Plan Review Details - Permit 18100540
| Plan Review Stops For Permit 18100540 |
| Review Stop |
AD |
ADDRESSING |
| Rev No |
6 |
Status |
P |
Date |
2021-09-08 |
|
|
Cont ID |
|
| Sent By |
cpuell |
Date |
2021-09-08 |
Time |
08:56 |
Rev Time |
0.00 |
| Received By |
cpuell |
Date |
2021-09-08 |
Time |
08:56 |
Sent To |
|
|
| Notes |
| 2021-09-08 08:59:29 | ADDRESS APPROVED AS FOLLOWS: | | | | | | 500 N QUADRILLE BLVD - PRIMARY ADDRESS | | | 550 N QUADRILLE BLVD - OFFICE BLDG MAIN ENTRANCE | | | 570 N QUADRILLE BLVD - DAYCARE | | | 415 4TH ST - RETAIL | | | 445 4TH ST - EVENT AREA | | | 455 4TH ST - EVENT AREA | | | 465 4TH ST - HOTEL MAIN ENTRANCE | | | 525 N DIXIE HWY - RETAIL | | | 551 N DIXIE HWY - TENNIS LOBBY | | | 555 N DIXIE HWY - CONDOS MAIN ENTRANCE |
|
|
| Review Stop |
AD |
ADDRESSING |
| Rev No |
5 |
Status |
F |
Date |
2021-08-13 |
|
|
Cont ID |
|
| Sent By |
cpuell |
Date |
2021-08-13 |
Time |
08:28 |
Rev Time |
0.00 |
| Received By |
cpuell |
Date |
2021-08-13 |
Time |
08:28 |
Sent To |
|
|
| Notes |
| 2021-08-13 08:29:47 | EMAILED CUSTOMER, EXPLAINED THAT ADDRESSES NEED TO BE | | | ASSIGNED FOR THE DIFFERENT SPACES, ASKED THEM TO CONTAT | | | ME SO WE CAN WORK THROUGH IT. PLEASE CONTACT | | | [email protected] OR CALL 561-805-6659 |
|
|
| Review Stop |
AD |
ADDRESSING |
| Rev No |
4 |
Status |
F |
Date |
2021-05-18 |
|
|
Cont ID |
|
| Sent By |
cpuell |
Date |
2021-05-18 |
Time |
10:14 |
Rev Time |
0.00 |
| Received By |
cpuell |
Date |
2021-05-18 |
Time |
10:14 |
Sent To |
|
|
| Notes |
| 2021-05-18 10:14:56 | CONTACTED CUSTOMER, WAITING ON RESPONCE. PLEASE EMAIL | | | [email protected] |
|
|
| Review Stop |
AD |
ADDRESSING |
| Rev No |
3 |
Status |
F |
Date |
2021-01-26 |
|
|
Cont ID |
|
| Sent By |
cpuell |
Date |
2021-01-26 |
Time |
10:02 |
Rev Time |
0.00 |
| Received By |
cpuell |
Date |
2021-01-26 |
Time |
10:02 |
Sent To |
|
|
| Notes |
| 2021-01-26 10:06:18 | REACHED OUT TO APPLICANT ON 2/19/20 ASKING FOR THEM TO | | | PROVIDE A PLAN SHOWING THE DIFFERENT ENTRANCES TO THE | | | PROPERTY AND IF THEY ARE FOR INDIVIDUAL UNITS. ALL THE | | | OFFICES, HOTEL, APARTMENTS AND RETAIL WILL NEED TO BE | | | ALLOCATED AN ADDRESS, I WOULD LIKE TO COMMENCE WORKING | | | ON THEM BEFORE THE PERMIT IS ISSUED, SO THAT THE PERMIT | | | IS ISSUED WITH THE CORRECT ADDRESS. PLEASE CONTACT | | | [email protected] AND EMAIL REQUIRED DOCUMENTATION. |
|
|
| Review Stop |
AD |
ADDRESSING |
| Rev No |
2 |
Status |
F |
Date |
2020-03-19 |
|
|
Cont ID |
|
| Sent By |
cpuell |
Date |
2020-03-19 |
Time |
10:23 |
Rev Time |
0.00 |
| Received By |
cpuell |
Date |
2020-02-19 |
Time |
11:19 |
Sent To |
|
|
| Notes |
| 2020-02-19 11:20:02 | CONTACTED CUSTOMER, WAITING ON RESPONCE. PLEASE EMAIL | | | [email protected] |
|
|
| Review Stop |
AD |
ADDRESSING |
| Rev No |
1 |
Status |
F |
Date |
2019-04-04 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2019-04-04 |
Time |
05:04 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2019-04-04 |
Time |
05:04 |
Sent To |
|
|
| Notes |
| 2019-04-04 05:04:47 | FOR ADDRESSING, PLEASE CONTACT (PREFERABLY VIA EMAIL): | | | | | | MICHAEL ORIO | | | GIS SUPPORT SPECIALIST | | | [email protected] | | | CITY OF WEST PALM BEACH | | | INFORMATION TECHNOLOGY DEPARTMENT | | | 401 CLEMATIS STREET, WEST PALM BEACH, FLORIDA 33401 | | | P: 561.494.1080 | | | | | | |
|
|
| Review Stop |
AIPP |
ART IN PUBLIC PLACES |
| Rev No |
1 |
Status |
P |
Date |
|
|
|
Cont ID |
|
| Sent By |
|
Date |
2021-09-08 |
Time |
|
Rev Time |
0.00 |
| Received By |
|
Date |
2021-09-08 |
Time |
|
Sent To |
|
|
| Notes |
| 2021-09-08 15:11:17 | **PROVISO** PROVIDED TO MY ATTENTION WITHIN 10 BUSINESS | | | DAYS. | | | | | | MISSING: | | | | | | 1. ARTIST'S QUALIFICATIONS- THIS IS FOR THE RECORD ? | | | CV/BIO/WEBSITE | | | | | | 2. DETAILED DESCRIPTION AND DEPICTION OF THE ARTWORK, | | | INCLUDING CONCEPTUAL APPROACH AND RELEVANT DESIGN | | | INFORMATION. | | | | | | 3. DRAWINGS AND RENDERINGS OF THE PROPOSED ARTWORK, IN | | | TERMS OF SIZE, SCALE, COLOR, SHAPE, AND MATERIALS IN | | | SUFFICIENT DETAIL TO PROVIDE A CLEAR UNDERSTANDING OF | | | THE ART OR ELEMENTS PROPOSED. | | | 4. DRAWINGS AND RENDERINGS SHALL BE TO SCALE, AT THE | | | PROPOSED LOCATION(S) ON SITE PLAN - SHOW SURROUNDING | | | LANDSCAPING, BUILDINGS, LIGHTING, PUBLIC RIGHT-OF-WAY, | | | PLAQUE PLACEMENT, PARKING, FRONTAGE, AND ANY OTHER | | | INFORMATION RELEVANT TO THE SITE AND PLACEMENT. | | | | | | 5. MATERIALS AND METHOD DESCRIPTION INCLUDING ALL | | | PROPOSED MATERIALS AND INSTALLATION | | | | | | 6. SCHEDULE. PROPOSED PROJECT SCHEDULE AND PROJECT | | | DEVELOPMENT TIMELINES, INCLUDING CITY REVIEWS AND | | | ARTWORK INSTALLATION SCHEDULE. | | | | | | BY CITY CODE THE ARTWORK MUST BE REVIEWED BY THE | | | ARTLIFE (PUBLIC ART) COMMITTEE AND BE RECOMMENDED TO | | | CITY COMMISSION BEFORE ARTIST MAY BEGIN PRODUCTION. | | | | | | ALLOW TWO MONTHS FOR REVIEW PROCESS. ALLOW 15 TO 18 | | | MONTHS FOR PRODUCTION/FABRICATION FROM AN ARTIST | | | STUDIO. | | | | | | CALL ME WITH ANY QUESTIONS. | | | | | | SYBILLE | | | | | | SYBILLE WELTER | | | ADMINISTRATOR OF PUBLIC ART AND CULTURE | | | CITY OF WEST PALM BEACH | | | | | | PUBLIC ART FOR AN INSPIRED CITY | | | 401 CLEMATIS STREET | | | WEST PALM BEACH, FL 33401 | | | DIRECT: 561.822.1521 | | | [email protected] | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
6 |
Status |
P |
Date |
2021-09-03 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2021-09-03 |
Time |
17:14 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2021-09-03 |
Time |
15:36 |
Sent To |
|
|
| Notes |
| 2021-09-03 17:14:26 | DEFERRED SUBMITTALS | | | SEE SHEET A0.001 FOR LIST OF DEFERRED ITEMS. | | | PER THE DESIGNER THE SALES AND SERVICE COUNTERS | | | DRAWINGS AND DETAILS WILL BE PROVIDED FOR APPROVAL AT A | | | LATER DATE. | | | | | | NOTE: SEPARATE PERMITS (APPLICATIONS, PLANS, AND FEES) | | | ARE REQUIRED FOR: | | | LIGHT POLES/SITE LIGHTING | | | FIRE ALARM | | | FIRE SPRINKLER | | | LOW VOLTAGE | | | ACCESS | | | LANDSCAPING | | | IRRIGATION | | | PARKING LOT | | | SWIMMING POOLS AND SPAS - THE POOL DRAWINGS | | | 13.001-SP.001 THRU 13.033-SP.750 ARE NOT LISTED IN THE | | | INDEX OF PLANS. SEPARATE POOL/SPA PERMITS WILL BE | | | REQUIRED FOR THE (3) POOLS/SPAS. | | | GENERATORS | | | ALL OTHER ITEMS OTHER THAN BMEP | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
5 |
Status |
F |
Date |
2021-08-24 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2021-08-24 |
Time |
17:09 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2021-08-23 |
Time |
15:50 |
Sent To |
|
|
| Notes |
| 2021-08-24 17:08:58 | BUILDING REVIEW COMMENTS: | | | | | | W.P.B. PERMIT: 18100540 | | | 550 N. QUADRILLE BLVD. | | | BUILDING PERMIT 30 STORY BLDG W/ TWO TOWERS | | | CONSTRUCTION TYPE: 1A, SPRINKLERED | | | MIXED OCCUPANCY: B, R-1, R-2, A-2, A4, S-2, M, E | | | | | | 1 ST REVIEW: APRIL 18, 2019 - DYLAN BATTLES | | | 2 ND REVIEW: MARCH 2, 2020 - DYLAN BATTLES | | | 3 RD REVIEW: JANUARY 13, 2021 - ROBERT MCDOUGAL | | | 4 TH REVIEW: JUNE 10, 2021 - ROBERT MCDOUGAL | | | 5 TH REVIEW: AUGUST 23, 2021 - ROBERT MCDOUGAL | | | | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | FLORIDA BUILDING CODE,5TH EDITION (2014) | | | FBC[AMENDED] = 2014 CHAPTER 1 WPB AMENDMENTS (SEE LINK | | | BELOW) | | | HTTPS://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/ | | | BUILDING-PERMIT-FORMS | | | FBC[B] = FBC BUILDING | | | FBC[A] = FBC ACCESSIBILITY | | | FBC[E] = FBC ENERGY CONSERVATION | | | | | | | | | BUILDING REVIEW COMMENTS: | | | | | | 1) RESOLVED. | | | | | | A) RESOLVED. | | | | | | B) RESOLVED. | | | | | | C) RESOLVED. | | | | | | D) RESOLVED. | | | | | | E) RESOLVED. | | | | | | F) RESOLVED. | | | | | | G) RESOLVED. | | | | | | H) RESOLVED. | | | | | | 2) RESOLVED. | | | | | | 3) RESOLVED. | | | | | | 4) RESOLVED. | | | | | | 5) RESOLVED. | | | | | | 6) RESOLVED. | | | | | | FAIRHOUSING REVIEW: | | | | | | 7) RESOLVED. | | | | | | A) RESOLVED. | | | | | | B) RESOLVED. | | | | | | C) RESOLVED. | | | | | | D) RESOLVED. | | | | | | E) RESOLVED. | | | | | | F) RESOLVED. | | | | | | LIFE SAFETY: | | | | | | 8) RESOLVED. | | | | | | 9) RESOLVED. | | | | | | 10) RESOLVED. | | | | | | 11) RESOLVED. | | | | | | 12) RESOLVED. | | | | | | 13) RESOLVED. | | | | | | 14) RESOLVED. | | | | | | 15) RESOLVED. | | | | | | 16) NOT COMPLETELY RESOLVED. [RAMP 4 STILL DOES NOT | | | COMPLY.] [ RAMP 4 ON A1.228 IS REQUIRED TO HAVE A | | | LANDING WITH 60" X 60" CLEAR SPACE AT THE CHANGE IN | | | DIRECTION. RAMP 8 ON 5.123 REQUIRES A 60" (5') CLEAR | | | LANDING AND THE DRAWING HAS 59" (4'-11"). FBC-A 405.7] | | | THERE ARE SEVERAL RAMPS SHOWN ON THE PLANS. PLEASE | | | IDENTIFY EACH WITH AN ID TAG AND PROVIDE DETAILS FOR | | | EACH OF THEM TO SHOW THAT THEY MEET THE ACCESSIBILITY | | | REQUIREMENTS FOR RAMPS. FBC ACCESSIBILITY 405. 1003.5 | | | FBC[B] ELEVATION CHANGE. DOES EXIT FROM RESIDENT LOBBY | | | TO STAIR 2 HAVE STEPS? PLEASE REVIEW | | | -HOW DO STEPS WORK AT EGRESS FROM RESIDENT LOUNGE TO | | | STAIR ST2? PLEASE REVIEW 1003.5 FOR CHANGE IN ELEVATION | | | IN PATH OF EGRESS. | | | | | | 17) RESOLVED. | | | | | | 18) RESOLVED. | | | | | | 19) RESOLVED. | | | | | | 20) RESOLVED. | | | | | | DEFERRED SUBMITTALS | | | 21) RESOLVED. SEE SHEET A0.001 FOR LIST OF DEFERRED | | | ITEMS. | | | | | | 22) DEFERRED. | | | | | | 23) RESOLVED. | | | | | | ACCESSIBILITY REVIEW: | | | | | | 24) RESOLVED. | | | | | | 25) RESOLVED. | | | | | | 26) RESOLVED. THE POOL DRAWINGS 13.001-SP.001 THRU | | | 13.033-SP.750 ARE NOT LISTED IN THE INDEX OF PLANS. | | | SEPARATE POOL/SPA PERMITS WILL BE REQUIRED FOR THE (3) | | | POOLS/SPAS. | | | | | | 27) RESOLVED. | | | | | | CHAPTER 4 - HIGHRISE: | | | | | | 28) RESOLVED. | | | | | | 29) RESOLVED. | | | | | | 30) RESOLVED. BUILDING IS LESS THAN 420 FEET IN HEIGHT. | | | | | | NEW COMMENTS: | | | | | | 31) RESOLVED. | | | | | | 32) RESOLVED. | | | | | | 33) RESOLVED. | | | | | | 34) RESOLVED. | | | | | | 35) NOT RESOLVED. [THE EXITS STILL DO NOT COMPLY.] [ | | | BASED ON THE NUMBERS THAT YOU HAVE PROVIDED (487 OCC.) | | | THE CAPACITY OF THE TWO EXISTS THAT ARE PROVIDED ARE | | | NOT ADEQUATE FOR THE OCCUPANT LOAD OF THIS AREA. SEE | | | FBC SECTIONS 1004, 1005 AND 1006. FBC 1005.5 | | | DISTRIBUTION OF EGRESS CAPACITY WHERE MORE THAN ONE | | | EXIT, OR ACCESS TO MORE THAN ONE EXIT, IS REQUIRED, THE | | | MEANS OF EGRESS SHALL BE CONFIGURED SUCH THAT THE LOSS | | | OF ANY ONE EXIT, OR ACCESS TO ONE EXIT, SHALL NOT | | | REDUCE THE AVAILABLE CAPACITY TO LESS THAN 50 PERCENT | | | OF THE REQUIRED CAPACITY. CHECK THE AREA AND OCCUPANT | | | LOAD AND PROVIDE CODE COMPLIANT EGRESS. ] | | | ON PAGE 04.024 -ALS1.109, SHOW THE TOTAL OCCUPANT LOAD | | | OF THE TERRACE AND PICKLE BALL COURTS, THE LOADS AT | | | EACH EXIT DOOR AND THE COMBINED LOADS AT THE HOTEL AND | | | RESIDENT EXIT STAIRWAYS. FBC 1004 | | | | | | 36) RESOLVED. | | | | | | 37) RESOLVED. | | | | | | 38) RESOLVED. | | | | | | 39) RESOLVED. | | | | | | 40) RESOLVED. | | | | | | 41) RESOLVED. | | | | | | 42) RESOLVED. | | | | | | 43) DEFERRED. PER THE DESIGNER THE SALES AND SERVICE | | | COUNTERS DRAWINGS AND DETAILS WILL BE PROVIDED FOR | | | APPROVAL AT A LATER DATE. NOT RESOLVED. [THE ONLY PLAN | | | SHEET I SAW WAS ID7.010 SUBMITTED AS AN ATTACHED | | | SUPPLEMENTAL DOCUMENT. IT ONLY HAS THE RECEPTION DESKS | | | FOR THE HOTEL AND THE RESIDENTIAL UNITS. SALES AND | | | SERVICE COUNTERS ARE REQUIRED TO COMPLY WITH | | | FBC-ACCESSIBILITY 904.4 SALES COUNTERS AND SERVICE | | | COUNTERS SHALL COMPLY WITH 904.4.1 OR 904.4.2. THE | | | ACCESSIBLE PORTION OF THE COUNTER TOP SHALL EXTEND THE | | | SAME DEPTH AS THE SALES OR SERVICE COUNTER TOP. THE | | | SHEET IS NOT SIGNED AND SEALED. WHAT ABOUT THE OTHER | | | COMMON AREA ITEMS?] I DID NOT SEE THE | | | DETAILS/ELEVATIONS OF BUILT-IN ITEMS IN THE COMMON USE | | | AREAS, SUCH AS RECEPTION DESKS, SERVICE COUNTERS, BREAK | | | ROOM KITCHENS, ETC. THAT ARE REQUIRED TO BE ACCESSIBLE | | | PER FBC ACCESSIBILITY CHAPTERS 8 AND 9. PLEASE INDICATE | | | SHEETS THEY ARE ON OR PROVIDE SHEETS WITH DETAILS AND | | | ELEVATIONS FOR THESE ITEMS. | | | | | | 44) NOTE: ADDITIONAL COMMENTS MAY RESULT FROM THE | | | RESPONSES TO THESE PLAN REVIEW COMMENTS. | | | | | | -PROVIDE COMMENT RESPONSE SHEET TO EXPLAIN HOW EACH | | | COMMENT IS BEING ADDRESSED. | | | -FEEL FREE TO CONTACT ME AT 561-805-6714 (M-F 8-5) TO | | | DISCUSS COMMENTS, OR E-MAIL ANYTIME [email protected] | | | | | | NOTE: SEPARATE PERMITS (APPLICATIONS, PLANS, AND FEES) | | | ARE REQUIRED FOR: | | | LIGHT POLES/SITE LIGHTING | | | FIRE ALARM | | | FIRE SPRINKLER | | | LOW VOLTAGE | | | ACCESS | | | LANDSCAPING | | | IRRIGATION | | | PARKING LOT | | | SWIMMING POOLS AND SPAS | | | GENERATORS | | | ALL OTHER ITEMS OTHER THAN BMEP | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
4 |
Status |
F |
Date |
2021-06-21 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2021-06-21 |
Time |
11:51 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2021-06-10 |
Time |
10:01 |
Sent To |
|
|
| Notes |
| 2021-06-10 10:09:35 | BUILDING REVIEW COMMENTS: | | | | | | W.P.B. PERMIT: 18100540 | | | 550 N. QUADRILLE BLVD. | | | BUILDING PERMIT 30 STORY BLDG W/ TWO TOWERS | | | CONSTRUCTION TYPE: 1A, SPRINKLERED | | | MIXED OCCUPANCY: B, R-1, R-2, A-2, A4, S-2, M, E | | | | | | 1 ST REVIEW: APRIL 18, 2019 - DYLAN BATTLES | | | 2 ND REVIEW: MARCH 2, 2020 - DYLAN BATTLES | | | 3 RD REVIEW: JANUARY 13, 2021 - ROBERT MCDOUGAL | | | 4 TH REVIEW: JUNE 10, 2021 - ROBERT MCDOUGAL | | | | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | FLORIDA BUILDING CODE,5TH EDITION (2014) | | | FBC[AMENDED] = 2014 CHAPTER 1 WPB AMENDMENTS (SEE LINK | | | BELOW) | | | HTTPS://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/ | | | BUILDING-PERMIT-FORMS | | | FBC[B] = FBC BUILDING | | | FBC[A] = FBC ACCESSIBILITY | | | FBC[E] = FBC ENERGY CONSERVATION | | | | | | | | | BUILDING REVIEW COMMENTS: | | | | | | 1) RESOLVED. | | | | | | A) RESOLVED. | | | | | | B) RESOLVED. | | | | | | C) RESOLVED. | | | | | | D) RESOLVED. | | | | | | E) RESOLVED. | | | | | | F) RESOLVED. | | | | | | G) RESOLVED. | | | | | | H) RESOLVED. | | | | | | 2) RESOLVED. | | | | | | 3) RESOLVED. | | | | | | 4) RESOLVED. | | | | | | 5) RESOLVED. | | | | | | 6) RESOLVED. | | | | | | FAIRHOUSING REVIEW: | | | | | | 7) RESOLVED. | | | | | | A) PARTIALLY RESOLVED. [ UNIT B-1 ON SHEET A1.524, DOES | | | NOT APPEAR TO COMPLY WITH FAIR HOUSING SPECIFICATION B | | | BATHROOMS. THE ACCESS TO THE BATHTUB CONTROLS CAN NOT | | | BE OBSTRUCTED BY THE TOILET OR VANITY IN ONE OF THE | | | BATHROOMS IN ORDER TO BE A SPECIFICATION B. ] THE TUBS | | | PAGE 03.097(A1.519) THE MASTER BATH TOILET IN | | | RESIDENTIAL UNIT S8 DOES NOT APPEAR TO COMPLY WITH A | | | TYPE B BATHROOM. ON PAGE 03.102(A1.524) RESIDENTIAL | | | UNIT B1 HAS ONE BATH ROOM MARKED AS TYPE A AND THE | | | OTHER AS TYPE B. THE UNIT CAN ONLY BE ONE TYPE. ON PAGE | | | 03.104(A1.526) SHOW THE REQUIRED CLEAR FLOOR SPACE AT | | | THE TOILET IN UNIT B3.1. IT WOULD BE HELPFUL TO ADD A | | | MATRIX OF ROOMS ON SHEET A1.500 WHICH BATHROOM SPEC IS | | | BEING USED AND APPLY THE FOLLOWING FOR SPEC A AND B | | | | | | SPECIFICATION A: | | | IF SPECIFICATION A IS USED IT APPLIES TO ALL BATHROOMS, | | | AND ALL FIXTURES IN THOSE BATHROOMS MUST BE USABLE. ALL | | | BATHROOMS IN THAT UNIT ARE REQUIRED TO MEET THE | | | SPECIFICATION A REQUIREMENTS. | | | SPECIFICATION B: | | | IF SPECIFICATION B IS USED, IT APPLIES TO ONE BATHROOM, | | | AND ONLY ONE OF EACH TYPE OF FIXTURE MUST BE USABLE; | | | ADDITIONAL BATHROOMS IN THE UNIT ARE EXEMPT ONLY FROM | | | MANEUVERING AND CLEAR FLOOR SPACE REQUIREMENTS AT | | | FIXTURES. | | | | | | B) RESOLVED. | | | | | | C) RESOLVED. | | | | | | D) RESOLVED. | | | | | | E) RESOLVED. | | | | | | F) RESOLVED. | | | | | | LIFE SAFETY: | | | | | | 8) RESOLVED. | | | | | | 9) RESOLVED. | | | | | | 10) RESOLVED. | | | | | | 11) RESOLVED. | | | | | | 12) RESOLVED. | | | | | | 13) RESOLVED. | | | | | | 14) RESOLVED. | | | | | | 15) RESOLVED. | | | | | | 16) NOT COMPLETELY RESOLVED. [ RAMP 4 ON A1.228 IS | | | REQUIRED TO HAVE A LANDING WITH 60" X 60" CLEAR SPACE | | | AT THE CHANGE IN DIRECTION. RAMP 8 ON 5.123 REQUIRES A | | | 60" (5') CLEAR LANDING AND THE DRAWING HAS 59" | | | (4'-11"). FBC-A 405.7] THERE ARE SEVERAL RAMPS SHOWN ON | | | THE PLANS. PLEASE IDENTIFY EACH WITH AN ID TAG AND | | | PROVIDE DETAILS FOR EACH OF THEM TO SHOW THAT THEY MEET | | | THE ACCESSIBILITY REQUIREMENTS FOR RAMPS. FBC | | | ACCESSIBILITY 405. 1003.5 FBC[B] ELEVATION CHANGE. DOES | | | EXIT FROM RESIDENT LOBBY TO STAIR 2 HAVE STEPS? PLEASE | | | REVIEW | | | -HOW DO STEPS WORK AT EGRESS FROM RESIDENT LOUNGE TO | | | STAIR ST2? PLEASE REVIEW 1003.5 FOR CHANGE IN ELEVATION | | | IN PATH OF EGRESS. | | | | | | 17) RESOLVED. | | | | | | 18) RESOLVED. | | | | | | 19) RESOLVED. | | | | | | 20) RESOLVED. | | | | | | DEFERRED SUBMITTALS | | | 21) RESOLVED. SEE SHEET A0.001 FOR LIST OF DEFERRED | | | ITEMS. | | | | | | 22) DEFERRED. | | | | | | 23) RESOLVED. | | | | | | ACCESSIBILITY REVIEW: | | | | | | 24) RESOLVED. | | | | | | 25) RESOLVED. | | | | | | 26) RESOLVED. THE POOL DRAWINGS 13.001-SP.001 THRU | | | 13.033-SP.750 ARE NOT LISTED IN THE INDEX OF PLANS. | | | SEPARATE POOL/SPA PERMITS WILL BE REQUIRED FOR THE (3) | | | POOLS/SPAS. | | | | | | 27) RESOLVED. | | | | | | CHAPTER 4 - HIGHRISE: | | | | | | 28) RESOLVED. | | | | | | 29) RESOLVED. | | | | | | 30) NOT RESOLVED. [ RESPONSE TO COMMENT STATES THAT IT | | | HAS BEEN DETERMINED THAT NEITHER BUILDING EXCEEDS 420' | | | IN HEIGHT THUS THE REQUIREMENTS OF FBC 403.3.1 ARE NOT | | | APPLICABLE. PLEASE PROVIDE DETAILS OF HOW THIS WAS | | | DETERMINED. THE FBC DEFINES BUILDING HEIGHT AS THE | | | VERTICAL DISTANCE FROM GRADE PLAIN TO THE AVERAGE | | | HEIGHT OF THE HIGHEST ROOF SURFACE. THE DEFINITION OF | | | GRADE PLANE IS A REFERENCE PLANE REPRESENTING THE | | | AVERAGE OF FINISHED GROUND LEVEL ADJOINING THE BUILDING | | | AT THE EXTERIOR WALLS. THE PLAN ELEVATIONS SHOW THAT | | | THE HIGH ROOF OF THE OFFICE BUILDING IS 437'-0"NAVD AND | | | THE AVERAGE GRADE AT THE BUILDING IS AROUND 15' NAVD. | | | THIS WOULD MEAN THAT THE BUILDING HEIGHT IS 437' - 15' | | | OR 422'. ] ADD NOTES TO PAGE 10.001 SHEET FR.001 THAT | | | SPECIFY THAT A MINIMUM OF TWO RISERS WILL BE PROVIDED | | | AND THAT EACH RISER SHALL SUPPLY SPRINKLERS ON | | | ALTERNATE FLOORS. 403.3.1 FBC[B]NUMBER OF SPRINKLER | | | RISERS AND SYSTEM DESIGN. EACH SPRINKLER SYSTEM ZONE IN | | | BUILDINGS THAT ARE MORE THAN 420 FEET (128 000 MM) IN | | | BUILDING HEIGHT SHALL BE SUPPLIED BY NO FEWER THAN TWO | | | RISERS. EACH RISER SHALL SUPPLY SPRINKLERS ON ALTERNATE | | | FLOORS. IF MORE THAN TWO RISERS ARE PROVIDED FOR A | | | ZONE, SPRINKLERS ON ADJACENT FLOORS SHALL NOT BE | | | SUPPLIED FROM THE SAME RISER. | | | -PLEASE SEE HOW THIS APPLIES TO OFFICE TOWER ONLY AND | | | UPDATE FS DRAWINGS AS APPLICABLE. | | | | | | NEW COMMENTS: | | | | | | 31) RESOLVED. | | | | | | 32) RESOLVED. | | | | | | 33) RESOLVED. | | | | | | 34) RESOLVED. | | | | | | 35) NOT RESOLVED. [ BASED ON THE NUMBERS THAT YOU HAVE | | | PROVIDED (487 OCC.) THE CAPACITY OF THE TWO EXISTS THAT | | | ARE PROVIDED ARE NOT ADEQUATE FOR THE OCCUPANT LOAD OF | | | THIS AREA. SEE FBC SECTIONS 1004, 1005 AND 1006. FBC | | | 1005.5 DISTRIBUTION OF EGRESS CAPACITY WHERE MORE THAN | | | ONE EXIT, OR ACCESS TO MORE THAN ONE EXIT, IS REQUIRED, | | | THE MEANS OF EGRESS SHALL BE CONFIGURED SUCH THAT THE | | | LOSS OF ANY ONE EXIT, OR ACCESS TO ONE EXIT, SHALL NOT | | | REDUCE THE AVAILABLE CAPACITY TO LESS THAN 50 PERCENT | | | OF THE REQUIRED CAPACITY. CHECK THE AREA AND OCCUPANT | | | LOAD AND PROVIDE CODE COMPLIANT EGRESS. ] | | | ON PAGE 04.024 -ALS1.109, SHOW THE TOTAL OCCUPANT LOAD | | | OF THE TERRACE AND PICKLE BALL COURTS, THE LOADS AT | | | EACH EXIT DOOR AND THE COMBINED LOADS AT THE HOTEL AND | | | RESIDENT EXIT STAIRWAYS. FBC 1004 | | | | | | 36) RESOLVED. | | | | | | 37) RESOLVED. | | | | | | 38) RESOLVED. | | | | | | 39) RESOLVED. | | | | | | 40) RESOLVED. | | | | | | 41) RESOLVED. | | | | | | 42) RESOLVED. | | | | | | 43) NOT RESOLVED. [THE ONLY PLAN SHEET I SAW WAS | | | ID7.010 SUBMITTED AS AN ATTACHED SUPPLEMENTAL DOCUMENT. | | | IT ONLY HAS THE RECEPTION DESKS FOR THE HOTEL AND THE | | | RESIDENTIAL UNITS. SALES AND SERVICE COUNTERS ARE | | | REQUIRED TO COMPLY WITH FBC-ACCESSIBILITY 904.4 SALES | | | COUNTERS AND SERVICE COUNTERS SHALL COMPLY WITH 904.4.1 | | | OR 904.4.2. THE ACCESSIBLE PORTION OF THE COUNTER TOP | | | SHALL EXTEND THE SAME DEPTH AS THE SALES OR SERVICE | | | COUNTER TOP. THE SHEET IS NOT SIGNED AND SEALED. WHAT | | | ABOUT THE OTHER COMMON AREA ITEMS?] I DID NOT SEE THE | | | DETAILS/ELEVATIONS OF BUILT-IN ITEMS IN THE COMMON USE | | | AREAS, SUCH AS RECEPTION DESKS, SERVICE COUNTERS, BREAK | | | ROOM KITCHENS, ETC. THAT ARE REQUIRED TO BE ACCESSIBLE | | | PER FBC ACCESSIBILITY CHAPTERS 8 AND 9. PLEASE INDICATE | | | SHEETS THEY ARE ON OR PROVIDE SHEETS WITH DETAILS AND | | | ELEVATIONS FOR THESE ITEMS. | | | | | | 44) NOTE: ADDITIONAL COMMENTS MAY RESULT FROM THE | | | RESPONSES TO THESE PLAN REVIEW COMMENTS. | | | | | | -PROVIDE COMMENT RESPONSE SHEET TO EXPLAIN HOW EACH | | | COMMENT IS BEING ADDRESSED. | | | -FEEL FREE TO CONTACT ME AT 561-805-6714 (M-F 8-5) TO | | | DISCUSS COMMENTS, OR E-MAIL ANYTIME [email protected] | | | | | | NOTE: SEPARATE PERMITS (APPLICATIONS, PLANS, AND FEES) | | | ARE REQUIRED FOR: | | | LIGHT POLES/SITE LIGHTING | | | FIRE ALARM | | | FIRE SPRINKLER | | | LOW VOLTAGE | | | ACCESS | | | LANDSCAPING | | | IRRIGATION | | | PARKING LOT | | | SWIMMING POOLS AND SPAS | | | GENERATORS | | | ALL OTHER ITEMS OTHER THAN BMEP | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
F |
Date |
2021-02-03 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2021-02-03 |
Time |
12:33 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2021-01-13 |
Time |
13:48 |
Sent To |
|
|
| Notes |
| 2021-01-29 10:39:57 | BUILDING REVIEW COMMENTS: | | | | | | W.P.B. PERMIT: 18100540 | | | 550 N. QUADRILLE BLVD. | | | BUILDING PERMIT 30 STORY BLDG W/ TWO TOWERS | | | CONSTRUCTION TYPE: 1A, SPRINKLERED | | | MIXED OCCUPANCY: B, R-1, R-2, A-2, A4, S-2, M, E | | | | | | 1 ST REVIEW: APRIL 18, 2019 - DYLAN BATTLES | | | 2 ND REVIEW: MARCH 2, 2020 - DYLAN BATTLES | | | 3 RD REVIEW: JANUARY 13, 2021 - ROBERT MCDOUGAL | | | | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | FLORIDA BUILDING CODE,5TH EDITION (2014) | | | FBC[AMENDED] = 2014 CHAPTER 1 WPB AMENDMENTS (SEE LINK | | | BELOW) | | | HTTPS://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/ | | | BUILDING-PERMIT-FORMS | | | FBC[B] = FBC BUILDING | | | FBC[A] = FBC ACCESSIBILITY | | | FBC[E] = FBC ENERGY CONSERVATION | | | | | | 1) NOT RESOLVED. THERE ARE STILL SOME ERRORS AND THE | | | PAGE DID NOT LOAD PROPERLY. THE BOTTOM OF THE SHEET IS | | | CUT OFF AND THERE IS A PARTIAL SHEET AT THE TOP. | | | 107.5.3 FBC[AMENDED]PLEASE UPDATE SHEET A0.102 SITE | | | DATA. THE DIAGRAM IN THE UPPER RIGHT CORNER DOESN'T | | | REFLECT THE CHANGES IN ROOMS SHOWN IN THE PLANS. | | | COMPARE SHEET A1.500 FOR SUITE AND UNIT COUNTS. | | | | | | A) NOT RESOLVED. THERE ARE SEVERAL PAGES OF THE SAME | | | SHEETS. RATHER THAN BEING THE SAME SHEET VERSION-ED, | | | THERE IS A PAGE WITH THE OLD PLAN SHEET AND A PAGE WITH | | | THE REVISED PLAN SHEET. AS A GENERAL COMMENT, PLEASE | | | LOOK IN PROJECTDOX AND NOTE IF SOME SHEETS MAY NOT HAVE | | | BEEN REPLACED FOR SECOND REVIEW. EITHER UPLOAD REVISED | | | SHEETS, LEAVE IT DIDN'T CHANGE OR REQUEST IT TO BE | | | DELETED. | | | | | | B) NOT RESOLVED COMPLETELY. A PORTION OF THE WALL IS | | | MISSING BETWEEN UNIT B-1 AND THE UNIT ABOVE IT THAT IS | | | NOT LABELED. THE WOMENS BATHROOM AT THE PREFUNCTION | | | AREA IS MISSING DETAILS. SEE MARKUPS ON SHEET A1.260. | | | LEVEL 8 - SHEET A1.260. IS THE COLUMN LAYER TURNED OFF? | | | ALSO, MISSING UNIT NUMBER ABOVE UNIT B1 08-22 | | | THIS SHEET WAS NOT REVISED FROM FIRST REVIEW SO I THINK | | | IT REFLECTS OLD LAYOUT. PLEASE UPLOAD NEW LEVEL 8 | | | RESIDENTIAL SHEET. | | | | | | C) NOT RESOLVED. SEE SHEETS PAGES 03.071(A1.265) AND | | | 03.072(A1.266) FOR REDUNDANT AND CONFLICTING | | | INFORMATION. LEVEL 13-14 - 08 UNITS EACH FLOOR . SHEET | | | A1.265 SAYS LEVEL 13-14, BUT THEN THE NEXT SHEET IS | | | LEVEL 14. PLEASE ADJUST TITLE BLOCK TO STATE LEVEL 13 | | | ONLY. | | | | | | D) NOT RESOLVED. PAGE 03.072(A1.266) IS STILL IN THE | | | PLANS. LEVEL 14 - 08 UNITS. SHEET A1.266 IS THE COLUMN | | | LAYER TURNED OFF? ALSO, MISSING UNIT NUMBERS. | | | | | | E) RESOLVED. LEVEL 3 - MISSING SUITE NUMBER NEXT TO | | | SUITE 7.1 ON SHEET A1.103. LOOKS LIKE IT SHOULD BE | | | SUITE 8. | | | | | | F) RESOLVED. LEVEL 9 - MISSING SUITE NUMBER NEXT | | | BETWEEN SUITE 1.3B AND 1.3D ON SHEET A1.109 | | | | | | G) RESOLVED. LEVEL 16 - SUITE 2B ADA LOOKS LIKE WALL | | | WAS LEFT BETWEEN ENTRY AND SLEEPING AREA. | | | | | | H) RESOLVED. LEVEL 17, I CAN'T FIND OFFICE LEVEL FLOOR | | | PLAN. I DO SEE RCP AND LIFE SAFETY. PLEASE CHECK IF IT | | | WAS LOADED INTO PROJECT DOX. | | | | | | 2) NOT RESOLVED. PAGE 03.052 (A1.240) WAS NOT UPDATED | | | AND IS STILL IN THE PLANS. 107.5.3 FBC[AMENDED]SHEET | | | 03.052 - A1.240 - HOTEL TOWER FLOOR PLAN - LEVEL 8 HAS | | | NOT BEEN UPDATED. PLEASE UPLOAD A NEW VERSION, OR | | | REQUEST IT BE DELETED FROM THE FOLDER. LEVEL EIGHT IS | | | SHOWN ON PODIUM LEVEL 8 DRAWING 03.014 - A1.108 - | | | PODIUM FLOOR PLAN AND IN QUADRANT PAGES AS WELL. | | | | | | 3) NOT RESOLVED. THERE ARE STILL SOME ISSUES WITH THE | | | ADA REQUIREMENTS. THE GUEST ROOM MATRIX ON PAGE 03.082 | | | (A1.500) HAS THE REQUIRED ADA ROOMS WITH MOBILITY | | | FEATURES AS (5) ROOMS WITHOUT ROLL-IN SHOWERS, (2) | | | ROOMS WITH ROLL-IN SHOWERS. THE 2010 ADA TABLE 224.2 | | | REQUIRES (6) ROOMS WITHOUT ROLL-IN SHOWERS, (2) ROOMS | | | WITH ROLL-IN SHOWERS FOR A TOTAL OF (8) ROOMS. THE ADA | | | REQUIREMENTS FOR GUEST ROOMS WITH COMMUNICATION | | | FEATURES IN TABLE 224.4 IS 14 ROOMS WHEN 200 GUEST | | | ROOMS ARE PROVIDED. AT LEAST ONE GUEST ROOM REQUIRED TO | | | PROVIDE MOBILITY FEATURES COMPLYING WITH 806.2 SHALL | | | ALSO PROVIDE COMMUNICATION FEATURES COMPLYING WITH | | | 806.3. NOT MORE THAN 10 PERCENT OF GUEST ROOMS REQUIRED | | | TO PROVIDE MOBILITY FEATURES COMPLYING WITH 806.2 SHALL | | | BE USED TO SATISFY THE MINIMUM NUMBER OF GUEST ROOMS | | | REQUIRED TO PROVIDE COMMUNICATION FEATURES COMPLYING | | | WITH 806.3. REVISE THE ROOM MATRIX TO CLEARLY SHOW | | | COMPLIANCE OF SPECIFIC ROOMS. ALSO REVISE THE PLANS TO | | | COMPLY. | | | 107.5.3 FBC[AMENDED]PLEASE ADD COMMUNICATION SYMBOL TO | | | SUITE 4.2B ON SHEET A1.243 ROOM SUMMARY SHEET STATES | | | LEVEL 12-15 AS COMMUNICATION. PLEASE ADD SYMBOL TO | | | THOSE ROOMS AS WELL. ADD BOTH SYMBOLS TO SUITE 2.B ON | | | SHEET A1.246 | | | PLEASE LOOK AT MOBILITY FEATURES DATA LAST LINE WHERE | | | IT SAYS LEVEL 8-16 SUITE 4.2B. I DO SEE THAT THERE IS | | | ADA ON LEVEL 16. ADD SYMBOLS AND CORRECT WHERE IT | | | STATES 8-16 OR SHOW THAT LEVEL 8-15 SUITE 4.2B ARE ADA | | | SUITES. | | | | | | 4) NOT RESOLVED. PROVIDE A ROOM MATRIX THAT SHOWS WHICH | | | SPECIFIC HOTEL ROOMS WILL MEET THE ACCESSIBILITY | | | REQUIREMENTS FOR MOBILITY AND COMMUNICATION FEATURES. | | | SEE FBC ACCESSIBILITY SECTIONS 224 AND 806. NOT MORE | | | THAN 10 PERCENT OF GUEST ROOMS REQUIRED TO PROVIDE | | | MOBILITY FEATURES COMPLYING WITH 806.2 SHALL BE USED TO | | | SATISFY THE MINIMUM NUMBER OF GUEST ROOMS REQUIRED TO | | | PROVIDE COMMUNICATION FEATURES COMPLYING WITH 806.3. | | | SPECIFY THE LOCATION AND ACCESSIBILITY TYPE OT HOTEL | | | ROOMS WITH THE APPROPRIATE SYMBOLS ON THE PLANS. 224.5 | | | FBC[A]DISPERSION. GUEST ROOMS REQUIRED TO PROVIDE | | | MOBILITY FEATURES COMPLYING WITH 806.2 AND GUEST ROOMS | | | REQUIRED TO PROVIDE COMMUNICATION FEATURES COMPLYING | | | WITH 806.3 SHALL BE DISPERSED AMONG THE VARIOUS CLASSES | | | OF GUEST ROOMS, AND SHALL PROVIDE CHOICES OF TYPES OF | | | GUEST ROOMS, NUMBER OF BEDS, AND OTHER AMENITIES | | | COMPARABLE TO THE CHOICES PROVIDED TO OTHER | | | GUESTS.WHERE THE MINIMUM NUMBER OF GUEST ROOMS REQUIRED | | | TO COMPLY WITH 806 IS NOT SUFFICIENT TO ALLOW FOR | | | COMPLETE DISPERSION, GUEST ROOMS SHALL BE DISPERSED IN | | | THE FOLLOWING PRIORITY: GUEST ROOM TYPE, NUMBER OF | | | BEDS, AND AMENITIES. AT LEAST ONE GUEST ROOM REQUIRED | | | TO PROVIDE MOBILITY FEATURES COMPLYING WITH 806.2 SHALL | | | ALSO PROVIDE COMMUNICATION FEATURES COMPLYING WITH | | | 806.3. NOT MORE THAN 10 PERCENT OF GUEST ROOMS REQUIRED | | | TO PROVIDE MOBILITY FEATURES COMPLYING WITH 806.2 SHALL | | | BE USED TO SATISFY THE MINIMUM NUMBER OF GUEST ROOMS | | | REQUIRED TO PROVIDE COMMUNICATION FEATURES COMPLYING | | | WITH 806.3. | | | -ONLY 10 PERCENT OF REQUIRED ROOMS CAN SHARE | | | COMMUNICATION AND MOBILITY. PLEASE SHOW COMMUNICATION | | | ROOMS ONLY SHARE IN ONE SUITE. | | | -PLEASE VERIFY THAT ROOMS ARE EVENLY DISTRIBUTED FOR | | | ROOM TYPES AND PRICE RANGE. | | | | | | 5) NOT RESOLVED. PROVIDE A ROOM MATRIX TO SHOW WHICH | | | SPECIFIC HOTEL ROOMS WILL MEET THIS REQUIREMENT. 806.4 | | | FBC[A]HOTEL,MOTEL AND CONDOMINIUM SPECIAL ACCESSIBILITY | | | FEATURES. THIS SECTION DOES NOT RELIEVE THE OWNER OF | | | THE RESPONSIBILITY OF PROVIDING ACCESSIBLE ROOMS IN | | | CONFORMANCE WITH SECTION 224 AND 806 OF THIS CODE. IN | | | ALL BUILDINGS, STRUCTURES AND FACILITIES LICENSED AS A | | | HOTEL, MOTEL OR RESORT CONDOMINIUM PURSUANT TO CHAPTER | | | 509, F.S., A NUMBER OF ROOMS EQUALING AT LEAST 5 | | | PERCENT OF THE GUEST ROOMS MINUS THE TOTAL NUMBER OF | | | REQUIRED (ACCESSIBLE) ROOMS REQUIRED BY TABLE 224.2 | | | SHALL PROVIDE THE FOLLOWING ADDITIONAL SPECIAL | | | ACCESSIBILITY FEATURES: | | | (I) GRAB RAILS IN BATHROOMS AND TOILET ROOMS WHICH | | | COMPLY WITH SECTION 604.5. | | | (II) ALL BEDS IN DESIGNED ACCESSIBLE GUEST ROOMS SHALL | | | BE OPEN-FRAME TYPE THAT ALLOWS THE PASSAGE OF LIFT | | | DEVICES. | | | (III)WATER CLOSETS THAT COMPLY WITH SECTION 604.4. | | | -SHOW WHICH ROOMS COMPLY WITH 806.4 | | | | | | 6) NOT RESOLVED. THERE ARE HOTEL ROOMS THAT APPEAR TO | | | BE EQUIPPED WITH COOKING APPLIANCES. YOUR RESPONSE | | | STATES THAT NOTE 26 ON SHEET A0.201 ADDRESSES THIS | | | COMMENT. IT STATES THAT SERVICE APARTMENTS DESIGNED FOR | | | STAYS OF MORE THAN 30 DAYS ARE REQUIRED TO COMPLY WITH | | | FAIRHOUSING RATHER THAN ADA ACCESSIBILITY REQUIREMENTS. | | | THIS IS NOT ACCURATE. BECAUSE THESE ARE HOTEL ROOMS | | | THEY ARE NOT APARTMENTS AND ARE REQUIRED TO COMPLY WITH | | | THE FLORIDA ACCESSIBILITY CODE AS WELL AS FAIRHOUSING | | | GUIDELINES IF THEY ARE USED FOR STAYS OF MORE THAN 30 | | | DAYS. YOU WILL NEED TO IDENTIFY THESE ROOMS AND SHOW | | | THAT THEY MEET THE MOST RESTRICTIVE REQUIREMENTS OF THE | | | TWO. 224.1 ADVISORY FBC[A]ARE THERE NON-TRANSIENT ROOMS | | | (MORE THAN 30 DAY STAY)? | | | IF SO, THOSE ROOMS MAY FALL UNDER THE FAIRHOUSING | | | GUIDELINES IN ADDITION TO ACCESSIBILITY FBC 2017 6 TH | | | EDITION. | | | | | | FAIRHOUSING REVIEW: | | | 7) RESOLVED. 1986 ANSI [A117.1] IF A DESIGNER OR | | | BUILDER CHOOSES TO FOLLOW AN ACCESSIBILITY STANDARD | | | OTHER THAN THE 1986 ANSI A117.1 STANDARD, OR A MORE | | | RECENT VERSION OF THE ANSI A117.1, SUCH AS THE 1992 | | | CABO/ANSI, THAT CARE BE TAKEN TO ENSURE THE STANDARD | | | USED IS AT LEAST EQUIVALENT TO OR STRICTER THAN THE | | | 1986 ANSI A117.1 STANDARD. | | | -WHAT STANDARD IS BEING APPLIED FOR COMPLIANCE WITH | | | FAIR HOUSING? YOU CAN USE GUIDELINES THAT FALL WITHIN | | | THE SAFE HARBOR FOR COMPLIANCE? | | | | | | A) PARTIALLY RESOLVED. PAGE 03.097(A1.519) THE MASTER | | | BATH TOILET IN RESIDENTIAL UNIT S8 DOES NOT APPEAR TO | | | COMPLY WITH A TYPE B BATHROOM. ON PAGE 03.102(A1.524) | | | RESIDENTIAL UNIT B1 HAS ONE BATH ROOM MARKED AS TYPE A | | | AND THE OTHER AS TYPE B. THE UNIT CAN ONLY BE ONE TYPE. | | | ON PAGE 03.104(A1.526) SHOW THE REQUIRED CLEAR FLOOR | | | SPACE AT THE TOILET IN UNIT B3.1. IT WOULD BE HELPFUL | | | TO ADD A MATRIX OF ROOMS ON SHEET A1.500 WHICH BATHROOM | | | SPEC IS BEING USED AND APPLY THE FOLLOWING FOR SPEC A | | | AND B | | | | | | SPECIFICATION A: | | | IF SPECIFICATION A IS USED IT APPLIES TO ALL BATHROOMS, | | | AND ALL FIXTURES IN THOSE BATHROOMS MUST BE USABLE. | | | SPECIFICATION B: | | | IF SPECIFICATION B IS USED, IT APPLIES TO ONE BATHROOM, | | | AND ONLY ONE OF EACH TYPE OF FIXTURE MUST BE USABLE; | | | ADDITIONAL BATHROOMS IN THE UNIT ARE EXEMPT ONLY FROM | | | MANEUVERING AND CLEAR FLOOR SPACE REQUIREMENTS AT | | | FIXTURES. | | | | | | B) RESOLVED. PLEASE ADD TO FAIRHOUSING NOTES ON SHEET | | | A1.528. THIS SAYS ALL BATHROOMS TO BE SPEC A. PLEASE | | | ADJUST NOTE SINCE BOTH SPEC ARE BEING USED. | | | | | | C) RESOLVED. ADD NOTE FOR USABLE HARDWARE. | | | REQUIREMENT 3 - USABLE DOORS. THE DOORS IN COMMON | | | SPACES AND THE SIDE ENTERING INTO DWELLING UNITS NEED | | | TO HAVE USABLE HARDWARE THAT CAN BE USED WITHOUT TIGHT | | | GRASPING OR TWISTING. | | | -TYPICALLY THE HARDWARE WOULD BE A LEVER TYPE. THIS | | | TYPE OF HARDWARE WOULD NOT BE REQUIRED ONCE INSIDE THE | | | UNIT. YOU MAY WANT TO CLARIFY HARDWARE ON THE DOOR | | | SCHEDULE. | | | | | | D) NOT RESOLVED. DOOR SCHEDULES ON PAGES 03.242(A6.104) | | | AND 03.243(A6.105) NEED TO BE CLEANED UP AND MADE | | | LEGIBLE. DOOR SCHEDULE ON SHEET A6.104 IS DISTORTED AND | | | INFORMATION IS NOT LEGIBLE. PLEASE ADJUST AND POPULATE | | | AS NEEDED. | | | | | | E) RESOLVED. SHOW ACCESSIBLE ROUTES FOR EACH UNIT TYPE. | | | | | | F) RESOLVED. ADD DETAIL OF HOW ACCESS IS GAINED AT | | | RESIDENTIAL BALCONY. IS THERE ELEVATION CHANGE TO MEET | | | FAIRHOUSING MAX OF 4 INCHES TOP OF THRESHOLD? | | | | | | LIFE SAFETY: | | | | | | 8) PARTIALLY RESOLVED. SPECIFY THE REQUIRED FIRE | | | RATINGS FOR THE EXIT STAIR DOORS AND THE FIRE SERVICE | | | ACCESS LOBBY DOORS IN THE DOOR SCHEDULES. 3006.2 | | | FBC[B]SHEET A1.107 SHOWS NO ELEVATOR LOBBY ON LEVEL 7 | | | AT ELEVATORS 8, 9 AND 10. IF REQUIRED PLEASE SHOW THE | | | DOORS. | | | 1024.4 FBC[B]TERMINATION. EXIT PASSAGEWAYS ON THE LEVEL | | | OF EXIT DISCHARGE SHALL TERMINATE AT AN EXIT DISCHARGE. | | | EXIT PASSAGEWAYS | | | ON OTHER LEVELS SHALL TERMINATE AT AN EXIT. | | | EXIT DISCHARGE. THAT PORTION OF A MEANS OF EGRESS | | | SYSTEM BETWEEN THE TERMINATION OF AN EXIT AND A PUBLIC | | | WAY. | | | | | | 9) RESOLVED. 3005.5 FBC[B] SHUNT TRIP. WHERE ELEVATOR | | | HOISTWAYS, ELEVATOR MACHINE ROOMS, CONTROL ROOMS AND | | | CONTROL SPACES CONTAINING ELEVATOR CONTROL EQUIPMENT | | | ARE PROTECTED WITH AUTOMATIC SPRINKLERS, A MEANS | | | INSTALLED IN ACCORDANCE WITH SECTION 21.4 OF NFPA 72 | | | SHALL BE PROVIDED TO DISCONNECT AUTOMATICALLY THE MAIN | | | LINE POWER SUPPLY TO THE AFFECTED ELEVATOR PRIOR TO THE | | | APPLICATION OF WATER. THIS MEANS SHALL NOT BE | | | SELF-RESETTING. THE ACTIVATION OF AUTOMATIC SPRINKLERS | | | OUTSIDE THE HOISTWAY, MACHINE ROOM, MACHINERY SPACE, | | | CONTROL ROOM OR CONTROL SPACE SHALL NOT DISCONNECT THE | | | MAIN LINE POWER SUPPLY. | | | | | | 10) RESOLVED. 3006.2 FBC[B] HOISTWAY OPENING PROTECTION | | | REQUIRED. ELEVATOR HOISTWAY DOOR OPENINGS SHALL BE | | | PROTECTED IN ACCORDANCE WITH SECTION 3006.3 WHERE AN | | | ELEVATOR HOISTWAY CONNECTS MORE THAN THREE STORIES, IS | | | REQUIRED TO BE ENCLOSED WITHIN A SHAFT ENCLOSURE IN | | | ACCORDANCE WITH SECTION 712.1.1 AND ANY OF THE | | | FOLLOWING CONDITIONS APPLY: | | | 5. THE BUILDING IS A HIGH RISE AND THE ELEVATOR | | | HOISTWAY IS MORE THAN 75 FEET (22 860 MM) IN HEIGHT. | | | THE HEIGHT OF THE HOISTWAY SHALL BE MEASURED FROM THE | | | LOWEST FLOOR TO THE HIGHEST FLOOR OF THE FLOORS SERVED | | | BY THE HOISTWAY. | | | -IS THE PRE FUNCTION AREA OPEN AIR? IT IS HARD TO TELL | | | BUT IT APPREARS TO BE COVERED BY RESIDENTIAL ABOVE. | | | -FREIGHT ELEVATOR DOES NOT HAVE ELEVATOR LOBBY ON THE 8 | | | TH FLOOR. PLEASE REVIEW 3006.2 FOR OPENING PROTECTION | | | ON SHAFT MORE THAN 75 FEET. | | | | | | 11) NOT RESOLVED. YOUR RESPONSE STATES THAT A LIFE | | | SAFETY PLAN FOR THE PARK WAS ADDED ON SHEET ALS1.109. | | | THERE IS NO SUCH SHEET IN THE PLANS OR THE PLAN INDEX. | | | PLEASE CLARIFY. 107.5.3 FBC[AMENDED]ADD SCALE TO LIFE | | | SAFETY PLANS. I THINK IT IS 1/16 SCALE. | | | ALSO, IS THERE A LIFE SAFETY SHEET FOR THE PARK ABOVE | | | THE TENNIS PAVILION? PLEASE PROVIDE OR LET ME KNOW | | | WHICH SHEET I CAN FIND IT. | | | | | | 12) NOT RESOLVED. THERE ARE EXIT DOORS AT GRADE LEVEL | | | THAT DO NOT HAVE EGRESS LOAD TAGS. 1004 FBC[B]PLEASE | | | PROVIDE TOTAL OCCUPANT LOAD FOR EACH EGRESS DOOR AT | | | GRADE WHERE THE DOOR PROVIDES EGRESS FROM MULTIPLE | | | AREAS. FOR EXAMPLE EGRESS DOORS IN HOTEL LOBBY PICKUP | | | THE STAIRS AND OTHER AREAS FROM FIRST LEVEL USES. I AM | | | LOOKING FOR DATA TAG LIKE WAS USED AT STAIRWAY DOORS. | | | | | | 13) RESOLVED. 1025.1 FBC[B]GENERAL. APPROVED LUMINOUS | | | EGRESS PATH MARKINGS DELINEATING THE EXIT PATH SHALL BE | | | PROVIDED IN HIGH-RISE BUILDINGS OF GROUP A, B, E, I, M, | | | AND R-1 OCCUPANCIES IN ACCORDANCE WITH SECTIONS 1025.1 | | | THROUGH 1025.5. | | | -ST4 AND ST3 FROM R-1 LEVELS TO MEET 1025.1 FOR | | | LUMINOUS MARKINGS. | | | | | | 14) RESOLVED. 1013.2 FBC[B] FLOOR-LEVEL EXIT SIGNS IN | | | GROUP R-1. WHERE EXIT SIGNS ARE REQUIRED IN GROUP R-1 | | | OCCUPANCIES BY SECTION 1013.1, ADDITIONAL LOW-LEVEL | | | EXIT SIGNS SHALL BE PROVIDED IN ALL AREAS SERVING GUEST | | | ROOMS IN GROUP R-1 OCCUPANCIES AND SHALL COMPLY WITH | | | SECTION 1013.5. | | | -ADD LOW LEVEL EXIT SIGNS AS REQUIRED, OR STATE WHICH | | | PAGE THIS INFORMATION CAN BE FOUND. | | | | | | 15) NOT RESOLVED. THE EXIT ACCESS TRAVEL DISTANCE FOR | | | SPRINKLERED TYPE M OCCUPANCIES IS 250' IN 2014 FBC | | | TABLE 1016.2 AND THE TABLE ON SHEET ALS1.101 HAS 400'. | | | THE EGRESS TRAVEL DISTANCE FOR SPRINKLERED RESIDENTIAL | | | OCCUPANCIES IS 250' IN FBC TABLE 1016.2 AND THE TABLE | | | ON THE LIFE SAFETY PLANS SHEETS WITH RESIDENTIAL UNITS | | | HAS 325'. YOU ARE REQUIRED TO MEET THE MOST RESTRICTIVE | | | REQUIREMENT BETWEEN THE F.F.P.C. AND THE FBC BUILDING. | | | SOME DESIGNERS LIST THE REQUIREMENTS OF BOTH CODES IN | | | THEIR TABLES WITH A NOTE TO USE THE MOST RESTRICTIVE | | | REQUIREMENT. PLEASE REVIEW ALL LIFE SAFETY PLANS FOR | | | REQUESTED DATA. THE RESIDENTS LOUNGE AREA (0161) HAS AN | | | OCCUPANT LOAD OF MORE THAN 49 AND REQUIRES TWO EXITS | | | PER TABLE 1015.1. BE SURE TO SHOW EXIT ROUTES FOR ALL | | | AREAS. 107.3.5 FBC[AMENDED] MINIMUM REVIEW CRITERIA. | | | THIS IS FOR ALL LIFE SAFETY SHEETS | | | A. ADD MAX COMMON PATH AND MAX TRAVEL DISTANCE FOR R-1 | | | AND R-2 TO ALS1.100 COMPLIANCE SUMMARY FOR FLORIDA | | | BUILDING CODE IN ADDITION TO THE PROVIDED NFPA. THE | | | MORE RESTRICTIVE CODE WILL APPLY. | | | B. SHOW MAXIMUM PATH OF TRAVEL ON ALL L.S. PLANS. | | | CURRENTLY, L.S. SHEETS SHOW PATH OF TRAVEL DISTANCE OR | | | TOTAL DISTANCE. PLANS SHOULD SHOW BOTH COMMON PATH OF | | | TRAVEL AND EXIT ACCESS TRAVEL DISTANCE. THIS SHOULD BE | | | DONE FOR WORST CASE IN EACH GENERAL AREA. | | | | | | 16) NOT COMPLETELY RESOLVED. THERE ARE SEVERAL RAMPS | | | SHOWN ON THE PLANS. PLEASE IDENTIFY EACH WITH AN ID TAG | | | AND PROVIDE DETAILS FOR EACH OF THEM TO SHOW THAT THEY | | | MEET THE ACCESSIBILITY REQUIREMENTS FOR RAMPS. FBC | | | ACCESSIBILITY 405. 1003.5 FBC[B] ELEVATION CHANGE. DOES | | | EXIT FROM RESIDENT LOBBY TO STAIR 2 HAVE STEPS? PLEASE | | | REVIEW | | | -HOW DO STEPS WORK AT EGRESS FROM RESIDENT LOUNGE TO | | | STAIR ST2? PLEASE REVIEW 1003.5 FOR CHANGE IN ELEVATION | | | IN PATH OF EGRESS. | | | | | | 17) RESOLVED. 1012.9 FBC[B] INTERMEDIATE HANDRAILS. | | | STAIRWAYS SHALL HAVE INTERMEDIATE HANDRAILS LOCATED IN | | | SUCH A MANNER THAT ALL PORTIONS OF THE STAIRWAY MINIMUM | | | WIDTH OR REQUIRED CAPACITY ARE WITHIN 30 INCHES (762 | | | MM) OF A HANDRAIL. ON MONUMENTAL STAIRS, HANDRAILS | | | SHALL BE LOCATED ALONG THE MOST DIRECT PATH OF EGRESS | | | TRAVEL. | | | -CHECK COMPLIANCE WITH 1012.9 AT BALLROOM STEPS. | | | | | | 18) RESOLVED. 713.13.4 CHUTE DISCHARGE ROOM. WASTE OR | | | LINEN CHUTES SHALL DISCHARGE INTO AN ENCLOSED ROOM | | | SEPARATED BY FIRE BARRIERS WITH A FIRE RESISTANCE | | | RATING NOT LESS THAN THE REQUIRED FIRE RATING OF THE | | | SHAFT ENCLOSURE AND CONSTRUCTED IN ACCORDANCE WITH | | | SECTION 707 OR HORIZONTAL ASSEMBLIES CONSTRUCTED IN | | | ACCORDANCE WITH SECTION 711, OR BOTH. OPENINGS INTO THE | | | DISCHARGE ROOM FROM THE REMAINDER OF THE BUILDING SHALL | | | BE PROTECTED BY OPENING PROTECTIVES HAVING A FIRE | | | PROTECTION RATING EQUAL TO THE PROTECTION REQUIRED FOR | | | THE SHAFT ENCLOSURE. DOORS SHALL BE SELF- OR | | | AUTOMATICCLOSING UPON THE DETECTION OF SMOKE IN | | | ACCORDANCE WITH SECTION 716.5.9.3. WASTE CHUTES SHALL | | | NOT TERMINATE IN AN INCINERATOR ROOM. WASTE AND LINEN | | | ROOMS THAT ARE NOT PROVIDED WITH CHUTES NEED ONLY | | | COMPLY WITH TABLE 509. | | | -DOUBLE DOORS TO TRASH ROOM AT BASE LEVEL SHOW 90 | | | MINUTE RATING, BUT 713.13.4 REQUIRES SAME LEVEL OF | | | PROTECTION FOR OPENINGS IN DISCHARGE ROOM EQUAL TO THE | | | SHAFT ENCLOSURE (2 HOURS). | | | | | | 19) RESOLVED. 420.3 FBC[B]HORIZONTAL SEPARATION AND | | | FBC[B] 602 FLOOR ASSEMBLIES SEPARATING DWELLING UNITS | | | IN THE SAME BUILDINGS, FLOOR ASSEMBLIES SEPARATING | | | SLEEPING UNITS IN THE SAME BUILDING AND FLOOR | | | ASSEMBLIES SEPARATING DWELLING OR SLEEPING UNITS FROM | | | OTHER OCCUPANCIES CONTIGUOUS TO THEM IN THE SAME | | | BUILDING SHALL BE CONSTRUCTED AS HORIZONTAL ASSEMBLIES | | | IN ACCORDANCE WITH SECTION 711. | | | -602 FBC[B]SHEET A7.310 HAS CEILING ASSEMBLIES. PLEASE | | | SHOW THE RATED ASSEMBLY FOR CEILINGS SEPARATING | | | DWELLING AND SLEEPING UNITS AS STATED IN LIFE SAFETY | | | COMPLIANCE SUMMARY ALS1.100. | | | | | | 20) NOT RESOLVED. THE TAG ON THE WASTE CHUTE ACCESS | | | DOORS FROM THE CORRIDORS STILL HAVE NR INSTEAD OF 45 | | | MIN. ON THE LIFE SAFETY PLANS.713.13.3 FBC[B]CHUTE | | | ACCESS ROOMS. ACCESS OPENINGS FOR WASTE OR LINEN CHUTES | | | SHALL BE LOCATED IN ROOMS OR COMPARTMENTS ENCLOSED BY | | | NOT LESS THAN 1-HOUR FIRE BARRIERS CONSTRUCTED IN | | | ACCORDANCE WITH SECTION 707 OR HORIZONTAL ASSEMBLIES | | | CONSTRUCTED IN ACCORDANCE WITH SECTION 711, OR BOTH. | | | OPENINGS INTO THE ACCESS ROOMS SHALL BE PROTECTED BY | | | OPENING PROTECTIVES HAVING A FIRE PROTECTION RATING OF | | | NOT LESS THAN 3/4 HOUR. DOORS SHALL BE SELF- OR | | | AUTOMATIC-CLOSING UPON THE DETECTION OF SMOKE IN | | | ACCORDANCE WITH SECTION 716.5.9.3. | | | -LIFE SAFETY SHEETS SHOW CHUTE ACCESS DOORS AS NOT | | | RATED (NR). THESE ACCESS DOORS ARE REQUIRED TO HAVE A | | | 3/4 HOUR RATING PER 713.13.3. | | | - ADD DOOR TAG TO THE DOORS LEADING TO THE TRASH CHUTE | | | OR TELL ME WHAT SHEETS THER ARE ON. I WAS LOOKING ON | | | QUADRANT SHEETS WHERE THE OTHER TAGS FOR COMMON SPACE | | | DOORS WERE LOCATED. | | | | | | DEFERRED SUBMITTALS | | | 21) NOT COMPLETELY RESOLVED. PLEASE LABEL GENERAL NOTE | | | 16 ON SHEET A0.001 AS "DEFERRED SUBMITTALS" AND NOTE | | | THAT THE ITEMS BEING DEFERRED ARE REQUIRED TO BE | | | REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF | | | RECORDED AND SUBMITTED AND APPROVED BY THE CITY OF WEST | | | PALM BEACH BUILDING DEPARTMENT PRIOR TO BEING | | | INSTALLED. ANY ITEMS NOT LISTED WILL HAVE TO BE | | | APPROVED BEFORE THE PERMIT CAN BE ISSUED. 107.3.4.1 | | | FBC[AMENDED] PLEASE PROVIDE A LIST OF DEFERRED | | | SUBMITTALS ON PLANS SO THAT I WILL NOT ASK FOR ITEMS | | | THAT WILL BE SUPPLIED AT A LATER DATE, OR INDICATE | | | WHICH PAGE A LIST CAN BE FOUND. | | | THESE ARE THE ONES I BELIEVE WE WILL NEED, BUT THIS IS | | | NOT A COMPLETE LIST. | | | A) COMPONENT & CLADDING PRODUCT APPROVALS (COMPLY WITH | | | PRESSURES SHOWN ON SHEET S0.0.5) | | | B) CURTAIN WALL SUBMITTAL (COMPLY WITH PRESSURES SHOWN | | | ON SHEET S0.0.5) | | | C) FENESTRATION SHOP DRAWINGS TO INCLUDE ALL WINDOWS, | | | DOORS, TRANSOMS, SLIDERS, LOUVERS AND MULL BARS. | | | D) FLOORING UNDERLAYMENT WITH THREE REPORTS: | | | 1. 1207.2 FBC[B] AIR-BORNE SOUND. WALLS, PARTITIONS AND | | | FLOOR/CEILING ASSEMBLIES SEPARATING DWELLING UNITS AND | | | SLEEPING UNITS FROM EACH OTHER OR FROM PUBLIC OR | | | SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS OF | | | NOT LESS THAN 50, OR NOT LESS THAN 45 IF FIELD TESTED, | | | FOR AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM | | | E90. | | | 2. 1207.3 FBC[B] STRUCTURE-BORNE SOUND. FLOOR/CEILING | | | ASSEMBLIES BETWEEN DWELLING UNITS AND SLEEPING UNITS OR | | | BETWEEN A DWELLING UNIT OR SLEEPING UNIT AND A PUBLIC | | | OR SERVICE AREA WITHIN THE STRUCTURE SHALL HAVE AN | | | IMPACT INSULATION CLASS RATING OF NOT LESS THAN 50, OR | | | NOT LESS THAN 45 IF FIELD TESTED, WHEN TESTED IN | | | ACCORDANCE WITH ASTM E492. | | | 3. 603.1 FBC[B] ALLOWABLE MATERIALS IN NON COMBUSTIBLE | | | BUILDINGS, SEE ITEM 2, EXCEPTION 2, ACOUSTICAL | | | INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID | | | DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED | | | TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200. SEE | | | 803.1.1, PROVIDE TEST DATA IN ACCORDANCE WITH ASTM E 84 | | | OR UL 723. | | | E) RAILINGS AND GUARDRAILS. INCLUDES BALCONIES, STAIRS | | | AND COMMON SPACES. | | | F) PARKING GARAGE VEHICLE BARRIER PER 406.4.2 FBC[B] | | | G) FIRE SPRAY | | | H) 806.1 FBC[B] GENERAL REQUIREMENTS. CURTAINS, | | | DRAPERIES, HANGINGS AND OTHER DECORATIVE MATERIALS | | | SUSPENDED FROM WALLS OR CEILINGS SHALL MEET THE FLAME | | | PROPAGATION PERFORMANCE CRITERIA OF NFPA 701 IN | | | ACCORDANCE WITH SECTION 806.2 OR BE NONCOMBUSTIBLE. | | | I) LIGHTWIEGHT CONCRETE. | | | J) WINDOW WASHING EQUIPMENT ATTACHMENTS/LOCATIONS AT | | | ROOF. | | | K) E.F.I.S. IF APPLICABLE | | | L) LIGHTING CONTROLS PER ENERGY CODE C405.2 LIGHTING | | | CONTROLS (MANDATORY) C405.5 EXTERIOR LIGHTING | | | (MANDATORY) | | | M) FINAL GYM EQUIPMENT LAYOUT WITH ACCESSIBILTY | | | REQUIREMENTS PROVIDED. | | | PRODUCT APPROVALS FOR ROOFING ARE PROVIDED, BUT NO | | | SELECTIONS ARE MADE AND IT IS NOT CLEAR WHICH AREA OF | | | ROOF RECEIVE. | | | ROOFING CAN BE ADDED TO DEFERRED SUBMITTAL LIST. | | | | | | 22) NOT RESOLVED. THE PRODUCT APPROVALS THAT WERE | | | SUBMITTED ARE REQUIRED TO BE REVIEWED AND APPROVED IN | | | WRITING BY THE DESIGNER OF RECORD. IF YOU ARE NOT SURE | | | WHICH PRODUCTS WILL BE USED, YOU CAN SPECIFY ON THE | | | PLANS THAT THEY WILL BE SUBMITTED LATER. ALSO, PROVIDE | | | PRODUCT APPROVAL FOR ROOF INSULATION AND ATTACHMENT. | | | OTHER PRODUCT APPROVALS WERE SUBMITTED FOR DOORS, BUT | | | THEY WERE NOT STAMPED AS REVIEWED. AS PART OF | | | FENESTRATION PACKAGE PROVIDE ALL PRODUCT APPROVALS WITH | | | INDICATION THAT THEY WERE REVIEWED BY THE DESIGNER OF | | | RECORD. | | | | | | 23) RESOLVED. ENERGY CODE REVIEW: | | | A) THIS BUILDING WAS BROUGHT IN UNDER 2014 CODE CYCLE. | | | PLEASE REVISE TO THAT CODE DATE, OR PROVIDE LETTER OF | | | COMPLIANCE THAT CURRENT CODES ARE EQUIVALENT. | | | B) C407.2.1 ROOF/CEILING THERMAL ENVELOPE. SECTIONS FOR | | | ROOFING AND DOORS SHOW NO DATA. PLEASE INCLUDE THOSE | | | VALUES IN THE ENERGY CALCULATIONS. | | | C) IN SECTION FOR WALLS THE ASSEMBLY STATES 6 INCH | | | INSULATION. WHERE IS THAT ASSEMBLY BEING USED ON THE | | | BUILDING? | | | | | | ACCESSIBILITY REVIEW: | | | | | | 24) PROVIDE DETAILS TO SHOW THAT THE BUILT IN LOCKER | | | ROOM BENCHES ARE ADA COMPLIANT. 803.1 FBC[A] GENERAL. | | | DRESSING, FITTING, AND LOCKER ROOMS SHALL COMPLY WITH | | | 803. | | | 803.2 FBC[A] TURNING SPACE. TURNING SPACE COMPLYING | | | WITH 304 SHALL BE PROVIDED WITHIN THE ROOM. | | | 803.3 FBC[A] DOOR SWING. DOORS SHALL NOT SWING INTO THE | | | ROOM UNLESS A CLEAR FLOOR OR GROUND SPACE COMPLYING | | | WITH 305.3 IS PROVIDED BEYOND THE ARC OF THE DOOR | | | SWING. | | | 803.4 FBC[A] BENCHES. A BENCH COMPLYING WITH 903 SHALL | | | BE PROVIDED WITHIN THE ROOM. | | | 903.4 FBC[A] BACK SUPPORT. THE BENCH SHALL PROVIDE FOR | | | BACK SUPPORT OR SHALL BE AFFIXED TO A WALL. BACK | | | SUPPORT SHALL BE 42 INCHES LONG MINIMUM AND SHALL | | | EXTEND FROM A POINT 2 INCHES MAXIMUM ABOVE THE SEAT | | | SURFACE TO A POINT 18 INCHES MINIMUM ABOVE THE SEAT | | | SURFACE. BACK SUPPORT SHALL BE 21/2 INCHES MAXIMUM FROM | | | THE REAR EDGE OF THE SEAT MEASURED HORIZONTALLY. | | | | | | 25) NOT COMPLETELY RESOLVED. THE ADA INFORMATION, CLEAR | | | FLOOR SPACE WAS NOT PROVIDED FOR THE EXERCISE EQUIPMENT | | | IN THE MENS GYM. 236.1 FBC[A]GENERAL. AT LEAST ONE OF | | | EACH TYPE OF EXERCISE MACHINE AND EQUIPMENT SHALL | | | COMPLY WITH 1004. | | | 1004.1 FBC[A]CLEAR FLOOR SPACE. EXERCISE MACHINES AND | | | EQUIPMENT SHALL HAVE A CLEAR FLOOR SPACE COMPLYING WITH | | | 305 POSITIONED FOR TRANSFER OR FOR USE BY AN INDIVIDUAL | | | SEATED IN A WHEELCHAIR. CLEAR FLOOR OR GROUND SPACES | | | REQUIRED AT EXERCISE MACHINES AND EQUIPMENT SHALL BE | | | PERMITTED TO OVERLAP. | | | | | | ADVISORY 1004.1 FBC[A]CLEAR FLOOR SPACE. ONE CLEAR | | | FLOOR OR GROUND SPACE IS PERMITTED TO BE SHARED BETWEEN | | | TWO PIECES OF EXERCISE EQUIPMENT.TO OPTIMIZE SPACE USE, | | | DESIGNERS SHOULD CAREFULLY CONSIDER LAYOUT OPTIONS SUCH | | | AS CONNECTING ENDS OF THE ROW AND CENTER AISLE SPACES. | | | THE POSITION OF THE CLEAR FLOOR SPACE MAY VARY GREATLY | | | DEPENDING ON THE USE OF THE EQUIPMENT OR MACHINE. FOR | | | EXAMPLE, TO PROVIDE ACCESS TO A SHOULDER PRESS MACHINE, | | | CLEAR FLOOR SPACE NEXT TO THE SEAT WOULD BE APPROPRIATE | | | TO ALLOW FOR TRANSFER. CLEAR FLOOR SPACE FOR A BENCH | | | PRESS MACHINE DESIGNED FOR USE BY AN INDIVIDUAL SEATED | | | IN A WHEELCHAIR, HOWEVER, WILL MOST LIKELY BE CENTERED | | | ON THE OPERATING MECHANISMS. | | | | | | 26) NOT RESOLVED. THE NOTES ON THE POOLS STATE TO REFER | | | TO SHEETS SP.001, SP.002 AND SP.003. I WAS NOT ABLE TO | | | FIND THESE SHEETS. SHOW HOW THE POOLS WILL COMPLY WITH | | | FBC ACCESSIBILITY SECTION 242.2 SWIMMING POOLS. AT | | | LEAST TWO ACCESSIBLE MEANS OF ENTRY SHALL BE PROVIDED | | | FOR SWIMMING POOLS. (SEE EXCEPTIONS) ACCESSIBLE MEANS | | | OF ENTRY SHALL BE SWIMMING POOL LIFTS COMPLYING WITH | | | 1009.2; SLOPED ENTRIES COMPLYING WITH 1009.3; TRANSFER | | | WALLS COMPLYING WITH 1009.4; TRANSFER SYSTEMS COMPLYING | | | WITH 1009.5; AND POOL STAIRS COMPLYING WITH 1009.6. AT | | | LEAST ONE ACCESSIBLE MEANS OF ENTRY PROVIDED SHALL | | | COMPLY WITH 1009.2 OR 1009.3. ADVISORY 242.2 SWIMMING | | | POOLS. WHERE MORE THAN ONE MEANS OF ACCESS IS PROVIDED | | | INTO THE WATER, IT IS RECOMMENDED THAT THE MEANS BE | | | DIFFERENT. PROVIDING DIFFERENT MEANS OF ACCESS WILL | | | BETTER SERVE THE VARYING NEEDS OF PEOPLE WITH | | | DISABILITIES IN GETTING INTO AND OUT OF A SWIMMING | | | POOL. IT IS ALSO RECOMMENDED THAT WHERE TWO OR MORE | | | MEANS OF ACCESS ARE PROVIDED, THEY NOT BE PROVIDED IN | | | THE SAME LOCATION IN THE POOL. DIFFERENT LOCATIONS WILL | | | PROVIDE INCREASED OPTIONS FOR ENTRY AND EXIT, | | | ESPECIALLY IN LARGER POOLS. ADVISORY 242.2 SWIMMING | | | POOLS EXCEPTION 1. POOL WALLS AT DIVING AREAS AND AREAS | | | ALONG POOL WALLS WHERE THERE IS NO POOL ENTRY BECAUSE | | | OF LANDSCAPING OR ADJACENT STRUCTURES ARE TO BE COUNTED | | | WHEN DETERMINING THE NUMBER OF ACCESSIBLE MEANS OF | | | ENTRY REQUIRED. | | | COMMUNITY POOLS THAT ARE ASSOCIATED WITH A PRIVATE | | | RESIDENTIAL COMMUNITY THAT DO NOT RECEIVE GOVERNMENTAL | | | FINANCIAL ASSISTANCE OR SPONSORSHIP AND ARE LIMITED TO | | | THE EXCLUSIVE OF RESIDENTS AND THEIR GUESTS ARE NOT | | | COVERED BY THE ADA ACCESSIBILITY REQUIREMENTS, | | | INCLUDING PROVISIONS FOR POOL LIFTS OR SLOPED ENTRIES. | | | IF A SWIMMING POOL LOCATED IN A RESIDENTIAL COMMUNITY | | | IS MADE AVAILABLE TO THE PUBLIC FOR RENTAL OR USE IT IS | | | REQUIRED TO COMPLY WITH TITLE II OF THE ADA. SPECIFY ON | | | THE PLANS THE FORMER OR SHOW COMPLIANCE WITH THE LATTER | | | STATEMENTS. SEE DECLARATORY STATEMENT, DS 2013-011. | | | | | | 1009.1 GENERAL. WHERE PROVIDED, POOL LIFTS, SLOPED | | | ENTRIES, TRANSFER WALLS, TRANSFER SYSTEMS, AND POOL | | | STAIRS SHALL COMPLY WITH 1009. | | | -IF POOL LIFTS ARE PROVIDED PLEASE ADD DETAILS TO THE | | | ADA DETAIL SHEET. | | | ALSO, ADD ANY ADDITIONAL DETAILS IF APPLICABLE TO ADA | | | DETAILS FOR THE POOLS. | | | | | | 27) NOT RESOLVED. PROVIDE DETAILS OF ALL RAMPS TO SHOW | | | COMPLIANCE WITH ACCESSIBILITY REQUIREMENTS. THE MAXIMUM | | | RAMP SLOPE IS 1:12 (8%). FBC ACCESSIBILITY SECTION 405. | | | 405.8 FBC[A]HANDRAILS.RAMP RUNS WITH A RISE GREATER | | | THAN 6 INCHES (150 MM) SHALL HAVE HANDRAILS COMPLYING | | | WITH 505. | | | -SHEET ALS1.107 SHOWS RAMP FROM PRE-FUNCTION UP TO | | | ELEVATORS AND STAIR ST8. WILL THERE BE RAILS PROVIDE | | | THE RAMP AS REQUIRED? ALSO, IS THE WALKWAY FROM RAMP TO | | | STAIR 8 GOING TO HAVE RAIL OR IS IT OPEN FROM ABOVE TO | | | PRE-FUNCTION? | | | | | | CHAPTER 4 - HIGHRISE: | | | | | | 28) RESOLVED. 403.5.3.1 FBC[B]STAIRWAY COMMUNICATION | | | SYSTEM. A TELEPHONE OR OTHER TWO-WAY COMMUNICATIONS | | | SYSTEM CONNECTED TO AN APPROVED CONSTANTLY ATTENDED | | | STATION SHALL BE PROVIDED AT NOT LESS THAN EVERY FIFTH | | | FLOOR IN EACH STAIRWAY WHERE THE DOORS TO THE STAIRWAY | | | ARE LOCKED. | | | -WILL THE DOORS BE LOCKED FROM THE STAIRWAY SIDE? IF SO | | | PLEASE ADD COMMUNICATION SYSTEM AS REQUIRED IN | | | 403.5.3.1 | | | | | | 29) NOT RESOLVED. THERE ARE SEVERAL EXIT STAIRWAYS THAT | | | ARE NOT CONTINUOUS FROM THE UPPER FLOORS TO THE LEVEL | | | OF EXIT DISCHARGE AT THE GROUND FLOOR. THE PLANS SHOW | | | THAT THE STAIRWAYS TRANSFER THROUGH A FIRE RATED | | | "TRANSFER" CORRIDOR (EXIT PASSAGEWAY) TO ANOTHER | | | STAIRWAY IN ORDER TO TRAVEL TO THE EXIT DISCHARGE. | | | THERE ARE OPENINGS INTO THE CORRIDOR (EXIT PASSAGEWAY) | | | TO AN AHU ROOM AND TWO MAINTENANCE/ACCESS ROOMS. PLEASE | | | KEEP IN MIND THAT ONCE AN OCCUPANT ENTERS AN EXIT | | | STAIRWAY THE EXPECTATION IS THAT THE OCCUPANT WILL HAVE | | | THE SAME PROTECTION AS PROVIDED BY THE EXIT STAIRWAY | | | UNTIL THEY REACH THE EXIT DISCHARGE. THE SAME | | | REQUIREMENTS FOR THE STAIRWAY WILL APPLY TO THE | | | TRANSFER CORRIDOR. NO OPENINGS, PENETRATIONS OR SYSTEMS | | | OTHER THAN THOSE REQUIRED AS A PART OF THE EMERGENCY | | | EGRESS SYSTEM AND THOSE THAT SERVICE THE STAIRWAY ARE | | | ALLOWED. THERE IS ALSO A CONCERN THAT A DOUBLE DOOR | | | THAT OPENS DIRECTLY TO THE PARKING GARAGE. PLEASE | | | PROVIDE A NARRATIVE THAT EXPLAINS THE RATIONALE AND | | | INTENTIONS FOR THE EXIT STAIRS THAT HAVE THIS DESIGN. | | | FBC 1009 THE1022.8 FBC[B] DISCHARGE IDENTIFICATION. AN | | | INTERIOR EXIT STAIRWAY AND RAMP SHALL NOT CONTINUE | | | BELOW ITS LEVEL OF EXIT DISCHARGE UNLESS AN APPROVED | | | BARRIER IS PROVIDED AT THE LEVEL OF EXIT DISCHARGE TO | | | PREVENT PERSONS FROM UNINTENTIONALLY CONTINUING INTO | | | LEVELS BELOW. DIRECTIONAL EXIT SIGNS SHALL BE PROVIDED | | | AS SPECIFIED IN SECTION 1011. | | | -IF STAIRWAY 4 AT 2 ND LEVEL TRANSFERS TO STAIRWAY 11 | | | THAN 1022.8 APPLIES. | | | | | | 30) NOT RESOLVED. ADD NOTES TO PAGE 10.001 SHEET FR.001 | | | THAT SPECIFY THAT A MINIMUM OF TWO RISERS WILL BE | | | PROVIDED AND THAT EACH RISER SHALL SUPPLY SPRINKLERS ON | | | ALTERNATE FLOORS. 403.3.1 FBC[B]NUMBER OF SPRINKLER | | | RISERS AND SYSTEM DESIGN. EACH SPRINKLER SYSTEM ZONE IN | | | BUILDINGS THAT ARE MORE THAN 420 FEET (128 000 MM) IN | | | BUILDING HEIGHT SHALL BE SUPPLIED BY NO FEWER THAN TWO | | | RISERS. EACH RISER SHALL SUPPLY SPRINKLERS ON ALTERNATE | | | FLOORS. IF MORE THAN TWO RISERS ARE PROVIDED FOR A | | | ZONE, SPRINKLERS ON ADJACENT FLOORS SHALL NOT BE | | | SUPPLIED FROM THE SAME RISER. | | | -PLEASE SEE HOW THIS APPLIES TO OFFICE TOWER ONLY AND | | | UPDATE FS DRAWINGS AS APPLICABLE. | | | | | | NEW COMMENTS: | | | | | | 31) THERE ARE SOME SHEETS THAT ARE DUPLICATED AND THEY | | | ARE NOT LISTED AS PREVIOUS VERSIONS OF THE SHEET. I AM | | | NOT SURE WHY THIS HAPPENED. PERHAPS THEY WERE NAMED | | | DIFFERENTLY WHEN RESUBMITTING. PLEASE REMOVE THE | | | DUPLICATED SHEETS THAT ARE NOT VERSION-ED. CONTACT THE | | | PERMIT LIBRARIAN IF YOU REQUIRE ASSISTANCE. FBC | | | AMENDMENTS 107 | | | | | | 32) SHOW COMPLIANCE WITH FBC 403.4.5 EMERGENCY | | | RESPONDER RADIO COVERAGE SHALL BE PROVIDED IN | | | ACCORDANCE WITH THE FLORIDA FIRE PREVENTION CODE. THIS | | | TYPICALLY REQUIRES A BI-DIRECTIONAL ANTENNA (BDA | | | SYSTEM) OR SOME OTHER APPROVED METHOD. | | | | | | 33) NOTE #4 ON SHEET ALS1.100 IS APPARENTLY FOR ANOTHER | | | PROJECT. IT SPECIFIES OCEAN DRIVE AND HEATHER DRIVE AS | | | EMERGENCY STAGING AREAS. PLEASE CORRECT. FBC AMENDMENTS | | | 107.2.1 | | | | | | 34) ON PAGE 04.016 - ALS1.116, THE RESIDENTIAL ELEVATOR | | | MACHINE ROOM LIFE SAFETY PLAN IS NOT CLEAR. IT APPEARS | | | THAT THE PATH OF TRAVEL IS GOING THROUGH WALLS. PLEASE | | | CLARIFY. FBC AMENDMENTS 107.2.1 | | | | | | 35) ON PAGE 04.024 -ALS1.109, SHOW THE TOTAL OCCUPANT | | | LOAD OF THE TERRACE AND PICKLE BALL COURTS, THE LOADS | | | AT EACH EXIT DOOR AND THE COMBINED LOADS AT THE HOTEL | | | AND RESIDENT EXIT STAIRWAYS. FBC 1004 | | | | | | 36) ON SHEET A7.700 THERE APPEARS TO BE A WALL SHOWN IN | | | THE CENTER OF THE SCREEN ROOM THAT IS RUNNING THROUGH | | | SOME OF THE SEATING. PLEASE CLARIFY. FBC 107.2.1 | | | | | | 37) ON SHEET A0.001, GENERAL NOTES 6-10 ARE MISSING. | | | PLEASE CLARIFY. FBC AMENDMENTS 107.2.1 | | | | | | 38) ALSO ON SHEET A0.001, GENERAL NOTE 15 SHOULD | | | REFERENCE ASCE 7-10, RATHER THAN ASCE 7-88. FBC CHAPTER | | | 35. | | | | | | 39) FBC ACCESSIBILITY 505.10.3 REQUIRES THE HANDRAIL | | | EXTENSIONS AT THE BOTTOM OF STAIRS TO EXTEND AT THE | | | SLOPE OF THE STAIRFLIGHT FOR THE LENGTH OF A STAIR | | | TREAD BEFORE RETURNING TO THE WALL, FLOOR OR POST. | | | | | | 40) THE STAIR DETAIL DRAWINGS THAT START ON PG | | | 03.208-A5.101 APPEAR TO HAVE SOME ISSUES. PLEASE REVIEW | | | THE MINIMUM 44" STAIRWAY WIDTH REQUIRED BY FBC 1009.4. | | | THE 3'-8" RADIUS AT THE STAIR LANDINGS IN SOME OF THE | | | DETAILS ARE INCORRECT. | | | | | | 41) ON PAGE 04.002 - ALS1.101, EXIT PASSAGEWAY 0158 IS | | | SHOWN WITH A ONE HOUR FIRE RATED WALL AND A 45 MINUTE | | | FIRE RATED DOOR. FBC 1023 REQUIRES EXIT PASSAGEWAY | | | ENCLOSURES TO HAVE WALLS, FLOORS AND CEILINGS OF NOT | | | LESS THAN THAT REQUIRED FOR ANY CONNECTING INTERIOR | | | EXIT STAIRWAY OR RAMP. SINCE THE CONNECTING STAIRWAY | | | HAS A TWO HOUR FIRE RATING, THIS PASSAGEWAY IS ALSO | | | REQUIRED TO HAVE A TWO HOUR FIRE RATING AND A 90 MINUTE | | | FIRE RATED DOOR. | | | | | | 42) THE BUILDING OFFICIAL HAS DETERMINED THAT WHEN CAR | | | CHARGING STATIONS ARE PROVIDED, AT LEAST ONE ACCESSIBLE | | | EV CHARGING STATION IS TO BE PROVIDED FOR EVERY 25 | | | TOTAL EV CHARGING STATIONS. THE ACCESSIBLE EV CHARGING | | | STATIONS CAN BE LOCATED WITH THE OTHERS. | | | | | | 43) I DID NOT SEE THE DETAILS/ELEVATIONS OF BUILT-IN | | | ITEMS IN THE COMMON USE AREAS, SUCH AS RECEPTION DESKS, | | | SERVICE COUNTERS, BREAK ROOM KITCHENS, ETC. THAT ARE | | | REQUIRED TO BE ACCESSIBLE PER FBC ACCESSIBILITY | | | CHAPTERS 8 AND 9. PLEASE INDICATE SHEETS THEY ARE ON OR | | | PROVIDE SHEETS WITH DETAILS AND ELEVATIONS FOR THESE | | | ITEMS. | | | | | | 44) NOTE: ADDITIONAL COMMENTS MAY RESULT FROM THE | | | RESPONSES TO THESE PLAN REVIEW COMMENTS. | | | | | | -PROVIDE COMMENT RESPONSE SHEET TO EXPLAIN HOW EACH | | | COMMENT IS BEING ADDRESSED. | | | -FEEL FREE TO CONTACT ME AT 561-805-6714 (M-F 8-5) TO | | | DISCUSS COMMENTS, OR E-MAIL ANYTIME [email protected] | | | | | | NOTE: SEPARATE PERMITS (APPLICATIONS, PLANS, AND FEES) | | | ARE REQUIRED FOR: | | | LIGHT POLES/SITE LIGHTING | | | FIRE ALARM | | | FIRE SPRINKLER | | | LOW VOLTAGE | | | ACCESS | | | LANDSCAPING | | | IRRIGATION | | | PARKING LOT | | | SWIMMING POOLS AND SPAS | | | GENERATORS | | | ALL OTHER ITEMS OTHER THAN BMEP | | | | | | | | | | | | | | | | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2020-03-11 |
|
|
Cont ID |
|
| Sent By |
dbattles |
Date |
2020-03-11 |
Time |
09:12 |
Rev Time |
0.00 |
| Received By |
dbattles |
Date |
2020-02-18 |
Time |
07:38 |
Sent To |
|
|
| Notes |
| 2020-03-11 09:14:02 | BUILDING REVIEW COMMENTS: | | | | | | W.P.B. PERMIT: 18100540 | | | BUILDING PERMIT 30 STORY BLDG W/ TWO TOWERS | | | 1 ST REVIEW: APRIL 18, 2019 | | | 2 ND REVIEW: MARCH 2, 2020 | | | | | | DYLAN BATTLES | | | BUILDING PLANS EXAMINER PX4191 | | | [email protected] | | | 561-805-6718 | | | | | | FLORIDA BUILDING CODE,5TH EDITION (2014) | | | FBC[AMENDED] = 2014 CHAPTER 1 WPB AMENDMENTS (SEE LINK | | | BELOW) | | | HTTPS://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/ | | | BUILDING-PERMIT-FORMS | | | FBC[B] = FBC BUILDING | | | FBC[EXISTING] = FBC EXISTING BUILDING | | | FBC[A] = FBC ACCESSIBILITY | | | FBC[E] = FBC ENERGY CONSERVATION | | | FBC[R] = FBC RESIDENTIAL | | | | | | 1) 107.5.3 FBC[AMENDED]PLEASE UPDATE SHEET A0.102 SITE | | | DATA. THE DIAGRAM IN THE UPPER RIGHT CORNER DOESN'T | | | REFLECT THE CHANGES IN ROOMS SHOWN IN THE PLANS. | | | COMPARE SHEET A1.500 FOR SUITE AND UNIT COUNTS. | | | | | | A) AS A GENERAL COMMENT, PLEASE LOOK IN PROJECTDOX AND | | | NOTE IF SOME SHEETS MAY NOT HAVE BEEN REPLACED FOR | | | SECOND REVIEW. EITHER UPLOAD REVISED SHEETS, LEAVE IT | | | DIDN'T CHANGE OR REQUEST IT TO BE DELETED. | | | | | | B) LEVEL 8 - SHEET A1.260. IS THE COLUMN LAYER TURNED | | | OFF? ALSO, MISSING UNIT NUMBER ABOVE UNIT B1 08-22 | | | THIS SHEET WAS NOT REVISED FROM FIRST REVIEW SO I THINK | | | IT REFLECTS OLD LAYOUT. PLEASE UPLOAD NEW LEVEL 8 | | | RESIDENTIAL SHEET. | | | | | | C) LEVEL 13-14 - 08 UNITS EACH FLOOR . SHEET A1.265 | | | SAYS LEVEL 13-14, BUT THEN THE NEXT SHEET IS LEVEL 14. | | | PLEASE ADJUST TITLE BLOCK TO STATE LEVEL 13 ONLY. | | | | | | D) LEVEL 14 - 08 UNITS. SHEET A1.266 IS THE COLUMN | | | LAYER TURNED OFF? ALSO, MISSING UNIT NUMBERS. | | | | | | E) LEVEL 3 - MISSING SUITE NUMBER NEXT TO SUITE 7.1 ON | | | SHEET A1.103. LOOKS LIKE IT SHOULD BE SUITE 8. | | | | | | F) LEVEL 9 - MISSING SUITE NUMBER NEXT BETWEEN SUITE | | | 1.3B AND 1.3D ON SHEET A1.109 | | | | | | G) LEVEL 16 - SUITE 2B ADA LOOKS LIKE WALL WAS LEFT | | | BETWEEN ENTRY AND SLEEPING AREA. | | | | | | H) LEVEL 17, I CAN'T FIND OFFICE LEVEL FLOOR PLAN. I DO | | | SEE RCP AND LIFE SAFETY. PLEASE CHECK IF IT WAS LOADED | | | INTO PROJECT DOX. | | | | | | 2) 107.5.3 FBC[AMENDED]SHEET 03.052 - A1.240 - HOTEL | | | TOWER FLOOR PLAN - LEVEL 8 HAS NOT BEEN UPDATED. PLEASE | | | UPLOAD A NEW VERSION, OR REQUEST IT BE DELETED FROM THE | | | FOLDER. LEVEL EIGHT IS SHOWN ON PODIUM LEVEL 8 DRAWING | | | 03.014 - A1.108 - PODIUM FLOOR PLAN AND IN QUADRANT | | | PAGES AS WELL. | | | 3) 107.5.3 FBC[AMENDED]PLEASE ADD COMMUNICATION SYMBOL | | | TO SUITE 4.2B ON SHEET A1.243 | | | ROOM SUMMARY SHEET STATES LEVEL 12-15 AS COMMUNICATION. | | | PLEASE ADD SYMBOL TO THOSE ROOMS AS WELL. | | | ADD BOTH SYMBOLS TO SUITE 2.B ON SHEET A1.246 | | | PLEASE LOOK AT MOBILITY FEATURES DATA LAST LINE WHERE | | | IT SAYS LEVEL 8-16 SUITE 4.2B. I DO SEE THAT THERE IS | | | ADA ON LEVEL 16. ADD SYMBOLS AND CORRECT WHERE IT | | | STATES 8-16 OR SHOW THAT LEVEL 8-15 SUITE 4.2B ARE ADA | | | SUITES. | | | | | | 4) 224.5 FBC[A]DISPERSION. GUEST ROOMS REQUIRED TO | | | PROVIDE MOBILITY FEATURES COMPLYING WITH 806.2 AND | | | GUEST ROOMS REQUIRED TO PROVIDE COMMUNICATION FEATURES | | | COMPLYING WITH 806.3 SHALL BE DISPERSED AMONG THE | | | VARIOUS CLASSES OF GUEST ROOMS, AND SHALL PROVIDE | | | CHOICES OF TYPES OF GUEST ROOMS, NUMBER OF BEDS, AND | | | OTHER AMENITIES COMPARABLE TO THE CHOICES PROVIDED TO | | | OTHER GUESTS.WHERE THE MINIMUM NUMBER OF GUEST ROOMS | | | REQUIRED TO COMPLY WITH 806 IS NOT SUFFICIENT TO ALLOW | | | FOR COMPLETE DISPERSION, GUEST ROOMS SHALL BE DISPERSED | | | IN THE FOLLOWING PRIORITY: GUEST ROOM TYPE, NUMBER OF | | | BEDS, AND AMENITIES. AT LEAST ONE GUEST ROOM REQUIRED | | | TO PROVIDE MOBILITY FEATURES COMPLYING WITH 806.2 SHALL | | | ALSO PROVIDE COMMUNICATION FEATURES COMPLYING WITH | | | 806.3. NOT MORE THAN 10 PERCENT OF GUEST ROOMS REQUIRED | | | TO PROVIDE MOBILITY FEATURES COMPLYING WITH 806.2 SHALL | | | BE USED TO SATISFY THE MINIMUM NUMBER OF GUEST ROOMS | | | REQUIRED TO PROVIDE COMMUNICATION FEATURES COMPLYING | | | WITH 806.3. | | | -ONLY 10 PERCENT OF REQUIRED ROOMS CAN SHARE | | | COMMUNICATION AND MOBILITY. PLEASE SHOW COMMUNICATION | | | ROOMS ONLY SHARE IN ONE SUITE. | | | -PLEASE VERIFY THAT ROOMS ARE EVENLY DISTRIBUTED FOR | | | ROOM TYPES AND PRICE RANGE. | | | | | | 5) 806.4 FBC[A]HOTEL,MOTEL AND CONDOMINIUM SPECIAL | | | ACCESSIBILITY FEATURES. THIS SECTION DOES NOT RELIEVE | | | THE OWNER OF THE RESPONSIBILITY OF PROVIDING ACCESSIBLE | | | ROOMS IN CONFORMANCE WITH SECTION 224 AND 806 OF THIS | | | CODE. IN ALL BUILDINGS, STRUCTURES AND FACILITIES | | | LICENSED AS A HOTEL, MOTEL OR RESORT CONDOMINIUM | | | PURSUANT TO CHAPTER 509, F.S., A NUMBER OF ROOMS | | | EQUALING AT LEAST 5 PERCENT OF THE GUEST ROOMS MINUS | | | THE TOTAL NUMBER OF REQUIRED (ACCESSIBLE) ROOMS | | | REQUIRED BY TABLE 224.2 SHALL PROVIDE THE FOLLOWING | | | ADDITIONAL SPECIAL ACCESSIBILITY FEATURES: | | | (I) GRAB RAILS IN BATHROOMS AND TOILET ROOMS WHICH | | | COMPLY WITH SECTION 604.5. | | | (II) ALL BEDS IN DESIGNED ACCESSIBLE GUEST ROOMS SHALL | | | BE OPEN-FRAME TYPE THAT ALLOWS THE PASSAGE OF LIFT | | | DEVICES. | | | (III)WATER CLOSETS THAT COMPLY WITH SECTION 604.4. | | | -SHOW WHICH ROOMS COMPLY WITH 806.4 | | | | | | 6) 224.1 ADVISORY FBC[A]ARE THERE NON-TRANSIENT ROOMS | | | (MORE THAN 30 DAY STAY)? | | | IF SO, THOSE ROOMS MAY FALL UNDER THE FAIRHOUSING | | | GUIDELINES IN ADDITION TO ACCESSIBILITY FBC 2017 6 TH | | | EDITION. | | | | | | FAIRHOUSING REVIEW: | | | 7) 1986 ANSI [A117.1] IF A DESIGNER OR BUILDER CHOOSES | | | TO FOLLOW AN ACCESSIBILITY STANDARD OTHER THAN THE 1986 | | | ANSI A117.1 STANDARD, OR A MORE RECENT VERSION OF THE | | | ANSI A117.1, SUCH AS THE 1992 CABO/ANSI, THAT CARE BE | | | TAKEN TO ENSURE THE STANDARD USED IS AT LEAST | | | EQUIVALENT TO OR STRICTER THAN THE 1986 ANSI A117.1 | | | STANDARD. | | | -WHAT STANDARD IS BEING APPLIED FOR COMPLIANCE WITH | | | FAIR HOUSING? YOU CAN USE GUIDELINES THAT FALL WITHIN | | | THE SAFE HARBOR FOR COMPLIANCE? | | | | | | A) IT WOULD BE HELPFUL TO ADD A MATRIX OF ROOMS ON | | | SHEET A1.500 WHICH BATHROOM SPEC IS BEING USED AND | | | APPLY THE FOLLOWING FOR SPEC A AND B | | | | | | SPECIFICATION A: | | | IF SPECIFICATION A IS USED IT APPLIES TO ALL BATHROOMS, | | | AND ALL FIXTURES IN THOSE BATHROOMS MUST BE USABLE. | | | SPECIFICATION B: | | | IF SPECIFICATION B IS USED, IT APPLIES TO ONE BATHROOM, | | | AND ONLY ONE OF EACH TYPE OF FIXTURE MUST BE USABLE; | | | ADDITIONAL BATHROOMS IN THE UNIT ARE EXEMPT ONLY FROM | | | MANEUVERING AND CLEAR FLOOR SPACE REQUIREMENTS AT | | | FIXTURES. | | | | | | B) PLEASE ADD TO FAIRHOUSING NOTES ON SHEET A1.528. | | | THIS SAYS ALL BATHROOMS TO BE SPEC A. PLEASE ADJUST | | | NOTE SINCE BOTH SPEC ARE BEING USED. | | | | | | C) ADD NOTE FOR USABLE HARDWARE. | | | REQUIREMENT 3 - USABLE DOORS. THE DOORS IN COMMON | | | SPACES AND THE SIDE ENTERING INTO DWELLING UNITS NEED | | | TO HAVE USABLE HARDWARE THAT CAN BE USED WITHOUT TIGHT | | | GRASPING OR TWISTING. | | | -TYPICALLY THE HARDWARE WOULD BE A LEVER TYPE. THIS | | | TYPE OF HARDWARE WOULD NOT BE REQUIRED ONCE INSIDE THE | | | UNIT. YOU MAY WANT TO CLARIFY HARDWARE ON THE DOOR | | | SCHEDULE. | | | | | | D) DOOR SCHEDULE ON SHEET A6.104 IS DISTORTED AND | | | INFORMATION IS NOT LEGIBLE. PLEASE ADJUST AND POPULATE | | | AS NEEDED. | | | | | | E) SHOW ACCESSIBLE ROUTES FOR EACH UNIT TYPE. | | | | | | F) ADD DETAIL OF HOW ACCESS IS GAINED AT RESIDENTIAL | | | BALCONY. IS THERE ELEVATION CHANGE TO MEET FAIRHOUSING | | | MAX OF 4 INCHES TOP OF THRESHOLD? | | | | | | LIFE SAFETY: | | | | | | 8) 3006.2 FBC[B]SHEET A1.107 SHOWS NO ELEVATOR LOBBY ON | | | LEVEL 7 AT ELEVATORS 8, 9 AND 10. IF REQUIRED PLEASE | | | SHOW THE DOORS. | | | 1024.4 FBC[B]TERMINATION. EXIT PASSAGEWAYS ON THE LEVEL | | | OF EXIT DISCHARGE SHALL TERMINATE AT AN EXIT DISCHARGE. | | | EXIT PASSAGEWAYS | | | ON OTHER LEVELS SHALL TERMINATE AT AN EXIT. | | | EXIT DISCHARGE. THAT PORTION OF A MEANS OF EGRESS | | | SYSTEM BETWEEN THE TERMINATION OF AN EXIT AND A PUBLIC | | | WAY. | | | | | | 9) 3005.5 FBC[B]SHUNT TRIP. WHERE ELEVATOR HOISTWAYS, | | | ELEVATOR MACHINE ROOMS, CONTROL ROOMS AND CONTROL | | | SPACES CONTAINING ELEVATOR CONTROL EQUIPMENT ARE | | | PROTECTED WITH AUTOMATIC SPRINKLERS, A MEANS INSTALLED | | | IN ACCORDANCE WITH SECTION 21.4 OF NFPA 72 SHALL BE | | | PROVIDED TO DISCONNECT AUTOMATICALLY THE MAIN LINE | | | POWER SUPPLY TO THE AFFECTED ELEVATOR PRIOR TO THE | | | APPLICATION OF WATER. THIS MEANS SHALL NOT BE | | | SELF-RESETTING. THE ACTIVATION OF AUTOMATIC SPRINKLERS | | | OUTSIDE THE HOISTWAY, MACHINE ROOM, MACHINERY SPACE, | | | CONTROL ROOM OR CONTROL SPACE SHALL NOT DISCONNECT THE | | | MAIN LINE POWER SUPPLY. | | | | | | 10) 3006.2 FBC[B]HOISTWAY OPENING PROTECTION REQUIRED. | | | ELEVATOR HOISTWAY DOOR OPENINGS SHALL BE PROTECTED IN | | | ACCORDANCE WITH SECTION 3006.3 WHERE AN ELEVATOR | | | HOISTWAY CONNECTS MORE THAN THREE STORIES, IS REQUIRED | | | TO BE ENCLOSED WITHIN A SHAFT ENCLOSURE IN ACCORDANCE | | | WITH SECTION 712.1.1 AND ANY OF THE FOLLOWING | | | CONDITIONS APPLY: | | | 5. THE BUILDING IS A HIGH RISE AND THE ELEVATOR | | | HOISTWAY IS MORE THAN 75 FEET (22 860 MM) IN HEIGHT. | | | THE HEIGHT OF THE HOISTWAY SHALL BE MEASURED FROM THE | | | LOWEST FLOOR TO THE HIGHEST FLOOR OF THE FLOORS SERVED | | | BY THE HOISTWAY. | | | -IS THE PRE FUNCTION AREA OPEN AIR? IT IS HARD TO TELL | | | BUT IT APPREARS TO BE COVERED BY RESIDENTIAL ABOVE. | | | -FREIGHT ELEVATOR DOES NOT HAVE ELEVATOR LOBBY ON THE 8 | | | TH FLOOR. PLEASE REVIEW 3006.2 FOR OPENING PROTECTION | | | ON SHAFT MORE THAN 75 FEET. | | | | | | 11) 107.5.3 FBC[AMENDED]ADD SCALE TO LIFE SAFETY PLANS. | | | I THINK IT IS 1/16 SCALE. | | | ALSO, IS THERE A LIFE SAFETY SHEET FOR THE PARK ABOVE | | | THE TENNIS PAVILION? PLEASE PROVIDE OR LET ME KNOW | | | WHICH SHEET I CAN FIND IT. | | | | | | 12) 1004 FBC[B]PLEASE PROVIDE TOTAL OCCUPANT LOAD FOR | | | EACH EGRESS DOOR AT GRADE WHERE THE DOOR PROVIDES | | | EGRESS FROM MULTIPLE AREAS. FOR EXAMPLE EGRESS DOORS IN | | | HOTEL LOBBY PICKUP THE STAIRS AND OTHER AREAS FROM | | | FIRST LEVEL USES. I AM LOOKING FOR DATA TAG LIKE WAS | | | USED AT STAIRWAY DOORS. | | | | | | 13) 1025.1 FBC[B]GENERAL. APPROVED LUMINOUS EGRESS PATH | | | MARKINGS DELINEATING THE EXIT PATH SHALL BE PROVIDED IN | | | HIGH-RISE BUILDINGS OF GROUP A, B, E, I, M, AND R-1 | | | OCCUPANCIES IN ACCORDANCE WITH SECTIONS 1025.1 THROUGH | | | 1025.5. | | | -ST4 AND ST3 FROM R-1 LEVELS TO MEET 1025.1 FOR | | | LUMINOUS MARKINGS. | | | | | | 14) 1013.2 FBC[B] FLOOR-LEVEL EXIT SIGNS IN GROUP R-1. | | | WHERE EXIT SIGNS ARE REQUIRED IN GROUP R-1 OCCUPANCIES | | | BY SECTION 1013.1, ADDITIONAL LOW-LEVEL EXIT SIGNS | | | SHALL BE PROVIDED IN ALL AREAS SERVING GUEST ROOMS IN | | | GROUP R-1 OCCUPANCIES AND SHALL COMPLY WITH SECTION | | | 1013.5. | | | -ADD LOW LEVEL EXIT SIGNS AS REQUIRED, OR STATE WHICH | | | PAGE THIS INFORMATION CAN BE FOUND. | | | | | | 15) 107.3.5 FBC[AMENDED] MINIMUM REVIEW CRITERIA. THIS | | | IS FOR ALL LIFE SAFETY SHEETS | | | A. ADD MAX COMMON PATH AND MAX TRAVEL DISTANCE FOR R-1 | | | AND R-2 TO ALS1.100 COMPLIANCE SUMMARY FOR FLORIDA | | | BUILDING CODE IN ADDITION TO THE PROVIDED NFPA. THE | | | MORE RESTRICTIVE CODE WILL APPLY. | | | B. SHOW MAXIMUM PATH OF TRAVEL ON ALL L.S. PLANS. | | | CURRENTLY, L.S. SHEETS SHOW PATH OF TRAVEL DISTANCE OR | | | TOTAL DISTANCE. PLANS SHOULD SHOW BOTH COMMON PATH OF | | | TRAVEL AND EXIT ACCESS TRAVEL DISTANCE. THIS SHOULD BE | | | DONE FOR WORST CASE IN EACH GENERAL AREA. | | | | | | 16) 1003.5 FBC[B] ELEVATION CHANGE. DOES EXIT FROM | | | RESIDENT LOBBY TO STAIR 2 HAVE STEPS? PLEASE REVIEW | | | -HOW DO STEPS WORK AT EGRESS FROM RESIDENT LOUNGE TO | | | STAIR ST2? PLEASE REVIEW 1003.5 FOR CHANGE IN ELEVATION | | | IN PATH OF EGRESS. | | | | | | 17) 1012.9 FBC[B] INTERMEDIATE HANDRAILS. STAIRWAYS | | | SHALL HAVE INTERMEDIATE HANDRAILS LOCATED IN SUCH A | | | MANNER THAT ALL PORTIONS OF THE STAIRWAY MINIMUM WIDTH | | | OR REQUIRED CAPACITY ARE WITHIN 30 INCHES (762 MM) OF A | | | HANDRAIL. ON MONUMENTAL STAIRS, HANDRAILS SHALL BE | | | LOCATED ALONG THE MOST DIRECT PATH OF EGRESS TRAVEL. | | | -CHECK COMPLIANCE WITH 1012.9 AT BALLROOM STEPS. | | | | | | 18) 713.13.4 CHUTE DISCHARGE ROOM. WASTE OR LINEN | | | CHUTES SHALL DISCHARGE INTO AN ENCLOSED ROOM SEPARATED | | | BY FIRE BARRIERS WITH A FIRE RESISTANCE RATING NOT LESS | | | THAN THE REQUIRED FIRE RATING OF THE SHAFT ENCLOSURE | | | AND CONSTRUCTED IN ACCORDANCE WITH SECTION 707 OR | | | HORIZONTAL ASSEMBLIES CONSTRUCTED IN ACCORDANCE WITH | | | SECTION 711, OR BOTH. OPENINGS INTO THE DISCHARGE ROOM | | | FROM THE REMAINDER OF THE BUILDING SHALL BE PROTECTED | | | BY OPENING PROTECTIVES HAVING A FIRE PROTECTION RATING | | | EQUAL TO THE PROTECTION REQUIRED FOR THE SHAFT | | | ENCLOSURE. DOORS SHALL BE SELF- OR AUTOMATICCLOSING | | | UPON THE DETECTION OF SMOKE IN ACCORDANCE WITH SECTION | | | 716.5.9.3. WASTE CHUTES SHALL NOT TERMINATE IN AN | | | INCINERATOR ROOM. WASTE AND LINEN ROOMS THAT ARE NOT | | | PROVIDED WITH CHUTES NEED ONLY COMPLY WITH TABLE 509. | | | -DOUBLE DOORS TO TRASH ROOM AT BASE LEVEL SHOW 90 | | | MINUTE RATING, BUT 713.13.4 REQUIRES SAME LEVEL OF | | | PROTECTION FOR OPENINGS IN DISCHARGE ROOM EQUAL TO THE | | | SHAFT ENCLOSURE (2 HOURS). | | | | | | 19) 420.3 FBC[B]HORIZONTAL SEPARATION AND FBC[B] 602 | | | FLOOR ASSEMBLIES SEPARATING DWELLING UNITS IN THE SAME | | | BUILDINGS, FLOOR ASSEMBLIES SEPARATING SLEEPING UNITS | | | IN THE SAME BUILDING AND FLOOR ASSEMBLIES SEPARATING | | | DWELLING OR SLEEPING UNITS FROM OTHER OCCUPANCIES | | | CONTIGUOUS TO THEM IN THE SAME BUILDING SHALL BE | | | CONSTRUCTED AS HORIZONTAL ASSEMBLIES IN ACCORDANCE WITH | | | SECTION 711. | | | -602 FBC[B]SHEET A7.310 HAS CEILING ASSEMBLIES. PLEASE | | | SHOW THE RATED ASSEMBLY FOR CEILINGS SEPARATING | | | DWELLING AND SLEEPING UNITS AS STATED IN LIFE SAFETY | | | COMPLIANCE SUMMARY ALS1.100. | | | | | | 20) 713.13.3 FBC[B]CHUTE ACCESS ROOMS. ACCESS OPENINGS | | | FOR WASTE OR LINEN CHUTES SHALL BE LOCATED IN ROOMS OR | | | COMPARTMENTS ENCLOSED BY NOT LESS THAN 1-HOUR FIRE | | | BARRIERS CONSTRUCTED IN ACCORDANCE WITH SECTION 707 OR | | | HORIZONTAL ASSEMBLIES CONSTRUCTED IN ACCORDANCE WITH | | | SECTION 711, OR BOTH. OPENINGS INTO THE ACCESS ROOMS | | | SHALL BE PROTECTED BY OPENING PROTECTIVES HAVING A FIRE | | | PROTECTION RATING OF NOT LESS THAN 3/4 HOUR. DOORS | | | SHALL BE SELF- OR AUTOMATIC-CLOSING UPON THE DETECTION | | | OF SMOKE IN ACCORDANCE WITH SECTION 716.5.9.3. | | | -LIFE SAFETY SHEETS SHOW CHUTE ACCESS DOORS AS NOT | | | RATED (NR). THESE ACCESS DOORS ARE REQUIRED TO HAVE A | | | 3/4 HOUR RATING PER 713.13.3. | | | - ADD DOOR TAG TO THE DOORS LEADING TO THE TRASH CHUTE | | | OR TELL ME WHAT SHEETS THER ARE ON. I WAS LOOKING ON | | | QUADRANT SHEETS WHERE THE OTHER TAGS FOR COMMON SPACE | | | DOORS WERE LOCATED. | | | | | | DEFERRED SUBMITTALS | | | 21) 107.3.4.1 FBC[AMENDED]PLEASE PROVIDE A LIST OF | | | DEFERRED SUBMITTALS ON PLANS SO THAT I WILL NOT ASK FOR | | | ITEMS THAT WILL BE SUPPLIED AT A LATER DATE, OR | | | INDICATE WHICH PAGE A LIST CAN BE FOUND. | | | THESE ARE THE ONES I BELIEVE WE WILL NEED, BUT THIS IS | | | NOT A COMPLETE LIST. | | | A) COMPONENT & CLADDING PRODUCT APPROVALS (COMPLY WITH | | | PRESSURES SHOWN ON SHEET S0.0.5) | | | B) CURTAIN WALL SUBMITTAL (COMPLY WITH PRESSURES SHOWN | | | ON SHEET S0.0.5) | | | C) FENESTRATION SHOP DRAWINGS TO INCLUDE ALL WINDOWS, | | | DOORS, TRANSOMS, SLIDERS, LOUVERS AND MULL BARS. | | | D) FLOORING UNDERLAYMENT WITH THREE REPORTS: | | | 1. 1207.2 FBC[B] AIR-BORNE SOUND. WALLS, PARTITIONS AND | | | FLOOR/CEILING ASSEMBLIES SEPARATING DWELLING UNITS AND | | | SLEEPING UNITS FROM EACH OTHER OR FROM PUBLIC OR | | | SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS OF | | | NOT LESS THAN 50, OR NOT LESS THAN 45 IF FIELD TESTED, | | | FOR AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM | | | E90. | | | 2. 1207.3 FBC[B] STRUCTURE-BORNE SOUND. FLOOR/CEILING | | | ASSEMBLIES BETWEEN DWELLING UNITS AND SLEEPING UNITS OR | | | BETWEEN A DWELLING UNIT OR SLEEPING UNIT AND A PUBLIC | | | OR SERVICE AREA WITHIN THE STRUCTURE SHALL HAVE AN | | | IMPACT INSULATION CLASS RATING OF NOT LESS THAN 50, OR | | | NOT LESS THAN 45 IF FIELD TESTED, WHEN TESTED IN | | | ACCORDANCE WITH ASTM E492. | | | 3. 603.1 FBC[B] ALLOWABLE MATERIALS IN NON COMBUSTIBLE | | | BUILDINGS, SEE ITEM 2, EXCEPTION 2, ACOUSTICAL | | | INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID | | | DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED | | | TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200. SEE | | | 803.1.1, PROVIDE TEST DATA IN ACCORDANCE WITH ASTM E 84 | | | OR UL 723. | | | E) RAILINGS AND GUARDRAILS. INCLUDES BALCONIES, STAIRS | | | AND COMMON SPACES. | | | F) PARKING GARAGE VEHICLE BARRIER PER 406.4.2 FBC[B] | | | G) FIRE SPRAY | | | H) 806.1 FBC[B] GENERAL REQUIREMENTS. CURTAINS, | | | DRAPERIES, HANGINGS AND OTHER DECORATIVE MATERIALS | | | SUSPENDED FROM WALLS OR CEILINGS SHALL MEET THE FLAME | | | PROPAGATION PERFORMANCE CRITERIA OF NFPA 701 IN | | | ACCORDANCE WITH SECTION 806.2 OR BE NONCOMBUSTIBLE. | | | I) LIGHTWIEGHT CONCRETE. | | | J) WINDOW WASHING EQUIPMENT ATTACHMENTS/LOCATIONS AT | | | ROOF. | | | K) E.F.I.S. IF APPLICABLE | | | L) LIGHTING CONTROLS PER ENERGY CODE C405.2 LIGHTING | | | CONTROLS (MANDATORY) C405.5 EXTERIOR LIGHTING | | | (MANDATORY) | | | M) FINAL GYM EQUIPMENT LAYOUT WITH ACCESSIBILTY | | | REQUIREMENTS PROVIDED. | | | PRODUCT APPROVALS FOR ROOFING ARE PROVIDED, BUT NO | | | SELECTIONS ARE MADE AND IT IS NOT CLEAR WHICH AREA OF | | | ROOF RECEIVE. | | | ROOFING CAN BE ADDED TO DEFERRED SUBMITTAL LIST. | | | | | | 22) ALSO, PROVIDE PRODUCT APPROVAL FOR ROOF INSULATION | | | AND ATTACHMENT. | | | OTHER PRODUCT APPROVALS WERE SUBMITTED FOR DOORS, BUT | | | THEY WERE NOT STAMPED AS REVIEWED. AS PART OF | | | FENESTRATION PACKAGE PROVIDE ALL PRODUCT APPROVALS WITH | | | INDICATION THAT THEY WERE REVIEWED BY THE DESIGNER OF | | | RECORD. | | | | | | 23) ENERGY CODE REVIEW: | | | A) THIS BUILDING WAS BROUGHT IN UNDER 2014 CODE CYCLE. | | | PLEASE REVISE TO THAT CODE DATE, OR PROVIDE LETTER OF | | | COMPLIANCE THAT CURRENT CODES ARE EQUIVALENT. | | | B) C407.2.1 ROOF/CEILING THERMAL ENVELOPE. SECTIONS FOR | | | ROOFING AND DOORS SHOW NO DATA. PLEASE INCLUDE THOSE | | | VALUES IN THE ENERGY CALCULATIONS. | | | C) IN SECTION FOR WALLS THE ASSEMBLY STATES 6 INCH | | | INSULATION. WHERE IS THAT ASSEMBLY BEING USED ON THE | | | BUILING? | | | | | | ACCESSIBILITY REVIEW: | | | 24) 803.1 FBC[A] GENERAL. DRESSING, FITTING, AND LOCKER | | | ROOMS SHALL COMPLY WITH 803. | | | 803.2 FBC[A] TURNING SPACE. TURNING SPACE COMPLYING | | | WITH 304 SHALL BE PROVIDED WITHIN THE ROOM. | | | 803.3 FBC[A] DOOR SWING. DOORS SHALL NOT SWING INTO THE | | | ROOM UNLESS A CLEAR FLOOR OR GROUND SPACE COMPLYING | | | WITH 305.3 IS PROVIDED BEYOND THE ARC OF THE DOOR | | | SWING. | | | 803.4 FBC[A] BENCHES. A BENCH COMPLYING WITH 903 SHALL | | | BE PROVIDED WITHIN THE ROOM. | | | 903.4 FBC[A] BACK SUPPORT. THE BENCH SHALL PROVIDE FOR | | | BACK SUPPORT OR SHALL BE AFFIXED TO A WALL. BACK | | | SUPPORT SHALL BE 42 INCHES LONG MINIMUM AND SHALL | | | EXTEND FROM A POINT 2 INCHES MAXIMUM ABOVE THE SEAT | | | SURFACE TO A POINT 18 INCHES MINIMUM ABOVE THE SEAT | | | SURFACE. BACK SUPPORT SHALL BE 21/2 INCHES MAXIMUM FROM | | | THE REAR EDGE OF THE SEAT MEASURED HORIZONTALLY. | | | | | | 25) 236.1 FBC[A]GENERAL. AT LEAST ONE OF EACH TYPE OF | | | EXERCISE MACHINE AND EQUIPMENT SHALL COMPLY WITH 1004. | | | | | | 1004.1 FBC[A]CLEAR FLOOR SPACE. EXERCISE MACHINES AND | | | EQUIPMENT SHALL HAVE A CLEAR FLOOR SPACE COMPLYING WITH | | | 305 POSITIONED FOR TRANSFER OR FOR USE BY AN INDIVIDUAL | | | SEATED IN A WHEELCHAIR. CLEAR FLOOR OR GROUND SPACES | | | REQUIRED AT EXERCISE MACHINES AND EQUIPMENT SHALL BE | | | PERMITTED TO OVERLAP. | | | | | | ADVISORY 1004.1 FBC[A]CLEAR FLOOR SPACE. ONE CLEAR | | | FLOOR OR GROUND SPACE IS PERMITTED TO BE SHARED BETWEEN | | | TWO PIECES OF EXERCISE EQUIPMENT.TO OPTIMIZE SPACE USE, | | | DESIGNERS SHOULD CAREFULLY CONSIDER LAYOUT OPTIONS SUCH | | | AS CONNECTING ENDS OF THE ROW AND CENTER AISLE SPACES. | | | THE POSITION OF THE CLEAR FLOOR SPACE MAY VARY GREATLY | | | DEPENDING ON THE USE OF THE EQUIPMENT OR MACHINE. FOR | | | EXAMPLE, TO PROVIDE ACCESS TO A SHOULDER PRESS MACHINE, | | | CLEAR FLOOR SPACE NEXT TO THE SEAT WOULD BE APPROPRIATE | | | TO ALLOW FOR TRANSFER. CLEAR FLOOR SPACE FOR A BENCH | | | PRESS MACHINE DESIGNED FOR USE BY AN INDIVIDUAL SEATED | | | IN A WHEELCHAIR, HOWEVER, WILL MOST LIKELY BE CENTERED | | | ON THE OPERATING MECHANISMS. | | | | | | 26) 1009.1 GENERAL. WHERE PROVIDED, POOL LIFTS, SLOPED | | | ENTRIES, TRANSFER WALLS, TRANSFER SYSTEMS, AND POOL | | | STAIRS SHALL COMPLY WITH 1009. | | | -IF POOL LIFTS ARE PRVIDED PLEASE ADD DETAILS TO THE | | | ADA DETAIL SHEET. | | | ALSO, ADD ANY ADDITIONAL DETAILS IF APPLICABLE TO ADA | | | DETAILS FOR THE POOLS. | | | | | | 27) 405.8 FBC[A]HANDRAILS.RAMP RUNS WITH A RISE GREATER | | | THAN 6 INCHES (150 MM) SHALL HAVE HANDRAILS COMPLYING | | | WITH 505. | | | -SHEET ALS1.107 SHOWS RAMP FROM PRE-FUNCTION UP TO | | | ELEVATORS AND STAIR ST8. WILL THERE BE RAILS PROVIDE | | | THE RAMP AS REQUIRED? ALSO, IS THE WALKWAY FROM RAMP TO | | | STAIR 8 GOING TO HAVE RAIL OR IS IT OPEN FROM ABOVE TO | | | PRE-FUNCTION? | | | | | | CHAPTER 4 ? HIGHRISE | | | 28) 403.5.3.1 FBC[B]STAIRWAY COMMUNICATION SYSTEM. A | | | TELEPHONE OR OTHER TWO-WAY COMMUNICATIONS SYSTEM | | | CONNECTED TO AN APPROVED CONSTANTLY ATTENDED STATION | | | SHALL BE PROVIDED AT NOT LESS THAN EVERY FIFTH FLOOR IN | | | EACH STAIRWAY WHERE THE DOORS TO THE STAIRWAY ARE | | | LOCKED. | | | -WILL THE DOORS BE LOCKED FROM THE STAIRWAY SIDE? IF SO | | | PLEASE ADD COMMUNICATION SYSTEM AS REQUIRED IN | | | 403.5.3.1 | | | | | | 29) 1022.8 FBC[B] DISCHARGE IDENTIFICATION. AN INTERIOR | | | EXIT STAIRWAY AND RAMP SHALL NOT CONTINUE BELOW ITS | | | LEVEL OF EXIT DISCHARGE UNLESS AN APPROVED BARRIER IS | | | PROVIDED AT THE LEVEL OF EXIT DISCHARGE TO PREVENT | | | PERSONS FROM UNINTENTIONALLY CONTINUING INTO LEVELS | | | BELOW. DIRECTIONAL EXIT SIGNS SHALL BE PROVIDED AS | | | SPECIFIED IN SECTION 1011. | | | -IF STAIRWAY 4 AT 2 ND LEVEL TRANSFERS TO STAIRWAY 11 | | | THAN 1022.8 APPLIES. | | | | | | 30) 403.3.1 FBC[B]NUMBER OF SPRINKLER RISERS AND SYSTEM | | | DESIGN. EACH SPRINKLER SYSTEM ZONE IN BUILDINGS THAT | | | ARE MORE THAN 420 FEET (128 000 MM) IN BUILDING HEIGHT | | | SHALL BE SUPPLIED BY NO FEWER THAN TWO RISERS. EACH | | | RISER SHALL SUPPLY SPRINKLERS ON ALTERNATE FLOORS. IF | | | MORE THAN TWO RISERS ARE PROVIDED FOR A ZONE, | | | SPRINKLERS ON ADJACENT FLOORS SHALL NOT BE SUPPLIED | | | FROM THE SAME RISER. | | | -PLEASE SEE HOW THIS APPLIES TO OFFICE TOWER ONLY AND | | | UPDATE FS DRAWINGS AS APPLICABLE. | | | | | | -PROVIDE COMMENT RESPONSE SHEET TO EXPLAIN HOW EACH | | | COMMENT IS BEING ADDRESSED. | | | -FEEL FREE TO CONTACT ME AT 561-805-6718 (M-F 8-5) TO | | | DISCUSS COMMENTS, OR E-MAIL ANYTIME [email protected] | | | | | | | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2019-04-18 |
|
|
Cont ID |
|
| Sent By |
dbattles |
Date |
2019-04-18 |
Time |
15:07 |
Rev Time |
0.00 |
| Received By |
dbattles |
Date |
2019-03-26 |
Time |
08:47 |
Sent To |
|
|
| Notes |
| 2019-04-18 15:07:33 | ****CORRECTIONS**** | | | W.P.B. PERMIT: 18100540 | | | REVIEWED: APRIL 18, 2019 | | | | | | DYLAN BATTLES | | | BUILDING PLANS EXAMINER PX4191 | | | [email protected] | | | 561-805-6718 | | | | | | FBC[AMENDED] = FLORIDA BUILDING CODE,5TH EDITION (2014) | | | FBC[B] = FBC BUILDING | | | FBC[A] = FBC ACCESSIBILITY | | | FBC[E] = FBC ENERGY CONSERVATION | | | FBC[R] = FBC RESIDENTIAL | | | | | | 1) 107.2.1 FBC[B]DRAWINGS STATE THAT THEY ARE AT 80 | | | PERCENT. | | | -A FULL REVIEW CANNOT BE PROVIDED UNTIL 100% PLANS ARE | | | PROVIDED. THIS REVIEW IS BASED ON THE 80 PERCENT PLANS | | | PROVIDED. WHEN RE-UPLOADING PLEASE ADD DIGITAL | | | REPRESENTATION OF SEAL AND REMOVE 80% DESIGNATION. | | | | | | 2) 107.2.1 FBC[AMENDED] PLACE A DIGITALLY CREATED IMAGE | | | OF YOUR SEAL AND THE FOLLOWING SENTENCES WHERE AN | | | ORIGINAL SIGNATURE WOULD APPEAR IF THE ITEM WERE BEING | | | PHYSICALLY SIGNED DATED AND SEALED. THE SENTENCES CAN | | | BE PART OF THE DIGITAL SIGNATURE CUSTOM APPEARANCE | | | AVAILABLE IN THE SIGNING TOOL, OR THEY CAN BE PLACED ON | | | THE DOCUMENT OUTSIDE OF THE DIGITAL SIGNATURE BLOCK. | | | THIS ITEM HAS BEEN ELECTRONICALLY SIGNED AND SEALED BY | | | [LICENSEE, RA, OR LS] ON THE DATE AND/OR TIME STAMP | | | SHOWN USING A DIGITAL SIGNATURE. | | | -SEE SIGNATURE REVIEW. CONTACT PERMIT LIBRARIAN OR | | | BUILDING PLANS EXAMINER FOR OPTIONS TO SATISFY 107.2.1. | | | | | | 3) 107.3.4.1 FBC[AMENDED] DEFERRED SUBMITTALS. FOR THE | | | PURPOSES OF THIS SECTION, DEFERRED SUBMITTALS ARE | | | DEFINED AS THOSE PORTIONS OF THE DESIGN THAT ARE NOT | | | SUBMITTED AT THE TIME OF THE APPLICATION AND THAT ARE | | | TO BE SUBMITTED TO THE BUILDING OFFICIAL WITHIN A | | | SPECIFIED PERIOD. DEFERRAL OF ANY SUBMITTAL ITEMS SHALL | | | HAVE THE PRIOR APPROVAL OF THE BUILDING OFFICIAL. THE | | | REGISTERED DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE | | | SHALL LIST THE DEFERRED SUBMITTALS ON THE CONSTRUCTION | | | DOCUMENTS FOR REVIEW BY THE BUILDING OFFICIAL. | | | DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE | | | SUBMITTED TO THE REGISTERED DESIGN PROFESSIONAL IN | | | RESPONSIBLE CHARGE WHO SHALL REVIEW THEM AND FORWARD | | | THEM TO THE BUILDING OFFICIAL WITH A NOTATION | | | INDICATING THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE | | | BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO | | | THE DESIGN OF THE BUILDING. THE DEFERRED SUBMITTAL | | | ITEMS SHALL NOT BE INSTALLED UNTIL THE DEFERRED | | | SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE BUILDING | | | OFFICIAL. | | | -PLEASE PROVIDE A LIST OF DEFERRED SUBMITTALS SO THAT | | | I WILL NOT ASK FOR ITEMS THAT WILL BE SUPPLIED AT A | | | LATER DATE, OR INDICATE WHICH PAGE A LIST CAN BE FOUND. | | | | | | 4) 107.3.4.1 FBC[AMENDED] PRODUCT APPROVALS. PRODUCT | | | APPROVALS ARE PROVIDED FOR WINDOWS, DOORS AND ROOFING. | | | A. PLEASE INCULDE ON WINDOW AND DOOR SCHEDULES WHICH | | | APPROVAL APPLIES TO EACH OPENING. | | | B. NOTE ON ROOFING PLANS WHAT ROOF TYPE EACH AREA WILL | | | RECEIVE. IF THESE APPROVALS WILL LIKELY CHANGE YOU MAY | | | WANT TO DO ROOFING AS A DEFERRED SUBMITTAL. CHANGING | | | ROOF SYSTEMS LATER MAY REQUIRE REVISION IF NOT | | | SPECIFIED UP FRONT AS A DEFERRED SUBMITTAL. | | | | | | 5) 107.3.5 FBC[AMENDED] MIN REVIEW CRITERIA. FLOOR | | | PLANS FOR ALL RESIDENTIAL LEVELS ARE INCOMPLETE | | | (ESPECIALLY ABOVE PODIUM LEVELS). MISSING WALL TYPES, | | | DIMENSIONS, DOOR TYPES, OPENING SCHEDULES FINISHES AND | | | DETAILS AS APPLICABLE. | | | | | | 6) 107.3.5 FBC[AMENDED] MIN REVIEW CRITERIA.COMPLETE | | | ADDING WALL TYPES FOR SOUND CONTROL BETWEEN PUBLIC | | | AREAS AND OTHER WALLS AS APPLICABLE. | | | | | | 7) 107.3.5 FBC[AMENDED]ARE BALCONIES SEPARATED? IF SO | | | PROVIDE DETAILS. | | | | | | 8) 107.3.5 FBC[AMENDED]SHEET A1.602 ENLARGED | | | BATHROOMS. | | | -TOILETS DO NOT SHOW UP ON THIS SHEET AND I THINK | | | COLUMNS ARE TURNED OFF AS WELL. IS THIS SHEET GOING TO | | | BE DIMENSIONED AND CLEAR SPACES SHOWN FOR ADA | | | CLEARANCES? | | | | | | 9) 107.3.5 FBC[AMENDED] GEOMETRY PLANS RESIDENTIAL WILL | | | NEED TO BE COMPLETE BEFORE REVIEWING. A10.212 TO | | | A10.255. OTHER GEOMETRY SHEETS MAT NEED TO BE COMPLETES | | | AS WELL. | | | | | | 10) 107.3.5 FBC[AMENDED] MEANS OF EGRESS | | | -SHEETS A1.101, A1.202 AND ALS1.101 LOOKING AT | | | REVOLVING DOORS IT APPEARS THAT A SMALL REVOLVING DOOR | | | IS ON TOP OF LARGER REVOLVING DOOR IN TWO DOORS INTO | | | HOTEL LOBBY. ALSO , THIS SMALLER REVOLVE APPEARS OVER | | | DOUBLE DOORS NEAR VALET DROP OFF. | | | | | | 11) 107.3.5 FBC[AMENDED] WHERE IS SAYS VALET DROP-OFF | | | THERE IS A DIRECTION ARROW THAT MAKES IT APPERAR TO BE | | | A ROADWAY. I DON'T SEE THE ARROW ON OTHER SHEETS, SO | | | CHECK IF IT SHOULD BE REMOVED. | | | | | | 12) 107.3.5 FBC[AMENDED]SOME DOORS HAVE NUMBERS LIKE | | | 267, 262 AND OTHERS ARE NOT NUMBERED. THE NUMBERS DO | | | NOT CORESPOND TO NUMBERING SYSTEM ON THE DOOR | | | SCHEDULE. | | | -PLEASE TELL ME HOW THE DOORS CORESPOND TO THE DOOR | | | SCHEDULE. | | | | | | 13) ON ALL LIFE SAFETY SHEETS THE COLUMN LAYER DOESN'T | | | SHOW UP ON DRAWINGS. IT MAKES THE PLANS TO APPEAR AS IF | | | THERE ARE SPACES BETWEEN AREAS. | | | A. PLEASE SHOW COLUMNS ON ALL LIFE SAFETY SHEET. ALSO, | | | SHEET ALS1.114 AT ELEVATOR LOBBY IN RESIDENTIAL SIDE | | | WITH THREE ELEVATOR BANKS LOOKS LIKE WALLS INSTEAD OF | | | DOORS. | | | B. SAME COMMENT FOR PLAN SHEETS A1.240 - A1.255 AND | | | A1.260 - A1.272. PLEASE SHOW COLUMNS ON ALL SHEETS. | | | | | | 14) 107.3.5 FBC[AMENDED] SHEET ALS1.114 CHECK UNIT A4 | | | OCCUPANCY SIZE AND COUNT | | | A. ADJUST SQ. FOOTAGE OF UNIT AS 5,205 SF IS NOT | | | CORRECT FOR THE UNIT. | | | B. ADJUST OCCUPANCY COUNT TOTALS AS NEEDED. | | | | | | 15) 107.3.5 FBC[AMENDED] SHEET A1.602SHOW DIMENSIONS ON | | | ENLARGED BATHROOM PLANS. | | | | | | | | | 16) 107.3.5 FBC[AMENDED] MINIMUM REVIEW CRITERIA. THIS | | | IS FOR ALL LIFE SAFETY SHEETS | | | A. ADD MAX COMMON PATH AND MAX TRAVEL DISTANCE FOR R-1 | | | AND R-2 TO ALS1.100 COMPLIANCE SUMMARY | | | ADD STAIR 10 AND 12 DATA TO EXIT CAPACITY TABLE. IS | | | THERE A STAIRWAY 11? | | | B. STAIR 12 MERGES WITH STAIR 6. STAIR DATA SHOULD | | | INCLUDE ACTUAL LOAD AT EACH STAIR AND ANY MERGING | | | SHOULD BE INCLUDED IN THE TOTAL. | | | C. CHECK ALL EXIT CAPACITY TABLES FOR DOOR CAPACITY | | | BASED ON .2 INCHES PER OCCUPANT AND THE DOOR WIDTH | | | NEEDS TO BE CLEAR WIDTH. | | | D. COLUMNS DON?T SHOW ON THE PLAN LIFE SAFETY PLANS. | | | PLEASE SHOW COLUMNS ON ALL PLANS. | | | E. IT?S NOT CLEAR WHAT THE COMMON PATH OF TRAVEL IS | | | AND WHAT THE MAX TRAVEL DISTANCE WILL BE FOR THE | | | RESIDENTIAL. COMMON PATH OF TRAVEL WOULD BE FROM MOST | | | REMOTE POINT IN UNIT TO THE COORIDOR WHERE 2 EXIT | | | OPTIONS ARE PROVIDED. | | | F. PROVIDE OCCUPANT LOAD FOR SEPARATE OCCUPANCIES (R-2 | | | AND S-2), EXITS REQUIRED, EXITS PROVIDED AND OCCUPANT | | | LOAD AT EACH EXIT IN ADDITION TO THE LIMITING CAPACITY | | | PROVIDED. | | | G. ALL LIFE SAFETY SHEETS AND ALL FP SHEETS NEED TO BE | | | COORDINATED. STANDPIPES APPEAR TO BLOCK PATH OF EGRESS | | | AT GROUND FLOORS AND EGRESS DOORS DON?T LINE UP WITH | | | EXTENDED WALLS AT CURTAIN WALL. | | | | | | 17) 107.3.5 FBC[AMENDED] MINIMUM REVIEW CRITERIA. | | | ALS1.101 | | | A. REVIEW PLACEMENT EXIT SIGN .WHERE DOES THE EXIT | | | SIGN NEXT TO TRUCKS EGRESS? | | | B. TOILETS DON?T SHOW ON THE PLAN, THEN THEY DON?T | | | SHOW ON THE ENLARGED A1602 | | | C. REVOLVING DOORS OVERLAPPING AND DIFFERENT SIZES. | | | D. STAIRWAY 11 SAYS 6IN. STANDPIPE, BUT IT IS 8 IN. ON | | | FP.201.B | | | E. LABEL FPL VAULT. ALSO LABEL FPL ON OTHER APPLICABLE | | | SHEETS. | | | F. WHAT ARE THE 2 WALL AREAS THAT LOOK LIKE OPENINGS | | | IN FPL VAULT? LOUVERS? | | | | | | 18) 107.3.5 FBC[AMENDED] MINIMUM REVIEW CRITERIA. | | | ALS1.102 | | | A. ROOM TAG MISSING ON SHEET ALS1.102, A1.102 AND | | | A1.208 (PLUS OTHER APPLICABLE SHEETS) | | | B. ADD EXIT SIGN TO STAIR 6 FROM GARAGE TO EXIT STAIR. | | | | | | 19) 107.3.5 FBC[AMENDED] MINIMUM REVIEW CRITERIA. | | | ALS1.103 | | | A. ADD EXIT SIGN TO STAIR 6 FROM GARAGE TO EXIT STAIR. | | | B. REVIEW DATA TAG ON UNITS S1.3 (TWO UNITS SHOW | | | SAME). SAYS NOT ENCLOSED AND 0 OCCUPANTS. | | | | | | 20) 107.3.5 FBC[AMENDED] MINIMUM REVIEW CRITERIA. | | | ALS1.104 | | | -REVIEW DATA TAG ON UNIT S1.2. SAYS NOT ENCLOSED AND 0 | | | OCCUPANTS. | | | | | | 21) 107.3.5 FBC[AMENDED] MINIMUM REVIEW CRITERIA. | | | ALS1.105 | | | -REVIEW DATA TAG ON UNIT S1.2. SAYS NOT ENCLOSED AND 0 | | | OCCUPANTS. | | | | | | 22) 107.3.5 FBC[AMENDED] MINIMUM REVIEW CRITERIA. | | | ALS1.106 | | | -UPDATE PER TYPICAL COMMENTS. | | | | | | 23) 107.3.5 FBC[AMENDED] MINIMUM REVIEW CRITERIA. | | | ALS1.107 | | | A. IS LEVEL 7 SHARED BY HOTEL AND RESIDENTIAL? | | | B. POOL DECK OCCUPANT LOAD SHOWS ZERO. | | | C. 1011.6 FBC[B] STAIRWAY LANDINGS. CHECK EGRESS DOOR | | | SWING FROM POOL DECK INTO STAIR 5 IS IT TOO FAR INTO | | | STAIRWAY PATH OF EGRESS? | | | D.1003.5 FBC[B] ELEVATION CHANGE. DOES EXIT FROM | | | RESIDENT LOBBY TO STAIR 2 HAVE STEPS? PLEASE REVIEW | | | E. HOW DO STEPS WORK AT 2 ND EGRESS FROM RESIDENT | | | LOUNGE? (SEE SECTION A4.200) | | | F. 1003.5 FBC[B] REVIEW EGRESS AT BALLROOM TO STAIR 8. | | | DOES THIS EGRESS USE STAIRS FOR EGRESS? | | | G. CHECK EGRESS FROM BALLROOM TERRACE. THE BALLROOM | | | ELEVATION IS 2 FEET LOWER THAN RESIDENTIAL DECK. HOW | | | DOES EGRESS FROM BALLROOM TO STAIR 7 WORK WITH | | | ELEVATION DIFFERENCE? | | | H. SHEET A5.104 CHECK DOOR ELEVATION FOR STAIR 2 AT | | | 7TH LEVEL. THE DOOR IS POSITIONED TWO FEET HIGHER | | | BECAUSE THERE ARE STEPS DOWN TO GET TO STAIR 2 AND IT | | | LOOKS TO BE SET AT ELEVATION OF POOL DECK AND | | | RESIDENTIAL LOUNGE. | | | I. CAPACITY SHOWN IN TABLE DOESN?T EXCEED THE AMOUNT | | | OF OCCUPANTS ON LEVEL AND IT ISN?T CLEAR WHICH EXITS | | | SERVE WHICH OCCUPANTS. | | | J. PROVIDE EGRESS BASED ON OCCUPANCY REQUIRED WIDTH | | | AND PROVIDED. THE TABLES PROVIDED ARE BASED ON | | | CAPACITY, BUT OCCUPANCY NEEDS TO BE LOOKED AT BY AREA | | | SERVED. | | | K. REVIEW EGRESS FROM TENNIS AND TERRACE AREAS. TENNIS | | | COURTS AND TERRACES REQUIRES 292 INCHES OF EGRESS FOR | | | 1457 OCCUPANTS. STAIR 5 AND 9 STATE (2) 40 INCH DOORS | | | FOR 160 INCHES AND STAIRWAY 10 MAY PROVIDE ADDITIONAL | | | 80 (ADD DATA TO CHART AND THE LOAD FROM LEVEL 8 GETS | | | ADDED INTO LEVEL 7 FOR 1005.6 FBC[B] CONVERGENCE). | | | TOTAL IS NOW 240, SO 52 INCHES WOULD STILL NEED TO BE | | | SUPPLIED WITHIN THE MAX TRAVEL DISTANCE. THERE IS PATH | | | GOING TO RESIDENTIAL STAIR, BUT THE DOOR IS 32 INCHES | | | AND THE DOOR WOULD NEED TO BE UNLOCKED FROM EGRESS | | | SIDE. STAIR 2 ALSO HAS RESIDENTIAL AND POOL AREA | | | APPLIED TO THE EGRESS WIDTH OF STAIR 2. | | | | | | 24) 107.3.5 FBC[AMENDED] PLEASE REVIEW HOW MANY | | | OCCUPANTS CONTRIBUTE TO EACH EXIT AND CALCULATE TOTAL | | | FOR EACH EXIT. CURRENT LIFE SAFETY SEEMS TO LOOK AT | | | ENTIRE FLOOR AND BASED ON CAPACITY, BUT EACH FLOOR | | | NEEDS MORE DETAIL AS TO HOW MANY OCCUPANTS, NUMBER OF | | | EXITS REQUIRED AND CONVERGENCE. | | | -SHOW HOW CONVERGENCE IS HANDLED FROM STAIR 10 LEVEL 8 | | | TO LEVEL 7. | | | | | | 25) 107.3.5 FBC[AMENDED] SHEET ALS1.110 SUITE 12-10 | | | DOESN?T SHOW OCCUPANT LOAD. PLEASE ADD TO FLOOR COUNT. | | | | | | 26) 107.3.5 FBC[AMENDED] THE REFLECTED CEILING PLANS | | | (RCP) DO NOT APPEAR TO BE COMPLETE. PLEASE SUBMIT | | | COMPLETED RCP PLANS FOR SECOND REVIEW. | | | | | | 27) 107.3.5 FBC[B] MISSING LS FOR RESIDENTIAL FLOORS 8, | | | 9, 10 AND 11. THEY HAVE A DIFFERENT CONFIGURATION THAN | | | FLOORS 13-30. | | | -PROVIDE LIFE SAFTY SHEET FOR EACH FLOOR | | | CONFIGURATION. | | | | | | 28) 107.3.5 FBC[AMENDED] SHEET ALS1.111 REMOVE WALL AT | | | EGRESS 90 MINUTE DOOR. | | | | | | 29) 107.3.5 FBC[AMENDED] SHEET ALS1.112 OCCUPANT | | | SCHEDULE LOAD EXCEEDS EXIT CAPACITY TABLE, AND ROOM | | | LABELS DO NOT MATCH SCHEDULE LOADS. | | | | | | 30) 107.3.5 FBC[AMENDED] SHEET ALS1.112 PLANTERS APPEAR | | | TO BLOCK ROOF DRAINS. | | | | | | 31) 107.3.5 FBC[B] THE HOTEL LEVEL , AND BUSINESS | | | ABOVE, RELY ON TWO INTERIOR STAIRWAYS FOR EGRESS. | | | A. BOTH INTERIOR STAIRWAY DOORS ON THE LEVEL OF EXIT | | | DISCHARGE ARE SWINGING IN. PLEASE REVIEW THIS AS EACH | | | EXIT WILL SERVE MORE THAN 50 PERSONS. | | | B. IS THE INTENT TO EGRESS FROM STAIRWAY 4 AT 2ND | | | LEVEL AND TRANSFER TO STAIRWAY 11? | | | | | | 32) 107.3.5 FBC[A] COVERED MULTIFAMILY DWELLINGS FOR | | | FIRST OCCUPANCY AFTER MARCH 13, 1991, SHALL BE DESIGNED | | | AND CONSTRUCTED TO HAVE AT LEAST ONE BUILDING ENTRANCE | | | ON AN ACCESSIBLE ROUTE UNLESS IT IS IMPRACTICAL TO DO | | | SO BECAUSE OF THE SITE. | | | A. SHOW ACCESSIBLE PATH FOR RESIDENTIAL UNITS. | | | | | | 1986 ANSI [A117.1] IF A DESIGNER OR BUILDER CHOOSES TO | | | FOLLOW AN ACCESSIBILITY STANDARD OTHER THAN THE 1986 | | | ANSI A117.1 STANDARD, OR A MORE RECENT VERSION OF THE | | | ANSI A117.1, SUCH AS THE 1992 CABO/ANSI, THAT CARE BE | | | TAKEN TO ENSURE THE STANDARD USED IS AT LEAST | | | EQUIVALENT TO OR STRICTER THAN THE 1986 ANSI A117.1 | | | STANDARD. | | | FHA AND ADA ARE BEING USED, BUT IT IS NOT CLEAR WHICH | | | CODE APPLIES TO MIXED USE OCCUPANCIES. PLEASE PROVIDE A | | | SUMMARY OF EACH OCCUPANCY AND IF ADA OR FHA IS BEING | | | APPLIED. | | | -WHAT STANDARD IS BEING USED TO INCORPORATE FAIR | | | HOUSING GUIDELINES? | | | | | | WALKS THAT ARE PART OF ACCESSIBLE ROUTES BECOME RAMPS | | | WHEN THEIR SLOPE EXCEEDS 5% (1 IN 20). HANDRAILS ARE | | | NOT REQUIRED ON WALKS WITH SLOPES BETWEEN 0% AND 5%, | | | BUT THEY ARE REQUIRED ON THOSE STEEPER THAN 5% AND UP | | | TO 8.33% (1 IN 12) | | | B. CLEARLY INDICATE ANY RAMPS ON PLANS. LEVEL 7 FOR | | | EXAMPLE HAS 2 FOOT DIFFERENCE BETWEEN POOL DECK AND | | | BALLROOM. RAMPS WILL AFFECT EGRESS AND PATH OF TRAVEL. | | | | | | IN DWELLING UNITS CONTAINING MORE THAN ONE BATHROOM, IF | | | SPECIFICATION A IS SELECTED AS THE BASIS FOR DESIGNING | | | A BATHROOM, ALL BATHROOMS IN THE DWELLING UNIT ALSO | | | MUST COMPLY WITH THE A SPECIFICATIONS. IF SPECIFICATION | | | B IS SELECTED, ONLY ONE BATHROOM IN THE DWELLING UNIT | | | MUST MEET THOSE REQUIREMENTS ALL BATHROOMS AS DEFINED | | | IN THE GUIDELINES MUST: | | | 1. BE ON AN ACCESSIBLE ROUTE (REQUIREMENT 4), | | | 2. HAVE 32-INCH NOMINAL CLEAR WIDTH DOORWAYS | | | (REQUIREMENT 3) | | | 3. HAVE SWITCHES, OUTLETS, AND CONTROLS IN ACCESSIBLE | | | LOCATIONS (REQUIREMENT 5) | | | 4. HAVE REINFORCING AROUND TOILETS, TUBS, AND SHOWERS | | | (REQUIREMENT 6) | | | 5. MEET REQUIREMENT 7, SPECIFICATION A OR B: | | | POWDER ROOMS MUST: | | | 1. BE ON AN ACCESSIBLE ROUTE (REQUIREMENT 4), | | | 2. HAVE 32-INCH NOMINAL CLEAR WIDTH DOOR-WAYS | | | (REQUIREMENT 3), AND | | | 3. HAVE SWITCHES, OUTLETS, AND CONTROLS IN ACCESSIBLE | | | LOCATIONS (REQUIREMENT 5). EXCEPTION WHEN THE POWDER | | | ROOM IS THE ONLY TOILET FACILITY ON THE ENTRY LEVEL OF | | | A MULTI-STORY UNIT IN A BUILDING WITH ONE OR MORE | | | ELEVATORS, IT MUST, IN ADDITION TO REQUIREMENTS 3, 4, | | | AND 5, MEET THE REINFORCING SPECIFICATIONS OF | | | REQUIREMENT 6 AND THE MANEUVERING AND CLEAR FLOOR | | | SPECIFICATIONS OF REQUIREMENT 7. | | | 101.4.1 FBC[CE] MIXED OCCUPANCY. WHERE A BUILDING | | | INCLUDES BOTH RESIDENTIAL AND COMMERCIAL OCCUPANCIES, | | | EACH OCCUPANCY SHALL BE SEPARATELY CONSIDERED AND MEET | | | THE APPLICABLE PROVISIONS OF FLORIDA BUILDING CODE, | | | ENERGY CONSERVATION?COMMERCIAL PROVISIONS OR FLORIDA | | | BUILD. | | | C. PROVIDE DOCUMENTS TO SHOW COMPLIANCE WITH FBC | | | ENERGY FOR EACH OCCUPANCY. | | | | | | 33) 208.1 FBC[A] SHEET A0.102 PARKING. PLEASE INDICATE | | | ON THE PLANS WHICH PARKING SPOTS ARE SHARED. IF ANY | | | SPOTS ARE NOT TO BE SHARED THEN THEY SHOULD NOT BE | | | INCLUDED IN THE SHARED PARKING TABLE. | | | A. IF ALL SPOTS ARE SHARED AS INDICATED, PROVIDE | | | DETAILS OF HOW TANDEM AND LIFT SPOTS ARE USABLE BY ALL | | | OCCUPANCIES. | | | B. WHICH OCCUPANCIES ARE SERVED BY VALET AND WHERE DO | | | THEY PARK? | | | | | | 34) 206.1 FBC[A] GENERAL. ACCESSIBLE ROUTES SHALL BE | | | PROVIDED IN ACCORDANCE WITH 206 AND SHALL COMPLY WITH | | | CHAPTER 4. | | | 208.3.1 FBC[A] LOCATION. WHERE PARKING SERVES MORE THAN | | | ONE ACCESSIBLE ENTRANCE, PARKING SPACES COMPLYING WITH | | | 502 SHALL BE DISPERSED AND LOCATED ON THE SHORTEST | | | ACCESSIBLE ROUTE TO THE ACCESSIBLE ENTRANCES.IF THERE | | | ARE MULTIPLE ENTRANCES FOR MULTIPLE RETAIL STORES THE | | | PARKING SPACES MUST BE DISPERSED TO PROVIDE PARKING AT | | | THE NEAREST ACCESSIBLE ENTRANCE. IN PARKING FACILITIES | | | THAT DO NOT SERVE A PARTICULAR BUILDING OR FACILITY, | | | PARKING SPACES COMPLYING WITH 502 SHALL BE LOCATED ON | | | THE SHORTEST ACCESSIBLE ROUTE TO AN ACCESSIBLE | | | PEDESTRIAN ENTRANCE OF THE PARKING FACILITY. | | | -CURRENT PARKING DOES NOT MEET FBC[A] 208.2.3.1. | | | PLEASE PROVIDE REVISED PARKING AND SHOW ACCESSIBLE PATH | | | FROM EACH SPACE TO OCCUPANCY SERVED. EACH OCCUPANCY | | | SHOULD HAVE REQUIRED NUMBER SPACES AND ACCESSIBLE PATH | | | LEADING TO THEM. | | | | | | 35) 224.1.2 FBC[A] GUEST ROOM DOORS AND | | | DOORWAYS.ENTRANCES, DOORS, AND DOORWAYS PROVIDING USER | | | PASSAGE INTO AND WITHIN GUEST ROOMS THAT ARE NOT | | | REQUIRED TO PROVIDE MOBILITY FEATURES COMPLYING WITH | | | 806.2 SHALL COMPLY WITH 404.2.3. | | | A. 224.2, 224.3, 224.4, 224.5 AND 224.6.3 TRANSIENT | | | LODGING GUEST ROOMS. THIS IS ISN?T READY FOR REVIEW, SO | | | PLEASE LOOK AT ALL SECTIONS OF CODE. FOR INSTANCE, | | | GENERAL FLOOR PLAN A1.244 SHOWING FLOORS 12-16 DOESN?T | | | PROVIDE ENOUGH INFO THE SATISFY DISPERSION. THAT IS | | | WHERE A MATRIX WOULD HELP TO SEE THAT THE ROOMS ARE | | | BEING DISPERSED AND THAT ALL ROOMS ARE ACCOUNTED FOR. | | | B. ADD MATRIX TO SHOW COMPLIANCE WITH FBC [A] 224.2, | | | 224.3, 224.4, 224.5 AND 224.6.3 ACCORDING TO THE AMOUNT | | | OF ROOMS ON SHEET A0.102 THERE SHOULD BE 11 ROOMS WITH | | | MOBILITY FBC[A] 806.2, 17 ROOMS WITH COMMUNICATION | | | FBC[A]806.3 AND 10 ADDITIONAL ROOMS WITH SPECIAL | | | ACCESSIBLE FEATURES FBC[A] 806.4. AT LEAST ONE, BUT NO | | | MORE THAN 10% OF THE ROOMS TO COMPLY WITH MOBILITY CAN | | | ALSO BE USED TO COMPLY WITH COMMUNICATION FEATURES. | | | THAT WOULD MEAN THAT ONE ROOM CAN BE USED TO SATISFY | | | BOTH. | | | | | | 36) 401.2 FBC[CE] APPLICATION. COMMERCIAL BUILDINGS | | | SHALL COMPLY WITH ONE OF THE FOLLOWING: | | | 1. THE REQUIREMENTS OF ANSI/ASHRAE/IESNA 90.1, | | | EXCLUDING SECTION 9.4.1.1(G) OF THE STANDARD. | | | 2. THE REQUIREMENTS OF SECTIONS C402 THROUGH C405. IN | | | ADDITION, COMMERCIAL BUILDINGS SHALL COMPLY WITH | | | SECTION C406 AND TENANT SPACES SHALL COMPLY WITH | | | SECTION C406.1.1. | | | 3. THE REQUIREMENTS OF SECTIONS C402.5, C403.2, C404, | | | C405.2, C405.3, C405.5, C405.6 AND C407. THE BUILDING | | | ENERGY COST SHALL BE EQUAL TO OR LESS THAN 85 PERCENT | | | OF THE STANDARD REFERENCE DESIGN BUILDING. | | | | | | 37) 402.1 FBC[A] PROVIDE ACCESSIBLE ROUTE FROM PARKING | | | LOT. IN ADDITION TO ACCESSIBLE ENTRANCES REQUIRED BY | | | SECTIONS 1105.1.1 THROUGH 1105.1.7 (PARKING GARAGE | | | ENTRANCES, ENTRANCES FROM TUNNELS OR ELEVATED WALKWAYS, | | | RESTRICTED ENTRANCES, ENTRANCES FOR INMATES OR | | | DETAINEES, SERVICE ENTRANCES AND ENTRANCES TO TENANT | | | SPACES, DWELLING UNITS AND SLEEPING UNITS), AT LEAST 60 | | | PERCENT OF ALL PUBLIC ENTRANCES SHALL BE ACCESSIBLE. | | | SEE THE EXCEPTIONS FOR ENTRANCES TO AREAS NOT REQUIRED | | | TO BE ACCESSIBLE AND LOADING/SERVICE ENTRANCES THAT ARE | | | NOT THE ONLY TENANT SPACE ENTRANCE. | | | -PROVIDE DETAILS ON PLANS TO SHOW HOW DROP OFF AREAS | | | MEET FBC[A] 502 FOR PASSENGER LOADING ZONES AT HOTEL | | | AND RESIDENTIAL LOBBY. LENGTH, WIDTH AND MARKINGS. | | | | | | 38) 403.3.2 FBC[B] WATER SUPPLY TO REQUIRED FIRE PUMPS. | | | REQUIRED FIRE PUMPS SHALL BE SUPPLIED BY CONNECTIONS TO | | | NO FEWER THAN TWO WATER MAINS LOCATED IN DIFFERENT | | | STREETS. SEPARATE SUPPLY PIPING SHALL BE PROVIDED | | | BETWEEN EACH CONNECTION TO THE WATER MAIN AND THE | | | PUMPS. EACH CONNECTION AND THE SUPPLY PIPING BETWEEN | | | THE CONNECTION AND THE PUMPS SHALL BE SIZED TO SUPPLY | | | THE FLOW AND PRESSURE REQUIRED FOR THE PUMPS TO | | | OPERATE. | | | -IS THIS ACCOUNTED FOR ON CIVIL AND PLUMBING PLANS? | | | PLEASE STATE WHICH SHEETS. | | | | | | 39) 403.5.4 FBC[B] SMOKEPROOF ENCLOSURES. EVERY | | | REQUIRED EXIT STAIRWAY SERVING FLOORS MORE THAN 75 FEET | | | (22 860 MM) ABOVE THE LOWEST LEVEL OF FIRE DEPARTMENT | | | VEHICLE ACCESS SHALL BE A SMOKEPROOF ENCLOSURE IN | | | ACCORDANCE WITH SECTIONS 909.20 AND 1022.10. | | | | | | 40) 407.4.1 FBC[A] CAR DIMENSIONS. INSIDE DIMENSIONS OF | | | ELEVATOR CARS AND CLEAR WIDTH OF ELEVATOR DOORS SHALL | | | COMPLY WITH TABLE 407.4.1. | | | -PLEASE ADD CAB DIMENSIONS ON PLANS. | | | | | | 41) 704.9 FBC[B] IMPACT PROTECTION. WHERE THE FIRE | | | PROTECTIVE COVERING OF A STRUCTURAL MEMBER IS SUBJECT | | | TO IMPACT DAMAGE FROM MOVING VEHICLES, THE HANDLING OF | | | MERCHANDISE OR OTHER ACTIVITY, THE FIRE PROTECTIVE | | | COVERING SHALL BE PROTECTED BY CORNER GUARDS OR BY A | | | SUBSTANTIAL JACKET OF METAL OR OTHER NONCOMBUSTIBLE | | | MATERIAL TO A HEIGHT ADEQUATE TO PROVIDE FULL | | | PROTECTION, BUT NOT LESS THAN 5 FEET FROM THE FINISHED | | | FLOOR. EXCEPTION: CORNER PROTECTION IS NOT REQUIRED ON | | | CONCRETE COLUMNS IN OPEN OR ENCLOSED PARKING GARAGES. | | | -VERIFY IF COLUMNS IN PARKING GARAGE ARE SUBJECT TO | | | 704.9 IMPACT PROTECTION. | | | | | | 42) 803.1 GENERAL. PROVIDE INTERIOR FINISH SCHEDULES. | | | A. SUPPLY MORE DEVELOPED PLANS TO SHOW BUILT INS AND | | | FURNITURE LAYOUTS. | | | B. ADD FURNITURE PLAN TO ROOMS TO VERIFY ADA AND | | | EGRESS COMPLIANCE. | | | | | | 43) 806.1 FBC[B] GENERAL REQUIREMENTS. IN OCCUPANCIES | | | IN GROUPS A, E, I AND R-1 AND DORMITORIES IN GROUP R-2, | | | CURTAINS, DRAPERIES, HANGINGS AND OTHER DECORATIVE | | | MATERIALS SUSPENDED FROM WALLS OR CEILINGS SHALL MEET | | | THE FLAME PROPAGATION PERFORMANCE CRITERIA OF NFPA 701 | | | IN ACCORDANCE WITH SECTION 806.2 OR BE NONCOMBUSTIBLE. | | | -ADD TO DEFERRED SUBMITTAL LIST IF APPLICABLE. | | | | | | 44) 909.3 FBC[B] SPECIAL INSPECTION AND TEST | | | REQUIREMENTS. IN ADDITION TO THE ORDINARY INSPECTION | | | AND TEST REQUIREMENTS WHICH BUILDINGS, STRUCTURES AND | | | PARTS THEREOF ARE REQUIRED TO UNDERGO, SMOKE CONTROL | | | SYSTEMS SUBJECT TO THE PROVISIONS OF SECTION 909 SHALL | | | UNDERGO SPECIAL INSPECTIONS AND TESTS SUFFICIENT TO | | | VERIFY THE PROPER COMMISSIONING OF THE SMOKE CONTROL | | | DESIGN IN ITS FINAL INSTALLED CONDITION. THE DESIGN | | | SUBMISSION ACCOMPANYING THE CONSTRUCTION DOCUMENTS | | | SHALL CLEARLY DETAIL PROCEDURES AND METHODS TO BE USED | | | AND THE ITEMS SUBJECT TO SUCH INSPECTIONS AND TESTS. | | | SUCH COMMISSIONING SHALL BE IN ACCORDANCE WITH | | | GENERALLY ACCEPTED ENGINEERING PRACTICE AND, WHERE | | | POSSIBLE, BASED ON PUBLISHED STANDARDS FOR THE | | | PARTICULAR TESTING INVOLVED. | | | | | | 45) 909.4 FBC[B] ANALYSIS. A RATIONAL ANALYSIS | | | SUPPORTING THE TYPES OF SMOKE CONTROL SYSTEMS TO BE | | | EMPLOYED, THEIR METHODS OF OPERATION, THE SYSTEMS | | | SUPPORTING THEM AND THE METHODS OF CONSTRUCTION TO BE | | | UTILIZED SHALL ACCOMPANY THE SUBMITTED CONSTRUCTION | | | DOCUMENTS AND SHALL INCLUDE, BUT NOT BE LIMITED TO, THE | | | ITEMS INDICATED IN SECTIONS 909.4.1 THROUGH 909.4.6. | | | | | | 46) 909.20.5 FBC[B] STAIR PRESSURIZATION ALTERNATIVE. | | | WHERE THE BUILDING IS EQUIPPED THROUGHOUT WITH AN | | | AUTOMATIC SPRINKLER SYSTEM IN ACCORDANCE WITH SECTION | | | 903.3.1.1, THE VESTIBULE IS NOT REQUIRED, PROVIDED THAT | | | INTERIOR EXIT STAIRWAYS ARE PRESSURIZED TO A MINIMUM OF | | | 0.10 INCHES OF WATER (25 PA) AND A MAXIMUM OF 0.35 | | | INCHES OF WATER (87 PA) IN THE SHAFT RELATIVE TO THE | | | BUILDING MEASURED WITH ALL STAIRWAY DOORS CLOSED UNDER | | | MAXIMUM ANTICIPATED CONDITIONS OF STACK EFFECT AND WIND | | | EFFECT. | | | -PLEASE PROVIDE RATIONAL ANALYSIS FOR ALL SMOKE | | | CONTROL SYSTEMS STATING HOW HOISTWAYS AND STAIRWAYS | | | WILL MEET THE CODE REQUIREMENTS. | | | | | | 47) 1006.2.1 FBC TABLE[B] MAXIMUM COMMON PATH OF EGRESS | | | TRAVEL DISTANCE. | | | -ADD ROWS TO SHEET ALS1.100 TABLE A7.6 TO SHOW DATA | | | FOR R OCCUPANCIES. | | | | | | 48) 1006.2.1 FBC TABLE[B] HOW MANY EXITS ARE PROVIDED | | | ON RESIDENTIAL (R-2) FLOORS? LIFE SAFETY SHEETS APPEAR | | | TO USE ONE EXIT WITH ELEVATOR LOBBY CONNECTING TWO | | | SIDES. | | | -ADJUST LIFE SAFETY TO STATE HOW MANY EXITS ARE | | | REQUIRED, HOW MANY PROVIDED AND MARK EXIT SIGNS AND | | | EGRESS PATHS FOR THE REQUIRED NUMBER OF EXITS. | | | | | | 49) 1006.1 ILLUMINATION REQUIRED. THE MEANS OF EGRESS, | | | INCLUDING THE EXIT DISCHARGE, SHALL BE ILLUMINATED AT | | | ALL TIMES THE BUILDING SPACE SERVED BY THE MEANS OF | | | EGRESS IS OCCUPIED. | | | -SEE 1006.1 FOR EXCEPTIONS | | | | | | 50) 1006.3 EMERGENCY POWER FOR ILLUMINATION. THE POWER | | | SUPPLY FOR MEANS OF EGRESS ILLUMINATION SHALL NORMALLY | | | BE PROVIDED BY THE PREMISES? ELECTRICAL SUPPLY. IN THE | | | EVENT OF POWER SUPPLY FAILURE, AN EMERGENCY ELECTRICAL | | | SYSTEM SHALL AUTOMATICALLY ILLUMINATE ALL OF THE | | | FOLLOWING AREAS: (SEE 1006.3 FOR AREAS) | | | -PLEASE PROVIDE ELECTRICAL SHEET NUMBERS THAT SHOW THE | | | INFORMATION TO MEET 1006.1 AND 1006.3 | | | | | | 51) 1010.1.2.1 FBC[B] DIRECTION OF SWING. PIVOT OR | | | SIDE-HINGED SWINGING DOORS SHALL SWING IN THE DIRECTION | | | OF EGRESS TRAVEL WHERE SERVING A ROOM OR AREA | | | CONTAINING AN OCCUPANT LOAD OF 50 OR MORE PERSONS OR A | | | GROUP H OCCUPANCY. | | | A. SHEET A1.201 THE DOOR LEADING OUT OF STAIR 3 | | | BETWEEN 267 AND 262. IS THIS DOOR SUPPOSE TO SWING IN. | | | PLEASE VERIFY THE DIRECTION OF EGRESS AND IT ALSO NEEDS | | | A DOOR NUMBER. | | | B. SHEET A1.202 THE DOOR LEADING OUT OF STAIR 4 | | | LABELED 267 . IS THIS DOOR SUPPOSE TO SWING IN. PLEASE | | | VERIFY THE DIRECTION OF EGRESS AND IS IT SUPPOSED TO | | | HAVE THE SAME DOOR NUMBER AS A DOOR IN STAIR 3? | | | C. SHEET A1.204 THE DOOR LEADING OUT OF STAIR 2 | | | LABELED 262 SWINGS OUT INTO CORRIDOR 01-40. THEN EGRESS | | | CONTINUES OUT TO DOOR 291 WHICH IN TURN SWINGS IN. | | | PLEASE REVIEW DIRECTION OF EGRESS. ALSO, DOORS IN A | | | SERIES WOULD NEED 48 INCHES BETWEEN THEM FROM OPEN | | | POSITION (FBC ACCESSIBILITY 404.2.6) | | | | | | 52) 1013.2 FBC[B] FLOOR-LEVEL EXIT SIGNS IN GROUP R-1. | | | WHERE EXIT SIGNS ARE REQUIRED IN GROUP R-1 OCCUPANCIES | | | BY SECTION 1013.1, ADDITIONAL LOW-LEVEL EXIT SIGNS | | | SHALL BE PROVIDED IN ALL AREAS SERVING GUEST ROOMS IN | | | GROUP R-1 OCCUPANCIES AND SHALL COMPLY WITH SECTION | | | 1013.5. | | | -ADD FLOOR-LEVEL SIGNS TO LIFE SAFTEY PLANS FOR HOTEL | | | FLOORS WITH R-1 UNITS (LEVELS 9-16) | | | | | | 53) 1014.6 FBC[B] HANDRAIL EXTENSIONS. HANDRAILS SHALL | | | RETURN TO A WALL, GUARD OR THE WALKING SURFACE OR SHALL | | | BE CONTINUOUS TO THE HANDRAIL OF AN ADJACENT FLIGHT OF | | | STAIRS OR RAMP RUN. WHERE HANDRAILS ARE NOT CONTINUOUS | | | BETWEEN FLIGHTS, THE HANDRAILS SHALL EXTEND | | | HORIZONTALLY NOT LESS THAN 12 INCHES BEYOND THE TOP | | | RISER AND CONTINUE TO SLOPE FOR THE DEPTH OF ONE TREAD | | | BEYOND THE BOTTOM RISER. AT RAMPS WHERE HANDRAILS ARE | | | NOT CONTINUOUS BETWEEN RUNS, THE HANDRAILS SHALL EXTEND | | | HORIZONTALLY ABOVE THE LANDING 12 INCHES MINIMUM BEYOND | | | THE TOP AND BOTTOM OF RAMP RUNS. THE EXTENSIONS OF | | | HANDRAILS SHALL BE IN THE SAME DIRECTION OF THE FLIGHTS | | | OF STAIRS AT STAIRWAYS AND THE RAMP RUNS AT RAMPS. | | | -DETAIL 1/A5.121 AND 1/A5.122 SHOW HOW RAILING | | | EXTENSIONS WORK. ALL STAIR SECTIONSA5.101 TO A5.118 | | | SHOW 12 INCH HORIZONTAL PROJECTION FROM FIRST TREAD | | | HEIGHT. PLEASE HAVE DETAIL AND SECTION MATCH SO WE CAN | | | SEE HOW THIS AFFECTS WHERE BOTTOM HANDRAILS MEET DOOR | | | FRAMES. | | | | | | 54) 1015.6 DAY CARE MEANS OF EGRESS. DAY CARE | | | FACILITIES, ROOMS OR SPACES WHERE CARE IS PROVIDED FOR | | | MORE THAN 10 CHILDREN THAT ARE 2 1/2 YEARS OF AGE OR | | | LESS, SHALL HAVE ACCESS TO NOT LESS THAN TWO EXITS OR | | | EXIT ACCESS DOORWAYS. | | | -DAYCARE 2 EXITS NEEDED? PLEASE STATE THE AGE AND | | | AMOUNT OF CHILDREN ANTICIPATED AT THE DAYCARE. | | | | | | 55) 1022.5 PENETRATIONS. PENETRATIONS INTO AND OPENINGS | | | THROUGH INTERIOR EXIT STAIRWAYS AND RAMPS ARE | | | PROHIBITED EXCEPT FOR REQUIRED EXIT DOORS, EQUIPMENT | | | AND DUCTWORK NECESSARY FOR INDEPENDENT VENTILATION OR | | | PRESSURIZATION, SPRINKLER PIPING, STANDPIPES, | | | ELECTRICAL RACEWAY FOR FIRE DEPARTMENT COMMUNICATION | | | SYSTEMS AND ELECTRICAL RACEWAY SERVING THE INTERIOR | | | EXIT STAIRWAY AND RAMP AND TERMINATING AT A STEEL BOX | | | NOT EXCEEDING 16 SQUARE INCHES (0.010 M2). SUCH | | | PENETRATIONS SHALL BE PROTECTED IN ACCORDANCE WITH | | | SECTION 714. THERE SHALL BE NO PENETRATIONS OR | | | COMMUNICATING OPENINGS, WHETHER PROTECTED OR NOT, | | | BETWEEN ADJACENT INTERIOR EXIT STAIRWAYS AND RAMPS. | | | -HVAC COMMON FEEDING STAIRS FROM MAIN (SEE STAIRS AT | | | VAV-2)-INDEPENDENT SYSTEMS TO FEED STAIRWAYS? PLEASE | | | REVIEW PENETRATIONS INTO INTERIOR STAIRWAYS AND PROVIDE | | | INDEPENDENT SYSTEMS AS REQUIRED IN 1022.5. | | | | | | 56) 1022.8 FBC[B] DISCHARGE IDENTIFICATION. AN INTERIOR | | | EXIT STAIRWAY AND RAMP SHALL NOT CONTINUE BELOW ITS | | | LEVEL OF EXIT DISCHARGE UNLESS AN APPROVED BARRIER IS | | | PROVIDED AT THE LEVEL OF EXIT DISCHARGE TO PREVENT | | | PERSONS FROM UNINTENTIONALLY CONTINUING INTO LEVELS | | | BELOW. DIRECTIONAL EXIT SIGNS SHALL BE PROVIDED AS | | | SPECIFIED IN SECTION 1011. | | | A. IF STAIRWAY 4 AT 2 ND LEVEL TRANSFERS TO STAIRWAY | | | 11 THAN 1022.8 APPLIES. | | | B. REVIEW EGRESS PATH TO STAIR 11. DOUBLE DOORS | | | SWINGING INTO PATH AND WIDTH OF 90 DEGREE TURN. | | | | | | 57) 1022.9 FBC[B] SIGNAGE. GENERAL COMMENT. | | | A. 1022.9 FBC[B] STAIRWAY IDENTIFICATION SIGNS. | | | B. 1022.9.1 FBC[B] SIGNAGE REQUIREMENTS. | | | | | | 58) 1022.10.2 FBC[B] ENCLOSURE ACCESS. ACCESS TO THE | | | STAIRWAY WITHIN A SMOKEPROOF ENCLOSURE SHALL BE BY WAY | | | OF A VESTIBULE OR AN OPEN EXTERIOR BALCONY. | | | EXCEPTION: FBC[B] ACCESS IS NOT REQUIRED BY WAY OF A | | | VESTIBULE OR EXTERIOR BALCONY FOR STAIRWAYS USING THE | | | PRESSURIZATION ALTERNATIVE COMPLYING WITH SECTION | | | 909.20.5. | | | | | | 59) 1022.10 FBC[B] SMOKEPROOF ENCLOSURES AND | | | PRESSURIZED STAIRWAYS AND RAMPS. WHERE REQUIRED BY | | | SECTION 403.5.4 OR 405.7.2, INTERIOR EXIT STAIRWAYS AND | | | RAMPS SHALL BE SMOKEPROOF ENCLOSURES OR PRESSURIZED | | | STAIRWAYS OR RAMPS IN ACCORDANCE WITH SECTION 909.20. | | | 1022.10.1 FBC[B] TERMINATION AND EXTENSION. A | | | SMOKEPROOF ENCLOSURE OR PRESSURIZED STAIRWAY SHALL | | | TERMINATE AT AN EXIT DISCHARGE OR A PUBLIC WAY. THE | | | SMOKEPROOF ENCLOSURE OR PRESSURIZED STAIRWAY SHALL BE | | | PERMITTED TO BE EXTENDED BY AN EXIT PASSAGEWAY IN | | | ACCORDANCE WITH SECTION 1022.3. THE EXIT PASSAGEWAY | | | SHALL BE WITHOUT OPENINGS OTHER THAN THE FIRE DOOR | | | ASSEMBLY REQUIRED BY SECTION 1022.3.1 AND THOSE | | | NECESSARY FOR EGRESS FROM THE EXIT PASSAGEWAY. THE EXIT | | | PASSAGEWAY SHALL BE SEPARATED FROM THE REMAINDER OF THE | | | BUILDING BY 2-HOUR FIRE BARRIERS CONSTRUCTED IN | | | ACCORDANCE WITH SECTION 707 OR HORIZONTAL ASSEMBLIES | | | CONSTRUCTED IN ACCORDANCE WITH SECTION 711, OR BOTH. | | | -SEE 1022.10.1 FOR EXCEPTIONS | | | | | | 60) 1024.1 FBC[B] GENERAL. APPROVED LUMINOUS EGRESS | | | PATH MARKINGS DELINEATING THE EXIT PATH SHALL BE | | | PROVIDED IN HIGH-RISE BUILDINGS OF GROUP A, B, E, I, M, | | | AND R-1 OCCUPANCIES IN ACCORDANCE WITH SECTIONS 1024.1 | | | THROUGH 1024.5. | | | EXCEPTION: LUMINOUS EGRESS PATH MARKINGS SHALL NOT BE | | | REQUIRED ON THE LEVEL OF EXIT DISCHARGE IN LOBBIES THAT | | | SERVE AS PART OF THE EXIT PATH IN ACCORDANCE WITH | | | SECTION 1027.1, EXCEPTION 1 | | | | | | 61) 1024.2 FBC[B] MARKINGS WITHIN EXIT COMPONENTS. | | | EGRESS PATH MARKINGS SHALL BE PROVIDED IN INTERIOR EXIT | | | STAIRWAYS, INTERIOR EXIT RAMPS AND EXIT PASSAGEWAYS, IN | | | ACCORDANCE WITH SECTIONS 1024.2.1 THROUGH 1024.2.6. | | | -ADD DETAILS TO SHOW COMPLIANCE WITH 1024.2.1 THROUGH | | | 1024.2.6 | | | | | | 62) 1207 FBC[B] PROVIDE FLOORING SUBMITTAL FOR SOUND | | | CONTROL, OR ADD TO THE DEFERRED SUBMITTAL LIST. | | | -PLEASE ADVISE, WHAT FLOORING AND UNDERLAYMENT ARE | | | PROPOSED? PLEASE ADVISE VIA EMAIL. IF THE UNDERLAYMENT | | | PRODUCT PROPOSED IS NOT ONE FOR WHICH WE HAVE TEST | | | REPORTS ON FILE, THE FOLLOWING REPORTS ARE REQUIRED: | | | 1207.2 FBC[B] AIR-BORNE SOUND. WALLS, PARTITIONS AND | | | FLOOR/CEILING ASSEMBLIES SEPARATING DWELLING UNITS FROM | | | EACH OTHER OR FROM PUBLIC OR SERVICE AREAS SHALL HAVE A | | | SOUND TRANSMISSION CLASS (STC) OF NOT LESS THAN 50 (45 | | | IF FIELD TESTED) FOR AIR-BORNE NOISE WHEN TESTED IN | | | ACCORDANCE WITH ASTM E 90. PENETRATIONS OR OPENINGS IN | | | CONSTRUCTION ASSEMBLIES FOR PIPING; ELECTRICAL DEVICES; | | | RECESSED CABINETS; BATHTUBS; SOFFITS; OR HEATING, | | | VENTILATING OR EXHAUST DUCTS SHALL BE SEALED, LINED, | | | INSULATED OR OTHERWISE TREATED TO MAINTAIN THE REQUIRED | | | RATINGS. THIS REQUIREMENT SHALL NOT APPLY TO DWELLING | | | UNIT ENTRANCE DOORS; HOWEVER, SUCH DOORS SHALL BE TIGHT | | | FITTING TO THE FRAME AND SILL. | | | 1207.3 FBC[B] STRUCTURE-BORNE SOUND. FLOOR/CEILING | | | ASSEMBLIES BETWEEN DWELLING UNITS OR BETWEEN A DWELLING | | | UNIT AND A PUBLIC OR SERVICE AREA WITHIN THE STRUCTURE | | | SHALL HAVE AN IMPACT INSULATION CLASS (IIC) RATING OF | | | NOT LESS THAN 50 (45 IF FIELD TESTED) WHEN TESTED IN | | | ACCORDANCE WITH ASTM E 492. | | | FBC 603.1, ALLOWABLE MATERIALS IN NON COMBUSTIBLE | | | BUILDINGS, SEE ITEM 2, EXCEPTION 2, ACOUSTICAL | | | INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID | | | DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED | | | TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200. SEE | | | 803.1.1, PROVIDE TEST DATA IN ACCORDANCE WITH ASTM E 84 | | | OR UL 723. | | | -MANUFACTURER SPEC SHEETS ARE NOT ACCEPTABLE DUE TO | | | DISCREPANCIES BETWEEN SPEC SHEETS/BROCHURES AND TEST | | | REPORTS FOR SOME MANUFACTURERS (NOT NECESSARILY THE | | | MANUFACTURER SELECTED; THIS IS A GENERAL COMMENT) | | | | | | 63) 1012.9 FBC[B] INTERMEDIATE HANDRAILS. STAIRWAYS | | | SHALL HAVE INTERMEDIATE HANDRAILS LOCATED IN SUCH A | | | MANNER THAT ALL PORTIONS OF THE STAIRWAY MINIMUM WIDTH | | | OR REQUIRED CAPACITY ARE WITHIN 30 INCHES (762 MM) OF A | | | HANDRAIL. ON MONUMENTAL STAIRS, HANDRAILS SHALL BE | | | LOCATED ALONG THE MOST DIRECT PATH OF EGRESS TRAVEL. | | | -CHECK COMPLIANCE WITH 1012.9 AT BALLROOM STEPS. | | | | | | 64) 1210.2 FBC[B] FINISH MATERIALS. WALLS, FLOORS AND | | | PARTITIONS IN TOILET AND BATHROOMS SHALL COMPLY WITH | | | SECTIONS 1210.2.1 THROUGH 1210.2.4. | | | | | | 65) 1210.2.1 FBC[B] FLOORS AND WALL BASES. IN OTHER | | | THAN DWELLING UNITS, TOILET, BATHING AND SHOWER ROOM | | | FLOOR FINISH MATERIALS SHALL HAVE A SMOOTH, HARD, | | | NONABSORBENT SURFACE. THE INTERSECTIONS OF SUCH FLOORS | | | WITH WALLS SHALL HAVE A SMOOTH, HARD, NONABSORBENT | | | VERTICAL BASE THAT EXTENDS UPWARD ONTO THE WALLS NOT | | | LESS THAN 4 INCHES (102 MM). | | | | | | 66) 1210.2.2 FBC[B] WALLS AND PARTITIONS. WALLS AND | | | PARTITIONS WITHIN 2 FEET (610 MM) OF SERVICE SINKS, | | | URINALS AND WATER CLOSETS SHALL HAVE A SMOOTH, HARD, | | | NONABSORBENT SURFACE, TO A HEIGHT OF NOT LESS THAN 4 | | | FEET (1219 MM) ABOVE THE FLOOR, AND EXCEPT FOR | | | STRUCTURAL ELEMENTS, THE MATERIALS USED IN SUCH WALLS | | | SHALL BE OF A TYPE THAT IS NOT ADVERSELY AFFECTED BY | | | MOISTURE. EXCEPTION: THIS SECTION DOES NOT APPLY TO THE | | | FOLLOWING BUILDINGS AND SPACES: SEE 1210.2.2 FOR | | | EXCEPTIONS. | | | | | | 67) 3006.3 FBC[B] HOISTWAY OPENING PROTECTION. WHERE | | | SECTION 3006.2 REQUIRES PROTECTION OF THE ELEVATOR | | | HOISTWAY DOOR OPENING, THE PROTECTION SHALL BE PROVIDED | | | BY ONE OF THE FOLLOWING: | | | -(SEE OPTIONS 1-4 FROM FBC 3007.6.4) HOW IS PROTECTION | | | PROVIDED FOR ELEVATORS 8, 9 AND 10? ALSO, P-15, P-16, | | | P-06 AND P-07 | | | | | | 68) 3001 FBC[B] PROVIDE DETAILS OF FREIGHT ELEVATOR. | | | A. TYPE OF ELEVATOR AND REFERRENCED STANDARDS. | | | B. HOW IS MACHINE ROOM ACCESSED? | | | | | | 69) 3006.3 FBC[B] PRESSURIZATION. THE ELEVATOR MACHINE | | | ROOM, CONTROL ROOMS OR CONTROL SPACE WITH OPENINGS INTO | | | A PRESSURIZED ELEVATOR HOISTWAY SHALL BE PRESSURIZED | | | UPON ACTIVATION OF A HEAT OR SMOKE DETECTOR LOCATED IN | | | THE ELEVATOR MACHINE ROOM, CONTROL ROOM OR CONTROL | | | SPACE. | | | -PROVIDE PRESSURIZATION ANALYSIS. | | | | | | 70) 3005.1 FBC[B] ACCESS. AN APPROVED MEANS OF ACCESS | | | SHALL BE PROVIDED TO ELEVATOR MACHINE ROOMS, CONTROL | | | ROOMS, CONTROL SPACES AND MACHINERY SPACES. | | | -HOW ARE MACHINE ROOMS ACCESSED FOR P-06, P-07, P-16, | | | P-17 AND FREIGHT ELEVATORS? | | | | | | 71) 3005.3 FBC[B] PRESSURIZATION. THE ELEVATOR MACHINE | | | ROOM, CONTROL ROOMS OR CONTROL SPACE WITH OPENINGS INTO | | | A PRESSURIZED ELEVATOR HOISTWAY SHALL BE PRESSURIZED | | | UPON ACTIVATION OF A HEAT OR SMOKE DETECTOR LOCATED IN | | | THE ELEVATOR MACHINE ROOM, CONTROL ROOM OR CONTROL | | | SPACE. | | | | | | 72) 3006 FBC[B] GENERAL COMMENT. THIS COMMENT APPLIES | | | TO ALL OTHER ELEVATOR DRAWINGS. AT THIS STAGE THEY MAY | | | LACK COMPLETION, SO FURTHER REVIEW WILL BE REQUIRED | | | UPON RESUBMITTAL. | | | -ELEVATORS P-06 AND 07. HOW DO YOU ACCESS MACHINE | | | ROOMS? | | | | | | 73) 3306.1 FBC[B] PROTECTION REQUIRED. PEDESTRIANS | | | SHALL BE PROTECTED DURING CONSTRUCTION, REMODELING AND | | | DEMOLITION ACTIVITIES AS REQUIRED BY THIS CHAPTER AND | | | TABLE 3306.1. SIGNS SHALL BE PROVIDED TO DIRECT | | | PEDESTRIAN TRAFFIC. | | | -AS THE BUILDING CONSTRUCTION INCREASES THE SIDEWALK | | | PROTECTION WILL NEED TO MEET REQUIREMENTS BELOW. | | | -SEE 3306.1 TO 3306.9 FOR REQUIREMENTS TO PROVIDE | | | WALKWAYS, BARRIERS AND COVERED WALKWAYS. | | | | | | 74) 3007.7.4 FBC[B] LOBBY SIZE. EACH ENCLOSED FIRE | | | SERVICE ACCESS ELEVATOR LOBBY SHALL BE NOT LESS THAN | | | 150 SQUARE FEET (14 M2) IN AN AREA WITH A MINIMUM | | | DIMENSION OF 8 FEET (2440 MM). | | | -ALS1.114 FIRE LOBBY ON FLOORS 12-30 IS UNDERSIZED. | | | CORRIDOR 01-40 ON ALS1.101. GROUND LEVEL FIRE SERVICE | | | AND FREIGHT ARE SHOWING ELEVATOR LOBBIES. THIS ARE NOT | | | REQUIRED AT EXIT LEVEL AND THE FIRE SERVICE WOULD NOT | | | PROVIDE 150 SQ. FT. PLEASE REVIEW THIS AND COORDINATE | | | IF FREIGHT IS PRESSURIZED, OR IF LOBBY REQUIRED AT | | | LEVEL 7. | | | | | | 75) 3007.7.1 ACCESS. DOOR CONFIGURATION TWO 90 SWINGING | | | INTO EXIT STAIR FROM FIRE SERVICE LOBBY. | | | -EXIT DOOR FROM FIRE LOBBY WOULD BLOCK EXIT DOOR FROM | | | CORRIDOR. PLEASE REVIEW CONFIGURATION AND POSSIBLE. CAN | | | SWING FROM FIRE LOBBY BE CHANGED BASED ON 1010.1.2.1 | | | FBC[B] DIRECTION OF SWING? | | | | | | 76) 3007.7.4 FBC[B] LOBBY SIZE. REGARDLESS OF THE | | | NUMBER OF FIRE SERVICE ACCESS ELEVATORS SERVED BY THE | | | SAME ELEVATOR LOBBY, THE ENCLOSED FIRE SERVICE ACCESS | | | ELEVATOR LOBBY SHALL BE NOT LESS THAN 150 SQUARE FEET | | | (14 M2) IN AN AREA WITH A DIMENSION OF NOT LESS THAN 8 | | | FEET (2440 MM). | | | A. FIRE LOBBIES THAT SERVE RESIDENTIAL FIRE SERVICE | | | ACCESS ELEVATORS DO NOT MEET THE MINIMUM SIZE REQUIRED | | | IN 3007.7.4. PLEASE REVIEW AND ADJUST ACCORDINGLY. | | | B. FIRE LOBBY S1 AT EXIT LEVEL IS UNDER SIZED AND FIRE | | | LOBBY ISN'T REQUIRED ON EXIT LEVEL. PLEASE REVIEW AND | | | ADJUST. | | | PLEASE REVIEW TO MEET 3007.7.4 | | | | | | 77) 3006.2 FBC[B] HOISTWAY OPENING PROTECTION REQUIRED | | | . PROTECTION OF ELEVATOR HOISTWAY DOOR OPENINGS IS NOT | | | REQUIRED AT THE LEVEL(S) OF EXIT DISCHARGE, PROVIDED | | | THE LEVEL(S) OF EXIT DISCHARGE IS EQUIPPED WITH AN | | | AUTOMATIC SPRINKLER SYSTEM IN ACCORDANCE WITH SECTION | | | 903.3.1.1. | | | | | | 78) 3007.6.2 LOBBY ENCLOSURE. THE FIRE SERVICE ACCESS | | | ELEVATOR LOBBY SHALL BE ENCLOSED WITH A SMOKE BARRIER | | | HAVING A FIRE-RESISTANCE RATING OF NOT LESS THAN 1 | | | HOUR, EXCEPT THAT LOBBY DOORWAYS SHALL COMPLY WITH | | | SECTION 3007.6.3. EXCEPTION: ENCLOSED FIRE SERVICE | | | ACCESS ELEVATOR LOBBIES ARE NOT REQUIRED AT THE LEVELS | | | OF EXIT DISCHARGE. | | | | | | NOTES: | | | | | | -PLEASE PROVIDE COMMENT RESPONSE SHEET TO EXPLAIN HOW | | | EACH COMMENT IS BEING ADDRESSED. | | | | | | -COMMENTS ARE A BRIEF OVERVIEW OF CODE SECTIONS. | | | FURTHER REVIEW OF THE REFERENCED CODE SECTIONS WILL BE | | | REQUIRED. | | | | | | -ADDITIONAL COMMENTS MAY BE FORTHCOMING PENDING REVIEW | | | OF MATERIALS REQUESTED. | | | | | | PLEASE FEEL FREE TO CONTACT ME AT 561-805-6718 (M-F | | | 8-5) TO DISCUSS COMMENTS, OR E-MAIL ANYTIME | | | [email protected] | | | | | | | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
5 |
Status |
P |
Date |
2021-06-14 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2021-06-14 |
Time |
14:16 |
Rev Time |
0.00 |
| Received By |
jleahy |
Date |
2021-06-04 |
Time |
16:03 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
4 |
Status |
F |
Date |
2021-01-27 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2021-01-27 |
Time |
08:34 |
Rev Time |
0.00 |
| Received By |
jleahy |
Date |
2021-01-11 |
Time |
08:33 |
Sent To |
|
|
| Notes |
| 2021-01-27 08:36:20 | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | | | FLORIDA BUILDING CODE 2017 6TH EDITION | | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED | | | NFPA 70 2014 EDITION | | | | | | JAKE LEAHY BN, BU, PX | | | ELECTRICAL PLANS EXAMINER II | | | 561-805-6713 | | | [email protected] | | | | | | PAGE E.502A | | | 1) NO SIZES OF CONDUCTORS FROM THE PANELS TO THE | | | TRANSFORMERS AND THEN AGAIN ON THE SECONDARY SIDE. | | | | | | 2) GROUNDING SHOWN AT TRANSFORMERS PLEASE INDICATE WHAT | | | THEY ARE TO TIE INTO FOR GROUNDING. | | | | | | 3) FEEDERS TO THE FOLLOWING SHOW NOT SIZES AS WELL | | | N2A1, SWB3, SWBC, SWBH4, SWBH1, SWBH3, KITCHEN PANEL, | | | POOL PANEL, HOTEL POOL PANEL, GYM PANEL, AND N4H8B. | | | | | | PAGE E.502B | | | 1) NO SIZES OF CONDUCTORS FROM THE PANELS TO THE | | | TRANSFORMERS AND THEN AGAIN ON THE SECONDARY SIDE. | | | | | | 2) NO FEEDER SIZES TO CH, CWH | | | | | | PAGE E503 | | | 1) GENERATOR 1 HAS 800A FEEDER WITH OVERCURRENT | | | PROTECTION GOING TO FIRE PUMP, BUT IT HAS A 1600A | | | FEEDER WITH NO OVER CURRENT PROTECTION AT THE GENERATOR | | | WHAT SECTION ALLOWS THIS AND IF IT DOES THE CONDUCTORS | | | WILL HAVE TO BE 115% PER 445.13 | | | | | | 2) PANEL DQ4H5 SHOWS NO OVERCURRENT PROTECTION SIZES | | | AND APPEARS TO HAVE 3 SPARES? | | | | | | 3) PANEL DE4H5 SAME AS ABOVE | | | | | | 4) PANEL DQ4HRB NO WIRE SIZES FROM PANEL TO TRANSFORMER | | | AND THEN AGAIN ON THE SECONDARY SIDE OF THE | | | TRANSFORMER. | | | | | | PAGE E504 | | | 1) WIRE SIZES FROM PANELS TO TRANSFORMER AND THEN AGAIN | | | ON THE SECONDARY SIDE. | | | | | | 2) SWBNRR NO SIZES ON OVERCURRENT PROTECTION 5 SPARES? | | | | | | 3) DN4PR1 NO OVERCURRENT SIZES ON BREAKERS. | | | | | | | | | PAGE E505 | | | 1) PANELS DQ4RRA, DE4RR, AND DQ4RRB HAVE NO OVERCURRENT | | | PROTECTION SHOWN ON BREAKERS AND IF THERE ARE SPARES. | | | | | | 2) WIRE SIZES FROM PANELS TO TRANSFORMERS AND ON THE | | | SECONDARY SIDE ARE NOT SHOWN. | | | | | | PLANS ARE GENERALY GOOD PLANS BUT THE RISER HAS YOU | | | LOOKING IN SEVERAL PLACES TO COME UP WITH THE SIZES OF | | | CONDUCTORS AND OVERCURRENT PROTECTION ON PRIMARIES AND | | | SECONDARIES OF THE TRANSFORMERS. IT WOULD BE A BENEFIT | | | TO HAVE THE WIRE SIZES AND OVERCURRENT PROTECTION ON | | | THE RISER MAYBE WITH A TABLE SHOWING THE WIRES AND | | | OCPS. | | | | | | SMOKE ALARMS IN RESIDENTIAL UNITS NEEDS TO BE LOOKED AT | | | IN REFERENCE TO LOCATIONS OF THE SMOKE ALARMS OR | | | DETECTORS. NFPA 72 GIVES LOCATIONS FOR SMOKE ALARMS | | | NEAR BATHROOM DOORS AND COOKING APPLIANCES THAT SEEMED | | | TO HAVE BEEN OVERLOOKED. SEE NFPA 72 SECTIONS | | | 29.8.3.4(4), AND (6) FOR COOKING APPLIABCES AND | | | BATHROOM LOCATIONS. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
F |
Date |
2021-01-27 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2021-01-27 |
Time |
07:37 |
Rev Time |
0.00 |
| Received By |
jleahy |
Date |
2021-01-11 |
Time |
16:40 |
Sent To |
|
|
| Notes |
| 2021-02-03 07:39:15 | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | | | FLORIDA BUILDING CODE 2017 6TH EDITION | | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED | | | NFPA 70 2014 EDITION | | | | | | JAKE LEAHY BN, BU, PX | | | ELECTRICAL PLANS EXAMINER II | | | 561-805-6713 | | | [email protected] | | | | | | PAGE E.502A | | | 1) NO SIZES OF CONDUCTORS FROM THE PANELS TO THE | | | TRANSFORMERS AND THEN AGAIN ON THE SECONDARY SIDE. | | | | | | 2) GROUNDING SHOWN AT TRANSFORMERS PLEASE INDICATE WHAT | | | THEY ARE TO TIE INTO FOR GROUNDING. | | | | | | 3) FEEDERS TO THE FOLLOWING SHOW NOT SIZES AS WELL | | | N2A1, SWB3, SWBC, SWBH4, SWBH1, SWBH3, KITCHEN PANEL, | | | POOL PANEL, HOTEL POOL PANEL, GYM PANEL, AND N4H8B. | | | | | | PAGE E.502B | | | 1) NO SIZES OF CONDUCTORS FROM THE PANELS TO THE | | | TRANSFORMERS AND THEN AGAIN ON THE SECONDARY SIDE. | | | | | | 2) NO FEEDER SIZES TO CH, CWH | | | | | | PAGE E503 | | | 1) GENERATOR 1 HAS 800A FEEDER WITH OVERCURRENT | | | PROTECTION GOING TO FIRE PUMP, BUT IT HAS A 1600A | | | FEEDER WITH NO OVER CURRENT PROTECTION AT THE GENERATOR | | | WHAT SECTION ALLOWS THIS AND IF IT DOES THE CONDUCTORS | | | WILL HAVE TO BE 115% PER 445.13 | | | | | | 2) PANEL DQ4H5 SHOWS NO OVERCURRENT PROTECTION SIZES | | | AND APPEARS TO HAVE 3 SPARES? | | | | | | 3) PANEL DE4H5 SAME AS ABOVE | | | | | | 4) PANEL DQ4HRB NO WIRE SIZES FROM PANEL TO TRANSFORMER | | | AND THEN AGAIN ON THE SECONDARY SIDE OF THE | | | TRANSFORMER. | | | | | | PAGE E504 | | | 1) WIRE SIZES FROM PANELS TO TRANSFORMER AND THEN AGAIN | | | ON THE SECONDARY SIDE. | | | | | | 2) SWBNRR NO SIZES ON OVERCURRENT PROTECTION 5 SPARES? | | | | | | 3) DN4PR1 NO OVERCURRENT SIZES ON BREAKERS. | | | | | | | | | PAGE E505 | | | 1) PANELS DQ4RRA, DE4RR, AND DQ4RRB HAVE NO OVERCURRENT | | | PROTECTION SHOWN ON BREAKERS AND IF THERE ARE SPARES. | | | | | | 2) WIRE SIZES FROM PANELS TO TRANSFORMERS AND ON THE | | | SECONDARY SIDE ARE NOT SHOWN. | | | | | | PLANS ARE GENERALY GOOD PLANS BUT THE RISER HAS YOU | | | LOOKING IN SEVERAL PLACES TO COME UP WITH THE SIZES OF | | | CONDUCTORS AND OVERCURRENT PROTECTION ON PRIMARIES AND | | | SECONDARIES OF THE TRANSFORMERS. IT WOULD BE A BENEFIT | | | TO HAVE THE WIRE SIZES AND OVERCURRENT PROTECTION ON | | | THE RISER MAYBE WITH A TABLE SHOWING THE WIRES AND | | | OCPS. | | | | | | SMOKE ALARMS IN RESIDENTIAL UNITS NEEDS TO BE LOOKED AT | | | IN REFERENCE TO LOCATIONS OF THE SMOKE ALARMS OR | | | DETECTORS. NFPA 72 GIVES LOCATIONS FOR SMOKE ALARMS | | | NEAR BATHROOM DOORS AND COOKING APPLIANCES THAT SEEMED | | | TO HAVE BEEN OVERLOOKED. SEE NFPA 72 SECTIONS | | | 29.8.3.4(4), AND (6) FOR COOKING APPLIABCES AND | | | BATHROOM LOCATIONS. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
F |
Date |
2020-03-04 |
|
|
Cont ID |
|
| Sent By |
jpearson |
Date |
2020-03-04 |
Time |
15:48 |
Rev Time |
0.00 |
| Received By |
jpearson |
Date |
2020-03-01 |
Time |
15:09 |
Sent To |
|
|
| Notes |
| 2020-03-04 11:09:38 | CODES IN EFFECT: | | | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION | | | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 | | | 6TH ED, CHAPTER 1. | | | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 | | | 6TH EDITION | | | FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017 | | | 6TH EDITION | | | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION | | | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE | | | FS = FLORIDA STATUTES | | | | | | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | | | PREVIOUS COMMENTS THAT HAVE BEEN ADDRESSED | | | SATISFACTORILY ARE MARKED AS CORRECTED. PREVIOUS | | | COMMENTS THAT HAVE NOT BEEN ADDRESSED SATISFACTORILY | | | HAVE ADDITIONAL COMMENTS IN PARENTHESES. ANY NEW | | | COMMENTS WILL BE LISTED AFTER PREVIOUS COMMENTS. | | | | | | 1. CORRECTED. | | | 2. CORRECTED. | | | 3. CORRECTED. | | | 4. CORRECTED. | | | 5. CORRECTED. | | | 6. CORRECTED. | | | 7. CORRECTED. | | | 8. CORRECTED. | | | 9. CORRECTED. | | | 10. CORRECTED. | | | 11. CORRECTED. | | | 12. CORRECTED. | | | 13. CORRECTED. | | | 14. CORRECTED. | | | 15. CORRECTED. | | | 16. CORRECTED. | | | 17. CORRECTED. | | | 18. SHEETS E.506 AND E.803, SPECIFY WIRES SIZES FOR | | | GROUNDING SYSTEM TO CONFIRM CODE COMPLIANCE. NEC 250; | | | WPB FBC 107.2.1 (THESE SHEETS SEEM TO BE A AN EXACT | | | DUPLICATE, WHY ARE BOTH SHEETS NEEDED? SHEET E.506 IS | | | NOT SHOWN IN THE LEGEND OF SHEETS ON E.603. ALSO, THE | | | MAIN BONDING JUMPER SHOULD BE SIZED AT 12.5% OF TOTAL | | | FEEDER SIZE WHEN USING PARALLEL FEEDS. PROVIDE | | | CORRECTION. NEC 250.102(C)(1)) | | | 19. PROVIDE ACCURATE LOAD CALCULATION FOR ALL SERVICES. | | | NEC 220; WPB FBC 107.2.1 (LOAD CALCULATION FOR HOTEL / | | | GUEST ROOMS INCLUDES 166,588 VA FOR UNITS WITHOUT | | | COOKING. I ADDED THE LOAD FOR ALL OF THESE UNITS AND | | | CAME UP WITH 845,034 VA. PROVIDE CLARIFICATION AND/OR | | | CORRECTION.) | | | 20. CORRECTED. | | | 21. CORRECTED. | | | 22. CORRECTED. | | | 23. PROVIDE COMPLETED PANEL SCHEDULE FOR EACH PANEL, | | | INDICATING ANY NEW OR ALTERED CIRCUITS, THE WIRE AND | | | BREAKER SIZE FOR THESE CIRCUITS, AND AFCI OR GFCI | | | PROTECTION WHERE APPLICABLE TO COMPLY WITH CODE. MANY | | | PANELS SCHEDULES PROVIDED ARE BLANK OR HAVE LIMITED | | | INFORMATION. NEC 210.8, 210.12, 210.19, 210.20, 215.5, | | | 408.4 (SHHET E.616, 3 PANELS SHOWS CIRCUITS BEING FED, | | | BUT NO LOAD FOR THOSE CIRCUITS. PANELS N2H8, N2H9, AND | | | N2H12. PROVIDE CORRECTION.) | | | 24. CORRECTED. | | | 25. CORRECTED. | | | 26. CORRECTED. | | | 27. CORRECTED. | | | | | | NEW COMMENTS: | | | | | | 28. SHEET E.207D, RESTROOM 0756 AND 0757, THE | | | RECEPTACLE OUTLET IS NOT GFCI PROTECTED. PROVIDE | | | CORRECTION. NEC 210.8 | | | 29. SHEET E.107D AND E.108D, THERE SHOULD BE A MINUMUM | | | OF 3 FOOT CANDLES OF LIGHT AT THE POOL WATER SURFACE | | | AND THE POOL WET DECK SURFACE FOR OUTDOOR POOLS, AND 10 | | | FOOT CANDLES FOR INDOOR POOLS. PROVIDE COMPLIANCE. FBC | | | 454.1.4.2 | | | 30. SHEET E.301 AND E.303, KEYNOTE 1 SHOWS A RECEPTACLE | | | OUTLET FOR A TV IN A WATERPROOF ENCLOSURE. A RECEPTACLE | | | OUTLET IS NOT PERMITTED IN THE TUB OR SHOWER SPACE. | | | PROVIDE CORRECTION. NEC 406.9(C) | | | 31. SHEETS E.306, 307, 308, 309, 310, AND 311 ALL SHOW | | | INCORRECT WIRING OF BATHROOM CIRCUITS IN MODELS C1, D2, | | | B3.1, D3, D1, E1, B5, D4, AND B6. THERE MAY BE SOME | | | THAT I MISSED. A MINIMUM OF ONE 20 AMPERE BRANCH | | | CIRCUIT SHALL BE PROVIDED TO SUPPLY BATHROOM RECEPTACLE | | | OUTLET(S). SUCH CIRCUITS SHALL HAVE NO OTHER OUTLETS. | | | WHEN AN INDIVIDUAL CIRCUIT IS RAN TO A BATHROOM AND | | | THIS CIRCUIT IS USED FOR LIGHTING AND RECEPTACLE | | | OUTLETS, THIS CIRCUIT CANNOT BE USED IN ANOTHER | | | BATHROOM. IF THE CIRCUIT IS USED ONLY FOR THE | | | RECEPTACLE OUTLETS, IT CAN BE USED TO FEED OTHER | | | RECEPTACLE OUTLETS IN A DIFFERENT BATHROOM. SEVERAL | | | LOCATIONS SHOW CIRCUIT 14 OR 26, SOMETIMES BOTH, BEING | | | USED FOR LIGHTING AND RECEPTACLE OUTLETS IN MULTILPLE | | | BATHROOMS. PROVIDE CORRECTION. NEC 210.11(C)(3) | | | 32. SHEET E.501 SHOWS A 1200 AMP SERVICE FOR FUTURE | | | RETAIL USE. THIS DOES NOT HAVE A DESIGNATION THE SAME | | | AS OTHER MAINS DO. PLEASE CLARIFY THE NAME OF THIS | | | MAIN. WPB FBC 107.2.1 | | | 33. SHEET E.502A, BUSWAY RISER HA, 11TH FLOOR | | | DISCONNECT IS SHOWN AS A 300 AMP BREAKER WITH A 200 AMP | | | FEEDER TO THE DOWNSTREAM PANEL. PROVIDE CLARIFICATION | | | AND/OR CORRECTION. NEC 215.2, 240.4, 310.15(B)(16); WPB | | | FBC 107.2.1 | | | 34. SHEET E.603, PANEL SCHEDULE LEGEND. THE LEGEND FOR | | | SHEETS E.604, E.606, E.607, E.610, E.611, E.616, AND | | | E.622 DO NOT MATCH WHAT IS ON THOSE PAGES. SHEET E.506 | | | IS NOT IN THE LEGEND. PROVIDE CORRECTIONS. WPB FBC | | | 107.2.1 | | | 35. SHEET E.614, PANEL SWBNRR IS SHOWN AS A 1000 AMP | | | PANEL. THE RISER DIAGRAM SHOWS THIS AS A 2500 AMP | | | PANEL. THE LOADS SPECIFIED IN PANEL SCHEDULE ARE | | | DIFFERENT THAN WHAT IS SHOWN ON RISER. PROVIDE | | | CLARIFICATION AND/OR CORRECTION. WPB FBC 107.2.1; NEC | | | 215.2, 240.4, 310.15(B)(16) | | | 36. SHEET E.615, PANEL DN4H1 IS SHOWN AS AN 800 AMP | | | PANEL WITH A LOAD OF 945 AMPS. PROVIDE CLARIFICATION | | | AND/OR CORRECTION. WPB FBC 107.2.1; NEC 215.2, 240.4, | | | 310.15(B)(16) | | | 37. SHEET E.615, PANEL N2H1 IS SHOWN AS AN 400 AMP | | | PANEL WITH A LOAD OF 1959 AMPS. PROVIDE CLARIFICATION | | | AND/OR CORRECTION. WPB FBC 107.2.1; NEC 215.2, 240.4, | | | 310.15(B)(16) | | | 38. SHEET E.622, PANEL N4H7E IS SHOWN AS AN 225 AMP | | | PANEL WITH A LOAD OF 277 AMPS. PROVIDE CLARIFICATION | | | AND/OR CORRECTION. WPB FBC 107.2.1; NEC 215.2, 240.4, | | | 310.15(B)(16) | | | | | | END OF COMMENTS. | | | | | | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN | | | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES | | | INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY | | | REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED | | | SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD | | | SHEETS. | | | | | | SINCERELY, | | | | | | JOHN PEARSON | | | ELECTRICAL PLANS EXAMINER | | | 561-805-6746 | | | [email protected] | | | | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2019-03-29 |
|
|
Cont ID |
|
| Sent By |
jpearson |
Date |
2019-03-29 |
Time |
10:23 |
Rev Time |
0.00 |
| Received By |
jpearson |
Date |
2019-03-25 |
Time |
14:18 |
Sent To |
|
|
| Notes |
| 2019-03-29 10:23:07 | CODES IN EFFECT: | | | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION | | | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 | | | 6TH ED, CHAPTER 1. | | | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 | | | 6TH EDITION | | | FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017 | | | 6TH EDITION | | | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION | | | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE | | | FS = FLORIDA STATUTES | | | | | | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | | | BE ADVISED THAT A COMPLETE REVIEW WAS NOT POSSIBLE AT | | | THIS TIME. THE PLANS PROVIDED STATE THEY ARE 80% | | | DOCUMENTS, BUT IT APPEARS THE ELECTRICAL PORTION IS | | | LESS THAN THAT. SOME PAGES, SUCH AS E.502A, E.502B, | | | E.503, E.504A, AND E.504B ARE BLANK. OTHER PAGES THAT | | | STATE THEY ARE FOR LIGHTING AND POWER ARE MISSING | | | LIGHTING IN KEY AREAS, NOT EVEN SHOWING THE REQUIRED | | | MEANS OF EGRESS ILLUMINATION PER FBC 1008.2.1, AND NOT | | | SHOWING CIRCUIT NUMBERS AND KEY INFORMATION ON POWER | | | ITEMS. THEREFORE, THE NEXT REVIEW WILL LIKELY CONTAIN | | | COMMENTS FOR CORRECTION THAT ARE NOT ADDRESSED IN THIS | | | REVIEW. | | | | | | 1. SHEET E.201B, PROVIDE GFCI PROTECTION FOR ALL | | | RECEPTACLE OUTLETS IN KITCHEN. NEC 210.8(B)(2) | | | 2. SHEET E.202A, PROVIDE GFCI PROTECTION FOR ALL | | | RECEPTACLE OUTLETS IN BATHROOM. NEC 210.8(B)(1) | | | 3. PROVIDE AVAILABLE SHORT CIRCUIT CALCULATION FOR | | | SERVICE AND DOWNSTREAM PANELS, INCLUDING INFORMATION | | | FROM THE POWER COMPANY STATING WHAT THE AVAILABLE SHORT | | | CIRCUIT CURRENT IS FOR THE SERVICE TO CONFIRM THE | | | STATED AIC RATING OF THE SERVICE EQUIPMENT AND | | | DOWNSTREAM PANELS IS ADEQUATE. NEC 110.9, 110.10; FBC | | | RE E3606.3 | | | 4. PROVIDE NOTES TO INDICATE THE REQUIRED MARKING OF | | | SERVICE EQUIPMENT FOR ARC FLASH HAZARD WARNING AND | | | AVAILABLE FAULT CURRENT PER CODE. NEC 110.16, 110.24 | | | 5. PROVIDE CHART OF INTERIOR LIGHTING POWER ALLOWANCES | | | EXPRESSED IN WATTAGE PER THE FBC ENERGY CODE IN | | | RELATION TO THE WATTAGE OF THE CONNECTED INTERIOR | | | LIGHTING PROPOSED TO COMPLY WITH CODE. FOR RESIDENTIAL | | | AREAS, A MINIMUM OF 75 PERCENT OF THE LAMPS IN | | | PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL BE | | | HIGH-EFFICACY LAMPS OR A MINIMUM OF 75 PERCENT OF THE | | | PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL CONTAIN | | | ONLY HIGH EFFICACY LAMPS. FBC EC C405.1, C405.4.2 | | | 6. PROVIDE THE ADDITIONAL INTERIOR LIGHTING CONTROLS | | | STIPULATED IN THE FBC ENERGY CODE. MANY AREAS DO NOT | | | SHOW THE AUTOMATIC CONTROL REQUIRED. FBC EC C405.2 | | | 7. PROVIDE VOLTAGE DROP CALCULATIONS TO COMPLY WITH | | | CODE. FBC EC C405.6.3 | | | 8. PROVIDE BLOCK NOTE INDICATING COMPLIANCE: ?WITHIN 30 | | | DAYS AFTER THE DATE OF SYSTEM ACCEPTANCE, RECORD | | | DRAWINGS OF THE ACTUAL INSTALLATION SHALL BE PROVIDE TO | | | THE BUILDING OWNER, INCLUDING: 1. A SINGLE LINE DIAGRAM | | | OF THE BUILDING ELECTRICAL DISTRIBUTION SYSTEM AND 2. | | | FLOOR PLANS INDICATING LOCATION AND AREA SERVED FOR ALL | | | DISTRIBUTION.? FBC EC C405.6.4.1 | | | 9. PROVIDE RECEPTACLE CONTROL REQUIRED BY ASHREA 90.1: | | | 8.4.2. PER THIS REQUIREMENT, THE FOLLOWING SHALL BE | | | AUTOMATICALLY CONTROLLED: 1) AT LEAST 50% OF ALL | | | 125-VOLT, 15 AND 20 AMP RECEPTACLES, IN ALL PRIVATE | | | OFFICES, CONFERENCE ROOMS, ROOMS USED PRIMARILY FOR | | | PRINTING AND/OR COPYING FUNCTIONS, BREAK ROOMS, | | | CLASSROOMS, AND INDIVIDUAL WORKSTATIONS. 2) AT LEASE | | | 25% OF BRANCH CIRCUIT FEEDERS INSTALLED FOR MODULAR | | | FURNITURE NOT SHOWN ON THE CONSTRUCTION DOCUMENTS. FBC | | | EC C405.6.1 | | | 10. FOR POOL ROOM EQUIPMENT SHOWN ON SHEETS E.205C AND | | | E.207A, PROVIDE ENCLOSURE TYPES DESIGNED TO PROTECT | | | AGAINST CORROSIVE ENVIRONMENTS. NEC TABLE 110.28 | | | 11. SHEET E.207D, PROVIDE GFCI RECEPTACLE OUTLET FOR | | | POOL PER CODE. NEC 680.22(A) | | | 12. PROVIDE GFCI PROTECTION FOR ALL ELECTRIC WATER | | | COOLERS. NEC 422. 5, 422.52 | | | 13. PROVIDE GFCI PROTECTION FOR DISHWASHERS IN DWELLING | | | UNITS. NEC 210.8(D) | | | 14. SHEET E.218 AND E.405, PANEL SWBNHR DOES NOT APPEAR | | | TO HAVE THE PROPER CLEARANCE TO ALLOW FOR ONE ENTRANCE | | | TO AND EGRESS FROM THIS SPACE. ADDITIONAL INFORMATION | | | IS NEEDED TO CONFIRM AS THERE IS NO PANEL SCHEDULE FOR | | | THIS PANEL, OR ANY PERTINENT INFORMATION SUPPLIED. | | | PROVIDE CLARIFICATION AND/OR CORRECTIONS AS NEEDED. NEC | | | 110.26(C) | | | 15. NOTE 5 ON SHEETS E.301, E.302, E.303, AND NOTE 8 ON | | | SHEETS E.304, E.305, E.306, E.307, E.308, AND E.309 DO | | | NOT PROVIDE AFCI PROTECTION TO CODE. ALL BRANCH | | | CIRCUITS THAT SUPPLY 120-VOLT, SINGLE-PHASE, 15- AND | | | 20-AMPERE OUTLETS INSTALLED IN KITCHENS, FAMILY ROOMS, | | | DINING ROOMS, LIVING ROOMS, PARLORS, LIBRARIES, DENS, | | | BEDROOMS, SUN-ROOMS, RECREATIONS ROOMS, CLOSETS, | | | HALLWAYS, LAUNDRY AREAS AND SIMILAR ROOMS OR AREAS | | | SHALL BE AFCI PROTECTED. THIS INCLUDES LIGHTING AND | | | POWER OUTLETS AND RECEPTACLES. SOME AREAS REQUIRE BOTH | | | AFCI AND GFCI PROTECTION. PROVIDE CORRECTION. NEC | | | 210.8, 210.12 | | | 16. SHEET E.505, FEEDER FROM GDP-GEN2 TO ATS ER IS | | | SHOWN AS A 400 AMP FEEDER. HOWEVER, THIS IS FED FROM A | | | 600 AMP BREAKER. THE ATS IS ONLY RATED FOR 400 AMPS PER | | | DESCRIPTION ON PLAN. PROVIDE CLARIFICATION AND/OR | | | CORRECTIONS AS NEEDED. NEC 110.3, 310.15(B)(16), 701.4, | | | 701.5 | | | 17. PROVIDE GROUND FAULT PROTECTION PER NEC 230.95. | | | 18. SHEETS E.506 AND E.803, SPECIFY WIRES SIZES FOR | | | GROUNDING SYSTEM TO CONFIRM CODE COMPLIANCE. NEC 250; | | | WPB FBC 107.2.1 | | | 19. PROVIDE ACCURATE LOAD CALCULATION FOR ALL SERVICES. | | | NEC 220; WPB FBC 107.2.1 | | | 20. SHEET E.601, METER CENTER LOAD SUMMARY SHOWS A | | | TOTAL LOAD FOR MC-1 AS 1,064,094 VA, WITH A DEMAND LOAD | | | OF 330,120 VA. BUT THE FEEDER TO MC-1 SHOWS A LOAD OF | | | 840,000 VA AND A DEMAND LOAD OF 294,000, WITH A | | | DIFFERENT NUMBER OF UNITS SPECIFIED. THERE ARE SIMILAR | | | PROBLEMS WITH OTHER FEEDER CALCULATIONS. ALL DATA | | | SHOULD BE CONSISTENT. PROVIDE CORRECTION. WPB FBC | | | 107.2.1 NEC 220 | | | 21. THE LOAD CALCULATION PROVIDED FOR HOTEL GUEST ROOM | | | SUITES USES THE LOAD CALCULATION METHOD FROM NEC | | | 220.82. FOR THE DEMAND FACTORS IN THIS SECTION TO BE | | | USED, IT MUST BE A 120/240 OR 120/208 THREE WIRE | | | (SINGLE PHASE) FEEDER WITH A MINIMUM AMPACITY OF 100 | | | AMPS. THE LOAD CALCULATION SHOWS THIS AS THREE PHASE. | | | THE PANEL SCHEDULE ON SHEET E.603 SHOWS THE PANELS AS | | | SINGLE PHASE. PROVIDE CLARIFICATIONS AND CORRECTIONS AS | | | NEEDED. NEC 220; WPB FBC 107.2.1 | | | 22. GUEST ROOM FEEDER DEMAND USES 480 VOLT, 3 PHASE FOR | | | TOTAL DEMAND CALCULATIONS WHILE OTHER CALCULATIONS ARE | | | AT 208 VOLT, 3 PHASE. PROVIDE CLARIFICATIONS AND/OR | | | CORRECTIONS AS NEEDED. NEC 220; WPB FBC 107.2.1 | | | 23. PROVIDE COMPLETED PANEL SCHEDULE FOR EACH PANEL, | | | INDICATING ANY NEW OR ALTERED CIRCUITS, THE WIRE AND | | | BREAKER SIZE FOR THESE CIRCUITS, AND AFCI OR GFCI | | | PROTECTION WHERE APPLICABLE TO COMPLY WITH CODE. MANY | | | PANELS SCHEDULES PROVIDED ARE BLANK OR HAVE LIMITED | | | INFORMATION. NEC 210.8, 210.12, 210.19, 210.20, 215.5, | | | 408.4 | | | 24. PROVIDE DETAILS OF SELECTIVE COORDINATION PER NEC | | | 700.28 AND 701.27. | | | 25. PROVIDE DETAILS OF ARC ENERGY REDUCTION PER NEC | | | 240.87 | | | 26. PER NEC 230.72(B), THE DISCONNECTS FOR EMERGENCY | | | SYSTEMS SHALL BE LOCATED REMOTELY FROM NORMAL POWER | | | SYSTEMS. IT APPEARS FROM THIS DESIGN THAT THE NORMAL | | | POWER FEEDERS AND THE EMERGENCY POWER FEEDERS ARE FED | | | FROM THE SAME SWITCH BOARDS. PROVIDE CLARIFICATION | | | AND/OR CORRECTION AS NEEDED. NEC 230.72(B) | | | 27. BE ADVISED THAT FIRE ALARM, LOW VOLTAGE SYSTEMS, | | | DAS, LIGHTNING PROTECTION, GENERATORS, COMMERCIAL HOOD | | | SYSTEMS, WALK IN COOLERS, SIGNS, SITE LIGHTING, AND | | | SWIMMING POOLS (WHERE APPLICABLE) ARE NOT INCLUDED IN | | | THE SCOPE OF THIS PLAN REVIEW. PROVIDE A BLOCK NOTE | | | INDICATING THE REQUIRED SEPARATE PERMITS AND PLAN | | | SUBMITTALS FOR ANY OF THESE SYSTEMS PRESENT. WPB FBC | | | 105.1, 107.2.1 | | | | | | END OF COMMENTS. | | | | | | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN | | | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES | | | INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY | | | REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED | | | SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD | | | SHEETS. | | | | | | SINCERELY, | | | | | | JOHN PEARSON | | | ELECTRICAL PLANS EXAMINER | | | 561-805-6746 | | | [email protected] | | | | | | |
|
|
| Review Stop |
ENG |
ENGINEERING CSD |
| Rev No |
3 |
Status |
P |
Date |
2021-09-08 |
|
|
Cont ID |
|
| Sent By |
rrossano |
Date |
2021-09-08 |
Time |
|
Rev Time |
0.00 |
| Received By |
rrossano |
Date |
2021-09-08 |
Time |
|
Sent To |
I |
|
| Notes |
| 2021-09-08 08:33:01 | PASSED WITH PROVISO: CHECK WITH ENGINEERING SERVICES | | | PRIOR TO ISSUANCE OF CO FOR COMPLETION OF ENGINEERING | | | PERMIT (E19010014). |
|
|
| Review Stop |
ENG |
ENGINEERING CSD |
| Rev No |
2 |
Status |
P |
Date |
2020-02-11 |
|
|
Cont ID |
|
| Sent By |
rrossano |
Date |
2020-02-11 |
Time |
07:34 |
Rev Time |
0.00 |
| Received By |
rrossano |
Date |
|
Time |
|
Sent To |
I |
|
| Notes |
| 2020-02-11 07:34:40 | PASSED WITH PROVISO: CHECK WITH ENGINEERING SERVICES | | | PRIOR TO ISSUANCE OF CO FOR COMPLETION OF ENGINEERING | | | PERMIT (E19010014). CONTACT MANNY GONZALEZ, SENIOR | | | ENGINEERING PROJECT COORDINATOR, ENGINEERING SERVICES | | | DEPARTMENT, 401 CLEMATIS STREET, 4TH FLOOR, WEST PALM | | | BEACH, FL 33401, EMAIL: [email protected], | | | WWW.WPB.ORG/ENGINEERING | | | |
|
|
| Review Stop |
ENG |
ENGINEERING CSD |
| Rev No |
1 |
Status |
F |
Date |
2019-03-22 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2019-03-22 |
Time |
15:48 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2019-03-22 |
Time |
15:48 |
Sent To |
|
|
| Notes |
| 2019-03-22 15:49:07 | CONTACT ENGINEERING DEPARTMENT DIRECTLY AND SUBMIT | | | APPLICATION IF REQUIRED | | | HTTP://WWW.WPB.ORG/DEPARTMENTS/ENGINEERING-PUBLIC-WORKS | | | /FORMS,-PERMITS-APPLICATIONS | | | | | | ENGINEERING APPROVAL REQUIRED PRIOR TO PERMIT ISSUANCE | | | | | | MAIN PHONE: (561) 822-1200 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
5 |
Status |
P |
Date |
2021-06-07 |
|
|
Cont ID |
|
| Sent By |
pleduc |
Date |
2021-06-07 |
Time |
|
Rev Time |
0.00 |
| Received By |
pleduc |
Date |
2021-05-20 |
Time |
10:02 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
4 |
Status |
P |
Date |
2021-01-25 |
|
|
Cont ID |
|
| Sent By |
pleduc |
Date |
2021-01-25 |
Time |
|
Rev Time |
0.00 |
| Received By |
pleduc |
Date |
2021-01-07 |
Time |
09:35 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
3 |
Status |
P |
Date |
2020-03-13 |
|
|
Cont ID |
|
| Sent By |
pleduc |
Date |
2020-03-13 |
Time |
|
Rev Time |
0.00 |
| Received By |
pleduc |
Date |
2020-02-21 |
Time |
09:11 |
Sent To |
|
|
| Notes |
| 2020-03-12 10:09:50 | THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC, | | | FIRE MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | | | PLEASE CONSIDER THE FOLLOWING AS PROVISO: | | | | | | THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED | | | AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE | | | PROVISO COMMENTS WILL RESULT IN A FAILED FIRE | | | INSPECTION. | | | | | | | | | | | | 1) SHEET A 1.108 - PLEASE REVIEW THE REQUIREMENT FOR AN | | | ELEVATOR LOBBY AT THE FREIGHT ELEVATOR. | | | | | | PLEASE REVIEW AND CORRECT, IF APPLICABLE, WITH | | | REVISIONS. | | | | | | | | | | | | 2) STAIR PRESSURIZATION RATIONAL ANALYSIS REPORT - | | | | | | ON PAGE 13 OF THE STAIR PRESSURIZATION RATIONAL | | | ANALYSIS REPORT DOCUMENT SECTION 11. CONCLUSION THERE | | | IS AN INDICATION OF A DETAILED SEQUENCE OF OPERATION, | | | WHICH DOES NOT APPEAR TO BE SUBMITTED. | | | | | | PLEASE AND PROVIDE AND CONTINUE TO WORK WITH THE OFFICE | | | OF THE FIRE MARSHAL AND THE BUILDING DEPARTMENT'S | | | MECHANICAL PLAN REVIEWERS AND INSPECTORS FOR APPROVAL. | | | | | | | | | | | | | | | PETER LEDUC | | | FIRE MARSHAL | | | 561-804-4709 | | | [email protected] | | | |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
F |
Date |
2019-03-27 |
|
|
Cont ID |
|
| Sent By |
pleduc |
Date |
2019-03-27 |
Time |
|
Rev Time |
0.00 |
| Received By |
pleduc |
Date |
2019-03-08 |
Time |
14:17 |
Sent To |
|
|
| Notes |
| 2019-03-13 13:43:42 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE | | | MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | | | | | | 1) SHEET ALS 1.00 - THERE ARE INDICATIONS REGARDING THE | | | CONTENTS OF THE COMMAND ROOM. | | | | | | PER NFPA 1 AND 101 THERE ARE ADDITIONAL REQUIRMENTS NOT | | | LISTED. FOR CLARIFICATION PURPOSES THE EXACT CODE | | | LANGUAGE IS PROVIDED: | | | | | | THE FIRE COMMAND CENTER SHALL COMPLY WITH NFPA 1, | | | CHAPTER 11, BUILDING SERVICES; 11.9 AND SHALL CONTAIN | | | THE FOLLOWING FEATURES: | | | | | | 1. SHALL BE A MINIMUM OF 200 FT SQUARED WITH A MINIMUM | | | DIMENSION OF 10 FT. | | | 2. THE FIRE DEPARTMENT COMMUNICATIONS SYSTEM. | | | 3. A TELEPHONE FOR FIRE DEPARTMENT USE WITH CONTROLLED | | | ACCESS TO THE PUBLIC TELEPHONE SYSTEM | | | 4. SCHEMATIC BUILDING PLANS INDICATING THE TYPICAL | | | FLOOR PLAN AND DETAILING THE BUILDING CORE, MEANS OF | | | EGRESS, FIRE PROTECTION SYSTEMS, FIRE-FIGHTING | | | EQUIPMENT AND FIRE DEPARTMENT ACCESS AND THE LOCATION | | | OF FIRE WALLS, FIRE BARRIERS, FIRE PARTITIONS, SMOKE | | | BARRIERS AND SMOKE PARTITIONS | | | 5. A WORK TABLE. | | | 6. IF APPLICABLE, A HAZARDOUS MATERIAL MANAGEMENT PLAN | | | FOR THE BUILDING. | | | 7. THE EMERGENCY VOICE/ALARM COMMUNICATION SYSTEM | | | CONTROL UNIT. | | | 8. ANNUNCIATOR UNIT VISUALLY INDICATING THE LOCATION OF | | | THE ELEVATORS AND WHETHER THEY ARE OPERATIONAL | | | 9. STATUS INDICATORS AND CONTROLS FOR AIR DISTRIBUTION | | | SYSTEMS. | | | 10. CONTROLS FOR UNLOCKING STAIRWAY DOORS | | | SIMULTANEOUSLY | | | 11. SPRINKLER VALVE AND WATER FLOW DETECTOR DISPLAY | | | PANELS | | | 12. EMERGENCY AND STANDBY POWER STATUS INDICATORS | | | 13. FIRE PUMP STATUS INDICATORS | | | 14. GENERATOR SUPERVISION DEVICES AND MANUAL START AND | | | TRANSFER FEATURES. | | | 15. PUBLIC ADDRESS SYSTEM, WHERE SPECIFICALLY REQUIRED | | | BY OTHER SECTIONS OF THIS CODE | | | 16. CONTROLS REQUIRED FOR SMOKE CONTROL | | | 17. ELEVATOR FIRE RECALL SWITCH IN ACCORDANCE WITH ASME | | | A17.1. | | | 18. ELEVATOR EMERGENCY OR STANDBY POWER SELECTOR | | | SWITCH(ES), WHERE EMERGENCY OR STANDBY POWER IS | | | PROVIDED | | | | | | NFPA 101, CHAPTER 11, SPECIAL STRUCTURES AND HIGH RISE | | | BUILDINGS | | | | | | 11.8.6* EMERGENCY COMMAND CENTER. | | | 11.8.6.1 AN EMERGENCY COMMAND CENTER SHALL BE PROVIDED | | | IN A LOCATION APPROVED BY THE FIRE DEPARTMENT. | | | 11.8.6.2 THE EMERGENCY COMMAND CENTER SHALL CONTAIN THE | | | FOLLOWING: | | | (1) VOICE FIRE ALARM SYSTEM PANELS AND CONTROLS | | | (2) FIRE DEPARTMENT TWO-WAY TELEPHONE COMMUNICATION | | | SERVICE PANELS AND CONTROLS WHERE REQUIRED BY ANOTHER | | | SECTION OF THIS CODE | | | (3) FIRE DETECTION AND FIRE ALARM SYSTEM ANNUNCIATION | | | PANELS | | | (4) ELEVATOR FLOOR LOCATION AND OPERATION ANNUNCIATORS | | | (5) ELEVATOR FIRE RECALL SWITCH IN ACCORDANCE WITH ASME | | | A17.1/CSA B44, SAFETY CODE FOR ELEVATORS AND ESCALATORS | | | (6) ELEVATOR EMERGENCY POWER SELECTOR SWITCH(ES) WHERE | | | PROVIDED IN ACCORDANCE WITH ASME A17.1/CSA B44 | | | (7) SPRINKLER VALVE AND WATERFLOW ANNUNCIATORS | | | (8) EMERGENCY GENERATOR STATUS INDICATORS | | | (9) CONTROLS FOR ANY AUTOMATIC STAIRWAY DOOR UNLOCKING | | | SYSTEM | | | (10) FIRE PUMP STATUS INDICATORS | | | (11) TELEPHONE FOR FIRE DEPARTMENT USE WITH CONTROLLED | | | ACCESS TO THE | | | PUBLIC TELEPHONE SYSTEM | | | (12) STAIRWAY VIDEO MONITORING EQUIPMENT AS REQUIRED BY | | | 11.8.8 | | | | | | PLEASE REVIEW AND CORRECT. | | | | | | | | | | | | 2) SHEET ALS1.102 THRU 1.104 - THE HOTEL SIDE FIRE | | | LOBBY DOOR,EAST SIDE, INDICATES A SWING AGAINST THE | | | EXIT PATH OF TRAVEL. | | | | | | PER NFPA 101, CH 7, MEANS OF EGRESS | | | | | | 7.2.1.4.2 DOOR LEAF SWING DIRECTION. DOOR LEAVES | | | REQUIRED TO BE | | | OF THE SIDE-HINGED OR PIVOTED-SWINGING TYPE SHALL SWING | | | IN THE | | | DIRECTION OF EGRESS TRAVEL UNDER ANY OF THE FOLLOWING | | | CONDITIONS: | | | (1) WHERE SERVING A ROOM OR AREA WITH AN OCCUPANT LOAD | | | OF 50 OR | | | MORE, EXCEPT UNDER ANY OF THE FOLLOWING CONDITIONS: | | | (A) DOOR LEAVES IN HORIZONTAL EXITS SHALL NOT BE | | | REQUIRED TO | | | SWING IN THE DIRECTION OF EGRESS TRAVEL WHERE PERMITTED | | | BY 7.2.4.3.8.1 OR 7.2.4.3.8.2. | | | (B) DOOR LEAVES IN SMOKE BARRIERS SHALL NOT BE REQUIRED | | | TO | | | SWING IN THE DIRECTION OF EGRESS TRAVEL IN EXISTING | | | HEALTH | | | CARE OCCUPANCIES, AS PROVIDED IN CHAPTER 19. | | | (2) WHERE THE DOOR ASSEMBLY IS USED IN AN EXIT | | | ENCLOSURE, UNLESS | | | THE DOOR OPENING SERVES AN INDIVIDUAL LIVING UNIT THAT | | | OPENS | | | DIRECTLY INTO AN EXIT ENCLOSURE | | | (3) WHERE THE DOOR OPENING SERVES A HIGH HAZARD | | | CONTENTS AREA | | | | | | PLEASE REVIEW AND CORRECT OR JUSTIFY WITH SPECIFIC CODE | | | REFERENCES. | | | | | | | | | | | | | | | 3) SHEET A 1.102 & A 6.103 - THERE ARE NO CLEAR | | | INDICATIONS OF THE TRASH CHUTE ROOM DOOR NUMBER OR TYPE | | | ON THIS THESE SHEETS OR ANY OTHER SHEET. | | | | | | PLEASE REVIEW AND CORRECT OR CLARIFY | | | | | | | | | | | | 3A) SHEET A 1.102 - THE DOOR TO THE TRASH CHUTE OPENS | | | TOO FAR INTO THE EXIT CORRIDOR. | | | | | | PER NFPA 101, CH 7 MEANS OF EGRESS & CH 9 | | | | | | 7.2.1.4.3* DOOR LEAF ENCROACHMENT. | | | 7.2.1.4.3.1 DURING ITS SWING, ANY DOOR LEAF IN A MEANS | | | OF EGRESS | | | SHALL LEAVE NOT LESS THAN ONE-HALF OF THE REQUIRED | | | WIDTH OF AN AISLE, | | | A CORRIDOR, A PASSAGEWAY, OR A LANDING UNOBSTRUCTED, | | | UNLESS BOTH | | | OF THE FOLLOWING CONDITIONS ARE MET: | | | (1) THE DOOR OPENING PROVIDES ACCESS TO A STAIR IN AN | | | EXISTING | | | BUILDING. | | | (2) THE DOOR OPENING MEETS THE REQUIREMENT OF | | | 7.2.1.4.3.2. | | | | | | | | | 9.5 WASTE CHUTES, INCINERATORS, AND LAUNDRY CHUTES. | | | 9.5.1 ENCLOSURE. | | | 9.5.1.1 WASTE CHUTES AND LAUNDRY CHUTES SHALL BE | | | SEPARATELY | | | ENCLOSED BY WALLS OR PARTITIONS IN ACCORDANCE WITH THE | | | PROVISIONS | | | OF SECTION 8.3. | | | 9.5.1.2 CHUTE INTAKE OPENINGS SHALL BE PROTECTED IN | | | ACCORDANCE | | | WITH SECTION 8.3. | | | 9.5.1.3 THE DOORS OF CHUTES SPECIFIED IN 9.5.1.2 SHALL | | | OPEN ONLY TO | | | A ROOM THAT IS DESIGNED AND USED EXCLUSIVELY FOR | | | ACCESSING THE | | | CHUTE OPENING. | | | 9.5.1.4 CHUTE SERVICE OPENING ROOMS SHALL BE SEPARATED | | | FROM OTHER | | | SPACES IN ACCORDANCE WITH SECTION 8.7. | | | | | | PLEASE REVIEW AND CORRECT OR JUSTIFY WITH SPECIFIC CODE | | | REFERENCES AND NARRATIVE. | | | | | | | | | | | | 4) SHEET A1.105 - THERE ARE INDICATIONS OF LIFT IN SOME | | | OF THE PARKING GARAGE. | | | | | | WHAT DOES REPRESENT AND HOW WILL IT EFFECT THE FIRE | | | PROTECTION SYSTEMS? | | | | | | PLEASE REVIEW AND PROVIDE DETAILS WITH SPECIFIC CODE | | | REFERENCES. | | | | | | | | | | | | 5) SHEET A1.108 - THERE IS AN INDICATION OF AN EXIT | | | SIGN(TENNIS COURT SIDE) AND EXIT DOOR FIRE RESISTANCE | | | CALCULATION(45) LEADING TO THE CORRIDOR BY THE HOTEL | | | POOL EQUIPMENT ROOM. | | | | | | THERE IS NO INDICATION OF A DOOR. | | | | | | SHEET E108B INDICATES A DOUBLE DOOR AT THE WALL WITH AN | | | EXIT SIGN. | | | | | | PLEASE REVIEW AND CORRECT OR CLARIFY. | | | | | | | | | | | | | | | 6) SHEET A1.109, ALS 1.110 & A1.241- THERE IS AN | | | INDICATION OF THE FIRE LOBBY DOOR SWINGING IN THE PATH | | | OF TRAVEL ON A1.109 AND AGAINST THE PATH OF TRAVEL ON | | | THE OTHER TWO SHEETS. | | | | | | IT IS REQUIRED TO SWING IN THE PATH OF TRAVEL PER NPA | | | 101, CH 7 AS NOTED ABOVE. | | | | | | PLEASE REVIEW,CORRECT AND /OR CLARIFY. | | | | | | | | | | | | | | | 7) ALL APPLICABLE A & ALS SHEETS - THERE IS AN | | | INCORRECT TOTAL CALCULATION INDICATED FOR A 44" DOOR | | | OPENING. THE CODE REQUIRES THE LOAD CALCULATIONS TO BE | | | ROUNDED UP; 146.7 SHOULD BE ROUNDED UP TO 147 ON ALL | | | APPLICABLE SHEETS. | | | | | | 7.3.3* EGRESS CAPACITY. | | | 7.3.3.1 EGRESS CAPACITY FOR APPROVED COMPONENTS OF | | | MEANS OF | | | EGRESS SHALL BE BASED ON THE CAPACITY FACTORS SHOWN IN | | | TABLE | | | 7.3.3.1, UNLESS OTHERWISE PROVIDED IN 7.3.3.2 | | | | | | PLEASE REVIEW AND CORRECT | | | | | | | | | | | | 8) ALL APPLICABLE A & ALS SHEETS - THERE IS AN | | | INCORRECT TOTAL CALCULATION INDICATED FOR A 60" STAIR | | | WIDTH; 218(.2 WAS USED . THE CODE REQUIRES THE LOAD | | | CALCULATIONS TO BE .03; 200 SHOULD ON ALL APPLICABLE | | | SHEETS. | | | | | | 7.3.3* EGRESS CAPACITY. | | | 7.3.3.1 EGRESS CAPACITY FOR APPROVED COMPONENTS OF | | | MEANS OF | | | EGRESS SHALL BE BASED ON THE CAPACITY FACTORS SHOWN IN | | | TABLE | | | 7.3.3.1, UNLESS OTHERWISE PROVIDED IN 7.3.3.2 | | | | | | PLEASE REVIEW AND CORRECT. | | | | | | | | | | | | 9) SHEET A1.109 , A1.110 & ALS1.110 - THERE ARE | | | INDICATIONS OF CONFLICTS WITH THE CORE DOOR FIRE | | | RATINGS, DOOR LOCATION AND DOOR SWING. | | | | | | THE LS SHEET SHOWS TWO DOORS, NR, IN THE H.K. ROOM WITH | | | NO RATING ON THE BACK WALL. | | | | | | THE MECH ROOM DOOR IS 20 MIN IN A 2 HOUR WALL. | | | | | | THE LS SHEET DOOR SWING ON THE FIRE LOBBY SHOWS IN THE | | | PATH OF TRAVEL WHILE OTHER SHEETS SHOW OPPISITE. | | | | | | PLEASE REVIEW AND CORRECT OR CLARIFY. | | | | | | | | | | | | 10) SHEET ALS1.111 - THERE IS AN INDICATION OF NR | | | DOUBLE DOORS AT THE MECH ROOM. THESE DOORS ARE REQUIRED | | | TO BE RATED. | | | | | | PER NFPA 101, CH 38 | | | | | | 38.3.2 PROTECTION FROM HAZARDS. | | | 38.3.2.1* GENERAL. HAZARDOUS AREAS INCLUDING, BUT NOT | | | LIMITED TO, | | | AREAS USED FOR GENERAL STORAGE, BOILER OR FURNACE | | | ROOMS, AND | | | MAINTENANCE SHOPS THAT INCLUDE WOODWORKING AND PAINTING | | | AREAS | | | SHALL BE PROTECTED IN ACCORDANCE WITH SECTION 8.7. | | | 38.3.2.2* HIGH HAZARD CONTENTS AREAS. HIGH HAZARD | | | CONTENTS | | | AREAS, AS CLASSIFIED IN SECTION 6.2, SHALL MEET ALL OF | | | THE FOLLOWING | | | CRITERIA: | | | (1) THE AREA SHALL BE SEPARATED FROM OTHER PARTS OF THE | | | BUILDING BY | | | FIRE BARRIERS HAVING A MINIMUM 1-HOUR FIRE RESISTANCE | | | RATING, | | | WITH ALL OPENINGS THEREIN PROTECTED BY SELF-CLOSING | | | FIRE DOOR | | | ASSEMBLIES HAVING A MINIMUM 3?4-HOUR FIRE PROTECTION | | | RATING. | | | (2) THE AREA SHALL BE PROTECTED BY AN AUTOMATIC | | | EXTINGUISHING | | | SYSTEM IN ACCORDANCE WITH 9.7.1.1(1) OR 9.7.1.2. | | | | | | | | | PLEASE REVIEW AND CORRECT OR JUSTIFY WITH SPECIFIC CODE | | | REFERENCES. | | | | | | | | | | | | | | | 11) SHEET ALS1.114 - THERE ARE INDICATIONS AT THE FIRE | | | LOBBY & STAIR #1 EXIT DOORS OBSTRUCTING EACH OTHER. | | | | | | PER NFPA 101 CH 7 | | | 7.2.1.4.3* DOOR LEAF ENCROACHMENT. | | | 7.2.1.4.3.1 DURING ITS SWING, ANY DOOR LEAF IN A MEANS | | | OF EGRESS | | | SHALL LEAVE NOT LESS THAN ONE-HALF OF THE REQUIRED | | | WIDTH OF AN AISLE, | | | A CORRIDOR, A PASSAGEWAY, OR A LANDING UNOBSTRUCTED, | | | UNLESS BOTH | | | OF THE FOLLOWING CONDITIONS ARE MET: | | | (1) THE DOOR OPENING PROVIDES ACCESS TO A STAIR IN AN | | | EXISTING | | | BUILDING. | | | (2) THE DOOR OPENING MEETS THE REQUIREMENT OF | | | 7.2.1.4.3.2. | | | | | | PLEASE REVIEW AND CORRECT OR JUSTIFY WITH SPECIFIC CODE | | | REFERENCES AND NARRATIVE. | | | | | | | | | | | | 12) SHEET ALS1.114 - THERE ARE INDICATION THAT EACH | | | STAIR IS INDICATED AS STAIR # 1. SHEET ALS1.101 | | | INDICATES THEM DIFFERENTLY. | | | | | | PLEASE REVIEW AND CORRECT OR JUSTIFY. | | | | | | | | | | | | | | | 13) ENGINEERING DOCUMENTATION - THERE IS NO SPECIFIC | | | ENGINEEERING DOCUMENTATION REGARDING THE SMOKE CONTROL | | | FOR THIS PROJECT. | | | | | | PER NFPA 101, CH 9 | | | | | | 9.3 SMOKE CONTROL. | | | 9.3.1 INSTALLATION. WHERE REQUIRED BY ANOTHER SECTION | | | OF THIS | | | CODE, SMOKE CONTROL SYSTEMS SHALL BE DESIGNED, | | | INSTALLED, | | | INSPECTED, TESTED, AND MAINTAINED IN ACCORDANCE WITH | | | NFPA 92, | | | STANDARD FOR SMOKE CONTROL SYSTEMS; NFPA 204, STANDARD | | | FOR | | | SMOKE AND HEAT VENTING; OR NATIONALLY RECOGNIZED | | | STANDARDS, | | | ENGINEERING GUIDES, OR RECOMMENDED PRACTICES, AS | | | APPROVED BY | | | THE AUTHORITY HAVING JURISDICTION. | | | 9.3.2 SYSTEM DESIGN. THE ENGINEER OF RECORD SHALL | | | CLEARLY IDENTIFY | | | THE INTENT OF THE SYSTEM, THE DESIGN METHOD USED, THE | | | APPROPRIATENESS OF THAT METHOD, AND THE REQUIRED MEANS | | | OF | | | INSPECTING, TESTING, AND MAINTAINING THE SYSTEM. | | | | | | PLEASE REVIEW AND PROVIDE THE SPECIFIC DOCUMENTATION. | | | | | | | | | | | | 14) DOOR SCHEDULES - IT IS DIFFICULT TO CONFIRM WITH | | | ANY CERTAINTY THE CORRECT RATING AND HARDWARES OF THE | | | DOORS DUE TO NO ONE SHEET OF EACH FLOOR HAS ALL THE | | | DOORS NUMBERS MARKED, | | | | | | PLEASE MARK THE DOORS ON THE ALS SHEETS TO BETTER MARK | | | EACH DOOR NUMBER WITH THE RATING THAT CAN BE CLEARLY | | | AND ACCURATELY CHECKED AGAINST THE DOOR SCHEDULE. | | | | | | PLEASE REVIEW AND CORRECT OR HELP TO CLARIFY | | | VERIFICATIONS. | | | | | | | | | | | | | | | 15) SHEET ALS1.10 & ALS1.108 - THERE IS AN INDICATION | | | OF A LARGE STAIRCASE CONNECTING THESE TO FLOOR LEVELS. | | | THERE ARE NO INDICATIONS OF HOW THIS CONVENIENCE | | | OPENING WILL BE PROTECTED. | | | | | | PER NFPA 101, CH 8 | | | | | | 8.6.9 CONVENIENCE OPENINGS. | | | 8.6.9.1 WHERE PERMITTED BY CHAPTERS 11 THROUGH 43, | | | UNENCLOSED | | | VERTICAL OPENINGS NOT CONCEALED WITHIN THE BUILDING | | | CONSTRUCTION SHALL | | | BE PERMITTED AS FOLLOWS: | | | (1) SUCH OPENINGS SHALL CONNECT NOT MORE THAN TWO | | | ADJACENT STORIES | | | (ONE FLOOR PIERCED ONLY). | | | (2) SUCH OPENINGS SHALL BE SEPARATED FROM UNPROTECTED | | | VERTICAL | | | OPENINGS SERVING OTHER FLOORS BY A BARRIER COMPLYING | | | WITH 8.6.5. | | | (3) SUCH OPENINGS SHALL BE SEPARATED FROM CORRIDORS. | | | (4) *IN OTHER THAN APPROVED, EXISTING CONVENIENCE | | | OPENINGS, SUCH | | | OPENINGS SHALL BE SEPARATED FROM OTHER FIRE OR SMOKE | | | COMPARTMENTS ON THE SAME FLOOR. | | | (5) IN NEW CONSTRUCTION, THE CONVENIENCE OPENING SHALL | | | BE SEPARATED | | | FROM THE CORRIDOR REFERENCED IN 8.6.9.1(3) BY A SMOKE | | | PARTITION, | | | UNLESS CHAPTERS 11 THROUGH 43 REQUIRE THE CORRIDOR TO | | | HAVE A FIRE | | | RESISTANCE RATING. | | | (6) *SUCH OPENINGS SHALL NOT SERVE AS A REQUIRED MEANS | | | OF EGRESS. | | | | | | 8.6.9.2 WHERE PERMITTED BY CHAPTERS 11 THROUGH 43, | | | UNENCLOSED | | | VERTICAL OPENINGS CREATED BY CONVENIENCE STAIRWAYS | | | SHALL COMPLY WITH | | | ALL OF THE FOLLOWING: | | | (1) THE CONVENIENCE STAIR OPENINGS SHALL NOT SERVE AS | | | REQUIRED | | | MEANS OF EGRESS. | | | (2) THE BUILDING SHALL BE PROTECTED THROUGHOUT BY AN | | | APPROVED, | | | SUPERVISED AUTOMATIC SPRINKLER SYSTEM IN ACCORDANCE | | | WITH | | | SECTION 9.7. | | | (3) *THE CONVENIENCE STAIR OPENINGS SHALL BE PROTECTED | | | IN | | | ACCORDANCE WITH THE METHOD DETAILED FOR THE PROTECTION | | | OF | | | VERTICAL OPENINGS IN NFPA 13, STANDARD FOR THE | | | INSTALLATION OF | | | SPRINKLER SYSTEMS. | | | (4) IN NEW CONSTRUCTION, THE AREA OF THE FLOOR OPENING | | | SHALL NOT | | | EXCEED TWICE THE HORIZONTAL PROJECTED AREA OF THE | | | STAIRWAY. | | | (5) FOR NEW CONSTRUCTION, SUCH OPENINGS SHALL NOT | | | CONNECT MORE THAN | | | FOUR CONTIGUOUS STORIES, UNLESS OTHERWISE PERMITTED BY | | | CHAPTERS | | | 11 THROUGH 43. | | | | | | PLEASE REVIEW, CORRECT AND PROVIDE DETAILS. | | | | | | | | | | | | | | | 16) SHEET ALS1.108 - THERE IS AN INDICATION OF AN EXIT | | | SIGN AT THE TOP OF THE STAIRWAY NOTED ABOVE; HOWEVER, | | | PER 8.6.9.2 (1) THE STAIR SHALL NOT SERVE AS A REQUIRED | | | MEANS OF EGRESS. | | | | | | THIS STAIR APPEARS TO SERVE AS A REQUIRED MEANS OF | | | EGRESS. | | | | | | PLEASE REVIEW AND CORRECT OR JUSTIFY WITH SPECIFIC CODE | | | REFERENCES AND NARRATIVE. | | | | | | | | | | | | | | | 17) SHEET FP 301 - THERE ARE INDICATIONS OF TWO PUMPS. | | | THE PUMP SCHEDULES INDICATE 750 GPM WITH MAX CHURN | | | PRESSURE OF 235. | | | | | | THOSE THESE ARE NOT SHOP DRAWINGS, THESE FIGURES DO NOT | | | APPEAR TO BE ABLE TO SUPPORT FIRE DEMANDS ON UPPER | | | FLOORS, NOR SEPARATE FIRE LOCATED IN DIFFERENT TOWERS | | | AT THE SAME TIME. | | | | | | PLEASE REIVEW AND CORRECT OR JUSTIFY WITH THE EOR | | | NARRATIVE. | | | | | | | | | | | | 18) SHEET A1.105 & E - THERE IS AN INDICATION OF A | | | GENERATOR ROOM; HOWEVER, THERE ARE NO INDICATIONS OF | | | WHAT TYPE, CLASS, ETC. | | | | | | PER NFPA 110 | | | | | | CHAPTER 4 CLASSIFICATION OF EMERGENCY POWER SUPPLY | | | SYSTEMS (EPSSS) | | | 4.1* GENERAL. THE EPSS SHALL PROVIDE A SOURCE OF | | | ELECTRICAL | | | POWER OF REQUIRED CAPACITY, RELIABILITY, AND QUALITY TO | | | LOADS FOR | | | A LENGTH OF TIME AS SPECIFIED IN TABLE 4.1(A) AND | | | WITHIN A SPECIFIED | | | TIME FOLLOWING LOSS OR FAILURE OF THE NORMAL POWER | | | SUPPLY | | | AS SPECIFIED IN TABLE 4.1(B). | | | | | | 4.2* CLASS. THE CLASS DEFINES THE MINIMUM TIME, IN | | | HOURS, FOR | | | WHICH THE EPSS IS DESIGNED TO OPERATE AT ITS RATED LOAD | | | WITHOUT | | | BEING REFUELED OR RECHARGED. [SEE TABLE 4.1(A).] | | | 4.3 TYPE. THE TYPE DEFINES THE MAXIMUM TIME, IN | | | SECONDS, | | | THAT THE EPSS WILL PERMIT THE LOAD TERMINALS OF THE | | | TRANSFER | | | SWITCH TO BE WITHOUT ACCEPTABLE ELECTRICAL POWER. TABLE | | | 4.1(B) | | | PROVIDES THE TYPES DEFINED BY THIS STANDARD. | | | 4.4* LEVEL. THIS STANDARD RECOGNIZES TWO LEVELS OF | | | EQUIPMENT | | | INSTALLATION, PERFORMANCE, AND MAINTENANCE. | | | 4.4.1* LEVEL 1 SYSTEMS SHALL BE INSTALLED WHERE FAILURE | | | OF THE | | | EQUIPMENT TO PERFORM COULD RESULT IN LOSS OF HUMAN LIFE | | | OR | | | SERIOUS INJURIES. | | | 4.4.2* LEVEL 2 SYSTEMS SHALL BE INSTALLED WHERE FAILURE | | | OF THE | | | EPSS TO PERFORM IS LESS CRITICAL TO HUMAN LIFE AND | | | SAFETY. | | | 4.4.3 ALL EQUIPMENT SHALL BE PERMANENTLY INSTALLED. | | | 4.4.4* LEVEL 1 AND LEVEL 2 SYSTEMS SHALL ENSURE THAT | | | ALL LOADS | | | SERVED BY THE EPSS ARE SUPPLIED WITH ALTERNATE POWER | | | THAT | | | MEETS ALL THE FOLLOWING CRITERIA: | | | (1) OF A QUALITY WITHIN THE OPERATING LIMITS OF THE | | | LOAD | | | (2) FOR A DURATION SPECIFIED FOR THE CLASS AS DEFINED | | | IN TABLE | | | 4.1(A) | | | (3) WITHIN THE TIME SPECIFIED FOR THE TYPE AS DEFINED | | | IN TABLE | | | 4.1(B) | | | | | | THE GENERATOR SHALL BE INSTALLED UNDER SEPARATE SHOP | | | DRAWINGS. | | | | | | PLEASE REVIEW AND PROVIDE DETAILS AND A NOTE OF | | | ACKNOWLEDGEMENT. | | | | | | | | | | | | 19) SHEET A 1.108 & ALS 1.108 - STAIRWAYS # 5 & 9 | | | INDICATE EXIT SIGNS AND OPENINGS; HOWEVER, THERE ARE NO | | | DOORS INDICATED ON THESE SHEETS OR ANY OTHER SHEET FOR | | | THESE OPENINGS. | | | | | | PER NFPA 101 CH 7, EXIT STAIRWELLS ARE TO BE PROTECTED. | | | | | | 7.2.2.5 ENCLOSURE AND PROTECTION OF STAIRS. | | | 7.2.2.5.1 ENCLOSURES. | | | 7.2.2.5.1.1 ALL INSIDE STAIRS SERVING AS AN EXIT OR | | | EXIT COMPONENT | | | SHALL BE ENCLOSED IN ACCORDANCE WITH 7.1.3.2. | | | | | | 7.1.3.2 EXITS. | | | 7.1.3.2.1 WHERE THIS CODE REQUIRES AN EXIT TO BE | | | SEPARATED FROM OTHER | | | PARTS OF THE BUILDING, THE SEPARATING CONSTRUCTION | | | SHALL MEET THE | | | REQUIREMENTS OF SECTION 8.2 AND THE FOLLOWING: | | | (1) *THE SEPARATION SHALL HAVE A MINIMUM 1-HOUR FIRE | | | RESISTANCE | | | RATING WHERE THE EXIT CONNECTS THREE OR FEWER STORIES. | | | | | | (8) OPENINGS IN THE SEPARATION SHALL BE PROTECTED BY | | | FIRE DOOR | | | ASSEMBLIES EQUIPPED WITH DOOR CLOSER COMPLYING WITH | | | 7.2.1.8. | | | | | | | | | PLEASE REVIEW AND CORRECT OR JUSTIFY. | | | | | | | | | | | | | | | 20) OUTDOOR TERRACE/POOL/ROOFTOP AREAS - THERE DOES NOT | | | APPEAR TO BE ANY BBQ'S PROPOSED FOR THIS PROJECT; | | | HOWEVER, SHOULD THEY BE A FUTURE INSTALL THEY SHALL | | | COMPLY WITH THE ALL APPLICABLE CODES INCLUDING NFPA 1 | | | | | | 10.10.6 COOKING EQUIPMENT. | | | 10.10.6.1 FOR OTHER THAN ONE- AND TWO-FAMILY DWELLINGS, | | | NO | | | HIBACHI, GRILL, OR OTHER SIMILAR DEVICES USED FOR | | | COOKING, HEATING, | | | OR ANY OTHER PURPOSE SHALL BE USED OR KINDLED ON ANY | | | BALCONY, | | | UNDER ANY OVERHANGING PORTION, OR WITHIN 10 FT (3 M) OF | | | ANY | | | STRUCTURE. | | | 10.10.6.1.1 LISTED ELECTRIC PORTABLE, TABLETOP GRILLS, | | | NOT TO EXCEED | | | 200 SQUARE INCHES OF COOKING SURFACE, OR OTHER SIMILAR | | | APPARATUS | | | SHALL BE PERMITTED. | | | 10.10.6.2 FOR OTHER THAN ONE- AND TWO-FAMILY DWELLINGS, | | | NO | | | HIBACHI, GRILL, OR OTHER SIMILAR DEVICES USED FOR | | | COOKING SHALL BE | | | STORED ON A BALCONY. | | | 10.10.6.3* LISTED EQUIPMENT PERMANENTLY INSTALLED IN | | | ACCORDANCE | | | WITH ITS LISTING, APPLICABLE CODES, AND MANUFACTURER?S | | | INSTRUCTIONS | | | SHALL BE PERMITTED. | | | 10.10.7 INSTALLATION OF PATIO HEATERS. THE INSTALLATION | | | OF PATIO | | | HEATERS SHALL COMPLY WITH 69.3.11. | | | | | | SHOULD THERE BE REVISIONS, BBQ'S SHALL BE CLEARLY | | | IDENTIFIED, LOCATED PER THE CODE AND ALL MANUFACTURES | | | SPECIFICATIONS ATTACHED, AND COMPLY WITH THOSE | | | SPECIFICATIONS, PRIOR TO ANY APPROVAL. | | | | | | PLEASE ENSURE COMPLIANCE. | | | | | | | | | | | | | | | 21) RESIDENTIAL TOWER SHEETS - AT THE FIRE SERVICE | | | ELEVATOR EXIT DOOR TO THE STARIWELL THE DOOR OPENS INTO | | | THE REQUIRED EGRESS OF THE CORRIDOR DOOR AND VISA A | | | VERSA. | | | | | | PER NFPA 101, CH 7 | | | | | | 7.2.1.4.3* DOOR LEAF ENCROACHMENT. | | | 7.2.1.4.3.1 DURING ITS SWING, ANY DOOR LEAF IN A MEANS | | | OF EGRESS | | | SHALL LEAVE NOT LESS THAN ONE-HALF OF THE REQUIRED | | | WIDTH OF AN AISLE, | | | A CORRIDOR, A PASSAGEWAY, OR A LANDING UNOBSTRUCTED, | | | UNLESS BOTH | | | OF THE FOLLOWING CONDITIONS ARE MET: | | | (1) THE DOOR OPENING PROVIDES ACCESS TO A STAIR IN AN | | | EXISTING | | | BUILDING. | | | (2) THE DOOR OPENING MEETS THE REQUIREMENT OF | | | 7.2.1.4.3.2. | | | 7.2.1.4.3.2 WHEN FULLY OPEN, ANY DOOR LEAF IN A MEANS | | | OF EGRESS | | | SHALL NOT PROJECT MORE THAN 7 IN. (180 MM) INTO THE | | | REQUIRED WIDTH | | | OF AN AISLE, A CORRIDOR, A PASSAGEWAY, OR A LANDING, | | | UNLESS THE DOOR | | | LEAF IS EQUIPPED WITH AN APPROVED SELF-CLOSING DEVICE | | | AND IS NOT | | | REQUIRED BY THE PROVISIONS OF 7.2.1.4.2 TO SWING IN THE | | | DIRECTION OF | | | EGRESS TRAVEL. | | | | | | PLEASE REVIEW AND CORRECT OT JUSTIFY/CLARIFY WITH | | | SPECIFIC CODE REFERENCES. | | | | | | | | | | | | | | | | | | 23) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET | | | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE | | | ABOVE. | | | | | | | | | | | | | | | 24) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE | | | RE-SUBMITTAL OF THE ABOVE. | | | | | | | | | | | | | | | PETER LEDUC | | | FIRE MARSHAL | | | 561-804-4709 | | | [email protected] | | | | | | |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
P |
Date |
2018-11-27 |
|
|
Cont ID |
|
| Sent By |
pleduc |
Date |
2018-11-27 |
Time |
|
Rev Time |
0.00 |
| Received By |
pleduc |
Date |
2018-11-05 |
Time |
09:54 |
Sent To |
|
|
| Notes |
| 2018-11-27 16:08:49 | FIRE REVIEWED THIS SUBMITTAL WITH THE UNDERSTANDING | | | THAT IT WOULD BE CURSORY IN SUPPORT OF A FOUNDATION | | | ONLY SUBMITTAL. | | | | | | FIRE APPROVES THIS SUBMITTAL FOR FOUNDATION ONLY AND | | | THAT FUTURE COMPLETE PLANS WILL BE SUBMITTED FOR THE | | | REMAINDER OF THE PROPOSED PROJECT. | | | | | | PETER LEDUC | | | FIRE MARSHAL | | | 561-804-4709 | | | [email protected] | | | |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
5 |
Status |
P |
Date |
2021-08-16 |
|
|
Cont ID |
|
| Sent By |
lcrespo |
Date |
2021-08-16 |
Time |
12:00 |
Rev Time |
0.00 |
| Received By |
lcrespo |
Date |
2021-08-16 |
Time |
12:00 |
Sent To |
|
|
| Notes |
| 2021-08-16 12:31:46 | 08/13/21 REVIEWED FOR CODE COMPLIANCE (GAS) | | | | | | BY REVIEWING THE PLANS / SPECIFICATIONS FOR CODE | | | COMPLIANCE DOES NOT RELIEVE THE OWNER, DESIGN | | | PROFESSIONAL, CONTRACTORS, OR THEIR REPRESENTATIVES | | | FROM THE RESPONSIBILITY TO COMPLY WITH ALL LOCAL, | | | STATE, AND NATIONAL CODES AND STANDARDS IN EFFECT AT | | | THE TIME OF PERMIT ISSUANCE. OUR REVIEW IS NOT A CHECK | | | OF EVERY ITEM AND DOES NOT PREVENT THIS DEPARTMENT FROM | | | REQUIRING CORRECTIONS DURING CONSTRUCTION. ANY CHANGES | | | / ALTERATIONS TO APPROVED PLANS SHALL BE APPROVED TO | | | AVOID VOIDING OF THE PERMIT. | | | | | | LUIS A. CRESPO | | | PLUMBING PLAN EXAMINER / INSPECTOR | | | EMAIL: [email protected] OFFICE: 561 805-6720 | | | |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
4 |
Status |
F |
Date |
2021-06-21 |
|
|
Cont ID |
|
| Sent By |
lcrespo |
Date |
2021-06-21 |
Time |
15:46 |
Rev Time |
0.00 |
| Received By |
lcrespo |
Date |
2021-06-14 |
Time |
14:32 |
Sent To |
|
|
| Notes |
| 2021-06-21 15:48:10 | 06/21/21 4TH GAS REVIEW**DENIED** WITH COMMENTS | | | | | | NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS | | | TIME, AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE | | | GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS. | | | | | | | | | 1. DONE. | | | | | | 2. DONE. | | | | | | 3. DONE. | | | | | | 4. DONE. | | | | | | 5. DONE. | | | | | | 6. DONE. | | | | | | 7. DONE. | | | | | | 8. THERE IS CLOUD AND NO INFORMATION, SO PLEASE | | | CORRECT. SHEET P.700, KEYNOTE #3 - IDENTIFY THIS FUTURE | | | LINE/SYSTEM ON THE GAS RISER PER THE WPB AMENDMENTS TO | | | FBC SEC. 107.2.1. | | | | | | 9. DONE. | | | | | | 10. DONE. | | | | | | 11. THIS COMMENT HAS NOT BEEN ADDRESSED, AND BOTH | | | SHEETS DO NOT MATCH; SHEET P.700 - KEYNOTE #14 SHOWS | | | THE GAS LINE WITH 579 CFH AND SHT. P.700A, DETAIL #2 | | | SHOWS 500 CFH. CLARIFY. | | | | | | 12. DONE. | | | | | | 13. ON SHEET 700A DETAIL #6, THE LONGEST RUN IS NOT | | | CLEAR THE LONGEST RUN. IS TO THE PRV REGULATOR OR THE | | | BOILER. THIS NEEDS TO BE KNOWN AS THE LONGEST RUN | | | DETERMINE THE SIZE CALCULATION, SO PLEASE CLARIFY PER | | | THE WPB AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION | | | ON CONSTRUCTION DOCUMENTS. | | | | | | 14. ON SHEET 700A DETAIL #5, SIZE THE SHORT SECTION OF | | | THE GAS MAIN LINE BETWEEN THE 4 INCH LINE AND THE 2 ? | | | INCH LINE NEEDS A SIZE FIELD CLARIFICATION, PLEASE | | | PROVIDE PER THE WPB AMENDMENTS TO THE FBC SEC. 107.2.1 | | | INFORMATION ON CONSTRUCTION DOCUMENTS. | | | | | | 15. DONE. | | | | | | 16. DONE. | | | | | | 17. DONE. | | | | | | 18. DONE. | | | | | | 19. DONE. | | | | | | WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION & | | | REMOVE ANY VOIDED SHEETS & REPLACE ANY NECESSARY PAGES. | | | A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW | | | COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION | | | MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE | | | THE CHANGES CAN BE FOUND, WILL HELP EXPEDITE YOUR | | | PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. | | | | | | HTTPS://CODES.ICCSAFE.ORG/CODES/FLORIDA | | | | | | LUIS A. CRESPO | | | PLUMBING PLAN EXAMINER / INSPECTOR | | | EMAIL: [email protected] OFFICE: 561 805-6720 | | | | | | |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
3 |
Status |
F |
Date |
2021-02-19 |
|
|
Cont ID |
|
| Sent By |
tklarge |
Date |
2021-02-19 |
Time |
09:48 |
Rev Time |
0.00 |
| Received By |
tklarge |
Date |
2021-02-18 |
Time |
11:51 |
Sent To |
|
|
| Notes |
| 2021-02-18 12:49:05 | 1) SHT. P.509 - DETAIL #2 SHOWS A 1 INCH GAS LINE DOWN | | | TO AN AHU. WHERE IS THIS AHU LOCATED? THE GAS LINE | | | SHOWS A SHUTOFF VALVE ON THE GAS LINE. THE SHUTOFF | | | VALVE SHALL BE LOCATED IN THE SAME ROOM AS THE | | | APPLIANCE AND WITHIN 6 FEET OF THE APPLIANCE PER | | | FBC-FUEL GAS SEC.409.5.1. CLARIFY. | | | 2) SHT. P.700 - KEYNOTE #7 - PROVIDE A REFERENCE RISER | | | TAG FOR THIS LINE OR PROVIDE A SHEET NUMBER AS TO WHERE | | | THE CONTINUATION OF THIS LINE CAN BE FOUND AND PROVIDE | | | A COMPLETE GAS RISER FOR THIS AREA SHOWING ALL PIPE | | | SIZES, BTU LOADS OF APPLIANCES/EQUIPMENT, GAS PRESURE | | | OF SYSTEM, VALVES, LONGEST RUN FROM POINT OF DELIVRY, | | | ETC. WPB AMEND. TO FBC SEC. 107.2.1,107.3.5.1.5. | | | 3) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE GAS | | | APPLIANCES/EQUIPMENT IN THE RESTAURANT. WPB AMEND. TO | | | FBC SEC. 107.2.1. | | | 4) SHT. P.700 - KEYNOTE #11 - SUBMIT A COMPLETE GAS | | | RISER FOR THIS AREA EVEN THOUGH IT IS FOR FUTURE OR THE | | | LOAD IS ESTIMATED. WPB AMEND. TO FBC SEC. 107.2.1, | | | 107.3.5.1.5. | | | 5) WHERE CONNECTED TO RIGID PIPING, A UNION SHALL BE | | | INSTALLED WITHIN 1 FOOT OF EITHER SIDE OF THE | | | REGULATORS PER FBC-FUEL GAS SEC.410.2 (7). | | | 6) THE INSTALLATION OF THE MP REGULATORS SHALL ALSO | | | COMPLY WITH FBC-FUEL GAS SEC.410.2 ITEMS #1-#6. | | | 7) SHT. P.700 - NATURAL GAS SYSTEMS TABLE - SYSTEM #1 | | | SHOWS THE MAXIMUM BTU LOAD AS 4854 CFH BUT THE GAS | | | RISER ON THE SAME PAGE SHOWS THE BTU LOAD AS 3229 CFH. | | | CLARIFY. | | | 8) SHT. P.700 - KEYNOTE #3 - IDENTIFY THIS FUTURE | | | LINE/SYSTEM ON THE GAS RISER.WPB AMEND. TO FBC SEC. | | | 107.2.1. | | | 9) SHT. P.700 - NATURAL GAS SYSTEMS TABLE - GAS SYSTEM | | | #5 - THE TABLE NOTES THE BTU LOAD AS 3,650 CFH BUT THE | | | RISER SHOWS 3,500 CFH. CLARIFY.. | | | 10) SHT. P.700 - KEYNOTE #11 - PROVIDE A REFERENCE | | | RISER TAG FOR THIS LINE OR PROVIDE A SHEET NUMBER AS TO | | | WHERE THE CONTINUATION OF THIS LINE CAN BE FOUND AND | | | PROVIDE A COMPLETE GAS RISER FOR THIS AREA SHOWING ALL | | | PIPE SIZES, BTU LOADS OF APPLIANCES/EQUIPMENT, GAS | | | PRESURE OF SYSTEM, VALVES, LONGEST RUN FROM POINT OF | | | DELIVERY, ETC. WPB AMEND. TO FBC SEC. 107.2.1, | | | 107.3.5.1.5. | | | 11) SHT. P.700 - KEYNOTE #14 SHOWS THE GAS LINE WITH | | | 579 CFH AND SHT. P.700A, DETAIL #2 SHOWS 500 CFH. | | | CLARIFY. | | | 12) SHT. P.700 - THERE ARE RISER TAGS AT HE GAS RISER | | | ON LEVELS 6,7, & 8 WITH NO DRAWING LOCATIONS/SHEET | | | NUMBERS ON THE RISER TAGS. CLARIFY. | | | 13) SHT. P.700A - DETAIL #6 SHOWS THE THE LONGEST RUN | | | AS 550 FEET.THIS LINE IS UNDERSIZED AS DESIGNED. A | | | MAXIMUM OF 556,000 BTU'S CAN BE ACCOMMODATED ON A 2 1/2 | | | INCH LINE AT A DISTANCE OF 550 FEET IN ACCORDANCE WITH | | | FBC-FUEL GAS TABLE 402.4(1). CLARIFY. | | | 14) SHT. P.700A - DETAIL #5 - SIZE THE SHORT SECTION OF | | | THE GAS MAIN LINE BETWEEN THE 4 INCH LINE AND THE 2 1/2 | | | INCH LINE. SIZING SHALL COMPLY WITH FBC-FUEL GAS TABLE | | | 402.4 (1). 2ND REQUEST. CLARIFY. | | | 15) SHT. P.700A - DETAILS # 1- #6 - THERE IS A NOTE ON | | | ALL THE DETAILS THAT REFER TO DETAIL #10 ON SHT.P.802 | | | BUT THERE IS NO SUCH DETAIL ON THIS SHEET. 2ND | | | REQUEST.CLARIFY. THE RESPONSE NARRATIVE STATES THE | | | DETAIL IS ON SHT. P.804, DETAIL #10, BUT THAT DETAIL IS | | | FOR A THERMOSTATIC MIXING VALVE AND IS NOT APPLICABLE. | | | 16) SHT. P.700A - DETAILS #1 & #3 - NOTE #4 STATES TO | | | REFER TO SHT. P.802, DETAIL #6 FOR THE WATER HEATER | | | DETAIL. DETAIL #6 ON SHT.P.802 IS FOR A CONDENSATE | | | DRAIN. 2ND REQUEST. CLARIFY. | | | 17) SHT. P.700A - PLACE THE SPECIFIC SHEET NUMBER OF | | | THE ORIGIN/CONTINUATION OF THE GAS SUPPLY LIINES TO THE | | | APPLIANCES/EQUIPMENT ON EACH GAS RISER DETAIL. 2ND | | | REQUEST. | | | 18) SHT. P.804 - SUBMIT THE SPECIFICATIONS/INSTALLATION | | | MANUAL FOR THE GAS DETECTION SYSTEM AND REFERENCE THE | | | STANDARD ON WHICH THIS SYSTEM IS DESIGNED. 2ND | | | REQUEST.WPB AMEEND. TO FBC SEC.107.2.1. | | | 19) SHT. P.700 - THERE ARE FOUR RISER TAGS ON THIS PAGE | | | IDENTIFIED AS G/H1, G/H2, G/H3 AND G/R1 WITH NO DRAWING | | | LOCATION ON THESE RISER TAGS. CLARIFY. | | | | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | PLUMBING PLAN REVIEW | | | 561-805-6692 | | | [email protected] | | | | | | |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
2 |
Status |
F |
Date |
2020-03-28 |
|
|
Cont ID |
|
| Sent By |
tklarge |
Date |
2020-03-28 |
Time |
10:06 |
Rev Time |
0.00 |
| Received By |
tklarge |
Date |
2020-03-28 |
Time |
07:22 |
Sent To |
|
|
| Notes |
| 2020-03-28 09:34:43 | 1) SHT. P.700A - THERE IS A NOTE ON ALL THE DETAILS | | | THAT STATES "REFER TO SHT. P.802, DETAIL #10 FOR | | | SEDIMENT TRAP DETAIL." THERE IS NO DETAIL #10 ON SHT. | | | P.802 ? CLARIFY. | | | 2) 2) SHT. P700A - DETAIL #5 - SIZE THE MAIN LINE | | | BETWEEN THE 4 INCH AND 2 1/2 INCH SECTIONS OF PIPE THAT | | | SUPPLIES WATER HEATERS 1B & 1C. | | | 3) SHT. P700A - DETAILS #1 & #3 - NOTE #4 - THERE IS | | | NOTE ON THESE DETAILS THAT REFERS TO SHT. P.802 FOR | | | WATER HEATER DETAIL. THIS DETAIL HAS NOTHING TO DO WITH | | | GAS WATER HEATERS. THE CORRECT SHEET IS P.804.PLEASE | | | REVISE THE NOTE ON THE PLAN. | | | 4) SHT. P.803 - THE GAS WATER HEATER SCHEMATICS REFER | | | TO THE HVAC DRAWINGS FOR FLUE INFORMATION FOR THE WATER | | | HEATERS. PLACE THE SPECIFIC MECHANICAL SHEET NUMBERS ON | | | THE DRAWINGS WHERE THE INFORMATION CAN BE FOUND. WPB | | | AMEND. TO FBC SEC. 107.2.1. | | | 5) SHT. P700 - KEYNOTE #8 - SHOWS THE CFH AS 2,012 BUT | | | THE GAS RISER SHOWS THE CFH AS 3,075. IF THIS NUMBER OF | | | 3, 075 IS CORRECT, THEN THE REST OF THE CFH ON THE GAS | | | RISER IS WRONG. CLARIFY. | | | 6) SHT. P700 - THE NUMBERING ON THE GAS TAGS ON THE GAS | | | RISER ARE VERY LIGHT AND ALMOST ILLEGIBLE. PLEASE | | | REVISE. | | | 7) SHT. P.804 - SUBMIT ADDITIONAL INFORMATION | | | (SPECIFICATIONS/ INSTALLATION MANUAL) FOR THE GAS | | | DETECTION SYSTEM AND REFERENCE THE STANDARD ON WHICH | | | THIS SYSTEM IS DESIGNED. WPB AMEND. TO FBC SEC. | | | 107.2.1. | | | 8) SHT. P.700A - PLACE THE SPECIFIC SHEET NUMBER IN THE | | | GAS ISOMETRICS FOR THE ORIGINATING POINTS OF THE GAS | | | LINES. WPB AMEND. TO FBC SEC. 107.2.1, 107.3.5.1.5. | | | 9) ALL GAS EQUIPMENT SHALL BE LISTED AND LABELED PER | | | FBC-FUEL GAS SEC.301.3. | | | 10) SUBMIT CALCULATIONS FOR COMBUSTION AIR. PROVIDE | | | VERIFICATION & CALCULATIONS AS TO HOW THE REQUIREMENTS | | | ARE BEING MET. PROVIDE THE CODE SECTIONS FROM THE GAS | | | CODE THAT YOU ARE USING IN THE DESIGN OF THE COMBUSTION | | | AIR REQUIREMENTS PER THE 2014 FBC-FUEL GAS CODE | | | SEC.304.1, | | | 11) SUBMIT DETAILS FOR THE TYPE OF GAS VENT MATERIAL, | | | LOCATION, SIZE, TERMINATION POINT, HEIGHT ABOVE ROOF, | | | AND ANCHORING DETAILS OF THE GAS VENTS. FBC-FUEL GAS | | | SECS.502 THROUGH 505. | | | 12) THE RESPONSE NARRATIVE STATES THAT A PDF PACKAGE | | | HAS BEEN CREATED AND SUBMITTED ALONG WITH REQUESTED | | | DRAWINGS TO COMPLY WITH PREVIOUS COMMENT # 4 FROM THE | | | GAS REVIEW FROM 4/9/19 REQUESTING TWO COPIES OF | | | MANUFACTURER?S SPECIFICATIONS AND INSTALLATION MANUALS | | | FOR ALL GAS EQUIPMENT BUT THERE ARE NO SUCH DOCUMENTS | | | IN THIS SUBMITTAL. CLARIFY. | | | 13) SHT. P.509 - DETAIL #2 SHOWS THE SHUTOFF VALVE | | | OUTSIDE THE ROOM WHERE THE POOL HEATER IS LOCATED. | | | CLARIFY. | | | 14) SHT. P.105C SHOWS VENT PIPING FROM THE GAS | | | REGULATOR RUNNING FOR AN EXTENSIVE DISTANCE TO ITS | | | TERMINATION POINT. VENT PIPING SHALL NOT EXCEED THE | | | LENGTH SPECIFIED IN THE REGULATOR MANUFACTURER?S | | | INSTRUCTIONS. SUBMIT THE VENT INSTALLATION INSTRUCTIONS | | | FOR ALL THE REGULATORS TO BE USED. FBC-FUEL GAS SEC. | | | 410.3.1. | | | 15) SHOW THE SIZE OF THE GAS REGULATOR VENTS ON THE | | | PLANS. WPB AMEND. TO FBC SEC. 107.2.1. | | | | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | PLUMBING PLAN REVIEW | | | 561-805-6692 | | | [email protected] | | | | | | | | | | | | |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
1 |
Status |
F |
Date |
2019-04-09 |
|
|
Cont ID |
|
| Sent By |
gjohnson |
Date |
2019-04-09 |
Time |
10:28 |
Rev Time |
0.00 |
| Received By |
gjohnson |
Date |
2019-04-09 |
Time |
10:28 |
Sent To |
|
|
| Notes |
| 2019-04-09 10:28:30 | 1ST REVIEW: 18100540 | | | 2017 FLORIDA BUILDING CODE 6TH EDITION | | | 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION | | | 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH | | | EDITION | | | 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION | | | 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION | | | 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH | | | EDITION | | | 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH | | | EDITION | | | | | | GAS COMMENTS: | | | | | | 1. SHT. P-700 SHOW ON THE ISOMETRIC DRAWING THE PIPING | | | UP TO THE CONNECTION OF EVERY GAS APPLIANCE INCLUDING | | | VALVES, REGULATOR AND DRIP LEG OR PROVIDE A DETAIL FOR | | | EACH APPLIANCE OR GROUP WITH A CORRESPONDING TAG TO THE | | | OVERALL ISOMETRIC. PER WPB AMEND TO FBC 107.2.1 | | | 2. SUBMIT TWO COPIES OF A DETAIL SHOWING THE TYPE OF | | | VENT, LOCATION, SIZE, TERMINATION POINT, HEIGHT ABOVE | | | THE ROOF AND ANCHORING DETAILS OF THE GAS VENT(S) PER | | | 2017 FBC-FUEL GAS SECS. 502 THRU 505 OR 2017 FBC-RES. | | | SEC.G2426 THROUGH G2439. | | | 3. SUBMIT CALCULATIONS FOR COMBUSTION AIR PER THE 2017 | | | FBC-FUEL GAS CODE SEC.304.1, 614.6 (CLOTHES DRYERS) OR | | | 2017 FBC-RES. SEC.G 2407.1 AND G2439.4 (CLOTHES | | | DRYERS). | | | 4. SUBMIT TWO COPIES OF THE MANUFACTURER?S | | | SPECIFICATION SHEETS / INSTALLATION MANUAL FOR ALL GAS | | | EQUIPMENT TO VERIFY COMPLIANCE WITH STANDARDS NFPA 54, | | | NFPA 58, AND FBC-2017 FUEL GAS CODE SEC. 402.2, AND | | | 301.3 OR 2017 FBC-RES. SEC. G2404.3. GAS APPLIANCES | | | SHALL BE LISTED AND LABELED. THE INSTALLATION MANUALS | | | FOR ALL GAS APPLIANCES / EQUIPMENT SHALL BE ONSITE AT | | | THE TIME OF INSPECTION. FGC SEC.305.1, FBC-RES. | | | SEC.G2408.1. | | | 5. SUBMIT MANUFACTURER?S SPECIFICATIONS AND | | | INSTALLATION INSTRUCTIONS FOR THE PRESSURE REGULATORS. | | | REGULATORS INSTALLED ON THE EXTERIOR OF THE BUILDING | | | SHALL BE APPROVED FOR OUTDOOR INSTALLATION. IDENTIFY ON | | | THE SPECIFICATION SHEETS WHICH MODEL REGULATOR IS BEING | | | INSTALLED AND THE ORIFICE SIZE TO ENSURE THE REGULATOR | | | CAN ACCOMMODATE THE BTU LOAD THROUGH THE REGULATOR.2017 | | | FGC SEC.410.1, 2017 FBC-RES. SEC. G2421.1. | | | 6. SHOW DISTANCE BETWEEN 2ND STAGE REGULATOR AND | | | APPLIANCE SIZE AND TYPE OF PIPE. PER WPB AMEND TO FBC | | | 107.2.1 | | | 7. GAS SYSTEM # 3 SHALL BE MARKED FOR REFERENCE ONLY OR | | | PROVIDE PIPE SIZE, TYPE, LENGTH OF RUN AND BTU LOAD. | | | PER 2017 FBC-FUEL GAS, SECS. 402.4.1, 402.4.2. OR 2017 | | | FBC-R SEC. G2413.4.1, G2413.4.2. | | | | | | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT | | | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID | | | THE PREVIOUSLY REVIEWED SHEETS. | | | | | | GEORGE JOHNSON | | | PLUMBING PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | 561-805-6711 | | | [email protected] |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
7 |
Status |
N |
Date |
2021-09-08 |
|
|
Cont ID |
|
| Sent By |
cpuell |
Date |
2021-09-08 |
Time |
08:59 |
Rev Time |
0.00 |
| Received By |
cpuell |
Date |
2021-09-02 |
Time |
09:04 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
6 |
Status |
N |
Date |
2021-08-30 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2021-08-30 |
Time |
08:07 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2021-08-11 |
Time |
09:39 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
5 |
Status |
N |
Date |
2021-06-22 |
|
|
Cont ID |
|
| Sent By |
lmarchan |
Date |
2021-06-22 |
Time |
09:01 |
Rev Time |
0.00 |
| Received By |
lmarchan |
Date |
2021-05-17 |
Time |
15:41 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
4 |
Status |
N |
Date |
2021-03-04 |
|
|
Cont ID |
|
| Sent By |
lmarchan |
Date |
2021-03-04 |
Time |
16:41 |
Rev Time |
0.00 |
| Received By |
lmarchan |
Date |
2020-12-22 |
Time |
17:06 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2020-03-30 |
|
|
Cont ID |
|
| Sent By |
lmarchan |
Date |
2020-03-30 |
Time |
10:04 |
Rev Time |
0.00 |
| Received By |
lmarchan |
Date |
2020-02-10 |
Time |
12:18 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2019-04-29 |
|
|
Cont ID |
|
| Sent By |
cpuell |
Date |
2019-04-29 |
Time |
12:36 |
Rev Time |
0.00 |
| Received By |
cpuell |
Date |
2019-02-26 |
Time |
07:42 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2018-11-29 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2018-11-29 |
Time |
16:01 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2018-10-24 |
Time |
08:08 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
IMPACT |
COUNTY IMPACT FEES |
| Rev No |
1 |
Status |
P |
Date |
2019-04-30 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2019-04-30 |
Time |
11:00 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2019-03-18 |
Time |
12:52 |
Sent To |
|
|
| Notes |
| 2019-04-30 11:01:27 | SEE IMPACT FEE REVIEW UNDER STRUCTURE REVISION 19020102 | | | | | 2019-03-18 12:53:08 | 3/18/19 SENT EMAIL TO IMPACT FEE OFFICE. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
5 |
Status |
P |
Date |
2021-08-16 |
|
|
Cont ID |
|
| Sent By |
medwards |
Date |
2021-08-16 |
Time |
09:10 |
Rev Time |
0.00 |
| Received By |
medwards |
Date |
2021-08-16 |
Time |
07:54 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
4 |
Status |
F |
Date |
2021-06-10 |
|
|
Cont ID |
|
| Sent By |
medwards |
Date |
2021-06-10 |
Time |
13:12 |
Rev Time |
0.00 |
| Received By |
medwards |
Date |
2021-06-10 |
Time |
13:12 |
Sent To |
|
|
| Notes |
| 2021-06-10 13:12:17 | 4TH REVIEW FBC-2020 MECHANICAL | | | PERMIT-18100540 | | | | | | CODES IN EFFECT: | | | | | | FBC B- FLORIDA BUILDING CODE | | | FBC M- FLORIDA MECHANICAL CODE | | | FBC EC- FLORIDA ENERGY CONSERVATION | | | FBC FG- FLORIDA FUEL GAS | | | FBC EX- FLORIDA EXISTING BUILDING CODE | | | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE | | | FS- FLORIDA STATUTES | | | FAC- FLORIDA ADMINISTRATIVE CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) PLEASE ADDRESS NOTE (3) OF THE PREVIOUS COMMENTS, | | | THERE STILL IS NO SHEET MP.002 WHICH IS SUPPOSE TO SHOW | | | THE REMOTE FUEL FILL STATION AND FILL PIPE. | | | | | | 2) SHEET M-715: DRYER EXHAUST RISER R3 AND R14 STILL | | | APPEAR TO NOT MEET FBC M 504.8 (4) | | | | | | 3) PLEASE SEE NOTE (5) OF THE PREVIOUS COMMENTS: SHEET | | | M.715 PLEASE SHOW THAT THE EXHAUST FAN FOR THE DRYER | | | EXHAUST SUB DUCT MEETS FBC M 504.8 (5). | | | | | | 4) PLEASE SEE COMMENT (6) OF PREVIOUS COMMENTS: SHEET | | | M-715- PLEASE SHOW THAT THE EXHAUST FAN FOR THE DRYER | | | SUB DUCT MEETS FBC M 504.8 (8) | | | | | | 5) WITH NO RESPONSE LETTER FROM THE DESIGNER I DO NOT | | | SEE THAT COMMENT (10) OF PREVIOUS COMMENTS HAS BEEN | | | ADDRESSED: PLEASE PROVIDE THE SPECIFIC DRYER | | | SPECIFICATIONS ALONG WITH THE DRYER DUCT LENGTHS. FBC M | | | 504.6.4 | | | | | | 6) | | | | | | BUILDERS RISK WITH X VENT | | | | | | THE INSTALLATION OF THE PROPOSED XVENT DRYER EXHAUST | | | TERMINATION PROCEEDS ENTIRELY AT THE RISK OF THE | | | DEVELOPER. IN ORDER TO SHOW THAT THE PRODUCT IS IN | | | COMPLIANCE WITH SECTION 504.4 OF FLORIDA BUILDING CODE, | | | MECHANICAL, AT A MEETING BETWEEN CITY OF WEST PALM | | | BEACH STAFF AND XVENT ON 5/27/21, XVENT PERSONNEL | | | AGREED TO CONDUCT AN AUDIT TO COMPARE LINT BUILD UP ON | | | TYPICAL LOUVERED BACKDRAFT DAMPER DRYER VENT | | | TERMINATIONS VERSUS BUILD UP ON THE FIXED LOUVERS OF | | | THE XVENT PRODUCT WHEN USED AS A DRYER EXHAUST | | | TERMINATION. THE PURPOSE OF THE AUDIT IS FOR XVENT TO | | | JUSTIFY THE USE OF THEIR PRODUCT BY SHOWING THAT THEIR | | | FIXED LOUVER PRODUCT IS NOT MORE SUSCEPTIBLE TO LINT | | | BUILD UP THAN A TYPICAL LOUVERED BACKDRAFT DAMPER DRYER | | | VENT TERMINATION. CODE COMPLIANCE WILL BE DETERMINED | | | BASED ON THE RESULTS OF THE AUDIT. | | | | | | | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM. | | | | | | MICHAEL EDWARDS | | | MECHANICAL EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL. 33401 | | | 561-805-6728 | | | [email protected] | | | |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
3 |
Status |
F |
Date |
2021-01-07 |
|
|
Cont ID |
|
| Sent By |
medwards |
Date |
2021-01-07 |
Time |
09:01 |
Rev Time |
0.00 |
| Received By |
medwards |
Date |
2021-01-07 |
Time |
09:01 |
Sent To |
|
|
| Notes |
| 2021-01-07 09:01:37 | 3RD REVIEW FBC-2017 MECHANICAL | | | PERMIT-18100540 | | | | | | CODES IN EFFECT: | | | | | | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 | | | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 | | | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION | | | 2017 | | | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 | | | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION | | | 2017 | | | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH | | | EDITION 2017 | | | FS- FLORIDA STATUTES | | | FAC- FLORIDA ADMINISTRATIVE CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH | | | EDITION 2017 | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) SHEET M.201A AND SHEET M.201B: PLEASE SHOW A DETAIL | | | OF THE MECHANICAL SYSTEM FOR THE EXIT PASSAGEWAY | | | SHOWING HOW IT MEETS FBC M 601.3. THE EXIT PASSAGEWAY | | | CANNOT BE SERVED BY A SYSTEM THAT SERVES ANY OTHER | | | AREA. | | | | | | 2) SHEET M.201A AND M.201B: PLEASE EXPLAIN THE INTAKE | | | DUCT IN ELECTRIC ROOM (E4) FBC 107.2.1 | | | | | | 3) PREVIOUS COMMENT #12- THE RESPONSE STATES TO LOOK ON | | | SHEET MP.002 FOR THE REMOTE FUEL FILL STATION AND FILL | | | PIPE. THERE IS NO MP.002 SHEET SUBMITTED IN THIS | | | PACKAGE. | | | | | | 4) SHEET M.715 AND SHEET M.707: THE DRYER EXHAUST | | | DIAGRAM SHOWS OFF SETS IN SEVERAL RISERS, PLEASE SHOW | | | HOW THIS WOULD MEET FBC M 504.8 (4) | | | | | | 5) SHEET M.715: PLEASE SHOW THAT THE EXHAUST FAN FOR | | | THE DRYER EXHAUST SUB DUCT MEETS FBC M 504.8 (5) | | | | | | 6) SHEET M.715: PLEASE SHOW THAT THE EXHAUST FAN FOR | | | THE DRYER SUBDUCT MEETS FBC M 504.8 (8) | | | | | | 7) SHEETS M.254- SHEET M.262: PLEASE REMOVE THE DRYER | | | BOOSTER FANS AS THERE IS NO REFERENCE OF THESE IN THE | | | 2014 FBC M. | | | | | | 8) THE DRYER EXHAUST DUCT MUST BE INSTALLED BY THE | | | MANUFACTURES INSTALLATION INSTRUCTIONS. THE TYPICAL | | | DRYER INSTALLATION MANUAL WILL ALLOW ONLY (4) 90 DEGREE | | | FITTINGS IN A SINGLE RUN. I DO SEE SEVERAL DRYER DUCT | | | WITH MORE THAN THE 4 90 DEGREE FITTINGS IN A SINGLE | | | RUN, PLEASE CORRECT THIS. FBC M 504.6.4.2 | | | | | | 9) PLEASE PROVIDE A LETTER FROM THE DRYER MANUFACTURER | | | STATING THAT THE X VENT DRYER EXHAUST TERMINATION IS | | | ALLOWED WITH EACH SPECIFIC DRYER. THE X VENT IS UNIQUE | | | IN THE FACT THAT IT USES BOTH THE BACK-DRAFT DAMPER AND | | | THE LOUVER. THE INSTALLATION MANUAL DOES NOT ADDRESS | | | THIS KIND OF INSTALLATION. WITH THE X VENT SYSTEM THE | | | BOX OF THE X VENT IS MOUNTED INTO THE EXTERIOR OF THE | | | WALL AND THE LOUVER IS FLUSH TO THE EXTERIOR WALL. THE | | | EXHAUST OF THE DRYER MUST TRAVEL THROUGH THE EXHAUST | | | DUCT, OPEN THE BACK-DRAFT DAMPER AND TRAVEL THROUGH THE | | | X VENT COVER (LOUVER) BEFORE IT IS EXHAUSTED TO THE | | | OUTDOORS. BECAUSE THIS PRODUCT USES BOTH THE BACK-DRAFT | | | DAMPER AND THE OUTER COVER OF THE BOX (LOUVER) INSTEAD | | | OF EITHER THE BACK-DRAFT DAMPER OR THE LOUVER AS | | | TYPICALLY SEEN IN THE MANUFACTURES INSTALLATION MANUAL | | | THE OUTER LOUVER IS A RESTRICTION THAT MUST BE | | | ADDRESSED. IN LIEU OF THE MANUFACTURES LETTER STATING | | | THE MAXIMUM DRYER EXHAUST DUCT TO BE USED WITH THE X | | | VENT SYSTEM THE ENGINEER OF RECORD MUST DETERMINE THE | | | AMOUNT OF RESTRICTION THIS CREATES AND THE EFFECT TO | | | THE DRYER EXHAUST DUCT LENGTH. THE ENGINEER OF RECORD | | | MUST SUBMIT THE CALCULATIONS AND PROVIDE MAX. EXHAUST | | | DRYER DUCT LENGTHS FOR EACH DRYER USED IN THIS PROJECT. | | | FBC M 504.8.4.2 | | | | | | 10) PLEASE PROVIDE THE SPECIFIC DRYER SPECIFICATIONS | | | ALONG WITH THE DRYER DUCT LENGTHS. FBC M 504.6.4 | | | | | | 11) SHEET M.205B; WHAT IS THE WATER HEATER INTAKE AND | | | EXHAUST PIPING MATERIAL? PLEASE PROVIDE THE | | | SPECIFICATIONS FOR THE MENTIONED FIRE WRAP MATERIAL | | | CALLED OUT ON THE DRAWING FOR THE SPECIFIC PIPING | | | MATERIAL OF THE INTAKE AND EXHAUST PIPING. FBC 107.2.1 | | | | | | 12) SHEET M.701; I DO NOT SEE THE MENTIONED SD?S AT THE | | | RETURN DUCT OF THE ERU-3 AND AHU-11 ON EACH LEVEL OF | | | OFFICE TOWER. PLEASE CLOUD THE SD?S TO CLEARLY SHOW THE | | | CHANGES. FBC 107.2.1 | | | | | | 13) SHEETS M.606-M.607; PLEASE IDENTIFY EACH VENT ZONE | | | IN THE OUTDOOR AIR CALCULATIONS TO MATCH THE TABLES | | | EITHER IN THE 2014 FBC M TABLE 403.3 OR ASHRAE 62.1 | | | TABLE 6.2.2.1 | | | | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT | | | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD | | | SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER | | | SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN | | | THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS | | | PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS | | | PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR | | | UPDATED. | | | | | | MICHAEL EDWARDS | | | MECHANICAL EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL. 33401 | | | 561-805-6728 | | | [email protected] | | | |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
F |
Date |
2020-03-10 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2020-03-10 |
Time |
18:05 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2020-02-26 |
Time |
13:34 |
Sent To |
|
|
| Notes |
| 2020-03-10 18:06:30 | 2ND REVIEW FBC-2014 MECHANICAL | | | PERMIT #18100540 | | | 550 N QUADRILLE BLVD | | | 3/2/20 | | | | | | CODES IN EFFECT: | | | | | | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2014 | | | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2014 | | | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION | | | 2014 | | | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2014 | | | FS- FLORIDA STATUTES | | | FAC- FLORIDA ADMINISTRATIVE CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH | | | EDITION 2017 | | | | | | 1) ENERGYGAUGE COMPLIANCE REPORT PAGE 47: THE COOLING | | | TOWER MUST MEET THE MINIMUM EFFICIENCY REQUIREMENT | | | LISTED IN TABLE C403.2.3(8) FBC EC. PLEASE CORRECT THE | | | N/A CHECKMARK. A) PLEASE NOTE THAT THE PLANS FOR THE | | | PROPOSED PROJECT ARE BEING DESIGNED IN ACCORDANCE WITH | | | THE FLORIDA BUILDING CODE- 2014 FIFTH EDITION. AS A | | | RESULT THE 2017 VERSION OF THE ENERGYGAUGE COMPLIANCE | | | SOFTWARE CANNOT BE USED. PLEASE SUBMIT THE 2014 | | | ENERGYGAUGE SOFTWARE VERSION. | | | | | | 2) THE STAIR PRESSURIZATION RATIONAL ANALYSIS SHALL BE | | | ELECTRONICALLY SIGNED AND SEALED BY THE ENGINEER WHO | | | PREPARED THE DOCUMENT- FL. STATUTE 471.025 AND SECTION | | | 61G15-23.005 FLORIDA ADMINISTRATIVE CODE. IN ADDITION, | | | THE ARCHITECT OF RECORD AND THE MECHANICAL ENGINEER OF | | | RECORD SHALL EACH PROVIDE A REVIEW AND APPROVAL STAMP | | | ON THE DOCUMENT- SECTION 107.2.1 WPB. PLEASE NOTE THAT | | | SPECIAL INSPECTION AND COMMISSIONING OF THE SYSTEMS | | | SHALL BE CONDUCTED IN ACCORDANCE WITH SECTION 909.18.1 | | | FBC B, AND A FINAL COMMISSIONING REPORT SHALL BE | | | PROVIDED TO THE CITY OF WEST PALM BEACH BUILDING | | | DIVISION AND THE WPB FIRE DEPARTMENT AS A CONDITION OF | | | RECEIVING A FINAL CERTIFICATE OF OCCUPANCY FOR THE | | | BUILDING- SEE SECTIONS 909.3 AND 909.18.8.1- 909.20 FBC | | | B. THE ENGINEER OF RECORD AND SMOKE CONTROL ARE ADVISED | | | TO LOOK AT THE ISSUES LISTED BELOW. | | | A) MISSING FROM THE REPORT IS A DETAILED NARRATIVE | | | DESCRIPTION OF HOW THE FIRE ALARM AND PRESSURIZATIONS | | | SYSTEMS IN THE TWO TOWERS AND PODIUM WILL COORDINATE | | | AND INTERACT TOGETHER UNDER EMERGENCY ALARM CONDITIONS. | | | FOR EXAMPLE- WILL ALL THE INTERIOR EXIT STAIRWAYS BE | | | PRESSURIZED IN THE TOWERS AND THE PODIUM IF AN ALARM | | | OCCURS IN JUST ONE AREA OF THE BUILDING SUCH AS THE | | | PODIUM OR ONE OF THE TOWERS, OR WILL JUST THE STAIRWAYS | | | IN THE AREA OF THE INCIDENT BE PRESSURIZED? | | | B) STAIR 1 HAS AN EXTENSION AT THE GROUND FLOOR THAT IS | | | MISLABELED AS A CORRIDOR, AND SHOULD BE LABELED AS AN | | | EXIT PASSAGEWAY- SECTION 1022.3.1 FBC B. THE PASSAGEWAY | | | SHALL BE PRESSURIZED IN THE SAME MANNER AS THE | | | STAIRWAY- SECTION 1022.10.1 FBC B. | | | C) ITEM 4.2 OF THE REPORT SPECIES SMOKE DETECTION AT | | | THE ENTRANCE TO THE PRESSURIZED STAIRWELLS, AND DUCT | | | SMOKE DETECTORS ARE SHOWN ON THE PLANS IN THE | | | PRESSURIZATION DUCTS AND FAN HOUSINGS. PLEASE NOTE THAT | | | SECTION 606.2.1 FBC M REQUIRES UL LISTED AND LABELED | | | DUCT SMOKE DETECTORS IN THE RETURN DUCTS OF AIR | | | DISTRIBUTION SYSTEMS, BUT NOT IN PRESSURIZATION SUPPLY | | | DUCTS. PLEASE PROVIDE A WRITTEN SEQUENCE OF OPERATION | | | FOR THE DETECTORS AND A PRODUCT SUBMITTAL. THE | | | SUBMITTAL SHALL INDICATE THE DEVICES ARE LISTED AND | | | LABELED FOR USE IN PRESSURIZATION SYSTEMS- SECTION | | | 107.2.1 WPB. | | | D) FIRE WRAPPING AND FLAMEBAR DUCTWORK ARE BEING USED | | | THROUGHOUT THE BUILDING TO PROVIDE THE REQUIRED 2-HR. | | | FIRE BARRIER ENCLOSURE FOR THE PRESSURIZATION DUCTS | | | THAT ARE CONNECTING THE O/A INLETS AND FANS TO THE | | | STAIRWAYS. 1) FIRE WRAP: PLEASE VERIFY AND ACKNOWLEDGE | | | IN THE ANALYSIS THAT THE WRAPPING HAS THE REQUIRED UL | | | LISTING AND LABELING TO PROVIDE THE REQUIRED FIRE | | | RESISTANCE PER SECTION 703.2.1 FBC B. 2) FLAMEBAR: | | | PROVIDE A COMPLETE FLAMEBAR DUCTWORK SUBMITTAL PACKAGE | | | INCLUDING UL LISTED ASSEMBLIES AND JOB-SPECIFIC | | | INSTALLATION DETAILS- JOINTS, CONNECTIONS, SUPPORTS. | | | PLEASE NOTE THAT THE MECHANICS ASSEMBLING THE DUCTWORK | | | SHALL BE CERTIFIED TO DO THE INSTALLATIONS AND THE | | | CERTS SHALL BE ONSITE AT TIME OF INSPECTION. | | | | | | 3) SHEETS M.606 & M.607: PLEASE PROVIDE INDIVIDUAL O/A | | | CFM TOTALS FOR THE OFFICE TOWER, HOTEL TOWER, AND | | | RESIDENTIAL TOWER AND PODIUM. | | | A) INDICATE WHAT THE "K" SYMBOL MEANS THAT IS SHOWN IN | | | THE ZONE POPULATION COLUMN OF THE SCHEDULES. | | | B) THE PROVIDED (ACTUAL OUTDOOR AIRFLOW RATE) CFMS IN | | | MANY OF THE ROOMS AND SPACES SHOWN IN THE TABLES IS | | | LESS THAN THE REQUIRED CFMS FOR EXAMPLE THE BALLROOM, | | | PREFUNCTION, CONFERENCE, RESIDENTIAL LOBBY, TENNIS | | | EVENT, MAIL, FITNESS, HOTEL ELEVATOR LOBBY ETC. PLEASE | | | CORRECT THE SCHEDULES- TABLE 403.3.1.1 FBC M. | | | C) PROVIDE VENTILATION CALCULATIONS FOR THE INDOOR | | | TENNIS COURTS AND THE INDOOR POOL- TABLE 403.3.1.1 FBC | | | M. | | | | | | 4) PLEASE NOTE THAT THE PLANS FOR THE PROPOSED PROJECT | | | ARE BEING DESIGNED IN ACCORDANCE WITH THE FLORIDA | | | BUILDING CODE- 2014 FIFTH EDITION. AS A RESULT, ALL | | | PREVIOUS REVIEW COMMENTS REQUIRING DUCT SMOKE DETECTORS | | | IN THE SUPPLY SYSTEMS OF THE AIR HANDLERS ARE NOT | | | APPLICABLE. WHERE REQUIRED, THE DUCT SMOKE DETECTORS | | | SHALL BE INSTALLED IN THE RETURN AIR SYSTEMS. | | | | | | PODIUM | | | | | | 5) M201, 202, 203, 204, 205: THE REVISED PLANS ARE | | | MISSING DUCT SIZES, AND LABELS FOR DUCTS, DIFFUSERS | | | RETURN GRILLS, VAV'S, AHU'S, SENSORS ETC.- SECTION | | | 107.2.1 WPB. | | | | | | 6) M201.A & ALSI.101: THE VESTIBULE AT STAIR #3 IS | | | NEITHER FIRE-RATED OR VENTILATED- TABLE 1028.1 FBC B | | | AND TABLE 403.3.1.1 FBC M. | | | | | | 7) M201.A: PROVIDE CONSTRUCTION DETAILS FOR THE | | | FIRE-RATED PRESSURIZATION DUCT ENCLOSURE AT STAIR #3- | | | SECTION 703.2.1 & 717.2.1 FBC B. | | | | | | 8) M201.B: SHOW THE FUTURE TERMINATION LOCATIONS AND | | | REQUIRED CLEARANCES FOR THE KITCHEN HOOD GREASE EXHAUST | | | DUCT, AND ALL OTHER KITCHEN EXHAUST DUCTS- SEE SECTION | | | 506 FBC M. | | | | | | 9) M201B: FIRE DAMPERS MISSING AT DUCTS PENETRATING THE | | | 1-HR FIRE RATED WALLS AT THE RECEIVING, LUGGAGE, | | | CORRIDOR 0141, OFFICE ROOM WALLS- SECTION 607.5.2 FBC | | | M. | | | | | | 10) M201.C: PROVIDE PRODUCT SUBMITTALS FOR THE DIESEL | | | FIRE PUMP AND THE PUMP EXHAUST DUCTWORK- SECTIONS 4.2 | | | AND 11.5.2.5 NFPA 20. PLEASE NOTE THAT THE SUBMITTALS | | | MAY BE DEFERRED BY REQUEST. A) SHOW THE LOCATION OF THE | | | PUMP IN THE ROOM AND REFER TO SECTION 11.3.2.4.3 NFPA | | | 20 FOR EXHAUST REQUIREMENTS FOR RADIATOR-COOLED | | | ENGINES. A DIRECT DUCT CONNECTION TO THE PUMP VIA A | | | FLEXIBLE SECTION MAY BE REQUIRED. B) PLEASE ADD NOTES | | | TO INDICATE THE VENTILATION SYSTEM FOR THE PUMP AS | | | DESIGNED WILL BE CAPABLE OF MAINTAINING A MAXIMUM | | | TEMPERATURE OF 120 DEGREES F IN THE ROOM, WILL PROVIDE | | | ADEQUATE COMBUSTION AIR, AND WILL REMOVE ALL HAZARDOUS | | | VAPORS- SECTION 11.3.2.1 NFPA 20. PLEASE NOTE THERE IS | | | NO AC SYSTEM IN THE ROOM. | | | | | | 11) M201.C: PROVIDE THE SEQUENCE OF OPERATION FOR THE | | | GENERATOR FUEL STORAGE TANK ROOM EXHAUST SYSTEM- | | | SECTION 502.8.1.1 FBC M. | | | | | | 12) M.301C & M711- DIESEL FIRE PUMP AND FUEL TANK: A) | | | PROVIDE FUEL TANK, FILL AND VENT PIPE SPECIFICATIONS, | | | PIPE SIZING CALCULATIONS, PIPE INSTALLATION DETAILS- | | | JOINTS AND CONNECTIONS, AND PIPE SUPPORT DETAILS- | | | SECTION 1302, 1303, 1305 FBC M. B) SHOW THE REMOTE FILL | | | PIPING LOCATION AND FILL PIPING RUN- SECTION 1305.6 FBC | | | M. C) INDICATE THE REQUIRED CLEARANCES FOR THE VENT | | | PIPING TO BUILDING OPENINGS- SECTION 1305.7 FBC M. IT | | | APPEARS THE LOCATIONS ARE STILL INSIDE THE BUILDING | | | FOOTPRINT WHICH IS NOT ALLOWED. | | | | | | 13) M301.C & M711- GENERATOR FUEL TANK: PROVIDE THE | | | FILL AND VENT PIPING SPECIFICATIONS, PIPE SIZING | | | CALCULATIONS, PIPE INSTALLATION DETAILS- JOINTS AND | | | CONNECTIONS, AND PIPE SUPPORT DETAILS- SECTION 1302, | | | 1303, 1305 FBC M. B) THE EMERGENCY VENT LINE FROM THE | | | TANK SHALL TERMINATE OUTSIDE OF THE BUILDING- SECTION | | | 1305.7 FBC M & SECTION 27.8.2.6 NFPA 30. C) INDICATE | | | HOW THE LINES WILL BE PROTECTED- SECTION 1305.7 FBC M. | | | D) INDICATE THE REQUIRED CLEARANCES FOR THE FILL AND | | | VENT PIPING TO BUILDING OPENINGS- SECTION 1305.7 FBC M. | | | IT APPEARS THE LOCATIONS ARE STILL INSIDE THE BUILDING | | | FOOTPRINT WHICH IS NOT ALLOWED. | | | | | | 14) M.711: THE LOCATIONS OF THE 3-HR. FIRE-RATED FUEL | | | LINE SHAFTS THROUGHOUT THE BUILDING ARE NOT SHOWN | | | CLEARLY AND ACCURATELY ON THE LIFE SAFETY, | | | ARCHITECTURAL, AND MECHANICAL AIR DISTRIBUTION PLANS. | | | THE LIFE SAFETY PLANS APPEAR TO SHOW THEM IN THE SAME | | | SHAFT WITH AN HVAC DUCT WHICH IS NOT ALLOWED. PLEASE | | | SHOW THE LOCATIONS, NOTE THEM CLEARLY ON THE PLANS, AND | | | PROVIDE CONSTRUCTION DETAILS FOR THE SHAFT- SECTION | | | 713.1 FBC B. A) PLEASE EMBOLDEN THE KEY NOTES IN THE | | | DIAGRAM. | | | | | | 15) M201.C: PROVIDE A SUBMITTAL FOR THE 2-HR FIRE RATED | | | EXHAUST DUCT WRAP. PLEASE NOTE THE WRAP SHALL BE LISTED | | | AND LABELED FOR USE ON HAZARDOUS EXHAUST DUCTS- SECTION | | | 510.7.3 FBC M. | | | | | | 16) M201.C NOTE #1: THE 3' CLEARANCE TO OPERABLE | | | OPENINGS IS ALLOWABLE FOR EXHAUST DUCTS SERVING A TYPE | | | II HOOD ONLY. PLEASE PROVIDE MORE INFORMATION AND | | | SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE HOOD, | | | EXHAUST DUCT, AND THE COOKING APPLIANCE- SEE SECTIONS | | | 506.3.13.3 AND 506.4.2 FBC M. PLEASE NOTE THAT SEPARATE | | | PERMITS ARE REQUIRED FOR KITCHEN EXHAUST AND FIRE | | | SUPPRESSION SYSTEMS- SECTION 107.2.1 WPB. | | | | | | 17) M201C: CU 5 SHALL BE INSTALLED OUTDOORS IN | | | ACCORDANCE WITH THE LISTING AND LABELING OF THE | | | APPLIANCE AND MANUFACTURER'S GUIDELINES- SECTION 304.1 | | | FBC M. | | | | | | 18) M201.C: FIRE DAMPERS MISSING AT THE AHU-13 SUPPLY | | | AND RETURN DUCT PENETRATIONS- SECTIONS 606.2 AND | | | 607.6.1 FBC M.22) M202.B: FIRE DAMPER MISSING FOR THE | | | 8X6 ERU SUPPLY DUCT PENETRATING FIRE-RATED WALL AT THE | | | FIRE LOBBY. | | | | | | 19) M202A AND ALL ENCLOSED GARAGE FLOORS: THE PLANS | | | SHOW THE GARAGE FANS WILL BE EXHAUSTING THE AIR INTO | | | THE SPACE BETWEEN THE EXTERIOR WALLS AND THE GREEN | | | SCREEN. PLEASE VERIFY THAT THE EXHAUST AIR WILL BE ABLE | | | TO FLOW FREELY OUT OF THE BUILDING AND NOT BE | | | OBSTRUCTED BY THE SCREEN. | | | | | | 20) M202.B, C, & D C: NO O/A PROVIDED AT THE ELEVATOR | | | OR FIRE LOBBIES- TABLE 403.3.1.1 AND SECTION 404.3 FBC | | | M. | | | | | | 21) M202.C: SHOW THE SIZE OF THE SPF/01 PRESSURIZATION | | | DUCT- SECTION 107.2.1 WPB. | | | | | | 22) M202.C: FIRE DAMPER MISSING AT THE AHU-13 SUPPLY | | | DUCT FLOOR PENETRATION- SECTION 607.6.1 FBC M. | | | | | | 23) M202.C & D - M206.C & D: ACCORDING TO THE SCHEDULE | | | AHU-14 SUPPLYING AIR TO THE RESIDENTIAL UNITS (AND ALL | | | OTHER AHU'S IN THE SCHEDULE ON SHEET M.602) IS NOT | | | BEING EQUIPPED WITH A MOTORIZED OUTSIDE AIR DAMPER | | | (NOTE #8 IN THE SCHEDULE). THE PLAN SHOWS AN ACD FOR | | | AHU-14, HOWEVER PLEASE NOTE SECTION C403.2.4.4 FBC EC | | | REQUIRES OUTDOOR AIR SUPPLY DUCTS TO BE EQUIPPED WITH | | | GRAVITY OR MOTORIZED DAMPERS THAT WILL AUTOMATICALLY | | | SHUT WHEN THE SYSTEMS OR SPACES ARE NOT IN USE. PROVIDE | | | DAMPERS FOR EACH DUCT SUPPLYING O/A TO THE VHP'S. | | | | | | 24) M202 C & D- M206.C & D, M605, M707: REFER TO | | | SECTION 504.8 FBC M AND PROVIDE THE FOLLOWING DETAILS | | | AND INFORMATION CONCERNING THE CLOTHES DRYER EXHAUST | | | SYSTEMS- TYPE OF DUCTWORK, SEQUENCE OF OPERATION FOR | | | THE EXHAUST FANS, AND HOW MAKEUP AIR IS BEING PROVIDED. | | | A) PROVIDE AIR BALANCE CALCULATIONS FOR THE RESIDENTIAL | | | UNITS THAT INCLUDE THE CLOTHES DRYER AND TOILET EXHAUST | | | SYSTEMS. | | | | | | 25) M203.B, C, & D C: NO O/A PROVIDED AT THE ELEVATOR | | | OR FIRE LOBBIES- TABLE 403.3.1.1 AND SECTION 404.3 FBC | | | M. | | | | | | 26) M203.B, 204.B, 205.B, 206.B: IT APPEARS THAT | | | FIRE-WRAPPING IS BEING USED TO CREATE CONTINUOUS | | | VERTICAL TO HORIZONTAL SHAFTS FOR THE ERU-01 SUPPLY | | | DUCTS AND THE RETURN/SMOKE PURGE DUCTS. PLEASE PROVIDE | | | A UL LISTED ASSEMBLY SHOWING THE FIRE WRAPPING USED IN | | | THIS CONFIGURATION- PLEASE SEE SECTION 703.2.1 FBC B. | | | | | | 27) M203.B- M206.B: SECTION C403.2.4.4 FBC EC REQUIRES | | | OUTDOOR AIR SUPPLY DUCTS TO BE EQUIPPED WITH GRAVITY OR | | | MOTORIZED DAMPERS THAT WILL AUTOMATICALLY SHUT WHEN THE | | | SYSTEMS OR SPACES ARE NOT IN USE. PROVIDE DAMPERS FOR | | | EACH DUCT SUPPLYING O/A TO THE FCU'S. | | | | | | 28) M204.C, & D: NO O/A PROVIDED AT THE ELEVATOR OR | | | FIRE LOBBIES- TABLE 403.3.1.1 AND SECTION 404.3 FBC M. | | | | | | 29) M205.B: CU-2 SHALL BE INSTALLED OUTDOORS IN | | | ACCORDANCE WITH THE LISTING AND LABELING OF THE | | | APPLIANCE AND MANUFACTURER'S GUIDELINES- SECTION 304.1 | | | FBC M. | | | | | | 30) M205.B: SUBMIT MANUFACTURER'S SPECIFICATIONS FOR | | | THE WATER HEATER INTAKE VENT AND EXHAUST FLUE | | | FIRE-WRAPPING- SECTION 304.1 FBC M. THE SPECS SHALL | | | SHOW THE PRODUCT CAN BE USED FOR THIS TYPE OF | | | INSTALLATION IN LIEU OF A FIRE-RATED SHAFT | | | | | | 31) M205.D: NO O/A PROVIDED AT THE ELEVATOR OR FIRE | | | LOBBIES- TABLE 403.3.1.1 AND SECTION 404.3 FBC M. | | | | | | 32) M205.C & M206.C: IT APPEARS FD'S ARE MISSING AT THE | | | AHU-14 SUPPLY AND RETURN DUCT FLOOR/CEILING | | | PENETRATIONS. | | | | | | 33) M205.C: PLEASE CLARIFY THE PURPOSE OF THE FSD SHOWN | | | IN THE MIDDLE OF THE 24X20 SUPPLY DUCT FROM AHU-14. | | | | | | 34) M205.C & M206.C POOL EQUIPMENT ROOM: A) PROVIDE A | | | POOL EQUIPMENT SCHEDULE AND SUBMIT MANUFACTURER'S | | | SPECIFICATIONS FOR THE POOL HEATERS AND DIRECT VENT | | | EXHAUST AND INTAKE DUCTS- SECTION 301.3 FBC FG. B) | | | PROVIDE A GAS PIPING PLAN AND ISOMETRIC DRAWING- | | | SECTION 402.1 FBC FG. C) THE AIR INTAKE LOUVER SHALL | | | COMMUNICATE DIRECTLY TO THE OUTDOORS AND CANNOT DRAW | | | VENTILATION AIR FROM THE ENCLOSED GARAGE SPACE- TABLE | | | 403.3.1.1 FOOTNOTE B. D) REFER TO SECTION 414.1.3 FBC B | | | AND PROVIDE A LIST OF POOL TREATMENT CHEMICALS AND | | | THEIR QUANTITIES TO BE USED AND STORED IN THE ROOM. E) | | | INDICATE THE SEQUENCE OF OPERATION FOR EF 62 AND THE | | | TYPE OF EXHAUST DUCTWORK TO BE INSTALLED- REFER TO | | | SECTIONS 510.2- 510.9 FBC M. F) INDICATE THE REQUIRED | | | CLEARANCES FOR THE EXHAUST OUTLET- SECTION 501.3.1 FBC | | | M. G) SHOW COMPLIANCE WITH SECTION 305.3.2 FBC FG: | | | CONNECTION OF A PARKING GARAGE WITH ANY ROOM IN WHICH | | | THERE IS A FUEL-FIRED APPLIANCE SHALL BE BY MEANS OF A | | | VESTIBULE PROVIDING A TWO-DOORWAY SEPARATION, EXCEPT | | | THAT A SINGLE DOOR IS PERMITTED WHERE THE SOURCES OF | | | IGNITION IN THE APPLIANCE ARE ELEVATED IN ACCORDANCE | | | WITH SECTION 305.3. | | | | | | 35) M206.A, EMERGENCY GENERATOR: THE EXHAUST DUCT FROM | | | EF-53 SHALL RUN INDEPENDENTLY AND DIRECTLY TO THE | | | EXTERIOR OF THE BUILDING, AND SHALL NOT CONNECT INTO | | | THE RADIATOR EXHAUST PLENUM- SECTION 510.6.7 FBC M. | | | PLEASE NOTE THAT THE GENERATOR WILL BE UNDER SEPARATE | | | PERMIT. A COMPLETE SEPARATE PLAN AND SUBMITTAL PACKAGE | | | WILL BE REQUIRED INCLUDING AN ENLARGED DRAWING OF THE | | | EPSS (EMERGENCY GENERATOR) ROOM SHOWING THE LOCATIONS | | | OF THE GENERATOR AND SUB-BASE TANK, FUEL OIL PIPE AND | | | EXHAUST PIPE RUNS AND TERMINATION LOCATIONS, AND ALL | | | OTHER ASSOCIATED EQUIPMENT INCLUDING EMERGENCY | | | ELECTRICAL PANELS ETC. PLEASE INCLUDE THE REQUIRED | | | CLEARANCE DISTANCE MEASUREMENTS FOR ALL EQUIPMENT VENT | | | PIPING RUNS AND SPECIFICATIONS INCLUDING FILL PIPING | | | LOCATIONS. THE SUBMITTAL PACKAGE SHALL INCLUDE: | | | A) MANUFACTURER'S SPECIFICATIONS FOR THE GENERATOR AND | | | THE 190-GALLON FUEL TANK, FUEL PIPING, ENGINE EXHAUST | | | PIPE, MUFFLER, AND ALL OTHER ASSOCIATED SYSTEM | | | COMPONENTS- SECTION 304.1 FBC M | | | B) THE UL 2200 CERTIFICATE OF COMPLIANCE FOR THE | | | GENERATOR- SECTION 915.1 FBC M. | | | C) THE MANUFACTURER'S SPECIFICATIONS AND/OR UL | | | CERTIFICATE SHALL INDICATE THE GENERATOR IS COMPLIANT | | | WITH THE NFPA 37 AND NFPA 110 STANDARD AND IS | | | CLASSIFIED AS A LEVEL 1 EPSS- SECTION 4.4.1 NFPA 110. | | | D) PRODUCT CUT SHEET FOR THE FUEL TANK THAT INCLUDES | | | THE TANK'S UL LISTING- UL 142 OR UL 2085- SEE SECTION | | | 21.4.2.1.1 NFPA 30. | | | E) GENERATOR EXHAUST PIPE SPECIFICATIONS AND PROVIDE AN | | | EXHAUST PIPE DIAGRAM SHOWING THE TOTAL SYSTEM RUN AND | | | LENGTH MEASUREMENT, AND TERMINATION LOCATION PLEASE | | | INCLUDE ALL COMPONENTS OF THE SYSTEM INCLUDING THE | | | SILENCER, AND ANY CONTRACTOR SUPPLIED PIPING- SEE | | | SECTIONS 8.1 ? 8.4 NFPA 37, AND SECTION 501.3.1 FBC M. | | | F) BACKPRESSURE CALCULATIONS FOR THE GENERATOR EXHAUST | | | PIPE RUN- SECTION 304.1 FBC M. | | | G) DETAILS AND SPECIFICATIONS FOR NORMAL AND EMERGENCY | | | RELIEF VENTING OF THE TANK, INCLUDING VENT PIPING RUNS | | | AND TERMINATION LOCATIONS AT THE EXTERIOR OF THE | | | BUILDING- SECTION 24.13 NFPA 30. | | | | | | 36) M206.A: REFER TO SECTION 7.7.1 NFPA 110- 2016 AND | | | VERIFY THAT THE VENTILATION AIRFLOW IN THE | | | GENERATOR/TANK (EPS) ROOM IS DESIGNED TO LIMIT THE | | | MAXIMUM AIR TEMPERATURE IN THE ROOM TO THE MAXIMUM | | | AMBIENT AIR TEMPERATURE REQUIRED BY THE GENERATOR | | | MANUFACTURER. CONSIDERATION SHALL BE GIVEN TO ALL THE | | | HEAT EMITTED TO THE ROOM BY THE ENERGY CONVERTER, | | | EXHAUST PIPES, AND ALL OTHER HEAT PRODUCING EQUIPMENT- | | | SECTION 7.7.1.1. DESIGN OF THE HEATING, COOLING, AND | | | VENTILATION SYSTEM SHALL AMONG OTHER THINGS, INCLUDE | | | PROVISIONS FOR FACTORS SUCH AS HEAT, COLD, HUMIDITY, | | | LOUVERS, ETC.- SECTION | | | 'S SPECS FOR THE BOILERS AND WATER HEATERS- SECTIONS | | | 402.1, 503.1, AND 624.1 FBC FG. | | | | | | 38) M206.B: PROVIDE A DUCT SMOKE DETECTOR IN THE RETURN | | | AIR SYSTEM OF ERU-01- SECTION 606.2.1 FBC M. | | | | | | 39) M206.C: NOTE THE REQUIRED CLEARANCES FOR THE | | | COMBUSTION AIR INTAKE DUCTS PER MANUFACTURER'S | | | SPECIFICATIONS, AND PER SECTION 304.1 (8) FBC FG. | | | | | | 40) M206.C: SHOW O/A SUPPLY TO THE RESIDENTIAL UNITS OR | | | INDICATE NATURAL VENTILATION IN THE NOTES- SECTION 402 | | | FBC M. | | | | | | 41) M206.C: PLEASE PLACE NOTES ON THE PLAN TO INDICATE | | | THE WHAT TYPE OF HORIZONTAL 2-HR FIRE-RATED ENCLOSURES | | | WILL BE INSTALLED FOR THE DRYER AND TOILET EXHAUST | | | DUCTS AND INDICATE WHERE THE DETAILS ARE FOUND IN THE | | | PLANS- SECTION 107.2.1 WPB. | | | | | | 42) M206.C: THE REVISED PLAN SHOWS SPF-13 PRESSURIZING | | | THE CORRIDOR BUT NOT THE STAIRWAY WHICH IS NOW SHOWN | | | CLOSED OFF WITH DOORS- SECTION 909.6 FBC B AND 513.6 | | | FBC M. | | | | | | 43) M207.A: THE VENTILATION CALCULATIONS SHOWN AT THE | | | TOP OF THE PAGE ARE NOT IN COMPLIANCE WITH TABLE | | | 403.3.1.1 FBC M. PLEASE REVISE AND PROVIDE AIR BALANCE | | | CALCULATIONS FOR ALL ROOMS AND SPACES USING EXHAUST | | | VENTILATION SYSTEMS- SECTION 501.4 FBC M. A) INCLUDE | | | THE AHU SERVING THE LAP POOL IN THE CALCULATIONS. | | | PLEASE NOTE THAT THIS APPEARS TO BE A SYSTEM OF SUPPLY | | | AND RETURN AIR, HOWEVER THE CALCULATION INDICATES | | | O/A/EXHAUST. PLEASE CORRECT OR PROVIDE EXHAUST IN THE | | | ROOM. | | | | | | 44) M207.A POOL EQUIPMENT ROOM: A) PROVIDE A POOL | | | EQUIPMENT SCHEDULE AND SUBMIT MANUFACTURER'S | | | SPECIFICATIONS FOR THE POOL HEATERS AND DIRECT VENT | | | EXHAUST AND INTAKE DUCTS- SECTION 301.3 FBC FG. B) | | | PROVIDE A GAS PIPING PLAN AND ISOMETRIC DRAWING- | | | SECTION 402.1 FBC FG. C) REFER TO SECTION 414.1.3 FBC B | | | AND PROVIDE A LIST OF POOL TREATMENT CHEMICALS AND | | | THEIR QUANTITIES TO BE USED AND STORED IN THE ROOM. D) | | | INDICATE THE SEQUENCE OF OPERATION FOR EF 48 AND THE | | | TYPE OF EXHAUST DUCTWORK TO BE INSTALLED- REFER TO | | | SECTIONS 510.2- 510.9 FBC M. E) INDICATE THE REQUIRED | | | CLEARANCES FOR THE EXHAUST OUTLET- SECTION 501.3.1 FBC | | | M.36 | | | | | | 45) M207.A LAUNDRY: PLACE A NOTE INDICATING UNDER | | | SEPARATE PERMIT AS WAS INDICATED IN THE RESPONSE | | | NARRATIVE. | | | | | | 46) M207.B: PER THE NOTE, THE KITCHENS ARE UNDER | | | SEPARATE PERMIT, HOWEVER IT WILL BE HELPFUL TO SHOW THE | | | PROPOSED LOCATIONS OF KITCHEN HOOD EXHAUST DUCT | | | TERMINATIONS ON THE PLAN (THERE IS NO NOTE INDICATING A | | | SCRUBBER IS TO BE USED PER THE RESPONSE NARRATIVE). | | | PLEASE BE ADVISED THAT THE REQUIREMENT FOR KITCHEN | | | EXHAUST MAKEUP AIR TEMPERATURE UNDER SECTION 508.1.1 | | | WILL BE ENFORCED UNDER THE SEPARATE PERMIT. | | | | | | 47) M207.B: LABEL THE ELEVATOR RELIEF VENT- SECTION | | | 107.2.1 WPB. | | | | | | 48) M208.A & B: THE RR-4 RETURN FROM THE TENNIS COURTS | | | APPEARS TO BE CONNECTED TO TWO SUPPLY DIFFUSERS. WHICH | | | SYSTEM(S) ARE THESE DUCTS CONNECTED TO?- SECTION | | | 107.2.1 WPB. | | | | | | 49) M208.B HOTEL POOL EQUIPMENT ROOM: A) PROVIDE A POOL | | | EQUIPMENT SCHEDULE AND SUBMIT MANUFACTURER'S | | | SPECIFICATIONS FOR THE POOL HEATERS AND DIRECT VENT | | | EXHAUST AND INTAKE DUCTS- SECTION 301.3 FBC FG. B) | | | PROVIDE A GAS PIPING PLAN AND ISOMETRIC DRAWING- | | | SECTION 402.1 FBC FG. C) REFER TO SECTION 414.1.3 FBC B | | | AND PROVIDE A LIST OF POOL TREATMENT CHEMICALS AND | | | THEIR QUANTITIES TO BE USED AND STORED IN THE ROOM. D) | | | INDICATE THE SEQUENCE OF OPERATION FOR EF-52 AND THE | | | TYPE OF EXHAUST DUCTWORK TO BE INSTALLED- REFER TO | | | SECTIONS 510.2- 510.9 FBC M. E) INDICATE THE REQUIRED | | | CLEARANCES FOR THE POOL ROOM EXHAUST OUTLET- SECTION | | | 501.3.1 FBC M, AND THE POOL HEATER INTAKE OPENINGS AND | | | EXHAUST OUTLETS. | | | | | | 50) M208.C: NO VENTILATION PROVIDED TO THE ELEVATOR | | | LOBBY. | | | HOTEL TOWER | | | | | | 51) M209, 210, 211, 212: PROVIDE A DETAIL SHOWING THE | | | FCU INSTALLATION IN THE CLOSET INCLUDING THE RETURN AIR | | | SYSTEM, AND REQUIRED CLEARANCE AND ACCESS FOR SERVICE | | | AND REPLACEMENT OF THE UNIT- SECTION 306.1 FBC M. | | | | | | 52) M209-M211 TENNIS COURT SYSTEMS: PLEASE CORRECT THE | | | REFERENCES TO PLAN SHEETS M.224 AND M.226 WHICH ARE NOT | | | RELATED TO THE TENNIS COURT SYSTEMS- SECTION 107.2.1 | | | WPB. | | | | | | 53) M209 & M210: THE DRYERS APPEAR TO BE REMOVED FROM | | | THE HOTEL FLOOR PLANS. PLEASE REMOVE GENERAL NOTE #3 | | | CONCERNING THE MAKEUP AIR IN THE CLOSETS. | | | | | | 54) M209, M210, M211, & M212: THE KITCHEN EXHAUST SHALL | | | RUN INDEPENDENTLY AND NOT BE CONNECTED TO THE TOILET | | | EXHAUST DUCT SYSTEM- SECTIONS 501.2 & 505.1 FBC M. | | | | | | OFFICE TOWER | | | | | | 55) M.701 AND ALL OFFICE FLOOR PLAN SHEETS: PROVIDE | | | DUCT SMOKE DETECTORS AT EACH FLOOR LEVEL OF THE ERU-03 | | | RETURN AIR RISER- SECTION 606.2.3 FBC M. PROVIDE DS | | | SYMBOLS ON THE PLANS TO INDICATE THE LOCATIONS. | | | | | | 56) M.218: THE MECHANICAL ROOM VENTILATION CALCULATIONS | | | ARE NOT IN COMPLIANCE WITH SECTION 1105.6.3.1 FOR | | | NORMAL CONDITIONS, AND SECTION 1105.6.3.2 FOR EMERGENCY | | | CONDITIONS. PLEASE CORRECT THE CALCULATIONS AND PROVIDE | | | A SEQUENCE OF OPERATION FOR EF-58. | | | | | | 57) M.218 & M.603: PROVIDE THE MISSING PERFORMANCE DATA | | | FOR THE COOLING TOWERS IN THE SCHEDULE. | | | | | | 58) M.218: PROVIDE SITE SPECIFIC STRUCTURAL ENGINEERING | | | FOR INSTALLATION OF THE COOLING TOWERS, CONDENSER | | | UNITS, ROOFTOP AND ALL OTHER EXPOSED MECHANICAL | | | EQUIPMENT AND APPLIANCES- SECTION 301.15 FBC M. PLEASE | | | NOTE THE ENGINEERING MAY BE DEFERRED AND CAN BE NOTED | | | AS SUCH ON THE PLAN SHEET. | | | | | | 59) M.219: IT APPEARS THAT AN AC-4 AND AC-9 ARE TO BE | | | INSTALLED INSIDE THE ELEVATOR HOISTWAYS WHICH IS | | | PROHIBITED- SECTION 303.8 FBC M. | | | | | | 60) THERE ARE NO COOLING AND HEATING CALCULATIONS FOR | | | ERU-03 & OAU-1. | | | | | | RESIDENTIAL TOWER | | | | | | 61) M.220: PROVIDE A DUCT SMOKE DETECTOR IN THE RETURN | | | AIR SYSTEM OF AHU-12- SECTION 606.2.1 FBC M. | | | | | | 62) M.222: CHANGE THE REFERENCE TO SHEET M.228 TO | | | M.229- SECTION 107.2.1 WPB. | | | | | | 63) M.222: PROVIDE CONSTRUCTION DETAILS FOR THE 2-HR | | | FIRE-RATED ELEVATOR RELIEF DUCT ENCLOSURE- SECTION | | | 703.2.1 FBC B. | | | | | | 64) M.227: PROVIDE SITE SPECIFIC STRUCTURAL ENGINEERING | | | FOR INSTALLATION OF THE COOLING TOWERS, GENERATOR, OAU | | | AND ROOFTOP DUCTWORK, CONDENSING UNITS, AND ALL OTHER | | | MECHANICAL EQUIPMENT AND APPLIANCES- SECTION 301.15 FBC | | | M. PLEASE NOTE THE ENGINEERING MAY BE DEFERRED AND CAN | | | BE NOTED AS SUCH ON THE PLAN SHEET. | | | | | | 65) M.228: PROVIDE SITE SPECIFIC STRUCTURAL ENGINEERING | | | FOR INSTALLATION OF ROOFTOP CONDENSING UNITS, AND ALL | | | OTHER EXPOSED MECHANICAL EQUIPMENT AND APPLIANCES- | | | SECTION 301.15 FBC M. PLEASE NOTE THE ENGINEERING MAY | | | BE DEFERRED AND CAN BE NOTED AS SUCH ON THE PLAN SHEET. | | | | | | 66) M.228: IT APPEARS THAT AN AC-4 IS TO BE INSTALLED | | | INSIDE THE ELEVATOR HOISTWAY WHICH IS PROHIBITED- | | | SECTION 303.8 FBC M. | | | | | | 67) M.229: LABEL THE MAIN RETURN AIR GRILL AND OPENING | | | SIZE- SECTION 601.5 FBC M. | | | | | | 68) M.229: INDICATE THE HEIGHT OF EF-A10 FROM THE | | | FINISHED FLOOR- SEE SECTION 306.5 FBC M. | | | | | | 69) M.229: PROVIDE A MECHANICAL ROOF PLAN FOR THE | | | TENNIS COURT STRUCTURE WHICH SHOWS THE LOCATIONS OF THE | | | CONDENSING UNITS, GRAVITY INTAKES AND EXHAUST FANS AS | | | CALLED OUT ON M.229. A) PROVIDE ENGINEERING FOR ALL | | | ROOFTOP MECHANICAL INSTALLATIONS- MAY BE DEFERRED WITH | | | A NOTE ON THE PLAN. B) PROVIDE CLEARANCE DISTANCE | | | MEASUREMENTS FOR ALL SERVICEABLE MECHANICAL EQUIPMENT | | | TO ROOF EDGES- SEE SECTION 304.11 FBC M. | | | | | | 70) M.259- M261 RESIDENTIAL UNITS: PLEASE PROVIDE | | | DETAILS OR NOTES ON THE PLAN INDICATING COMPLIANCE WITH | | | THE FOLLOWING ITEMS. | | | A) IDENTIFY ALL ROOMS ON THE PLANS. | | | B) PROVIDE A FRONT VIEW DRAWING OF THE AIR HANDLER IN | | | THE CLOSET SHOWING REQUIRED CLEARANCES, CONDENSATE | | | DISPOSAL DETAILS, SUPPLY PLENUM AND RETURN AIR | | | CONNECTIONS. | | | C) INDICATE DIFFUSER AND RETURN GRILL DIMENSIONS OR | | | PROVIDE A SCHEDULE ON THE PLAN. PLEASE NOTE BALANCED | | | RETURN AIR IS REQUIRED- TRANSFER DUCTS SHALL BE SIZED | | | 1-1/2 TIMES THE AREA OF THE SUPPLY DUCT TO THE ROOM, | | | RETURN GRILLS SHALL BE SIZED AT 50 CFMS PER 100 SQ. | | | INCHES, AND ALL AIR SUPPLIED TO MASTER BEDROOMS SHALL | | | BE RETURNED- SEE SECTION 601.5 FBC M | | | D) PROVIDE COOKING APPLIANCE SCHEDULES AND SUBMIT | | | MANUFACTURER?S SPECIFICATIONS FOR EACH COOKING | | | APPLIANCE. MAY BE DEFERRED AND NOTED AS SUCH ON THE | | | PLANS. | | | E) PROVIDE EXHAUST VENTILATION FOR THE KITCHENS AT A | | | RATE OF 100 CFM INTERMITTENT OR 25 CFMS CONTINUOUS- | | | TABLE 403.3.1.1. | | | F) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE CLOTHES | | | DRYERS AND THE DRYER EXHAUST BOOSTER FAN. PLEASE NOTE | | | THAT THERE IS NO REQUIREMENT FOR BOOSTER FANS IN THE | | | FBC-14 MECHANICAL CODE. DRYERS SHALL BE EXHAUSTED IN | | | ACCORDANCE WITH MANUFACTURER?S SPECIFICATIONS AND | | | INSTALLATION INSTRUCTIONS- SECTION 504.1 FBC M. | | | G) PROVIDE A SUBMITTAL FOR THE X-VENT BOXES. | | | | | | 71) M.501: PROVIDE DUCT CONNECTION, SUPPORT AND HANGING | | | DETAILS PER THE CURRENT SMACNA HVAC DUCT CONSTRUCTION | | | STANDARD- METAL AND FLEXIBLE 2005, AND SMACNA FIBROUS | | | GLASS DUCT- 2010. | | | | | | 72) PLEASE PROVIDE COMPLETE CONDENSATE DISPOSAL PLANS | | | INCLUDING RISER DRAWINGS FOR THE TOWER AND PODIUM | | | SYSTEMS- SECTION 307.2.1 FBC M. | | | | | | 73) PLEASE LABEL ALL ELEVATOR EQUIPMENT ROOMS ON THE | | | PLANS AND SHOW THE REQUIRED VENTILATION SYSTEMS- | | | SECTION 3006.2 FBC B. | | | | | | ENERGY COMPLIANCE REPORT | | | | | | 74) THE PROJECT IS BEING DESIGNED UNDER THE 2014 | | | FLORIDA BUILDING CODES. SUBMIT THE 2014 ENERGYGAUGE | | | COMPLIANCE REPORT. | | | | | | 75) M.218 & M.603: THE SYSTEM FULL LOAD AND IPLV | | | COMPLIANCE DATA FOR THE CHILLERS IN THE SCHEDULE DOES | | | NOT MATCH THE DATA IN THE ENERGY REPORT- SEE TABLE | | | C403.2.3(7) FBC EC. | | | | | | 76) NO COMPLIANCE DATA FOR OAU-1, THE WATER HEATERS, | | | SERVICE WATER PIPING, AIR COOLED SPLIT SYSTEMS- AC-1- | | | 9, INDOOR POOL AHU-08, AND THE CAPACITIES FOR FCU?S | | | 2-18, | | | | | | 77) M.603: THE TOTAL MBH LISTED IN THE SCHEDULE FOR | | | AHU-12, 13, & 14 DOES NOT MATCH THE CAPACITIES LISTED | | | IN THE REPORT. | | | | | | 78) M.604: THE CAPACITY LISTED FOR FCU-01 IN THE | | | SCHEDULE DOES NOT MATCH THE REPORT. | | | | | | 79) M.604 VHP'S: A) MBH IN SCHEDULE FOR VHP- 2, 3 & 4 | | | DOESN'T MATCH DATA IN THE REPORT. B) PLEASE INDICATE | | | THE NUMBER OF EACH VHP (1-7)) TO BE INSTALLED ON THE | | | PROJECT. | | | | | | 80) M.604 HHP'S: A) NO DATA IN THE REPORT FOR HHP-2, 5, | | | 6, 7, 8, & 9. B) PLEASE INDICATE THE NUMBER OF EACH HHP | | | (1-9)) TO BE INSTALLED ON THE PROJECT. | | | | | | HEAT LOAD CALCULATIONS | | | | | | 81) SHEET M.602: THE COOLING CAPACITIES (MBH) SHOWN IN | | | THE AHU AND ERU SCHEDULE ARE EITHER UNDER OR OVER THE | | | HEAT LOADS SHOWN IN CALCULATIONS- SECTION C403.2.2 FBC | | | EC. | | | | | | A) AHU-01 OFFICE/LOBBY: SCHEDULE- 207 MBH, CALCS- 436 | | | MBH. | | | | | | B) AHU-02 LOBBY/CAFE: SCHEDULE- 158 MBH, CALCS- 177 | | | MBH. | | | | | | C) AHU-03 HOTEL LOBBY: SCHEDULE- 275 MBH, CALCS- 320 | | | MBH | | | | | | D) AHU-04 RETAIL/RESTAURANT: SCHEDULE- 903 MBH, CALCS- | | | 773 MBH | | | | | | E) AHU-05 DAYCARE: SCHEDULE- 126 MBH, CALCS- 193 MBH | | | | | | F) AHU-07A & B: SCHEDULE 1,417 MBH, CALCS- 1,650 MBH. | | | | | | G) AHU-08 INDOOR POOL: SCHEDULE- 359 MBH, CALCS- 251 | | | MBH. | | | | | | H) AHU-09 FITNESS/SPA: SCHEDULE- 265 MBH, CALCS- 667 | | | MBH. | | | | | | I) AHU-10A & B TENNIS COURT ASSEMBLY: SCHEDULE- 1,387 | | | MBH, CALCS- 1,552 MBH. PLEASE NOTE THAT THERE IS | | | ANOTHER CALCULATION FOR THE ?TENNIS COURT? INDICATING | | | 890 MBH. PLEASE CLARIFY. | | | | | | J) AHU-12 RES/LOUNGE: SCHEDULE- 404 MBH, CALCS- 357 | | | MBH. | | | | | | K) AHU-13 RES LOBBY: SCHEDULE- 453 MBH, CALCS | | | | | | L) ERU-1: SCHEDULE- 761 MBH, CALCS 911 MBH. | | | | | | M) THERE ARE NO COOLING AND HEATING CALCULATIONS FOR | | | ERU-03 & OAU-1. | | | | | | |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2019-04-08 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2019-04-08 |
Time |
17:50 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2019-04-01 |
Time |
14:17 |
Sent To |
|
|
| Notes |
| 2019-04-08 17:58:15 | 1ST REVIEW FBC-2017 MECHANICAL | | | PERMIT #18100540 | | | 550 N QUADRILLE BLVD | | | 4/2/19 | | | CODES IN EFFECT: | | | | | | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 | | | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 | | | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION | | | 2017 | | | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 | | | FS- FLORIDA STATUTES | | | FAC- FLORIDA ADMINISTRATIVE CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH | | | EDITION 2017 | | | PLAN REVIEW RESULTS: DENIED. | | | | | | THE MECHANICAL PLANS HAVE FAILED FOR THE DEFICIENCIES | | | AND OMISSIONS LISTED BELOW. PLEASE REVIEW ALL COMMENTS, | | | INCLUDING THOSE LISTED FOR ADVISORY PURPOSES, AND | | | RESUBMIT CORRECTED PLANS AND REQUIRED DOCUMENTS. WHEN | | | RESUBMITTING, PLEASE PROVIDE A RESPONSE LETTER | | | ADDRESSING EACH ITEM ALONG WITH THE CITY RE-SUBMITTAL | | | FORM. | | | PRIOR TO MECHANICAL PERMIT ISSUANCE, THE GENERAL | | | CONTRACTOR AND MECHANICAL SUB-CONTRACTOR FOR THE | | | PROJECT ARE REQUESTED TO ATTEND A MEETING AT THE WPB | | | BUILDING DEPARTMENT WITH THE STAFF- CHIEF MECHANICAL | | | INSPECTOR, PLANS EXAMINER, AND OTHER OFFICIALS- TO | | | DISCUSS TIMELINES AND GUIDELINES FOR INSPECTIONS AND | | | THE DOCUMENT SUBMITTAL PROCESS . FURTHER INFORMATION | | | WILL FOLLOW ONCE ALL PLANS ARE APPROVED. | | | | | | 1) THE FOLLOWING LIST OF DOCUMENTS WERE NOT SUBMITTED | | | BUT ARE REQUIRED TO PERFORM A COMPLETE MECHANICAL | | | REVIEW FOR THE PROJECT. | | | 1A) SMOKE CONTROL RATIONAL ANALYSIS- SECTION 513.4 FBC | | | M: A RATIONAL ANALYSIS SUPPORTING THE TYPES OF SMOKE | | | CONTROL SYSTEMS TO BE EMPLOYED, THEIR METHODS OF | | | OPERATION, THE SYSTEMS SUPPORTING THEM AND THE METHODS | | | OF CONSTRUCTION TO BE UTILIZED SHALL ACCOMPANY THE | | | SUBMITTED CONSTRUCTION DOCUMENTS AND SHALL INCLUDE, BUT | | | NOT BE LIMITED TO, THE ITEMS INDICATED IN SECTIONS | | | 513.4.1 THROUGH 513.4.7. | | | 513.4.1 STACK EFFECT: THE SYSTEM SHALL BE DESIGNED SUCH | | | THAT THE MAXIMUM PROBABLE NORMAL OR REVERSE STACK | | | EFFECTS WILL NOT ADVERSELY INTERFERE WITH THE SYSTEM'S | | | CAPABILITIES. IN DETERMINING THE MAXIMUM PROBABLE STACK | | | EFFECTS, ALTITUDE, ELEVATION, WEATHER HISTORY AND | | | INTERIOR TEMPERATURES SHALL BE USED. | | | 513.4.2 TEMPERATURE EFFECT OF FIRE: BUOYANCY AND | | | EXPANSION CAUSED BY THE DESIGN FIRE IN ACCORDANCE WITH | | | SECTION 513.9 SHALL BE ANALYZED. THE SYSTEM SHALL BE | | | DESIGNED SUCH THAT THESE EFFECTS DO NOT ADVERSELY | | | INTERFERE WITH ITS CAPABILITIES. | | | 513.4.3 WIND EFFECT: THE DESIGN SHALL CONSIDER THE | | | ADVERSE EFFECTS OF WIND. SUCH CONSIDERATION SHALL BE | | | CONSISTENT WITH THE WIND-LOADING PROVISIONS OF THE | | | FLORIDA BUILDING CODE, BUILDING. | | | 513.4.4 HVAC SYSTEMS: THE DESIGN SHALL CONSIDER THE | | | EFFECTS OF THE HEATING, VENTILATING AND | | | AIR-CONDITIONING (HVAC) SYSTEMS ON BOTH SMOKE AND FIRE | | | TRANSPORT. THE ANALYSIS SHALL INCLUDE ALL PERMUTATIONS | | | OF SYSTEMS STATUS. THE DESIGN SHALL CONSIDER THE | | | EFFECTS OF FIRE ON THE HVAC SYSTEMS. | | | 513.4.5 CLIMATE: THE DESIGN SHALL CONSIDER THE EFFECTS | | | OF LOW TEMPERATURES ON SYSTEMS, PROPERTY AND OCCUPANTS. | | | AIR INLETS AND EXHAUSTS SHALL BE LOCATED SO AS TO | | | PREVENT SNOW OR ICE BLOCKAGE. | | | 513.4.6 DURATION OF OPERATION: ALL PORTIONS OF ACTIVE | | | OR ENGINEERED SMOKE CONTROL SYSTEMS SHALL BE CAPABLE OF | | | CONTINUED OPERATION AFTER DETECTION OF THE FIRE EVENT | | | FOR A PERIOD OF NOT LESS THAN EITHER 20 MINUTES OR 1.5 | | | TIMES THE CALCULATED EGRESS TIME, WHICHEVER IS GREATER. | | | 513.4.7 SMOKE CONTROL SYSTEM INTERACTION: THE DESIGN | | | SHALL CONSIDER THE INTERACTION EFFECTS OF THE OPERATION | | | OF MULTIPLE SMOKE CONTROL SYSTEMS FOR ALL DESIGN | | | SCENARIOS. | | | THE SMOKE ANALYSIS SHALL CONTAIN A PROJECT DESCRIPTION | | | OF SMOKE CONTROL SYSTEMS, SPRINKLER AND STANDPIPE | | | SYSTEMS, FIRE ALARM SYSTEMS, SHAFT VENTING, AND CONTROL | | | SYSTEMS. INCLUDED IN THE ANALYSIS SHALL BE SPECIAL | | | INSPECTION AND TEST REQUIREMENTS, TESTING PROCEDURES, | | | AND FINAL COMMISSIONING REQUIREMENTS FOR THE SYSTEMS. | | | IMPORTANT NOTE: ACCEPTANCE TESTING OF THE PROJECT'S | | | SMOKE CONTROL SYSTEMS SHALL BE COMPLETED UNDER NORMAL | | | AND EMERGENCY POWER. PLEASE PROVIDE A DESCRIPTION OF | | | THE EMERGENCY PROCEDURE THAT INCLUDES BOTH EMERGENCY | | | GENERATORS AND HOW THE FIRE ALARM AND LIFE SAFETY | | | SYSTEMS IN THE TWO TOWERS AND PODIUM WILL COORDINATE | | | AND INTERACT TOGETHER. | | | | | | 1B) AC COOLING AND HEATING CALCULATIONS- SECTION | | | C403.2.1 FBC EC: DESIGN LOADS ASSOCIATED WITH HEATING, | | | VENTILATING AND AIR CONDITIONING OF THE BUILDING SHALL | | | BE DETERMINED IN ACCORDANCE WITH ANSI/ASHRAE/ACCA | | | STANDARD 183 OR ACCA MANUAL N OR BY AN APPROVED | | | EQUIVALENT COMPUTATIONAL PROCEDURE USING THE DESIGN | | | PARAMETERS SPECIFIED IN CHAPTER 3. HEATING AND COOLING | | | LOADS SHALL BE ADJUSTED TO ACCOUNT FOR LOAD REDUCTIONS | | | THAT ARE ACHIEVED WHERE ENERGY RECOVERY SYSTEMS ARE | | | UTILIZED IN THE HVAC SYSTEM IN ACCORDANCE WITH THE | | | ASHRAE HVAC SYSTEMS AND EQUIPMENT HAND-BOOK BY AN | | | APPROVED EQUIVALENT COMPUTATIONAL PROCEDURE. DESIGN | | | LOADS SHALL BE ATTACHED TO THE CODE COMPLIANCE FORM | | | SUBMITTED TO THE BUILDING DEPARTMENT WHEN THE BUILDING | | | IS PERMITTED OR, IN THE EVENT THE MECHANICAL PERMIT IS | | | OBTAINED AT A LATER TIME, THE SIZING CALCULATION SHALL | | | BE SUBMITTED WITH THE APPLICATION FOR THE MECHANICAL | | | PERMIT. | | | | | | 1C) ENERGY EFFICIENCY COMPLIANCE REPORT- SECTION C401.2 | | | FBC EC. | | | COMMERCIAL BUILDINGS SHALL COMPLY WITH ONE OF THE | | | FOLLOWING:\] | | | 1.THE REQUIREMENTS OF ANSI/ASHRAE/IESNA 90.1, EXCLUDING | | | SECTION 9.4.1.1(G) OF THE STANDARD. | | | 2.THE REQUIREMENTS OF SECTIONS C402 THROUGH C405. IN | | | ADDITION, COMMERCIAL BUILDINGS SHALL COMPLY WITH | | | SECTION C406 AND TENANT SPACES SHALL COMPLY WITH | | | SECTION C406.1.1. | | | 3.THE REQUIREMENTS OF SECTIONS C402.5, C403.2, C404, | | | C405.2, C405.3, C405.5, C405.6 AND C407. THE BUILDING | | | ENERGY COST SHALL BE EQUAL TO OR LESS THAN 85 PERCENT | | | OF THE STANDARD REFERENCE DESIGN BUILDING. | | | PLEASE REVIEW SECTION C101.5.1 FBC EC: THE FLORIDA | | | BUILDING COMMISSION SHALL APPROVE SPECIFIC COMPUTER | | | SOFTWARE. THE CODE OFFICIAL SHALL BE PERMITTED TO | | | APPROVE WORKSHEETS, COMPLIANCE MANUALS AND OTHER | | | SIMILAR MATERIALS THAT MEET THE INTENT OF THIS CODE. | | | | | | 1D) COMMISSIONING PLAN: COMMISSIONING OF THE MECHANICAL | | | SYSTEMS AND SERVICE WATER HEATING SYSTEMS IS REQUIRED | | | PER SECTION C408.2 FBC EC. COMMISSIONING PLAN. "PRIOR | | | TO THE FINAL MECHANICAL AND PLUMBING INSPECTIONS, THE | | | LICENSED DESIGN PROFESSIONAL, ELECTRICAL ENGINEER, | | | MECHANICAL ENGINEER, OR APPROVED AGENCY SHALL PROVIDE | | | EVIDENCE OF MECHANICAL SYSTEMS COMMISSIONING AND | | | COMPLETION IN ACCORDANCE WITH THE PROVISIONS OF THIS | | | SECTION". | | | A COMMISSIONING PLAN SHALL BE DEVELOPED BY A LICENSED | | | DESIGN PROFESSIONAL, ELECTRICAL ENGINEER, MECHANICAL | | | ENGINEER OR APPROVED AGENCY AND SHALL INCLUDE THE | | | FOLLOWING ITEMS: | | | 1. A NARRATIVE DESCRIPTION OF THE ACTIVITIES THAT WILL | | | BE ACCOMPLISHED DURING EACH PHASE OF COMMISSIONING, | | | INCLUDING THE PERSONNEL INTENDED TO ACCOMPLISH EACH OF | | | THE ACTIVITIES. | | | 2. A LISTING OF THE SPECIFIC EQUIPMENT, APPLIANCES OR | | | SYSTEMS TO BE TESTED AND A DESCRIPTION OF THE TESTS TO | | | BE PERFORMED. | | | 3. FUNCTIONS TO BE TESTED INCLUDING, BUT NOT LIMITED | | | TO, CALIBRATIONS AND ECONOMIZER CONTROLS. | | | 4. CONDITIONS UNDER WHICH THE TEST WILL BE PERFORMED. | | | TESTING SHALL AFFIRM WINTER AND SUMMER DESIGN | | | CONDITIONS AND FULL OUTSIDE AIR CONDITIONS. | | | 5. MEASURABLE CRITERIA FOR PERFORMANCE' | | | | | | 2) SUBMITTALS: REQUIRED SUBMITTALS LISTED BELOW SHALL | | | HAVE SHOP DRAWING STAMPS BY THE EOR AND BE IN THE FIELD | | | AT TIME OF INSPECTION. | | | A) SMOKE CONTROL FANS INCLUDING SMOKE EXHAUST FANS, AND | | | STAIRWELL AND ELEVATOR PRESSURIZATION FANS. | | | B) FIRE DAMPERS AND FIRE/SMOKE DAMPERS. | | | C) MOTORIZED AND GRAVITY DAMPERS | | | D) DUCT SMOKE DETECTORS | | | E) LOUVERS FOR EXHAUST AND OUTSIDE AIR INTAKES | | | INCLUDING MANUFACTURER'S SPECIFICATIONS AND FL. PRODUCT | | | APPROVALS AND/OR MIAMI-DADE NOA'S | | | F) AC STAND NOA'S OR FL. PRODUCT APPROVALS | | | G) C0, N02, & CO2 SENSORS, AND REFRIGERANT LEAK | | | DETECTORS. | | | H) COOLING TOWERS AND CHILLERS | | | I) FACTORY BUILT DUCTWORK | | | J) DUCT FIRE WRAPPING | | | K) CLOTHES DRYERS | | | L) TOILET AND DRYER EXHAUST WALL CAPS | | | M) COOKING APPLIANCES | | | N) TEST AND BALANCE REPORTS | | | O) SMOKE CONTROL TEST REPORTS. | | | | | | 2A) SUBMITTALS TO BE PROVIDED TO THE BUILDING | | | DEPARTMENT FOR REVIEW. | | | A) SIGNED AND SEALED STRUCTURAL ENGINEERING FOR | | | INSTALLATION OF ALL EXTERIOR MECHANICAL EQUIPMENT AND | | | APPLIANCES. ALL DELEGATED ENGINEERING SHALL BEAR THE | | | SHOP DRAWING STAMP OF THE STRUCTURAL ENGINEER RECORD. | | | B) GENERATORS AND FUEL TANKS AND ALL ASSOCIATED | | | EQUIPMENT, VENT FLUES, AND FUEL OIL PIPING. | | | C) BOILERS AND WATER HEATERS INCLUDING COMBUSTION AIR | | | DUCTS AND VENT FLUES. | | | D) COMMISSIONING REPORTS | | | PLEASE NOTE: ALL SUBMITTALS AND SHOP DRAWINGS SHALL | | | BEAR THE APPROVAL STAMP AND SIGNATURE OF THE DESIGN | | | PROFESSIONAL OF RECORD. ALL REQUIRED SUBMITTALS MAY BE | | | DEFERRED IN ACCORDANCE WITH SECTION 107.3.4.1 WPB. IT | | | WILL BE HELPFUL TO UPLOAD A MASTER LIST OF DEFERRED | | | SUBMITTALS IN DOCUMENT FORM, OR IN THE FORM OF NOTES ON | | | THE MECHANICAL PLANS. | | | DEFERRED SUBMITTALS: FOR THE PURPOSES OF THIS SECTION, | | | DEFERRED SUBMITTALS ARE DEFINED AS THOSE PORTIONS OF | | | THE DESIGN THAT ARE NOT SUBMITTED AT THE TIME OF THE | | | APPLICATION AND THAT ARE TO BE SUBMITTED TO THE | | | BUILDING OFFICIAL WITHIN A SPECIFIED PERIOD. DEFERRAL | | | OF ANY SUBMITTAL ITEMS SHALL HAVE THE PRIOR APPROVAL OF | | | THE BUILDING OFFICIAL. THE REGISTERED DESIGN | | | PROFESSIONAL IN RESPONSIBLE CHARGE SHALL LIST THE | | | DEFERRED SUBMITTALS ON THE CONSTRUCTION DOCUMENTS FOR | | | REVIEW BY THE BUILDING OFFICIAL. | | | DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE | | | SUBMITTED TO THE REGISTERED DESIGN PROFESSIONAL IN | | | RESPONSIBLE CHARGE WHO SHALL REVIEW THEM AND FORWARD | | | THEM TO THE BUILDING OFFICIAL WITH A NOTATION | | | INDICATING THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE | | | BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO | | | THE DESIGN OF THE BUILDING. | | | | | | 3) SEPARATE PERMITS: SEPARATE PERMITS ARE REQUIRED FOR | | | COMMERCIAL KITCHEN EXHAUST HOODS, FIRE SUPPRESSION | | | SYSTEMS, AND WALK-IN COOLERS AND FREEZERS. PLEASE PLACE | | | NOTES ON THE MAIN BUILDING PLANS ACCORDINGLY AND | | | PROVIDE THE FOLLOWING INFORMATION FOR THE KITCHEN | | | HOODS. | | | A) LOCATIONS OF HOODS, EXHAUST AND MAKEUP AIR FANS AND | | | DUCTWORK, EXHAUST AND MAKEUP AIR OUTLETS AND INLETS, | | | MUA UNITS IF PROVIDED. | | | B) AIR BALANCE CALCULATIONS. | | | C) ADVISORY: REFER TO SECTION 508.1.1 FBC M. MAKEUP AIR | | | TEMPERATURE: THE TEMPERATURE DIFFERENTIAL BETWEEN | | | MAKEUP AIR AND THE AIR IN THE CONDITIONED SPACE SHALL | | | NOT EXCEED 10 DEGREES F (6 DEGREES C) EXCEPT WHERE THE | | | ADDED HEATING AND COOLING LOADS OF THE MAKEUP AIR DO | | | NOT EXCEED THE CAPACITY OF THE HVAC SYSTEM. | | | | | | 4) PROVIDE VENTILATION CALCULATIONS AND A SCHEDULE THAT | | | INDICATES THE REQUIRED AND PROVIDED OUTDOOR AND EXHAUST | | | AIRFLOW RATES. THE O/A CFMS LISTED IN THE 100% O/A-ERU | | | AND AHU EQUIPMENT SCHEDULES SHALL CORRELATE WITH THE | | | CALCULATIONS. PLEASE ALSO PROVIDE AIR BALANCE | | | CALCULATIONS ? TABLE 403.3.1.1 FBC M & SECTION C403.2.7 | | | FBC EC. | | | 5) PROVIDE CALCULATIONS FOR THE POST FIRE SMOKE PURGE | | | SYSTEM AND FANS- SEE SECTION 403.4.7 FBC B. | | | 6) PARKING GARAGE EXHAUST- PODIUM LEVELS 1- 6 (SHEETS | | | M201, 202, 203, 204, 205, 206) PROVIDE CALCULATIONS- | | | TABLE 403.3.1.1 AND SECTION 404.1 FBC M. A) INDICATE | | | THE SEQUENCE OF OPERATION FOR THE EXHAUST SYSTEM- | | | SECTION 404.2 FBC M. ADVISORY: PLEASE PROVIDE NOTES AND | | | DETAILS ON THE PLANS THAT ARE CONSISTENT WITH THE | | | SEQUENCING NOTES ON SHEET M.813. B) SUBMIT | | | MANUFACTURER'S SPECIFICATIONS FOR THE CO AND NO2 | | | SENSORS (MAY BE DEFERRED PER COMMENT #2). C) REFER TO | | | SECTION C403.2.6.2 FBC EC FOR ENERGY COMPLIANCE | | | REQUIREMENTS. | | | | | | PODIUM | | | 7) SHEETS M.201-M.208 A, B, C, & D QUADRANTS: DUCT | | | SMOKE DETECTORS ARE REQUIRED IN THE SUPPLY SYSTEMS OF | | | THE AHU'S PER SECTION 606.2.1 FBC M. PLEASE PROVIDE DS | | | SYMBOLS ON THE PLANS AND RISER DRAWINGS TO SHOW THE | | | LOCATIONS. | | | 8) M.201-M.208 A, B, C, & D QUADRANTS: DUCT SMOKE | | | DETECTORS ARE REQUIRED IN THE SUPPLY SYSTEMS OF THE | | | 100% O/A ERU SYSTEMS, AND AT EACH STORY OF THE RA/EA | | | RISER- SECTION 606.2.3. PLEASE PROVIDE DS SYMBOLS ON | | | THE PLANS AND RISER DRAWINGS TO SHOW THE LOCATIONS. | | | 9) M.201-M.208 A, B, C, & D QUADRANTS: SHOW CLEARANCE | | | DISTANCE MEASUREMENTS FOR O/A INTAKES AND EXHAUST | | | OUTLETS IN COMPLIANCE WITH SECTIONS 401.4 AND 501.3.1 | | | FBC M OR PROVIDE GENERAL KEYNOTES. | | | 10) M.201-M.208 A, B, C, & D QUADRANTS: REFER TO | | | SECTION 306.1 AND VERIFY ACCESS IS PROVIDED FOR AC AND | | | FAN UNITS LOCATED ABOVE HARD CEILING. SHOW AN ACCESS | | | PANEL WITH DIMENSIONS ON THE DRAWINGS WHERE REQUIRED- | | | SECTION 306.1 FBC M.1 | | | 11) M.201-M.208 A, B, C, & D QUADRANTS: PLACE NOTES TO | | | INDICATE LOCATIONS OF ABOVE CEILING PLENUMS AND NO | | | COMBUSTIBLE MATERIALS PERMITTED. | | | 12) SHEETS M.201-M.208 A, B, C, & D QUADRANTS: BRANCH | | | AND FLEX DUCT SIZES NOT SHOWN- SECTION 603.1 FBC M. | | | 13) M.201- M.208 A, B, C, D QUADRANTS WHERE APPLICABLE: | | | FIRE DAMPERS MISSING FOR THE O/A BRANCH DUCTS | | | PENETRATING THE FIRE-RATED CORRIDOR/SUITE, AND | | | CORRIDOR/RESIDENTIAL UNIT WALLS- SECTION 607.5.3 FBC M. | | | 14) M.201- M.208 A, B, C, D QUADRANTS WHERE APPLICABLE: | | | PLACE NOTES TO INDICATE NO COMBUSTIBLE MATERIALS | | | PERMITTED IN THE VHP CLOSETS INCLUDING THE DOORS- | | | SECTION 602.2.1 FBC M. IT APPEARS THE DOORS WILL BE | | | LOUVERED TO ALLOW RETURN AIR TO THE HEAT PUMPS, | | | OTHERWISE INDICATE MEANS OF RETURN AIR- SECTION 601.6 | | | FBC M. | | | 15) M.201- M.208 A, B, C, D: AUTOMATICALLY OPERATING | | | SHUTOFF DAMPERS ARE REQUIRED FOR THE O/A DUCTS SERVING | | | THE SUITES AND THE UNITS- SECTION C403.2.4.3 FBC EC. | | | 16) M.201A: AN AUTOMATIC SHUTOFF DAMPER IS REQUIRED FOR | | | THE O/A SUPPLY TO AHU-5- SECTION C403.2.4.3 FBC EC | | | 17) SHEET ALS1.101 & M.201B: FIRE DAMPERS MISSING FOR | | | TOILET EXHAUST DUCT PENETRATING OFFICE/LOBBY & | | | VALET/LOBBY WALLS, & 48X20 EXHAUST DUCT PENETRATING | | | MENS WC/VALET WALL- SECTION 607.5.2 FBC M. | | | 18) M.201B: IDENTIFY THE AC SYSTEM CONNECTED TO THE | | | SUPPLY AND RETURN DROPS IN THE OFFICE/LOBBY ROOM- | | | PROVIDE A NOTE ON THE PLAN- SECTION 107.2.1 WPB. A) | | | IDENTIFY WITH A NOTE THE SYSTEM CONNECTED TO THE 40X20 | | | RETURN DUCT- SECTION 107.2.1 WPB. B) FIRE DAMPERS | | | MISSING FOR THE 48X20 EXHAUST DUCT PENETRATING | | | FIRE-RATED WALLS AT THE FIRE LOBBY, RECEIVING ROOM, AND | | | MENS WC. C) FIRE DAMPER MISSING FOR THE 6X6 SUPPLY | | | PENETRATING FIRE-RATED WALL AT THE FIRE LOBBY. | | | 19) M.201C: LABEL THE SYSTEM CONNECTED TO THE 60X24 | | | DROPS IN THE SCREENING ROOM- SECTION 107.2.1 WPB. | | | 20) ALS1.101 & M.201C: THERE ARE NUMEROUS FIRE DAMPERS | | | MISSING FOR SUPPLY, RETURN, AND EXHAUST DUCTS RUNNING | | | THROUGH THE FIRE-RATED WALLS AT THE TRASH ROOM, OFFICE, | | | RESIDENT?S LOUNGE, ETC.- SECTION 607.5.2 FBC M. MANY OF | | | THESE ARE BRANCHING OFF THE TWO MAIN 60X24 DUCTS. | | | 21) M.201C: SHOW THE LOCATION OF MAU-01. | | | 22) M.201C: SUBMIT MANUFACTURER'S SPECIFICATIONS AND UL | | | CERTIFICATE FOR THE 2000-GALLON FUEL TANK. | | | 23) M.201C: VENTILATION IS REQUIRED FOR THE FUEL TANK | | | ROOM AND IT CANNOT BE ACHIEVED NATURALLY BECAUSE OF THE | | | ROOM LOCATION. REFER TO SECTION 24.10.2 NFPA 30 AND | | | PROVIDE A MECHANICAL VENTILATION SYSTEM THAT INCLUDES | | | CALCULATIONS AND SPECIFICATIONS FOR EXHAUST AND MAKEUP | | | AIR. A) PROVIDE DETAILS AND SPECIFICATIONS FOR NORM AND | | | EMERGENCY RELIEF VENTING OF THE TANK, INCLUDING VENT | | | PIPING RUNS AND TERMINATION LOCATIONS AT THE EXTERIOR | | | OF THE BUILDING- SECTION 24.13 NFPA 30. | | | 24) THE EXHAUST SYSTEM FOR THE FIRE PUMP ROOM IS | | | INCOMPLETE- PLEASE PROVIDE THE TYPE AND SIZE OF EXHAUST | | | DUCT, LOCATION OF EXHAUST FAN, FAN EQUIPMENT SCHEDULE, | | | EXHAUST CALCULATIONS AND SEQUENCE OF OPERATION, AND | | | SOURCE OF MAKEUP AIR. | | | 25) M.201D: FIRE DAMPERS MISSING FOR THE DUCTS | | | PENETRATING THE FIRE-RATED WALLS AT THE SERVICE | | | CORRIDOR AND AHU LOBBY ROOM- SECTION 607.5.2 FBC M. | | | 26) M202B: THE EXHAUST FROM EF-A01 & EF-A02 SHALL | | | DISCHARGE TO THE OUTDOORS AND NOT INTO THE ENCLOSED | | | GARAGE- SECTION 501.3 FBC M. | | | 27) M.202B: DUCTWORK IN THE OPEN AREA IS INCOMPLETE- NO | | | DUCT SIZES, AIRFLOWS, SYSTEM IDENTIFICATION ETC.- | | | SECTION 107.2.1 WPB. | | | 28) M.202B: PROVIDE NOTES AT AHU-03 TO INDICATE WHICH | | | AREA IS BEING CONDITIONED BY THE SYSTEM, AND HOW O/A IS | | | BEING PROVIDED AND AUTOMATICALLY CONTROLLED- SECTION | | | C404.2.4.3 FBC EC. | | | 29) M.202B: FIRE DAMPER MISSING FOR THE 8X8 SUPPLY DUCT | | | PENETRATING FIRE-RATED WALL AT THE FIRE LOBBY. | | | 30) M.202C: PROVIDE A TERMINATION CAP FOR THE PFP SMOKE | | | PURGE DUCT, AND INDICATE MINIMUM 10' CLEARANCE TO THE | | | O/A INTAKES LOCATED IN PROXIMITY OF THE OUTLET- SECTION | | | 501.3.1 FBC M. | | | 31) M.202C: AUTOMATIC SHUTOFF DAMPERS ARE REQUIRED FOR | | | THE O/A SUPPLY DUCTS TO AHU-5 AND SPF-01- SECTION | | | C403.2.4.3 FBC EC. | | | 32) M.202C: IDENTIFY THE SOURCE OF THE O/A DUCT TRUCK | | | SUPPLYING THE VERTICAL HEAT PUMPS (VHP) IN THE UNITS | | | AND PROVIDE AUTOMATIC SHUTOFF DAMPERS AT EACH SUPPLY- | | | SECTION 107.2.1 WPB AND SECTION C403.2.4.3 FBC EC. | | | 33) M.202C: THE 22X22 SPF-01 INTAKE DUCT SHALL BE | | | COMPLETELY ENCLOSED IN A FIRE-RATED HORIZONTAL ASSEMBLY | | | AS REQUIRED BY SECTION 909.20.6.1 FBC B. SUBMIT | | | MANUFACTURER?S SPECIFICATIONS FOR THE 2-HR FIRE | | | WRAPPING (MAY BE DEFERRED SUBMITTAL). A FIRE/SMOKE | | | DAMPER IS REQUIRED AT SG-3 PENETRATION INTO STAIR-1 - | | | SECTION 1023.5 FBC B. | | | 34) M.202D: PROVIDE NOTES AT AHU-04 TO INDICATE WHICH | | | AREA IS BEING CONDITIONED BY THE SYSTEM, AND HOW O/A IS | | | BEING PROVIDED AND AUTOMATICALLY CONTROLLED- SECTION | | | C404.2.4.3 FBC EC. | | | 35) M.202D: FIRE DAMPERS MISSING FOR THE O/A BRANCH | | | DUCTS PENETRATING THE FIRE-RATED CORRIDOR WALLS. | | | 36) M.203B: IDENTIFY THE SOURCE OF THE O/A DUCT TRUCK | | | SUPPLYING THE FAN COIL UNITS (FCU) IN THE UNITS AND | | | PROVIDE AUTOMATIC SHUTOFF DAMPERS FOR THE SUPPLY AT | | | EACH UNIT- SECTION 107.2.1 WPB AND SECTION C403.2.4.3 | | | FBC EC. | | | 37) M.203B: INDICATE WHAT AIR IS BEING RETURNED VIA THE | | | 54X24 RA DUCT IN THE SHAFT. THE PLAN SHOWS NO DUCTS | | | CONNECTING TO IT. | | | 38) M.203B: FIRE DAMPER MISSING FOR THE 6X6 SUPPLY DUCT | | | PENETRATING FIRE-RATED WALL AT THE FIRE LOBBY. | | | 39) M.203C: THE SPF-03 INTAKE DUCT SHALL BE COMPLETELY | | | ENCLOSED IN A FIRE-RATED HORIZONTAL ASSEMBLY AS | | | REQUIRED BY SECTION 909.20.6.1 FBC B. A FIRE/SMOKE | | | DAMPER IS REQUIRED AT SG-2 PENETRATION INTO STAIR-2 - | | | SECTION 1023.5 FBC B. | | | 40) M.203C & D: IDENTIFY THE SOURCE OF THE O/A DUCT | | | TRUCK SUPPLYING THE VERTICAL HEAT PUMPS (VHP) IN THE | | | UNITS AND PROVIDE AUTOMATIC SHUTOFF DAMPERS FOR THE | | | SUPPLY AT EACH UNIT- SECTION 107.2.1 WPB AND SECTION | | | C403.2.4.3 FBC EC. | | | 41) M.203C & D: FIRE DAMPERS MISSING FOR THE O/A BRANCH | | | DUCTS PENETRATING THE FIRE-RATED CORRIDOR WALLS- | | | SECTION 607.5.3 FBC M. | | | 42) M.203C & D: PLACE NOTES TO INDICATE NO COMBUSTIBLE | | | MATERIALS PERMITTED IN THE VHP CLOSETS INCLUDING THE | | | DOORS- SECTION 602.2.1 FBC M. IT APPEARS THE DOORS WILL | | | BE LOUVERED TO ALLOW RETURN AIR TO THE HEAT PUMPS., | | | OTHERWISE INDICATE MEANS OF RETURN AIR- SECTION 601.6 | | | FBC M. | | | 43) M.204B: FIRE DAMPERS MISSING FOR THE O/A BRANCH | | | DUCTS PENETRATING THE FIRE-RATED CORRIDOR/SUITE WALLS- | | | SECTION 607.5.3 FBC M. | | | 44) M.204B: INDICATE WHAT AIR IS BEING RETURNED VIA THE | | | 54X24 RA DUCT IN THE SHAFT. THE PLAN SHOWS NO DUCTS | | | CONNECTING TO IT. | | | 45) M.204B: FIRE DAMPER MISSING FOR THE 6X6 SUPPLY DUCT | | | PENETRATING FIRE-RATED WALL AT THE FIRE LOBBY. | | | 46) M.204C & D: IDENTIFY THE SOURCE OF THE O/A DUCT | | | TRUCK SUPPLYING THE VERTICAL HEAT PUMPS (VHP) IN THE | | | UNITS AND PROVIDE AUTOMATIC SHUTOFF DAMPERS FOR THE | | | SUPPLY AT EACH UNIT- SECTION 107.2.1 WPB AND SECTION | | | C403.2.4.3 FBC EC. | | | 47) M.204C & D: FIRE DAMPERS MISSING FOR THE O/A BRANCH | | | DUCTS PENETRATING THE FIRE-RATED CORRIDOR WALLS- | | | SECTION 607.5.3 FBC M. | | | 48) M.205B: SHOW THE O/A AND EXHAUST DUCT RUNS AND | | | INLET AND OUTLET LOCATIONS FOR ERU-01- SECTION 107.2.1 | | | WPB AND SECTIONS 401.4 & 501.3.1 FBC M. | | | 49) M.205B: FIRE DAMPER MISSING FOR THE 6X6 SUPPLY DUCT | | | PENETRATING FIRE-RATED WALL AT THE FIRE LOBBY. | | | 50) M.205C: SHOW THE O/A AND EXHAUST DUCT RUNS AND | | | INLET AND OUTLET LOCATIONS FOR ERU-02- SECTION 107.2.1 | | | WPB AND SECTIONS 401.4 & 501.3.1 FBC M. | | | 51) M.205C & D: FIRE DAMPERS MISSING FOR THE O/A BRANCH | | | DUCTS PENETRATING THE FIRE-RATED CORRIDOR WALLS- | | | SECTION 607.5.3 FBC M. | | | 52) M.205C & D: IDENTIFY THE SOURCE OF THE O/A DUCT | | | TRUCK SUPPLYING THE VERTICAL HEAT PUMPS (VHP) IN THE | | | UNITS AND PROVIDE AUTOMATIC SHUTOFF DAMPERS FOR THE | | | SUPPLY AT EACH UNIT- SECTION 107.2.1 WPB AND SECTION | | | C403.2.4.3 FBC EC. | | | 53) M.206A: PROVIDE AN ENLARGED DRAWING OF THE EPSS | | | (EMERGENCY GENERATOR) ROOM SHOWING THE LOCATIONS OF THE | | | GENERATOR AND FUEL TANK, FUEL OIL PIPE AND EXHAUST PIPE | | | RUNS AND TERMINATION LOCATIONS, AND ALL OTHER | | | ASSOCIATED EQUIPMENT INCLUDING EMERGENCY ELECTRICAL | | | PANELS ETC. PLEASE INCLUDE THE REQUIRED CLEARANCE | | | DISTANCE MEASUREMENTS FOR ALL EQUIPMENT VENT PIPING | | | RUNS AND SPECIFICATIONS INCLUDING FILL PIPING | | | LOCATIONS. | | | A) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE | | | GENERATOR AND THE 190-GALLON FUEL TANK, FUEL PIPING, | | | ENGINE EXHAUST PIPE, MUFFLER, AND ALL OTHER ASSOCIATED | | | SYSTEM COMPONENTS- SECTION 304.1 FBC M | | | B) SUBMIT THE UL 2200 CERTIFICATE OF COMPLIANCE FOR THE | | | GENERATOR- SECTION 915.1 FBC M. | | | C) THE MANUFACTURER'S SPECIFICATIONS AND/OR UL | | | CERTIFICATE SHALL INDICATE THE GENERATOR IS COMPLIANT | | | WITH THE NFPA 37 AND NFPA 110 STANDARDS | | | D) SUBMIT A CUT SHEET FOR THE FUEL TANK THAT INCLUDES | | | THE TANK'S UL LISTING- UL 142 OR UL 2085- SEE SECTION | | | 21.4.2.1.1 NFPA 30. | | | E) REFER TO 4.1 NFPA 110 AND INDICATE THE | | | CLASSIFICATION AND LEVEL OF THE EPSS SYSTEM. PLEASE | | | INCLUDE THIS INFORMATION IN THE SMOKE CONTROL RATIONAL | | | ANALYSIS. | | | F) SUBMIT THE GENERATOR EXHAUST PIPE SPECIFICATIONS AND | | | PROVIDE AN EXHAUST PIPE DIAGRAM SHOWING THE TOTAL | | | SYSTEM RUN AND LENGTH MEASUREMENT, AND TERMINATION | | | LOCATION PLEASE INCLUDE ALL COMPONENTS OF THE SYSTEM | | | INCLUDING THE SILENCER, AND ANY CONTRACTOR SUPPLIED | | | PIPING- SEE SECTION 8.1 ? 8.4 NFPA 37, AND SECTION | | | 501.3.1 FBC M. | | | G) PROVIDE BACKPRESSURE CALCULATIONS FOR THE GENERATOR | | | EXHAUST PIPE RUN- SECTION 304.1 FBC M. | | | H) REFER TO SECTIONS 7.7.2,1 &, 7.7.2.3 & 7.7.3 NFPA | | | 110: PER THE ENGINEER'S PLAN AND NARRATIVE, THE | | | VENTILATION AIR FOR THE GENERATOR ROOM IS BEING DRAWN | | | IN THROUGH A LOUVERED OPENING IN THE 2HR. FIRE-RATED | | | WALL GENERATOR ROOM WALL THAT ADJACENT TO THE PARKING | | | GARAGE WHICH IS NOT PERMITTED PER SECTION 7.7.2.1 & | | | 7.7.2.3. THESE SECTIONS STATE THAT VENTILATION AIR MUST | | | BE SUPPLIED DIRECTLY FROM A SOURCE OUTSIDE THE | | | BUILDING. SECTION 7.7.2.3 PROHIBITS THE USE OF A FIRE | | | DAMPER TO PROTECT THE OPENING, THEREFORE THE | | | VENTILATION OPENING LOCATION WOULD NOT BE COMPLIANT | | | BECAUSE OPENINGS IN FIRE BARRIERS REQUIRE PROTECTION | | | ACCORDING TO SECTION 607.5.2 FBC M. INDICATE HOW | | | VENTILATION WILL BE PROVIDED FOR THE GENERATOR/FUEL | | | TANK ROOM. | | | J) PROVIDE DETAILS AND SPECIFICATIONS FOR NORM AND | | | EMERGENCY RELIEF VENTING OF THE TANK, INCLUDING VENT | | | PIPING RUNS AND TERMINATION LOCATIONS AT THE EXTERIOR | | | OF THE BUILDING- SECTION 24.13 NFPA 30. | | | K) M-401: REFER TO SECTION 7.7.1 NFPA 110- 2016 AND | | | VERIFY THAT THE VENTILATION AIRFLOW IN THE | | | GENERATOR/TANK (EPS) ROOM IS DESIGNED TO LIMIT THE | | | MAXIMUM AIR TEMPERATURE IN THE ROOM TO THE MAXIMUM | | | AMBIENT AIR TEMPERATURE REQUIRED BY THE GENERATOR | | | MANUFACTURER. CONSIDERATION SHALL BE GIVEN TO ALL THE | | | HEAT EMITTED TO THE ROOM BY THE ENERGY CONVERTER, | | | EXHAUST PIPES, AND ALL OTHER HEAT PRODUCING EQUIPMENT- | | | SECTION 7.7.1.1. DESIGN OF THE HEATING, COOLING, AND | | | VENTILATION SYSTEM SHALL AMONG OTHER THINGS, INCLUDE | | | PROVISIONS FOR FACTORS SUCH AS HEAT, COLD, HUMIDITY, | | | LOUVERS, ETC.- SECTION 7.7.7. 57) M.205A, B, C, & D: | | | SHOW CLEARANCE DISTANCE MEASUREMENTS FOR O/A INTAKES | | | AND EXHAUST OUTLETS IN COMPLIANCE WITH SECTIONS 401.4 | | | AND 501.3.1 FBC M OR PROVIDE GENERAL KEYNOTES. | | | 54) M.206A & B: INDICATE WHAT APPLIANCES ARE CONNECTED | | | TO THE INTAKE VENT AND EXHAUST FLUE PIPES AT THE H. | | | AMENITIES ROOM. SHOW THE APPLIANCES IN THE ROOM, | | | PROVIDE EQUIPMENT SCHEDULES ON THE PLAN AND SUBMIT | | | MANUFACTURER?S SPECIFICATIONS- SECTIONS 503.1 AND 624.1 | | | FG. ASSUMING THESE APPLIANCES ARE GAS-FIRED PLEASE | | | PROVIDE THE GAS PIPING REQUIREMENTS TO THE MAIN GAS | | | PLAN- SECTION 402.1 FBC FG. | | | 55) M.206B: FIRE DAMPERS MISSING FOR THE O/A BRANCH | | | DUCTS PENETRATING THE FIRE-RATED CORRIDOR/SUITE WALLS- | | | SECTION 607.5.3 FBC M. | | | 56) M.206B: THE 16X6 O/A DUCT SHALL NOT PENETRATE AND | | | RUN THROUGH THE INTERIOR EXIT STAIRWAY- 1023.5 FBC B. | | | 57) M.206B: THE ERU EXHAUST SHALL TERMINATE OUTDOORS OF | | | THE BUILDING. IT APPEARS TO BE EXHAUSTING INTO AN | | | INTERSTITIAL SPACE- SECTION 501.3 FBC M. | | | 58) M.206C: FIRE DAMPERS MISSING FOR THE O/A BRANCH | | | DUCTS PENETRATING THE FIRE-RATED CORRIDOR WALLS- | | | SECTION 607.5.3 FBC M. | | | 59) M.206C: DUCT DROPS TO ERU-02 ARE MISLABELED AS | | | DROPS TO AHU-02- SECTION 107.2.1 FBC M. | | | 60) M.206C: IN-LINE EXHAUST FANS ARE SHOWN ON EXHAUST | | | DUCTS THAT ARE SPECIFIED TO HAVE FIRE WRAPPING WHICH IS | | | NOT IN COMPLIANCE WITH EITHER THE FAN OR THE DUCT WRAP | | | LISTING AND INSTALLATION INSTRUCTIONS- SECTION 304.1 | | | FBC M. | | | 61) M.206C: THE SPF-13 INTAKE DUCT SHALL BE COMPLETELY | | | ENCLOSED IN A FIRE-RATED HORIZONTAL ASSEMBLY AS | | | REQUIRED BY SECTION 909.20.6.1 FBC B. A FIRE/SMOKE | | | DAMPER IS REQUIRED AT SG-3 PENETRATION INTO STAIR-12 - | | | SECTION 1023.5 FBC B. | | | 62) M.207A: FIRE DAMPERS MISSING FOR SUPPLY AND RETURN | | | DUCTS FROM AHU-08 & AHU-09 PENETRATING FIRE-RATED WALLS | | | AT POOL EQUIP, POOL DECK, FITNESS STUDIO, AND MENS WC | | | WALLS- SECTION 607.5.2 FBC M. | | | 63) M.207A: FIRE DAMPERS MISSING FOR SUPPLY AND RETURN | | | DUCTS FROM AHU-08 & AHU-09 PENETRATING FIRE-RATED WALLS | | | AT MENS WC AND PREFUNCTION- SECTION 607.5.2 FBC M. A) | | | INDICATE THE DIMENSIONS OF THE AHU-09 SUPPLY DUCT. | | | 64) M.207A: THE EXHAUST DUCT FROM MENS WC AND WOMENS WC | | | SHALL DISCHARGE TO THE OUTDOORS- SECTION 501.3 FBC M. | | | 65) M.207A: AUTOMATIC DAMPERS ARE REQUIRED FOR THE O/A | | | INTAKES AT AHU-08 & 09- SECTION C403.2.4.3 FBC EC. | | | 66) M.207A: PROVIDE EXHAUST VENTILATION CALCULATIONS | | | FOR EF-A07 & EF-A09. IT APPEARS ONE OF FANS IS | | | CONNECTED TO THE RA DUCT AT AHU-09. | | | 67) M.207A: IT APPEARS THE PRESSURIZATION DUCTS FROM | | | SPF-07, 10, & 15 ARE ENCLOSED IN FIRE WRAPPING. PLEASE | | | CLARIFY BY PLACING A NOTE ON THE PLAN- SECTION | | | 909.20.6.1 FBC B. | | | 68) M.207A: SUBMIT MANUFACTURER'S SPECIFICATIONS FOR | | | THE 3-HR FIRE WRAP ENCLOSING THE GENERATOR EXHAUST | | | DUCT. TERMINATE DUCT AT THE EXTERIOR WITH AN ENDCAP. | | | 69) M.207A: PROVIDE AN ENLARGED DRAWING OF THE LAUNDRY | | | ROOM THAT SHOWS THE LOCATION OF ALL EQUIPMENT, AND THE | | | EXHAUST AND MAKEUP AIR SYSTEM DETAILS AND | | | SPECIFICATIONS. SUBMIT MANUFACTURER'S SPECIFICATIONS | | | FOR THE DRYERS PER SECTION- 504.1 FBC M. | | | 70) M.207A: INDICATE THE TYPE OF DUCTWORK TO BE USED IN | | | THE LAP POOL ROOM- SECTION 603 FBC M. | | | 71) M.207A: PROVIDE EXHAUST VENTILATION CALCULATIONS | | | FOR THE POOL ROOM AND SHOW HOW MAKEUP AIR IS BEING | | | PROVIDED- SECTION 501.4 FBC M. CLARIFY IF THE POOL | | | EQUIPMENT IS TO BE INSTALLED UNDER SEPARATE PERMIT- | | | PLACE A NOTE ON THE PLANS. | | | 72) M.207B: VERIFY THE EXHAUST AIR LOUVER FOR THE | | | FUTURE KITCHEN IS IN COMPLIANCE WITH SECTION 506.3.13.2 | | | AND 506.3.13.3 FBC M. REFER TO COMMENT #3 FOR MORE | | | INFORMATION. | | | 73) M.207B: FIRE DAMPERS MISSING FOR THE O/A BRANCH | | | DUCTS PENETRATING THE FIRE-RATED CORRIDOR WALLS- | | | SECTION 607.5.3 FBC M. | | | 74) M.207B: FIRE/SMOKE DAMPERS REQUIRED AT SG-3 | | | PRESSURIZATION INLETS AT STAIR-4 AND STAIR-8. | | | 75) M.207C: FIRE DAMPERS REQUIRED FOR THE AHU-09 SUPPLY | | | DUCT AND 36X30 TRANSFER DUCT PENETRATING THE FITNESS | | | AND SPA FIRE-RATED WALLS, AND THE 10' DUCT PENETRATING | | | THE SPA/FITNESS OFFICE WALL- SECTION 607.5.2 FBC M. | | | FIRE WRAPPING OF THE DUCT IN JUST THESE SECTIONS OF THE | | | DUCT MUST BE VERIFIED TO BE CONSISTENT WITH THE | | | MANUFACTURER'S LISTING AND INSTALLATION INSTRUCTIONS- | | | SECTION 304.1 FBC M. | | | 76) M.207C: NO DIFFUSER IS SHOWN AT THE END OF THE | | | 16X14 SUPPLY DUCT AT THE SPA- SECTION 603. | | | 77) M.207C: FIRE DAMPERS MISSING FOR THE LOCKER ROOM | | | EXHAUST DUCTS PENETRATING THE FIRE-RATED LOCKER ROOM | | | WALLS- SECTION 607.5.3 FBC M. | | | 79) M.207C: FIRE DAMPERS MISSING FOR THE LOCKER ROOM | | | SUPPLY AND RETURN DUCTS PENETRATING THE FIRE-RATED | | | LOCKER ROOM WALLS- SECTION 607.5.2 FBC M. | | | 80) M.207C: IT APPEARS NO O/A HAS BEEN PROVIDED FOR | | | UNITS A6, B1, AND S6- TABLE 403.3.1.1. FBC M. | | | 81) M.207D: FIRE DAMPERS MISSING AT THE DUCTS | | | PENETRATING THE CORRIDOR/WOMENSWC/MENSWC FIRE RATED | | | WALLS- SECTION 607.5.2 FBC M. | | | 82) M.208A: LABEL THE PRESSURIZATION FAN SHOWN AT THE | | | UNIDENTIFIED INTERIOR EXIT STAIRWAY THE INTAKE DUCT | | | SHALL BE COMPLETELY ENCLOSED IN A FIRE-RATED HORIZONTAL | | | ASSEMBLY AS REQUIRED BY SECTION 909.20.6.1 FBC B. A | | | FIRE/SMOKE DAMPER IS REQUIRED AT THE DIFFUSER | | | PENETRATION INTO THE STAIRWAY- SECTION 1023.5 FBC | | | 83) M.208A: FIRE DAMPERS AND O/A DAMPER MISSING AT THE | | | 28X28 INTAKE DUCT PENETRATING INTO THE STORAGE ROOM | | | 84) M.208A: FIRE DAMPERS MISSING FOR THE TENNIS COURTS | | | SUPPLY AND RETURN DUCTS PENETRATING INTO THE STORAGE | | | ROOM. | | | 85) M.208AAC SYSTEM FOR THE TENNIS COURTS IN THE | | | STORAGE ROOM NOT IDENTIFIED. | | | 86) M.208C: IT APPEARS NO O/A HAS BEEN PROVIDED FOR | | | UNITS B1, B2, B3, & A4- TABLE 403.3.1.1. FBC M. | | | 87) M.208C: FIRE DAMPERS MISSING FOR THE 18X14 SUPPLY | | | AND RETURN DUCTS PENETRATING THROUGH THE FIRE-RATED | | | CORRIDOR WALL- SECTION 607.5.3 FBC M. | | | 88) M.208D: FIRE DAMPERS MISSING FOR THE BRANCH DUCT | | | PENETRATING THE FIRE LOBBY WALL, AND ALL OTHER BRANCH | | | DUCTS PENETRATING FIRE-RATED CORRIDOR WALLS- SECTION | | | 607.5.2 & 607.5.3 FBC M. | | | | | | HOTEL TOWER | | | 89) SHEETS M.209, M.211, & M.212: DUCT SMOKE DETECTORS | | | ARE REQUIRED IN THE SUPPLY SYSTEMS OF THE AHU'S PER | | | SECTION 606.2.1 FBC M. PLEASE PROVIDE DS SYMBOLS ON THE | | | PLANS AND RISER DRAWINGS TO SHOW THE LOCATIONS. | | | 91) M.209, M.211, M.212: DUCT SMOKE DETECTORS ARE | | | REQUIRED IN THE SUPPLY SYSTEMS OF THE 100% O/A ERU | | | SYSTEMS, AND AT EACH STORY OF THE RA/EA RISER- SECTION | | | 606.2.3. PLEASE PROVIDE DS SYMBOLS ON THE PLANS AND | | | RISER DRAWINGS TO SHOW THE LOCATIONS. | | | 92) M.209, M.211, M.212: PROVIDE A FIRE-RATED ENCLOSURE | | | AND ACCESS PANEL FOR THE DEF'S AND SUBMIT SPECS FOR THE | | | FAN AND THE EXHAUST DUCT FIRE WRAPPING- SECTIONS 304.1 | | | & 306.1. A) REFER TO SECTION 504.1 AND SUBMIT | | | MANUFACTURER'S SPECIFICATIONS FOR THE CLOTHES DRYERS. | | | PROVIDE ON THE PLANS DRYER EXHAUST DUCT DIAGRAMS THAT | | | SHOW THE TOTAL RUN LENGTHS OF THE SYSTEMS CONSISTENT | | | WITH THE MANUFACTURER'S GUIDELINES. B) REFER TO SECTION | | | 504.9 AND PROVIDE A SEQUENCE OF OPERATION FOR THE | | | DEF?S. | | | 93) M.209, M.211, M.212: FIRE DAMPERS MISSING FOR THE | | | O/A BRANCH DUCTS AND TOILET EXHAUST DUCTS PENETRATING | | | THE FIRE-RATED CORRIDOR/SUITE WALLS- SECTION 607.5.3 | | | FBC M. | | | 94) M.209, M.211, M.212: SHOW CLEARANCE DISTANCE | | | MEASUREMENTS FOR THE EXHAUST OUTLETS IN COMPLIANCE WITH | | | SECTIONS 501.3.1 FBC M OR PROVIDE GENERAL KEYNOTES. | | | 95) M.209, M.211, M.212: REFER TO SECTION 306.1 AND | | | VERIFY ACCESS IS PROVIDED FOR AC AND FAN UNITS LOCATED | | | ABOVE HARD CEILING. SHOW AN ACCESS PANEL WITH | | | DIMENSIONS ON THE DRAWINGS WHERE REQUIRED- SECTION | | | 306.1 FBC M. | | | 96) M.209, M.211, M.212: INDICATE LOCATIONS OF ABOVE | | | CEILING PLENUMS AND AIR HANDLER CLOSETS AND NOTE NO | | | COMBUSTIBLE MATERIALS PERMITTED. | | | 97) M.209, M.211, M.212: BRANCH DUCT SIZES NOT SHOWN- | | | SECTION 603.1 FBC M. | | | 98) M.209, M.211, M.212: AUTOMATICALLY OPERATING | | | SHUTOFF DAMPERS ARE REQUIRED FOR THE O/A DUCTS SERVING | | | THE SUITES- SECTION C403.2.4.3 FBC EC. | | | | | | OFFICE TOWER | | | 100) SHEETS M.213, M.214, M.215: INCOMPLETE PLANS AND | | | DETAILS. IT APPEARS THAT OFFICE SHELL SPACES ARE | | | DEPICTED HOWEVER THERE ARE NO NOTES TO CLARIFY. PLEASE | | | LABEL ALL THE ROOMS SHOWN ON THE PLAN- SECTION 107.2.1 | | | WPB. | | | 101) M.213, M.214, M.215: LABEL THE SYSTEMS IN THE MECH | | | RM- SECTION 107.2.1 WPB.102) | | | 102) M.213, M.214, M.215: FIRE/SMOKE DAMPERS MISSING | | | FOR THE 64X28 SUPPLY AND RETURN DUCTS PENETRATING THE | | | FIRE-RATED MECH RM WALLS- SECTION 607.5.3 FBC M. | | | 103) M.213, M.214, M.215: NO O/A OR CONDITIONING HAS | | | BEEN PROVIDED IN THE FIRE AND ELEVATOR LOBBIES- SECTION | | | 107.2.1 WPB. | | | 104): M.213, M.214, M.215: DUCT SMOKE DETECTORS ARE | | | REQUIRED IN THE SUPPLY SYSTEMS OF THE AHU'S PER SECTION | | | 606.2.1 FBC M. PLEASE PROVIDE DS SYMBOLS ON THE PLANS | | | AND RISER DRAWINGS TO SHOW THE LOCATIONS. | | | 105) M.213, M.214, M.215: DUCT SMOKE DETECTORS ARE | | | REQUIRED IN THE SUPPLY SYSTEMS OF THE 100% O/A ERU | | | SYSTEMS, AND AT EACH STORY OF THE RA/EA RISER- SECTION | | | 606.2.3. PLEASE PROVIDE DS SYMBOLS ON THE PLANS AND | | | RISER DRAWINGS TO SHOW THE LOCATIONS. | | | 106) M.216: LABEL ALL ROOMS AND AREAS SHOWN ON THE | | | PLANS- SECTION 107.2.1 WPB. | | | 107) M.216: FIRE DAMPERS MISSING FOR ERU-03 SUPPLY AND | | | RETURN DUCTS PENETRATING THE FIRE-RATED MECHANICAL ROOM | | | WALLS- SECTION 607.5.3 FBC M. | | | 108) M.216: NO O/A OR CONDITIONING HAS BEEN PROVIDED IN | | | THE FIRE AND ELEVATOR LOBBIES- SECTION 107.2.1 WPB. | | | 109) M.216: LABEL THE AIR INLET OPENING AT THE ERU-03 | | | MECHANICAL ROOM- SECTION 107.2.1 WPB. | | | 110) M.216: IT APPEARS THE SMOKE PURGE EXHAUST AND | | | ERU-03 RETURN DUCTS ARE CONNECTED OR IN THE SAME SHAFT- | | | PLEASE CLARIFY- SECTION 107.2.1 WPB. | | | 110) M.216: PROVIDE ENLARGED DRAWINGS OF THE CHILLER | | | MECHANICAL ROOMS AND SHOW HOW THE ROOMS ARE BEING | | | VENTILATED PER SECTIONS 1105.6 FBC M. A) PROVIDE NORMAL | | | AND EMERGENCY VENTILATION CALCULATIONS AND DETAILS- | | | SECTIONS 1105.6.3.1 & 1105.6.3.2 FBC M. C) SHOW THE | | | LOCATIONS OF REFRIGERANT DETECTORS AND SUBMIT | | | MANUFACTURER'S SPECIFICATIONS. D) SHOW HOW THE CHILLERS | | | ARE BEING ANCHORED TO THE STRUCTURE. E) LABEL ALL | | | EQUIPMENT IN THE ROOM AND PROVIDE AN EQUIPMENT | | | SCHEDULE. | | | 111) M.216: PROVIDE AN ENLARGED DRAWING OF THE COOLING | | | TOWER ROOM AND SHOW HOW THE ROOM IS BEING VENTILATED- | | | NATURALLY OR MECHANICALLY- PROVIDE CALCULATIONS AND | | | DETAILS. A) SHOW VAPOR PLUME DISCHARGE LOCATIONS AND | | | REQUIRED CLEARANCE DISTANCES PER SECTION 908.3 FBC M. | | | B) SHOW HOW THE TOWERS ARE BEING ANCHORED TO THE | | | STRUCTURE- SECTION 908.4 FBC M (ENGINEERING FOR SUPPORT | | | AND PLATFORM STRUCTURES MAY BE DEFERRED). C) PROVIDED | | | WATER PIPING SUPPLY AND RETURN DIAGRAMS. D) SHOW THE | | | WATER FEED LINE PIPE AND BACKFLOW PREVENTER | | | CONNECTIONS- SECTION 908.5 FBC M. | | | 112) M.217: CLARIFY IF THE ELEVATOR HOISTWAYS ARE TO BE | | | VENTILATED AND PROVIDE DETAILS- SECTION 909.21.2 FBC B. | | | 113) M.216 & M.217: SHOW THE LOCATION OF THE ELEVATOR | | | CONTROL ROOM AND SHOW COMPLIANCE WITH SECTION 3005.2 | | | FBC B FOR INDEPENDENT VENTILATION SYSTEMS. | | | | | | RESIDENTIAL TOWER | | | 114) SHEETS M.218, M.219, M.220, & M.221: DUCT SMOKE | | | DETECTORS ARE REQUIRED IN THE SUPPLY SYSTEMS OF THE | | | AHU'S PER SECTION 606.2.1 FBC M. PLEASE PROVIDE DS | | | SYMBOLS ON THE PLANS AND RISER DRAWINGS TO SHOW THE | | | LOCATIONS. | | | 115) M.218, M.219, M.220, & M.221: DUCT SMOKE DETECTORS | | | ARE REQUIRED IN THE SUPPLY SYSTEMS OF THE 100% O/A ERU | | | SYSTEMS, AND AT EACH STORY OF THE RA/EA RISER- SECTION | | | 606.2.3. PLEASE PROVIDE DS SYMBOLS ON THE PLANS AND | | | RISER DRAWINGS TO SHOW THE LOCATIONS. | | | 116) M.218, M.219, M.220, & M.221: INDICATE HOW O/A IS | | | BEING PROVIDED TO THE UNITS AND PROVIDE CALCULATIONS- | | | SECTION 401.2 FBC M. | | | 117) M.218, M.219, M.220, & M.221: SHOW CLEARANCE | | | DISTANCE MEASUREMENTS FOR THE TOILET AND DRYER EXHAUST | | | OUTLETS IN COMPLIANCE WITH SECTIONS 501.3.1 FBC M OR | | | PROVIDE GENERAL KEYNOTES. | | | 118) M.218, M.219, M.220, & M.221: REFER TO SECTION | | | 306.1 AND VERIFY ACCESS IS PROVIDED FOR AC AND FAN | | | UNITS LOCATED ABOVE HARD CEILING. SHOW AN ACCESS PANEL | | | WITH DIMENSIONS ON THE DRAWINGS WHERE REQUIRED- SECTION | | | 306.1 FBC M. | | | 119) M.218, M.219, M.220, & M.221: INDICATE LOCATIONS | | | OF ABOVE CEILING PLENUMS AND AIR HANDLER CLOSETS AND | | | NOTE NO COMBUSTIBLE MATERIALS PERMITTED.120 | | | 120) M.218, M.219, M.220, & M.221: BRANCH DUCT SIZES | | | NOT SHOWN- SECTION 603.1 FBC M. | | | 121) M.218, M.219, M.220, & M.221: AUTOMATICALLY | | | OPERATING SHUTOFF DAMPERS WILL BE REQUIRED FOR O/A | | | DUCTS SERVING THE UNITS- SECTION C403.2.4.3 FBC EC. | | | 122) M.218, M.219, M.220, & M.221: PROVIDE VENTILATION | | | FOR THE CORRIDORS, ELEVATOR AND FIRE LOBBIES- TABLE | | | 403.3.1.1 FBC M. | | | 123) M.220: NO DUCT LAYOUT PLANS PROVIDED- SECTION | | | 107.2.1 FBC M. | | | 124) M.218, M.219, M.220, & M.221: REFER TO SECTION | | | 504.1 AND SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE | | | CLOTHES DRYERS. PROVIDE ON THE PLANS DRYER EXHAUST DUCT | | | DIAGRAMS THAT SHOW THE TOTAL RUN LENGTHS OF THE SYSTEMS | | | CONSISTENT WITH THE MANUFACTURER'S GUIDELINES. | | | 125) M.222: PROVIDE ENLARGED DRAWINGS OF THE MECHANICAL | | | ROOM AND SHOW HOW THE ROOMS IS BEING VENTILATED PER | | | SECTIONS 1105.6 FBC M. A) PROVIDE NORMAL AND EMERGENCY | | | VENTILATION CALCULATIONS AND DETAILS- SECTIONS | | | 1105.6.3.1 & 1105.6.3.2 FBC M. C) SHOW THE LOCATIONS OF | | | REFRIGERANT DETECTORS AND SUBMIT MANUFACTURER'S | | | SPECIFICATIONS. D) SHOW HOW THE CHILLERS ARE BEING | | | ANCHORED TO THE STRUCTURE. E) LABEL ALL EQUIPMENT IN | | | THE ROOM AND PROVIDE AN EQUIPMENT SCHEDULE. E) PROVIDE | | | MANUFACTURER?S SPECIFICATIONS FOR THE BOILERS- SECTION | | | 631.1 FBC FG. PLEASE NOTE THAT OPEN FAME GAS EQUIPMENT | | | SHALL NOT USE COMBUSTION AIR FROM THE MACHINERY ROOM- | | | SECTION 1105.5 FBC FG. | | | 126) M.222: PROVIDE AN ENLARGED DRAWING OF THE COOLING | | | TOWER ROOM AND SHOW HOW THE ROOM IS BEING VENTILATED- | | | NATURALLY OR MECHANICALLY- PROVIDE CALCULATIONS AND | | | DETAILS. A) SHOW VAPOR PLUME DISCHARGE LOCATIONS AND | | | REQUIRED CLEARANCE DISTANCES PER SECTION 908.3 FBC M. | | | B) SHOW HOW THE TOWERS ARE BEING ANCHORED TO THE | | | STRUCTURE- SECTION 908.4 FBC M (ENGINEERING FOR SUPPORT | | | AND PLATFORM STRUCTURES MAY BE DEFERRED). C) PROVIDED | | | WATER PIPING SUPPLY AND RETURN DIAGRAMS. D) SHOW THE | | | WATER FEED LINE PIPE AND BACKFLOW PREVENTER | | | CONNECTIONS- SECTION 908.5 FBC M. | | | 127) M.222: SUBMIT MANUFACTURER'S SPECIFICATIONS FOR | | | THE GENERATOR, FUEL PIPING, ENGINE EXHAUST PIPE, | | | MUFFLER, AND ALL OTHER ASSOCIATED SYSTEM COMPONENTS- | | | SECTION 304.1 FBC M. A) SUBMIT THE UL 2200 CERTIFICATE | | | OF COMPLIANCE FOR THE GENERATOR- SECTION 915.1 FBC M. | | | THE MANUFACTURER'S SPECIFICATIONS AND/OR UL CERTIFICATE | | | SHALL INDICATE THE GENERATOR IS COMPLIANT WITH THE NFPA | | | 37 AND NFPA 110 STANDARDS. B) SUBMIT MANUFACTURER'S | | | SPECIFICATIONS FOR THE FUEL TANK THAT INCLUDES THE | | | TANK'S UL LISTING- UL 142 OR UL 2085- SEE SECTION | | | 21.4.2.1.1 NFPA 30. C) REFER TO 4.1 NFPA 110 AND | | | INDICATE THE CLASSIFICATION AND LEVEL OF THE EPSS | | | SYSTEM. PLEASE INCLUDE THIS INFORMATION IN THE SMOKE | | | CONTROL RATIONAL ANALYSIS. D) SUBMIT THE GENERATOR | | | EXHAUST PIPE SPECIFICATIONS AND PROVIDE AN EXHAUST PIPE | | | DIAGRAM SHOWING THE TOTAL SYSTEM RUN AND LENGTH | | | MEASUREMENT, AND TERMINATION LOCATION PLEASE INCLUDE | | | ALL COMPONENTS OF THE SYSTEM INCLUDING THE SILENCER, | | | AND ANY CONTRACTOR SUPPLIED PIPING- SEE SECTION 8.1. | | | 8.4 NFPA 37, AND SECTION 501.3.1 FBC M. E) PROVIDE | | | DETAILS AND SPECIFICATIONS FOR NORMAL AND EMERGENCY | | | RELIEF VENTING OF THE TANK, INCLUDING VENT PIPING RUNS | | | AND TERMINATION LOCATIONS- SECTION 24.13 NFPA 30. | | | 128) M.222: PROVIDE WIND LOAD ENGINEERING FOR | | | ATTACHMENT OF THE GENERATOR TO THE ROOF STRUCTURE- | | | SECTION 301.15 FBC M. | | | 129) M.223: SHOW THE LOCATIONS OF THE ELEVATOR CONTROL | | | ROOMS AND SHOW COMPLIANCE WITH SECTION 3005.2 FBC B FOR | | | INDEPENDENT VENTILATION SYSTEMS. | | | | | | HOTEL SUITES: | | | 130) M.250- M.253: SHOW HOW O/A IS BEING PROVIDED TO | | | THE SUITES- SECTION 401.2 FBC M, AND HOW IT IS BEING | | | AUTOMATICALLY CONTROLLED- SECTION C403.2.4.3 FBC EC. | | | 131) M.250- M.253: REFER TO SECTION 306.1 AND VERIFY | | | ACCESS IS PROVIDED FOR THE FCU'S LOCATED ABOVE HARD | | | CEILINGS OR IN CLOSETS. SHOW AN ACCESS PANEL WITH | | | DIMENSIONS ON THE DRAWINGS WHERE REQUIRED- SECTION | | | 306.1 FBC M. | | | 132) M.250- M.253: INDICATE LOCATIONS OF ABOVE CEILING | | | PLENUMS AND AIR HANDLER PLENUM CLOSETS AND NOTE NO | | | COMBUSTIBLE MATERIALS PERMITTED. | | | | | | RESIDENTIAL UNITS | | | 133) M.254- M.258: LABEL ALL ROOMS AND SPACES ON THE | | | PLANS- SECTION 107.2.1 WPB. | | | 134) M.254- M.258: SHOW HOW O/A IS BEING PROVIDED TO | | | THE UNITS- SECTION 401.2 FBC M, AND HOW IT IS BEING | | | AUTOMATICALLY CONTROLLED- SECTION C403.2.4.3 FBC EC. | | | 135) M.254- M.258: PLACE NOTES TO INDICATE NO | | | COMBUSTIBLE MATERIALS PERMITTED IN THE VHP CLOSETS | | | INCLUDING THE DOORS- SECTION 602.2.1 FBC M. IT APPEARS | | | THE DOORS WILL BE LOUVERED TO ALLOW RETURN AIR TO THE | | | HEAT PUMPS, OTHERWISE INDICATE MEANS OF RETURN AIR- | | | SECTION 601.6 FBC M. | | | 136) M.254- M.258: INDICATE HOW AIR IS BEING RETURNED | | | FROM THE BEDROOMS- SECTION 601.6. | | | 137) M.254- M.258: REFER TO SECTION 504.1 AND SUBMIT | | | MANUFACTURER'S SPECIFICATIONS FOR THE CLOTHES DRYERS. | | | PROVIDE ON THE PLANS DRYER EXHAUST DUCT DIAGRAMS THAT | | | SHOW THE TOTAL RUN LENGTHS OF THE SYSTEMS CONSISTENT | | | WITH THE MANUFACTURER'S GUIDELINES. | | | 138) M.254- M.258: PROVIDE AN ENLARGED DRAWING OF THE | | | VHP CLOSETS SHOWING REQUIRED CLEARANCES- SECTION | | | C403.2.9.3.3 FBC EC, AND PRIMARY AND SECONDARY MEANS OF | | | CONDENSATE DISPOSAL- SECTION 307.2.1, 307.2.2, & | | | 307.2.3 FBC M. | | | 139) PROVIDE A CONDENSATE DISPOSAL RISER DRAWING- TABLE | | | 307.2.2 FBC M. | | | 140) PROVIDE FIRESTOPPING DETAILS FOR CHILLED AND HOT | | | WATER PIPES, AND DUCTWORK. | | | | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT | | | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE | | | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND | | | KEEP THEM WITH THE SUBMITTALS | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
5 |
Status |
P |
Date |
2021-08-23 |
|
|
Cont ID |
|
| Sent By |
lcrespo |
Date |
2021-08-23 |
Time |
18:03 |
Rev Time |
0.00 |
| Received By |
lcrespo |
Date |
2021-08-23 |
Time |
11:44 |
Sent To |
|
|
| Notes |
| 2021-08-23 14:52:18 | 08/23/21 REVIEWED FOR CODE COMPLIANCE (PLUMBING) | | | | | | BY REVIEWING THE PLANS / SPECIFICATIONS FOR CODE | | | COMPLIANCE DOES NOT RELIEVE THE OWNER, DESIGN | | | PROFESSIONAL, CONTRACTORS, OR THEIR REPRESENTATIVES | | | FROM THE RESPONSIBILITY TO COMPLY WITH ALL LOCAL, | | | STATE, AND NATIONAL CODES AND STANDARDS IN EFFECT AT | | | THE TIME OF PERMIT ISSUANCE. OUR REVIEW IS NOT A CHECK | | | OF EVERY ITEM AND DOES NOT PREVENT THIS DEPARTMENT FROM | | | REQUIRING CORRECTIONS DURING CONSTRUCTION. ANY CHANGES | | | / ALTERATIONS TO APPROVED PLANS SHALL BE APPROVED TO | | | AVOID VOIDING OF THE PERMIT. | | | | | | LUIS A. CRESPO | | | PLUMBING PLAN EXAMINER / INSPECTOR | | | EMAIL: [email protected] OFFICE: 561 805-6720 | | | |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
4 |
Status |
F |
Date |
2021-06-21 |
|
|
Cont ID |
|
| Sent By |
lcrespo |
Date |
2021-06-21 |
Time |
15:48 |
Rev Time |
0.00 |
| Received By |
lcrespo |
Date |
2021-06-14 |
Time |
14:32 |
Sent To |
|
|
| Notes |
| 2021-06-21 15:54:24 | 06/21/21 1ST PLUMBING REVIEW**DENIED** WITH COMMENTS | | | | | | NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS | | | TIME, AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE | | | GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS. | | | | | | 1. NO RESPONSE TO THIS?SHEET C.03 SHOWS A 15-INCH PVC | | | RWL NEAR THE PROPERTY'S SOUTHWEST CORNER NEAR THE BUS | | | STOP. THE LINE IS NOT SHOWN ON SHT. P100 (NEAR COLUMN | | | LINE #1). CLARIFY. | | | | | | 2. DONE. | | | | | | 3. DONE. | | | | | | 4. DONE. | | | | | | 5. DONE. | | | | | | 6. SHEET A1.502A - DETAIL #2 DOES NOT SHOW A SEAT IN | | | THE SHOWER, AND DETAIL #3 SHOWS A SEAT. CLARIFY. | | | | | | THE SEAT DRAWN IN IS A SIDE SEAT, AND THE ONE ON THE | | | ADA FUTURE IS THE BACK SEAT. PLEASE CORRECT AS BACKING | | | DETAIL IS REQUIRED AND PROVIDED PER THE WPB AMENDMENTS | | | TO THE FBC SEC. 107.2.1 INFORMATION ON CONSTRUCTION | | | DOCUMENTS. | | | | | | 7. DONE. | | | | | | 8. DONE. | | | | | | 9. DONE. | | | | | | 10. THIS ITEM HAS NOT BEEN ADDRESSED, SHEET A1.600 - | | | DETAIL #1 - WOMEN'S RESTROOM - THE PLAN STATES A CLEAR | | | FLOOR SPACE OF 60 INCHES WIDE FOR THE ACCESSIBLE STALL, | | | BUT THE PLAN ALSO SHOWS THE CLEAR INSIDE WIDTH 4 FEET | | | 11 1/2 INCHES. IF THIS IS A ROUGH DIMENSION, THEN THIS | | | STALL WILL NOT BE WIDE ENOUGH AFTER THE FINISH. COMPLY | | | WITH FBC-ACCESS. SEC.604.3.1.2ND REQUEST. CLARIFY. | | | | | | 11. THIS ITEM HAS NOT BEEN ADDRESSED, SHEET A1.600 | | | DETAIL #1 - MEN'S RESTROOM - ONE OF THE URINALS IS | | | SHOWN AS 1 FOOT 2 INCHES FROM A WALL TO THE CENTERLINE | | | OF THE URINAL. A MINIMUM OF 15 INCHES FROM A WALL TO | | | THE CENTER OF THE URINAL IS REQUIRED. FBC-PLUMBING | | | SEC.405.3.1. 2ND REQUEST. | | | | | | 12. THIS ITEM HAS NOT BEEN ADDRESSED, SHEET A1.600 - | | | GROUND LEVEL BATHROOM #0132- IS THIS A UNISEX TOILET | | | ROOM OR GENDER-SPECIFIC? CLARIFY. 2ND REQUEST, IT SEEMS | | | AS THERE SHOULD BE A V3 SHEET. | | | | | | 13. DONE. | | | | | | 14. DONE. | | | | | | 15. DONE. | | | | | | 16. DONE. | | | | | | 17. DONE BUT NEW COMMENT; | | | | | | ON SHEET 606 FHA; | | | | | | A. DETAIL #3, DOOR IS SWINGING INTO THE CLEAR FLOOR | | | SPACE OF THE LAVE, AND THE CLEAR FLOOR SPACE IS NOT | | | SHOWN FOR THE TUB. PLEASE NOTE THAT THE DISTANCE FROM | | | THE DOOR OPENING TO THE TUB MAY BE ENCROACHING IN THE | | | FLOOR SPACE. | | | | | | B. DETAIL #9 UNIT D1 SHOWS CLEAR FLOOR SPACE BUT NOT AN | | | FHA UNIT; PLEASE REMOVE OR CLARIFY STATUS. | | | | | | ON SHEET 607 FHA; | | | A. DETAIL #2, THE CLEAR FLOOR SPACE FOR TUB AND LAV NOT | | | SHOWN. | | | | | | B. DETAIL # 3 AND #6, MASTER TUB CLEAR FLOOR SPACE NOT | | | SHOWN. | | | | | | C. DETAIL # 7, LAV AND SHOW CLEAR FLOOR SPACE NOT | | | SHOWN. | | | | | | ON SHEET 608 FHA; | | | | | | A. DETAIL #1, #4, AND 6, THE CLEAR FLOOR SPACE FOR TUB | | | NOT SHOWN. | | | | | | B. DETAIL #3 UNIT B4 SHOWS CLEAR FLOOR SPACE BUT NOT AN | | | FHA UNIT; PLEASE REMOVE OR CLARIFY STATUS. | | | | | | C. DETAIL #10 UNIT C1 SHOWS BACKING ON TUB AND TOILET. | | | IS THIS AN FHA UNIT; PLEASE CLARIFY? | | | | | | ON SHEET 609 FHA; | | | | | | A. DETAIL #1, #3, AND #8, MASTER TUB CLEAR FLOOR SPACE | | | NOT SHOWN. | | | | | | B. DETAIL #5 UNIT D1 SHOWS BACKING. IS THIS AN FHA | | | UNIT; PLEASE CLARIFY? | | | | | | C. DETAIL #6 UNIT D3, LAV, AND TUB CLEAR FLOOR SPACE | | | NOT SHOWN. | | | | | | D. DETAIL #7 UNIT D3 BATHROOM 2 & 3 SHOWS BACKING AND | | | TOILET CLEAR FLOOR SPACE; IS THIS AN FHA? PLEASE | | | CLARIFY. | | | | | | E. DETAIL 9 UNIT D4 SHOWS BACKING. IS THIS AN FHA UNIT; | | | PLEASE CLARIFY? | | | | | | 18. DONE. | | | | | | 19. DONE. | | | | | | 20. DONE. | | | | | | 21. DONE. | | | | | | 22. DONE. | | | | | | 23. DONE. | | | | | | 24. DONE. | | | | | | 25. DONE. | | | | | | 26. DONE. | | | | | | 27. DONE. | | | | | | 28. THE PAGE FOR V5 DOES NOT COINCIDE WITH THE PRIOR | | | VERSION, SHEET A1.610 - DETAIL # 2 - CLEAN UP THIS | | | PLAN. THE LAVATORY IS SHOWN LOCATED PARTIALLY IN THE | | | WALL. | | | | | | 29. THE PAGE FOR V5 DOES NOT COINCIDE WITH THE PRIOR | | | VERSION, SHEET A1.610 - DETAIL #1 - THE FLOOR PLAN | | | SHOWS THE DOOR SWINGING INTO THE SHOWER AND THE TOILET | | | COMPARTMENT. THE INSWING DOOR IMPEDES ACCESS TO THE | | | SHOWER CONTROLS AND THE TOILET AND DOES NOT COMPLY WITH | | | FAIR HOUSING. REVERSE THE SWING OF THE DOOR. | | | | | | 30. THE PAGE FOR V5 DOES NOT COINCIDE WITH THE PRIOR | | | VERSION, SHEET A1.610 - DETAIL #3 - THE NOTES AND | | | DETAILS FOR THE GRAB BAR REINFORCEMENT DON'T MAKE | | | SENSE. CORRECT THE DEFICIENCIES. IF THIS IS SUPPOSED TO | | | BE AN FHA-COMPLIANT BATHROOM, SHOW ALL CLEAR FLOOR | | | SPACES AND THE FHA BATHROOM TYPE ON THE PLAN. THE | | | LAVATORY APPEARS TO ENCROACH INTO THE REQUIRED CLEAR | | | FLOOR SPACE FOR THE SHOWER. PLEASE CLARIFY. | | | | | | 31. THE PAGE FOR V5 DOES NOT COINCIDE WITH THE PRIOR | | | VERSION, SHEET A1.610 - DETAIL # 6 - IF THIS IS THE | | | FHA-COMPLIANT BATHROOM, PLACE THE TYPE OF FHA BATHROOM | | | ON THE PLAN AND CORRECT THE OVERLAY OF THE UNIT NUMBER | | | ON THE FLOOR PLAN. PLEASE CORRECT THE OVERLAY ON DETAIL | | | #5 ALSO. | | | | | | 32. THE PAGE FOR V5 DOES NOT COINCIDE WITH THE PRIOR | | | VERSION, SHEET A1.610 - DETAIL #7 - CORRECT THIS | | | DETAIL. THE LOCATION OF REINFORCEMENT AND CLEAR FLOOR | | | SPACES ARE OUT OF WHACK. CONTROLS ARE CALLED OUT ON THE | | | LAVATORY. THE BATHROOM FLOOR PLAN IS CUT OFF AND | | | INCOMPLETE. PLEASE CLARIFY. | | | | | | 33. DONE. | | | | | | 34. THIS ITEM SEEMS TO HAVE A PIPE THAT IS NOT CLEAR TO | | | WHERE THEY GO OR ARE ON SHEET P100. IF POSSIBLE, EXPAND | | | THE PIPING LAYOUT FOR THE SANITARY AND VENT LINES AND | | | TAG THE RISERS AT THE TOILET ROOMS BY ELEVATORS P03, | | | P04, & P05 ON COLUMN LINE H. | | | | | | 35. DONE. | | | | | | 36. DONE. | | | | | | 38. THIS IS NOT CORRECTED; SHEET P.101B SHOWS AN 8-INCH | | | SANITARY LINE WITHIN STAIRWAY # 4 AND A 4 INCH GW LINE | | | IN STAIRWAY #10. THE LINE IS NOT PERMITTED WITHIN THE | | | STAIRWAY PER FBC-BUILDING SEC.1023.5. THERE IS A CIRCLE | | | WITH A LINE IN THIS AND ANOTHER ELEVATOR THAT WILL NEED | | | TO BE REMOVED OR RELATED OUT OF THE STAIRWAY TO MOVE | | | FORWARD TO A FINAL REVIEW, SO PLEASE DO YOUR BEST TO | | | CORRECT THESE ITEMS. | | | | | | 39. DONE. | | | | | | 40. DONE. | | | | | | 41. THE RISER TAGS FOR THE LW R2 P 7XX RISERS ARE | | | MISSING THE DRAWING LOCATIONS ON THE RISER TAGS. PLEASE | | | CLARIFY PER THE WPB AMENDMENTS TO FBC SEC. 107.2.1. | | | PLEASE ALSO CLARIFY ANY ABOVE FLOORS IN POD C AND ANY | | | OTHERS ON THIS PLAN TO PREVENT A DELAY IN YOUR REVIEW. | | | | | | 42. NEW COMMENT; ON SHEET 103C UNIT IN GRID J/12, THE | | | PIPES FOR SANITARY P702 AND P 7XX ARE IN THE WRONG | | | LOCATION, AND THE ARROW IS NOT POINTED TO THEM AND | | | PLEASE CORRECT OTHER UNITS BESIDE P709 AND P702A PER | | | THE WPB AMEND. TO FBC SEC. 107.2.1, 107.3.5.1.3. | | | | | | 43. NEW COMMENT; ON SHEET 104C UNIT IN GRID J/12, THE | | | PIPES FOR SANITARY P702 AND P 7XX ARE IN THE WRONG | | | LOCATION, AND THE ARROW IS NOT POINTED TO THEM AND | | | PLEASE CORRECT OTHER UNITS BESIDE P709 AND P702A PER | | | THE WPB AMEND. TO FBC SEC. 107.2.1, 107.3.5.1.3. | | | | | | 44. NEW COMMENT; ON SHEET 105C UNIT IN GRID J/12, THE | | | PIPES FOR SANITARY P702 AND P 7XX ARE IN THE WRONG | | | LOCATION, AND THE ARROW IS NOT POINTED TO THEM AND | | | PLEASE CORRECT OTHER UNITS BESIDE P709 AND P702A PER | | | THE WPB AMEND. TO FBC SEC. 107.2.1, 107.3.5.1.3. | | | | | | 45. NEW COMMENT; ON SHEET 106C UNIT IN GRID J/12, THE | | | PIPES FOR SANITARY BELOW TO THE LABELS BELOW ARE NOT | | | CLEAR OR ARE MISSED LABELED; PLEASE TRY TO CLARIFY AND | | | CORRECT AS THEY ARE TOO MANY TO MENTION PER THE WPB | | | AMEND. TO FBC SEC. 107.2.1, 107.3.5.1.3. | | | | | | 46. DONE. | | | | | | 47. DONE. | | | | | | 48. DONE. | | | | | | 49. DONE. | | | | | | 50. DONE. | | | | | | 51. DONE. | | | | | | 52. DONE. | | | | | | 53. DONE. | | | | | | 54. DONE. | | | | | | 55. DONE. | | | | | | 56. DONE. | | | | | | 57. DONE. | | | | | | 58. DONE. | | | | | | 59. DONE. | | | | | | 60. DONE. | | | | | | 61. DONE. | | | | | | 62. DONE. | | | | | | 63. DONE. | | | | | | 64. DONE. | | | | | | 65. DONE. | | | | | | 66. DONE. | | | | | | 67. DONE. | | | | | | 68. DONE. | | | | | | 68 A. NEW COMMENT, ON SHEET 702A AND 702 B, FROM WATER | | | SERVICE TO PUMPS, THE CW HAS TOO LIGHT LABELS; PLEASE | | | CORRECT BY DARKENING THEM PER THE WPB AMENDMENTS TO THE | | | FBC SEC. 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. | | | | | | 69. DONE. | | | | | | 70. DONE. | | | | | | 71. DONE. | | | | | | 72. DONE. | | | | | | 73. PARTLY DONE, BUT ON SHEET 704, TAG SS/R8 AND SS/R9 | | | ARE MISSING PXXX DESTINATION. PLEASE CORRECT PER THE | | | WPB AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON | | | CONSTRUCTION DOCUMENTS. PLEASE NOTE THE SHEET 704 AND | | | CONTINUING PAGES HAVE A TABLE THAT REFERS TO THE 2014 | | | CODE FOR TABLE 710.1(2), AND IT SHOULD BE THE 2017 FBC | | | P TABLE 710.2 CODE, SO PLEASE CORRECT ALL PAGES TO | | | PREVENT FURTHER DELAYS PER THE WPB AMENDMENTS TO THE | | | FBC SEC. 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. | | | | | | 74. DONE. | | | | | | 75. THERE ARE TAGS ON LEVELS EIGHT AND ELEVEN THAT ARE | | | NOT LABELED ON SHEET. P.704B - RISER TAGS ARE MISSING | | | THE DRAWING LOCATION NUMBERS ON THE RISER TAGS. ENSURE | | | ALL RISER TAGS ARE COMPLETE. | | | | | | 76. DONE. | | | | | | 76. A. PLEASE NOTE THE SHEET 705, 705 A, 706, AND | | | CONTINUING PAGES HAVE A TABLE THAT REFERS TO THE 2014 | | | CODE FOR TABLE 709.1. IT SHOULD BE THE 2017 FBC P TABLE | | | 709.1 CODE, SO PLEASE CORRECT ALL PAGES TO PREVENT | | | FURTHER DELAYS PER THE WPB AMENDMENTS TO THE FBC SEC. | | | 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. | | | | | | 77. DONE. | | | | | | 78. DONE. | | | | | | 79. DONE. | | | | | | 80. DONE. | | | | | | 81. DONE. | | | | | | 82. DONE. | | | | | | 83. DONE. | | | | | | 84. DONE. | | | | | | 85. DONE. | | | | | | 86. DONE. | | | | | | 87. DONE. | | | | | | 88. DONE. | | | | | | 89. ON SHEET P.711, DETAIL #6, THE RISER TAG | | | INFORMATION FOR DOMESTIC WATER RISER IS SO LIGHT IT IS | | | ILLEGIBLE. PLEASE CORRECT. | | | | | | 90. DONE. | | | | | | 91. ON SHEET P.712 DETAIL #6 ? | | | | | | A. THE MEN'S AND WOMEN'S ROOMS REQUIRE SHUT-OFF VALVES | | | AT HOSE BIBBS PER THE FBC-PLUMBING SEC. 606.2. | | | | | | B. THE WATER COOLER REQUIRES A HAMMER ARRESTOR PER THE | | | 2017 FBC P 604.9 WATER HAMMER. | | | | | | 92. ON SHEET P.712, DETAILS #3, #4 (SS/0#), - THE RISER | | | TAGS MISS THE RISER INFORMATION. ENSURE ALL RISER TAGS | | | ARE COMPLETE. | | | | | | 93. ON SHEET P.712, THE WATER RISER FOR THE OFFICE | | | TOWER-MEN?S OFFICE TOWER MEN?S TOILET ROOM LEVEL 17 IS | | | MISSING AIR ARRESTORS AND SHUT-OFF VALES PER THE 2017 | | | FBC P 604.9 AND 606.1. OFFICE TOWER-MEN?S TOILET IS | | | ONLY MISSING AIR ARRESTORS. | | | | | | 94. INCOMPLETE, ON SHEET P.720 ? THE IDENTIFIED RISER | | | TAGS INFO FIXTURE UNIT LOADS FOR SS/P60 HAS P7XX; | | | PLEASE ADD CORRESPONDING NUMBERS. AND SS/P1 DOES NOT | | | HAVE A STACK NUMBER. PLEASE CORRECT PER THE WPB | | | AMENDMENTS TO FBC SEC. 107.2.1, 107.3.5.1.3. | | | | | | 95. DONE BUT OVERLAPPING; PLEASE CORRECT. ON SHEET | | | P.730 - IDENTIFY ALL RISERS WITH RISER TAGS COMPLETE | | | WITH ALL RISER TAG INFO AND THE GPM'S DRAINING INTO | | | EACH RISER. WPB AMEND. TO FBC SEC. 107.2.1, | | | 107.3.5.1.3. | | | | | | 96. ON SHEET P.731 - THE DRAWING HAS A FLOATING FITTING | | | AND DRAINS WITH SECTIONS OF PIPE ARE MISSING, PIPE | | | SIZES ARE NOT CONNECTED, RISER TAGS ALL OVER THE PLACE | | | AND NOT DIRECTED OR POINTED TO A REFERENCE POINT, | | | SECTIONS OF THE PIPING SYSTEM ARE CONGESTED AND | | | DIFFICULT TO REVIEW ON THE TOP PART. PLEASE CORRECT PER | | | THE WPB AMENDMENTS TO FBC SEC. 107.2.1, 107.3.5.1.3. | | | | | | 97. ON SHEET P.732 - THE RISER SHOWS THE SQUARE FOOTAGE | | | AREA BEING DRAINED BUT NO GPM'S WITH 2014 FBC-PLUMBING | | | SEC. TABLE 1106.3, AND THE CODE THAT SHOULD BE USED AND | | | REFERENCED IS 2017 FBC SEC. TABLE 1106.2, SO PLEASE | | | CLARIFY AND OR RECALCULATE. THIS IN ALL OTHER SECTION | | | OF THIS PLUMBING FOR SANITARY HAS 2014, PLEASE CORRECT | | | AND CLARIFY IF NEED BE, | | | | | | 98. ON SHEET. P.733, SECOND REQUEST, SEVERAL RISER TAGS | | | ARE MISSING THE DRAWING LOCATION INFORMATION. PLEASE | | | ENSURE ALL RISER TAGS ARE COMPLETE. | | | | | | 99. ON SHEET. P.734, SECOND REQUEST, SEVERAL RISER TAGS | | | ARE MISSING THE DRAWING LOCATION INFORMATION. PLEASE | | | ENSURE ALL RISER TAGS ARE COMPLETE. | | | | | | 100. DONE. | | | | | | 101. ON THE SHEET, P.803 - DETAIL #3 SHOWS JOINTS UNDER | | | THE SLAB - PLUMBING SPECIFICATIONS SEC. 22 1110 - PART | | | 2 - 2.02 STATES THAT "ENTRANCE PIPING TO THE BUILDING | | | TO TERMINATE ABOVE GRADE." THE DETAIL ON P.803 SHOWS | | | FLANGED FITTINGS UNDER THE SLAB. CLARIFY. IF THIS | | | PIPING ARRANGEMENT IS TO REMAIN, SUBMIT DETAILS ON | | | FITTING RESTRAINTS AND THRUST BLOCK INFORMATION. WPB | | | AMEND. TO FBC SEC. 107.2.1, 107.3.5.1.3. 2ND REQUEST | | | AND THE THERE IS NO NEW DRAWING, AND THE RESPONSE SAYS | | | DETAIL HAS BEEN UPDATED PLEASE CLARIFY PER THE WPB | | | AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON | | | CONSTRUCTION DOCUMENTS. | | | | | | 102. RIGID SUPPORT SWAY BRACING SHALL BE PROVIDED AT | | | CHANGES IN A DIRECTION MORE SIGNIFICANT THAN 45 DEGREES | | | FOR PIPE SIZES 4 INCHES AND LARGER PER FBC-PLUMBING | | | SEC. 308.6. SUBMIT DETAILS FOR THE BRACING. 2ND | | | REQUEST, NO DETAIL FOUND PER RESPOND ?#3 HAS BEEN | | | UPDATED. REFER TO REVISED SHEET P803?. | | | | | | 103. DONE. | | | | | | 104. DONE. | | | | | | | | | WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION & | | | REMOVE ANY VOIDED SHEETS & REPLACE ANY NECESSARY PAGES. | | | A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW | | | COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION | | | MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE | | | THE CHANGES CAN BE FOUND, WILL HELP EXPEDITE YOUR | | | PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. | | | | | | HTTPS://CODES.ICCSAFE.ORG/CODES/FLORIDA | | | | | | LUIS A. CRESPO | | | PLUMBING PLAN EXAMINER / INSPECTOR | | | EMAIL: [email protected] OFFICE: 561 805-6720 | | | |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
3 |
Status |
F |
Date |
2021-02-21 |
|
|
Cont ID |
|
| Sent By |
tklarge |
Date |
2021-02-21 |
Time |
09:15 |
Rev Time |
0.00 |
| Received By |
tklarge |
Date |
2021-01-24 |
Time |
03:14 |
Sent To |
|
|
| Notes |
| 2021-02-19 11:02:15 | 1) SHT. C.03 SHOWS A 15 INCH PVC RWL NEAR THE SOUTHWEST | | | CORNER OF THE PROPERTY NEAR THE BUS STOP. THE LINE IS | | | NOT SHOWN ON SHT. P100 ( NEAR COLUMN LINE #1). CLARIFY. | | | 2) SHT.L5-711 - THE POOL DECK SHOWER DOES NOT APPEAR TO | | | BE COMPLIANT WITH ANSI A117.1-1986 SEC.4.25.4.FOR FAIR | | | HOUSING ACT COMPLIANCE. THE CONTROL RING APPEARS LIKE | | | IT MAY REQUIRE GRASPING OR TWISTING OF THE WRIST TO | | | OPERATE WHICH WILL VIOLATE THIS SECTION. THE SUBMITTED | | | SPECIFICATION SHEET DOES NOT SHOW THAT THIS A HANDICAP | | | ACCESSIBLE COMPLIANT UNIT. PROVIDE DOCUMENTATION TO | | | SHOW COMPLIANCE.THE RESPONSE NARRATIVE REFERS TO DETAIL | | | #8 ON THIS SHEET BUT THE DETAIL SHOWS A PLAN VIEW OF | | | THE SHOWER WHICH DOES NOT ADDRESS THIS COMMENT. 2ND | | | REQUEST. | | | 3) SHT. L5-711 - SHOW THE HEIGHT OF THE SHOWER CONTROL | | | RING FROM FINISH GRADE TO THE CENTER OF THE CONTROL | | | RING IN US CUSTOMARY UNITS.THE SPECIFICATION CURRENTLY | | | SHOWS THE MEASUREMENT IN WHAT APPEARS TO BE | | | MILLIMETERS. THE HEIGHT OF THE CONTROL RING SHALL | | | COMPLY WITH ANSI A117.1-1986 SECS.4.2.5 & 4.2.6. | | | 4) SHT.A0.203 - ALTERNATIVE ROLL-IN SHOWER W/SEAT - THE | | | CONTROLS SHALL BE LOCATED A MAXIMUM OF 15 INCHES FROM | | | THE CENTERLIINE OF THE SEAT TO THE CENTERLINE OF THE | | | CCONTROLS PER FBC-ACCESS. SEC.608.5.3 AND FIGURE | | | 608.5.3. THE DRAWING SHOWS THE 15 INCHES TO THE EDGE OF | | | THE CONTROL AREA, NOT TO THE CENTER. | | | 5) SHT. A1.256 - SHT. A1.256 - OFFICE TOWER FLOOR PLAN | | | - ROOF LEVEL - SUBMIT INFORMATION FOR THE CHEMICAL | | | TREATMENT SYSTEM. SUBMIT MSDS SHEETS FOR THE CHEMICALS | | | BEING USED. SUBMIT INFORMATION ON THE AMOUNTS OF EACH | | | CHEMICAL BEING USED, WHERE THEY ARE BEING STORED, THE | | | TYPES OF CONTAINERS THE CHEMICALS ARE STORED IN, ETC. | | | COMPLIANCE WITH SEC. 414 & 415 OF THE 2014 FBC MAY BE | | | REQUIRED. THE SUBMITTED RESPONSE NARRATIVE STATES THIS | | | SYSTEM IS LIISTED UNDER THE DEFERRED SUBMITTALS ON SHT. | | | M.002 BUT IT IS NOT. | | | 6) SHT.A1.502A - DETAIL #2 DOES NOT SHOW A SEAT IN THE | | | SHOWER AND DETAIL #3 SHOWS A SEAT. CLARIFY. | | | 7) SHT. A1.503 - DETAIL #2 - SHOW THE LOCATION OF THE | | | SHOWER CONTROLS. THE LOCATION OF THE CONTROLS SHALL | | | COMPLY WITH FBC-ACCESS. SEC.608.5.2. | | | 8) SHT. A1.532 - MASTER BATH - THE FLOOR PLAN SHOWS THE | | | DOOR SWINGING INTO THE SHOWER AND THE TOILET | | | COMPARTMENT. THE INSWING DOOR IS IMPEDING ACCESS TO THE | | | SHOWER CONTROLS AND THE USE OF THE TOILET AND DOES NOT | | | COMPLY WITH FAIR HOUSING. REVERSE THE SWING OF THE | | | DOOR. | | | 9) SHT. A1.532 - SHOW THE REQUIRED CLEAR FLOOR SPACE AT | | | ALL THE FIXTURES IN THE FHA ADAPTABLE BATHROOM. WPB | | | AMEND. TO FBC SEC. 107.2.1. | | | 10) SHT.A1.600 - DETAIL #1 - WOMEN'S RESTROOM - THE | | | PLAN STATES A CLEAR FLOOR SPACE OF 60 INCHES WIDE FOR | | | THE ACCESSIBLE STALL BUT THE PLAN ALSO SHOWS THE INSIDE | | | CLEAR WIDTH AS 4 FEET 11 1/2 INCHES. IF THIS IS A ROUGH | | | DIMENSION THEN THIS STALL WILL NOT BE WIDE ENOUGH AFTER | | | FINISH. COMPLY WITH FBC-ACCESS. SEC.604.3.1.2ND | | | REQUEST. CLARIFY. | | | 11) SHT. A1.600 - SHT.A1.600 - DETAIL #1 - MEN'S | | | RESTROOM - ONE OF THE URINALS IS SHOWN AS 1 FOOT 2 | | | INCHES FROM A WALL TO THE CENTERLINE OF THE URINAL. A | | | MINIMUM OF 15 INCHES FROM A WALL TO THE CENTER OF THE | | | URINAL IS REQUIRED. FBC-PLUMBING SEC.405.3.1. 2ND | | | REQUEST. | | | 12) SHT. A1.600 - GROUND LEVEL BATHROOM #0132- IS THIS | | | A UNISEX TOILET ROOM OR GENDER SPECIFIC? CLARIFY.2ND | | | REQUEST. | | | 13) SHT.A1.601 - DETAIL # 1 - GROUND LEVEL BATHROOM | | | #0121 - THE DOOR TO ONE OF THE TOILET ROOMS IS SWINGING | | | INTO THE CLEAR FLOOR SPACE FOR THE LAVATORY. | | | FBC-ACCESS. SEC. 603.2.3. SEE EXCEPTIONS. SHOW THE | | | REQUIRED 30 INCH MINIMUM BY 48 INCH MINIMUM CLEAR FLOOR | | | SPACE BEYOND THE ARC OF THE DOOR SWING ON THE PLANS. IT | | | IS NOT SHOWN. 2ND REQUEST. | | | 14) SHT. A1.601 - DETAIL #1 - TOILET ROOM #0121 - THE | | | DOOR IS IN FRONT OF THE WATER CLOSET. THE WATER CLOSET | | | CANNOT OVERLAP THE REQUIRED MANEUVERING CLEARANCE FOR | | | THE DOOR INSIDE THE ROOM. SHOW THE REQUIRED MANEUVERING | | | CLEARANCE FOR THE DOOR IN ACCORDANCE WITH FBC-ACCESS. | | | 404.2.4. | | | 15) SHT. A1..602 - DETAIL #1 - WOMEN'S RESTROOM #0731- | | | SHOW THE INSIDE CLEAR LENGTH OF THE AMBULATORY | | | ACCESSIBLE TOILET STALL AND THE STANDARD TOILET STALLS. | | | THE DIMENSIONS SHOWN ON THE PLAN ARE NOT CLEAR INSIDE | | | DIMENSIONS. FBC-ACCESS. SEC.604.8.2.1, | | | 604.8.2FBC-PLUMBING SEC.405.3.1.2ND REQUEST. | | | 16) SHT. A1.603 - DETAILS #1 & #5 - IDENTIFY ON THE | | | PLANS THAT THESE BATHROOMS ARE LOCATED IN THE HOTEL. | | | 2ND REQUEST. | | | 17) SHT. A1.607 - DETAIL #8 - THERE ARE NOTES ON THE | | | PLAN POINTING TO NOTHING AND TO WRONG ITEMS, LOCATION | | | OF GRAB BAR REINFORCEMENT IS WRONG,AND THE DOOR SWINGS | | | INTO THE SHOWER. A PERSON IN A WHEELCHAIR WOULD NOT BE | | | ABLE TO ACCESS THE CONTROLS. REVERSE THE DOOR SWING ON | | | THE SHOWER. | | | 18) SHT. A1.607 - DETAIL #6 - IDENTIFY THE FHA BATHROOM | | | TYPE ON THE PLANS. | | | 19) SHT. A1.608 - DETAIL #5 CALLS OUT A MASTER BATH BUT | | | THE FLOOR PLAN SHOWS A KITCHEN. CLARIFY. | | | 20) SHT. A1.608 - DETAIL #4 - IDENTIFY THE FHA BATHROOM | | | TYPE ON THE DETAIL AND PLEASE FIX THE OVERLAY OF THE | | | UNIT NUMBER OVER THE COLUMN NUMBER. | | | 21) SHT. A1.608 - DETAIL #10 - THE LOCATION OF THE GRAB | | | BAR REINFORCEMENTS ARE SHOWN IN THE MIDDLE OF THE | | | FLOOR. CLARIFY. | | | 22) SHT. A1.609 - DETAIL #5 - THERE IS AN OVERLAY ON | | | THIS DETAIL THAT NEEDS TO BE REMOVED AND ALSO FLOATING | | | NOTES. CLEAN UP THIS DETAIL. WPB AMEND. TO FBC SEC. | | | 107.2.1. | | | 23) SHT.A1.609 - DETAIL #2 - CLEAN UP THIS DETAIL. | | | CLEAR FLOOR SPACE IS SHOWN IN THE CLOSET. IF THIS IS | | | SUPPOSED TO BE AN FHA COMPLIANT BATHROOM IT IS NOT. A | | | WATER CLOSET CANNOT BE LOCATED NEXT TO THE SHOWER | | | BECAUSE THE REQUIRED FLOOOR SPACE FOR THE SHOWER CANNOT | | | BE PROVIDED. A NOTE ON THIS DETAIL STATES "BATHROOM 1 | | | FHA TYPE B." CLARIFY. | | | 24) SHT. A1.609 - DETAILL # 3 - INDICATE ON THE DETAIL | | | IF THIS IS THE FHA COMPLIANT BATHROOM. IF SO, SHOW ALL | | | THE REQUUIRED CLEAR FLOOR SPACES, LOCATION OF GRAB BAR | | | REINFORCEMENT, AND THE DOORS ON THE SHOWER AND THE | | | TOILET CCOMPARTMENT CANNOT SWING IN PER FHA DESIGN | | | MANUAL/GUIDELINES. | | | 25) SHT. A1.609 - DETAIL #4 CALLS OUT BATHROOM 3 BUT | | | THERE IS NO BATHROOM PLAN SHOWN. CLARIFY. | | | 26) SHT. A1.609 - DETAIL #8 - CORRECT THE LOCATION OF | | | THE GRAB BAR REINFORCEMENT FOR THE TOILET ON THE PLAN. | | | 27) SHT. A1.609 - DETAIIL #9 - IF THIS IS SUPPOSED TO | | | BE AN FHA COMPLIANT BATHROOM IT IS NOT. A WATER CLOSET | | | CANNOT BE LOCATED NEXT TO THE SHOWER BECAUSE THE | | | REQUIRED FLOOOR SPACE FOR THE SHOWER CANNOT BE | | | PROVIDED. CLARIFY. | | | 28) SHT. A1.610 - DETAIL # 2 - CLEAN UP THIS PLAN. THE | | | LAVATORY IS SHOWN LOCATED PARTIALLY IN THE WALL. | | | 29) SHT. A1.610 - DETAIL #1 - THE FLOOR PLAN SHOWS THE | | | DOOR SWINGING INTO THE SHOWER AND THE TOILET | | | COMPARTMENT. THE INSWING DOOR IS IMPEDING ACCESS TO THE | | | SHOWER CONTROLS AND THE USE OF THE TOILET AND DOES NOT | | | COMPLY WITH FAIR HOUSING. REVERSE THE SWING OF THE | | | DOOR. | | | 30) SHT. A1.610 - DETAIL #3 - THE NOTES AND DETAILS FOR | | | THE GRAB BAR REINFORCEMENT DON'T MAKE SENSE. CORRECT | | | THE DEFICIENCIES. IF THIS IS SUPPOSED TO BE AN FHA | | | OMPLIANT BATHROOM SHOW ALL CLEAR FLOOR FLOOOR SPACES | | | AND THE FHA BATHROOM TYPE ON THE PLAN. THE LAVATORY | | | APPEARS LIKE ENCROACH INTO THE REQUIRED CLEAR FLOOR | | | SPACE FFOR THE SHOWER.CLARIFY. | | | 31) SHT. A1.610 - DETAIL # 6 - IF THIS IS THE FHA | | | COMPLIANT BATHROOM, PLACE THE TYPE OF FHA BATHROOM ON | | | THE PLAN AND CORRECT THE OVERLAY OF THE UNIT NUMBER ON | | | THE FLOOR PLAN.PLEASE CORRECT THE OVERLAY ON DETAIL #5 | | | ALSO. | | | 32) SHT. A1.610 - DETAIL #7 - CORRECT THIS DETAIL. | | | LOCATION OF REINFORCEMENT AND CLEAR FLOOR SPACES ARE | | | OUT OF WHACK. CONTROLS ARE CALLED OUT ON THE | | | LAVATORY.BATHROOM FLOOR PLAN IS CUTOFF AND INCOMPLETE. | | | CLARIIFY. | | | 33) SHT. P1.00 - THERE IS A LINE IDENTIFIED AS "8 INCH | | | CWS UP" AND THE ARROW APPEARS TO POINT TO A 10 INCH | | | SANITARY LINE. REFER TO COLUMN LINE G-11 NEAR STAIR #1. | | | CLARIFY. | | | 34) SHT. P100 - EXPAND THE PIPING LAYOUT FOR THE | | | SANITARY AND VENT LINES AND TAG THE RISERS AT THE | | | TOILET ROOMS BY ELEVATORS P03, P04, & P05 ON COLUUMN | | | LINE H. | | | 35) SHT. P100 - ONE OF THE 6 INCH KW LINES BY THE | | | GREASE IINTERCEPTORS IS ALSO LABELED AS AN 8 INCH CW | | | UP. CLARIFY. | | | 36) SHT. P100 - THERE ARE A LOT OF DRAIN LINES ON THIS | | | PLAN, ESPECIALLY AT THE STAIRS, THAT BEAR NO RISER | | | TAGS.CLARIFY. | | | 38) SHT. P.101 & SHT. P.101B SHOWS AN 8 INCH SANITARY | | | LINE WITHIN THE STAIRWAY # 4 AND ALSO A 4 INCH GW LINE | | | IN STAIRWAY #10. THE LINE IS NOT PERMITTED WITHIN THE | | | STAIRWAY PER FBC-BUILDING SEC.1023.5. | | | 39) SHTS. P.101A, P.101B, P.101C, & P.101C - THERE ARE | | | DRAIN, GAS, RAINWATER, CONDENSATE AND WATER LINES THAT | | | HAVE NO RISER TAGS AND SOME RISER TAGS HAVE NO DRAWING | | | LOCATIONS ON THEM, RISER TAGS WITH NO ARROWS | | | IDENTIFYING THE SPECIFIC LINES, ETC.PROVIDE THE | | | REQUESTED INFORMATION ON THESE DRAWINGS. WPB AMEND. TO | | | FBC SEC. 107.2.1, 107.3.5.1.3. | | | 40) IDENTIFY THE STAIR NUMBERS ON THE PLUMBING SHEETS. | | | THIS WILL HELP IN DETERMINING THE LOCATION OF PIPE | | | SYSTEMS ON THE RE-REVIEW.WPB AMND. TO FBC SEC. | | | 107.2.1.2ND REQUEST. | | | 41) SHTS. P.102A, P.102B, P.102C, P.102D - THERE ARE | | | DRAIN, RAINWATER, CONDENSATE AND WATER LINES THAT HAVE | | | NO RISER TAGS AND SOME RISER TAGS HAVE NO DRAWING | | | LOCATIONS ON THEM, RISER TAGS WITH NO ARROWS | | | IDENTIFYING THE SPECIFIC LINES, ETC.PROVIDE THE | | | REQUESTED INFORMATION ON THESE DRAWINGS. WPB AMEND. TO | | | FBC SEC. 107.2.1, 107.3.5.1.3. | | | 42) SHTS.P.103A, P.103B, P.103C, P.103D - THERE ARE | | | DRAIN, RAINWATER, CONDENSATE AND WATER LINES THAT HAVE | | | NO RISER TAGS AND SOME RISER TAGS HAVE NO DRAWING | | | LOCATIONS ON THEM, RISER TAGS WITH NO ARROWS | | | IDENTIFYING THE SPECIFIC LINES, ETC.PROVIDE THE | | | REQUESTED INFORMATION ON THESE DRAWINGS. WPB AMEND. TO | | | FBC SEC. 107.2.1, 107.3.5.1.3. | | | 43 - SHTS. P.104A THROUGH SHT. P104D - THERE ARE DRAIN, | | | RAINWATER, CONDENSATE AND WATER LINES THAT HAVE NO | | | RISER TAGS AND SOME RISER TAGS HAVE NO DRAWING | | | LOCATIONS ON THEM, RISER TAGS WITH NO ARROWS | | | IDENTIFYING THE SPECIFIC LINES, ETC.PROVIDE THE | | | REQUESTED INFORMATION ON THESE DRAWINGS. WPB AMEND. TO | | | FBC SEC. 107.2.1, 107.3.5.1.3. | | | 44) SHTS. P1.05A THROUGH P.105D - THERE ARE DRAIN, | | | RAINWATER, CONDENSATE AND WATER LINES THAT HAVE NO | | | RISER TAGS AND SOME RISER TAGS HAVE NO DRAWING | | | LOCATIONS ON THEM, RISER TAGS WITH NO ARROWS | | | IDENTIFYING THE SPECIFIC LINES, ETC.PROVIDE THE | | | REQUESTED INFORMATION ON THESE DRAWINGS. WPB AMEND. TO | | | FBC SEC. 107.2.1, 107.3.5.1.3. | | | 45) SHTS. P.106A THROUGH SHT. 106D - THERE ARE DRAIN, | | | RAINWATER, CONDENSATE AND WATER LINES THAT HAVE NO | | | RISER TAGS AND SOME RISER TAGS HAVE NO DRAWING | | | LOCATIONS ON THEM, RISER TAGS WITH NO ARROWS | | | IDENTIFYING THE SPECIFIC LINES, ETC.PROVIDE THE | | | REQUESTED INFORMATION ON THESE DRAWINGS. WPB AMEND. TO | | | FBC SEC. 107.2.1, 107.3.5.1.3. | | | 46) SHTS. P.107A THROUGH P.107D - THERE ARE DRAIN, | | | RAINWATER, CONDENSATE AND WATER LINES THAT HAVE NO | | | RISER TAGS AND SOME RISER TAGS HAVE NO DRAWING | | | LOCATIONS ON THEM, RISER TAGS WITH NO ARROWS | | | IDENTIFYING THE SPECIFIC LINES, ETC.PROVIDE THE | | | REQUESTED INFORMATION ON THESE DRAWINGS. WPB AMEND. TO | | | FBC SEC. 107.2.1, 107.3.5.1.3. | | | 47) SHTS. P.108A THROUGH P.108D - THERE ARE DRAIN, | | | RAINWATER, CONDENSATE AND WATER LINES THAT HAVE NO | | | RISER TAGS AND SOME RISER TAGS HAVE NO DRAWING | | | LOCATIONS ON THEM, RISER TAGS WITH NO ARROWS | | | IDENTIFYING THE SPECIFIC LINES, ETC.PROVIDE THE | | | REQUESTED INFORMATION ON THESE DRAWINGS. WPB AMEND. TO | | | FBC SEC. 107.2.1, 107.3.5.1.3. | | | 48) SHT. P.105D SHOWS 2-4INCH RW LINES WITHIN THE | | | STAIRWAY #7. THESE LINES ARE NOT PERMITTED WITHIN THE | | | STAIRWAY PER FBC-BUILDING SEC.1023.5. | | | 49) SHT. P.106D SHOWS FOUR- 4 INCH ROOF DRAINS AND A 4 | | | INCH RW LINE WITHIN STAIRWAY #7.THE LINES ARE NOT | | | PERMITTED WITHIN THE STAIRWAY PER FBC-BUILDING | | | SEC.1023.5. | | | 50) SHTS. P.107A, P.107C & P.107D - THE DRAWINGS SHOW | | | RAINWATER DRAIN PIPING AND ROOF DRAINS LOCATED IN | | | STAIRWAYS #5, #12, & #7. THESE LINES AND DRAINS ARE NOT | | | PERMITTED WITHIN THE STAIRWAY PER FBC-BUILDING | | | SEC.1023.5. | | | 51) SHTS. P.108A, P.108B, P.108C - THE DRAWINGS SHOW | | | RAINWATER DRAIN PIPING, DRAINS AND CONDENSATE PIPING IN | | | STAIRWAYS #5, 8 & #9. THE LINES AND DRAINS ARE NOT | | | PERMITTED WITHIN THE STAIRWAY PER FBC-BUILDING | | | SEC.1023.5. | | | 52) THE OVERALL PIPNG PLANS FOR THE PODIUM LEVELS ARE | | | MISSING SECTIONS OF PIPING AND BASICALLY HAVE NO | | | INFORMATION ON THEM AND ARE USELESS FOR REVIEW.I | | | UNDERSTAND THAT THESE ARE OVERALLL PLANS BUT THE | | | DRAWINGS ARE MISSING BASIC ESSENTIAL INFORMATION FOR | | | PLAN REVIEW. WPB AMEND. TO FFBC SEC. 107.2.1, | | | 107.3.5.1.3. | | | 53) SHTS. P.251 THROUGH 256 - THE RISER TAGS FOR THE LW | | | RISERS ARE MISSING THE DRAWING LOCATIONS ON THE RISER | | | TAGS. CLARIFY. | | | 54) SHTS. P. 258 THROUGH P.261 - THE RISER TAGS FOR THE | | | LW RISERS ARE MISSING THE DRAWING LOCATIONS ON THE | | | RISER TAGS.CLARIFY. | | | 55) SHT. P.510 - DETAIL #6 - TWO LAVATORIES ARE MISSING | | | FROM THE SANITARY RISER. CLARIFY. | | | 56) SHT. P.510 - DETAIL #3 - A LAVATORY IN THE MEN'S | | | AND WOMEN'S HANDICAP STALL IS MISSING FROM SANITARY | | | RISER. CLARIFY. | | | 57) SHT. P.510 - DETAILS #2 & #3 THE DRINKING FOUNTAINS | | | ARE MISSING FROM THE SANITARY AND WATER RISERS. | | | 58) SHT. P.5.11 - DETAIL #4 - ROOMS #0243 & 0245 - THE | | | URINAL DOES NOT APPEAR TO BE VENTED. CLARIFY. | | | 59) SHT. P.511 -DETAIL #4 - THE LAVATORY IN THE | | | HANDICAP STALL IN THE WOMEN'S CHANGING FACILITY IS NOT | | | SHOWN ON THE SANITARY RISER. | | | 60) SHT. P.511 - DETAIL #4 - IT APPEARS THERE IS A | | | STANDARD WATER CLOSET IN THE WOMEN'S CHANGING FACILITY | | | THAT IS NOT SHOWN ON THE SANITARY RISER DIAGRAM. | | | 61) SHT. P.511 - DETAIL #4 - THE LAVATORY IN THE MEN'S | | | HANDICAP STALL IS NOT SHOWN ON THE SANITARY RISER. | | | 62) SHT. P.511 - DETAIL #4 - THERE IS A LAVATORY ON THE | | | RISER DIAGRAM FOR THE MEN'S CHANGING FACILITY THAT IS | | | NOT SHOWN ON THE FLOOR PLAN. 61) SHT. P.503 - | | | 63) SHT. P.513 - DETAIL #1 - REVVISE THIS DETAIL TO | | | CLEARLY SHOW THE 3 LAVATORIES IN EACH RESTROOM. THERE | | | IS AN OVERLAY THAT CURRENTLY LOOKS LIKE 5 LAVATORIES. | | | 2ND REQUEST. | | | 64) SHT. P.514 - DETAI #5 - THE LW RISER TAGS DO NOT | | | HAVE DRAWING LOCATIONS ON THE RISER TAGS. CLARIFY. | | | 65) SHT. P.514 - DETAIL#6 - THE LAVATORY IN THE WOMEN'S | | | HANDICAP ACCESSIIBLE STALL IS NOT SHOWN ON THE SANITARY | | | RISER. CLARIFY. | | | 66) SHT. P.701 - THE RISER TAGS AT THE BOTTOM AND TOP | | | OF THE HOTEL/OFFICE DOMESTIC WATER RISERS ARE MISSING | | | THE DRAWING LOCATIONS. CLARIFY. | | | 67) SUBMIT A PIPING DETAIL FOR MASTER THERMOSTATIC | | | MIXING VALVES TMV-1, TMV-2 & TMV-3. THE PIPING FOR | | | RECIRCULATION SYSTEMS HAVING MASTER THERMOSTATIC VALVES | | | SHALL CCOMPLY WITH FBC-PLUMBING SEC. 607.2.2. 2ND | | | REQUEST. | | | 68) SHT. P.702 - THERE ARE BRANCHES OFF THE WATER | | | RISERS THAT SOME HAVE NO SIZES OR THE AREA THEY SUPPLY. | | | REFER TO LEVELS 2-8. SUPPLY THE REQUIRED INFO. WPB | | | AMEND. TO FBC SEC. 107.3.5.1.3. 2ND REQUEST. | | | 69) SHT. P.703 - ALMOST ALL OF THE RISER TAGS ARE | | | MISSING DRAWING LOCATION INFORMATION. CLARIFY. | | | 70) SHT. P.703A & P.703B - THERE ARE DRAWING LOCATION | | | NUMBERS MISSING FROM NUMEROUS RISER TAGS ON THESE | | | SHEETS.SUPPLY THE APPLICABLE DRAWING LOCATION NUMBERS | | | ON THESE TAGS. | | | 71) SHT. P.703A - THE STACK DESIGNATION TYPE AND RISER | | | NUMBERING ON THE RISER TAGS DOES NOT CORRELATE WITH THE | | | REFERENCED RISER TAGS ON SHTS. P502 & SHT. P.503. | | | CLARIFY. | | | 72) SHT. P.703B - RISER TAGS ARE MISSING THE DRAWING | | | LOCATION NUMBERS ON THE RISER TAGS. ENSURE ALL RISER | | | TAGS ARE COMPLETE. | | | 73) SHT. P.704 - NUMEROUS RISER TAGS ARE MISSING | | | DRAWING LOCATION INFORMATION/NUMBERS. | | | 74) SHT. P.704A - RISER TAGS ARE MISSING THE DRAWING | | | LOCATION NUMBERS ON THE RISER TAGS. ENSURE ALL RISER | | | TAGS ARE COMPLETE. | | | 75) SHT. P.704B - RISER TAGS ARE MISSING THE DRAWING | | | LOCATION NUMBERS ON THE RISER TAGS. ENSURE ALL RISER | | | TAGS ARE COMPLETE. | | | 76) SHT. P.705A - THE PRINTING ON THE RISER TAGS IS SO | | | LIGHT THAT IT IS ILLEGIBLE. PROVIDE LEGIBLE INFO. WPB | | | AMEND. TO FBC SEC. 107.2.1. | | | 77) SHT. SHT. P.706 - DETAILS #7, 8, 10, 11, &12 - ONLY | | | 4 FIXTURE UNITS ARE ALLOWED ON A 2 INCH WET VENT PER | | | FBC-PLUMBING TABLE 912.3. THE HORIZONTAL DRAIN FROM THE | | | WATER CLOSET SHALL BE 3 INCHES UP TO THE FIRST | | | HORIZONTAL FIXTURE DRAIN (BATHTUB/SHOWER). | | | 78) SHT. P.706 - DETAIL #9 - THE HORIZONTAL DRAIN FROM | | | THE WATER CLOSET UP TO THE FIRST HORIZONTAL BRANCH | | | SHALL BE 3 INCHES IN DIAMETER PER FBC-PLUMBING TABLE | | | 912.3. | | | 79) SHT. P.706 - DETAIL #10 & #20 - THE BATHTUBS ARE | | | NOT VENTED. THEY CANNOT CONNECT DIRECTLY TO THE SHOWER | | | OR WATER CLOSET FIXTURE DRAIN. FBC-PLUMBING | | | SECS.1002.1, 901.2. | | | 80) SHT. P.706 - DETAIL #19 - THE DRAIN FROM THE | | | WASHING MACHINE BOX TO THE STACK SHALL BE A MINIMUM OF | | | 3 INCHES IN DIAMETER PERR FBC-PLUMBING SEC.406.2. | | | 81) SHT. P.707 - DETAILS #1,2,3,4,,& 5 - RISER TAG | | | NUMBERS, STACK DESIGNATION AND DRAWING LOCATION | | | INFORMATION IS MISSING FROM THE RISER TAGS. ENSURE ALL | | | RISER TAGS ARE COMPLETE. | | | 82) SHT. P.709 - THE DRAIN FROM THE WASHING MACHINE BOX | | | TO THE STACK SHALL BE A MINIMUM OF 3 INCHES IN DIAMETER | | | PERR FBC-PLUMBING SEC.406.2. | | | 83) SHT. P.709 - THE DRAWING LOCATION INFORMATION IS | | | MISSING FROM ALL OF THE WASTE AN SANITARY STACK RISER | | | DIAGRAMS. ENSURE ALL RISER TAGS ARE COMPLETE. | | | 84) SHT. P.709 - IDENTIFY THE CONTINUATION POINTS OF | | | BOTH 6 INCH VERTICAL SANITARY DRAINS THAT TURN DOWN. | | | 85) SHT. P.710 - DETAIL #5 - THE WATER RISER DIAGRAM | | | DOES NOT CORRELATE WITH THE REFERENCED ENLARGED FLOOR | | | PLAN DETAIL #5 ON SHT. P.505. THESES ARE TWO DIFFERENT | | | UNITS. CLARIFY. | | | 86) SHT.P.710 - DETAIL #4 - THE WATER CONNECTION FROM | | | THE WATER RISER TO THE UNIT IS MISSING. CLARIFY. | | | 87) SHT. P.711 - DETAIL #2 - THERE IS A BATHTUB MISSING | | | ON THE WATER RISER IN ONE OF THE BATHROOMS AND THE | | | SHOWER IS LABELED AS A BATHTUB IN THE SAME BATHROOM, | | | AND ONLY ONE LAVATORY IS SHOWN ON THE RISER IN THIS | | | SAME BATH. CLARIFY. | | | 88) SHT. P.711 - DETAIL #2 - THERE IS A BATHTUB SHOWN | | | ON THE WATER RISER IN THE MASTER BATH BUT IT IS NOT | | | SHOWN ON THE FLOOR PLAN AND THE WATER CLOSET AND | | | LAVATORY ARE REVRSED ON THE WATER RISER IN THE MASTER | | | BATH.. CLARIFFY. | | | 89) SHT. P.711 - DETAIL #6 -THE LAYOUT OF THE FIXTURES | | | ON THE WATER RISER DIAGRAM DOES NOT CORRELATE WITH THE | | | LAYOUT OF THE PLUMBING FIXTURES ON REFERENCED SHT. | | | P.507, DETAIL #2. ALSO, THE RISER TAG INFORMATION IS SO | | | LIGHT IT IS ILLEGIBLE. CLARIFY. | | | 90) SHT. P.712 - DETAIL #F - THE SANITARY RISER IS | | | INCOMPLETE. FIXTURES ARE MISSING. EXPAND THE RIDER SO A | | | PROPER REVIEW CAN BE DONE. WPB AMEND. TO FBC SEC. | | | 107.2.1, 107.3.5.1.3. | | | 91) SHT. P.712 - THE WATER SUPPLY BRANCHES FROM THE | | | RISERS TO THE MEN'S AND WOMEN'S OFFICE TOILET RROOMS | | | REQUIRE SHUTOFF VALVES TO RESTROOMS. FBC-PLUMBING SEC. | | | 606.1. | | | 92) SHT. P.712 - DETAILS #3, #4, & #6 - THE RISER TAGS | | | ARE MISSING THE RISER INFORMATION. ENSURE ALL RISER | | | TAGS ARE COMPLETE. | | | 93) SHT. P.712 - DETAIL #6 - THE DRINKING FOUNTAINS | | | SHOWN ON DETAIL #3 ARE NOT SHOWN ON THE WATER RISER ON | | | DETAIL #6 OR THE WATER RISER FOR THE OFFICE TOWER - | | | WOMEN'S TOILET ROOM. CLARIFY. | | | 94) SHT. P.720 - IDENTIFY ALL RISERS WITH RISER TAGS | | | COMPLETE WITH ALL RISER TAG INFO AND FIXTURE UNIT | | | LOADS. THERE ARE STILL RISERS THAT HAVE NO TAGS. WPB | | | AMEND. TO FBC SEC. 107.2.1, 107.3.5.1.3. | | | 95) SHT. P.730 - IDENTIFY ALL RISERS WITH RISER TAGS | | | COMPLETE WITH ALL RISER TAG INFO AND THE GPM'S DRAINING | | | INTO EACH RISER. WPB AMEND. TO FBC SEC. 107.2.1, | | | 107.3.5.1.3. | | | 96) SHT. P.731 - THE DRAWING IS INCOMPLETE.SECTIONS OF | | | PIPE ARE MISSING, PIPE SIZES ARE MISSING, NO RISER | | | TAGS, SECTIONS OF THE PIPING SYSTEM ARE CONGESTED AND | | | DIFICULT TO REVIEW.WPB AMEND. TO FBC SEC. 107.2.1, | | | 107.3.5.1.3. | | | 97) SHT. P.732 - THE RISER SHOWS THE SQUARE FOOTAGE | | | AREA BEING DRAINED BUT NO GPM'S. COMPLY WITH | | | FBC-PLUMBING SEC. 11106.2. CLARIFY. | | | 98) SHT. P.733- THERE ARE SEVERAL RISER TAGS MISSING | | | THE DRAWING LOCATION INFORMATION.ENSURE ALL RISER TAGS | | | ARE COMPLETE. | | | 99) SHT. P.734 - THERE ARE SEVERAL RISER TAGS MISSING | | | THE DRAWING LOCATION INFORMATION.ENSURE ALL RISER TAGS | | | ARE COMPLETE. | | | 100) SHT. P.803 - DETAIL #9 - SUBMIT DETAILS AS TO HOW | | | THE WOOD BLOCK IS BEING ATTACHED TO THE ROOF. WPB | | | AMEND. TO FBC SEC. 107.2.1.2ND REQUEST. | | | 101) HT. P.803 - DETAIL #3 SHOWS JOINTS UNDER THE SLAB | | | - PLUMBING SPECIFICATIONS SEC.221110 - PART 2 - 2.02 | | | STATES THAT "ENTRANCE PIPING TO THE BUILDING TO | | | TERMINATE ABOVE GRADE." THE DETAIL ON P.803 SHOWS | | | FLANGED FITTINGS UNDER THE SLAB. CLARIFY. IF THIS | | | PIPING ARRANGEMENT IS TO REMAIN, SUBMIT DETAILS ON | | | FITTING RESTRAINTS AND THRUST BLOCK INFORMATION. WPB | | | AMEND. TO FBC SEC. 107.2.1, 107.3.5.1.3.2ND REQUEST. | | | 102) RIGID SUPPORT SWAY BRACING SHALL BE PROVIDED AT | | | CHANGES IN DIRECTION GREATER THAN 45 DEGREES FOR PIPE | | | SIZES 4 INCHES AND LARGER PER FBC-PLUMBING SEC.308.6. | | | SUBMIT DETAILS FOR THE BRACING. 2ND REQUEST. | | | 103) SHT. P.804 - DETAIL #7 - THE REDUCED PRESSURE | | | BACKFLOW PREVENTER AT HE TRASH CHUTE REQUIRES A DRAIN | | | PIPED TO AN APPROVEDD POINT OF DISPOSAL.M | | | 104) THE PLUMBING SPECIFICATIONS SECTION 22 1323 - PART | | | 2 - SECTION 2.01 (GREASE INTERCEPTOR) :TAG # GT-1 - | | | SECTION C -ACCESSORIES: CALLS OUT A 4-INCH INFLUENT AND | | | EFFLUENT TWO-WAY CLEANOUT, BUT ALSO CALLS OUT A 6-INCH | | | SAMPLING PORT. THIS WOULD CREATE AN OBSTRUCTION TO FLOW | | | AND VIOLATES FBC-PLUMBING SEC.706.2. THIS SECTION ALSO | | | CALLS OUT A SCHIER INTERCEPTOR WITH 6-INCH INLET AND | | | OUTLET. CLARIFY. 2ND REQUEST. THE SUBMITTED RESPONSE | | | NARRATIVE STATES THE 4 INCH REFERENCE IS INCCORRECT BUT | | | THE SPECIFICATION IS STILL WRONG.CORRECT THE | | | SPECIFICATION. | | | NOTE: WHEN THE REVISED PLANS ARE UPLOADED, ENSURE THEY | | | ARE DONE IN SEQUENTIAL ORDER AND THAT ALL PLANS ARE IN | | | SEQUENTIAL ORDER. I HAVE WASTED AN INORDINATE AMOUNT OF | | | TIME DURING THIS LAST REVIEW SEARCHING THROUGH NUMEROUS | | | DRAWINGS TO FIND THE CORRECT PLAN THAT WAS SUPPOSED TO | | | HAVE ADDRESSED THE REVIEW COMMENT. | | | | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | PLUMBING PLAN REVIEW | | | 561-805-6692 | | | [email protected] | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | . | | | |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
F |
Date |
2020-03-28 |
|
|
Cont ID |
|
| Sent By |
tklarge |
Date |
2020-03-28 |
Time |
10:03 |
Rev Time |
0.00 |
| Received By |
tklarge |
Date |
2020-02-29 |
Time |
05:31 |
Sent To |
|
|
| Notes |
| 2020-03-22 04:50:20 | STEP ADDED BY MISTAKE. | | 2020-03-22 04:49:29 | THE FOLLOWING COMMENTS ARE FROM THE PLUMBING PLAN | | | REVIEW THAT WAS DONE ON 4/9/2019 THAT HAVE NOT BEEN | | | PROPERLY ADDRESSED: | | | PLUMBING: | | | COMMENT # 2 - PLACE A NOTE ON THE PLANS THAT THE | | | RESIDENTIAL TOWER UNITS AND THE COMMON AREAS SHALL | | | COMPLY WITH THE FAIR HOUSING ACT REQUIREMENTS AND ANSI | | | A117.1 - 1986. THE NOTE THAT WAS PLACED ON THE PLAN | | | REFERS TO THE FLORIDA BUILDING CODE ACCESSIBILITY 2014. | | | 2ND REQUEST. | | | COMMENT #32 -ON THE PLUMBING SHEETS, LABEL AND TAG ALL | | | RISERS ON ALL FLOOR PLANS. THERE ARE NUMEROUS RISERS | | | THAT HAVE NO LABELS OR TAGS AND THERE ARE OTHERS THAT | | | HAVE INCOMPLETE INFORMATION ( RISERS ARE LABELED WITH | | | NO TAG OR TAGGED WITH NO LABEL). WPB AMEND. TO FBC SEC. | | | 107.2.1. | | | COMMENT #35 - THE PLANS SHOW AIR ADMITTANCE VALVES | | | INSTALLED ON SOME OF THE KITCHEN SINKS.WHERE THE | | | HORIZONTAL BRANCH IS LOCATED MORE THAN FOUR BRANCH | | | INTERVALS FROM THE TOP OF THE STACK, THE HORIZONTAL | | | BRANCH SHALL BE PROVIDED WITH A RELIEF VENT THAT SHALL | | | CONNECT TO A VENT STACK OR STACK VENT , OR EXTEND | | | OUTDOORS TO THE OPEN AIR. I DID NOT SEE WHERE THIS WAS | | | DONE. PROVIDE THE SHEET/DRAWING NUMBER(S) THAT WAS | | | REVISED TO SHOW COMPLIANCE. WPB AMEND. TO FBC SEC. | | | 107.2.1, 2014 FBC-PLUMBING SEC. 918.3.1. | | | COMMENT # 38 - PROVIDE A COMPLETE SANITARY ISOMETRIC | | | DIAGRAM FOR THE UNDERGROUND / UNDERSLAB COLLECTION | | | SYSTEM. THE DRAWING SUBMITTED ON SHT. P.720 IS | | | INSUFFICIENT AND DEFICIENT IN THE NECESSARY INFORMATION | | | TO PERFORM A COMPREHENSIVE REVIEW ON THE DRAWING.WPB | | | AMEND. TO FBC SEC. 107.3.5.1.3. | | | COMMENT #40 - PLACE A NOTE ON THE PLANS THAT ACCESS | | | SHALL BE PROVIDED TO THE WATER SUPPLY SHUTOFF VALVES | | | FOR THE STACKABLE WASHING MACHINES IN THE RESIDENTIAL | | | UNITS. 2014 FBC-PLUMBING SEC. 606.3. THE RESPONSE | | | NARRATIVE FROM THE DESIGN PROFESSIONAL STATES THAT A | | | NOTE WAS ADDED TO THE PLANS BUT I COULD NOT LOCATE THIS | | | NOTE. PROVIDE THE SHEET/ DRAWING NUMBER WHERE THE NOTE | | | CAN BE FOUND. WPB AMEND. TO FBC SEC. 107.2.1. | | | COMMENT # 42 - THE ENLARGED PLUMBING FLOOR PLANS APPEAR | | | TO HAVE TAGS ON THE STACKS THAT ARE INCOMPLETE.ENSURE | | | THAT ALL STACKS/RISERS ARE FULLY LABELED AND TAGGED TO | | | MATCH THE ISOMETRIC DRAWING AND FULL FLOOR PLANS. | | | | | | NEW PLUMBING COMMENTS: | | | | | | 1) PLACE A NOTE ON THE PLANS THAT THE BACKFLOW | | | PREVENTERS WILL REQUIRE A SEPARATE PERMIT AND SHALL | | | COMPLY WITH 2014 FBC-PLUMBING SEC.605.2.1 AND THE CITY | | | OF WEST PALM BEACH CROSS-CONNECTION CONTROL MANUAL. | | | 2) PLACE A NOTE ON THE PLUMBING PLANS THAT A SEPARATE | | | PERMIT IS REQUIRED FOR THE GREASE INTERCEPTORS. | | | 3) SHT.A1.602 - DETAIL #1 - WOMEN'S RESTROOM - SHOW THE | | | INSIDE CLEAR DIMENSIONS (L X W) OF THE HANDICAP | | | ACCESSIBLE TOILET COMPARTMENTS AND SHOW THE LENGTH OF | | | THE STANDARD TOILET COMPARTMENTS ON THE PLAN. WPB | | | AMEND. TO FBC SEC. 107.2.1. | | | 4) SHT. A1.602 - DETAIL #1 - WOMEN'S RESTROOM - SHOW | | | THE LENGTH AND WIDTH DIMENSIONS OF THE AMBULATORY | | | ACCESSIBLE TOILET COMPARTMENT ON THE PLANS. COMPLY WITH | | | 2014 FBC- ACCESS. SECS.604.8.2.1, 604.8.2.2, 604.8.2.3. | | | 5) SHT. A1.602 - DETAIL #2 - SHOW THE LENGTH OF THE | | | AMBULATORY ACCESSIBLE TOILET COMPARTMENT IN THE MEN?S | | | RESTROOM. COMPLY WITH 2014 FBC- ACCESS. SECS.604.8.2.1, | | | 604.8.2.2, 604.8.2.3. | | | 6) SHT. L5-711 - DETAIL #6 - SUBMIT ADDITIONAL | | | DOCUMENTATION FOR THE POOL DECK SHOWER. IF THIS SHOWER | | | IS IN THE RESIDENTIAL TOWER POOL AREA, IT SHALL COMPLY | | | WITH ANSI A117.1-1986. IF IT IS IN THE HOTEL, THE | | | SHOWER CONTROLS SHALL COMPLY WITH THE 2014 FBC-ACCESS. | | | SEC. 308 FOR REACH RANGES AND SEC.309 FOR OPERABLE | | | PARTS. | | | 7) SHT. L5-711 - DETAIL #7- SUBMIT ADDITIONAL | | | INFORMATION FOR THE WATER FOUNTAIN AT THE POOL DECK. IF | | | THIS DRINKING FOUNTAIN IS IN THE RESIDENTIAL TOWER POOL | | | AREA, IT SHALL COMPLY WITH ANSI A117.1-1986. IF IT IS | | | IN THE HOTEL, THE DRINKING FOUNTAIN SHALL COMPLY WITH | | | SECS. 211 AND 602 OF THE 2014 FBC-ACCESS. | | | 8) SHT. A0.101 - HEADING III - CODE DATA - THERE IS AN | | | ITEM STATING, "SWIMMING POOL TABLE NOT REQUIRED PER FBC | | | 2014 424.1.6.1". THERE IS NO SUCH CODE SECTION IN THE | | | 2014 FBC. SECTION. 424 IS FOR CHILDREN'S PLAY | | | STRUCTURES. CLARIFY. | | | 9) SHT. A0.101 - APPLICABLE CODES - THE LIST REFERS TO | | | THE 2010 EDITION OF THE PLUMBING AND MECHANICAL CODES. | | | THIS PROJECT FALLS UNDER THE 2014 EDITIONS OF THE | | | PLUMBING AND MECHANICAL CODES. CLARIFY. | | | 10) SHT. A0.201 - FAIR HOUSING REQUIREMENTS - NOTE #4 | | | REFERS TO "FBC SECTION 11-4.26.3." THERE IS NO SUCH | | | CODE SECTION IN THE 2014 EDITION OF THE FBC. CLARIFY. | | | 11) SHT. A0.202 - FBC- ACC FIXTURE MOUNTING HEIGHTS AND | | | GRAB BAR MOUNTING REQUIREMENTS - GRAB BARS SHALL BE | | | MEASURED FROM THE FINISH FLOOR TO THE TOP OF THE | | | GRIPPING SURFACE PER 2014 FBC-ACCESS. SEC. 609.4. | | | 12) SHT. A0.202 - FBC -ACC FIXTURE MOUNTING HEIGHTS - | | | SHOW THE HEIGHT OF THE WATER CLOSET ABOVE THE FINISH | | | FLOOR. COMPLY WITH 2014 FBC-ACCESS. SEC. 604.4. | | | 13) SHTS. A0.201, A0.202, & A0.203 - THE DETAILS ARE | | | LABELED AS ADA. THESE DETAILS ARE TO BE LABELED AS | | | FLORIDA ACCESSIBILITY CODE. THE ADA IS NOT ENFORCED. | | | FLORIDA'S ACCESSIBILITY CODE IS A DEPT. OF JUSTICE | | | CERTIFIED CODE AS BEING SUBSTANTIALLY EQUIVALENT TO THE | | | ADA STANDARDS. | | | 14) SHT.A0.203 - SHOWER ELEVATIONS - THE SHOWER SPRAY | | | UNIT SHALL BE LOCATED NO MORE THAN 48 INCHES ABOVE THE | | | SHOWER FLOOR. THE ELEVATION SHOWS 5 FEET. 2014 | | | FBC-ACCESS. SEC. 608.5.2, 608.5.3. | | | 15) SHT. A1.107 - MEN'S RESTROOM #0757 & WOMEN'S | | | RESTROOM #0756 - THE DOORS FOR THE AMBULATORY | | | ACCESSIBLE COMPARTMENTS CANNOT SWING INTO THE MINIMUM | | | REQUIRED COMPARTMENT AREA. 2014 FBC-ACCESS. | | | SEC.604.8.2.2. | | | 16) SHT.A1.107 - MEN'S RESTROOM # 0730 - AN AMBULATORY | | | ACCESSIBLE TOILET COMPARTMENT IS REQUIRED PER 2014 | | | FBC-ACCESS. SEC.213.3.1. | | | 17) SHT. A1.256 - OFFICE TOWER FLOOR PLAN - ROOF LEVEL | | | - SUBMIT INFORMATION FOR THE CHEMICAL TREATMENT SYSTEM. | | | SUBMIT MSDS SHEETS FOR THE CHEMICALS BEING USED. SUBMIT | | | INFORMATION ON THE AMOUNTS OF EACH CHEMICAL BEING USED, | | | WHERE THEY ARE BEING STORED, THE TYPES OF CONTAINERS | | | THE CHEMICALS ARE STORED IN, ETC. COMPLIANCE WITH SEC. | | | 414 & 415 OF THE 2014 FBC MAY BE REQUIRED. | | | 18) SHT. A1-501 - FAIR HOUSING NOTE #3 REFERS TO SEC. | | | 11-4.26.3. THERE IS NO SUCH SECTION IN THE FAIR HOUSING | | | DESIGN MANUAL. CLARIFY. | | | 19) SHT. A1.503 - DETAIL #2 - HOTEL SUITE 3.1A OR 3.1B | | | - THE SEAT IN THE SHOWER SHALL COMPLY WITH FBC-ACCESS. | | | SEC. 610.3. AS SHOWN, IT DOES NOT COMPLY. | | | 20) SHT. A1.600 - DETAIL #1 - WOMEN'S RESTROOM - THE | | | PLAN STATES A CLEAR FLOOR SPACE OF 60 INCHES WIDE, BUT | | | THE PLAN ALSO SHOWS THE WIDTH OF THIS SPACE AS 4 FEET, | | | 11 INCHES. CLARIFY. COMPLY WITH FBC-ACCESS. | | | SEC.604.3.1. | | | 21) SHT.A1.600 - DETAIL #1 - MEN'S RESTROOM - ONE OF | | | THE URINALS IS SHOWN AS 1 FOOT 2 INCHES FROM A WALL TO | | | THE CENTERLINE OF THE URINAL. A MINIMUM OF 15 INCHES | | | FROM A WALL TO THE CENTER OF THE URINAL IS REQUIRED. | | | FBC-PLUMBING SEC.405.3.1. | | | 22) SHT.A1.601 - DETAIL # 1 - GROUND LEVEL BATHROOM | | | #0121 - THE DOOR TO ONE OF THE TOILET ROOMS IS SWINGING | | | INTO THE CLEAR FLOOR SPACE FOR THE LAVATORY. | | | FBC-ACCESS. SEC. 603.2.3. SEE EXCEPTIONS. | | | 23) SHT. A1.601 - THE DOOR IS IN FRONT OF THE WATER | | | CLOSET. THE WATER CLOSET CANNOT OVERLAP THE REQUIRED | | | MANEUVERING CLEARANCE FOR THE DOOR INSIDE THE ROOM. | | | SHOW THE REQUIRED MANEUVERING CLEARANCE FOR THE DOOR IN | | | ACCORDANCE WITH FBC-ACCESS. 404.2.4. | | | 24) SHT. A1.600 - GROUND LEVEL BATHROOM #0132- IS THIS | | | A UNISEX TOILET ROOM OR GENDER SPECIFIC? CLARIFY. | | | 25) SHT. A1.601 - DETAIL #6 -LEVEL 02 BATHROOM 0240 - | | | THE BENCHES IN THE MEN'S AND WOMEN'S RESTROOM SHALL | | | COMPLY WITH FBC-ACCESS. SEC.903. | | | 26) SHT. A1.601 - DETAIL #6 - LEVEL 02 BATHROOM 0240 - | | | ONE LAVATORY OUTSIDE OF THE STALL IN THE MEN?S AND | | | WOMEN?S RESTROOM SHALL COMPLY WITH FBC-ACCESS. SEC.606. | | | 27) SHT. A1.602 - DETAIL #1 - LEVEL 07 BATHROOM #0759 | | | -IDENTIFY THE AMBULATORY ACCESSIBLE COMPARTMENT ON THE | | | PLANS AND SHOW THE GRAB BARS AND PLACE THE DIMENSIONS | | | OF THE STALL ON THE PLANS. COMPLY WITH FBC-ACCESS. | | | SEC.604.8.2. | | | 28) SHOW THE LENGTH OF THE STANDARD TOILET COMPARTMENTS | | | ON THE PLANS. COMPLY WITH FBC-PLUMBING SEC.405.3.1. | | | 29) SHT. A1.602 - DETAIL #1 - LEVEL 07 BATHROOM #0759 - | | | ONE LAVATORY OUTSIDE OF THE STALL IN THE WOMEN?S | | | RESTROOM SHALL COMPLY WITH FBC-ACCESS. SEC.606. | | | 30) SHT. A1.602 - DETAIL #2 - LEVEL 8 BATHROOM 08119 - | | | IDENTIFY THE HANDICAP ACCESSIBLE URINAL. SHOW THE | | | REQUIRED CLEAR FLOOR SPACE ON THE PLAN. FBC-ACCESS. | | | SECS. 605, 305. | | | 31) SHT. A4.300 - DETAIL #2- SUBMIT A DETAIL FOR THE | | | OVERFLOW SCUPPER FOR THE OPEN DECK ON LEVEL 6 -PODIUM. | | | SHOW THE DIMENSIONS OF THE SCUPPER. | | | 31) SHT. A5.110 - DETAILS #7 & #8 - THERE ARE SYMBOLS | | | IN THESE STAIR ENCLOSURES THAT LOOK LIKE DRAINS. | | | CLARIFY. COMPLY WITH FBC-BUILDING SEC. 1022.5. | | | 32) SHT. A1.118 - DETAILS A & B - DRAINS ARE SHOWN IN | | | THE STAIR ENCLOSURE. THESE ARE NOT PERMITTED PER | | | FBC-BUILDING SEC. 1022.5. | | | 33) SANITIZING UNIT FOR THE TRASH CHUTE WILL REQUIRE A | | | HIGHER DEGREE OF BACKFLOW PROTECTION OTHER THAN A | | | VACUUM BREAKER PER FBC-PLUMBING SEC.608.1, 608.5. | | | 34) SHT. A7.501 - PROVIDE DETAILS IF THERE ARE SEPARATE | | | SHUTOFF VALVES FOR THE TUBS AND IF SO, HOW IS ACCESS | | | GOING TO BE PROVIDED TO THE SHUTOFF VALVES? | | | FBC-PLUMBING SEC.606.2. | | | 35) SHT. A7.502 - DETAIL #2 - THE HIGH POINT AT THE | | | SHOWER SHALL NOT EXCEED 1/2 OF AN INCH PER FBC-ACCESS. | | | SEC. 303, 608.7. | | | 36) SHT. A0.204 - GROUND LEVEL - MERCANTILE - THE | | | PLUMBING FIXTURE TABLE NOTES 1 DRINKING FOUNTAIN AND 1 | | | WATER COOLER TO BE PROVIDED. A MINIMUM OF TWO DRINKING | | | FOUNTAINS ARE REQUIRED PER FBC- PLUMBING SEC. 410.2, | | | FBC-ACCESS. SEC. 211.2. A SERVICE SINK IS ALSO REQUIRED | | | PER FBC-PLUMBING TABLE 403.1. THE SUBSTITUTION FOR | | | WATER COOLERS SHALL COMPLY WITH FBC-PLUMBING SEC.410.3. | | | 37).37) WHERE ONE DRINKING FOUNTAIN IS LISTED AS BEING | | | REQUIRED, A MINIMUM OF TWO DRINKING FOUNTAINS SHALL BE | | | PROVIDED IN ACCORDANCE WITH FBC-PLUMBING SEC.410.2 AND | | | FBC-ACCESS. SEC. 211.2. | | | 38) 8TH LEVEL AMENITIES - ASSEMBLY-2-BAR- PROVIDE THE | | | OCCUPANT LOAD AND FIXTURE REQUIREMENTS FOR THIS AREA. | | | THE PLAN NOTES "PENDING" CLARIFY. | | | 39) THE SUBSTITUTION FOR WATER COOLERS SHALL COMPLY | | | WITH FBC-PLUMBING SEC. 410.3. | | | 40) THERE IS A FOOTNOTE AT THE BOTTOM OF THE PLUMBING | | | FIXTURE CHART ON SHT. A0.204 THAT REFERS TO FBC SEC. | | | 403.6 FOR THE EXCEPTION OF SANITARY FACILITIES FOR | | | PUBLIC SWIMMING POOLS. SECTION 403.6 OF THE | | | 2014FBC-BUILDING REFERS TO ELEVATORS IN HIGH RISE | | | BUILDINGS. THE CORRECT CODE SECTION IS 454.1.6 | | | EXCEPTION. PLEASE EXPLAIN HOW ALL THE LIVING UNITS CAN | | | BE WITHIN A 200 FEET HORIZONTAL RADIUS OF THE NEAREST | | | WATER'S EDGE. | | | 41) SHT. A1.269 A - THE COVERED DWELLING UNITS THAT | | | HAVE DOUBLE BASINS SHALL HAVE THE CLEAR FLOOR SPACE | | | CENTERED ON ONE OF THE BASINS PER THE FAIR HOUSING | | | DESIGN MANUAL. | | | 42) SHT. A1.502A - THIS SHEET HAS FAIR HOUSING NOTES ON | | | IT. THIS SHEET IS FOR THE HOTEL ROOMS. THE FAIR HOUSING | | | ACT DOES NOT APPLY. THIS IS THE FBC-ACCESS. DELETE THIS | | | FAIR HOUSING NOTE FROM THE PLAN. WPB AMEND. TO FBC SEC. | | | 107.2.1. SEE SHEETS A1.507 AND A1.508 ALSO. | | | 43) A1.603 - INDICATE ON THE PLANS IN WHICH BUILDING | | | THESE SANITARY FACILITIES ARE LOCATED WPB AMEND. TO FBC | | | SEC. 107.2.1. | | | 44) A1.603 - DETAIL # 1 - LEVEL 07 BATHROOM 0760. - | | | SHOW THE REQUIRED AMBULATORY ACCESSIBLE COMPARTMENT ON | | | THE PLANS. SHOW THE GRAB BARS AND ALL DIMENSIONS. | | | 45) A1.603 - SHOW THE LOCATION AND THE CLEAR FLOOR | | | SPACE FOR THE ACCESSIBLE URINAL AND THE REQUIRED | | | HANDICAP LAVATORY OUTSIDE THE TOILET COMPARTMENT. | | | FBC-ACCESS. SEC.213.3.4, 213.3.3. | | | 46) SHT. A1.603 - DETAIL # 5 - LEVEL 8 BATHROOM 0835 - | | | THE DOOR ON THE HANDICAP ACCESSIBLE STALL IS SWINGING | | | INTO THE COMPARTMENT. DOORS SHALL NOT SWING INTO THE | | | MINIMUM REQUIRED COMPARTMENT AREA. FBC-ACCESS. SEC. | | | 604.8.1.2. | | | 47) SHT. A1.604 - DETAIL #1 - LEVEL 07 BATHROOM 0742 | | | AND 0741 - THE DOOR OF THE AMBULATORY STALL CANNOT | | | SWING INTO THE MINIMUM REQUIRED COMPARTMENT AREA. | | | FBC-ACCESS. SEC 604.8.2.2. | | | 48) A1.604 - DETAIL #1 - SHOW THE REQUIRED ACCESSIBLE | | | LAVATORY OUTSIDE THE TOILET COMPARTMENT PER FBC-ACCESS. | | | SEC.213.3.4 AND SHOW THE REQUIRED CLEAR FLOOR SPACE. | | | 49) SHT. A1.604 - DETAIL #7 - TWO OF THE TOILET STALLS | | | SHOW A WIDTH OF 29 INCHES. THE MINIMUM WIDTH IS 30 | | | INCHES. FBC-PLUMBING SEC.405.3.1. | | | 50) SHT. A1.604 - DETAIL #7 - SHOW THE REQUIRED | | | ACCESSIBLE LAVATORY AND CLEAR FLOOR SPACE FOR A | | | LAVATORY OUTSIDE THE TOILET COMPARTMENT. FBC-ACCESS. | | | 213.3.4. SHOW THE GRAB BARS FOR THE WATER CLOSET IN THE | | | HANDICAP ACCESSIBLE COMPARTMENT. | | | 51) SHT. A1.605 - SHOW THE LOCATION OF THE COMPARTMENT | | | DOOR ON THE FLOOR PLAN. COMPLY WITH FBC-ACCESS. | | | SEC.604.8.1.2. | | | 52) SHT. A1.606 - DETAIL #13 - THE WATER CLOSET SHALL | | | BE LOCATED 18 INCHES TO THE CENTERLINE FROM THE EDGE OF | | | THE BATHTUB PER THE FHA DESIGN MANUAL. | | | 53) DIAPER CHANGING STATIONS ARE REQUIRED IN THE | | | RESTROOMS SERVING THE POOLS. IDENTIFY THIS ITEM IN THE | | | RESTROOMS SERVING THE POOLS. FBC-BUILDING SEC. | | | 454.1.6.1. | | | 54) SHT. P100 SHOWS A 12-INCH RAINWATER LINE BY COLUMN | | | #6 BUT THIS LINE IS NOT SHOWN ON SHT. C.03. CLARIFY. | | | 55) SHT. P.100 - THERE IS A 4-INCH CONDENSATE LINE BY | | | COLUMN LINE #6, A 6-INCH CONDENSATE LINE BY COLUMN LINE | | | 8, AND A 4-INCH CONDENSATE LINE BY COLUMN LINE #1 THAT | | | STATES "FOR CONTINUATION REFER TO CIVIL DRAWINGS." | | | THESE LINES ARE NOT SHOWN ON THE CIVIL DRAWINGS. REFER | | | TO THE SPECIFIC CIVIL DRAWING WHERE THESE LINES CAN BE | | | FOUND OR SUBMIT THE APPLICABLE DRAWINGS IF THEY ARE NOT | | | IN THIS SUBMITTAL. WPB AMEND. TO FBC SEC. 107.2.1. | | | 56) SHT. P100 - SHOW THE LOCATION OF THE WATER SERVICE | | | ON THIS PLAN BY COLUMN LINE #10. WPB AMEND. TO FBC SEC. | | | 107.2SUBMIT DETAILS FOR THE GAS/OIL SEPARATOR. THE | | | SEPARATOR SHALL COMPLY WITH FBC-PLUMBING SEC. 1003.4.2. | | | 57) SUBMIT DETAILS OF THE ELEVATOR SUMP/ SUMP PIPING. | | | WPB AMEND. TO FBC SEC. 107.2.1. | | | 58) SHT.P101 - THE PIPING SYSTEM IS EXTREMELY DIFFICULT | | | TO REVIEW. MOST OF THE PIPING SYSTEMS ARE NOT | | | IDENTIFIED, PIPELINES HAVE NO CONTINUATION POINTS, ETC. | | | THE SHEET IS NOT COMPLETE ENOUGH FOR REVIEW. WPB AMEND. | | | TO FBC SEC. 107.2.1. | | | 59) IDENTIFY THE STAIR NUMBERS ON THE PLUMBING SHEETS. | | | THIS WILL HELP IN DETERMINING THE LOCATION OF PIPE | | | SYSTEMS ON THE RE-REVIEW. WPB AMEND. TO FBC- SEC. | | | 107.2.1. | | | 60) ON THE MAJORITY OF THE PLUMBING DRAWINGS THERE ARE | | | SYMBOLS INDICATING PIPES GOING VERTICAL BUT THERE ARE | | | NO PIPES ATTACHED, LINES AND RISERS HAVE NO | | | IDENTIFICATION TAGS AS TO WHAT THEY ARE, PIPES GOING | | | NOWHERE, NO CONTINUATION LINES, NUMEROUS SYMBOLS | | | (CIRCLES) ON THE DRAWINGS WITH NO IDENTIFICATION, PIPE | | | LINES SO CONGESTED TOGETHER THEY ARE ILLEGIBLE, AND | | | SECTIONS OF PIPE TO NOWHERE. PLEASE CLEAN THESE | | | DRAWINGS UP SO A PROPER REVIEW CAN BE DONE. WPB AMEND. | | | TO FBC SEC. 107.2.1. | | | 61) SHT. P102C SHOWS A 1-INCH CD LINE FROM A FCU. FROM | | | WHERE? WHERE DOES IT BEGIN AND TERMINATE? INDICATE ON | | | THE PLANS. | | | 62) THE PLUMBING SHEETS SHOULD BE IDENTIFIED AS TO | | | BEING FOR THE HOTEL/ OFFICE OR THE RESIDENTIAL TOWER. | | | WPB AMEND. TO FBC SEC. 107.2.1. | | | 63) PLACE A PROPER KEY PLAN ON THE PLAN SHEETS. THE | | | SAME KEY PLAN IS ON EVERY SHEET. WPB AMEND. TO FBC SEC. | | | 107.2.1. | | | 64) SHT. P1.05 - THIS SHEET NEEDS TO BE REPLACED. AS | | | IS, IT IS NOT REVIEWABLE. | | | 65) SHT. P1.06 - THE PIPELINES AND PIPE SYMBOLS ARE SO | | | CONGESTED THIS SHEET CANNOT BE REVIEWED. | | | 66) SHT. P.223 - THERE ARE GRAY HEART SHAPED DESIGNS ON | | | THIS SHEET AND OTHER SHEETS THAT ARE MAKING THE REVIEW | | | DIFFICULT. SUBMIT REVISED SHEETS. | | | 67) SHT. P.233 - PIPELINES ARE SO CONGESTED AT THE | | | RESTROOMS THAT THE PLANS CANNOT BE REVIEWED. SUBMIT A | | | REVISE PLAN THAT IS LEGIBLE. WPB AMEND. TO FBC SEC. | | | 107.2.1. | | | 68) SHT. P.252 - THERE ARE SYMBOLS FOR PIPES GOING UP | | | AND NO RISER TAGS, NO IDENTIFICATION, LINES TERMINATING | | | NOWHERE, NO RISER TAGS. MOST OF THE SUBMITTED PLANS | | | MIRROR THIS CONDITION AND CANNOT BE PROPERLY REVIEWED. | | | 69) SHT. P.262 SHOWS A 6-INCH ROOF DRAIN FOR THE | | | COOLING TOWER BLOWDOWN. COOLING TOWER WATER IS | | | PROHIBITED FROM DISCHARGING TO THE STORMWATER SYSTEM | | | PER CITY OF WEST PALM BEACH CODE OF ORDINANCES CHAPTER | | | 90, ARTICLE III, SEC. 90-126 (B) (5). | | | 70) THE DOMESTIC WATER RISERS FOR THE RESIDENTIAL UNITS | | | SHOW INCOMPLETE SECTIONS OF PIPING GOING NOWHERE, PIPE | | | LINES ARE NOT IDENTIFIED AS TO USE, SOME PLUMBING | | | FIXTURES ARE NOT IDENTIFIED ON THE RISERS, THE WATER | | | PIPING FOR SOME OF THE FIXTURES ARE NOT SHOWN ON THE | | | WATER RISERS. THIS COMMENT IS TYPICAL FOR MOST OF THE | | | WATER RISERS. EACH RISER SHALL BE CHECKED FOR ACCURACY | | | AND REVISED AS NECESSARY. WPB AMEND. TO FBC SEC. | | | 107.2.1, 107.3.5.1.3. | | | 71) SHT. P.509 - DETAIL #1, #2, #3 SHOWS NPCW TO POOL | | | AND SPA FILL SYSTEM. WHAT IS THE SOURCE OF THE | | | NON-POTABLE COLD WATER? NON-POTABLE WATER PIPING SHALL | | | BE IDENTIFIED IN ACCORDANCE WITH 2014FBC-PLUMBING | | | SEC.608.8 ? 608.8.10. SUBMIT DETAILS FOR COMPLIANCE. | | | THIS APPLIES TO ANY OTHER PORTIONS OF THE BUILDINGS | | | THAT WILL UTILIZE NON-POTABLE WATER. | | | 72) SHT. P.701 - THE 4-INCH CW-X TO 3-INCH CW-3 OFFICE | | | TOWER MAIN SHOWS TYPICAL 1 INCH AND 2-INCH BRANCHES OFF | | | THE MAIN. WHAT DO THESE BRANCHES SUPPLY? IF THEY ARE | | | FUTURE, THERE SHALL BE A VALVE AND CAP AND DESIGNATED | | | AS FUTURE. | | | 73) SHT. P.701 - THERE SHALL BE A FULL-OPEN VALVE AT | | | THE BASE OF THE 4-INCH CW-X RISER FOR THE OFFICE TOWER | | | PER FBC-PLUMBING SEC.606.1 (4). | | | 74) SHT. P.701 - A FULL OPEN VALVE IS REQUIRED ON THE | | | TOP OF THE HOT WATER RECIRCULATION LINES PER | | | FBC-PLUMBING SEC. 606.1 (5). | | | 75) SHT. P.702 - THERE IS A 2 - INCH COLD WATER LINE | | | LABELED AS CW-1 ON LEVEL 1 THAT TERMINATES TO A TEE | | | WITH 2 BRANCHES. THERE ARE NO PIPE SIZES ON THESE | | | BRANCHES OR WHAT THEY SUPPLY. CLARIFY. | | | 76) SHT. P.702 - THERE ARE BRANCHES OFF THE WATER | | | RISERS THAT SOME HAVE NO SIZES OR THE AREA THEY SUPPLY. | | | REFER TO LEVELS 2-8. SUPPLY THE REQUIRED INFO. WPB | | | AMEND. TO FBC SEC. 107.3.5.1.3. | | | 77) SHT. P.705 & P.705A - SOME OF THE SANITARY | | | ISOMETRICS SHOW THE WATER CLOSET AS S-TRAPPED. CLARIFY. | | | 78) SHT. P.705 - DETAIL #2 - CLARIFY THE VENTING FOR | | | THE KITCHEN SINK. THE DETAIL IS CONFUSING. CLARIFY. IF | | | AN AIR ADMITTANCE VALVE IS BEING USED, IT MUST HAVE A | | | RELIEF IF THE HORIZONTAL BRANCH IS LOCATED MORE THAN | | | FOUR BRANCH INTERVALS FROM THE TOP OF THE STACK. | | | FBC-PLUMBING SEC. 918.3.1. | | | 79) SHT. P.705 - DETAIL #3 - THE WASTE STACK IS LABELED | | | AS A VENT STACK AND THE VENT STACK IS LABELED AS A | | | WASTE STACK. CLARIFY. | | | 80) SHT. P.705 - DETAIL #7 - CLEARLY SHOW THE WATER | | | CLOSET CONNECTION LAVATORY CONNECTION TO THE STACKS. | | | THERE IS PIPE MISSING ON THIS RISER. | | | 80) SHT. P.705 - DETAIL #5 - WHAT ELSE IS CONNECTED TO | | | THE SANITARY DRAIN? THERE IS NOTHING SHOWN. IS IT A | | | TUB, SHOWER? CLARIFY. | | | 81) SHT. P7.06 - DETAILS #1, #2, #3 & #5 - CLEAN UP THE | | | RISERS. THERE ARE SECTIONS OF PIPE MISSING. THE RISER | | | IS INCOMPLETE. | | | 82) THE SANITARY AND VENT RISER FOR THE HOTEL ONLY GOES | | | UP TO THE LEVEL 7 PODIUM. WHAT ABOUT THE REST OF THE | | | UPPER FLOORS? SUBMIT A COMPLETE SANITARY VENT AND RISER | | | SHEET SHOWING ALL FLOORS. WPB AMEND. TO FBC SEC. | | | 107.2.1, 107.3.5.1.3. | | | 83) SHTS. P 7.06 (DETAIL #5), P.707 (DETAILS #1-#5), | | | P.708 (DETAILS #4 & #6) P.709 ? (DETAILS #$ & #6) - | | | CLARIFY THE PIPING CONNECTIONS TO THE STACK. THE RISERS | | | ARE CONGESTED AND VERY DIFFICULT TO REVIEW. THERE ARE | | | SECTIONS OF PIPING TO NOWHERE. RISER TAGS ARE MISSING, | | | PIPELINES AND SECTIONS OF PIPE ARE MISSING, HOT AND | | | COLD-WATER LINES NOT IDENTIFIED ON THE RISERS, WATER | | | PIPING MISSING FOR THE WATER CLOSET ON DETAILS #4 & #6. | | | 84) SHT. P.707 - DETAILS #1,2,3,4 &5 - RISER TAG | | | NUMBERS ARE MISSING, IDENTIFICATION ARROWS POINTING TO | | | NOTHING, STRAY LINES ON THE RISE. CLEAN UP THE RISERS. | | | SHT. P.709 - DETAIL #4 - RISER IS INCOMPLETE. | | | 85) SHT. P701A - SUBMIT A PIPING DETAIL OF THE TMV AND | | | THE PIPING CONNECTED THERETO. THE PIPING SHALL COMPLY | | | WITH FBC-PLUMBING SEC.607.2.2. | | | 86) SHT.P.701B - THE VERTICAL 4-INCH LINE CW-X IS SHOWN | | | AS 4 INCHES ON LEVEL 18 AND ALSO SHOWN AS 3 INCHES ON | | | LEVEL 19. CLARIFY. | | | 87) SHT. P702A - THE 6-INCH LINE CW-X IS ALSO SHOWN AS | | | 3 INCH. CLARIFY, | | | 88) SHT.P703A - THE RISER TAGS REFER TO SHEETS P.502 | | | AND P.503. THE RISERS ARE NOT SHOWN ON THESE SHEETS. | | | CLARIFY. | | | 89) SHT. P.709A - RISERS SS/2, SS/3, WS/2 - THE WATER | | | CLOSET, BATHTUB AND SHOWER ARE NOT PROPERLY VENTED. | | | FBC-PLUMBING SEC. 901.2.1. | | | 90) SHT. P.710 - DETAILS #1 THROUGH #6 - THERE ARE | | | WATER LINES MISSING, HOT AND COLD-WATER LINES CALLED | | | OUT AND NOTHING IS SHOWN, FIXTURES MISSING, PARTIAL | | | SANITARY LINES SHOWN, THE RISERS ARE INCOMPLETE, | | | IDENTIFY ALL FIXTURES ON THE WATER RISERS. | | | 91) SHT. P.711 - DETAILS #1 THROUGH #5 - THERE ARE | | | WATER LINES MISSING, HOT AND COLD-WATER LINES CALLED | | | OUT AND NOTHING IS SHOWN, FIXTURES MISSING, PARTIAL | | | SANITARY LINES SHOWN, THE RISERS ARE INCOMPLETE, | | | IDENTIFY ALL FIXTURES ON THE WATER RISERS. | | | 92) SHT.P.712 - THE LAVATORY IS MISSING FROM THE | | | SANITARY RISER ON DETAIL - "C". | | | 93) SUBMIT WATER RISER DIAGRAM FOR THE TOILET ROOMS ON | | | SHT. P.712. WPB AMEND. TO FBC SEC. 107.3.5.1.3. | | | 94) SHT. P.720 - SUBMIT A COMPLETE UNDER | | | SLAB/UNDERGROUND SANITARY RISER DIAGRAM FOR REVIEW. ALL | | | THE RISERS SHALL BE IDENTIFIED BY RISER NUMBER TAGS, | | | PIPE SIZES SHALL BE SHOWN, FIXTURE UNIT LOADS, SLOPE OF | | | PIPE, REQUIRED CLEANOUTS, GREASE WASTE PIPING AND ALL | | | POINTS OF CONNECTION. THE SUBMITTED SHEET P.720 IS | | | UNACCEPTABLE, SEVERELY DEFICIENT AND CANNOT BE | | | REVIEWED. WPB AMEND. TO FBC-SEC. 107.3.5.1.3. | | | 95) SHT. P.730 - SUBMIT A COMPLETE UNDER | | | SLAB/UNDERGROUND STORM RISER DIAGRAM FOR REVIEW. ALL | | | THE RISERS SHALL BE IDENTIFIED BY RISER NUMBER TAGS, | | | PIPE SIZES SHALL BE SHOWN, REQUIRED CLEANOUTS AND ALL | | | POINTS OF CONNECTION. THE SUBMITTED SHEETT. IS | | | UNACCEPTABLE AND DEFICIENT. | | | WPB AMEND. TO FBC-SEC. 107.3.5.1.3. | | | 96) INDICATE ON THE RAINWATER PLANS THE PITCH OF THE | | | PIPE USED FOR THE ABOVEGROUND HORIZONTAL STORM DRAIN | | | PIPING AND THE RAINFALL RATE USED IN THE DESIGN OF THE | | | STORMWATER SYSTEM. FBC-PLUMBING SEC.1106.1. | | | 97) SHT. P.732 - DETAIL #2 - THE RAINWATER RISER IS | | | INCOMPLETE. THERE ARE LINES MISSING AND CONNECTION | | | POINTS MISSING. | | | 98) SHT.P.734 - THERE ARE SECTIONS OF THE RISER DIAGRAM | | | MISSING AND PIPE SIZES MISSING ON SOME OF THE LINES. | | | PIPING IS NOT IDENTIFIED, PORTIONS OF THE RISER ARE TOO | | | CONGESTED AND DIFFICULT TO REVIEW, NP CONTINUATION | | | POINTS .SUBMIT A REVISED SHEET FOR REVIEW. | | | 99) SHT. P.503A - THERE ARE ARROWS CALLING OUT VENT | | | PIPES, WASTE STACKS, AND CONDENSATE RISERS AND NOTHING | | | IS SHOWN. CLARIFY. | | | 100) SHT. P.505 - THERE IS A RISER TAG DW/P702A | | | POINTING TO A RISER LOCATION BUT THERE IS NOTHING | | | THERE. CLARIFY. | | | 101) CLEANOUTS ARE REQUIRED IN THE BASE OF EACH WASTE | | | OR SOIL STACK PER FBC-PLUMBING SEC.708.3.4. BUILDING | | | SEWERS SHALL BE PROVIDE WITH CLEANOUTS EVERY 100 FEET | | | IN ACCORDANCE WITH FBC-PLUMBING SEC.708.3.2. | | | 102) SHT. P.511 - DETAIL #1 - ONE OF THE WATER CLOSETS | | | IS MISSING ON THE SANITARY RISER. | | | 103) SHT. P.511 - ALL HOSE BIBBS SHALL BE SEPARATELY | | | VALVED PER FBC-PLUMBING SEC. 606.2 (2). | | | 104) SHT.P.511 - DETAIL #5 - A LAVATORY IN THE MEN'S | | | RESTROOM IS MISSING ON THE WATER RISER. | | | SHT. P.511 - DETAIL #6 - SHOWS VENTS ON THE FLOOR | | | DRAINS. AS DRAWN, THESE VENTS WILL BE IN THE MIDDLE OF | | | THE FLOOR OF THE RESTROOM. CLARIFY. | | | 105) SHT. P.513 - DETAIL #1 - REVISE THE DRAWING TO | | | CLEARLY SHOW THE BANK OF LAVATORIES IN EACH RESTROOM. | | | THERE IS AN OVERLAY THAT MAKES IT DIFFICULT TO REVIEW. | | | THERE IS ALSO A PARTIAL SANITARY DIAGRAM ON THE LEFT | | | SIDE OF THE PAGE THAT GOES NOWHERE. | | | 106) SHT. P.513 - THE WATER RISER FOR THE LEVEL 8 | | | RESTROOM #0822 IS OVERLAYED ONTO THE SANITARY RISER SO | | | A REVIEW COULD NOT BE DONE. SUBMIT A CLEAN PAGE FOR | | | REVIEW. | | | 107) SHT. P.513 - DETAILS #4 & #5 - THE LAYOUT OF THE | | | FIXTURES ON THE WATER RISER FOR THE LEVEL 7 TOILET | | | ROOMS #07-58/07-59 DOES NOT MATCH THE LAYOUT ON THE | | | SANITARY RISER. IT APPEARS THE WATER RISER IS FOR THE | | | LEVEL 8 TOILET ROOM. CLARIFY. | | | 108) SHT. P.514 - DETAILS #3 & #1-THE PLAN VIEW SHOWS 4 | | | WATER CLOSETS IN A ROW AND THE WATER RISER SHOWS 5. | | | CLARIFY. | | | 109) ) SHT.P.514 - DETAIL #3 - THE HANDICAP WATER | | | CLOSET IS NOT SHOWN ON THE WATER RISER. CLARIFY. | | | 110) SHT. P.514 - DETAIL #5 - SHOW THE CONTINUATION | | | POINT OF THE 6-INCH SANITARY RISER ON THE PLANS. | | | 111) SHT. P.514 -DETAIL #5 - THE FLOOR DRAINS ARE NOT | | | SHOWN ON THE SANITARY ISOMETRIC. CLARIFY. | | | 112) SHT. P.514 - THERE ARE VENTS SHOWN ON THE FLOOR | | | DRAINS. AS, DRAWN, THE VENTS WILL BE LOCATED IN THE | | | MIDDLE OF THE FLOR. CLARIFY. | | | 113) SHT. P.514 - DETAIL #3 - THERE ARE 5 WATER CLOSETS | | | IN A ROW SHOWN ON THE WATER RISER AND FOUR ON THE FLOOR | | | PLAN AND THE ACCESSIBLE WATER CLOSET IN THE MEN?S | | | RESTROOM IS NOT SHOWN ON THE WATER RISER. CLARIFY. | | | 114) SHT. P.514 - DETAIL #6 - THE LAVATORY IN THE | | | HANDICAP ACCESSIBLE TOILET COMPARTMENT IS NOT SHOWN ON | | | THE SANITARY RISER. CLARIFY. | | | 115) SHT. P.802 - SHOW PROVISIONS FOR THERMAL EXPANSION | | | FOR THE HOT WATER SYSTEM. FBC-PLUMBING SEC. 607.3. | | | 116) SHT.P8.02 - DETAIL #7 REFERS TO DETAIL #3 OF THIS | | | SAME SHEET FOR WATER HEATER INFO. DETAIL #3 IS | | | CONDENSATE DRAIN DETAIL. THE CORRECT DETAIL IS # 7. | | | REVISE THE NOTE. | | | 117) SHT. P.803 - DETAIL #1 & #2 - THE BACKFLOW | | | PREVENTION DEVICES SHALL BE LEAD FREE AND BE ON THE | | | UNIVERSITY OF SOUTHERN CALIFORNIA'S FOUNDATION FOR | | | CROSS CONNECTION CONTROL LIST OF APPROVED DEVICES. | | | 118) SHT. P8.03 - DETAIL #9 - SUBMIT DETAILS AS TO HOW | | | THE WOOD BLOCK IS BEING ATTACHED TO THE ROOF. WPB | | | AMEND. TO FBC SEC. 107.2.1. | | | 119) SHT. P.803 - DETAILS #1 & #2 - PLACE A NOTE BY THE | | | BACKFLOW DETAILS THAT A SEPARATE PERMIT IS REQUIRED FOR | | | THE BACKFLOW PREVENTERS. | | | 120) SHT. P.804 - DETAIL #3 - THE NOTES ARE BARELY | | | LEGIBLE. THERE IS AN OVERLAY OF OTHER NOTES. CLARIFY. | | | WPB AMEND. TO FBC-SEC. 107.2.1. | | | 121) SHT. P.804 - DETAIL #3 - THE OIL SEPARATOR SHALL | | | COMPLY WITH FBC-PLUMBING SEC. 1003.4.2, 1003.4.2.1. | | | 122) SHT. P.510 - DETAIL #6 - THERE IS A LAVATORY | | | MISSING FROM THE SANITARY RISER IN THE MEN-S RESTROOM | | | #0121.CLARIFY. | | | 123) SHT. P.510 - DETAIL #6 - TWO LAVATORIES ARE | | | MISSING FROM THE SANITARY RISER. CLARIFY. | | | 124) SHT. P.510 - DETAIL #3 - TOILET ROOMS 01-51 & | | | 01-52 - THE DRINKING FOUNTAIN IS MISSING ON THE | | | SANITARY RISER. CLARIFY. | | | 125) SHT. P.510 - DETAIL #6 SHOWS A FLAT, DRY VENT ON | | | THE FLOOR DRAIN. COMPLY WITH FBC-PLUMBING SEC.905.3. | | | 126) SUBMIT MANUFACTURER'S SPECIFICATIONS AND | | | INSTALLATION INSTRUCTIONS FOR THE MEMBRANE SYSTEM FOR | | | THE SHOWERS. THE SYSTEM BEING USED SHALL COMPLY WITH | | | THE APPLICABLE CODE SECTIONS IN THE FBC-PLUMBING CODE | | | SECS.417.5, 417.5.2, 417.5.2.5, 417.5.2.6. | | | 127) THE PLUMBING SPECIFICATIONS SECTION 22 1323 - PART | | | 2 - SECTION 2.01 (GREASE INTERCEPTOR) :TAG # GT-1 - | | | SECTION C -ACCESSORIES: CALLS OUT A 4-INCH INFLUENT AND | | | EFFLUENT TWO-WAY CLEANOUT, BUT ALSO CALLS OUT A 6-INCH | | | SAMPLING PORT. THIS WOULD CREATE AN OBSTRUCTION TO FLOW | | | AND VIOLATES FBC-PLUMBING SEC.706.2. THIS SECTION ALSO | | | CALLS OUT A SCHIER INTERCEPTOR WITH 6-INCH INLET AND | | | OUTLET. CLARIFY. | | | 128) SHOW THE CAPACITY OF THE GREASE INTERCEPTORS ON | | | THE CIVIL AND PLUMBING SHEETS. WPB AMEND TO FBC SEC. | | | 107.2.1. | | | 129) SHT. P.802 - DETAIL #4 - A FULL OPEN VALVE SHALL | | | BE INSTALLED ON THE DISCHARGE SIDE OF THE CHECK VALVE | | | AND SHALL BE INSTALLED IN THE PUMP / EJECTOR DISCHARGE | | | PIPING BETWEEN THE PUMP OR EJECTOR AND THE GRAVITY | | | DRAINAGE SYSTEM PER FBC-PLUMBING 712.2. | | | 130)) SHT. P.802 - DETAIL #8 SHOWS A 6-INCH TRAP | | | DISCHARGING INTO A 4-INCH LINE. CLARIFY. | | | 131) SHT.P.803 - DETAILS #1 & #2 - THE BACKFLOW DEVICES | | | SHALL BE LEAD FREE AND THE BACKFLOW DEVICES MUST BE ON | | | THE UNIVERSITY OF SOUTHERN CALIFORNIA'S (USC) LIST OF | | | APPROVED DEVICES. A SEPARATE PERMIT IS REQUIRED FOR THE | | | BACKFLOW DEVICES. | | | 132) RIGID SUPPORT SWAY BRACING SHALL BE PROVIDED AT | | | CHANGES IN DIRECTION GREATER THAN 45 DEGREES FOR PIPE | | | SIZES 4 INCHES AND LARGER PER FBC-PLUMBING SEC.308.6. | | | SUBMIT DETAILS FOR THE BRACING. | | | 133) FOR PIPE SIZES GREATER THAN 4 INCHES (102 MM), | | | RESTRAINTS SHALL BE PROVIDED FOR DRAIN PIPES AT ALL | | | CHANGES IN DIRECTION AND AT ALL CHANGES IN DIAMETER | | | GREATER THAN TWO PIPE SIZES. BRACES, BLOCKS, RODDING | | | AND OTHER SUITABLE METHODS AS SPECIFIED BY THE COUPLING | | | MANUFACTURER SHALL BE UTILIZED. | | | 134) THE PLUMBING SHEETS DO NOT BEAR THE DIGITAL | | | SIGNATURE AND SEAL OF THE DESIGN PROFESSIONAL IN | | | RESPONSIBLE CHARGE PER WPB AMEND. TO FBC SEC.107.3.4, | | | FL. ADMIN. CODE RULE 61G15-23.004, 61G15-23.005. | | | 135) THE SUPPLY LINES AND FITTINGS FOR THE RESIDENTIAL | | | DISHWASHERS SHALL BE INSTALLED SO AS TO PREVENT | | | BACKFLOW. PLUMBING FIXTURE FITTINGS SHALL PROVIDE | | | BACKFLOW PROTECTION IN ACCORDANCE WITH ASME | | | A112.18.1/CSA B125.1.FBC-PLUMBING SEC. 608.2. | | | 136) SHT. P.803 - DETAIL #3 SHOWS JOINTS UNDER THE SLAB | | | - PLUMBING SPECIFICATIONS SEC.221110 - PART 2 - 2.02 | | | STATES THAT "ENTRANCE PIPING TO THE BUILDING TO | | | TERMINATE ABOVE GRADE." THE DETAIL ON P.803 SHOWS | | | FLANGED FITTINGS UNDER THE SLAB. CLARIFY. IF THIS | | | PIPING ARRANGEMENT IS TO REMAIN, SUBMIT DETAILS ON | | | FITTING RESTRAINTS AND THRUST BLOCK INFORMATION. WPB | | | AMEND. TO FBC SEC. 107.2.1, 107.3.5.1.3. | | | | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | PLUMBING PLAN REVIEW | | | 561-805-6692 | | | [email protected] | | | | | | | | | | | | | | | |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2019-04-09 |
|
|
Cont ID |
|
| Sent By |
gjohnson |
Date |
2019-04-09 |
Time |
10:07 |
Rev Time |
0.00 |
| Received By |
gjohnson |
Date |
2019-03-28 |
Time |
07:07 |
Sent To |
|
|
| Notes |
| 2019-04-09 10:07:16 | 1ST REVIEW: 18100540 | | | 2017 FLORIDA BUILDING CODE 6TH EDITION | | | 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION | | | 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH | | | EDITION | | | 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION | | | 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION | | | 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH | | | EDITION | | | 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH | | | EDITION | | | | | | PLUMBING COMMENTS: DUE TO THE FACT THAT THESE PLANS ARE | | | INCOMPLETE I AM NOT ABLE TO DETERMINE CODE COMPLIANCE | | | AT THIS TIME. I HAVE REVIEWED THE INFORMATION PROVIDED | | | AND COMMENTED, WHEN A COMPLETE SET OF DESIGN DOCUMENTS | | | ARE PROVIDE PLEASE ADDRESS THESE COMMENTS.I WILL THEN | | | BE ABLE TO COMPLETE A MORE COMPREHENSIVE REVIEW. | | | | | | 1. PLEASE INDICATE ON THE PLAN WHICH DESIGN DOCUMENT | | | WAS USED TO DETERMINE COMPLIANCE TO THE FHA SUCH AS THE | | | FHA DESIGN MANUAL OR THE FHA GUIDE LINES FOUND IN THE | | | BACK OF THE FBC ACCESSIBILITY BOOK. PER WPB AMEND TO | | | FBC 107.2.1 | | | 2. PLEASE CLARIFY ON THE PLAN THAT THE RESIDENTIAL | | | UNITS AND AND COMMON AREAS FOR THOSE UNITS SHALL COMPLY | | | WITH FHA AND ANSI A117.1-1986. | | | 3. PLEASE CLARIFY ON THE PLAN THAT ALL OTHER | | | OCCUPANCY'S OTHER THAN THE RESIDENTIAL UNITS SHALL | | | COMPLY WITH THE 2017 6TH EDITION FLORIDA BUILDING CODE | | | ACCESSIBILITY NOT ADA | | | 4. PLEASE PROVIDE A MATRIX CHART FOR THE RESIDENTIAL | | | UNITS SHOWING WHICH BATHROOMS ARE COMPLYING WITH FHA | | | AND WHAT DESIGN SPEC IS BEING USED. PER WPB AMENDS TO | | | FBC 107.2.1 | | | 5. PLEASE PROVIDE A PLUMBING FIXTURE COUNT BREAK DOWN | | | FOR THE BUSINESS, ASSEMBLY AND MERCANTILE OCCUPANCY'S | | | PER FBC PL TABLE 403.1 | | | 6. PROVIDE BREAK DOWN OF ACCESSIBLE AND NON ACCESSIBLE | | | ROOMS FOR THE HOTEL. PER WPB AMENDS TO FBC 107.2.1 | | | 7. SHT. A0.202 SOME OF THE DETAILS ARE CONFUSING THEY | | | ARE COMBINING FHA WITH ADA THESE CODES DO NOT MATCH UP | | | AND THE PROJECT SHALL COMPLY WIH THE FBC ACC NOT ADA | | | PLEASE CLARIFY. PER WPB AMENDS TO FBC 107.2.1 | | | 8. THE MENS BATHROOM SHALL HAVE URINALS PLEASE PROVIDE | | | FIXTURE BREAKDOWN FOR ALL THE POOLS COMPLYING WITH FBC | | | PL TABLE 403.6 | | | 9. SHT. A1.505 SUITE 1.2 PROVIDE DIMENSIONS OF THE | | | SHOWER. PER WPB AMENDS TO FBC 107.2.1 | | | 10.SHT. A1.510 - A1.528 THE FHA SPEC DESIGNATION IS | | | MISSING FROM SOME OF THE BATHROOMS EACH RESIDENTIAL | | | UNIT SHALL BE DESIGNATED SPEC A OR B FOR THE BATHROOMS. | | | PER FHA | | | 11.SHT. A1.510 - A1.528 SOME OF THE CLEAR FLOOR SPACE | | | AND LOCATION OF GRAB BAR BACKING LOCATION ARE MISSING | | | THESE SHALL BE SHOWN ON ALL ENLARGED FLOOR PLANS WHERE | | | THEY ARE REQUIRED. PER WPB AMENDS TO FBC 107.2.1 | | | 12. SHT. A1.527 + A1.600 DETAIL 13 THE WING WALL NEXT | | | TO THE TOILET SHALL NOT EXTEND MORE THAN 24" FROM REAR | | | WALL THIS REQUIREMENT IS FOR ALL FHA COMPLIANT | | | BATHROOMS. PER FHADM REQ. #7 PG 7.43 | | | 13. SHOW THE DEPTH OF THE LAVATORY'S IN ALL FHA | | | COMPLIANT BATHROOMS. PER FHADM REQ. #7 PG 7.43 | | | 14. SHT. A1.600 DETAIL #11 IS SHOW MULTIPLE SHOWER | | | LAYOUTS ON TOP OF EACH OTHER PLEASE CLARIFY AND SHOW | | | DIMENSIONS. PER WPB AMEND TO FBC 107.2.1 | | | 15. SHT. A1.600 - A1.602 SHOW ALL DIMENSIONS OF THE | | | BATHROOMS. PER WPB AMEND TO FBC 107.2.1 | | | 16. SHT. A1.524 A1.600 DETAIL #7 SHOW CLEAR FLOOR | | | SPACE. PER WPB AMEND TO FBC 107.2.1 | | | 17. SHT. A1.600+601 SOME OF THE DETAILS ARE SHOW DOUBLE | | | FIXTURE OVERLAPPING PLEASE CLARIFY. | | | PER WPB AMEND TO FBC 107.2.1 | | | 18. SHT A1.521 THE CLEAR FLOOR SPACE AT THE KITCHEN IS | | | OVERLAPPING THE SINK AND CABINETS PLEASE CLARIFY. PER | | | WPB AMEND TO FBC 107.2.1 | | | 19. SHT A1.602 SHOW ALL CLEAR FLOOR SPACE WITH | | | DIMENSIONS FOR ACCESSIBLE TOILET, LAVATORY'S, URINALS | | | AND SHOWER AND WATER FOUNTAINS. PER WPB AMEND TO FBC | | | 107.2.1 AND FBC ACC CH6 | | | 20. SHT A1.602 SHOW DIMENSIONS FOR THE STALL AND | | | SHOWER. PER WPB AMEND TO FBC 107.2.1 | | | 21. SHT. A1.602 DETAIL #2 IN THE ACCESSIBLE STALL THE | | | SHOWER IS ENCROACHING INTO THE CLEAR FLOOR SPACE OF THE | | | TOILET SPACE IT SHALL COMPLY WITH FBC ACC 604.3.1 | | | 22. SHT A1.602 THE TRANSFER SHOWER SHALL HAVE A SEAT. | | | PER FBC ACC 608.4 | | | 23. IN THE PLUMBING FIXTURE BREAKDOWN PLEASE INDICATE | | | COMPLIANCE WITH POTTY PARITY. PER FBC ACC 403.1.3 | | | 24. SHT. A1.602 PLEASE LABEL ALL ENLARGED BATHROOM | | | GROUPS WITH THE ROOM NUMBER AND MENS OR WOMENS. PER WPB | | | AMEND TO FBC 107.2.1 | | | 25. PROVIDE ENLARGED BATHROOM DETAILS FOR ALL COMMON | | | AREA IN ALL THE DIFFERENT OCCUPANCY I FOUND THESE | | | MISSING, 07-55, 07-27, 07-61, 07-60, 08-28, 08-21, | | | 08-38, 08-39, 08-21. PER WPB AMEND TO FBC 107.2.1 | | | 26. PROVIDE DIMENSIONS FOR THE ROOF SCUPPERS MAIN AND | | | EMERGENCY SCUPPERS. PER WPB AMEND TO FBC 107.2.1 | | | 27. PROVIDE MANUFACTURE SPECIFICATIONS AND INSTILLATION | | | GUIDES FOR THE LIQUID APPLIED WATERPROOF MEMBRANE FOR | | | THE SHOWER PANS IT SHALL COMPLY WITH FBC PL 417.5.2.6 | | | AND ANSI A118.10 | | | 28. SHT. A7.502 ON THE DEPRESSION DETAIL THE HYDRO BAN | | | SHALL BE PITCHED TO TH SHOWER DRAIN FLANGE UNDER THE | | | MORTAR BED AND SEAL TO THE BOTTOM FLANGE UNDER THE | | | CLAMPING RING. PER FBC PL 417.5.2 | | | 29. IN THE RESIDENTIAL COMMON AREA LOUNGE AND SCREENING | | | ROOM AND RESIDENTIAL POOL IT DOES NOT APPEAR TO BE ANY | | | COMMON BATHROOMS PLEASE CLARIFY. PER WPB AMEND TO FBC | | | 107.2.1 | | | 30. PLEASE INDICATE ON THE PLAN ALL WORK SHALL COMPLY | | | WITH 2017 6TH EDITION FLORIDA BUILDING CODE , PLUMBING, | | | FUEL GAS, MECHANICAL, ACCESSIBILITY AND FHA | | | 31. SHT P-100 WHAT IS THE 2'X 2' SAND PIT LOCATED NEAR | | | GRID LINES B+8. PER WPB AMEND TO FBC 107.2.1 | | | 32. SHT. P'S LABEL AND TAG ALL RISERS ON ALL FLOOR | | | PLANS. PER WPB AMEND TO FBC 107.3.5.1.3(13) | | | 33. ON SANITARY FLOOR PLAN SHOW ALL COMMON AREA | | | BATHROOMS OR NOTE WHERE ENLARGED PLAN CAN BE FOUND. PER | | | WPB AMEND TO FBC 107.2.1 | | | 34. PLEASE IDENTIFY WHAT THE IWS IS SERVING. PER WPB | | | AMEND TO FBC 107.2.1 | | | 35. SHT P 107B SHOWS AN AAV THESE TYPE OF VENTS ARE | | | ONLY ALLOWED TO SERVE FIXTURES THAT ARE NO MORE THAN 4 | | | BRANCH INTERVALS FROM THE TOP OF THE VENT STACK UNLESS | | | A RELIEF VENT IS PROVIDED PLEASE CLARIFY . PER FBC PL | | | 918.3.1 | | | 36. SHT. P-109 IF PONDING CAN OCCUR ON THIS LEVEL | | | OVERFLOW DRAINS WILL BE REQUIRED FOR THE PD. PER FBC PL | | | 1108.1 | | | 37. PLEASE PROVIDE MANUFACTURE SPECIFICATIONS FOR ALL | | | PUMPS AND VALVES INCLUDING MIXING VALVE AND PRESSURE | | | REDUCING.PER WPB AMEND TO FBC 107.2.1 | | | 38. PROVIDE COMPLETE COLLECTION ISOMETRIC DRAWING FOR | | | ALL UNDER GROUND PLUMBING PLEASE SEPARATE EACH | | | DIFFERENT SYSTEM FOR CLARITY AND INCLUDE SIZING DFU | | | LOADS SGFT DRAINED. WPB AMEND TO FBC 107.3.5.1.3(13) | | | 39. A WYE STAINER IS REQUIRED AT ALL PRESSURE REDUCING | | | VALVES PLEASE SHOW ON ALL DETAILS AND ISOMETRIC | | | DRAWING. PER FBC PL 604.8 | | | 40. PLACE NOTE ON PLAN SHUT OFF VALVES FOR STACKABLE | | | WASHING MACHINES IN THE RESIDENCIAL UNITS SHALL BE | | | ACCESSIBLE. PER FBC PL 606.3 | | | 41. IN PUBLIC BATHROOMS TEMPERED WATER SHALL BE | | | DELIVERED FROM LAVATORIES AND GROUP WASH FIXTURES | | | LOCATED IN PUBLIC TOILET FACILITIES PROVIDED FOR | | | CUSTOMERS, PATRONS AND VISITORS. TEMPERED WATER SHALL | | | BE DELIVERED THROUGH AN APPROVED WATER-TEMPERATURE | | | LIMITING DEVICE THAT CONFORMS TO ASSE 1070 OR CSA | | | B125.3. PER FBC PL 416.5 | | | 42. THE ENLARGED PLUMBING FLOOR PLANS APPEAR TO HAVE | | | TAGS ON THE STACKS THAT ARE INCOMPLETE PLEASE MAKE SURE | | | ALL STACKS ARE LABBELED AND TAGED TO MATHCH THE | | | ISOMETRIC DRAWING AND FULL FLOOR PLANS. PER WPB AMEND | | | TO FBC 107.2.1 | | | 43. SHT. P-701 I CAN NOT DETERMINE CODE COMPLIANCE ON | | | THIS PAGE PLEASE SPLIT RISER AND ORIENT THE DRAWING SO | | | THE BOTTOM OF THE BUILDING MATCHES UP TO THE BOTTOM OF | | | THE PLAN SHEET.PER WPB AMEND TO FBC 107.2.1 | | | 44. SHT. P-701 PLEASE LABEL THE UNIT BRANCHES .PER WPB | | | AMEND TO FBC 107.2.1 | | | 45. PROVIDE COMPLETE STORM ISOMETRIC WITH SQFT AND | | | SLOPE OF THE PIPE. PER WPB AMEND TO FBC 107.3.5.1.3(13) | | | 46. SHT. P-703 ONLY 1 FIXTURE IS ALLOWED UPSTREAM OF | | | THE WET VENT ON THE BATHROOM GROUP SS/2 . PER FBC PL | | | 912.1 | | | | | | | | | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT | | | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID | | | THE PREVIOUSLY REVIEWED SHEETS. | | | | | | GEORGE JOHNSON | | | PLUMBING PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | 561-805-6711 | | | [email protected] |
|
|
| Review Stop |
P-GREASE |
GREASE INTERCEPTOR/TRAP REVIEW |
| Rev No |
5 |
Status |
N |
Date |
2021-08-16 |
|
|
Cont ID |
|
| Sent By |
lcrespo |
Date |
2021-08-16 |
Time |
12:03 |
Rev Time |
0.00 |
| Received By |
lcrespo |
Date |
2021-08-16 |
Time |
12:03 |
Sent To |
|
|
| Notes |
| 2021-08-16 12:03:30 | NOTE: A SEPARATE PERMIT APPLICATION AND REVIEW ARE | | | REQUIRED FROM ENGINEERING FOR THE GREASE INTERCEPTOR. |
|
|
| Review Stop |
P-GREASE |
GREASE INTERCEPTOR/TRAP REVIEW |
| Rev No |
4 |
Status |
F |
Date |
2021-06-21 |
|
|
Cont ID |
|
| Sent By |
lcrespo |
Date |
2021-06-21 |
Time |
15:54 |
Rev Time |
0.00 |
| Received By |
lcrespo |
Date |
2021-06-14 |
Time |
14:33 |
Sent To |
|
|
| Notes |
| 2021-06-21 15:54:54 | ON SHEET 804, DETAIL #2 OF NOTE TWO HAS SPECIFIED A | | | SCHIER 250 GALLONS. WHY IS THIS SPECIFIED? HOW DID YOU | | | DETERMINE THE USAGE OF THE RESTAURANT UNITS WITH | | | RESPECT TO THE RESTAURANT CAPACITY? HOW IS THIS | | | INFORMATION PROVIDED? IF SCHIER PROVIDED THESE | | | CALCULATIONS OR WILL ASSIST IN SIZING, PLEASE NOTE IN | | | DETAIL TWO HOW THE ENGINEERED SYSTEM IS TO COMPLY. | | | PLEASE PUT A NOTE RESPONSE OF P100 ON P 804 DETAIL 2. I | | | SPOKE TO SCHIER'S REP, AND THEY ARE WILLING TO HELP IN | | | ALL CALCULATION ASSISTANCE REQUIRED; IF HE NEEDS TO | | | CONTACT YOU, MAY LEE @ 561 632-3123, FYI. |
|
|
| Review Stop |
P-GREASE |
GREASE INTERCEPTOR/TRAP REVIEW |
| Rev No |
3 |
Status |
F |
Date |
2021-02-20 |
|
|
Cont ID |
|
| Sent By |
tklarge |
Date |
2021-02-19 |
Time |
09:51 |
Rev Time |
0.00 |
| Received By |
tklarge |
Date |
2021-02-19 |
Time |
09:48 |
Sent To |
|
|
| Notes |
| 2021-02-19 09:54:50 | 1) SUBMIT FACTORY SIZING CALCULATIONS FROM SCHIER FOR | | | THIS INTERCEPTOR PER FBC-PLUMBING SEC. 1003.2. 2ND | | | REQUEST. | | | | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | PLUMBING PLAN REVIEW | | | 561-805-6692 | | | [email protected] | | | |
|
|
| Review Stop |
P-GREASE |
GREASE INTERCEPTOR/TRAP REVIEW |
| Rev No |
2 |
Status |
F |
Date |
2020-03-28 |
|
|
Cont ID |
|
| Sent By |
tklarge |
Date |
2020-03-28 |
Time |
10:05 |
Rev Time |
0.00 |
| Received By |
tklarge |
Date |
2020-03-28 |
Time |
05:00 |
Sent To |
|
|
| Notes |
| 2020-03-28 05:16:23 | 1) SHOW THE CAPACITY OF THE GREASE INTERCEPTORS ON THE | | | CIVIL AND PLUMBING SHEETS. WPB AMEND TO FBC SEC. | | | 107.2.1. | | | 2) THE PLUMBING SPECIFICATIONS SECTION 22 1323 - PART 2 | | | - SECTION 2.01 (GREASE INTERCEPTOR) : | | | TAG # GT-1 - SECTION C -ACCESSORIES: CALLS OUT A 4-INCH | | | INFLUENT AND EFFLUENT TWO-WAY CLEANOUT, BUT ALSO CALLS | | | OUT A 6-INCH SAMPLING PORT. THIS WOULD CREATE AN | | | OBSTRUCTION TO FLOW AND VIOLATES FBC-PLUMBING | | | SEC.706.2. THIS SECTION ALSO CALLS OUT A SCHIER | | | INTERCEPTOR WITH 6-INCH INLET AND OUTLET. CLARIFY. | | | 3) THE INSTALLATION GUIDE/MANUAL FOR THE GREASE | | | INTERCEPTORS SHALL BE ONSITE FOR INSPECTION. | | | FBC-PLUMBING SEC. 1003.3.4. FACTORY SIZING CALCULATIONS | | | SHALL BE SUBMITTED FOR REVIEW. FBC-PLUMBING SEC.1003.2, | | | 1003.3.4. | | | 4) A SEPARATE PERMIT IS REQUIRED FOR THE GREASE | | | INTERCEPTORS. PLACE A NOTE ON DRAWING C.06 AND THE | | | PLUMBING DRAWINGS. | | | | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | PLUMBING PLAN REVIEW | | | 561-805-6692 | | | [email protected] | | | | | | |
|
|
| Review Stop |
P-GREASE |
GREASE INTERCEPTOR/TRAP REVIEW |
| Rev No |
1 |
Status |
F |
Date |
2019-04-09 |
|
|
Cont ID |
|
| Sent By |
gjohnson |
Date |
2019-04-09 |
Time |
10:07 |
Rev Time |
0.00 |
| Received By |
gjohnson |
Date |
2019-04-09 |
Time |
10:07 |
Sent To |
|
|
| Notes |
| 2019-04-09 10:08:18 | 1ST REVIEW: 18100540 | | | 2017 FLORIDA BUILDING CODE 6TH EDITION | | | 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION | | | 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH | | | EDITION | | | 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION | | | 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION | | | 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH | | | EDITION | | | 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH | | | EDITION | | | | | | GREASE INTERCEPTOR COMMENTS: | | | | | | 1. PROVIDE MANUFACTURE SIZING CALCULATION FOR THE | | | GREASE INTERCEPTOR AND THE OIL/SAND INTERCEPTOR. PER | | | FBC PL 1003.2 /1003.4.2.2 | | | 2. WHAT IS DISCHARGED THROUGH GARAGE WASTE SYSTEM IF IT | | | IS STORM WATER IT SHALL DISCHARGE TO THE STORM SYSTEM | | | NOT THE SANITARY SYSTEM. PER CITY OF WEST PALM BEACH | | | CODE OF ORDINANCE SEC. 90-126(5) | | | 3. SHT P-100 WHAT IS THE 2'X 2' SAND PIT LOCATED NEAR | | | GRID LINES B+8. PER WPB AMEND TO FBC 107.2.1 | | | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT | | | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID | | | THE PREVIOUSLY REVIEWED SHEETS. | | | | | | GEORGE JOHNSON | | | PLUMBING PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | 561-805-6711 | | | [email protected] |
|
|
| Review Stop |
P-IRRIGATE |
IRRIGATION REVIEW |
| Rev No |
3 |
Status |
P |
Date |
2021-02-19 |
|
|
Cont ID |
|
| Sent By |
tklarge |
Date |
2021-02-19 |
Time |
09:52 |
Rev Time |
0.00 |
| Received By |
tklarge |
Date |
2021-02-19 |
Time |
09:52 |
Sent To |
|
|
| Notes |
| 2021-02-19 09:55:52 | 1) A SEPARATE PERMIT IS REQUIRED FOR THE IRRIGATION | | | SYSTEM. | | | 20 A SEPARATE PERMIT IS REQUIRED FOR THE BACKFLOW | | | PREVENTER. |
|
|
| Review Stop |
P-IRRIGATE |
IRRIGATION REVIEW |
| Rev No |
2 |
Status |
F |
Date |
2020-03-28 |
|
|
Cont ID |
|
| Sent By |
tklarge |
Date |
2020-03-28 |
Time |
04:58 |
Rev Time |
0.00 |
| Received By |
tklarge |
Date |
2020-03-28 |
Time |
04:44 |
Sent To |
|
|
| Notes |
| 2020-03-28 04:45:45 | 1) SHT. LIR5-000 SHOWS A PRESSURE VACUUM BREAKER TYPE | | | BACKFLOW PREVENTION DEVICE FOR THE IRRIGATION SYSTEM. | | | THIS TYPE OF DEVICE IS NOT APPROVED TO BE INSTALLED ON | | | A COMMERCIAL IRRIGATION SYSTEM PER THE CITY OF WEST | | | PALM BEACH CROSS CONNECTION CONTROL MANUAL. A REDUCED | | | PRESSURE ZONE VALVE IS THE MINIMUM REQUIRED PROTECTION | | | ON THIS SYSTEM. A SEPARATE PERMIT IS REQUIRED FOR THE | | | INSTALLATION OF THIS DEVICE. THE DEVICE MUST BE LEAD | | | FREE AND BE LISTED ON THE UNIVERSITY OF SOUTHERN | | | CALIFORNIA'S FOUNDATION FOR CROSS CONNECTION CONTROL | | | LIST OF APPROVED DEVICES. THE DEVICE MUST BE TESTED AND | | | CERTIFIED BY THE CITY OF WEST PALM BEACH UTILITIES | | | DEPARTMENT WHEN IT IS INSTALLED PER THE CITY OF WEST | | | PALM BEACH CROSS CONNECTION CONTROL MANUAL. | | | | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | PLUMBING PLAN REVIEW | | | 561-805-6692 | | | [email protected] | | | | | | | | | |
|
|
| Review Stop |
P-IRRIGATE |
IRRIGATION REVIEW |
| Rev No |
1 |
Status |
F |
Date |
2019-04-08 |
|
|
Cont ID |
|
| Sent By |
gjohnson |
Date |
2019-04-08 |
Time |
08:26 |
Rev Time |
0.00 |
| Received By |
gjohnson |
Date |
2019-04-08 |
Time |
08:26 |
Sent To |
|
|
| Notes |
| 2019-04-08 08:50:25 | 1ST REVIEW: | | | 2017 FLORIDA BUILDING CODE 6TH EDITION | | | 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION | | | 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH | | | EDITION | | | 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION | | | 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION | | | 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH | | | EDITION | | | 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH | | | EDITION | | | | | | IRRIGATION COMMENTS: | | | | | | 1. SHT. LIRI - 100 SHOW LOCATION OF RAIN SENSOR . PER | | | WPB AMEND TO FBC 107.2.1 | | | | | | 2. ALL THE IRRIGATION PAGES SHALL BE DIGITALLY SIGNED | | | AND SEALED BY DESIGN PROFESSIONAL RESPONSIBLE FOR | | | SYSTEM DESIGN. PER FAC 61G15-23.003 OR FAC 61G1-16.005 | | | | | | | | | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT | | | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID | | | THE PREVIOUSLY REVIEWED SHEETS. | | | | | | GEORGE JOHNSON | | | PLUMBING PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | 561-805-6711 | | | [email protected] | | | |
|
|
| Review Stop |
R |
ROOF PLAN REVIEW |
| Rev No |
4 |
Status |
N |
Date |
2021-06-18 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2021-06-18 |
Time |
10:03 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2021-06-18 |
Time |
10:03 |
Sent To |
|
|
| Notes |
| 2021-06-18 10:06:00 | ROOFING PRODUCT MATERIALS HAVE BEEN DEFERRED. SEE NOTES | | | ON PLAN SHEET A0.001. |
|
|
| Review Stop |
R |
ROOF PLAN REVIEW |
| Rev No |
3 |
Status |
F |
Date |
2021-03-01 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2021-03-01 |
Time |
11:24 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2021-03-01 |
Time |
11:24 |
Sent To |
|
|
| Notes |
| 2021-03-01 11:10:09 | PLAN | | | REVIEW COMMENTS | | | | | | 3RD REVIEW: FBC FIFTH EDITION (2014) | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | ROOFING MATERIALS DENIED BY BUILDING | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | | | 1) THE ROOFING PRODUCT APPROVALS ARE REQUIRED TO BE | | | REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF | | | RECORD FOR THE PROJECT. FBC AMENDMENTS 107.3.4 | | | | | | 2) THERE ARE MUTIPLE SYSTEMS WITH DIFFERENT DESIGN | | | PRESSURES LISTED IN THE PRODUCT APPROVALS. HI-LIGHT OR | | | CIRCLE THE SPECIFIC MEMBRANE TYPE, SYSTEM TYPE AND | | | MAXIMUM DESIGN PRESSURES THAT APPLY IN THE PRODUCT | | | APPROVALS. FBC AMENDMENTS 107.2.1 | | | | | | 3) SEE BUILDING REVIEW COMMENT NUMBER 22. | | | | | | 4) SUBMIT PRODUCT APPROVALS FOR ROOF INSULATION. FBC | | | AMENDMENTS 107.3.4 | | | | | | 5) ROOFING PRODUCT APPROVALS SUBMITTED. | | | NOA NO. 15-0707.08 | | | NOA NO. 15-0709.14 | | | NOA NO. 16-0203.02 | | | NOA NO.16-0229.06 | | | NOA NO.17-0222.10 |
|
|
| Review Stop |
R |
ROOF PLAN REVIEW |
| Rev No |
2 |
Status |
F |
Date |
2020-03-06 |
|
|
Cont ID |
|
| Sent By |
dbattles |
Date |
2020-03-06 |
Time |
12:52 |
Rev Time |
0.00 |
| Received By |
dbattles |
Date |
2020-02-18 |
Time |
07:38 |
Sent To |
|
|
| Notes |
| 2020-03-06 12:53:26 | SEE BUILDING COMMENT #22 | | | | | | DYLAN BATTLES | | | BUILDING PLANS EXAMINER PX4191 | | | [email protected] | | | 561-805-6718 | | | |
|
|
| Review Stop |
R |
ROOF PLAN REVIEW |
| Rev No |
1 |
Status |
F |
Date |
2019-04-18 |
|
|
Cont ID |
|
| Sent By |
dbattles |
Date |
2019-04-18 |
Time |
15:08 |
Rev Time |
0.00 |
| Received By |
dbattles |
Date |
2019-04-08 |
Time |
13:37 |
Sent To |
|
|
| Notes |
| 2019-04-18 15:09:10 | SEE BUILDING COMMENTS. | | | PRODUCT APPROVALS WILL BE REVIEWED ON SECOND REVIEW, | | | UNLESS DEFERRED SUBMITTAL IS REQUESTED. |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
6 |
Status |
P |
Date |
2021-09-08 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2021-09-08 |
Time |
11:41 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2021-09-08 |
Time |
11:41 |
Sent To |
|
|
| Notes |
| 2021-09-08 11:42:23 | SIGNATURE ERRORS IN BLUEBEAM DO NOT OCCUR IN ADOBE. | | | PROVISO: ARCHITECT TO SEND DIGITALLY SIGNED PAGE VIA | | | EMAIL | | | |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
5 |
Status |
F |
Date |
2021-09-03 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2021-09-03 |
Time |
17:24 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2021-09-03 |
Time |
17:06 |
Sent To |
|
|
| Notes |
| 2021-09-03 17:23:48 | PLEASE CHECK FOR DIGITAL SIGNATURES ON ALL SUBMITEED | | | PLAN SHEETS. THERE ARE STILL ISSUES WITH SIGNATURES. | | | SHEET A1.272A ON PAGE 03.316 IS NOT SIGNED AND SEALED. | | | SEALS ON STRUCTURAL DRAWINGS SHOW AS REVOKED, FOR | | | EXAMPLE SEE PAGE 05.002-S1.002. THE CIVIL ENGINEER | | | RICHARD V. REIKENIS, IS SELF-CERTIFYING HIS SIGNATURE. | | | |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
4 |
Status |
F |
Date |
2021-08-27 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2021-08-27 |
Time |
08:52 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2021-08-27 |
Time |
08:52 |
Sent To |
|
|
| Notes |
| 2021-06-21 12:00:46 | SHEET A1.316 ON PAGE 03.316 IS NOT SIGNED AND SEALED. | | | SEALS ON STRUCTURAL DRAWINGS SHOW AS REVOKED, FOR | | | EXAMPLE SEE PAGE 05.002-S1.002. THE CIVIL ENGINEER | | | RICHARD V. REIKENIS, IS SELF-CERTIFYING HIS SIGNATURE. | | | STILL NEED TO LIST AND ORDER ALL SHEETS IN THE INDEX. | | | RM | | 2021-06-10 13:42:27 | MECHANICAL DRAWINGS SIGNATURE REVIEW- APPROVED. ME | | | 08/16/2021 MECHANICAL REVISED DRAWINGS SIGNATURE REVIEW | | | AAAPRROVED ME |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
3 |
Status |
F |
Date |
2021-03-01 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2021-03-01 |
Time |
07:31 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2021-03-01 |
Time |
07:31 |
Sent To |
|
|
| Notes |
| 2021-03-01 07:56:41 | SAMANTHA HILL | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6724 | | | | | | 1. PRIOR TO RESUBMITTING, PLEASE CONFIRM THAT ALL PAGES | | | ARE IN THE ORDER ON THE INDEX PAGE, PROPERLY VERSIONED | | | (NO DUPLICATES), ESPECIALLY PLUMBING. | | | | | | 2. NO ACTION REQUIRED - P, E, T, MP, M PAGES UPLOADED | | | 12/21/20 OK (SPOT CHECKED) | | | | | | 3. FA PAGES UPLOADED 12/21 LACK A DIGITAL SIGNATURE; | | | FOR INSTANCE FP.201A, FA208B, | | | | | | 4. ARCH PAGES - PAGE 03.317 - A1.501A, 03.310 - A10.227 | | | ARE NOT DIGITALLY SIGNED. OTHER PAGES UPLOADED 12/21 | | | ARE DIGITALLY SIGNED. CHECK ALL. | | | | | | 5. NO ACTION REQUIRED - FP, T, FA, E, S, A, M, P | | | UPLOADED 2/10/20, 2/6/20, 2/5/20, 2/4/20, 1/31/20 OK | | | | | | 6. CIVIL PAGES UPLOADED 2/28/2019 DIGITAL SIGNATURE OK, | | | BUT NO NEW PAGES HAVE BEEN SUBMITTED SINCE THEN. PLEASE | | | CONFIRM THAT THERE ARE NO CONFLICTS BETWEEN THE | | | 2/28/2019 CIVIL PAGES AND OTHER (NEWER) PAGES. | | | | | | 7. NO ACTION REQUIRED - A, T, E PAGES PULOADED | | | 2/25/2019, 2/23/2019 ARE OK (SPOT CHECKED) | | | | | | 8. M PAGE UPLOADED 2/25/2019 06.16 - M808 IS NOT | | | DIGITALLY SIGNED. | | | | | | | | | | | | | | | |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
2 |
Status |
F |
Date |
2020-02-10 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2020-02-10 |
Time |
18:05 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2020-02-10 |
Time |
17:44 |
Sent To |
|
|
| Notes |
| 2021-02-21 07:49:47 | PLUMBING SHEETS ARE NOT ELECTRONICALLY SIGNED AND | | | SEALED PER FL. ADMIN. CODE RULE 61G15--23.004, | | | 61G15-23.005. T.LARGE | | 2020-02-10 18:05:44 | SAMANTHA HILL | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6724 | | | **REVISED 12/15/20, DOCUSIGN OK PER FBPE EMAIL FROM | | | W.ANDERSON** | | | | | | 1. CIVIL, ARCH & STRUCTURAL PAGES SPOT CHECKED; OK. | | | | | | 2. COMMENT REMOVED PER FBPE EMAIL | | | | | | 3. COMMENT REMOVED PER FBPE EMAIL | | | | | | 4. FS471, IT IS NOT CLEAR WHO PREPARED THE STAIR | | | PRESSURIZATION RATIONAL ANALYSIS (SUPPORTING | | | DOCUMENTS). THERE IS NO TITLE BLOCK AND THE DOCUMENT IS | | | NOT SIGNED AND SEALED. THIS DOCUMENT SHOULD BE REVIEWED | | | BY DESIGNER OF RECORD. | | | | | | |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
1 |
Status |
F |
Date |
2019-03-28 |
|
|
Cont ID |
|
| Sent By |
dbattles |
Date |
2019-03-28 |
Time |
16:08 |
Rev Time |
0.00 |
| Received By |
dbattles |
Date |
2019-03-28 |
Time |
16:08 |
Sent To |
|
|
| Notes |
| 2019-04-08 17:59:20 | MECH SHEETS NOT ELECTRONICALLY SIGNED AND SEALED. | | 2019-03-28 16:12:43 | DIGITAL SIGNATURE IS VALID FOR ALL A SHEETS | | | NO DIGITAL IMAGE OF SEAL APPLIED TO A SHEETS | | | | | | 107.2.1 FBC[AMENDED] PLACE A DIGITALLY CREATED IMAGE OF | | | YOUR SEAL AND THE FOLLOWING SENTENCES WHERE AN ORIGINAL | | | SIGNATURE WOULD APPEAR IF THE ITEM WERE BEING | | | PHYSICALLY SIGNED DATED AND SEALED. THE SENTENCES CAN | | | BE PART OF THE DIGITAL SIGNATURE CUSTOM APPEARANCE | | | AVAILABLE IN THE SIGNING TOOL, OR THEY CAN BE PLACED ON | | | THE DOCUMENT OUTSIDE OF THE DIGITAL SIGNATURE BLOCK. | | | THIS ITEM HAS BEEN ELECTRONICALLY SIGNED AND SEALED BY | | | [LICENSEE, RA, OR LS] ON THE DATE AND/OR TIME STAMP | | | SHOWN USING A DIGITAL SIGNATURE. | | | | | | DIGITAL SIGNATURE IS VALID FOR ALL STRUCURAL SHEETS. | | | DIGITAL IMAGE OF SEAL IS APPLIED TO STRUCURAL SHEETS. | | | | | | ANY SHEETS UPLOADED TO ADDRESS COMMENTS WILL NEED TO BE | | | DIGITALLY SIGNED. | | 2019-03-25 14:18:20 | ELECTRICAL SHEETS OK. |
|
|
| Review Stop |
THRESHOLD |
THRESHOLD INSPECTOR DOCUMENTS |
| Rev No |
1 |
Status |
P |
Date |
2018-11-16 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2018-11-16 |
Time |
17:55 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2018-11-16 |
Time |
17:53 |
Sent To |
|
|
| Notes |
| 2018-11-16 17:56:28 | PASSED UNDER 16060825 | | | | | | MCNAMARA SALVIA | | | ANDREW P. SULLIVAN, PE | | | CHAD CASSETT, PE | | | SERGIO GONZALEZ, PE ADDED 9/23/19 | | | | | | |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
7 |
Status |
P |
Date |
2021-08-20 |
|
|
Cont ID |
|
| Sent By |
aaponte |
Date |
2021-08-20 |
Time |
08:17 |
Rev Time |
0.00 |
| Received By |
aaponte |
Date |
2021-08-20 |
Time |
08:17 |
Sent To |
|
|
| Notes |
| 2021-08-20 08:18:57 | PROVISO: | | | 1. DECORATIVE LIGHT FIXTURES AND POLES ALONG TEH STREET | | | FRONTAGE SHALL MATCH THE DOWNTOWN CITY STANDARD. | | | 2. SIDEWALK ELEVATION SHALL BE MAINTAINED ACROSS ALL | | | DRIVEWAYS. A REVISION SHALL BE SUBMITTED WITHIN 30 DAYS | | | OF PERMIT ISSUANCE. |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
6 |
Status |
|
Date |
|
|
|
Cont ID |
|
| Sent By |
|
Date |
|
Time |
|
Rev Time |
0.00 |
| Received By |
aaponte |
Date |
2021-08-16 |
Time |
13:37 |
Sent To |
|
|
| Notes |
| 2021-08-16 14:34:54 | PROVISOS: | | | 1.LIGHT FIXTURES AND POLES ALONG DIXIE HWAY, 4TH | | | STREET, AND QUADRILLE BOULEVARD SHALL MEET THE DOWNTOWN | | | CITY STANDARD. | | | | | | | | | PLANTING DETAILS FOR GARAGE GREEN SCREEN SHALL BE | | | INCLUDED IN THE LANDSCAPE DRAWING, AS WELL AS DETAILED | | | MAINTENANCE PROCEDURES FOR THE GREEN SCREEN. | | | 6. THE DAC ORDER REQUIRES THE SIDEWALK ELEVATION TO BE | | | MAINTAINED ACROSS THE DRIVEWAY ENTRANCES. I DON?T THINK | | | THE DRAWINGS REFLECT THAT CONDITION. PLEASE CONFIRM. I | | | WOULD NEED A DETAIL OR A NOTE IN THE CIVIL DRAWINGS. IT | | | IS REALLY HARD TO GET THE CONSTRUCTION TEAM TO DO THIS | | | BECAUSE THEY ARE USED TO THE DRIVEWAY PREFERENCE. | | | 7. PLEASE CONFIRM THAT THE GAS LINES ARE OK TO RUN | | | THROUGH THE STRUCTURAL SOIL. THE GAS LINE ON 4TH IS | | | GOING THROUGH STRUCTURAL SOIL. THERE ARE ALSO SOME ROOT | | | BARRIERS PROPOSED ON THE TREES ON 4TH NEXT TO THE | | | STRUCTURAL SOIL, COULD YOU EXPLAIN THE REASON? IT SEEMS | | | THAT DEFEATS THE PURPOSE OF THE STRUCTURAL SOIL. | | | 8. ADA PEDESTRIAN CROSSING AT 4TH AND DIXIE SHALL BE | | | APPROVED BY THE ENGINEERING DEPARTMENT. | | | 9. LANDSCAPE PERMIT SHALL BE SUBMITTED AS A SEPARATE | | | PERMIT. | | | 10. PLEASE PROVIDE A NARRATIVE EXPLAINING THE PARKING | | | GARAGE OPERATION THAT ACKNOWLEDGES THE SHARED PARKING | | | SYSTEM AND VALET OPERATION. | | | 11. CAR SHARING STATION SHALL BE CLEARLY LABELED. | | | 12. CONDITIONS OF APPROVAL INCLUDED IN DAC FINAL ORDER | | | AND SITE PLAN APPROVAL LETTER ARE APPLICABLE TO THE | | | BUILDING, AND SHALL BE FULFILLED ACCORDINGLY. | | | FOR ADDITONAL INFORMATION PLEASE CONTACT ANA MARIA | | | APONTE AT 561-822-1439. |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
5 |
Status |
F |
Date |
2021-06-23 |
|
|
Cont ID |
|
| Sent By |
aaponte |
Date |
2021-06-17 |
Time |
11:50 |
Rev Time |
0.00 |
| Received By |
aaponte |
Date |
2021-06-17 |
Time |
11:50 |
Sent To |
|
|
| Notes |
| 2021-06-17 11:51:26 | | | | 1. PLANTING DETAILS FOR GARAGE GREEN SCREEN SHALL BE | | | INCLUDED IN THE LANDSCAPE DRAWING, AS WELL AS DETAILED | | | MAINTENANCE PROCEDURES FOR THE GREEN SCREEN. | | | 2. THE EXFILTRATION TRENCH ALONG THE DIXIE FRONTAGE IS | | | NEXT TO SOME PROPOSED PALMS. I WOULD LIKE CONFIRMATION | | | FROM YOUR ENGINEER THAT THE SEPARATION IS OK AND THEY | | | WILL NOT HAVE A PROBLEM WITH THE PALMS SO CLOSE TO THE | | | EXFILTRATION TRENCH. | | | 3. PLEASE INCLUDE INFORMATION ABOUT THE RELOCATION OF | | | THE BUS SHELTER. WHERE IS IT GOING TO BE LOCATED? I DID | | | NOT SEE IT IN THE SITE PLAN. | | | 4. PLEASE CONFIRM FOR ME THAT THE LOADING DOCKS INCLUDE | | | AN OPAQUE GATE. | | | 5. I FOUND THE PHOTOMETRICS FOR THE STREET LIGHT, BUT | | | NOT THE SPECS FOR THE POLE AND FIXTURE. COULD YOU | | | PLEASE TELL ME THE PAGE NUMBER WHERE THE INFORMATION IS | | | LOCATED? IT NEEDS TO BE THE CITY STANDARD. | | | 6. THE DAC ORDER REQUIRES THE SIDEWALK ELEVATION TO BE | | | MAINTAINED ACROSS THE DRIVEWAY ENTRANCES. I DON?T THINK | | | THE DRAWINGS REFLECT THAT CONDITION. PLEASE CONFIRM. I | | | WOULD NEED A DETAIL OR A NOTE IN THE CIVIL DRAWINGS. IT | | | IS REALLY HARD TO GET THE CONSTRUCTION TEAM TO DO THIS | | | BECAUSE THEY ARE USED TO THE DRIVEWAY PREFERENCE. | | | 7. PLEASE CONFIRM THAT THE GAS LINES ARE OK TO RUN | | | THROUGH THE STRUCTURAL SOIL. THE GAS LINE ON 4TH IS | | | GOING THROUGH STRUCTURAL SOIL. THERE ARE ALSO SOME ROOT | | | BARRIERS PROPOSED ON THE TREES ON 4TH NEXT TO THE | | | STRUCTURAL SOIL, COULD YOU EXPLAIN THE REASON? IT SEEMS | | | THAT DEFEATS THE PURPOSE OF THE STRUCTURAL SOIL. | | | 8. ADA PEDESTRIAN CROSSING AT 4TH AND DIXIE SHALL BE | | | APPROVED BY THE ENGINEERING DEPARTMENT. | | | 9. LANDSCAPE PERMIT SHALL BE SUBMITTED AS A SEPARATE | | | PERMIT. | | | 10. PLEASE PROVIDE A NARRATIVE EXPLAINING THE PARKING | | | GARAGE OPERATION THAT ACKNOWLEDGES THE SHARED PARKING | | | SYSTEM AND VALET OPERATION. | | | 11. CAR SHARING STATION SHALL BE CLEARLY LABELED. | | | 12. CONDITIONS OF APPROVAL INCLUDED IN DAC FINAL ORDER | | | AND SITE PLAN APPROVAL LETTER ARE APPLICABLE TO THE | | | BUILDING, AND SHALL BE FULFILLED ACCORDINGLY. | | | FOR ADDITONAL INFORMATION PLEASE CONTACT ANA MARIA | | | APONTE AT 561-822-1439. |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
4 |
Status |
F |
Date |
2021-03-04 |
|
|
Cont ID |
|
| Sent By |
aaponte |
Date |
2021-03-04 |
Time |
16:12 |
Rev Time |
0.00 |
| Received By |
aaponte |
Date |
2021-03-04 |
Time |
16:12 |
Sent To |
|
|
| Notes |
| 2021-03-04 16:11:47 | 1. SATISFIED- SHEET A0.102 LIST BUILDING FOOTPRINT | | | REQUIREMENT AS MINIMUM PERCENTAGE, IT IS A MAXIMUM | | | PERCENTAGE. PLEASE CORRECT DATA TO ACCURATELY REFLECT | | | REQUIREMENT. | | | 2. SATISFIED. SHEET A0.102 STILL LIST 328 RESIDENTIAL | | | UNITS WITHIN THE PROJECT DESCRIPTION AND THE REQUIRED | | | PARKING DATA. PLEASE ADJUST TO THE CURRENT PROPOSAL OF | | | 230 UNITS. TABLE IN THE SAME SHEET LIST 202 REGULAR | | | RESIDENTIAL UNITS AND 23 MICRO UNITS FOR A TOTAL OF 205 | | | NOT THE NEW 230 LISTED. PLEASE CORRECT AND ADJUST ALL | | | RELATED CALCULATIONS. | | | 3. NOT SATISFIED. SHEET A1.500 WAS NOT UPLOADED. BASED | | | ON SHEET A1.500 PROVIDED BY ARCHITECT IT SEEMS THERE | | | ARE SOME HOTEL ROOMS BELOW THE MINIMUM 350SF | | | REQUIRED.PREVIOUS COMMENT:IN SHEET A1.500, THE HOTEL | | | UNITS DESCRIPTION AND AREAS SUITE 1.3C AND 1.3W UNIT | | | AREA IS NOT LISTED. PLEASE UPDATE TABLE AND INCLUDE | | | INFORMATION TO CONFIRM COMPLIANCE WITH MINIMUM 350SF | | | UNITS SIZE. | | | 4. SATISFIED. BASED ON SHEET A1.500 PROVIDED BY | | | ARCHITECT, NOT IN THE PERMIT SET.PLEASE INCLUDE THIS | | | SHEET IN RESUBMITTAL. PREVIOUS COMMENT:PLEASE PROVIDE | | | INFORMATION TO CONFIRM THAT REGULAR RESIDENTIAL UNITS | | | COMPLY WITH THE AVERAGE 800SF UNIT SIZE. | | | 5. NOT SATISFIED.PLEASE SUBMIT COLORED ELEVATIONS WITH | | | CALL OUT MATERIALS. | | | 6. NOT SATISFIED. TABLE SUBMITTED BUT NOT GRAPHIC BY | | | FLOOR. PLEASE SUBMIT REFLECTING ANY CAHNGES TO THE FAR | | | CACLUALTION. PREVIOSU COMMENT:PLEASE SUBMIT THE FAR | | | DETAIL INFORMATION PER FLOOR AS SUBMITTED FOR SITE PLAN | | | APPROVAL. | | | 7. NOT SATISTIED.PLEASE INDICATE THE PLANTING AREAS IN | | | THE GARAGE LEVESL.PREVIOUS COMMENT:PLEASE EXPLAIN HOW | | | THE PLANTS PROPOSED FOR THE GARAGE SCREENING WILL GROW | | | AND STILL MAINTAIN THE AIR FLOW REQUIRED FOR GARAGE | | | VENTILATION. | | | 8. SATISFIED.PLEASE CONFIRM THE GLASS UTILIZED FOR THIS | | | PROJECT AT THE GROUND FLOOR IS NOT DARK TINTED OR | | | REFLECTIVE TO THE POINT THAT THE INTERIOR IS NOT | | | VISIBLE FROM OUTSIDE. | | | 9. SATISFIED. PLEASE INCLUDE DETAILS IN THE LANDSCAPE | | | PERMIT. PREVIOUS COMMENT: FURTHER DISCUSSION IS | | | NECESSARY FOR THE SELECTION OF THE LANDSCAPE MATERIAL | | | TO BE LOCATED ON THE QUADRILLE BLVD MEDIAN. | | | 10. PARTIALLY SATISFIED. FOR PROJECT RECORDS, PLEASE | | | INCLUDE INFORMATION IN THE PERMIT SET. PREVIOUS | | | COMMENT: PLEASE CONFIRM PALM TRAM APPROVED THE | | | RELOCATION OF THE EXISTING SHELTER TO THE PROPOSED | | | LOCATION. | | | 11. SATISFIED.DUE TO THE PROPOSED MICROUNITS PROJECT IS | | | REQUIRED TO PROVIDE 1 CAR SHARING STATION PER EVERY 13 | | | MICROUNITS. IF PARKING IS PROVIDED FOR THE MICROUNITS | | | THERE MUST BE AT LEAST ONE CAR SHARING STATION ON SITE. | | | PLEASE IDENTIFY LOCATION OF CAR SHARING STATION INSIDE | | | PARKING GARAGE. | | | 12. ACKNOWLEDGED.DUE TO THE PROPOSED MICROUNITS, | | | PROJECT IS REQUIRED TO CONTRIBUTE A FEE INTO THE | | | TROLLEY OPERATION FUND. FEE IS EQUAL TO $10 PER | | | UNIT/MONTH. AN AGREEMENT WILL BE REQUIRED WITH THE | | | PROPERTY OWNER BEFORE FINAL CO. | | | 13. NOT SATISFIED. PLEASE INCLUDE IN PERMIT SET. | | | PREVIOUS COMMENT:PLEASE IDENTIFY THE LOCATION FOR | | | MICRO-MOBILITY STATION WITHIN THE PROJECT PUBLIC REALM | | | AREA. | | | 14. NOT SATISFIED. PLEASE INCLUDE IN PERMIT SET. | | | MINIMUM ACTIVE USE REQUIREMENT ALONG DIXIE HWAY IS 80% | | | NOT 79%. PLEASE ADJUST TO CONFIRM COMPLIANCE. | | | 15. NOT SATISFIED. PLEASE INCLUDE IN PERMIT SET.THE | | | VARIANCE APPROVED BY THE DAC TO REDUCE ACTIVE USES | | | ABOVE THE FIRST FLOOR ALONG QUADRILLE BLVD ALLOWED A | | | REDUCTION FROM 60% TO 47%. PROPOSED PROJECT LISTS | | | ACTIVE USES ONLY ALONG 31.9%. PLEASE INCREASE AMOUNT OF | | | ACTIVE USES TO COMPLY WITH VARIANCE APPROVED. | | | 16. PARTIALLY SATISFIED. THE ADA RAMP NEEDS TO EXPAND | | | TO COVER BOTH PEDESTRIAN CROSSINGS N-S AND E-W. | | | PREVIOUS COMMENT: PLEASE PROVIDE A PEDESTRIAN CROSSING | | | ACROSS DIXIE HWAY FROM THE SE CORNER OF THE PROJECT. | | | 17. SATISFIED.PLEASE RELOCATE AT LEAST 3 BIKE RACKS | | | CLOSER TO THE OFFICE TOWER OPEN SPACE, AND RELOCATE AT | | | LEAST 2 BIKE RACKS TO THE AREA CLOSER TO THE PROPOSED | | | RETAIL. | | | 18. GRADING PLAN SHEET 4 HAS LABELS BLACKED OUT. | | | 19. NOT SATISFIED. LANDSCAPE PERMIT WAS FAILED IN 2018 | | | AND IT HAS NOT BEEN RESUBMITTED SINCE THEN. A SEPARATE | | | LANDSCAPE PERMIT WILL BE REQUIRED FOR THIS PERMIT. | | | 20. NOT SATISFIED.PLEASE PROVIDE INFORMATION TO CONFIRM | | | COMPLIANCE WITH PLANAR BREAK AT ALL APPLICABLE FACADES. | | | 21. NOT SATISFIED. PLEASE SEE COMMENTS PROVIDED ON | | | 11/29/2018 AS SOME OF THOSE HAVE NTO BEEN ADDRESSED. | | | ADDITIONAL COMMENTS: | | | 22. WHEN YOU RESUBMIT, PLEASE INCLUDE UPDATED SHEETS TO | | | CONFIRM THE ZONING REQUIREMENTS ARE MET AND NOTHING HAS | | | CHANGED SINCE SITE PLAN APPROVAL IN RELATIONS TO PLANAR | | | BREAKS, ACTIVE USE PERCENTAGES ETC. | | | 23. IN THE RESPONSE SHEET PLEASE IDENTIFY THE SHEET IN | | | WHICH STAFF CAN FIND THE INFORMATION REQUESTED. | | | 24. PLEASE PROVIDE A NARRATIVE EXPLAINING HOW THE | | | PARKING OPERATION IS GOING TO WORK. THERE ARE SEVERAL | | | TANDEM SPACES THAT CAN ONLY WORK WITH VALET PARKING | | | BECAUSE THE PARKING IS CALCULATED BASED ON A SHARED | | | SYSTEM AND SPACES CANNOT BE ASSIGNED TO INDIVIDUAL | | | TENANTS. | | | 25. PLEASE PROVIDE PHOTOMETRICS FOR THE STREETLIGHTS TO | | | CONFIRM COMPLIANCE WITH THE MINIMUM 06 FOOTCANDLES | | | REQUIRED. STREETLIGHT FIXTURE AND POLE SHALL BE THE | | | DOWNTOWN STANDARD. | | | FOR ADDITIONAL INFORMATION PLEASE CONTACT ANA MARIA | | | APONTE AT 561-822-1439. |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
3 |
Status |
F |
Date |
2020-03-19 |
|
|
Cont ID |
|
| Sent By |
aaponte |
Date |
2020-03-19 |
Time |
16:13 |
Rev Time |
0.00 |
| Received By |
aaponte |
Date |
2020-03-19 |
Time |
09:44 |
Sent To |
|
|
| Notes |
| 2020-03-19 16:13:50 | 1. SHEET A0.102 LIST BUILDING FOOTPRINT REQUIREMENT AS | | | MINIMUM PERCENTAGE, IT IS A MAXIMUM PERCENTAGE. PLEASE | | | CORRECT DATA TO ACCURATELY REFLECT REQUIREMENT. | | | 2. SHEET A0.102 STILL LIST 328 RESIDENTIAL UNITS WITHIN | | | THE PROJECT DESCRIPTION AND THE REQUIRED PARKING DATA. | | | PLEASE ADJUST TO THE CURRENT PROPOSAL OF 230 UNITS. | | | TABLE IN THE SAME SHEET LIST 202 REGULAR RESIDENTIAL | | | UNITS AND 23 MICRO UNITS FOR A TOTAL OF 205 NOT THE NEW | | | 230 LISTED. PLEASE CORRECT AND ADJUST ALL RELATED | | | CALCULATIONS. | | | 3. IN SHEET A1.500, THE HOTEL UNITS DESCRIPTION AND | | | AREAS SUITE 1.3C AND 1.3W UNIT AREA IS NOT LISTED. | | | PLEASE UPDATE TABLE AND INCLUDE INFORMATION TO CONFIRM | | | COMPLIANCE WITH MINIMUM 350SF UNITS SIZE. | | | 4. PLEASE PROVIDE INFORMATION TO CONFIRM THAT REGULAR | | | RESIDENTIAL UNITS COMPLY WITH THE AVERAGE 800SF UNIT | | | SIZE. | | | 5. PLEASE SUBMIT COLORED ELEVATIONS WITH CALL OUT | | | MATERIALS. | | | 6. PLEASE SUBMIT THE FAR DETAIL INFORMATION PER FLOOR | | | AS SUBMITTED FOR SITE PLAN APPROVAL. | | | 7. PLEASE EXPLAIN HOW THE PLANTS PROPOSED FOR THE | | | GARAGE SCREENING WILL GROW AND STILL MAINTAIN THE AIR | | | FLOW REQUIRED FOR GARAGE VENTILATION. | | | 8. PLEASE CONFIRM THE GLASS UTILIZED FOR THIS PROJECT | | | AT THE GROUND FLOOR IS NOT DARK TINTED OR REFLECTIVE TO | | | THE POINT THAT THE INTERIOR IS NOT VISIBLE FROM | | | OUTSIDE. | | | 9. FURTHER DISCUSSION IS NECESSARY FOR THE SELECTION OF | | | THE LANDSCAPE MATERIAL TO BE LOCATED ON THE QUADRILLE | | | BLVD MEDIAN. | | | 10. PLEASE CONFIRM PALM TRAM APPROVED THE RELOCATION OF | | | THE EXISTING SHELTER TO THE PROPOSED LOCATION. | | | 11. DUE TO THE PROPOSED MICROUNITS PROJECT IS REQUIRED | | | TO PROVIDE 1 CAR SHARING STATION PER EVERY 13 | | | MICROUNITS. IF PARKING IS PROVIDED FOR THE MICROUNITS | | | THERE MUST BE AT LEAST ONE CAR SHARING STATION ON SITE. | | | PLEASE IDENTIFY LOCATION OF CAR SHARING STATION INSIDE | | | PARKING GARAGE. | | | 12. DUE TO THE PROPOSED MICROUNITS, PROJECT IS REQUIRED | | | TO CONTRIBUTE A FEE INTO THE TROLLEY OPERATION FUND. | | | FEE IS EQUAL TO $10 PER UNIT/MONTH. AN AGREEMENT WILL | | | BE REQUIRED WITH THE PROPERTY OWNER BEFORE FINAL CO. | | | 13. PLEASE IDENTIFY THE LOCATION FOR MICRO-MOBILITY | | | STATION WITHIN THE PROJECT PUBLIC REALM AREA. | | | 14. MINIMUM ACTIVE USE REQUIREMENT ALONG DIXIE HWAY IS | | | 80% NOT 79%. PLEASE ADJUST TO CONFIRM COMPLIANCE. | | | 15. THE VARIANCE APPROVED BY THE DAC TO REDUCE ACTIVE | | | USES ABOVE THE FIRST FLOOR ALONG QUADRILLE BLVD ALLOWED | | | A REDUCTION FROM 60% TO 47%. PROPOSED PROJECT LISTS | | | ACTIVE USES ONLY ALONG 31.9%. PLEASE INCREASE AMOUNT OF | | | ACTIVE USES TO COMPLY WITH VARIANCE APPROVED. | | | 16.PLEASE PROVIDE A PEDESTRIAN CROSSING ACROSS DIXIE | | | HWAY FROM THE SE CORNER OF THE PROJECT. | | | 17. PLEASE RELOCATE AT LEAST 3 BIKE RACKS CLOSER TO THE | | | OFFICE TOWER OPEN SPACE, AND RELOCATE AT LEAST 2 BIKE | | | RACKS TO THE AREA CLOSER TO THE PROPOSED RETAIL. | | | 18. GRADING PLAN SHEET 4 HAS LABELS BLACKED OUT. | | | 19. A SEPARATE LANDSCAPE PERMIT WILL BE REQUIRED FOR | | | THIS PERMIT. | | | 20. PLEASE PROVIDE INFORMATION TO CONFIRM COMPLIANCE | | | WITH PLANAR BREAK AT ALL APPLICABLE FACADES. | | | 21. PLEASE SEE COMMENTS PROVIDED ON 11/29/2018 AS SOME | | | OF THOSE HAVE NTO BEEN ADDRESSED. | | | FOR ADDITIONAL INFORMATION PLEASE CONTACT ANA MARIA | | | APONTE AT 561-822-1439. |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
F |
Date |
2019-04-29 |
|
|
Cont ID |
|
| Sent By |
aaponte |
Date |
2019-04-29 |
Time |
12:34 |
Rev Time |
0.00 |
| Received By |
aaponte |
Date |
2019-04-19 |
Time |
14:48 |
Sent To |
|
|
| Notes |
| 2019-04-29 12:35:24 | SITE PLAN APPROVAL NOT COMPLETED YET. |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
F |
Date |
2018-11-29 |
|
|
Cont ID |
|
| Sent By |
aaponte |
Date |
2018-11-29 |
Time |
11:41 |
Rev Time |
0.00 |
| Received By |
aaponte |
Date |
2018-11-28 |
Time |
13:49 |
Sent To |
|
|
| Notes |
| 2018-11-28 16:37:43 | 1. PROJECT DATA IN SHEET A0.007 DOES NOT MATCH THE | | | NUMBER OF RESIDENTIAL UNITS, AND THE TOTAL SQUARE | | | FOOTAGE INDICATED IN SURVEY (149,402SF) VS LOT AREA IN | | | THIS SHEET (150,245SF). THSI SHEED DOES NOT ACCURATELY | | | REFLECT THE GROUND FLOOR LAYOUT (PUBLIC REALM, DROP-OFF | | | AREAS) | | | 2. PLEASE AD A TABLE IN SHEET A0.008 TO INCLUDE THE | | | GROSS BUILDING AREA BY USE (OFFICE, RESIDENTIAL | | | (UNITS+SF), HOTEL (ROOMS+SF) AND OTHER. | | | 3. PLANTER AREAS FOR GARAGE ARE TOO FAR FROM SCREEN AND | | | LANDSCAPE WILL NOT PROJECT THROUGH SCREEN (SHEET | | | A4.300). PLANTING AREA IS 3.5 FEET AWAY FROM SCREEN IN | | | SOME CASES. | | | 4. A MANAGEMENT PLAN SHALL BE PROVIDED TO DESCRIBE HOW | | | THE GREEN SCREENS WILL BE ESTABLISHED AND MAINTAINED TO | | | ENSURE THE PLANT MATERIAL GROWS TO SCREEN THE GARAGE AS | | | INTENDED AND REPRESENTED IN RENDERINGS. | | | 5. PLEASE SUBMIT DIAGRAMS AND TABLES INDICATING THE | | | GROSS BUILDING AREA FOR EACH FLOOR. | | | 6. PLEASE PROVIDE COLORED ELEVATIONS CLEARLY INDICTING | | | EACH OF THE MATERIALS PROPOSED FOR THE FACADE ELEMENTS. | | | 7. PLEASE PROVIDED BLOW-OUT COLORED ELEVATIONS OF THE | | | FIRST FLOOR AND PODIUM, WITH CALL OUT MATEIRIALS AND | | | DETAILS. | | | 8. PLEASE EXPLAIN THE DIFFERENCE BETWEEN THE GREEN | | | SCREEN AND THE GREEN WALL INDICATED ON THE 6TH FLOOR. | | | 9. ON THE SECTION SHEETS, PLEASE PROVIDE A SMALL KEY TO | | | IDENTIFY THE LOCATION OF THE SETION. | | | 10. PLEASE INDICATE THE LOCATION OF THE GLASS DETAILS | | | THAT SPECIFICALLY CALL OUT THE TRANSPARENCY OF THE | | | GLASS ELEMENTS AT THE GROUND LEVEL. GROUND FLOOR VISUAL | | | ACCESS BETWEEN A BUILDING AND ITS ACTIVE USES FROM THE | | | PUBLIC SIDEWALK IS REQUIRED. | | | 11. PROPOSED CURB CUT ON 4TH STREET EXCEEDS THE MAXIMUM | | | 25 FEEET IN WIDTH ALLOWED. | | | 12. A SEPARATE LANDSCAPE AND HARDSCAPE PERMIT SHALL BE | | | SUBMITTED FOR THIS PROJECT. PLEASE INDICATE THE | | | LOCATION OF ALL UTILITY TO CONFIRM NO CONFLICT WITH LA | | | OR HARDSCAPE ELEMENTS. | | | 13. SEPARATE STREETLIGHTING PLAN WITH PHOTOMETRICS | | | SHALL BE SUBMITTED FOR THIS PROJECT. | | | 14. PLEASE DIMENSION PARKING SPACES TO CONFIRM | | | COMPLIANCE WITH MINIMUM REQUIREMENTS. SPACE ADJACENT TO | | | A WALL OR COLUMN SHALL BE WIDER (SEC 94-111(C)) | | | 15. CURB CUT SHALL BE DESIGNED IN A WAY THAT THE | | | SIDEWLK LEVEL IS MAINTAINED ACROSS CURB CUT AND NOT | | | LOWERED TO THE ROAD LEVEL. PEDESTRIANS GET PRIORITY, | | | NOT THE CARS. | | | 16. PLEASE PROVIDE A TABLE INDICATING THE SIZE OF THE | | | RESIDENTIAL UNITS TO CONFIRM COMPLIANCE WITH MINIMUM | | | AVERAGE OF 800SF. | | | 17. PLEASE INDICATE THE SIZE OF THE HOTEL ROOMS TO | | | CONFIRM COMPLIANCE WITH FULL SERVICE HOTEL DEFINITION. | | | 18. PLEASE INDICATE THE LOCATION OF THE CAR LIFTS. | | | 19. PLEASE INDICATE THE TENANT ACCESS TO THE BIKE | | | STORAGE ROOM. | | | | | | FOR RESUBMITTAL, PLEASE DRAFT A COMMENT RESPONSE LETTER | | | ADDRESSING EACH OF THE COMMENTS, AND THE LOCATION OF | | | THE INFORMATION IF APPLICABLE. | | | | | | FOR ADDITIONAL INFORMATION PLEASE CONTACT ANA MARIA | | | APONTE AT 561-822-1439. | | | | | | |
|
|
|
Account Summary | Usage Policy | Privacy Policy