Plan Review Details - Permit 18100278
Plan Review Stops For Permit 18100278
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2019-01-25 Cont ID  
Sent By cthroop Date 2019-01-25 Time 15:41 Rev Time 0.00
Received By cthroop Date 2019-01-25 Time 15:41 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2019-01-15 Cont ID  
Sent By cthroop Date 2019-01-15 Time 11:20 Rev Time 0.00
Received By cthroop Date 2019-01-14 Time 08:26 Sent To  
Notes
2019-01-15 11:26:23BUILDING PLAN REVIEW
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 BUILDING PLANS EXAMINER, PX3169
 1&2 FAMILY PLANS EXAMINER, SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 3RD REVIEW
 RESULTS: DENIED
 YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED
 BELOW.
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 ADVISORY:
 F.S. 553.80 (2) (B)
 (B)?WITH RESPECT TO EVALUATION OF DESIGN PROFESSIONALS?
 DOCUMENTS, IF A LOCAL GOVERNMENT FINDS IT NECESSARY, IN
 ORDER TO ENFORCE COMPLIANCE WITH THE FLORIDA BUILDING
 CODE AND ISSUE A PERMIT, TO REJECT DESIGN DOCUMENTS
 REQUIRED BY THE CODE THREE OR MORE TIMES FOR FAILURE TO
 CORRECT A CODE VIOLATION SPECIFICALLY AND CONTINUOUSLY
 NOTED IN EACH REJECTION, INCLUDING, BUT NOT LIMITED TO,
 EGRESS, FIRE PROTECTION, STRUCTURAL STABILITY, ENERGY,
 ACCESSIBILITY, LIGHTING, VENTILATION, ELECTRICAL,
 MECHANICAL, PLUMBING, AND GAS SYSTEMS, OR OTHER
 REQUIREMENTS IDENTIFIED BY RULE OF THE FLORIDA BUILDING
 COMMISSION ADOPTED PURSUANT TO CHAPTER 120, THE LOCAL
 GOVERNMENT SHALL IMPOSE, EACH TIME AFTER THE THIRD SUCH
 REVIEW THE PLANS ARE REJECTED FOR THAT CODE VIOLATION,
 A FEE OF FOUR TIMES THE AMOUNT OF THE PROPORTION OF THE
 PERMIT FEE ATTRIBUTED TO PLANS REVIEW.
  
 1. NOA 17-0630.08 SUBMITTED FOR REVIEW DOES NOT APPEAR
 ON THE SUBMITTED WINDOW SCHEDULE. PLEASE CLARIFY.
 2. PROVIDE PRODUCT APPROVALS FOR PROPOSED DOORS.
  
 FBC 107.3.4 ? PROVIDE PRODUCT APPROVALS FOR THOSE
 PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED
 AND APPROVED IN WRITING BY THE DESIGNER OF RECORD.
 SPECIFICALLY, PROVIDE WINDOW AND DOOR SUBMITTALS.
  
 PROVISO
  
 107.3.4.1 DEFERRED SUBMITTALS. FOR THE PURPOSES OF THIS
 SECTION, DEFERRED SUBMITTALS ARE DEFINED AS THOSE
 PORTIONS OF THE DESIGN THAT ARE NOT SUBMITTED AT THE
 TIME OF THE APPLICATION AND THAT ARE TO BE SUBMITTED TO
 THE BUILDING OFFICIAL WITHIN A SPECIFIED PERIOD.
 DEFERRAL OF ANY SUBMITTAL ITEMS SHALL HAVE THE PRIOR
 APPROVAL OF THE BUILDING OFFICIAL. THE REGISTERED
 DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE SHALL LIST
 THE DEFERRED SUBMITTALS ON
 THE CONSTRUCTION DOCUMENTS FOR REVIEW BY THE BUILDING
 OFFICIAL.
 DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE
 SUBMITTED TO THE REGISTERED DESIGN PROFESSIONAL IN
 RESPONSIBLE CHARGE WHO SHALL REVIEW THEM AND FORWARD
 THEM TO THE BUILDING OFFICIAL WITH A NOTATION
 INDICATING THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE
 BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO
 THE DESIGN OF THE BUILDING. THE DEFERRED SUBMITTAL
 ITEMS SHALL NOT BE INSTALLED UNTIL THE DEFERRED
 SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE BUILDING
 OFFICIAL.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO SUBMITTAL AND LEAVE THE PREVIOUSLY
 REVIEWED SHEETS DETACHED.
  
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2018-12-31 Cont ID  
Sent By cthroop Date 2018-12-31 Time 13:12 Rev Time 0.00
Received By cthroop Date 2018-12-31 Time 11:28 Sent To  
Notes
2018-12-31 13:14:42BUILDING PLAN REVIEW
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 BUILDING PLANS EXAMINER, PX3169
 1&2 FAMILY PLANS EXAMINER, SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 2ND REVIEW
 RESULTS: DENIED
 YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED
 BELOW.
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. PROVIDE PRODUCT APPROVALS FOR NEW WINDOWS AND DOORS.
  
 FBC 107.3.4 ? PROVIDE PRODUCT APPROVALS FOR THOSE
 PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED
 AND APPROVED IN WRITING BY THE DESIGNER OF RECORD.
 SPECIFICALLY, PROVIDE WINDOW AND DOOR SUBMITTALS.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO SUBMITTAL AND LEAVE THE PREVIOUSLY
 REVIEWED SHEETS DETACHED.
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2018-11-15 Cont ID  
Sent By jgomez Date 2018-11-15 Time 09:52 Rev Time 0.00
Received By jgomez Date 2018-11-15 Time 07:50 Sent To  
Notes
2018-11-15 09:52:47RESIDENTIAL (R3)ALTERATION, BUILDING REVIEW COMMENTS
 CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS.
  
 1- PLANS NEED TO SPECIFY THE CURRENT CODE FBC 6TH
 EDITION (2017). CHAPTER 553 FLORIDA STATUTE.
  
 2- PLANS NEED TO SPECIFY THE DESIGN CRITERIA, INCLUDING
 ULTIMATE AND NOMINAL WIND LOADS, BUILDING EXPOSURE,
 MEAN ROOF HEIGHT, DESIGN PRESSURES FOR EXTERIOR DOORS
 AND WINDOWS. SEC. R301.2.1 FBC-RESIDENTIAL.
  
 3- PROVIDE COMPLETE SECOND FLOOR FRAMING PLAN AND ROOF
 FRAMING PLAN FRO AREAS TO BE RE-FRAMED. SPECIFY ALL
 FRAMING MEMBERS SIZE, SPACING AND CONNECTORS. SEC.
 R301.1 FBC-RESIDENTIAL.
  
 4- PROVIDE COMPLETE WALL FRAMING DETAILS AND
 SPECIFICATIONS FOR WALL AREAS TO BE RE-FRAMED. SPECIFY
 ALL FRAMING MEMBERS SIZE, SPACING AND CONNECTORS AND
 INTERIOR AND EXTERIOR COMPONENTS (DRYWALL, WALL
 SHEATHING, STUCCO, ETC.). SEC. R301.1 FBC-RESIDENTIAL.
  
 5- PROVIDE COMPLETE WINDOW WALL FRAMING DETAILS AND
 SPECIFICATIONS FOR RELOCATED WINDOW AS SPECIFIED ON
 DEMOLITION ROOF FLOOR PLAN. SPECIFY ALL FRAMING MEMBERS
 SIZE AND CONNECTORS. SEC. R301.1 FBC-RESIDENTIAL.
  
 6- CLEARLY SPECIFY TYPE AND SIZE OF EXISTING WINDOWS
 AND TYPE AND SIZE OF PROPOSED WINDOWS TO VERIFY
 COMPLIANCE WITH THE EGRESS REQUIREMENTS OF SEC. 702.5
 FBC-EXISTING BUILDING.
 NOTE: CLEARLY IDENTIFY IN ALL FLOOR PLANS ALL ROOMS.
  
 702.5EMERGENCY ESCAPE AND RESCUE OPENINGS.
 WHERE WINDOWS ARE REQUIRED TO PROVIDE EMERGENCY ESCAPE
 AND RESCUE OPENINGS IN GROUP R-2 AND R-3 OCCUPANCIES
 AND ONE- AND TWO-FAMILY DWELLINGS AND TOWNHOUSES
 REGULATED BY THE FLORIDA BUILDING CODE, RESIDENTIAL,
 REPLACEMENT WINDOWS SHALL BE EXEMPT FROM THE
 REQUIREMENTS OF SECTIONS 1030.2, 1030.3 AND 1030.5 OF
 THE FLORIDA BUILDING CODE, BUILDING AND SECTIONS
 R310.21 AND R310.2.3 OF THE FLORIDA BUILDING CODE,
 RESIDENTIAL ACCORDINGLY, PROVIDED THE REPLACEMENT
 WINDOW IS THE MANUFACTURER?S LARGEST STANDARD SIZE
 WINDOW THAT WILL FIT WITHIN THE EXISTING FRAME OR
 EXISTING ROUGH OPENING. THE REPLACEMENT WINDOW SHALL BE
 PERMITTED TO BE OF THE SAME OPERATING STYLE AS THE
 EXISTING WINDOW OR A STYLE THAT PROVIDES FOR AN EQUAL
 OR GREATER WINDOW OPENING AREA THAN THE EXISTING
 WINDOW.
 WINDOW OPENING CONTROL DEVICES COMPLYING WITH ASTM
 F2090 SHALL BE PERMITTED FOR USE ON WINDOWS REQUIRED TO
 PROVIDE EMERGENCY ESCAPE AND RESCUE OPENINGS.
  
  
 7- CLEARLY IDENTIFY ON PLANS IF ANY SECOND FLOOR WINDOW
 WILL NEED WINDOW OPENING CONTROL DEVICES AS REQUIRED BY
 SEE SEC. 702.4 FBC-EXISTING BUILDING CODE. WINDOW
 OPENING CONTROL DEVICES IN WINDOW REPLACEMENT ARE
 REQUIRED WHEN THE FOLLOWING APPLY:
  
 702.4 WINDOW OPENING CONTROL DEVICES.
  
 IN GROUP R-2 OR R-3 BUILDINGS CONTAINING DWELLING UNITS
 AND ONE- AND TWO-FAMILY DWELLINGS AND TOWNHOUSES
 REGULATED BY THE FLORIDA BUILDING CODE, RESIDENTIAL,
 WINDOW OPENING CONTROL DEVICES COMPLYING WITH ASTM
 F2090 SHALL BE INSTALLED WHERE AN EXISTING WINDOW IS
 REPLACED AND WHERE ALL OF THE FOLLOWING APPLY TO THE
 REPLACEMENT WINDOW:
 1.THE WINDOW IS OPERABLE;
 2. THE WINDOW REPLACEMENT INCLUDES REPLACEMENT OF THE
 SASH AND THE FRAME;
 3.ONE OF THE FOLLOWING APPLIES:
 3.1.IN GROUP R-2 OR R-3 BUILDINGS CONTAINING DWELLING
 UNITS, THE TOP OF THE SILL OF THE WINDOW OPENING IS AT
 A HEIGHT LESS THAN 36 INCHES (915 MM) ABOVE THE
 FINISHED FLOOR; OR
 3.2. IN ONE- AND TWO-FAMILY DWELLINGS AND TOWNHOUSES
 REGULATED BY THE FLORIDA BUILDING CODE, RESIDENTIAL,
 THE TOP SILL OF THE WINDOW OPENING IS AT A HEIGHT LESS
 THAN 24 INCHES (610 MM) ABOVE THE FINISHED FLOOR;
 4.THE WINDOW WILL PERMIT OPENINGS THAT WILL ALLOW
 PASSAGE OF A 4-INCH-DIAMETER (102 MM) SPHERE WHEN THE
 WINDOW IS IN ITS LARGEST OPENED POSITION; AND
 5.THE VERTICAL DISTANCE FROM THE TOP OF THE SILL OF THE
 WINDOW OPENING TO THE FINISHED GRADE OR OTHER SURFACE
 BELOW, ON THE EXTERIOR OF THE BUILDING, IS GREATER THAN
 72 INCHES (1829 MM).
 THE WINDOW OPENING CONTROL DEVICE, AFTER OPERATION TO
 RELEASE THE CONTROL DEVICE ALLOWING THE WINDOW TO FULLY
 OPEN, SHALL NOT REDUCE THE MINIMUM NET CLEAR OPENING
 AREA OF THE WINDOW UNIT TO LESS THAN THE AREA REQUIRED
 BY THE FLORIDA BUILDING CODE, BUILDING.
  
 EXCEPTIONS:
 1.OPERABLE WINDOWS WHERE THE TOP OF THE SILL OF THE
 WINDOW OPENING IS LOCATED MORE THAN 75 FEET (22 860 MM)
 ABOVE THE FINISHED GRADE OR OTHER SURFACE BELOW, ON THE
 EXTERIOR OF THE ROOM, SPACE OR BUILDING, AND THAT ARE
 PROVIDED WITH WINDOW FALL PREVENTION DEVICES THAT
 COMPLY WITH ASTM F2006.
 2.OPERABLE WINDOWS WITH OPENINGS THAT ARE PROVIDED WITH
 WINDOW FALL PREVENTION DEVICES THAT COMPLY WITH ASTM
 F2090.
  
 8- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 FAC 61G20-3.001 FOR:
 (NOTE: THIS MAY BE SUBMITTED LATER AS A DEFERRED
 SUBMITTAL)
 A) FLAT ROOF. AND, CLEARLY MARK WHICH APPROVED ASSEMBLY
 IS GOING TO BE INSTALLED TO VERIFY COMPLIANCE WITH THE
 DESIGN PRESSURES OF SEC. R301.1 FBC-RESIDENTIAL. NOTE:
 IF THE SELECTED ASSEMBLY DOESN'T MEET THE DESIGN
 PRESSURES FOR ALL ROOF ZONES, THEN SIGNED AND SEALED
 RAS 117 CALCULATIONS ARE REQUIRED.
  
 B) ALL EXTERIOR DOORS AS SHOWN ON PLANS.
  
 C) ALL SINGLE HUNG WINDOWS AS SHOWN ON PLANS.
  
 D) ALL FIXED WINDOWS AS SHOWN ON PLANS.
  
 E) WINDOW MULLIONS AS SHOWN ON PLANS. AND, CLEARLY MARK
 MULLION SIZE TO VERIFY COMPLIANCE WITH THE CALCULATED
 DESIGN PRESSURES.
  
 F) HURRICANE SHUTTERS IF DOORS AND WINDOWS DON'T HAVE
 IMPACT GLAZING. AND, PROVIDE COMPLETE INSTALLATION
 SCHEDULE. SEE CITY SAMPLE.
  
 G) ALL STRUCTURAL CONNECTORS (FOR EXAMPLE SIMPSON
 CONNECTORS) SPECIFIED ON PLANS AND DETAILS. NOTE:
 PROVIDE ONLY THE FLORIDA PRODUCT APPROVAL COVER PAGE
 AND PAGE SHOWING THE SPECIFIED CONNECTOR OR DESIGN
 PROFESSIONAL TO LIST THE FLORIDA PRODUCT APPROVAL
 NUMBER NEXT TO EACH SPECIFIED CONNECTOR.
  
 9- DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS
 REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS.
  
 10- SIZE AND TYPE OF WINDOWS SHOWN IN THE WINDOW
 SCHEDULE ARE NOT CLEAR. SEC. 107.2.1 CITY AMENDMENTS.
 WINDOW W-1 IS NOT CLEAR IF IT'S A SINGLE HUNG WINDOW OR
 FIXED WINDOW. TYPICALLY A SH35 SINGLE HUNG WINDOW
 DOESN'T HAVE A 26-1/2" WIDTH (COORDINATE SIZE WITH
 WINDOW MANUFACTURER).
  
 11- THERE ARE A LOT OF TYPOS IN THE WINDOW SCHEDULE
 NOTES AND TERMITE PROTECTION NOTES. PLEASE REVISE AS
 REQUIRED TO AVOID CONFLICTS. SEC. 107.2.1 CITY
 AMENDMENTS.
  
  
 ****PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH
 COMMENT TO HELP EXPEDITE THE REVIEW PROCESS.
  
 ****PLEASE INSERT ANY REVISED DRAWING AND REMOVE OLD
 DRAWING. SUBMIT OLD DRAWINGS FOR REFERENCE OF ALREADY
 REVIEWED DRAWINGS. DO NOT STAPLE OLD DRAWINGS TO PLANS.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  
  

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2019-01-25 Cont ID  
Sent By cthroop Date 2019-01-25 Time 15:41 Rev Time 0.00
Received By cthroop Date 2019-01-25 Time 15:41 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2019-01-15 Cont ID  
Sent By cthroop Date 2019-01-15 Time 11:29 Rev Time 0.00
Received By cthroop Date 2019-01-14 Time 08:26 Sent To  
Notes
2019-01-15 11:31:37ELECTRICAL PLAN REVIEW
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 BUILDING PLANS EXAMINER, PX3169
 1&2 FAMILY PLANS EXAMINER, SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 3RD REVIEW
 RESULTS: DENIED
 YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED
 BELOW.
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 PREVIOUS COMMENTS THAT HAVE BEEN ADDRESSED
 SATISFACTORILY ARE MARKED AS CORRECTED. PREVIOUS
 COMMENTS THAT HAVE NOT BEEN ADDRESSED SATISFACTORILY
 HAVE ADDITIONAL COMMENTS IN PARENTHESES. ANY NEW
 COMMENTS WILL BE LISTED AFTER PREVIOUS COMMENTS.
  
 1. CORRECTED.
 2. CORRECTED.
  
 NEW COMMENTS:
  
 3. A MINIMUM OF TWO SMALL APPLIANCE BRANCH CIRCUITS
 SHALL BE INSTALLED FOR KITCHEN COUNTER TOP RECEPTACLES.
 PROVIDE CORRECTION. NEC 210.11(C)(1) , FBC RE E3703.2
 4. PROVIDE ACCURATE LOAD CALCULATION FOR SERVICE,
 INCLUDE EXISTING AND NEW LOADS TO CONFIRM CAPACITY OF
 SERVICE IS ADEQUATE. THE SQUARE FOOTAGE CALCULATION ON
 PLAN IS ONLY FOR 393 SQUARE FEET, WHICH DOES NOT AGREE
 WITH THE SQUARE FOOTAGE SHOWN ON PBC PAPA. NEC 215.2,
 220, 408.30; FBC RE E3602.2
 5. ONLY ONE SERVICE PER RESIDENTIAL ADDRESS IS
 PERMITTED. PROVIDE CORRECTION AND/OR CLARIFICATION. WPB
 FBC 107.2.1; NEC 230.2; FBC RE E3601.2
 6. IF NEW SERVICE IS PROPOSED, PROVIDE DETAILS OF
 EXISTING AND PROPOSED. PROVIDE AVAILABLE SHORT CIRCUIT
 CALCULATION FOR EACH PANEL INCLUDING INFORMATION FROM
 THE POWER COMPANY STATING WHAT THE AVAILABLE SHORT
 CIRCUIT CURRENT IS FOR THE SERVICE TO CONFIRM THE
 STATED AIC RATING OF THE SERVICE EQUIPMENT AND
 DOWNSTREAM PANELS IS ADEQUATE. NEC 110.9, 110.10; FBC
 RE E3606.3
 7. A SMOKE ALARM IS REQUIRED ON EACH LEVEL OF THE
 DWELLING UNIT. PROVIDE CORRECTION. FBC RE R314.3
 8. ALL BRANCH CIRCUITS THAT SUPPLY 120-VOLT,
 SINGLE-PHASE, 15- AND 20-AMPERE OUTLETS INSTALLED IN
 KITCHENS, FAMILY ROOMS, DINING ROOMS, LIVING ROOMS,
 PARLORS, LIBRARIES, DENS, BEDROOMS, SUN-ROOMS,
 RECREATIONS ROOMS, CLOSETS, HALLWAYS, LAUNDRY AREAS AND
 SIMILAR ROOMS OR AREAS SHALL BE AFCI PROTECTED. THIS
 INCLUDES LIGHTING AND POWER OUTLETS AND RECEPTACLES.
 SOME AREAS REQUIRE BOTH AFCI AND GFCI PROTECTION.
 PROVIDE CORRECTION. NEC 210.8, 210.12; FBC RE E3902;
 FBC EX 607.1.1 OR 801.1, 801.2, OR 901.2 AS APPLICABLE.
 9. GFCI PROTECTION IS REQUIRED FOR ALL EXTERIOR
 RECEPTACLE OUTLETS. PROVIDE CORRECTION. NEC 210.8; FBC
 RE E3902.3
 10. PROVIDE TAMPER RESISTANT RECEPTACLES PER CODE. A
 NOTE WILL SUFFICE. NEC 406.12; FBC RE E4002.14
 11. THERE APPEARS TO BE SOMETHING LOCATED IN FRONT OF
 ELECTRICAL PANEL. CLEARANCE IN FRONT OF THE PANEL IS
 REQUIRED. PROVIDE CORRECTION.NEC 110.26; FBC RE E3405.1
 12. PROVIDE LOCATION OF ELECTRICAL SERVICE ON PLAN. WPB
 FBC 107.2.1
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD
 SHEETS.
  
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2018-12-20 Cont ID  
Sent By jpearson Date 2018-12-20 Time 08:50 Rev Time 0.00
Received By jpearson Date 2018-12-20 Time 07:12 Sent To  
Notes
2019-01-02 15:23:09CONTRACT EMAILED, VALUE IS CORRECT. 1/2/19
  
  
2018-12-20 08:48:03CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 PREVIOUS COMMENTS THAT HAVE BEEN ADDRESSED
 SATISFACTORILY ARE MARKED AS CORRECTED. PREVIOUS
 COMMENTS THAT HAVE NOT BEEN ADDRESSED SATISFACTORILY
 HAVE ADDITIONAL COMMENTS IN PARENTHESES. ANY NEW
 COMMENTS WILL BE LISTED AFTER PREVIOUS COMMENTS.
  
 1. VALUE FOR WORK STATED ON PERMIT APPLICATION APPEARS
 LOW. PROVIDE COPY OF SIGNED CONTRACT WITH SCOPE AND
 VALUE OF WORK, TO INCLUDE ALL MATERIALS AND LABOR. THIS
 IS FOR TOTAL PROJECT, NOT JUST ELECTRICAL. FBC 109.3
 (NOT PROVIDED)
 2. CORRECTED.
  
 NEW COMMENTS:
  
 3. A MINIMUM OF TWO SMALL APPLIANCE BRANCH CIRCUITS
 SHALL BE INSTALLED FOR KITCHEN COUNTER TOP RECEPTACLES.
 PROVIDE CORRECTION. NEC 210.11(C)(1) , FBC RE E3703.2
 4. PROVIDE ACCURATE LOAD CALCULATION FOR SERVICE,
 INCLUDE EXISTING AND NEW LOADS TO CONFIRM CAPACITY OF
 SERVICE IS ADEQUATE. THE SQUARE FOOTAGE CALCULATION ON
 PLAN IS ONLY FOR 393 SQUARE FEET, WHICH DOES NOT AGREE
 WITH THE SQUARE FOOTAGE SHOWN ON PBC PAPA. NEC 215.2,
 220, 408.30; FBC RE E3602.2
 5. ONLY ONE SERVICE PER RESIDENTIAL ADDRESS IS
 PERMITTED. PROVIDE CORRECTION AND/OR CLARIFICATION. WPB
 FBC 107.2.1; NEC 230.2; FBC RE E3601.2
 6. IF NEW SERVICE IS PROPOSED, PROVIDE DETAILS OF
 EXISTING AND PROPOSED. PROVIDE AVAILABLE SHORT CIRCUIT
 CALCULATION FOR EACH PANEL INCLUDING INFORMATION FROM
 THE POWER COMPANY STATING WHAT THE AVAILABLE SHORT
 CIRCUIT CURRENT IS FOR THE SERVICE TO CONFIRM THE
 STATED AIC RATING OF THE SERVICE EQUIPMENT AND
 DOWNSTREAM PANELS IS ADEQUATE. NEC 110.9, 110.10; FBC
 RE E3606.3
 7. A SMOKE ALARM IS REQUIRED ON EACH LEVEL OF THE
 DWELLING UNIT. PROVIDE CORRECTION. FBC RE R314.3
 8. ALL BRANCH CIRCUITS THAT SUPPLY 120-VOLT,
 SINGLE-PHASE, 15- AND 20-AMPERE OUTLETS INSTALLED IN
 KITCHENS, FAMILY ROOMS, DINING ROOMS, LIVING ROOMS,
 PARLORS, LIBRARIES, DENS, BEDROOMS, SUN-ROOMS,
 RECREATIONS ROOMS, CLOSETS, HALLWAYS, LAUNDRY AREAS AND
 SIMILAR ROOMS OR AREAS SHALL BE AFCI PROTECTED. THIS
 INCLUDES LIGHTING AND POWER OUTLETS AND RECEPTACLES.
 SOME AREAS REQUIRE BOTH AFCI AND GFCI PROTECTION.
 PROVIDE CORRECTION. NEC 210.8, 210.12; FBC RE E3902;
 FBC EX 607.1.1 OR 801.1, 801.2, OR 901.2 AS APPLICABLE.
 9. GFCI PROTECTION IS REQUIRED FOR ALL EXTERIOR
 RECEPTACLE OUTLETS. PROVIDE CORRECTION. NEC 210.8; FBC
 RE E3902.3
 10. PROVIDE TAMPER RESISTANT RECEPTACLES PER CODE. A
 NOTE WILL SUFFICE. NEC 406.12; FBC RE E4002.14
 11. THERE APPEARS TO BE SOMETHING LOCATED IN FRONT OF
 ELECTRICAL PANEL. CLEARANCE IN FRONT OF THE PANEL IS
 REQUIRED. PROVIDE CORRECTION.NEC 110.26; FBC RE E3405.1
 12. PROVIDE LOCATION OF ELECTRICAL SERVICE ON PLAN. WPB
 FBC 107.2.1
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD
 SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2018-10-26 Cont ID  
Sent By jpearson Date 2018-10-26 Time 13:06 Rev Time 0.00
Received By jpearson Date 2018-10-26 Time 11:10 Sent To  
Notes
2018-10-26 13:05:59CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. VALUE FOR WORK STATED ON PERMIT APPLICATION APPEARS
 LOW. PROVIDE COPY OF SIGNED CONTRACT WITH SCOPE AND
 VALUE OF WORK, TO INCLUDE ALL MATERIALS AND LABOR. THIS
 IS FOR TOTAL PROJECT, NOT JUST ELECTRICAL. FBC 109.3
 2. PROVIDE ELECTRICAL PLAN FOR REVIEW, SIGNED AND
 SEALED BY THE PERSON RESPONSIBLE FOR THE DESIGN. WPB
 FBC 107.2.1, 107.3.5; FS 471, 481
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD
 SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop HIST HISTORICAL
Rev No 3 Status P Date 2019-01-10 Cont ID  
Sent By fmittner Date 2019-01-10 Time 09:26 Rev Time 0.00
Received By fmittner Date 2019-01-10 Time 09:26 Sent To  
Notes
***NONE***

Review Stop HIST HISTORICAL
Rev No 2 Status F Date 2018-12-14 Cont ID  
Sent By fmittner Date 2018-12-14 Time 11:19 Rev Time 0.00
Received By fmittner Date 2018-12-14 Time 11:19 Sent To  
Notes
2018-12-14 11:22:12PROPERTY LOXCATE DIN HSITORIC DISTRICT. ADDITIONS
 REQUIRE SUBMITTAL FO A COA. WINDOWS DO NOT MEET DESIGN
 GUIDELINES.....SHALL BE S/H ALUMINUM WITH GRID PATTERN
 TO MATCH EXISITNG HOUSE. QUESTIONS, CONTACT FRIEDERIKE
 MITTNER, CITY HISITORIC PRESERVATION PLANNER AT (561)
 822-1457 OR [email protected]

Review Stop HIST HISTORICAL
Rev No 1 Status P Date 2018-10-25 Cont ID  
Sent By fmittner Date 2018-10-25 Time 15:14 Rev Time 0.00
Received By fmittner Date 2018-10-25 Time 15:14 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2019-01-25 Cont ID  
Sent By cthroop Date 2019-01-25 Time 15:43 Rev Time 0.00
Received By cthroop Date 2019-01-23 Time 15:58 Sent To  
Notes
2019-01-24 15:58:44RESUB ROUTED TO CTHROOP

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2019-01-15 Cont ID  
Sent By cthroop Date 2019-01-15 Time 11:31 Rev Time 0.00
Received By cthroop Date 2019-01-03 Time 14:08 Sent To  
Notes
2019-01-04 14:08:29R31

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2018-12-31 Cont ID  
Sent By cthroop Date 2018-12-31 Time 13:15 Rev Time 0.00
Received By cthroop Date 2018-12-04 Time 15:37 Sent To  
Notes
2018-12-05 15:37:46R31

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-11-15 Cont ID  
Sent By jgomez Date 2018-11-15 Time 09:53 Rev Time 0.00
Received By jgomez Date 2018-10-05 Time 15:06 Sent To I
Notes
2018-10-09 15:06:32R07

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2018-12-21 Cont ID  
Sent By cmontell Date 2018-12-21 Time 14:03 Rev Time 0.00
Received By cmontell Date 2018-12-21 Time 14:03 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2018-10-27 Cont ID  
Sent By cmontell Date 2018-10-27 Time 06:00 Rev Time 0.00
Received By cmontell Date 2018-10-27 Time 05:58 Sent To  
Notes
2018-10-27 06:00:25MECHANICAL PLAN REVIEW FAIL
  
 1 - NEED MECHANICAL PLANS PER 2017 FLORIDA BUILDING
 CODE - BUILDING, SIXTH EDITION 107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS
  
  
 CHRIS MONTELLO
 561-805-6733

Review Stop P PLUMBING
Rev No 2 Status P Date 2018-12-31 Cont ID  
Sent By cthroop Date 2018-12-31 Time 12:54 Rev Time 0.00
Received By cthroop Date 2018-12-31 Time 11:29 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status N Date 2018-11-06 Cont ID  
Sent By jesmith Date 2018-11-06 Time 12:36 Rev Time 0.00
Received By jesmith Date 2018-11-06 Time 12:27 Sent To  
Notes
2018-11-06 12:36:29THERE APPEARS TO BE NO PLUMBING IN THE SCOPE OF WORK.A
 PLUMBING PLAN HAS NOT BEEN INCLUDED IN THIS SUBMITTAL
 PACKAGE. A PLUMBING PLAN REVIEW HAS NOT BEEN PERFORMED
 AT THIS TIME. A SEPARATE PLUMBING PERMIT AND PLANS WILL
 BE REQUIRED FOR A CONTRACTOR TO PERFORM ANY RELATED
 WORK.
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
 EMAIL: [email protected]
 PHONE: 561-805-6715

Review Stop R ROOF PLAN REVIEW
Rev No 4 Status P Date 2019-01-25 Cont ID  
Sent By cthroop Date 2019-01-25 Time 15:41 Rev Time 0.00
Received By cthroop Date 2019-01-25 Time 15:41 Sent To  
Notes
2019-01-25 15:43:08FBC 107.3.4 ? PROVIDE PRODUCT APPROVALS FOR THOSE
 PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED
 AND APPROVED IN WRITING BY THE DESIGNER OF RECORD.
 SPECIFICALLY, PROVIDE ROOFING SUBMITTALS.
  
  
 PROVISO
  
 107.3.4.1 DEFERRED SUBMITTALS. FOR THE PURPOSES OF THIS
 SECTION, DEFERRED SUBMITTALS ARE DEFINED AS THOSE
 PORTIONS OF THE DESIGN THAT ARE NOT SUBMITTED AT THE
 TIME OF THE APPLICATION AND THAT ARE TO BE SUBMITTED TO
 THE BUILDING OFFICIAL WITHIN A SPECIFIED PERIOD.
 DEFERRAL OF ANY SUBMITTAL ITEMS SHALL HAVE THE PRIOR
 APPROVAL OF THE BUILDING OFFICIAL. THE REGISTERED
 DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE SHALL LIST
 THE DEFERRED SUBMITTALS ON
 THE CONSTRUCTION DOCUMENTS FOR REVIEW BY THE BUILDING
 OFFICIAL.
 DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE
 SUBMITTED TO THE REGISTERED DESIGN PROFESSIONAL IN
 RESPONSIBLE CHARGE WHO SHALL REVIEW THEM AND FORWARD
 THEM TO THE BUILDING OFFICIAL WITH A NOTATION
 INDICATING THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE
 BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO
 THE DESIGN OF THE BUILDING. THE DEFERRED SUBMITTAL
 ITEMS SHALL NOT BE INSTALLED UNTIL THE DEFERRED
 SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE BUILDING
 OFFICIAL.
  
  

Review Stop R ROOF PLAN REVIEW
Rev No 3 Status F Date 2019-01-15 Cont ID  
Sent By cthroop Date 2019-01-15 Time 11:26 Rev Time 0.00
Received By cthroop Date 2019-01-14 Time 08:26 Sent To  
Notes
2019-01-15 11:28:59BUILDING PLAN REVIEW - ROOFING
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 BUILDING PLANS EXAMINER, PX3169
 1&2 FAMILY PLANS EXAMINER, SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 3RD REVIEW
 RESULTS: DENIED
 YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED
 BELOW.
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. PROVIDE PRODUCT APPROVALS FOR PROPOSED ROOF SYSTEM.
  
 FBC 107.3.4 ? PROVIDE PRODUCT APPROVALS FOR THOSE
 PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED
 AND APPROVED IN WRITING BY THE DESIGNER OF RECORD.
 SPECIFICALLY, PROVIDE ROOFING SUBMITTALS.
  
 PROVISO
  
 107.3.4.1 DEFERRED SUBMITTALS. FOR THE PURPOSES OF THIS
 SECTION, DEFERRED SUBMITTALS ARE DEFINED AS THOSE
 PORTIONS OF THE DESIGN THAT ARE NOT SUBMITTED AT THE
 TIME OF THE APPLICATION AND THAT ARE TO BE SUBMITTED TO
 THE BUILDING OFFICIAL WITHIN A SPECIFIED PERIOD.
 DEFERRAL OF ANY SUBMITTAL ITEMS SHALL HAVE THE PRIOR
 APPROVAL OF THE BUILDING OFFICIAL. THE REGISTERED
 DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE SHALL LIST
 THE DEFERRED SUBMITTALS ON
 THE CONSTRUCTION DOCUMENTS FOR REVIEW BY THE BUILDING
 OFFICIAL.
 DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE
 SUBMITTED TO THE REGISTERED DESIGN PROFESSIONAL IN
 RESPONSIBLE CHARGE WHO SHALL REVIEW THEM AND FORWARD
 THEM TO THE BUILDING OFFICIAL WITH A NOTATION
 INDICATING THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE
 BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO
 THE DESIGN OF THE BUILDING. THE DEFERRED SUBMITTAL
 ITEMS SHALL NOT BE INSTALLED UNTIL THE DEFERRED
 SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE BUILDING
 OFFICIAL.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO SUBMITTAL AND LEAVE THE PREVIOUSLY
 REVIEWED SHEETS DETACHED.
  
  
  
  
  

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status F Date 2018-12-31 Cont ID  
Sent By cthroop Date 2018-12-31 Time 13:10 Rev Time 0.00
Received By cthroop Date 2018-12-31 Time 11:28 Sent To  
Notes
2018-12-31 13:12:38 
 BUILDING PLAN REVIEW
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 BUILDING PLANS EXAMINER, PX3169
 1&2 FAMILY PLANS EXAMINER, SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 2ND REVIEW
 RESULTS: DENIED
 YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED
 BELOW.
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. PROVIDE PRODUCT APPROVALS FOR ROOF SYSTEM
 COMPONENETS.
  
 FBC 107.3.4 ? PROVIDE PRODUCT APPROVALS FOR THOSE
 PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED
 AND APPROVED IN WRITING BY THE DESIGNER OF RECORD.
 SPECIFICALLY, PROVIDE ROOFING SUBMITTALS.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO SUBMITTAL AND LEAVE THE PREVIOUSLY
 REVIEWED SHEETS DETACHED.
  
  
  

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2018-11-15 Cont ID  
Sent By jgomez Date 2018-11-15 Time 09:53 Rev Time 0.00
Received By jgomez Date 2018-11-15 Time 09:53 Sent To  
Notes
2018-11-15 09:53:551- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 FAC 61G20-3.001 FOR:
 (NOTE: THIS MAY BE SUBMITTED LATER AS A DEFERRED
 SUBMITTAL)
 A) FLAT ROOF. AND, CLEARLY MARK WHICH APPROVED ASSEMBLY
 IS GOING TO BE INSTALLED TO VERIFY COMPLIANCE WITH THE
 DESIGN PRESSURES OF SEC. R301.1 FBC-RESIDENTIAL. NOTE:
 IF THE SELECTED ASSEMBLY DOESN'T MEET THE DESIGN
 PRESSURES FOR ALL ROOF ZONES, THEN SIGNED AND SEALED
 RAS 117 CALCULATIONS ARE REQUIRED.
  
 2- DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS
 REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS.

Review Stop Z ZONING
Rev No 3 Status P Date 2019-01-10 Cont ID  
Sent By fmittner Date 2019-01-10 Time 09:26 Rev Time 0.00
Received By fmittner Date 2019-01-10 Time 09:26 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status F Date 2018-12-14 Cont ID  
Sent By fmittner Date 2018-12-14 Time 11:22 Rev Time 0.00
Received By fmittner Date 2018-12-14 Time 11:22 Sent To  
Notes
2018-12-14 11:22:55REQUIRES SUBMITTAL FO LOT COVERAGE AND FAR CALCS.

Review Stop Z ZONING
Rev No 1 Status P Date 2018-10-25 Cont ID  
Sent By fmittner Date 2018-10-25 Time 15:15 Rev Time 0.00
Received By fmittner Date 2018-10-25 Time 15:15 Sent To  
Notes
***NONE***