Plan Review Details - Permit 18100242
Plan Review Stops For Permit 18100242
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2018-12-20 Cont ID  
Sent By dbattles Date 2018-12-20 Time 13:02 Rev Time 0.00
Received By dbattles Date 2018-12-20 Time 13:02 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2018-12-06 Cont ID  
Sent By dbattles Date 2018-12-06 Time 16:38 Rev Time 0.00
Received By dbattles Date 2018-12-06 Time 16:37 Sent To  
Notes
2018-12-06 16:41:14ALL BUILDING COMMENTS ARE CLEARED, BUT THE TWO SETS
 DON'T MATCH.
 SHEETS H-1 AND H-2 WERE INSERTED INTO ONE SET AS THE
 LAST TWO SHEETS.
 THESE ARE GOOD BECAUSE THEY HAVE THE DRAINAGE
 ELEVATIONS.
  
 HOWEVER , THE OTHER SET DIDN'T GET SHEETS H-1 AND H-2
 THEY STILL HAVE SHEETS L-1 AND L2.
 PLEASE INSERT H-1 AND H-2 INTO DUPLICATE SET AND REMOVE
 L1-L2. SO BOTH SETS MATCH.
  
 DYLAN BATTLES
 BUILDING PLANS EXAMINER I
 [email protected]
 561-805-6718

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2018-11-09 Cont ID  
Sent By dbattles Date 2018-11-09 Time 16:40 Rev Time 0.00
Received By dbattles Date 2018-11-09 Time 12:00 Sent To  
Notes
2018-11-09 16:40:36****CORRECTIONS****
 W.P.B. PERMIT: 18100242
 REVIEWED: NOVEMBER 9, 2018
  
 DYLAN BATTLES
 BUILDING PLANS EXAMINER I
 [email protected]
 561-805-6718
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC AMENDED = FLORIDA BUILDING CODE,6TH EDITION (2017)
 FBC A = FBC ACCESSIBILITY
 FBC ENERGY = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 [FBC R322.2.1]THE CITY OF WPB HAS ADOPTED A 2?
 FREEBOARD ABOVE B.F.E. SEE AMENDMENT TO FBC R322.2.1 IN
 ORD. NO. 4765-18, ? 2, 3-12-2018(SEC 18-33)
 THIS PROJECT IS LOCATED IN A SPECIAL FLOOD HAZARD AREA
 (SFHA). THE SPECIFIC ZONE DESIGNATION FOR THIS SITE IS
 AE WITH A BASE FLOOD ELEVATION (BFE) OF 7FT. THE CITY
 OF WEST PALM BEACH (THROUGH ORDINANCE) REQUIRES AN
 ADDITIONAL 24 INCHES OF FREEBOARD REQUIRING THE DESIGN
 FLOOD ELEVATION (DFE) TO BE 9.0 FEET. PLEASE NOTE THIS
 INFORMATION ON YOUR PLANS.
  
 1. A CONSTRUCTION DRAWING ELEVATION CERTIFICATE IS
 REQUIRED AT TIME OF PERMIT APPLICATION.
 NOTE: ALL EQUIPMENT SERVICING THE BUILDINGS ON THIS
 SITE ARE REQUIRED TO BE AT OR ABOVE 9.0 FEET NGVD.
 ALLSO, UPDATE SURVEY AND SIRE PLAN TO SHOW LOWEST FLOOR
 ELEVATION OF 9 FT. GARAGE CAN BE LOWER WITH FLOOD VENTS
 AS SHOWN ON PLANS.
  
 AN UNDER CONSTRUCTION (FORMBOARD) SURVEY WITH FINISHED
 FLOOR ELEVATION IS RECOMMENDED.
  
 A FINISHED CONSTRUCTION ELEVATION CERTIFICATE IS
 REQUIRED AND SHALL BE SUBMITTED FOR REVIEW AND APPROVAL
 PRIOR TO THE ISSUANCE OF THE CERTIFICATE OF OCCUPANCY.
  
 2. [FBC 107.3.5.3]PROVIDE SEDIMENT CONTROL PLAN TO KEEP
 CONSTRUCTION DEBRIS FROM ENTERING ADJACENT PROPERTIES
 AND STORM DRAINS DURING CONSTRUCTION. YOU CAN FIND
 ENGINEERING STANDARD DETAILS FROM WPB WEBSITE-POLLUTION
 CONTROL
 HTTP://WWW.WPB.ORG/DEPARTMENTS/ENGINEERING-PUBLIC-WORKS
 /FORMS,-PERMITS-APPLICATIONS
  
 3. [FBC 107.5][FBC 110.9][FBC R401.3]PROVIDE SITE
 DRAINAGE PLAN.
 SURFACE DRAINAGE SHALL BE DIVERTED TO A STORM SEWER
 CONVEYANCE OR OTHER APPROVED POINT OF COLLECTION THAT
 DOES NOT CREATE A HAZARD. LOTS SHALL BE GRADED TO DRAIN
 SURFACE WATER AWAY FROM FOUNDATION WALLS. THE GRADE
 SHALL FALL A MINIMUM OF 6 INCHES (152 MM) WITHIN THE
 FIRST 10 FEET (3048 MM).
 EXCEPTION: WHERE LOT LINES, WALLS, SLOPES OR OTHER
 PHYSICAL BARRIERS PROHIBIT 6 INCHES (152 MM) OF FALL
 WITHIN 10 FEET (3048 MM), DRAINS OR SWALES SHALL BE
 CONSTRUCTED TO ENSURE DRAINAGE AWAY FROM THE STRUCTURE.
 IMPERVIOUS SURFACES WITHIN 10 FEET (3048 MM) OF THE
 BUILDING FOUNDATION SHALL BE SLOPED A MINIMUM OF 2
 PERCENT AWAY FROM THE BUILDING.
  
 4. [FBC AMENDED 107.3.4.1]SUBMIT TRUSS SHOP DRAWINGS TO
 THE BUILDING INSPECTOR PRIOR TO INSTALLATION.
  
 5. [FBC AMENDED 107.2.1.2]PROVIDE STAIRCASE AND GUARD
 RAIL ENGINEERING, OR INDICATE THAT IT WILL BE DEFERRED.
  
 6. SEPARATE PERMIT WILL BE REQUIRED FOR FENCE/WALL,
 DRIVEWAY(ENGINEERING DEPARTMENT), POOL AND GENERATOR.
  
 NOTE:
 -PLEASE PROVIDE COMMENT RESPONSE SHEET TO EXPLAIN HOW
 EACH COMMENT IS BEING ADDRESSED.
 -ADDITIONAL COMMENTS MAY BE FORTHCOMING PENDING REVIEW
 OF MATERIALS REQUESTED.
 -WHEN RESUBMITTING, PROVIDE TWO IDENTICAL COLLATED SETS
 OF DOCUMENTS FOR ISSUANCE. OLD SHEETS (BOTH SETS)
 SHOULD BE RETAINED IN THE PACKAGE; PLEASE DO NOT
 DISCARD ANY DOCUMENTS. THEY SHOULD BE BOUND TOGETHER
 SEPARATELY FROM THE TWO ISSUANCE SETS AND MARKED "VOID"
 OR "OLD SHEETS". PLEASE DO NOT STAMP THE PLANS VOID AS
 APPLICANTS ARE INADVERTENTLY STAMPING SHEETS THAT WE
 NEED "VOID", RENDERING THEM NOT USABLE.
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2018-12-07 Cont ID  
Sent By jpearson Date 2018-12-07 Time 15:41 Rev Time 0.00
Received By jpearson Date 2018-12-07 Time 14:08 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2018-10-24 Cont ID  
Sent By jpearson Date 2018-10-24 Time 14:23 Rev Time 0.00
Received By jpearson Date 2018-10-24 Time 10:11 Sent To  
Notes
2018-10-24 14:23:10CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. PROVIDE AVAILABLE SHORT CIRCUIT CALCULATION FOR EACH
 PANEL STATING WHAT THE AVAILABLE SHORT CIRCUIT CURRENT
 IS TO CONFIRM THE STATED AIC RATING OF THE SERVICE
 EQUIPMENT AND DOWNSTREAM PANELS IS ADEQUATE. NEC 110.9,
 110.10; FBC RE E3606.3
 2. AFCI PROTECTION SHOWN IN NOTE 10A ON SHEET E3 IS NOT
 CODE COMPLIANT. ALL BRANCH CIRCUITS THAT SUPPLY
 120-VOLT, SINGLE-PHASE, 15- AND 20-AMPERE OUTLETS
 INSTALLED IN KITCHENS, FAMILY ROOMS, DINING ROOMS,
 LIVING ROOMS, PARLORS, LIBRARIES, DENS, BEDROOMS,
 SUN-ROOMS, RECREATIONS ROOMS, CLOSETS, HALLWAYS,
 LAUNDRY AREAS AND SIMILAR ROOMS OR AREAS SHALL BE AFCI
 PROTECTED. THIS INCLUDES LIGHTING AND POWER OUTLETS AND
 RECEPTACLES. SOME AREAS REQUIRE BOTH AFCI AND GFCI
 PROTECTION. PROVIDE CORRECTION. NEC 210.8, 210.12; FBC
 RE E3902
 3. PROVIDE GFCI PROTECTION FOR DISHWASHER. NEC
 210.8(D); FBC RE E3902.10
 4. BE ADVISED THAT FIRE ALARM, LOW VOLTAGE SYSTEMS,
 DAS, LIGHTNING PROTECTION, GENERATORS, COMMERCIAL HOOD
 SYSTEMS, WALK IN COOLERS, SIGNS, SITE LIGHTING, AND
 SWIMMING POOLS (WHERE APPLICABLE) ARE NOT INCLUDED IN
 THE SCOPE OF THIS PLAN REVIEW. PROVIDE A BLOCK NOTE
 INDICATING THE REQUIRED SEPARATE PERMITS AND PLAN
 SUBMITTALS FOR ANY OF THESE SYSTEMS PRESENT. WPB FBC
 105.1, 107.2.1
 5. RISER DIAGRAM SHOWS 2/0 COPPER FEEDING THE 400 AMP
 METER FROM THE POWER COMPANY. SERVICE CONDUCTORS ARE
 REQUIRED TO HAVE AN AMPACITY OF NOT LESS THAN 83% OF
 THE SERVICE RATING. THE WIRE SIZE SPECIFIED IS ONLY
 RATED FOR 175 AMPS INSTEAD OF THE 332 AMPS REQUIRED.
 PROVIDE CORRECTION. NEC 310.15(B)(7) AND (B)(16); FBC
 RE E3603.1.1
 6. RISER DIAGRAM SHOWS 4/0 COPPER FEEDING THE TRANSFER
 SWITCH FROM THE METER CAN. SERVICE CONDUCTORS ARE
 REQUIRED TO HAVE AN AMPACITY OF NOT LESS THAN 83% OF
 THE SERVICE RATING. THE WIRE SIZE SPECIFIED IS ONLY
 RATED FOR 230 AMPS INSTEAD OF THE 332 AMPS REQUIRED.
 PROVIDE CORRECTION. NEC 310.15(B)(7) AND (B)(16); FBC
 RE E3603.1.1
 7. RISER DIAGRAM SHOWS 2/0 COPPER FEEDING PANEL 1 FROM
 THE TRANSFER SWITCH. FEEDER CONDUCTORS ARE REQUIRED TO
 HAVE AN AMPACITY EQUAL OR GREATER THAN THE PANEL BEING
 FED. THE WIRE SIZE SPECIFIED IS ONLY RATED FOR 175 AMPS
 INSTEAD OF THE 200 AMPS REQUIRED. PROVIDE CORRECTION.
 NEC 310.15(B)(7) AND (B)(16); FBC RE E3603.1.2
 8. RISER DIAGRAM SHOWS 2/0 COPPER FEEDING TRANSFER
 SWITCH FROM THE GENERATOR. FEEDER CONDUCTORS ARE
 REQUIRED TO HAVE AN AMPACITY EQUAL OR GREATER THAN THE
 PANEL BEING FED. THE WIRE SIZE SPECIFIED IS ONLY RATED
 FOR 175 AMPS INSTEAD OF THE 200 AMPS REQUIRED. PROVIDE
 CORRECTION. NEC 310.15(B)(7) AND (B)(16); FBC RE
 E3603.1.2
 9. PANELS 1 AND 2 ARE SHOWN AS MAIN LUG ONLY PANELS. IF
 THE INTENT IS TO TAP OFF THE 400 AMP MAIN IN THE
 TRANSFER SWITCH, THE TAP MUST TERMINATE IN A MAIN
 BREAKER. PROVIDE CORRECTION. NEC 215.3, 240.21
 10. PROVIDE SPEC SHEET FOR 400 AMP TRANSFER SWITCH. IS
 THIS SERVICE ENTRANCE RATED? IS THERE ONE 400 AMP
 BREAKER AS THE MAIN IN THIS TRANSFER SWITCH? WPB FBC
 107.2.1; NEC 110.3; FBC RE E3403.3
 11. POOL PUMP, SPA PUMP, AND SPA BLOWER REQUIRE GFCI
 PROTECTION. PROVIDE CORRECTION. NEC 680.21(C), 680.44;
 FBC RE E4203.1.3, E4208.1
 12. FOR A ONE FAMILY DWELLING AND EACH UNIT OF A
 TWO-FAMILY DWELLING THAT IS AT GRADE LEVEL, AT LEAST
 ONE RECEPTACLE OUTLET READILY ACCESSIBLE FROM GRADE AND
 NOT MORE THAN 2.0 M (6.5 FT) ABOVE GRADE LEVEL SHALL BE
 INSTALLED AT THE FRONT AND BACK OF THE DWELLING.
 PROVIDE CORRECTION FOR FRONT OF DWELLING. NEC
 210.52(E)(1) FBC RE E3901.7
 13. NOTE 3 ON SHEET E1 SPECIFIES THE 2011 NEC AS BASIS
 FOR DESIGN. PROVIDE CORRECTION. FBC PREFACE (ALSO SEE
 CURRENT CODES ABOVE)
 14. ALL OUTDOOR RECEPTACLE OUTLETS REQUIRE GFCI
 PROTECTION. PROVIDE CORRECTION FOR BBQ GRILL AREA. NEC
 210.8; FBC RE E3902.3
 15. SHEET E1, NOTE 15 IS FUNNY, THANKS FOR THE LAUGH.
 16. BATH 2 DOES NOT SHOW GFCI PROTECTION FOR RECEPTACLE
 OUTLET IN BATHROOM. PROVIDE CORRECTION. NEC 210.8; FBC
 RE E3902.1
 17. SMOKE ALARMS MUST BE INSTALLED AT LEAST 3 FEET FROM
 BATHROOM DOOR, 3 FEET FROM CEILING FANS, AND 3 FEET
 FROM ANY MECHANICAL DUCT. PROVIDE CORRECTIONS. FBC RE
 R314.3(4), NFPA 72:29.8.3.4
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD
 SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop ENG ENGINEERING CSD
Rev No 1 Status N Date 2018-11-20 Cont ID  
Sent By rrossano Date 2018-11-20 Time   Rev Time 0.00
Received By rrossano Date 2018-11-20 Time   Sent To I
Notes
2018-11-20 14:19:39PLEASE FILE FOR SEPARATE DRIVEWAY PERMIT. PLEASE
 PROVIDE SURVEY SHOWING REMOVAL OF EXISTING CONCRETE
 DRIVEWAYS ON FLAGLER DR. AND PROPOSED NEW DRIVEWAY ON
 GREGORY PLACE (MAXIMUM WIDTH OF 20 FEET WITH 3 FOOT
 FLARES.) FOOTING FOR PROPOSED WALL SHALL NOT ENCROACH
 INTO CITY RIGHT OF WAY.
  
 FEEL FREE TO CONTACT US IF YOU HAVE ANY QUESTIONS OR
 CONCERNS, THANKS.
  
 RICK ROSSANO
 PROJECT COORDINATOR
 ENGINEERING SERVICES DEPARTMENT
 401 CLEMATIS STREET, 4TH FLOOR
 WEST PALM BEACH, FL 33401
 (MAILING ADDRESS: P.O. BOX 3366, ZIP 33402)
 MAIN PHONE: (561) 822-1200
 DIRECT: (561) 494-1098
 FAX: (561) 494-1116
 MOBILE: (561) 246-9525
 EMAIL: [email protected]
 WWW.WPB.ORG/ENGINEERING
  
 MANNY GONZALEZ
 SENIOR ENGINEERING PROJECT COORDINATOR
 ENGINEERING SERVICES DEPARTMENT
 401 CLEMATIS STREET, 4TH FLOOR
 WEST PALM BEACH, FL 33401
 (MAILING ADDRESS: P.O. BOX 3366, ZIP 33402)
 MAIN PHONE: (561) 822-1200
 DIRECT: (561) 494-1085
 FAX: (561) 494-1116
 MOBILE: (561) 644-7301
 EMAIL: [email protected]
 WWW.WPB.ORG/ENGINEERING
  
  

Review Stop G GAS REVIEW
Rev No 1 Status N Date 2018-11-06 Cont ID  
Sent By jesmith Date 2018-11-06 Time 09:28 Rev Time 0.00
Received By jesmith Date 2018-11-06 Time 09:24 Sent To  
Notes
2018-11-06 09:28:41A GAS PLAN HAS NOT BEEN INCLUDED IN THIS SUBMITTAL
 PACKAGE. A GAS PLAN REVIEW HAS NOT BEEN PERFORMED AT
 THIS TIME. A SEPARATE GAS PERMIT AND PLANS WILL BE
 REQUIRED FOR A CONTRACTOR TO PERFORM THE RELATED WORK.
 PROVIDE COMPLETE PLANS, APPLIANCE/ EQUIPMENT
 SPECIFICATIONS AND GAS RISER THAT REFLECT THE ENTIRE
 SCOPE OF GAS WORK TO BE DONE. WPB AMEND. TO FBC SEC.
 107.2.1.
 GAS APPLIANCES SHALL BE LISTED AND LABELED PER THE
 FBC-R, SEC. G2404.3.
 GAS APPLIANCES SHALL BE LISTED AND LABELED PER FBC-FUEL
 GAS SEC. 301.3.
 A SEPARATE PERMIT AND PLANS IS REQUIRED FOR THE GAS
 INSTALLATION.
  
  
  
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
 EMAIL: [email protected]
 PHONE: 561-805-6715

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2018-12-20 Cont ID  
Sent By dbattles Date 2018-12-20 Time 13:02 Rev Time 0.00
Received By dbattles Date 2018-12-17 Time 12:38 Sent To  
Notes
2018-12-19 12:38:43RESUB ROUTED TO ZONING INBOX

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2018-12-17 Cont ID  
Sent By shill Date 2018-12-17 Time 10:39 Rev Time 0.00
Received By shill Date 2018-11-21 Time 16:40 Sent To  
Notes
2018-11-28 12:49:03R35
2018-11-21 16:41:42LIBRARY

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-11-20 Cont ID  
Sent By cpuell Date 2018-11-20 Time 14:51 Rev Time 0.00
Received By cpuell Date 2018-10-04 Time 15:26 Sent To  
Notes
2018-10-11 16:18:39R27
2018-10-05 15:27:04LIBRARY

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 3 Status P Date 2018-12-10 Cont ID  
Sent By dbattles Date 2018-12-10 Time 15:23 Rev Time 0.00
Received By dbattles Date 2018-12-10 Time 15:23 Sent To  
Notes
2018-12-10 15:21:14STAMP ON PLAN - OK
 M.U. # 2018-37792

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status F Date 2018-12-06 Cont ID  
Sent By dbattles Date 2018-12-06 Time 16:42 Rev Time 0.00
Received By dbattles Date 2018-12-06 Time 16:42 Sent To  
Notes
2018-12-06 16:43:55I RETAINED THE ORIGINAL SITE PLAN SHEET THAT HAS IMPACT
 REVIEW STAMP - OK.
  
 PLEASE PROVIDE MU NUMBER FROM THE RECEIPT.
  
 DYLAN BATTLES
 BUILDING PLANS EXAMINER I
 [email protected]
 561-805-6718

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2018-11-09 Cont ID  
Sent By dbattles Date 2018-11-09 Time 16:25 Rev Time 0.00
Received By dbattles Date 2018-11-09 Time 16:25 Sent To  
Notes
2018-11-09 16:25:46DYLAN BATTLES
 BUILDING PLANS EXAMINER I
 [email protected]
 561-805-6718
  
 [FBC AMENDED 109]PLANS REQUIRE REVIEW BY THE PBC IMPACT
 FEE OFFICE. CALL (561) 233-5025. UPON APPROVAL, YOU MAY
 CHECK OUT ONE PLAN SET AND TAKE TO THAT OFFICE FOR
 REVIEW. PLEASE RETURNED STAMPED AND WITH A COPY OF THE
 RECEIPT AS APPLICABLE. PLEASE PROVIDE THE MUNICIPAL
 IMPACT FEE QUESTIONNAIRE FORM TO THE PBC IMPACT FEE
 OFFICE. THE FORM CAN BE FOUND AT: HTTP://DISCOVER.PBCGO
 V.ORG/PZB/ADMINISTRATION/PDF/IMPACTFEES/FORMS/QUESTIONN
 AIRE.PDF
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2018-10-27 Cont ID  
Sent By cmontell Date 2018-10-27 Time 07:06 Rev Time 0.00
Received By cmontell Date 2018-10-27 Time 06:57 Sent To  
Notes
***NONE***

Review Stop NFIP NFIP REVIEW ACTIVITY
Rev No 2 Status P Date 2018-12-06 Cont ID  
Sent By dbattles Date 2018-12-06 Time 16:44 Rev Time 0.00
Received By dbattles Date 2018-12-06 Time 16:44 Sent To  
Notes
2018-12-06 16:45:26BFE OF 7 FEET
 THE F.F.E HAS BEEN SET TO 9 FEET TO MEET
 ORD. NO. 4765-18, ? 2, 3-12-2018(SEC 18-33)

Review Stop NFIP NFIP REVIEW ACTIVITY
Rev No 1 Status F Date 2018-11-09 Cont ID  
Sent By dbattles Date 2018-11-09 Time 16:18 Rev Time 0.00
Received By dbattles Date 2018-11-09 Time 16:18 Sent To  
Notes
2018-11-09 16:24:49****CORRECTIONS****
 W.P.B. PERMIT: 18100242
 REVIEWED: NOVEMBER 9, 2018
  
 DYLAN BATTLES
 BUILDING PLANS EXAMINER I
 [email protected]
 561-805-6718
  
 PLEASE ADJUST THE FLOOD ELEVATION CERTIFICATE ON PAGE 2
 THE TOP OF BOTTOM FLOOR SHOULD BE 9' AND THE GARAGE CAN
 BE LOWER WITH THE FLOOD VENTS AS SHOWN.
  
 SEE BUILDING COMMENT#1 FOR FURTHER DETAILS.

Review Stop P PLUMBING
Rev No 2 Status P Date 2018-12-13 Cont ID  
Sent By jesmith Date 2018-12-13 Time 15:45 Rev Time 0.00
Received By jesmith Date 2018-12-13 Time 15:45 Sent To  
Notes
2018-12-13 15:45:36APPROVED
 PLUMBING PROVISO
  
 1. ALL WORK PER CITY CODES SUBJECT TO FIELD INSPECTOR'S
 APPROVAL
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 PHONE 561-805-6715

Review Stop P PLUMBING
Rev No 1 Status F Date 2018-11-06 Cont ID  
Sent By jesmith Date 2018-11-06 Time 10:58 Rev Time 0.00
Received By jesmith Date 2018-11-06 Time 09:02 Sent To  
Notes
2018-11-06 10:57:05CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RES = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 FBC ACC = FLORIDA ACCESSIBILITY CODE 2017 6TH EDITION
 FBC EX = FLORIDA EXISTING BUILDING CODE 2017 6TH
 EDITION
 FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION
 FBC FG = FLORIDA FUEL GAS CODE 2017 6TH EDITION
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
 1ST REVIEW
 PLUMBING COMMENTS: DENIED
  
 1. DUE TO THE COMPLEXITY OF THE PROJECT, THE PLUMBING
 PIPING PLAN REQUIRES MORE INFORMATION. PROVIDE 1ST AND
 2ND FLOOR PLAN PLUMBING LAYOUT IN PLAN VIEW. SHOW WHICH
 WALLS THE SANITARY RISERS TO THE SECOND FLOOR WILL BE
 LOCATED. PLAN VIEWS AND RISER DIAGRAM SHALL MATCH. WPB
 FBC 107.2.1
 2. RE: PLAN SHEET A10; SANITARY RISER DIAGRAM
 A. PLEASE PROVIDE A DIRECTIONAL ORIENTATION SO THAT THE
 DIAGRAM CORRESPONDS WITH THE PLAN VIEW. WPB FPC 107.2.1
 B. PLEASE IDENTIFY BATHROOMS. WPB FBC 107.2.1
 C. PROVIDE INDIVIDUAL VENT FOR CLOTHES WASHER FIXTURE
 DRAIN.FBC RES P3102.2.1
 D. LAVATORY FIXTURE DRAINS IN BATH #4 CLOSEST TO THE
 WATER CLOSET, THE MASTER BATH AND BOTH HALF BATHS DROP
 VERTICALLY BEFORE CONNECTING TO THE VENT. THE TOTAL
 FALL IN A FIXTURE DRAIN DUE TO PIPE SLOPE SHALL NOT
 EXCEED THE DIAMETER OF THE FIXTURE DRAIN, NOR SHALL THE
 VENT CONNECTION TO A FIXTURE DRAIN, EXCEPT FOR WATER
 CLOSETS, BE BELOW THE WEIR OF THE TRAP PER FBC RES
 P3105.2. CORRECT AND RESUBMIT
 E. A LAVATORY IN THE MASTER BATH IS NOT SHOWN. INCLUDE
 ON RESUBMITTED DIAGRAM. WPB FBC 107.2.1
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD
 SHEETS.
  
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER
 EMAIL: [email protected]
 PHONE: 561-805-6715
  

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status P Date 2018-11-09 Cont ID  
Sent By dbattles Date 2018-11-09 Time 16:27 Rev Time 0.00
Received By dbattles Date 2018-11-09 Time 16:27 Sent To  
Notes
2018-11-09 16:27:47PRODUCT APPROVAL FOR METAL ROOF - OK

Review Stop Z ZONING
Rev No 3 Status P Date 2018-12-19 Cont ID  
Sent By awooten Date 2018-12-19 Time   Rev Time 0.00
Received By awooten Date 2018-12-19 Time   Sent To B
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status F Date 2018-12-17 Cont ID  
Sent By awooten Date 2018-12-17 Time   Rev Time 0.00
Received By awooten Date 2018-12-17 Time   Sent To  
Notes
2018-12-17 10:28:01*************************************ZONING REVIEW
 FAILED*************************************
  
 PLEASE SUBMIT A SEPARATE LANDSCAPE AND IRRIGATION
 PERMIT. SHOWING THE FOLLOWING:
 RESIDENTIAL LANDSCAPE REQUIREMENTS CITY OF WEST PALM
 BEACH
 SECTION 94-442(C)(2)A. SINGLE FAMILY DWELLING UNITS
  
 -GROSS LOT SQUARE FOOTAGE MINUS
 -BUILDING FOOTPRINT SQUARE FOOTAGE EQUALS
 -OPEN SPACE SQUARE FOOTAGE (ALL NON-BUILDING AREA)
 -ONE TREE REQUIRED FOR EACH 1,000 SQ FT OF OPEN SPACE
 OR PORTION THEREOF
 -ONE SHRUB REQUIRED FOR EACH 500 SQ FT OF OPEN SPACE OR
 PORTION THEREOF
  
 THE PROPOSED DRIVEWAY, POOL, AND FENCE REQUIRES A
 SEPARATE PERMIT.
  
 ALANA WOOTEN
 ASSOCIATE PLANNER
 PLANNING DIVISION
 561-822-1449
 [email protected]
  

Review Stop Z ZONING
Rev No 1 Status F Date 2018-10-23 Cont ID  
Sent By awooten Date 2018-10-23 Time   Rev Time  
Received By awooten Date 2018-10-23 Time   Sent To  
Notes
2018-10-23 14:51:40*************************************ZONING REVIEW
 FAILED*************************************
  
 PLEASE SUBMIT A SEPARATE LANDSCAPE AND IRRIGATION
 PERMIT. SHOWING THE FOLLOWING:
 RESIDENTIAL LANDSCAPE REQUIREMENTS CITY OF WEST PALM
 BEACH
 SECTION 94-442(C)(2)A. SINGLE FAMILY DWELLING UNITS
  
 -GROSS LOT SQUARE FOOTAGE MINUS
 -BUILDING FOOTPRINT SQUARE FOOTAGE EQUALS
 -OPEN SPACE SQUARE FOOTAGE (ALL NON-BUILDING AREA)
 -ONE TREE REQUIRED FOR EACH 1,000 SQ FT OF OPEN SPACE
 OR PORTION THEREOF
 -ONE SHRUB REQUIRED FOR EACH 500 SQ FT OF OPEN SPACE OR
 PORTION THEREOF
  
 THE PROPOSED DRIVEWAY, POOL, AND FENCE REQUIRES A
 SEPARATE PERMIT.
  
 ALANA WOOTEN
 ASSOCIATE PLANNER
 PLANNING DIVISION
 561-822-1449
 [email protected]
  