| 2018-10-16 18:52:50 | RESIDENTIAL (R2) BUILDING REVIEW COMMENTS |
| | CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS. |
| | |
| | ORIGINAL COMMENT: |
| | 1- PROVIDE SHUTTERS COMPLETE INSTALLATION SCHEDULE AS |
| | REQUIRED BY CITY IMPLEMENTATION STANDARD FOR WIND-BORNE |
| | DEBRIS IMPACT PROTECTION FOR THE FLORIDA BUILDING CODE. |
| | SEE CITY SAMPLE. ALL THE COLUMNS NEED TO BE COMPLETED. |
| | ALTERNATIVELY, YOU MAY PROVIDE COMPLETE INSTALLATION |
| | SCHEDULE IN ANY OTHER FORMAT AS LONG AS ALL THE |
| | REQUIRED INFORMATION IS PROVIDED. |
| | |
| | RESPONSE: |
| | A) ACCORDING TO DESIGN PRESSURES HIGHLIGHTED ON |
| | ENGINEER CALCULATIONS THE ANCHOR SPACING FOR TOP |
| | CONNECTION IS 5.5" FOR TYPE OF ANCHOR SPECIFIED NOT |
| | 6.5". AND THE ANCHOR SPACING FOR BOTTOM CONNECTION IS |
| | 4" NOT 7.5". REVISE AS REQUIRED BY THE PRODUCT APPROVAL |
| | SUBMITTED. |
| | SEC. 107.2.1 CITY AMENDMENTS. |
| | |
| | B) CLEARLY SPECIFY THE MINIMUM EDGE DISTANCE AS |
| | REQUIRED BY INSTALLATION DETAILS "G" AND "J" ON PRODUCT |
| | APPROVAL SUBMITTED. CLARIFY WHAT IS EDGE DISTANCE |
| | "TRAPPED" AS SPECIFIED ON THE SHUTTER INSTALLATION |
| | SCHEDULE SUBMITTED?. |
| | SEC. 107.2.1 CITY AMENDMENTS. |
| | |
| | ORIGINAL COMMENT: |
| | 2- ENGINEER CALCULATIONS SUBMITTED NEED TO HAVE THE |
| | ORIGINAL SEAL AND SIGNATURE OF THE ENGINEER OF RECORD |
| | AS REQUIRED BY SEC. 61G15-23.003 FAC AND CHAPTER 471 |
| | F.S. WHEN SUBMITTING PLANS/DOCUMENTS FOR PUBLIC |
| | RECORDS. |
| | |
| | RESPONSE: |
| | REPEAT COMMENT. NOT ADDRESSED. |
| | |
| | |
| | IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT |
| | JULIO GOMEZ |
| | COMMERCIAL COMBINATION PLANS EXAMINER |
| | DEVELOPMENT SERVICES DEPARTMENT |
| | BUILDING DIVISION |
| | (561)805-6712 |
| | [email protected] |
| | |