Plan Review Details - Permit 18100523
Plan Review Stops For Permit 18100523
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2019-02-19 Cont ID  
Sent By pvalenti Date 2019-02-19 Time 08:30 Rev Time 0.00
Received By pvalenti Date 2019-02-19 Time 08:30 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2018-11-20 Cont ID  
Sent By pvalenti Date 2018-11-20 Time 09:53 Rev Time 0.00
Received By pvalenti Date 2018-11-20 Time 09:53 Sent To  
Notes
2018-11-20 09:56:41****CORRECTIONS****
  
 PETER E VALENTI
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6673
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 FBC 107. PLEASE PROVIDE MORE INFORMATION: PLEASE SHOW
 LOCATION OF GENERATOR INCLUDING DISTANCE TO HOUSE AND
 THAT DISTANCE TO OPERABLE OPENINGS IS AT LEAST 10'.

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2018-10-31 Cont ID  
Sent By jleahy Date 2018-10-31 Time 17:05 Rev Time 0.00
Received By jleahy Date 2018-10-31 Time 17:05 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 2 Status P Date 2019-02-19 Cont ID  
Sent By tklarge Date 2019-02-19 Time 05:18 Rev Time 0.00
Received By tklarge Date 2019-02-19 Time 04:50 Sent To B
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2018-10-29 Cont ID  
Sent By tklarge Date 2018-10-29 Time 12:19 Rev Time 0.00
Received By tklarge Date 2018-10-29 Time 11:23 Sent To  
Notes
2018-10-29 12:19:371) THE PLANS INDICATE AN EXISTING GAS METER AND CITY
 RECORDS SHOW AN EXISTING GAS SYSTEM FOR THIS ADDRESS.
 THE BTU LOAD OF THE EXISTING GAS SYSTEM MUST BE ADDED
 INTO THE TOTAL BTU LOAD ON THE SYSTEM TO ENSURE THE
 EXISTING SYSTEM IS PROPERLY SIZED. SHOW THE BTU LOAD
 FOR THE EXISTING SYSTEM ON THE GAS RISER. FBC 107.2.1.
 2) SHOW THE SIZE OF THE PIPE TO THE EXISTING SYSTEM.
 FBC 107.2.1.
 3) SHOW THE SIZE OF THE PIPE AT THE OUTLET OF THE GAS
 METER. THIS SIZE MAY HAVE TO BE INCREASED BASED ON THE
 LONGEST RUN AND THE TOTAL BTU LOAD ON THE SYSTEM.
 4) THE SUBMITTED GAS PLAN SHOWS THE BTU LOAD FOR THE
 GENERATOR AT 750,000 BTU'S BUT THE GENERAC SPECS SHOW
 THE BTU LOAD AS 681,000 BTU'S . CLARIFY.
 5) PREVIOUS GAS PLAN ON FILE IN CITY RECORDS SHOWS THE
 DISTANCE TO THE FURTHEST OUTLET AT 202 FEET. THIS
 DISTANCE SHALL BE USED FOR THE SIZING OF THE GAS LINE
 TO THE GENERATOR, NOT 50 FEET AS SHOWN. 2017 FBC-FUEL
 GAS SEC.402.4.1. A MINIMUM SIZE OF 1 INCH PE IS
 REQUIRED TO THE GENERATOR. TABLE 402.4 (22).
 6) THE SIZE OF THE GALVANIZED LINE AT THE OUTLET OF THE
 GAS METER SHALL BE INCREASED TO 1 1/4 INCH PIPE PER
 TABLE 402.4 (5).
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2019-02-19 Cont ID  
Sent By pvalenti Date 2019-02-19 Time 08:30 Rev Time 0.00
Received By pvalenti Date 2019-02-08 Time 13:54 Sent To  
Notes
2019-02-11 13:54:19RESUB ROUTED TO TKLARGE

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-11-20 Cont ID  
Sent By pvalenti Date 2018-11-20 Time 09:56 Rev Time 0.00
Received By pvalenti Date 2018-10-11 Time 14:25 Sent To I
Notes
2018-10-12 14:26:04ROUTED TO ZONING INBOX

Review Stop Z ZONING
Rev No 1 Status P Date 2018-10-26 Cont ID  
Sent By mcruz Date 2018-10-26 Time 10:40 Rev Time 0.00
Received By mcruz Date 2018-10-26 Time 10:35 Sent To  
Notes
***NONE***