Plan Review Details - Permit 18100224
Plan Review Stops For Permit 18100224
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2018-12-17 Cont ID  
Sent By cthroop Date 2018-12-17 Time 14:22 Rev Time 0.00
Received By cthroop Date 2018-12-17 Time 14:03 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2018-12-03 Cont ID  
Sent By cthroop Date 2018-12-03 Time 15:04 Rev Time 0.00
Received By cthroop Date 2018-12-03 Time 14:54 Sent To  
Notes
2018-12-03 15:06:25BUILDING PLAN REVIEW
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER, PX3169
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 1. 1ST BLDG. REVIEW COMMENTS HAVE BEEN ADDRESSED.
 2. NEW PLAN SHEETS WILL BE REQUIRED PER ENGINEERING
 COMMENTS.
 3. ADDRESS ENGINEERING COMMENTS AND RE-SUBMIT.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2018-10-24 Cont ID  
Sent By cthroop Date 2018-10-24 Time 11:21 Rev Time 0.00
Received By cthroop Date 2018-10-24 Time 09:59 Sent To  
Notes
2018-10-24 11:22:49BUILDING PLAN REVIEW
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER, PX3169
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 1ST REVIEW
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 ACCESSIBLE PARKING
  
 PROVIDE A LEGIBLE PLAN TO PROVIDE THE FOLLOWING
 INFORMATION PER 208.2
 TOTAL NUMBER OF PARKING SPACES
 NUMBER OF ACCESSIBLE SPACES
 LOCATION OF ACCESSIBLE ENTRANCES
 LOCATION OF ACCESSIBLE SPACES AND ACCESS AISLES
 SHOW ACCESSIBLE ROUTE FROM PUBLIC WAY
 ACCESSIBLE ROUTE FROM ACCESSIBLE SPACE TO ACCESSIBLE
 ENTRANCE
  
 206.2.1SITE ARRIVAL POINTS.
 AT LEAST ONE ACCESSIBLE ROUTE SHALL BE PROVIDED WITHIN
 THE SITE FROM ACCESSIBLE PARKING SPACES AND ACCESSIBLE
 PASSENGER LOADING ZONES; PUBLIC STREETS AND SIDEWALKS;
 AND PUBLIC TRANSPORTATION STOPS TO THE ACCESSIBLE
 BUILDING OR FACILITY ENTRANCE THEY SERVE
  
 208.1 GENERAL.
 WHERE PARKING SPACES ARE PROVIDED, PARKING SPACES SHALL
 BE PROVIDED IN ACCORDANCE WITH 208. SEE SECTION 502.5
 REQUIREMENTS FOR VAN PARKING IN STRUCTURES.
  
 EXCEPTION: PARKING SPACES USED EXCLUSIVELY FOR BUSES,
 TRUCKS, OTHER DELIVERY VEHICLES, LAW ENFORCEMENT
 VEHICLES, OR VEHICULAR IMPOUND SHALL NOT BE REQUIRED TO
 COMPLY WITH 208 PROVIDED THAT LOTS ACCESSED BY THE
 PUBLIC ARE PROVIDED WITH A PASSENGER LOADING ZONE
 COMPLYING WITH 503.
  
 208.2 MINIMUM NUMBER.
 PARKING SPACES COMPLYING WITH 502 SHALL BE PROVIDED IN
 ACCORDANCE WITH TABLE 208.2 EXCEPT AS REQUIRED BY
 208.2.1, 208.2.2, AND 208.2.3. WHERE MORE THAN ONE
 PARKING FACILITY IS PROVIDED ON A SITE, THE NUMBER OF
 ACCESSIBLE SPACES PROVIDED ON THE SITE SHALL BE
 CALCULATED ACCORDING TO THE NUMBER OF SPACES REQUIRED
 FOR EACH PARKING FACILITY.
  
  

Review Stop ENG ENGINEERING CSD
Rev No 3 Status P Date 2018-12-17 Cont ID  
Sent By RRossano Date 2018-12-17 Time   Rev Time 0.00
Received By rrossano Date 2018-12-17 Time   Sent To B
Notes
***NONE***

Review Stop ENG ENGINEERING CSD
Rev No 2 Status F Date 2018-11-29 Cont ID  
Sent By RRossano Date 2018-11-29 Time   Rev Time 0.00
Received By rrossano Date 2018-11-29 Time   Sent To B
Notes
2018-11-29 06:55:48PLEASE SEE COMMENTS BELOW AND ATTACHMENT FROM TRACY
 WARD, SENIOR STORMWATER ENGINEER, ENGINEERING SERVICES,
 561-494-1120:
  
 SHEET C-1: PLEASE LABEL VERTICAL DATUM & PROVIDE
 CONVERSION EQUATION TO NGVD '29.
 SHEET C-2: PLEASE PROVIDE CONVERSION EQUATION TO NGVD
 '29.
 SHEET C-3: PLEASE REVISE STORMWATER CALCULATIONS PER
 ATTACHMENT. (ENVIRONMENTAL RESOURCE PERMIT INFORMATION
 MANUAL, PT. III - REFERENCES & DESIGN AIDS, SECTION U -
 DESIGN EXAMPLE FOR EXFILTRATION TRENCH & MARKUP OF
 SHEET U-6)
  
 FEEL FREE TO CONTACT US IF YOU HAVE ANY QUESTIONS OR
 CONCERNS, THANKS.
  
 RICK ROSSANO
 PROJECT COORDINATOR
 ENGINEERING SERVICES DEPARTMENT
 401 CLEMATIS STREET, 4TH FLOOR
 WEST PALM BEACH, FL 33401
 (MAILING ADDRESS: P.O. BOX 3366, ZIP 33402)
 MAIN PHONE: (561) 822-1200
 DIRECT: (561) 494-1098
 FAX: (561) 494-1116
 MOBILE: (561) 246-9525
 EMAIL: [email protected]
 WWW.WPB.ORG/ENGINEERING
  
 MANNY GONZALEZ
 SENIOR ENGINEERING PROJECT COORDINATOR
 ENGINEERING SERVICES DEPARTMENT
 401 CLEMATIS STREET, 4TH FLOOR
 WEST PALM BEACH, FL 33401
 (MAILING ADDRESS: P.O. BOX 3366, ZIP 33402)
 MAIN PHONE: (561) 822-1200
 DIRECT: (561) 494-1085
 FAX: (561) 494-1116
 MOBILE: (561) 644-7301
 EMAIL: [email protected]
 WWW.WPB.ORG/ENGINEERING
  
  

Review Stop ENG ENGINEERING CSD
Rev No 1 Status F Date 2018-10-15 Cont ID  
Sent By rrossano Date 2018-10-15 Time   Rev Time  
Received By rrossano Date 2018-10-15 Time   Sent To B
Notes
2018-10-15 10:57:301) SHOW 6 INCH DIP LATERAL AND ASSOCIATED ON-SITE FIRE
 HYDRANT. BOTH ARE IN VINCINITY OF PROPOSED PARKING LOT
 IMPROVEMENTS.
 2) THERE ARE WATER AND SEWER LINES IN THE VICINITY OF
 THIS PROJECT. PER CHAPTER 556 OF THE FLORIDA STATE
 STATUTES, YOU MUST CALL 811 FOR UTILITY LOCATES AT
 LEAST TWO FULL BUSINESS DAYS IN ADVANCE OF ANY
 CONSTRUCTION OR DEMOLITION WORK. MORE INFORMATION CAN
 BE FOUND HERE: HTTP://WWW.SUNSHINE811.COM/
 3) COMPLY WITH WPB PARKING DETAILS (ATTACHED TO
 APPLICATION PACKAGE FOR YOUR USE).
  
 THE FOLLOWING COMMENTS ARE FROM TRACY WARD, SENIOR
 STORMWATER ENGINEER, CITY OF WPB ENGINEERING SERVICES,
 561-494-1120
 SHEET C-1
 1) IS PARKING LOT ENTRANCE TOO CLOSE TO ROAD RIGHT OF
 WAY (15 FEET)?
 SHEET C-2
 1) DRAWINGS PROPOSE 12? HDPE PIPE BETWEEN SECTIONS OF
 15? PERFORATED PIPE. PLEASE REVISE.
 2) CONSIDER SHORTENING PARKING SPACES TO 16? SINCE
 CURBING IS ALREADY BEING USED.
 SHEET C-3
 1) H2 IS DEPTH TO WATER TABLE OR TRENCH, WHICHEVER IS
 LESS. IT IS MEASURED FROM THE CONTROL ELEVATION (WEIR)
 OR THE MINIMUM GRATE ELEVATION. SINCE THERE IS NO
 OUTFALL, THE MINIMUM GRATE ELEVATION IS USED (14.80).
 TOP OF TRENCH ELEVATION IS SHOWN AS 13.50, AND TRENCH
 IS 4 FEET DEEP. BOTTOM OF TRENCH IS 13.50 ? 4 = 9.50.
 H2 = 14.80 ? 9.50 = 5.3. VOLUME TREATED = 1780 C.F.
 LESS THAN 15.16 C.F. IS OK.
  
 FEEL FREE TO CONTACT US IF YOU HAVE ANY QUESTIONS OR
 CONCERNS, THANKS.
  
 RICK ROSSANO
 PROJECT COORDINATOR
 ENGINEERING SERVICES DEPARTMENT
 401 CLEMATIS STREET, 4TH FLOOR
 WEST PALM BEACH, FL 33401
 (MAILING ADDRESS: P.O. BOX 3366, ZIP 33402)
 MAIN PHONE: (561) 822-1200
 DIRECT: (561) 494-1098
 FAX: (561) 494-1116
 MOBILE: (561) 246-9525
 EMAIL: [email protected]
 WWW.WPB.ORG/ENGINEERING
  
 MANNY GONZALEZ
 SENIOR ENGINEERING PROJECT COORDINATOR
 ENGINEERING SERVICES DEPARTMENT
 401 CLEMATIS STREET, 4TH FLOOR
 WEST PALM BEACH, FL 33401
 (MAILING ADDRESS: P.O. BOX 3366, ZIP 33402)
 MAIN PHONE: (561) 822-1200
 DIRECT: (561) 494-1085
 FAX: (561) 494-1116
 MOBILE: (561) 644-7301
 EMAIL: [email protected]
 WWW.WPB.ORG/ENGINEERING

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2018-12-17 Cont ID  
Sent By cthroop Date 2018-12-17 Time 14:22 Rev Time 0.00
Received By cthroop Date 2018-12-06 Time 14:51 Sent To  
Notes
2018-12-07 14:51:33RESUB ROUTED TO ZONING INBOX

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2018-12-03 Cont ID  
Sent By cthroop Date 2018-12-03 Time 15:06 Rev Time 0.00
Received By cthroop Date 2018-11-15 Time 09:59 Sent To  
Notes
2018-11-16 09:59:52RESUB ROUTED TO ZONING INBOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-10-24 Cont ID  
Sent By cthroop Date 2018-10-24 Time 11:22 Rev Time 0.00
Received By cthroop Date 2018-10-04 Time 14:04 Sent To  
Notes
2018-10-05 14:05:01ROUTED TO ZONING INBOX

Review Stop Z ZONING
Rev No 3 Status P Date 2018-12-14 Cont ID  
Sent By mcruz Date 2018-12-14 Time 10:00 Rev Time 0.00
Received By mcruz Date 2018-12-14 Time 09:57 Sent To ENG
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date 2018-11-27 Cont ID  
Sent By mcruz Date 2018-11-27 Time 14:27 Rev Time 0.00
Received By mcruz Date 2018-11-27 Time 14:24 Sent To ENG
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2018-10-12 Cont ID  
Sent By mcruz Date 2018-10-12 Time 11:40 Rev Time 0.00
Received By mcruz Date 2018-10-12 Time 09:36 Sent To ENG
Notes
2018-10-12 11:39:00ZONING REVIEW FAILED, DUE TO THE FOLLOWING:
  
 1) SEPARATE LANDSCAPE PERMIT REQUIRED. ZONING WILL
 APPROVE ONCE LANDSCAPING IS ADDRESSED.
  
 FOR ADDITIONAL INFORMATION, THE ZONING AND LAND
 DEVELOPMENT REGULATIONS MAY BE VIEWED ONLINE AT
 WWW.MUNICODE.COM OR VISIT THE CITY OF WEST PALM BEACH
 PLANNING DEPARTMENT WEBSITE AT
 WWW.CITYOFWPB.COM/PLAN/INDEX.HTM.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE DO NOT HESITATE TO
 CONTACT ME.
  
 MAGGIE CRUZ
 ASSOCIATE PLANNER
 PLANNING AND ZONING DEPARTMENT
 TEL: 561-822-1442
 E-MAIL: [email protected]