Plan Review Details - Permit 18100183
Plan Review Stops For Permit 18100183
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2018-11-14 Cont ID  
Sent By jgomez Date 2018-11-14 Time 16:19 Rev Time 0.00
Received By jgomez Date 2018-11-14 Time 13:22 Sent To  
Notes
2018-11-14 16:20:13CHANGE OF OCCUPANCY BUILDING REVIEW COMMENTS.
 CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS.
  
 1- PERMIT APPLICATION STATES "ADD DAYCARE (E) OCCUPANCY
 TO EXISTING (R3) OCCUPANCY FOR 6 CHILDREN. NO REMODEL
 WORK PROPOSED".
 BASED ON THE NUMBER OF CHILDREN THE PROPOSED CHANGE OF
 OCCUPANCY REQUIRES FLOOR PLANS (SIGNED AND SEALED AS
 REQUIRED BY SEC. 481.229 F.S.) SHOWING COMPLIANCE WITH
 THE PROPOSED USE. ALSO, A NEW CERTIFICATE OF OCCUPANCY
 WILL BE REQUIRED. SEC. 1001.2 FBC-EXISTING BUILDING.
  
 2- FLOOR PLANS NEED TO BE CLEAR SPECIFYING THE AGES OF
 THE CHILDREN AND IF THE DAY CARE WILL PROVIDE
 EDUCATION. A DAY CARE WITH 6 CHILDREN MAY BE CONSIDERED
 AS EDUCATIONAL GROUP E (SEC. 305.2 FBC) OR
 INSTITUTIONAL I-4 (SEC. 308.6 FBC). DESIGNER OF RECORD
 TO MAKE CLEAR THE GROUP CLASSIFICATION FOR PROPER PLAN
 REVIEW. SEC. 107.2.1 CITY AMENDMENTS.
 NOTE: PLANS NEED TO SHOW COMPLIANCE WITH THE EGRESS
 REQUIREMENTS AND ACCESSIBILITY REQUIREMENTS FOR THE
 PROPOSED USE. SPRINKLERS MAY BE REQUIRED. PARKING AND
 ACCESSIBLE PARKING MAY BE REQUIRED. ALSO, CHECK SEC.
 466 FBC FOR DAY CARE OCCUPANCIES REQUIREMENTS.
  
 3- PLANS NEED TO SHOW SEPARATION OF OCCUPANCIES AS
 REQUIRED BY SEC. 508.4 FBC.
  
 4- IMPACT FEES - CHANGE OF OCCUPANCY REQUIRES REVIEW BY
 THE PBC IMPACT FEE OFFICE. CALL (561) 233-5025. UPON
 APPROVAL, YOU MAY CHECK OUT ONE PLAN SET AND TAKE TO
 THAT OFFICE FOR REVIEW. PLEASE RETURNED STAMPED AND
 WITH A COPY OF THE RECEIPT AS APPLICABLE. PLEASE
 PROVIDE THE MUNICIPAL IMPACT FEE QUESTIONNAIRE FORM TO
 THE PBC IMPACT FEE OFFICE. THE FORM CAN BE FOUND AT:
 HTTP://DISCOVER.PBCGO
 V.ORG/PZB/ADMINISTRATION/PDF/IMPACTFEES/FORMS/QUESTIONN
 AIRE.PDF
  
 5- SCOPE OF WORK NEEDS TO BE REVISED IN THE PERMIT
 APPLICATION. A LINCENSED CONTRACTOR MAY BE REQUIRED
 (SEC. 489.105 F.S. ). PERMIT FEES WILL APPLY BASED ON
 THE REVISED SCOPE OF WORK AND VALUATION. VALUATION TO
 INCLUDE ALL LABOR, MATERIALS, CONTRACTOR'S OVERHEAD AND
 PROFIT AND DESIGN PROFESSIONAL FEES AS REQUIRED BY SEC.
 109.3 CITY AMENDMENTS.
  
 6- SUBMITTAL OF ADDITIONAL AND/OR REVISED MATERIALS MAY
 RESULT IN NEW PLAN REVIEW COMMENTS. PLEASE PROVIDE
 RESPONSE LETTER ADDRESSING EACH COMMENT TO HELP
 EXPEDITE THE REVIEW PROCESS.
  
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2018-10-23 Cont ID  
Sent By jpearson Date 2018-10-23 Time 09:01 Rev Time 0.00
Received By jpearson Date 2018-10-23 Time 09:01 Sent To  
Notes
2018-10-23 09:01:05CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. PROVIDE ELECTRICAL PLAN FOR REVIEW, SIGNED AND
 SEALED BY THE PERSON RESPONSIBLE FOR THE DESIGN. WPB
 FBC 107.2.1, 107.3.5; FS 471 481
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD
 SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2018-10-18 Cont ID  
Sent By pleduc Date 2018-10-18 Time   Rev Time 0.00
Received By pleduc Date 2018-10-18 Time 11:46 Sent To  
Notes
2018-10-18 12:05:03THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
  
 1) THE SUBMITTED PLAD SHEETS DOES NOT PROVIDE
 SUFFICIENT INFORMATION TO DETERMINE COMPLIANCE WITH THE
 FLORIDA FIRE PREVENTION CODE.
  
 THE PROPOSED PROJECT SHALL MEET THE REQUIREMENTS OF THE
 6TH EDITION OF FLORIDA FIRE PREVENTION CODE INCLUDING
 THE 2015 EDITION OF NFPA 1 AND NFPA 101 AND ALL OTHER
 APPLICABLE CODES OR STANDARDS.
  
  
  
  
 2) PLEASE PROVIDE THE TYPE OF DAY-CARE BEING PROPOSED
 INCLUDING THE NUMBER OF PROPOSED CLIENTS AND AGES.
  
 PER NFPA 1, OCCUPANCY FIRE SAFETY
  
 20.3 DAY-CARE OCCUPANCIES.
 20.3.1 APPLICATION. NEW AND EXISTING DAY-CARE
 OCCUPANCIES SHALL
 COMPLY WITH SECTION 20.3 AND NFPA 101.
 20.3.1.1 IN NEW DAY-CARE OCCUPANCIES, WHERE A FACILITY
 HOUSES
 MORE THAN ONE AGE GROUP OR SELF-PRESERVATION
 CAPABILITY, THE
 STRICTEST REQUIREMENTS APPLICABLE TO ANY GROUP PRESENT
 SHALL APPLY
 THROUGHOUT THE DAY-CARE OCCUPANCY OR BUILDING, AS
 APPROPRIATE TO
 A GIVEN AREA, UNLESS THE AREA HOUSING SUCH A GROUP IS
 MAINTAINED
 AS A SEPARATE FIRE AREA.
  
 20.3.1.4 GENERAL. OCCUPANCIES THAT INCLUDE PRESCHOOLS,
 KINDERGARTENS, AND OTHER SCHOOLS WHOSE PURPOSE IS
 PRIMARILY
 EDUCATIONAL FOR CHILDREN 24 MONTHS OF AGE OR OLDER,
 EVEN THOUGH
 THE CHILDREN WHO ATTEND SUCH SCHOOLS ARE OF PRESCHOOL
 AGE, SHALL
 COMPLY WITH THE PROVISIONS OF CHAPTER 14 OR CHAPTER 15
 OF NFPA
 101, AS APPLICABLE.
  
 20.3.2.2* DOOR LATCHES. EVERY DOOR LATCH TO CLOSETS,
 STORAGE
 AREAS, KITCHENS, AND OTHER SIMILAR SPACES OR AREAS
 SHALL BE SUCH
 THAT CLIENTS CAN OPEN THE DOOR FROM INSIDE THE SPACE OR
 AREA. [101:
 16.2.2.2.4; 101: 17.2.2.2.4]
 20.3.2.3 BATHROOM DOORS. EVERY BATHROOM DOOR LOCK SHALL
 BE
 DESIGNED TO ALLOW OPENING OF THE LOCKED DOOR FROM THE
 OUTSIDE BY
 AN OPENING DEVICE THAT SHALL BE READILY ACCESSIBLE TO
 THE STAFF.
  
 20.3.4 DAY-CARE HOMES.
 20.3.4.1 CLASSIFICATION.
 20.3.4.1.1 IN NEW DAY-CARE HOMES, THE REQUIREMENTS OF
 20.3.4 SHALL
 APPLY TO DAY-CARE HOMES IN WHICH MORE THAN 3, BUT NOT
 MORE THAN 12,
 CLIENTS RECEIVE CARE, MAINTENANCE, AND SUPERVISION BY
 OTHER THAN THEIR
 RELATIVE(S) OR LEGAL GUARDIAN(S) FOR LESS THAN 24 HOURS
 PER DAY, GENERALLY
 WITHIN A DWELLING UNIT.
  
 20.3.4.1.3 IN NEW DAY-CARE HOMES, WHERE A FACILITY
 HOUSES MORE THAN
 ONE AGE GROUP OR ONE SELF-PRESERVATION CAPABILITY, THE
 STRICTEST
 REQUIREMENTS APPLICABLE TO ANY GROUP PRESENT SHALL
 APPLY THROUGHOUT THE
 DAY-CARE HOME OR BUILDING, AS APPROPRIATE TO A GIVEN
 AREA, UNLESS THE
 AREA HOUSING SUCH A GROUP IS MAINTAINED AS A SEPARATE
 FIRE AREA.
  
 PER NFPA 101, CHAPTER 16, NEW DAY-CARE OCCUPANCIES
  
 16.1 GENERAL REQUIREMENTS.
 16.1.1* APPLICATION.
 16.1.1.1 THE REQUIREMENTS OF THIS CHAPTER SHALL APPLY
 TO NEW
 BUILDINGS OR PORTIONS THEREOF USED AS DAY-CARE
 OCCUPANCIES. (SEE
 1.3.1.)
 16.1.1.2 ADMINISTRATION. THE PROVISIONS OF CHAPTER 1,
 ADMINISTRATION, SHALL APPLY.
 16.1.1.3 GENERAL. THE PROVISIONS OF CHAPTER 4, GENERAL,
 SHALL
 APPLY.
 16.1.1.4 THE REQUIREMENTS OF SECTIONS 16.1 THROUGH 16.5
 AND
 SECTION 16.7 SHALL APPLY TO DAY-CARE OCCUPANCIES IN
 WHICH MORE
 THAN 12 CLIENTS RECEIVE CARE, MAINTENANCE, AND
 SUPERVISION BY
 OTHER THAN THEIR RELATIVE(S) OR LEGAL GUARDIAN(S) FOR
 LESS THAN 24
 HOURS PER DAY.
  
 16.6.1.4 CLASSIFICATION OF OCCUPANCY.
 16.6.1.4.1 SUBCLASSIFICATION OF DAY-CARE HOMES.
 SUBCLASSIFICATION OF
 DAY-CARE HOMES SHALL COMPLY WITH 16.6.1.4.1.1 AND
 16.6.1.4.1.2.
 16.6.1.4.1.1 FAMILY DAY-CARE HOME. A FAMILY DAY-CARE
 HOME
 SHALL BE A DAY-CARE HOME IN WHICH MORE THAN THREE, BUT
 FEWER THAN
 SEVEN, CLIENTS RECEIVE CARE, MAINTENANCE, AND
 SUPERVISION BY OTHER
 THAN THEIR RELATIVE(S) OR LEGAL GUARDIAN(S) FOR LESS
 THAN 24 HOURS PER
 DAY, GENERALLY WITHIN A DWELLING UNIT.
 16.6.1.4.1.2 GROUP DAY-CARE HOME. A GROUP DAY-CARE HOME
 SHALL
 BE A DAY-CARE HOME IN WHICH NOT LESS THAN 7, BUT NOT
 MORE THAN 12,
 CLIENTS RECEIVE CARE, MAINTENANCE, AND SUPERVISION BY
 OTHER THAN
 THEIR RELATIVE(S) OR LEGAL GUARDIAN(S) FOR LESS THAN 24
 HOURS PER DAY,
 GENERALLY WITHIN A DWELLING UNIT.
  
 PLEASE REVIEW THESE CODES AND ENSURE COMPLAINCE AND
 PROVIDE SUCH DETAILS ON THE RESUBMITTAL.
  
  
  
 3) THERE ARE NO INDICATIONS OF A FIRE ALARM SYSTEM
  
 PER NFPA 101, CHAPTER 16, NEW DAY-CARE OCCUPANCIES
  
 16.3.4 DETECTION, ALARM, AND COMMUNICATIONS SYSTEMS.
 16.3.4.1 GENERAL. DAY-CARE OCCUPANCIES, OTHER THAN
 DAY-CARE
 OCCUPANCIES HOUSED IN ONE ROOM HAVING AT LEAST ONE DOOR
 OPENING DIRECTLY TO THE OUTSIDE AT GRADE PLANE OR TO AN
 EXTERIOR
 EXIT ACCESS BALCONY IN ACCORDANCE WITH 7.5.3, SHALL BE
 PROVIDED
 WITH A FIRE ALARM SYSTEM IN ACCORDANCE WITH SECTION
 9.6.
  
 9.6 FIRE DETECTION, ALARM, AND COMMUNICATIONS SYSTEMS.
 9.6.1* GENERAL.
 9.6.1.1 THE PROVISIONS OF SECTION 9.6 SHALL APPLY ONLY
 WHERE
 SPECIFICALLY REQUIRED BY ANOTHER SECTION OF THIS CODE
 OR WHERE
 SUPERVISION OF A NEW FIRE SPRINKLER SYSTEM OR NEW FIRE
 ALARM
 SYSTEM IS REQUIRED BY THE FLORIDA BUILDING CODE.
 9.6.1.2 FIRE DETECTION, ALARM, AND COMMUNICATIONS
 SYSTEMS
 INSTALLED TO MAKE USE OF AN ALTERNATIVE PERMITTED BY
 THIS CODE
 SHALL BE CONSIDERED REQUIRED SYSTEMS AND SHALL MEET THE
 PROVISIONS
 OF THIS CODE APPLICABLE TO REQUIRED SYSTEMS.
 9.6.1.3 FIRE ALARM SYSTEMS REQUIRED BY THIS CODE SHALL
 BE INSTALLED,
 TESTED, AND MAINTAINED IN ACCORDANCE WITH THE
 APPLICABLE
 REQUIREMENTS OF NFPA 70, NATIONAL ELECTRICAL CODE, AND
 NFPA
 72, NATIONAL FIRE ALARM AND SIGNALING CODE, UNLESS IT
 IS AN
 APPROVED EXISTING INSTALLATION, WHICH SHALL BE
 PERMITTED TO BE
 CONTINUED IN USE.
  
 PLEASE PROVIDE PER THE REQUIREMENTS.
  
  
  
  
 4) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
  
 5) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-11-14 Cont ID  
Sent By jgomez Date 2018-11-14 Time 17:01 Rev Time 0.00
Received By jgomez Date 2018-10-03 Time 09:23 Sent To I
Notes
2018-10-16 09:23:57C20

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2018-11-14 Cont ID  
Sent By jgomez Date 2018-11-14 Time 16:25 Rev Time 0.00
Received By jgomez Date 2018-11-14 Time 16:25 Sent To  
Notes
2018-11-14 16:26:00IMPACT FEES -
  
 PLANS REQUIRE REVIEW BY THE PBC IMPACT FEE OFFICE. CALL
 (561) 233-5025. UPON APPROVAL, YOU MAY CHECK OUT ONE
 PLAN SET AND TAKE TO THAT OFFICE FOR REVIEW. PLEASE
 RETURNED STAMPED AND WITH A COPY OF THE RECEIPT AS
 APPLICABLE. PLEASE PROVIDE THE MUNICIPAL IMPACT FEE
 QUESTIONNAIRE FORM TO THE PBC IMPACT FEE OFFICE. THE
 FORM CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/AD
 MINISTRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF
  
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2018-10-30 Cont ID  
Sent By hmoser Date 2018-10-30 Time 14:17 Rev Time 0.00
Received By hmoser Date 2018-10-30 Time 14:17 Sent To  
Notes
2018-10-30 14:20:37PLAN DENIED
 REFER TO SECTION 601.6 BALANCED RETURN AIR
 2017 FBC (M)
  
 PLAN REVIEW BY HAROLD MOSER
 [email protected]
 OFFICE 561-805-6732
 FAX 561-805-6676

Review Stop P PLUMBING
Rev No 1 Status F Date 2018-11-06 Cont ID  
Sent By gjohnson Date 2018-11-06 Time 13:08 Rev Time 0.00
Received By gjohnson Date 2018-11-06 Time 13:08 Sent To  
Notes
2018-11-06 13:22:121ST REVIEW:
 2017 FLORIDA BUILDING CODE 6TH EDITION
 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH
 EDITION
  
 PLUMBING COMMENTS:
  
 1. SHOW ALL PLUMBING FIXTURES A CHANGE OF OCCUPANCY
 SHALL COMPLY WITHE FBC EXISTING BUILDING 1010.1
 INCREASED DEMAND.WHERE THE OCCUPANCY OF AN EXISTING
 BUILDING OR PART OF AN EXISTING BUILDING IS CHANGED
 SUCH THAT THE NEW OCCUPANCY IS SUBJECT TO INCREASED OR
 DIFFERENT PLUMBING FIXTURE REQUIREMENTS OR TO INCREASED
 WATER SUPPLY REQUIREMENTS IN ACCORDANCE WITH THE
 FLORIDA BUILDING CODE, PLUMBING, THE NEW OCCUPANCY
 SHALL COMPLY WITH THE INTENT OF THE RESPECTIVE FLORIDA
 BUILDING CODE, PLUMBING PROVISIONS.
  
 2. PLEASE SHOW COMPLIANCE WITH FBC EXISTING BUILDING
 1006.1 GENERAL. ACCESSIBILITY IN PORTIONS OF BUILDINGS
 UNDERGOING A CHANGE OF OCCUPANCY CLASSIFICATION SHALL
 COMPLY WITH THE PROVISIONS OF THE FLORIDA BUILDING
 CODE, ACCESSIBILITY.
  
 3. IN COMPILING WITH THE OTHER TRADES IT MAY BE
 NECESSARY TO COMPLY WITH FBC ACC 202.1
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  

Review Stop Z ZONING
Rev No 1 Status P Date 2018-10-24 Cont ID  
Sent By ajones Date 2018-10-24 Time 16:11 Rev Time 0.00
Received By ajones Date 2018-10-24 Time 16:11 Sent To  
Notes
***NONE***