Plan Review Details - Permit 18100523
| Plan Review Stops For Permit 18100523 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
P |
Date |
2019-02-19 |
|
|
Cont ID |
|
| Sent By |
pvalenti |
Date |
2019-02-19 |
Time |
08:30 |
Rev Time |
0.00 |
| Received By |
pvalenti |
Date |
2019-02-19 |
Time |
08:30 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2018-11-20 |
|
|
Cont ID |
|
| Sent By |
pvalenti |
Date |
2018-11-20 |
Time |
09:53 |
Rev Time |
0.00 |
| Received By |
pvalenti |
Date |
2018-11-20 |
Time |
09:53 |
Sent To |
|
|
| Notes |
| 2018-11-20 09:56:41 | ****CORRECTIONS**** | | | | | | PETER E VALENTI | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6673 | | | | | | FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) | | | FBC B = FBC BUILDING | | | FBC EB = FBC EXISTING BUILDING | | | FBC A = FBC ACCESSIBILITY | | | FBC EC = FBC ENERGY CONSERVATION | | | FBC R = FBC RESIDENTIAL | | | | | | FBC 107. PLEASE PROVIDE MORE INFORMATION: PLEASE SHOW | | | LOCATION OF GENERATOR INCLUDING DISTANCE TO HOUSE AND | | | THAT DISTANCE TO OPERABLE OPENINGS IS AT LEAST 10'. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
P |
Date |
2018-10-31 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2018-10-31 |
Time |
17:05 |
Rev Time |
0.00 |
| Received By |
jleahy |
Date |
2018-10-31 |
Time |
17:05 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
2 |
Status |
P |
Date |
2019-02-19 |
|
|
Cont ID |
|
| Sent By |
tklarge |
Date |
2019-02-19 |
Time |
05:18 |
Rev Time |
0.00 |
| Received By |
tklarge |
Date |
2019-02-19 |
Time |
04:50 |
Sent To |
B |
|
| Notes |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
1 |
Status |
F |
Date |
2018-10-29 |
|
|
Cont ID |
|
| Sent By |
tklarge |
Date |
2018-10-29 |
Time |
12:19 |
Rev Time |
0.00 |
| Received By |
tklarge |
Date |
2018-10-29 |
Time |
11:23 |
Sent To |
|
|
| Notes |
| 2018-10-29 12:19:37 | 1) THE PLANS INDICATE AN EXISTING GAS METER AND CITY | | | RECORDS SHOW AN EXISTING GAS SYSTEM FOR THIS ADDRESS. | | | THE BTU LOAD OF THE EXISTING GAS SYSTEM MUST BE ADDED | | | INTO THE TOTAL BTU LOAD ON THE SYSTEM TO ENSURE THE | | | EXISTING SYSTEM IS PROPERLY SIZED. SHOW THE BTU LOAD | | | FOR THE EXISTING SYSTEM ON THE GAS RISER. FBC 107.2.1. | | | 2) SHOW THE SIZE OF THE PIPE TO THE EXISTING SYSTEM. | | | FBC 107.2.1. | | | 3) SHOW THE SIZE OF THE PIPE AT THE OUTLET OF THE GAS | | | METER. THIS SIZE MAY HAVE TO BE INCREASED BASED ON THE | | | LONGEST RUN AND THE TOTAL BTU LOAD ON THE SYSTEM. | | | 4) THE SUBMITTED GAS PLAN SHOWS THE BTU LOAD FOR THE | | | GENERATOR AT 750,000 BTU'S BUT THE GENERAC SPECS SHOW | | | THE BTU LOAD AS 681,000 BTU'S . CLARIFY. | | | 5) PREVIOUS GAS PLAN ON FILE IN CITY RECORDS SHOWS THE | | | DISTANCE TO THE FURTHEST OUTLET AT 202 FEET. THIS | | | DISTANCE SHALL BE USED FOR THE SIZING OF THE GAS LINE | | | TO THE GENERATOR, NOT 50 FEET AS SHOWN. 2017 FBC-FUEL | | | GAS SEC.402.4.1. A MINIMUM SIZE OF 1 INCH PE IS | | | REQUIRED TO THE GENERATOR. TABLE 402.4 (22). | | | 6) THE SIZE OF THE GALVANIZED LINE AT THE OUTLET OF THE | | | GAS METER SHALL BE INCREASED TO 1 1/4 INCH PIPE PER | | | TABLE 402.4 (5). | | | | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | PLUMBING PLAN REVIEW | | | 561-805-6692 | | | [email protected] | | | |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2019-02-19 |
|
|
Cont ID |
|
| Sent By |
pvalenti |
Date |
2019-02-19 |
Time |
08:30 |
Rev Time |
0.00 |
| Received By |
pvalenti |
Date |
2019-02-08 |
Time |
13:54 |
Sent To |
|
|
| Notes |
| 2019-02-11 13:54:19 | RESUB ROUTED TO TKLARGE |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2018-11-20 |
|
|
Cont ID |
|
| Sent By |
pvalenti |
Date |
2018-11-20 |
Time |
09:56 |
Rev Time |
0.00 |
| Received By |
pvalenti |
Date |
2018-10-11 |
Time |
14:25 |
Sent To |
I |
|
| Notes |
| 2018-10-12 14:26:04 | ROUTED TO ZONING INBOX |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
P |
Date |
2018-10-26 |
|
|
Cont ID |
|
| Sent By |
mcruz |
Date |
2018-10-26 |
Time |
10:40 |
Rev Time |
0.00 |
| Received By |
mcruz |
Date |
2018-10-26 |
Time |
10:35 |
Sent To |
|
|
| Notes |
|
|
|