Plan Review Details - Permit 18100445
Plan Review Stops For Permit 18100445
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2018-12-18 Cont ID  
Sent By jgomez Date 2018-12-18 Time 16:30 Rev Time 0.00
Received By jgomez Date 2018-12-18 Time 15:58 Sent To I
Notes
2018-12-18 15:59:30BUILDING REVIEW APPROVED WITH PROVISO:
 1- SHEET LS1-01: A) NUMBER OF PEOPLE SHOWN ON OCCUPANCY
 CALCULATION ON THE RIGHT HAND SIDE OF DRAWING DOESN'T
 MATCH NUMBER OF PEOPLE SHOWN ON FLOOR PLAN. CHECK
 ASSEMBLY OCCUPANTS AND REVISE.
 B)CODE SECTION REFERENCES CITED ON THE CODE ANALYSIS
 LEGEND AND EGRESS TRAVEL CALCULATIONS DON'T CORRESPOND
 TO THE CURRENT FBC 6TH EDITION (2017). REVISE AS
 REQUIRED.
 C) FLOOR PLAN SHOWS ONE PARTITION WALL IN THE LEFT HAND
 SIDE CORRIDOR OF FLOOR PLAN AND ANOTHER PARTITION WALL
 LOCATED IN THE UPPER LEFT CORNER CORRIDOR (SEE MARK UPS
 ON FLOOR PLAN). IT IS NOT CLEAR IF THESE ARE TRUE
 PARTITIONS. THERE IS NOT ACCESS TO THE OFFICES LOCATED
 IN THE UPPER LEFT CORNER. CLARIFY/REVISE.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2018-12-04 Cont ID  
Sent By jgomez Date 2018-12-04 Time 17:21 Rev Time 0.00
Received By jgomez Date 2018-12-04 Time 17:21 Sent To  
Notes
2018-12-04 17:21:57BUILDING REVIEW COMMENTS
 CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS.
  
 NOTE:
 BUILDING REVIEW MAY BE APPROVED WITH PROVISO. PROVISO
 MEANS CONTRACTOR WILL SUBMIT REQUIRED INFORMATION AFTER
 THE PERMIT IS ISSUED BUT BEFORE INSPECTIONS TO AVOID
 CONFLICTS/DELAYS. REVISION FEES MAY APPLY. CONTRACTOR
 TO ADVICE IF PROVISO OPTION IS PREFERRED AT THIS TIME
 OR IF RE-SUBMITTING REQUIRED INFORMATION BEFORE PERMIT
 ISSUANCE.
  
  
 1- SHEET LS1-01:
 A) NUMBER OF PEOPLE SHOWN ON OCCUPANCY CALCULATION ON
 THE RIGHT HAND SIDE OF DRAWING DOESN'T MATCH NUMBER OF
 PEOPLE SHOWN ON FLOOR PLAN. CHECK ASSEMBLY OCCUPANTS
 AND REVISE AS REQUIRED. TABLE 1004.1.2 FBC.
  
 B)CODE SECTION REFERENCES CITED ON THE CODE ANALYSIS
 LEGEND AND EGRESS TRAVEL CALCULATIONS DON'T CORRESPOND
 TO THE CURRENT FBC 6TH EDITION (2017). REVISE AS
 REQUIRED TO AVOID CONFLICTS. SEC. 107.2.1 CITY
 AMENDMENTS AND CHAPTER 553 F.S.
  
 C) FLOOR PLAN SHOWS ONE PARTITION WALL IN THE LEFT HAND
 SIDE CORRIDOR OF FLOOR PLAN AND ANOTHER PARTITION WALL
 LOCATED IN THE UPPER LEFT CORNER CORRIDOR (SEE MARK UPS
 ON FLOOR PLAN). IT IS NOT CLEAR IF THESE ARE TRUE
 PARTITIONS. THERE IS NOT ACCESS TO THE OFFICES LOCATED
 IN THE UPPER LEFT CORNER. CLARIFY/REVISE AS REQUIRED.
 NOTE: REVISE ALL DRAWINGS ACCORDINGLY. ALL OF THEM SHOW
 THESE PARTITIONS SEC. 107.2.1 CITY AMENDMENTS.
  
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE/VOID THE
 PREVIOUSLY REVIEWED SHEETS.
 PLEASE DON'T STAPLE OLD DRAWINGS. SUBMIT OLD DRAWINGS
 FOR REFERENCE.
  
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2018-10-31 Cont ID  
Sent By jpearson Date 2018-10-31 Time 15:41 Rev Time 0.00
Received By jpearson Date 2018-10-31 Time 15:14 Sent To  
Notes
2018-10-31 15:14:04ALL LOW VOLTAGE SHOWN AS EXISTING. ANY PERMIT FOR LOW
 VOLTAGE WILL REQUIRE A PLAN SUBMISSION.

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2018-10-18 Cont ID  
Sent By scaldero Date 2018-10-18 Time 08:30 Rev Time 0.00
Received By scaldero Date 2018-10-18 Time 08:23 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2018-12-18 Cont ID  
Sent By jgomez Date 2018-12-18 Time 16:44 Rev Time 0.00
Received By jgomez Date 2018-12-18 Time 15:58 Sent To I
Notes
2018-12-18 15:59:16GOOD AFTERNOON,
  
 ROBERT AND SAMANTHA THANK YOU FOR TAKING THE TIME TO
 SPEAK WITH ME THIS AFTERNOON. AT THIS TIME WE ARE
 REQUESTING TO HAVE THE PERMIT ISSUED WITH THE PROVISOS.
 PLEASE LET US KNOW WHEN THAT IS READY FOR PICKUP AND IF
 THE SIGNED PERMIT APPLICATION WILL BE REQUIRED AS WELL.
  
 THANK YOU AGAIN! PLEASE FEEL FREE TO CONTACT ME IF YOU
 HAVE ANY QUESTIONS OR COMMENTS.
 THANKS!
 BRANDI DAY
 (502) 544-8044
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-12-04 Cont ID  
Sent By jgomez Date 2018-12-04 Time 17:22 Rev Time 0.00
Received By jgomez Date 2018-10-17 Time 13:52 Sent To I
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status N Date 2018-12-04 Cont ID  
Sent By skennedy Date 2018-12-04 Time 10:25 Rev Time 0.00
Received By skennedy Date 2018-12-04 Time 10:25 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2018-11-16 Cont ID  
Sent By cmontell Date 2018-11-16 Time 11:36 Rev Time 0.00
Received By cmontell Date 2018-11-16 Time 10:54 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2018-12-04 Cont ID  
Sent By skennedy Date 2018-12-04 Time 10:24 Rev Time 0.00
Received By skennedy Date 2018-12-04 Time 10:24 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2018-10-31 Cont ID  
Sent By jpearson Date 2018-10-31 Time 15:02 Rev Time 0.00
Received By jpearson Date 2018-10-31 Time 15:02 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status N Date 2018-10-22 Cont ID  
Sent By eschneid Date 2018-10-22 Time 18:13 Rev Time 0.25
Received By eschneid Date 2018-10-22 Time 18:13 Sent To  
Notes
***NONE***