN BLUEBEAM DO NOT OCCUR IN ADOBE.
 PROVISO: ARCHITECT TO SEND DIGITALLY SIGNED PAGE VIA
 EMAIL
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 5 Status F Date 2021-09-03 Cont ID  
Sent By rmcdouga Date 2021-09-03 Time 17:24 Rev Time 0.00
Received By rmcdouga Date 2021-09-03 Time 17:06 Sent To  
Notes
2021-09-03 17:23:48PLEASE CHECK FOR DIGITAL SIGNATURES ON ALL SUBMITEED
 PLAN SHEETS. THERE ARE STILL ISSUES WITH SIGNATURES.
 SHEET A1.272A ON PAGE 03.316 IS NOT SIGNED AND SEALED.
 SEALS ON STRUCTURAL DRAWINGS SHOW AS REVOKED, FOR
 EXAMPLE SEE PAGE 05.002-S1.002. THE CIVIL ENGINEER
 RICHARD V. REIKENIS, IS SELF-CERTIFYING HIS SIGNATURE.
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 4 Status F Date 2021-08-27 Cont ID  
Sent By rmcdouga Date 2021-08-27 Time 08:52 Rev Time 0.00
Received By rmcdouga Date 2021-08-27 Time 08:52 Sent To  
Notes
2021-06-21 12:00:46SHEET A1.316 ON PAGE 03.316 IS NOT SIGNED AND SEALED.
 SEALS ON STRUCTURAL DRAWINGS SHOW AS REVOKED, FOR
 EXAMPLE SEE PAGE 05.002-S1.002. THE CIVIL ENGINEER
 RICHARD V. REIKENIS, IS SELF-CERTIFYING HIS SIGNATURE.
 STILL NEED TO LIST AND ORDER ALL SHEETS IN THE INDEX.
 RM
2021-06-10 13:42:27MECHANICAL DRAWINGS SIGNATURE REVIEW- APPROVED. ME
 08/16/2021 MECHANICAL REVISED DRAWINGS SIGNATURE REVIEW
 AAAPRROVED ME

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status F Date 2021-03-01 Cont ID  
Sent By shill Date 2021-03-01 Time 07:31 Rev Time 0.00
Received By shill Date 2021-03-01 Time 07:31 Sent To  
Notes
2021-03-01 07:56:41SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 1. PRIOR TO RESUBMITTING, PLEASE CONFIRM THAT ALL PAGES
 ARE IN THE ORDER ON THE INDEX PAGE, PROPERLY VERSIONED
 (NO DUPLICATES), ESPECIALLY PLUMBING.
  
 2. NO ACTION REQUIRED - P, E, T, MP, M PAGES UPLOADED
 12/21/20 OK (SPOT CHECKED)
  
 3. FA PAGES UPLOADED 12/21 LACK A DIGITAL SIGNATURE;
 FOR INSTANCE FP.201A, FA208B,
  
 4. ARCH PAGES - PAGE 03.317 - A1.501A, 03.310 - A10.227
 ARE NOT DIGITALLY SIGNED. OTHER PAGES UPLOADED 12/21
 ARE DIGITALLY SIGNED. CHECK ALL.
  
 5. NO ACTION REQUIRED - FP, T, FA, E, S, A, M, P
 UPLOADED 2/10/20, 2/6/20, 2/5/20, 2/4/20, 1/31/20 OK
  
 6. CIVIL PAGES UPLOADED 2/28/2019 DIGITAL SIGNATURE OK,
 BUT NO NEW PAGES HAVE BEEN SUBMITTED SINCE THEN. PLEASE
 CONFIRM THAT THERE ARE NO CONFLICTS BETWEEN THE
 2/28/2019 CIVIL PAGES AND OTHER (NEWER) PAGES.
  
 7. NO ACTION REQUIRED - A, T, E PAGES PULOADED
 2/25/2019, 2/23/2019 ARE OK (SPOT CHECKED)
  
 8. M PAGE UPLOADED 2/25/2019 06.16 - M808 IS NOT
 DIGITALLY SIGNED.
  
  
  
  
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status F Date 2020-02-10 Cont ID  
Sent By shill Date 2020-02-10 Time 18:05 Rev Time 0.00
Received By shill Date 2020-02-10 Time 17:44 Sent To  
Notes
2021-02-21 07:49:47PLUMBING SHEETS ARE NOT ELECTRONICALLY SIGNED AND
 SEALED PER FL. ADMIN. CODE RULE 61G15--23.004,
 61G15-23.005. T.LARGE
2020-02-10 18:05:44SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
 **REVISED 12/15/20, DOCUSIGN OK PER FBPE EMAIL FROM
 W.ANDERSON**
  
 1. CIVIL, ARCH & STRUCTURAL PAGES SPOT CHECKED; OK.
  
 2. COMMENT REMOVED PER FBPE EMAIL
  
 3. COMMENT REMOVED PER FBPE EMAIL
  
 4. FS471, IT IS NOT CLEAR WHO PREPARED THE STAIR
 PRESSURIZATION RATIONAL ANALYSIS (SUPPORTING
 DOCUMENTS). THERE IS NO TITLE BLOCK AND THE DOCUMENT IS
 NOT SIGNED AND SEALED. THIS DOCUMENT SHOULD BE REVIEWED
 BY DESIGNER OF RECORD.
  
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2019-03-28 Cont ID  
Sent By dbattles Date 2019-03-28 Time 16:08 Rev Time 0.00
Received By dbattles Date 2019-03-28 Time 16:08 Sent To  
Notes
2019-04-08 17:59:20MECH SHEETS NOT ELECTRONICALLY SIGNED AND SEALED.
2019-03-28 16:12:43DIGITAL SIGNATURE IS VALID FOR ALL A SHEETS
 NO DIGITAL IMAGE OF SEAL APPLIED TO A SHEETS
  
 107.2.1 FBC[AMENDED] PLACE A DIGITALLY CREATED IMAGE OF
 YOUR SEAL AND THE FOLLOWING SENTENCES WHERE AN ORIGINAL
 SIGNATURE WOULD APPEAR IF THE ITEM WERE BEING
 PHYSICALLY SIGNED DATED AND SEALED. THE SENTENCES CAN
 BE PART OF THE DIGITAL SIGNATURE CUSTOM APPEARANCE
 AVAILABLE IN THE SIGNING TOOL, OR THEY CAN BE PLACED ON
 THE DOCUMENT OUTSIDE OF THE DIGITAL SIGNATURE BLOCK.
 THIS ITEM HAS BEEN ELECTRONICALLY SIGNED AND SEALED BY
 [LICENSEE, RA, OR LS] ON THE DATE AND/OR TIME STAMP
 SHOWN USING A DIGITAL SIGNATURE.
  
 DIGITAL SIGNATURE IS VALID FOR ALL STRUCURAL SHEETS.
 DIGITAL IMAGE OF SEAL IS APPLIED TO STRUCURAL SHEETS.
  
 ANY SHEETS UPLOADED TO ADDRESS COMMENTS WILL NEED TO BE
 DIGITALLY SIGNED.
2019-03-25 14:18:20ELECTRICAL SHEETS OK.

Review Stop THRESHOLD THRESHOLD INSPECTOR DOCUMENTS
Rev No 1 Status P Date 2018-11-16 Cont ID  
Sent By shill Date 2018-11-16 Time 17:55 Rev Time 0.00
Received By shill Date 2018-11-16 Time 17:53 Sent To  
Notes
2018-11-16 17:56:28PASSED UNDER 16060825
  
 MCNAMARA SALVIA
 ANDREW P. SULLIVAN, PE
 CHAD CASSETT, PE
 SERGIO GONZALEZ, PE ADDED 9/23/19
  
  

Review Stop Z ZONING
Rev No 7 Status P Date 2021-08-20 Cont ID  
Sent By aaponte Date 2021-08-20 Time 08:17 Rev Time 0.00
Received By aaponte Date 2021-08-20 Time 08:17 Sent To  
Notes
2021-08-20 08:18:57PROVISO:
 1. DECORATIVE LIGHT FIXTURES AND POLES ALONG TEH STREET
 FRONTAGE SHALL MATCH THE DOWNTOWN CITY STANDARD.
 2. SIDEWALK ELEVATION SHALL BE MAINTAINED ACROSS ALL
 DRIVEWAYS. A REVISION SHALL BE SUBMITTED WITHIN 30 DAYS
 OF PERMIT ISSUANCE.

Review Stop Z ZONING
Rev No 6 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By aaponte Date 2021-08-16 Time 13:37 Sent To  
Notes
2021-08-16 14:34:54PROVISOS:
 1.LIGHT FIXTURES AND POLES ALONG DIXIE HWAY, 4TH
 STREET, AND QUADRILLE BOULEVARD SHALL MEET THE DOWNTOWN
 CITY STANDARD.
  
  
 PLANTING DETAILS FOR GARAGE GREEN SCREEN SHALL BE
 INCLUDED IN THE LANDSCAPE DRAWING, AS WELL AS DETAILED
 MAINTENANCE PROCEDURES FOR THE GREEN SCREEN.
 6. THE DAC ORDER REQUIRES THE SIDEWALK ELEVATION TO BE
 MAINTAINED ACROSS THE DRIVEWAY ENTRANCES. I DON?T THINK
 THE DRAWINGS REFLECT THAT CONDITION. PLEASE CONFIRM. I
 WOULD NEED A DETAIL OR A NOTE IN THE CIVIL DRAWINGS. IT
 IS REALLY HARD TO GET THE CONSTRUCTION TEAM TO DO THIS
 BECAUSE THEY ARE USED TO THE DRIVEWAY PREFERENCE.
 7. PLEASE CONFIRM THAT THE GAS LINES ARE OK TO RUN
 THROUGH THE STRUCTURAL SOIL. THE GAS LINE ON 4TH IS
 GOING THROUGH STRUCTURAL SOIL. THERE ARE ALSO SOME ROOT
 BARRIERS PROPOSED ON THE TREES ON 4TH NEXT TO THE
 STRUCTURAL SOIL, COULD YOU EXPLAIN THE REASON? IT SEEMS
 THAT DEFEATS THE PURPOSE OF THE STRUCTURAL SOIL.
 8. ADA PEDESTRIAN CROSSING AT 4TH AND DIXIE SHALL BE
 APPROVED BY THE ENGINEERING DEPARTMENT.
 9. LANDSCAPE PERMIT SHALL BE SUBMITTED AS A SEPARATE
 PERMIT.
 10. PLEASE PROVIDE A NARRATIVE EXPLAINING THE PARKING
 GARAGE OPERATION THAT ACKNOWLEDGES THE SHARED PARKING
 SYSTEM AND VALET OPERATION.
 11. CAR SHARING STATION SHALL BE CLEARLY LABELED.
 12. CONDITIONS OF APPROVAL INCLUDED IN DAC FINAL ORDER
 AND SITE PLAN APPROVAL LETTER ARE APPLICABLE TO THE
 BUILDING, AND SHALL BE FULFILLED ACCORDINGLY.
 FOR ADDITONAL INFORMATION PLEASE CONTACT ANA MARIA
 APONTE AT 561-822-1439.

Review Stop Z ZONING
Rev No 5 Status F Date 2021-06-23 Cont ID  
Sent By aaponte Date 2021-06-17 Time 11:50 Rev Time 0.00
Received By aaponte Date 2021-06-17 Time 11:50 Sent To  
Notes
2021-06-17 11:51:26 
 1. PLANTING DETAILS FOR GARAGE GREEN SCREEN SHALL BE
 INCLUDED IN THE LANDSCAPE DRAWING, AS WELL AS DETAILED
 MAINTENANCE PROCEDURES FOR THE GREEN SCREEN.
 2. THE EXFILTRATION TRENCH ALONG THE DIXIE FRONTAGE IS
 NEXT TO SOME PROPOSED PALMS. I WOULD LIKE CONFIRMATION
 FROM YOUR ENGINEER THAT THE SEPARATION IS OK AND THEY
 WILL NOT HAVE A PROBLEM WITH THE PALMS SO CLOSE TO THE
 EXFILTRATION TRENCH.
 3. PLEASE INCLUDE INFORMATION ABOUT THE RELOCATION OF
 THE BUS SHELTER. WHERE IS IT GOING TO BE LOCATED? I DID
 NOT SEE IT IN THE SITE PLAN.
 4. PLEASE CONFIRM FOR ME THAT THE LOADING DOCKS INCLUDE
 AN OPAQUE GATE.
 5. I FOUND THE PHOTOMETRICS FOR THE STREET LIGHT, BUT
 NOT THE SPECS FOR THE POLE AND FIXTURE. COULD YOU
 PLEASE TELL ME THE PAGE NUMBER WHERE THE INFORMATION IS
 LOCATED? IT NEEDS TO BE THE CITY STANDARD.
 6. THE DAC ORDER REQUIRES THE SIDEWALK ELEVATION TO BE
 MAINTAINED ACROSS THE DRIVEWAY ENTRANCES. I DON?T THINK
 THE DRAWINGS REFLECT THAT CONDITION. PLEASE CONFIRM. I
 WOULD NEED A DETAIL OR A NOTE IN THE CIVIL DRAWINGS. IT
 IS REALLY HARD TO GET THE CONSTRUCTION TEAM TO DO THIS
 BECAUSE THEY ARE USED TO THE DRIVEWAY PREFERENCE.
 7. PLEASE CONFIRM THAT THE GAS LINES ARE OK TO RUN
 THROUGH THE STRUCTURAL SOIL. THE GAS LINE ON 4TH IS
 GOING THROUGH STRUCTURAL SOIL. THERE ARE ALSO SOME ROOT
 BARRIERS PROPOSED ON THE TREES ON 4TH NEXT TO THE
 STRUCTURAL SOIL, COULD YOU EXPLAIN THE REASON? IT SEEMS
 THAT DEFEATS THE PURPOSE OF THE STRUCTURAL SOIL.
 8. ADA PEDESTRIAN CROSSING AT 4TH AND DIXIE SHALL BE
 APPROVED BY THE ENGINEERING DEPARTMENT.
 9. LANDSCAPE PERMIT SHALL BE SUBMITTED AS A SEPARATE
 PERMIT.
 10. PLEASE PROVIDE A NARRATIVE EXPLAINING THE PARKING
 GARAGE OPERATION THAT ACKNOWLEDGES THE SHARED PARKING
 SYSTEM AND VALET OPERATION.
 11. CAR SHARING STATION SHALL BE CLEARLY LABELED.
 12. CONDITIONS OF APPROVAL INCLUDED IN DAC FINAL ORDER
 AND SITE PLAN APPROVAL LETTER ARE APPLICABLE TO THE
 BUILDING, AND SHALL BE FULFILLED ACCORDINGLY.
 FOR ADDITONAL INFORMATION PLEASE CONTACT ANA MARIA
 APONTE AT 561-822-1439.

Review Stop Z ZONING
Rev No 4 Status F Date 2021-03-04 Cont ID  
Sent By aaponte Date 2021-03-04 Time 16:12 Rev Time 0.00
Received By aaponte Date 2021-03-04 Time 16:12 Sent To  
Notes
2021-03-04 16:11:471. SATISFIED- SHEET A0.102 LIST BUILDING FOOTPRINT
 REQUIREMENT AS MINIMUM PERCENTAGE, IT IS A MAXIMUM
 PERCENTAGE. PLEASE CORRECT DATA TO ACCURATELY REFLECT
 REQUIREMENT.
 2. SATISFIED. SHEET A0.102 STILL LIST 328 RESIDENTIAL
 UNITS WITHIN THE PROJECT DESCRIPTION AND THE REQUIRED
 PARKING DATA. PLEASE ADJUST TO THE CURRENT PROPOSAL OF
 230 UNITS. TABLE IN THE SAME SHEET LIST 202 REGULAR
 RESIDENTIAL UNITS AND 23 MICRO UNITS FOR A TOTAL OF 205
 NOT THE NEW 230 LISTED. PLEASE CORRECT AND ADJUST ALL
 RELATED CALCULATIONS.
 3. NOT SATISFIED. SHEET A1.500 WAS NOT UPLOADED. BASED
 ON SHEET A1.500 PROVIDED BY ARCHITECT IT SEEMS THERE
 ARE SOME HOTEL ROOMS BELOW THE MINIMUM 350SF
 REQUIRED.PREVIOUS COMMENT:IN SHEET A1.500, THE HOTEL
 UNITS DESCRIPTION AND AREAS SUITE 1.3C AND 1.3W UNIT
 AREA IS NOT LISTED. PLEASE UPDATE TABLE AND INCLUDE
 INFORMATION TO CONFIRM COMPLIANCE WITH MINIMUM 350SF
 UNITS SIZE.
 4. SATISFIED. BASED ON SHEET A1.500 PROVIDED BY
 ARCHITECT, NOT IN THE PERMIT SET.PLEASE INCLUDE THIS
 SHEET IN RESUBMITTAL. PREVIOUS COMMENT:PLEASE PROVIDE
 INFORMATION TO CONFIRM THAT REGULAR RESIDENTIAL UNITS
 COMPLY WITH THE AVERAGE 800SF UNIT SIZE.
 5. NOT SATISFIED.PLEASE SUBMIT COLORED ELEVATIONS WITH
 CALL OUT MATERIALS.
 6. NOT SATISFIED. TABLE SUBMITTED BUT NOT GRAPHIC BY
 FLOOR. PLEASE SUBMIT REFLECTING ANY CAHNGES TO THE FAR
 CACLUALTION. PREVIOSU COMMENT:PLEASE SUBMIT THE FAR
 DETAIL INFORMATION PER FLOOR AS SUBMITTED FOR SITE PLAN
 APPROVAL.
 7. NOT SATISTIED.PLEASE INDICATE THE PLANTING AREAS IN
 THE GARAGE LEVESL.PREVIOUS COMMENT:PLEASE EXPLAIN HOW
 THE PLANTS PROPOSED FOR THE GARAGE SCREENING WILL GROW
 AND STILL MAINTAIN THE AIR FLOW REQUIRED FOR GARAGE
 VENTILATION.
 8. SATISFIED.PLEASE CONFIRM THE GLASS UTILIZED FOR THIS
 PROJECT AT THE GROUND FLOOR IS NOT DARK TINTED OR
 REFLECTIVE TO THE POINT THAT THE INTERIOR IS NOT
 VISIBLE FROM OUTSIDE.
 9. SATISFIED. PLEASE INCLUDE DETAILS IN THE LANDSCAPE
 PERMIT. PREVIOUS COMMENT: FURTHER DISCUSSION IS
 NECESSARY FOR THE SELECTION OF THE LANDSCAPE MATERIAL
 TO BE LOCATED ON THE QUADRILLE BLVD MEDIAN.
 10. PARTIALLY SATISFIED. FOR PROJECT RECORDS, PLEASE
 INCLUDE INFORMATION IN THE PERMIT SET. PREVIOUS
 COMMENT: PLEASE CONFIRM PALM TRAM APPROVED THE
 RELOCATION OF THE EXISTING SHELTER TO THE PROPOSED
 LOCATION.
 11. SATISFIED.DUE TO THE PROPOSED MICROUNITS PROJECT IS
 REQUIRED TO PROVIDE 1 CAR SHARING STATION PER EVERY 13
 MICROUNITS. IF PARKING IS PROVIDED FOR THE MICROUNITS
 THERE MUST BE AT LEAST ONE CAR SHARING STATION ON SITE.
 PLEASE IDENTIFY LOCATION OF CAR SHARING STATION INSIDE
 PARKING GARAGE.
 12. ACKNOWLEDGED.DUE TO THE PROPOSED MICROUNITS,
 PROJECT IS REQUIRED TO CONTRIBUTE A FEE INTO THE
 TROLLEY OPERATION FUND. FEE IS EQUAL TO $10 PER
 UNIT/MONTH. AN AGREEMENT WILL BE REQUIRED WITH THE
 PROPERTY OWNER BEFORE FINAL CO.
 13. NOT SATISFIED. PLEASE INCLUDE IN PERMIT SET.
 PREVIOUS COMMENT:PLEASE IDENTIFY THE LOCATION FOR
 MICRO-MOBILITY STATION WITHIN THE PROJECT PUBLIC REALM
 AREA.
 14. NOT SATISFIED. PLEASE INCLUDE IN PERMIT SET.
 MINIMUM ACTIVE USE REQUIREMENT ALONG DIXIE HWAY IS 80%
 NOT 79%. PLEASE ADJUST TO CONFIRM COMPLIANCE.
 15. NOT SATISFIED. PLEASE INCLUDE IN PERMIT SET.THE
 VARIANCE APPROVED BY THE DAC TO REDUCE ACTIVE USES
 ABOVE THE FIRST FLOOR ALONG QUADRILLE BLVD ALLOWED A
 REDUCTION FROM 60% TO 47%. PROPOSED PROJECT LISTS
 ACTIVE USES ONLY ALONG 31.9%. PLEASE INCREASE AMOUNT OF
 ACTIVE USES TO COMPLY WITH VARIANCE APPROVED.
 16. PARTIALLY SATISFIED. THE ADA RAMP NEEDS TO EXPAND
 TO COVER BOTH PEDESTRIAN CROSSINGS N-S AND E-W.
 PREVIOUS COMMENT: PLEASE PROVIDE A PEDESTRIAN CROSSING
 ACROSS DIXIE HWAY FROM THE SE CORNER OF THE PROJECT.
 17. SATISFIED.PLEASE RELOCATE AT LEAST 3 BIKE RACKS
 CLOSER TO THE OFFICE TOWER OPEN SPACE, AND RELOCATE AT
 LEAST 2 BIKE RACKS TO THE AREA CLOSER TO THE PROPOSED
 RETAIL.
 18. GRADING PLAN SHEET 4 HAS LABELS BLACKED OUT.
 19. NOT SATISFIED. LANDSCAPE PERMIT WAS FAILED IN 2018
 AND IT HAS NOT BEEN RESUBMITTED SINCE THEN. A SEPARATE
 LANDSCAPE PERMIT WILL BE REQUIRED FOR THIS PERMIT.
 20. NOT SATISFIED.PLEASE PROVIDE INFORMATION TO CONFIRM
 COMPLIANCE WITH PLANAR BREAK AT ALL APPLICABLE FACADES.
 21. NOT SATISFIED. PLEASE SEE COMMENTS PROVIDED ON
 11/29/2018 AS SOME OF THOSE HAVE NTO BEEN ADDRESSED.
 ADDITIONAL COMMENTS:
 22. WHEN YOU RESUBMIT, PLEASE INCLUDE UPDATED SHEETS TO
 CONFIRM THE ZONING REQUIREMENTS ARE MET AND NOTHING HAS
 CHANGED SINCE SITE PLAN APPROVAL IN RELATIONS TO PLANAR
 BREAKS, ACTIVE USE PERCENTAGES ETC.
 23. IN THE RESPONSE SHEET PLEASE IDENTIFY THE SHEET IN
 WHICH STAFF CAN FIND THE INFORMATION REQUESTED.
 24. PLEASE PROVIDE A NARRATIVE EXPLAINING HOW THE
 PARKING OPERATION IS GOING TO WORK. THERE ARE SEVERAL
 TANDEM SPACES THAT CAN ONLY WORK WITH VALET PARKING
 BECAUSE THE PARKING IS CALCULATED BASED ON A SHARED
 SYSTEM AND SPACES CANNOT BE ASSIGNED TO INDIVIDUAL
 TENANTS.
 25. PLEASE PROVIDE PHOTOMETRICS FOR THE STREETLIGHTS TO
 CONFIRM COMPLIANCE WITH THE MINIMUM 06 FOOTCANDLES
 REQUIRED. STREETLIGHT FIXTURE AND POLE SHALL BE THE
 DOWNTOWN STANDARD.
 FOR ADDITIONAL INFORMATION PLEASE CONTACT ANA MARIA
 APONTE AT 561-822-1439.

Review Stop Z ZONING
Rev No 3 Status F Date 2020-03-19 Cont ID  
Sent By aaponte Date 2020-03-19 Time 16:13 Rev Time 0.00
Received By aaponte Date 2020-03-19 Time 09:44 Sent To  
Notes
2020-03-19 16:13:501. SHEET A0.102 LIST BUILDING FOOTPRINT REQUIREMENT AS
 MINIMUM PERCENTAGE, IT IS A MAXIMUM PERCENTAGE. PLEASE
 CORRECT DATA TO ACCURATELY REFLECT REQUIREMENT.
 2. SHEET A0.102 STILL LIST 328 RESIDENTIAL UNITS WITHIN
 THE PROJECT DESCRIPTION AND THE REQUIRED PARKING DATA.
 PLEASE ADJUST TO THE CURRENT PROPOSAL OF 230 UNITS.
 TABLE IN THE SAME SHEET LIST 202 REGULAR RESIDENTIAL
 UNITS AND 23 MICRO UNITS FOR A TOTAL OF 205 NOT THE NEW
 230 LISTED. PLEASE CORRECT AND ADJUST ALL RELATED
 CALCULATIONS.
 3. IN SHEET A1.500, THE HOTEL UNITS DESCRIPTION AND
 AREAS SUITE 1.3C AND 1.3W UNIT AREA IS NOT LISTED.
 PLEASE UPDATE TABLE AND INCLUDE INFORMATION TO CONFIRM
 COMPLIANCE WITH MINIMUM 350SF UNITS SIZE.
 4. PLEASE PROVIDE INFORMATION TO CONFIRM THAT REGULAR
 RESIDENTIAL UNITS COMPLY WITH THE AVERAGE 800SF UNIT
 SIZE.
 5. PLEASE SUBMIT COLORED ELEVATIONS WITH CALL OUT
 MATERIALS.
 6. PLEASE SUBMIT THE FAR DETAIL INFORMATION PER FLOOR
 AS SUBMITTED FOR SITE PLAN APPROVAL.
 7. PLEASE EXPLAIN HOW THE PLANTS PROPOSED FOR THE
 GARAGE SCREENING WILL GROW AND STILL MAINTAIN THE AIR
 FLOW REQUIRED FOR GARAGE VENTILATION.
 8. PLEASE CONFIRM THE GLASS UTILIZED FOR THIS PROJECT
 AT THE GROUND FLOOR IS NOT DARK TINTED OR REFLECTIVE TO
 THE POINT THAT THE INTERIOR IS NOT VISIBLE FROM
 OUTSIDE.
 9. FURTHER DISCUSSION IS NECESSARY FOR THE SELECTION OF
 THE LANDSCAPE MATERIAL TO BE LOCATED ON THE QUADRILLE
 BLVD MEDIAN.
 10. PLEASE CONFIRM PALM TRAM APPROVED THE RELOCATION OF
 THE EXISTING SHELTER TO THE PROPOSED LOCATION.
 11. DUE TO THE PROPOSED MICROUNITS PROJECT IS REQUIRED
 TO PROVIDE 1 CAR SHARING STATION PER EVERY 13
 MICROUNITS. IF PARKING IS PROVIDED FOR THE MICROUNITS
 THERE MUST BE AT LEAST ONE CAR SHARING STATION ON SITE.
 PLEASE IDENTIFY LOCATION OF CAR SHARING STATION INSIDE
 PARKING GARAGE.
 12. DUE TO THE PROPOSED MICROUNITS, PROJECT IS REQUIRED
 TO CONTRIBUTE A FEE INTO THE TROLLEY OPERATION FUND.
 FEE IS EQUAL TO $10 PER UNIT/MONTH. AN AGREEMENT WILL
 BE REQUIRED WITH THE PROPERTY OWNER BEFORE FINAL CO.
 13. PLEASE IDENTIFY THE LOCATION FOR MICRO-MOBILITY
 STATION WITHIN THE PROJECT PUBLIC REALM AREA.
 14. MINIMUM ACTIVE USE REQUIREMENT ALONG DIXIE HWAY IS
 80% NOT 79%. PLEASE ADJUST TO CONFIRM COMPLIANCE.
 15. THE VARIANCE APPROVED BY THE DAC TO REDUCE ACTIVE
 USES ABOVE THE FIRST FLOOR ALONG QUADRILLE BLVD ALLOWED
 A REDUCTION FROM 60% TO 47%. PROPOSED PROJECT LISTS
 ACTIVE USES ONLY ALONG 31.9%. PLEASE INCREASE AMOUNT OF
 ACTIVE USES TO COMPLY WITH VARIANCE APPROVED.
 16.PLEASE PROVIDE A PEDESTRIAN CROSSING ACROSS DIXIE
 HWAY FROM THE SE CORNER OF THE PROJECT.
 17. PLEASE RELOCATE AT LEAST 3 BIKE RACKS CLOSER TO THE
 OFFICE TOWER OPEN SPACE, AND RELOCATE AT LEAST 2 BIKE
 RACKS TO THE AREA CLOSER TO THE PROPOSED RETAIL.
 18. GRADING PLAN SHEET 4 HAS LABELS BLACKED OUT.
 19. A SEPARATE LANDSCAPE PERMIT WILL BE REQUIRED FOR
 THIS PERMIT.
 20. PLEASE PROVIDE INFORMATION TO CONFIRM COMPLIANCE
 WITH PLANAR BREAK AT ALL APPLICABLE FACADES.
 21. PLEASE SEE COMMENTS PROVIDED ON 11/29/2018 AS SOME
 OF THOSE HAVE NTO BEEN ADDRESSED.
 FOR ADDITIONAL INFORMATION PLEASE CONTACT ANA MARIA
 APONTE AT 561-822-1439.

Review Stop Z ZONING
Rev No 2 Status F Date 2019-04-29 Cont ID  
Sent By aaponte Date 2019-04-29 Time 12:34 Rev Time 0.00
Received By aaponte Date 2019-04-19 Time 14:48 Sent To  
Notes
2019-04-29 12:35:24SITE PLAN APPROVAL NOT COMPLETED YET.

Review Stop Z ZONING
Rev No 1 Status F Date 2018-11-29 Cont ID  
Sent By aaponte Date 2018-11-29 Time 11:41 Rev Time 0.00
Received By aaponte Date 2018-11-28 Time 13:49 Sent To  
Notes
2018-11-28 16:37:431. PROJECT DATA IN SHEET A0.007 DOES NOT MATCH THE
 NUMBER OF RESIDENTIAL UNITS, AND THE TOTAL SQUARE
 FOOTAGE INDICATED IN SURVEY (149,402SF) VS LOT AREA IN
 THIS SHEET (150,245SF). THSI SHEED DOES NOT ACCURATELY
 REFLECT THE GROUND FLOOR LAYOUT (PUBLIC REALM, DROP-OFF
 AREAS)
 2. PLEASE AD A TABLE IN SHEET A0.008 TO INCLUDE THE
 GROSS BUILDING AREA BY USE (OFFICE, RESIDENTIAL
 (UNITS+SF), HOTEL (ROOMS+SF) AND OTHER.
 3. PLANTER AREAS FOR GARAGE ARE TOO FAR FROM SCREEN AND
 LANDSCAPE WILL NOT PROJECT THROUGH SCREEN (SHEET
 A4.300). PLANTING AREA IS 3.5 FEET AWAY FROM SCREEN IN
 SOME CASES.
 4. A MANAGEMENT PLAN SHALL BE PROVIDED TO DESCRIBE HOW
 THE GREEN SCREENS WILL BE ESTABLISHED AND MAINTAINED TO
 ENSURE THE PLANT MATERIAL GROWS TO SCREEN THE GARAGE AS
 INTENDED AND REPRESENTED IN RENDERINGS.
 5. PLEASE SUBMIT DIAGRAMS AND TABLES INDICATING THE
 GROSS BUILDING AREA FOR EACH FLOOR.
 6. PLEASE PROVIDE COLORED ELEVATIONS CLEARLY INDICTING
 EACH OF THE MATERIALS PROPOSED FOR THE FACADE ELEMENTS.
 7. PLEASE PROVIDED BLOW-OUT COLORED ELEVATIONS OF THE
 FIRST FLOOR AND PODIUM, WITH CALL OUT MATEIRIALS AND
 DETAILS.
 8. PLEASE EXPLAIN THE DIFFERENCE BETWEEN THE GREEN
 SCREEN AND THE GREEN WALL INDICATED ON THE 6TH FLOOR.
 9. ON THE SECTION SHEETS, PLEASE PROVIDE A SMALL KEY TO
 IDENTIFY THE LOCATION OF THE SETION.
 10. PLEASE INDICATE THE LOCATION OF THE GLASS DETAILS
 THAT SPECIFICALLY CALL OUT THE TRANSPARENCY OF THE
 GLASS ELEMENTS AT THE GROUND LEVEL. GROUND FLOOR VISUAL
 ACCESS BETWEEN A BUILDING AND ITS ACTIVE USES FROM THE
 PUBLIC SIDEWALK IS REQUIRED.
 11. PROPOSED CURB CUT ON 4TH STREET EXCEEDS THE MAXIMUM
 25 FEEET IN WIDTH ALLOWED.
 12. A SEPARATE LANDSCAPE AND HARDSCAPE PERMIT SHALL BE
 SUBMITTED FOR THIS PROJECT. PLEASE INDICATE THE
 LOCATION OF ALL UTILITY TO CONFIRM NO CONFLICT WITH LA
 OR HARDSCAPE ELEMENTS.
 13. SEPARATE STREETLIGHTING PLAN WITH PHOTOMETRICS
 SHALL BE SUBMITTED FOR THIS PROJECT.
 14. PLEASE DIMENSION PARKING SPACES TO CONFIRM
 COMPLIANCE WITH MINIMUM REQUIREMENTS. SPACE ADJACENT TO
 A WALL OR COLUMN SHALL BE WIDER (SEC 94-111(C))
 15. CURB CUT SHALL BE DESIGNED IN A WAY THAT THE
 SIDEWLK LEVEL IS MAINTAINED ACROSS CURB CUT AND NOT
 LOWERED TO THE ROAD LEVEL. PEDESTRIANS GET PRIORITY,
 NOT THE CARS.
 16. PLEASE PROVIDE A TABLE INDICATING THE SIZE OF THE
 RESIDENTIAL UNITS TO CONFIRM COMPLIANCE WITH MINIMUM
 AVERAGE OF 800SF.
 17. PLEASE INDICATE THE SIZE OF THE HOTEL ROOMS TO
 CONFIRM COMPLIANCE WITH FULL SERVICE HOTEL DEFINITION.
 18. PLEASE INDICATE THE LOCATION OF THE CAR LIFTS.
 19. PLEASE INDICATE THE TENANT ACCESS TO THE BIKE
 STORAGE ROOM.
  
 FOR RESUBMITTAL, PLEASE DRAFT A COMMENT RESPONSE LETTER
 ADDRESSING EACH OF THE COMMENTS, AND THE LOCATION OF
 THE INFORMATION IF APPLICABLE.
  
 FOR ADDITIONAL INFORMATION PLEASE CONTACT ANA MARIA
 APONTE AT 561-822-1439.
  
  