Plan Review Details - Permit 18100294
Plan Review Stops For Permit 18100294
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2018-10-30 Cont ID  
Sent By jgomez Date 2018-10-30 Time 16:00 Rev Time 0.00
Received By jgomez Date 2018-10-30 Time 13:11 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2018-10-24 Cont ID  
Sent By jgomez Date 2018-10-24 Time 13:49 Rev Time 0.00
Received By jgomez Date 2018-10-24 Time 13:05 Sent To  
Notes
2018-10-24 13:52:40RESIDENTIAL (R3) BUILDING REVIEW COMMENTS
 CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS.
  
 1- PRODUCT APPROVAL UPLOADED UNDER THE TITLE "RIZZO
 HORIZONTAL ROLLER FL.PDF" IS FOR CASEMENT WINDOWS.
 UPLOAD CORRECT PRODUCT APPROVAL FOR HORIZONTAL ROLLER
 WINDOWS.
 SEC. 107.2.1 CITY AMENDMENTS AND FAC 61G20-3.001.
  
 NOTE: FOR INFORMATION ONLY. SEE SEC. 702.4 FBC-EXISTING
 BUILDING CODE. WINDOW OPENING CONTROL DEVICES IN WINDOW
 REPLACEMENT ARE REQUIRED WHEN THE FOLLOWING APPLY:
  
  
 702.4 WINDOW OPENING CONTROL DEVICES.
  
 IN GROUP R-2 OR R-3 BUILDINGS CONTAINING DWELLING UNITS
 AND ONE- AND TWO-FAMILY DWELLINGS AND TOWNHOUSES
 REGULATED BY THE FLORIDA BUILDING CODE, RESIDENTIAL,
 WINDOW OPENING CONTROL DEVICES COMPLYING WITH ASTM
 F2090 SHALL BE INSTALLED WHERE AN EXISTING WINDOW IS
 REPLACED AND WHERE ALL OF THE FOLLOWING APPLY TO THE
 REPLACEMENT WINDOW:
 1.THE WINDOW IS OPERABLE;
 2. THE WINDOW REPLACEMENT INCLUDES REPLACEMENT OF THE
 SASH AND THE FRAME;
 3.ONE OF THE FOLLOWING APPLIES:
 3.1.IN GROUP R-2 OR R-3 BUILDINGS CONTAINING DWELLING
 UNITS, THE TOP OF THE SILL OF THE WINDOW OPENING IS AT
 A HEIGHT LESS THAN 36 INCHES (915 MM) ABOVE THE
 FINISHED FLOOR; OR
 3.2. IN ONE- AND TWO-FAMILY DWELLINGS AND TOWNHOUSES
 REGULATED BY THE FLORIDA BUILDING CODE, RESIDENTIAL,
 THE TOP SILL OF THE WINDOW OPENING IS AT A HEIGHT LESS
 THAN 24 INCHES (610 MM) ABOVE THE FINISHED FLOOR;
 4.THE WINDOW WILL PERMIT OPENINGS THAT WILL ALLOW
 PASSAGE OF A 4-INCH-DIAMETER (102 MM) SPHERE WHEN THE
 WINDOW IS IN ITS LARGEST OPENED POSITION; AND
 5.THE VERTICAL DISTANCE FROM THE TOP OF THE SILL OF THE
 WINDOW OPENING TO THE FINISHED GRADE OR OTHER SURFACE
 BELOW, ON THE EXTERIOR OF THE BUILDING, IS GREATER THAN
 72 INCHES (1829 MM).
 THE WINDOW OPENING CONTROL DEVICE, AFTER OPERATION TO
 RELEASE THE CONTROL DEVICE ALLOWING THE WINDOW TO FULLY
 OPEN, SHALL NOT REDUCE THE MINIMUM NET CLEAR OPENING
 AREA OF THE WINDOW UNIT TO LESS THAN THE AREA REQUIRED
 BY THE FLORIDA BUILDING CODE, BUILDING.
  
 EXCEPTIONS:
 1.OPERABLE WINDOWS WHERE THE TOP OF THE SILL OF THE
 WINDOW OPENING IS LOCATED MORE THAN 75 FEET (22 860 MM)
 ABOVE THE FINISHED GRADE OR OTHER SURFACE BELOW, ON THE
 EXTERIOR OF THE ROOM, SPACE OR BUILDING, AND THAT ARE
 PROVIDED WITH WINDOW FALL PREVENTION DEVICES THAT
 COMPLY WITH ASTM F2006.
 2.OPERABLE WINDOWS WITH OPENINGS THAT ARE PROVIDED WITH
 WINDOW FALL PREVENTION DEVICES THAT COMPLY WITH ASTM
 F2090.
  
  
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2018-10-30 Cont ID  
Sent By jgomez Date 2018-10-30 Time 16:00 Rev Time 0.00
Received By jgomez Date 2018-10-24 Time 07:52 Sent To I
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-10-24 Cont ID  
Sent By jgomez Date 2018-10-24 Time 14:06 Rev Time 0.00
Received By jgomez Date 2018-10-08 Time 09:36 Sent To I
Notes
***NONE***