Plan Review Details - Permit 18100337
Plan Review Stops For Permit 18100337
Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2018-12-21 Cont ID  
Sent By tklarge Date 2018-12-21 Time 07:04 Rev Time 0.00
Received By tklarge Date 2018-12-06 Time 14:34 Sent To  
Notes
2018-12-07 14:34:29RESUB ROUTED TO TKLARGE

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2018-11-26 Cont ID  
Sent By tklarge Date 2018-11-26 Time 06:17 Rev Time 0.00
Received By tklarge Date 2018-11-05 Time 14:56 Sent To  
Notes
2018-11-06 14:56:13RESUB ROUTED TO ZONING INBOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-10-17 Cont ID  
Sent By mcruz Date 2018-10-17 Time 15:40 Rev Time 0.00
Received By mcruz Date 2018-10-09 Time 09:28 Sent To PC
Notes
2018-10-11 09:28:44ROUTED TO PLUMBING INBOX

Review Stop P PLUMBING
Rev No 3 Status P Date 2018-12-21 Cont ID  
Sent By tklarge Date 2018-12-21 Time 07:03 Rev Time 0.00
Received By tklarge Date 2018-12-20 Time 06:35 Sent To I
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2018-11-26 Cont ID  
Sent By mcruz Date 2018-11-26 Time 13:16 Rev Time 0.00
Received By tklarge Date 2018-11-26 Time 05:28 Sent To I
Notes
2018-11-26 06:15:491) THERE ARE COPIES OF THE SAME SHEET E-1 THAT SHOW TWO
 DIFFERENT DETAILS ON THE PLANS AND SEVERAL LOOSE PAGES.
 THERE ARE ALSO TWO COPIES OF A SHEET M.2. SUBMIT TWO
 COMPLETE SETS OF PLANS THAT CONTAIN ALL THE DRAWINGS
 FOR THIS PROJECT FOR REVIEW. WPB AMEND. TO FBC SEC.
 107.1.
 2) COPIES OF A PUMP PERFORMANCE CURVE, NUMBERING SYSTEM
 AND A DIMENSIONS AND WEIGHT SHEET HAVE BEEN SUBMITTED
 FOR REVIEW. EXPLAIN HOW THIS COMPLIES WITH THE REVIEW
 COMMENT FOR SUBMITTING TWO COPIES OF THE MANUFACTURER'S
 SPECIFICATIONS FOR THE PUMPS. THERE ARE MORE THAN 4
 PAGES IN THE MANUFACTURER'S SPECIFICATIONS. WPB AMEND.
 TO FBC SEC. 107.2.1. SUBMIT TWO CCOMPLETE COPIES OF THE
 MANUFACTURER'S PUMP SPECIFICATIONS FOR REVIEW. 2ND
 REQUEST.
 3) PRESSURE REDUCING VALVES ARE REQUIRED IF THE STSTIC
 WATER PRESSURE WITHIN THE BUILDING EXCEEDS 80 PSI.
 PRESSURE REDUCING VALVES SHALL COMPLY WITH 2017 FBC
 SEC. 604.8. INDICATE ON THE PLANS WHAT THE PROPOSED
 STATIC PRESSURE OF THE SYSTEM WILL BE AND IF THE
 EXISTING SYSTEM IS EQUIPPED WITH PRESSURE REDUCCING
 VALVES OR IF PRESSURE REDUCING VALVES WILL NEED TO BE
 INSTALLED. WPB AMEND TO FBC SEC. 107.2.1.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2018-10-15 Cont ID  
Sent By tklarge Date 2018-10-15 Time 10:09 Rev Time 0.00
Received By tklarge Date 2018-10-15 Time 06:32 Sent To Z
Notes
2018-10-15 10:09:081) SUBMIT TWO COPIES OF A SITE PLAN SHOWING THE
 LOCATION OF THE SLAB / PUMPS.FBC SECS. 107.1,
 107.3.5.1.
 2) SUBMIT TWO COPIES OF THE MANUFACTURER'S
 SPECIFICATIONS FOR THE PUMPS.FBC SEC. 107.2.1.
 3) SUBMIT ANCHORING DETAILS FOR THE PUMPS. INDICATE
 TYPE, LENGTH, NUMBER & DIAMETER OF THE FASTENERS. FBC
 107.2.1.
 4) SHOW THE TYPE AND SIZE OF ALL PIPE ON THE
 DRAWING.FBC 107.2.1.
 5) SUBMIT TWO COPIES OF THE MANUFACTURER'S
 SPECIFICATIONS FOR THE ALUMINUM HOUSING.
 6) A LOW-PRESSURE CUTOFF SHALL BE INSTALLED ON ALL
 BOOSTER PUMPS IN ACCORDANCE WITH THE 2017 FBC-PLUMBING
 SEC.606.5.5.
 7) SUBMIT DETAILS FOR THE SUPPORTING OF THE PIPE.
 COMPLY WITH 2017 FPC-PLUMBING TABLE 308.5.
 8) INDICATE ON THE PLANS IF YOU ARE REPLACING EXISTING
 PUMPS OR ADDING NEW PUMPS TO AN EXISTING DOMESTIC WATER
 SYSTEM, PRESSURE REDUCING VALVES WILL BE REQUIRED IF
 THE WATER PRESSURE WITHIN THE BUILDING EXCEEDS 80 PSI
 STATIC PRESSURE. VALVES SHALL COMPLY WITH 2017
 FBC-PLUMBING SEC.604.8.
  
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  

Review Stop Z ZONING
Rev No 2 Status P Date 2018-11-09 Cont ID  
Sent By mcruz Date 2018-11-09 Time 13:16 Rev Time 0.00
Received By mcruz Date 2018-11-09 Time 10:10 Sent To P
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2018-10-17 Cont ID  
Sent By mcruz Date 2018-10-17 Time 15:40 Rev Time 0.00
Received By mcruz Date 2018-10-17 Time 15:35 Sent To PC
Notes
2018-10-17 15:40:18ZONING REVIEW FAILED, DUE TO THE FOLLOWING:
  
 1) PROVIDE 2 COPIES OF PROPERTY SURVEY.
 2) INDICATE OF SURVEY THE LOCATION OF THE PROPOSED
 WATER BOOSTER PUMP STATION.
 3) IS THERE ARE LANDSCAPING THAT IS BEING REMOVED AS A
 RESULT OF THE PROPOSED WORK? IF SO, SHOW WHERE
 LANDSCAPING WILL BE REPLACED.
 4) RESPOND TO COMMENTS IN WRITING.
  
 FOR ADDITIONAL INFORMATION, THE ZONING AND LAND
 DEVELOPMENT REGULATIONS MAY BE VIEWED ONLINE AT
 WWW.MUNICODE.COM OR VISIT THE CITY OF WEST PALM BEACH
 PLANNING DEPARTMENT WEBSITE AT
 WWW.CITYOFWPB.COM/PLAN/INDEX.HTM.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE DO NOT HESITATE TO
 CONTACT ME.
  
 MAGGIE CRUZ
 ASSOCIATE PLANNER
 PLANNING AND ZONING DEPARTMENT
 TEL: 561-822-1442
 E-MAIL: [email protected]