Plan Review Details - Permit 18100338
Plan Review Stops For Permit 18100338
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2018-11-29 Cont ID  
Sent By dbattles Date 2018-11-29 Time 11:10 Rev Time 0.00
Received By dbattles Date 2018-11-29 Time 11:10 Sent To  
Notes
2018-11-29 11:09:57THE FOLLOWING SUBMITTALS WILL BE DEFERRED AS STATED ON
 SHEET A-003R:
 A. FENESTRATION PRODUCT APPROVALS (ENTRY DOORS).
 B. ROOFING PRODUCT APPROVALS AND ENHANCED NAILING IF
 REQUIRED.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2018-10-18 Cont ID  
Sent By dbattles Date 2018-10-18 Time 14:51 Rev Time 0.00
Received By dbattles Date 2018-10-17 Time 14:15 Sent To  
Notes
2018-10-18 14:56:34****CORRECTIONS****
 W.P.B. PERMIT: 18100338
 REVIEWED: OCTOBER 18, 2018
  
 DYLAN BATTLES
 BUILDING PLANS EXAMINER I
 [email protected]
 561-805-6718
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC AMENDED = FLORIDA BUILDING CODE,6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC ENERGY = FBC ENERGY CONSERVATION
  
 1. [FBC A307.2] AND [FBC 1003.3]PROTRUSION LIMITS.
 OBJECTS WITH LEADING EDGES MORE THAN 27 INCHES (685 MM)
 AND NOT MORE THAN 80 INCHES (2030 MM) ABOVE THE FINISH
 FLOOR OR GROUND SHALL PROTRUDE 4 INCHES (100 MM)
 MAXIMUM HORIZONTALLY INTO THE CIRCULATION PATH
 THE HAND WASH SINK IS PROTRUDING INTO CIRCULATION PATH
 AND MAY ALSO REDUCE THE EGRESS TO LESS THAN THE
 REQUIRED 44? MINIMUM. PLEASE REVIEW AND ADJUST LOCATION
 AS NEEDED.
  
 2. [FBC 307.4] VERTICAL CLEARANCE.
 VERTICAL CLEARANCE SHALL BE 80 INCHES (2030 MM) HIGH
 MINIMUM. GUARDRAILS OR OTHER BARRIERS SHALL BE PROVIDED
 WHERE THE VERTICAL CLEARANCE IS LESS THAN 80 INCHES
 (2030 MM) HIGH. THE LEADING EDGE OF SUCH GUARDRAIL OR
 BARRIER SHALL BE LOCATED 27 INCHES (685 MM) MAXIMUM
 ABOVE THE FINISH FLOOR OR GROUND.
 WHAT IS HAPPENING AT THE REAR DOOR WHERE THE EXISTING
 STAIRS ARE? I SEE AN ICE MAKER, BUT ITS NOT CLEAR WHERE
 80? IS AND WHAT IF THIS EQUIPMENT IS MOVED?
  
 3. [FBC 1017.2]ADD MAXIMUM TRAVEL DISTANCE TO SHEET
 A-103R.
 INCLUDE EXIT DISCHARGE DISTANCE TO PUBLIC RIGHT OF WAY
 FROM REAR EXITS AND INCLUDE OUTDOOR AREA IN LIFE SAFETY
 PLAN PER FBC 1004.5.
 REMOVE OLD LABEL THAT SAY EXISTING TAYLOR SHOP.
  
 4. [FBC 107.2.5]SHOW LOCATION OF STEEL POSTS FROM
 S-101R ON THE FLOOR PLAN. HOW WILL THE PROPOSED POCKET
 DOOR FUNCTION WITH THE POST IN THE WALL CAVITY?
 ADD TYPICAL DETAIL OF EXTERIOR WALL TO SHOW INSULATION,
 FURRING AND INTERIOR WALL MATERIAL.
  
 5. [FBC A404.2.4.1(C)]DOOR LABELED 6 AT THE REAR
 EGRESS. PROVIDE 12? SIDE CLEARANCE AT DOOR WITH FRONT
 APPROACH PUSH SIDE WITH CLOSER AND LATCH.
  
 6. [FBC A902.1]SHEET A-101R SHOWS ADA SECTION AT BAR.
 PROVIDE DETAIL OF HOW IT COMPLYS WITH ADA REQUIREMENTS.
 SHOW DETAIL OF HOW THE BAR IS CONSTRUCTED AND CONNECTED
 TO FLOOR.
 ALSO, SHOW DETAIL OF GLASS WALL AT ENTRY.
  
 7. [FBC A604 AND A606.1]INTERIOR ELEVATIONS OF ADA
 RESTROOMS TO COMPLY WITH A604-A606.
  
 8. [FBC A604.6]SHOW FLUSHING CONTROL TO BE ON THE OPEN
 SIDE OF THE WATER CLOSET.
  
 9. [FBC A604.5]ADD NOTE TO SUPPLY BACKING SUPPORT FOR
 RESTROOM GRAB BARS.
  
 10. [FBC A604.5.1] THE SIDE WALL GRAB BAR SHALL BE 42
 INCHES (1065 MM) LONG MINIMUM, LOCATED 12 INCHES (305
 MM) MAXIMUM FROM THE REAR WALL AND EXTENDING 54 INCHES
 (1370 MM) MINIMUM FROM THE REAR WALL.
 SHOW LENGTH OF BACK GRAB BARS IN RESTROOMS
  
 11. [FBC A604.5.2] THE REAR WALL GRAB BAR SHALL BE 36
 INCHES (915 MM) LONG MINIMUM AND EXTEND FROM THE
 CENTERLINE OF THE WATER CLOSET 12 INCHES (305 MM)
 MINIMUM ON ONE SIDE AND 24 INCHES (610 MM) MINIMUM ON
 THE OTHER SIDE.
 SHOW LENGTH OF SIDE GRAB BARS IN RESTROOMS
  
 12. [FBC 1511.1.1]WHAT PERCENTAGE OF ROOF IS BEING
 REPLACED? IF IT EXCEEDS 25% THAN THE WHOLE ROOF SHOULD
 BE REPLACED TO MEET CURRENT CODES.
  
 13. [FBC 1510.10]MECHANICAL UNITS.
 HOW ARE NEW RTU?S BEING SUPPORTED? PLEASE PROVIDE
 DETAILS OF HOW THESE UNITS ARE SUPPORTED ON THE ROOF.
  
 14. [FBC 1203.3]UNVENTED ATTIC AND UNVENTED ENCLOSED
 RAFTER ASSEMBLIES.
 PROVIDE CUT SHEET FOR ICYNENE(ICC-ES REPORT OR EQUAL)
 WITH THE TYPE SELECTED TO ESTABLISH THICKNESS NEEDED TO
 MEET REQUIRED R-VALUE, FLAME SPREAD INDEX AND SMOKE
 DEVELOPED INDEX.
 ALSO, ADJUST SHEET S-102R DETAIL SHOWS R-21 AT ROOF,
 BUT THE ENERGY CALCULATIONS CALL FOR R23.1.
  
 15. [FBC 1609.1.1]DETERMINATION OF WIND LOADS FOR
 COMPONANTS AND CLADDING.
 PROVIDE WIND LOAD DESIGN DATA FOR COMPONANTS AND
 CLADDING.
 METHOD OF DESIGN = (ASCE 7-10?)
 RISK CATEGORY = ___(II?)
 EXPOSURE CATEGORY = ___(B,C OR D?)
 BUILDING CLASSIFICATION = __________(ENCLOSED?)
 MEAN BLDG. HGT. = ___FT. ___IN.
 WIND SPEED V ULT = _____(170?)
 WIND SPEED V ASD = _____(132?)
 DESIGN PRESSURE FOR EACH OPENING = +___ & -___ ZONE OF
 OPENING = (4 OR 5)
  
 16. THE FOLLOWING SUBMITTALS WILL BE DEFERRED AS STATED
 ON SHEET A-003R:
 A. FENESTRATION PRODUCT APPROVALS (ENTRY DOORS).
 B. ROOFING PRODUCT APPROVALS AND ENHANCED NAILING IF
 REQUIRED.
 C. SEPARATE PERMIT FOR GENERATOR AND STAND.
 D. SEPARATE PERMITS FOR LOW VOLTAGE.
  
 NOTE:
 -PLEASE PROVIDE COMMENT RESPONSE SHEET TO EXPLAIN HOW
 EACH COMMENT IS BEING ADDRESSED.
 -ADDITIONAL COMMENTS MAY BE FORTHCOMING PENDING REVIEW
 OF MATERIALS REQUESTED.
 -WHEN RESUBMITTING, PROVIDE TWO IDENTICAL COLLATED SETS
 OF DOCUMENTS FOR ISSUANCE. OLD SHEETS (BOTH SETS)
 SHOULD BE RETAINED IN THE PACKAGE; PLEASE DO NOT
 DISCARD ANY DOCUMENTS. THEY SHOULD BE BOUND TOGETHER
 SEPARATELY FROM THE TWO ISSUANCE SETS AND MARKED "VOID"
 OR "OLD SHEETS". PLEASE DO NOT STAMP THE PLANS VOID AS
 APPLICANTS ARE INADVERTENTLY STAMPING SHEETS THAT WE
 NEED "VOID", RENDERING THEM NOT USABLE.
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2018-11-29 Cont ID  
Sent By gjohnson Date 2018-12-05 Time 09:06 Rev Time 0.00
Received By jpearson Date 2018-11-29 Time 07:20 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2018-11-26 Cont ID  
Sent By jpearson Date 2018-11-26 Time 15:32 Rev Time 0.00
Received By jpearson Date 2018-11-26 Time 15:32 Sent To B
Notes
2018-11-26 15:32:04CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
 (S)
  
 PREVIOUS COMMENTS THAT HAVE BEEN ADDRESSED
 SATISFACTORILY ARE MARKED AS CORRECTED. PREVIOUS
 COMMENTS THAT HAVE NOT BEEN ADDRESSED SATISFACTORILY
 HAVE ADDITIONAL COMMENTS IN PARENTHESES. ANY NEW
 COMMENTS WILL BE LISTED AFTER PREVIOUS COMMENTS.
  
 1. VALUE FOR WORK STATED ON PERMIT APPLICATION APPEARS
 LOW. PROVIDE COPY OF SIGNED CONTRACT WITH SCOPE AND
 VALUE OF WORK, TO INCLUDE ALL MATERIALS AND LABOR. THIS
 IS FOR TOTAL PROJECT, NOT JUST ELECTRICAL. FBC 109.3
 (THE RESPONSE LETTER PROVIDED STATED THAT THE MEP'S
 WILL STATE THE VALUE FOR THEIR WORK WHEN APPLYING FOR
 PERMIT. THIS IS NOT HOW THE PROCESS WORKS, AS THE MEP'S
 WILL PULL A SUB-PERMIT TO THE MASTER AND VALUE IS NOT
 CONSIDERED DURING THAT PROCESS. THE TOTAL VALUE FOR THE
 JOB MUST BE STATED ON THE MASTER PERMIT. PROVIDE AS
 PREVIOUSLY REQUESTED.)
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD
 SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2018-10-17 Cont ID  
Sent By jpearson Date 2018-10-17 Time 09:21 Rev Time 0.00
Received By jpearson Date 2018-10-17 Time 06:53 Sent To  
Notes
2018-10-17 09:21:00CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
 (S)
  
 1. VALUE FOR WORK STATED ON PERMIT APPLICATION APPEARS
 LOW. PROVIDE COPY OF SIGNED CONTRACT WITH SCOPE AND
 VALUE OF WORK, TO INCLUDE ALL MATERIALS AND LABOR. THIS
 IS FOR TOTAL PROJECT, NOT JUST ELECTRICAL. FBC 109.3
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD
 SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2018-10-12 Cont ID  
Sent By pleduc Date 2018-10-12 Time   Rev Time 0.00
Received By pleduc Date 2018-10-12 Time 13:44 Sent To I
Notes
2018-10-12 14:01:00THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 PLEASE CONSIDER THE FOLLOWING AS PROVISO:
  
 THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED
 AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE
 PROVISO COMMENTS WILL RESULT IN A FAILED FIRE
 INSPECTION.
  
  
 1) SHEET A 003R - THERE IS AN INCORRECT EDITION OF THE
 FLORIDA FIRE PREVENTION CODE
  
 THE PROPOSED PROJECT SHALL MEET THE REQUIREMENTS OF THE
 6TH EDITION OF FLORIDA FIRE PREVENTION CODE INCLUDING
 THE 2015 EDITION OF NFPA 1 AND NFPA 101 AND ALL OTHER
 APPLICABLE CODES OR STANDARDS.
  
 PLEASE REVIEW AND ENSURE COMPLIANCE.
  
  
  
  
 2) SHEET A 101R - THERE IS AN INDICATION OF DOOR 3
 SWINGING OUT INTO THE EXIT ACCESS CORRIDOR.
  
 PER NFPA 101 CHAPTER 7, MEANS OF EGRESS
  
 7.2.1.4.3 DOOR LEAF ENCROACHMENT
 7.2.1.4.3.1 DURING ITS SWING, ANY DOOR LEAF IN A MEANS
 OF EGRESS SHALL LEAVE NOT LESS THAN ONE-HALF OF THE
 REQUIRED WIDTH OF AN AISLE, A CORRIDOR, A PASSAGEWAY,
 OR A LANDING UNOBSTRUCTED AND SHALL NOT PROJECT NOT
 MORE THAN 7 IN. INTO THE REQUIRED WIDTH OF AN AISLE, A
 CORRIDOR, A PASSAGE WAY, OR A LANDING, WHEN FULLY OPEN,
 UNLESS BOTH OF THE FOLLOWING CONDITIONS ARE MET:
 (1) THE DOOR OPENING PROVIDES ACCESS TO A STAIR IN AN
 EXISTING BUILDING.
 (2) THE DOOR OPENING MEETS THE REQUIREMENTS THAT LIMITS
 PROJECTION TO NOT MORE THAN 7 IN. INTO THE REQUIRED
 WIDTH OF THE STAIR LANDING WHEN THE DOOR
 LEAF IS FULLY OPEN.
  
 PER CHAPTER 12, NEW ASSEMBLY OCCUPANCIES
  
 12.2.3.8 MINIMUM CORRIDOR WIDTH. THE WIDTH OF ANY EXIT
 ACCESS CORRIDOR SERVING 50 OR MORE PERSONS SHALL BE NOT
 LESS THAN
 44 IN. (1120 MM).
  
  
 PLEASE FIELD VARIFY AND ENSURE THAT THE WIDTH OF THE
 REMANING CORRIDOR WHEN THE DOOR IS OPEN IS NOT LESS
 THAN 22".
  
  
  
  
 3) SHEET FS 1.1 - THE PTOPOSED FIRE SPRINKLER SYSTEM
 SHALL BE SUBMITTED UNDER SEPARATE SHOP DRAWINGS BY A
 CERTIFIED FIRE SPRINKLER CONTRACTOR.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop G GAS REVIEW
Rev No 2 Status P Date 2019-04-19 Cont ID  
Sent By gjohnson Date 2019-04-19 Time 16:47 Rev Time 0.00
Received By gjohnson Date 2019-04-19 Time 16:47 Sent To  
Notes
2019-04-19 16:50:10GAS REVIEWED UNDER MASTER # 17020359 REVISION #
 18071140
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  

Review Stop G GAS REVIEW
Rev No 1 Status N Date 2018-11-01 Cont ID  
Sent By gjohnson Date 2018-11-01 Time 09:16 Rev Time 0.00
Received By gjohnson Date 2018-11-01 Time 09:16 Sent To  
Notes
2018-11-01 09:16:30GAS PLAN REVIEW
 A GAS PLAN HAS NOT BEEN INCLUDED IN THIS SUBMITTAL
 PACKAGE. A GAS PLAN REVIEW HAS NOT BEEN PERFORMED AT
 THIS TIME. A SEPARATE GAS PERMIT AND PLANS WILL BE
 REQUIRED FOR A CONTRACTOR TO PERFORM THE RELATED WORK.
 PROVIDE COMPLETE PLANS, APPLIANCE/ EQUIPMENT
 SPECIFICATIONS AND GAS RISER THAT REFLECT THE ENTIRE
 SCOPE OF GAS WORK TO BE DONE. WPB AMEND. TO FBC SEC.
 107.2.1.
  
 GAS APPLIANCES SHALL BE LISTED AND LABELED PER THE
 FBC-R, SEC. G2404.3.
 GAS APPLIANCES SHALL BE LISTED AND LABELED PER FBC-FUEL
 GAS SEC. 301.3.
  
 A SEPARATE PERMIT AND PLANS IS REQUIRED FOR THE GAS
 INSTALLATION OR MODIFICATION OF SYSTEM.
  
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2018-12-05 Cont ID  
Sent By gjohnson Date 2018-12-05 Time 09:06 Rev Time 0.00
Received By gjohnson Date 2018-11-21 Time 16:36 Sent To E
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-11-15 Cont ID  
Sent By cpuell Date 2018-11-15 Time 10:04 Rev Time 0.00
Received By cpuell Date 2018-10-09 Time 10:34 Sent To  
Notes
2018-11-14 13:39:05TO LMARCHAN.
2018-10-11 10:34:37B05

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status P Date 2018-12-06 Cont ID  
Sent By dbattles Date 2018-12-06 Time 09:08 Rev Time 0.00
Received By dbattles Date 2018-12-06 Time 09:08 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2018-11-29 Cont ID  
Sent By dbattles Date 2018-11-29 Time 11:14 Rev Time 0.00
Received By dbattles Date 2018-11-29 Time 11:14 Sent To  
Notes
2018-11-29 12:04:27DYLAN BATTLES
 BUILDING PLANS EXAMINER I
 [email protected]
 561-805-6718
  
 IMPACT STAMP WAS APPLIED TO SHEET A-003R WHICH IS NOW
 VOIDED.
 THIS SHEET WILL BE RETAINED FOR RECORD OF STAMP.
  
 [FBC AMENDED 109]
 CURRENTLY THE ONLY THING MISSING TO APPROVE IMPACT IS
 FINAL REVIEW OF PLUMBING TO PASS AND THERE IS NO
 RECEIPT FOR IMPACT FEE PAYMENT WITH THE PERMIT
 DOCUMENTS.
 PLEASE PROVIDE COPY OF RECEIPT FROM THE PBC IMPACT
 OFFICE FROM THE STAMP ON 11/20/18.
 IT MAY HAVE NO FEES PAID, BUT IT SHOULD HAVE AN MU
 NUMBER GENERATED FROM THE IMPACT FEE REVIEW.
  
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2018-10-24 Cont ID  
Sent By ccole Date 2018-10-23 Time 07:11 Rev Time 0.00
Received By ccole Date 2018-10-23 Time 07:11 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2018-12-05 Cont ID  
Sent By gjohnson Date 2018-12-05 Time 09:02 Rev Time 0.00
Received By gjohnson Date 2018-12-05 Time 09:02 Sent To  
Notes
2018-12-05 09:04:51PROVISO:
 1. THE LAVATORY SINKS IN THE BATHROOM SHALL SUPPLY
 TEMPERED WATER ONLY THROUGH A TEMPERATURE LIMITING
 DEVICE THAT COMPLIES WITH ASSE 1070 OR CSA B125.3. THE
 MIXING VALVE ON THE WHOLE HOT WATER SYSTEM DOES NOT
 COMPLY WITH ASSE 1070 OR CSA B125.3 SHALL COMPLY WITH
 FBC PL 416.5
 2. A HOT WATER RECIRCULATION SYSTEM IS REQUIRED FOR THE
 BAR SINK IT IS SHOWN ON THE WATER HEATER DETAIL ON
 SHT.P0.1 BUT IS NOT SHOWN ON THE FLOOR PLAN OR THE
 WATER ISOMETRIC. SHALL COMPLY WITH FBC PL 607.2
  
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2018-11-01 Cont ID  
Sent By gjohnson Date 2018-11-01 Time 09:03 Rev Time 0.00
Received By gjohnson Date 2018-11-01 Time 09:03 Sent To  
Notes
2018-11-01 09:03:301ST REVIEW:
 2017 FLORIDA BUILDING CODE 6TH EDITION
 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH
 EDITION
  
 PLUMBING COMMENTS:
  
 1. PLEASE PROVIDE ENLARGED DETAIL FLOOR PLAN SHOWING
 THE CLEAR FLOOR SPACE FOR THE TOILETS AND LAVATORIES
 WITH DIMENSIONS. PER FBC ACC 604.3.1, 606.2
  
 2. PER FBC ACC CH6 PLEASE PROVIDE DETAILS SHOWING
 HEIGHT REQUIREMENTS FOR ACCESSIBILITY FOR THE
 FOLLOWING.
 A) FBC ACC 606.3 HEIGHT. LAVATORIES AND SINKS SHALL BE
 INSTALLED WITH THE FRONT OF THE HIGHER OF THE RIM OR
 COUNTER SURFACE 34 INCHES MAXIMUM ABOVE THE FINISH
 FLOOR OR GROUND.
 B) FBC ACC 604.7 DISPENSERS. TOILET PAPER DISPENSERS
 SHALL COMPLY WITH 309.4 AND SHALL BE 7 INCHES MINIMUM
 AND 9 INCHES MAXIMUM IN FRONT OF THE WATER CLOSET
 MEASURED TO THE CENTERLINE OF THE DISPENSER. THE OUTLET
 OF THE DISPENSER SHALL BE 15 INCHES MINIMUM AND 48
 INCHES MAXIMUM ABOVE THE FINISH FLOOR.
 C) FBC ACC 604.4 SEATS. THE SEAT HEIGHT OF A WATER
 CLOSET ABOVE THE FINISH FLOOR SHALL BE 17 INCHES
 MINIMUM AND 19 INCHES MAXIMUM MEASURED TO THE TOP OF
 THE SEAT. SEATS SHALL NOT BE SPRUNG TO RETURN TO A
 LIFTED POSITION.
 D) FBC ACC 604.2 LOCATION. THE WATER CLOSET SHALL BE
 POSITIONED WITH A WALL OR PARTITION TO THE REAR AND TO
 ONE SIDE. THE CENTERLINE OF THE WATER CLOSET SHALL BE
 16 INCHES MINIMUM TO 18 INCHES MAXIMUM FROM THE SIDE
 WALL OR PARTITION,
 E) FBC ACC 604.5.1 SIDE WALL. THE SIDE WALL GRAB BAR
 SHALL BE 42 INCHES LONG MINIMUM, LOCATED 12 INCHES
 MAXIMUM FROM THE REAR WALL AND EXTENDING 54 INCHES
 MINIMUM FROM THE REAR WALL.
 F) FBC ACC 604.5.2 REAR WALL. THE REAR WALL GRAB BAR
 SHALL BE 36 INCHES LONG MINIMUM AND EXTEND FROM THE
 CENTERLINE OF THE WATER CLOSET 12 INCHES MINIMUM ON ONE
 SIDE AND 24 INCHES MINIMUM ON THE OTHER SIDE.
 G) FBC ACC 609.4 POSITION OF GRAB BARS. GRAB BARS SHALL
 BE INSTALLED IN A HORIZONTAL POSITION, 33 INCHES
 MINIMUM AND 36 INCHES MAXIMUM ABOVE THE FINISH FLOOR
 MEASURED TO THE TOP OF THE GRIPPING SURFACE.
 H) FBC ACC 603.3 MIRRORS. MIRRORS LOCATED ABOVE
 LAVATORIES OR COUNTERTOPS SHALL BE INSTALLED WITH THE
 BOTTOM EDGE OF THE REFLECTING SURFACE 40 INCHES MAXIMUM
 ABOVE THE FINISH FLOOR OR GROUND. MIRRORS NOT LOCATED
 ABOVE LAVATORIES OR COUNTERTOPS SHALL BE INSTALLED WITH
 THE BOTTOM EDGE OF THE REFLECTING SURFACE 35 INCHES
 MAXIMUM ABOVE THE FINISH FLOOR OR GROUND.
  
 3. PER FBC PL 1108.1 WHERE ROOF DRAINS ARE REQUIRED,
 SECONDARY (EMERGENCY OVERFLOW) ROOF DRAINS OR SCUPPERS
 SHALL BE PROVIDED WHERE THE ROOF PERIMETER CONSTRUCTION
 EXTENDS ABOVE THE ROOF IN SUCH A MANNER THAT WATER WILL
 BE ENTRAPPED IF THE PRIMARY DRAINS ALLOW BUILDUP FOR
 ANY REASON. WHERE PRIMARY AND SECONDARY ROOF DRAINS ARE
 MANUFACTURED AS A SINGLE ASSEMBLY, THE INLET AND OUTLET
 FOR EACH DRAIN SHALL BE INDEPENDENT. AND SHALL COMPLY
 WITH FBC PL 1108.2 AND 1108.3
  
 4. ARE THE ROOF SCUPPERS ON THE WEST SIDE OF THE
 EXISTING ROOF AREA 5 DUMPING INTO A DOWN SPOUT OR ONTO
 THE AREA 2 + 3 ROOFS PLEASE CLARIFY. PER WPB AMEND TO
 FBC 107.2.1
  
 5. PLEASE PROVIDE A STORM DRAIN ISOMETRIC DRAWING. PER
 WPB AMEND TO FBC 107.3.5.1.3(13)
  
 6. HOW WILL THE FLOOR DRAIN IN THE DUMPSTER ENCLOSURE
 BE PROTECTED FROM RECEIVING STORM WATER DISCHARGE.
 STORM WATER SHALL NOT DISCHARGE INTO THE SANITARY
 SEWER. PER WPB CODE OF ORDINANCE SEC. 90-126.(5)
  
 7. PLEASE PROVIDE MANUFACTURE SIZING CALCULATIONS AND
 INSTALLATION GUIDE FROM SCHIER FOR THE GREASE
 INTERCEPTOR. PER WPB AMEND TO FBC 107.2.1
  
 8. UNDER THE KITCHEN PLUMBING SCHEDULE IT LIST $ OF THE
 K7 HAND SINKS THE PLAN ONLY SHOWS ONE PLEASE CLARIFY.
 PER WPB AMEND TO FBC 107.2.1
  
 9. ONLY THE LAVATORIES IN THE BATHROOMS SHALL BE
 SUPPLIED WITH TEMPERED WATER ONLY ALL OTHER PLUMBING
 FIXTURES THAT ARE USED FOR CULINARY PURPOSES,
 CLEANSING, LAUNDRY OR BUILDING MAINTENANCE PURPOSES
 SHALL HAVE HOT WATER. PER FBC PL 607.1, 416.5, 202
  
 10. PLEASE PLACE NOTE ON PLAN SEPARATE PERMITS ARE
 REQUIRED FOR THE GREASE INTERCEPTOR, BACKFLOW DEVICE AT
 THE METER AND THE GAS. PER WPB AMEND TO FBC 107.2.1
  
  
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  

Review Stop P-GREASE GREASE INTERCEPTOR/TRAP REVIEW
Rev No 2 Status P Date 2018-12-05 Cont ID  
Sent By gjohnson Date 2018-12-05 Time 09:02 Rev Time 0.00
Received By gjohnson Date 2018-12-05 Time 09:02 Sent To  
Notes
***NONE***

Review Stop P-GREASE GREASE INTERCEPTOR/TRAP REVIEW
Rev No 1 Status F Date 2018-11-01 Cont ID  
Sent By gjohnson Date 2018-11-01 Time 09:12 Rev Time 0.00
Received By gjohnson Date 2018-11-01 Time 09:12 Sent To  
Notes
2018-11-01 09:12:39SEE PLUMBING COMMENTS

Review Stop Z ZONING
Rev No 1 Status P Date 2018-11-14 Cont ID  
Sent By aaponte Date 2018-11-14 Time 13:37 Rev Time 0.00
Received By aaponte Date 2018-11-14 Time 13:37 Sent To  
Notes
2018-11-14 13:38:28PROVISO: ANY NEW MECHANICAL EQUIPMENT ON ROOF SHALL BE
 SCREENED WITH LOUVERS OR WALLS AS TALL AS EQUIPMENT.