| Plan Review Stops For Permit 18100146 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
P |
Date |
2018-12-04 |
|
|
Cont ID |
|
| Sent By |
dbattles |
Date |
2018-12-04 |
Time |
14:27 |
Rev Time |
0.00 |
| Received By |
dbattles |
Date |
2018-12-04 |
Time |
14:27 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
P |
Date |
2018-11-16 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2018-11-16 |
Time |
15:00 |
Rev Time |
0.00 |
| Received By |
dbattles |
Date |
2018-11-15 |
Time |
14:15 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2018-12-07 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2018-12-07 |
Time |
08:32 |
Rev Time |
0.00 |
| Received By |
jleahy |
Date |
2018-12-07 |
Time |
08:32 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2018-10-22 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2018-10-22 |
Time |
17:38 |
Rev Time |
0.00 |
| Received By |
jleahy |
Date |
2018-10-11 |
Time |
12:09 |
Sent To |
|
|
| Notes |
| 2018-10-22 17:46:34 | FLORIDA BUILDING CODE 2014 5TH EDITION | | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH ED | | | NFPA 70 2011 EDITION | | | | | | JAKE LEAHY | | | ELECTRICAL PLANS EXAMINER II | | | 561-805-6713 | | | [email protected] | | | | | | PAGE E1.01L | | | | | | PLEASE PROVIDE CUT SHEETS FOR WATER FEATURE LIGHTS | | | | | | PAGE E2.27 | | | | | | SYMBOL FOR OUTLETS SHOWN ON ROOF NOT IN LEGEND | | | | | | CIRCUIT LRN 33, 35 NOT SHOWN ON PANEL SCHEDULE.ON PAGE | | | E6.13 | | | | | | CIRCUITS LRN 33, 35 TO BE GFCI PROTECTED | | | | | | PAGE E5.01 | | | | | | PH 24 RISER MSN-4 SIZE OF MAIN TO A1N NOT SHOWN | | | ATS-N, AND ATS-S SIZES NOT SHOWN | | | B1N, AND B1S SIZE NOT SHOWN | | | LRN4 AND LRS4 SIZE NOT SHOWN | | | | | | |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
P |
Date |
2018-10-10 |
|
|
Cont ID |
|
| Sent By |
pleduc |
Date |
2018-10-10 |
Time |
|
Rev Time |
0.00 |
| Received By |
pleduc |
Date |
2018-10-05 |
Time |
15:42 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
5 |
Status |
N |
Date |
|
|
|
Cont ID |
|
| Sent By |
|
Date |
2019-02-22 |
Time |
|
Rev Time |
0.00 |
| Received By |
lmarchan |
Date |
2019-02-19 |
Time |
11:47 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
4 |
Status |
N |
Date |
|
|
|
Cont ID |
|
| Sent By |
|
Date |
2019-02-19 |
Time |
|
Rev Time |
0.00 |
| Received By |
lmarchan |
Date |
2019-02-08 |
Time |
13:49 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2019-02-05 |
|
|
Cont ID |
|
| Sent By |
lmarchan |
Date |
2019-02-05 |
Time |
14:26 |
Rev Time |
0.00 |
| Received By |
lmarchan |
Date |
2019-01-11 |
Time |
14:14 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2018-12-31 |
|
|
Cont ID |
|
| Sent By |
cpuell |
Date |
2018-12-31 |
Time |
09:53 |
Rev Time |
0.00 |
| Received By |
cpuell |
Date |
2018-11-28 |
Time |
08:19 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2018-11-16 |
|
|
Cont ID |
|
| Sent By |
dbattles |
Date |
2018-11-16 |
Time |
15:00 |
Rev Time |
0.00 |
| Received By |
dbattles |
Date |
2018-10-03 |
Time |
13:14 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
5 |
Status |
P |
Date |
2019-02-22 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2019-02-22 |
Time |
17:25 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2019-02-22 |
Time |
17:25 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
4 |
Status |
F |
Date |
2019-02-19 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2019-02-19 |
Time |
08:58 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2019-02-13 |
Time |
17:16 |
Sent To |
|
|
| Notes |
| 2019-02-19 09:02:25 | 2ND REVIEW FBC-2010 MECHANICAL | | | PERMIT #18100146 | | | 2/19/19 | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) THE LETTER FROM DAVE LUCAS OF CARRIER ENTERPRISE | | | LISTS CARRIER SYSTEM MODELS THAT THAT DO NOT MATCH THE | | | MODEL NUMBERS OF THE CARRIER SYSTEMS TO BE INSTALLED IN | | | THE GARAGE ( SEE REVISED SHEET M-603 SIGNED AND SEALED | | | 9/26/18). | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT | | | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE | | | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND | | | KEEP THEM WITH THE SUBMITTALS | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | | | | | | | |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
3 |
Status |
F |
Date |
2019-01-30 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2019-01-30 |
Time |
14:27 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2019-01-29 |
Time |
16:58 |
Sent To |
|
|
| Notes |
| 2019-01-30 14:32:36 | 2ND REVIEW FBC-2010 MECHANICAL | | | REVISION #18100146 | | | MASTER #15111020 | | | 1/30/2019 | | | | | | CODES IN EFFECT: | | | | | | FBC B- FLORIDA BUILDING CODE- 2010 | | | FBC M- FLORIDA MECHANICAL CODE- 2010 | | | FBC EC- FLORIDA ENERGY CONSERVATION CODE- 2010 | | | FS- FLORIDA STATUTES | | | FAC- FLORIDA ADMINISTRATIVE CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) THE LETTER FROM DAVE LUCAS- REGIONAL DIRECTOR OF | | | CARRIER ENTERPRISE CERIFYING THE INSTALLATION OF THE | | | AC/P1-1 AND P1-2 OUTDOOR CONDENSERS IN THE PARKING | | | GARAGE IS NOT ACCEPTED BECAUSE THE LETTER IS NOT | | | ADDRESSING THE ACTUAL INSTALLATION LOCATIONS IN THE | | | ENCLOSED PARKING GARAGE. MR.LUCAS'S LETTER IS | | | ADDRESSING CONDENSERS IN "OUTDOOR ENVIRONMENTS AND | | | WITHIN OPEN VENTILATED COVERED AREAS WHERE AIR FLOW | | | CLEARANCES MEET WITH THE MINIMAL REQUIREMENTS AS SET | | | FORTH IN THE PRODUCT INSTALLATION INSTRUCTIONS." THE | | | INTERIOR OF THE WALL OF THE ENCLOSED PARKING GARAGE IS | | | NOT CONSIDERED AN OUTDOOR, OR OPEN VENTILATED COVERED | | | AREA, PROVIDE A REVISED LETTER THAN PROVIDES MORE | | | INFORMATION AND EVIDENCE OF COMPLIANCE, OR RELOCATE THE | | | CONDENSERS TO THE OUTDOORS. | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT | | | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE | | | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND | | | KEEP THEM WITH THE SUBMITTALS | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
F |
Date |
2018-12-19 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2018-12-19 |
Time |
11:13 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2018-12-19 |
Time |
08:30 |
Sent To |
|
|
| Notes |
| 2018-12-19 11:28:21 | 2ND REVIEW FBC-2010 MECHANICAL | | | REVISION #18100146 | | | MASTER #15111020 | | | 12/18/18 | | | | | | CODES IN EFFECT: | | | | | | FBC B- FLORIDA BUILDING CODE- 2010 | | | FBC M- FLORIDA MECHANICAL CODE- 2010 | | | FBC EC- FLORIDA ENERGY CONSERVATION CODE- 2010 | | | FS- FLORIDA STATUTES | | | FAC- FLORIDA ADMINISTRATIVE CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | THE COMMENTS LISTED BELOW ARE REMAINING FROM THE 1ST | | | REVIEW. PLEASE ADDRESS THEM COMPLETELY | | | | | | 1) SHEET M2.0P1: THE EXTERIOR CONDENSER FOR THE NEW | | | CARRIER SPLIT SYSTEM CANNOT BE INSTALLED ON THE | | | INTERIOR OF THE BUILDING BECAUSE IT HAS TO BE INSTALLED | | | IN ACCORDANCE WITH THE CONDITIONS OF THE LISTING AND | | | MANUFACTURER'S INSTRUCTIONS- SECTION 304.1 FBC M. | | | PLEASE RELOCATE THE CONDENSER TO THE OUTDOORS. | | | | | | 2)) M2.24: A) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR | | | THE EXHAUST HOOD. C) INDICATE WHAT COOKING APPLIANCES | | | WILL BE EXHAUSTED BY THE HOOD- MAKES AND MODELS, TYPE | | | OF FUEL, AND SUBMIT SPECS. D) PROVIDE A SEQUENCE OF | | | OPERATION FOR THE SYSTEM. F) PROVIDE SECTION VIEWS | | | SHOWING THE DUCT CONNECTIONS TO THE HOOD. E) NEW | | | COMMENT- REFERENCE IS MADE TO ARCHITECTURAL PLANS AND | | | DETAILS THAT CONTAIN CUSTOM SUPPLY AIR DEVICES. PLEASE | | | PROVIDE THE PLANS AND DETAILS OR INDICATE WHICH PLAN | | | SHEET THEY CAN BE FOUND ON. | | | | | | 3) M2.26: PROVIDE WIND LOAD ENGINEERING FOR | | | INSTALLATION OF THE NEW ROOFTOP FANS AND DUCTWORK- | | | SECTION 301.15. | | | | | | 4) M2.24: THE FIRE DAMPERS IN THE KITCHEN EXHAUST AND | | | MAKEUP AIR DUCTS ARE NOT REQUIRED PER SECTION 607.5.5 | | | (5). PLEASE REMOVE THE DAMPERS AND PROVIDE PROTECTION | | | FOR THE BOTTOM OF THE SHAFT ENCLOSURE IN COMPLIANCE | | | WITH SECTION 607.5.5.1 FBC M, AND 713.1.1 FBC B. | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT | | | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE | | | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND | | | KEEP THEM WITH THE SUBMITTALS | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2018-11-05 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2018-11-05 |
Time |
16:39 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2018-11-05 |
Time |
16:39 |
Sent To |
|
|
| Notes |
| 2018-11-05 17:23:12 | 1ST REVIEW FBC-2010 MECHANICAL | | | REVISION #18100146 | | | MASTER #15111020 | | | 11/5/18 | | | | | | CODES IN EFFECT: | | | | | | FBC B- FLORIDA BUILDING CODE- 2010 | | | FBC M- FLORIDA MECHANICAL CODE- 2010 | | | FBC EC- FLORIDA ENERGY CONSERVATION CODE- 2010 | | | FS- FLORIDA STATUTES | | | FAC- FLORIDA ADMINISTRATIVE CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) SHEET M2.0P1: THE EXTERIOR CONDENSER FOR THE NEW | | | CARRIER SPLIT SYSTEM CANNOT BE INSTALLED ON THE | | | INTERIOR OF THE BUILDING BECAUSE IT HAS TO BE INSTALLED | | | IN ACCORDANCE WITH THE CONDITIONS OF THE LISTING AND | | | MANUFACTURER'S INSTRUCTIONS- SECTION 304.1 FBC M. | | | PLEASE RELOCATE THE CONDENSER.TO THE OUTDOORS. | | | | | | 2) M2.0P2: RELOCATED PSGF-1A NOT SHOWN. | | | | | | 3) M2.24: A) PROVIDE AN EQUIPMENT SCHEDULE FOR THE | | | EXHAUST HOOD LISTING MAKE AND MODEL AND DIMENSIONS, AND | | | SUBMIT MANIFACTURER'S SPECIFICATIONS. B) INDICATE THE | | | TYPE AND GAGE OF EXHAUST AND MAKEUP AIR DUCT. C) | | | INDICATE WHAT COOKING APPLIANCE(S) WILL BE EXHAUSTED BY | | | THE HOOD- MAKE(S) AND MODEL(S), TYPE OF FUEL, AND | | | SUBMIT SPECS. D) PROVIDE A SEQUENCE OF OPERATION FOR | | | THE SYSTEM. E) CLARIFY IF A FIRE SUPPRESSION SYSTEM | | | WILL BE INSTALLED F) PROVIDE SECTION VIEWS SHOWING THE | | | DUCT CONNECTIONS TO THE HOOD. PLEASE NOTE THAT SEPARATE | | | PERMITS ARE REQUIRED FOR COMMERCIAL COOKING HOODS AND | | | FIRE SUPPRESSION SYSTEMS- SECTION 107.2.1 WPB. | | | | | | 4) M2.24: WHAT IS THE PURPOSE OF THE FD'S IN THE DUCTS? | | | HOW WILL THEY FUNCTION? ARE THEY BEING USED FOR | | | TRANSITIONING TO THE FLAMEBAR DUCTWORK? | | | | | | 5) M2.26: PROVIDE WIND LOAD ENGINEERING FOR | | | INSTALLATION OF THE NEW ROOFTOP FANS AND DUCTWORK- | | | SECTION 301.15. | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT | | | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE | | | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND | | | KEEP THEM WITH THE SUBMITTALS | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
P |
Date |
2018-11-05 |
|
|
Cont ID |
|
| Sent By |
gjohnson |
Date |
2018-11-05 |
Time |
07:19 |
Rev Time |
0.00 |
| Received By |
gjohnson |
Date |
2018-11-05 |
Time |
07:19 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
2 |
Status |
P |
Date |
2019-02-19 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2019-02-19 |
Time |
09:02 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2019-02-19 |
Time |
09:02 |
Sent To |
|
|
| Notes |
| 2019-01-30 14:57:07 | THE REVISED M2.24 PLAN SHEET IS NOT ELECTRONICALLY | | | SIGNED AND SEALED. |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
1 |
Status |
F |
Date |
2018-11-02 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2018-11-02 |
Time |
22:11 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2018-11-02 |
Time |
22:11 |
Sent To |
|
|
| Notes |
| 2018-11-02 22:12:10 | DIGITAL SIGNATURES ARE OK, ALL TRADES | | | NEW SHEETS SUBMITTED NEXT REVIEW NEED VERIFICATION | | | [email protected] | | | |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
4 |
Status |
P |
Date |
2019-02-06 |
|
|
Cont ID |
|
| Sent By |
jroach |
Date |
2019-02-06 |
Time |
10:53 |
Rev Time |
0.00 |
| Received By |
jroach |
Date |
2019-02-06 |
Time |
10:53 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
3 |
Status |
F |
Date |
2019-02-05 |
|
|
Cont ID |
|
| Sent By |
jroach |
Date |
2019-02-05 |
Time |
14:14 |
Rev Time |
0.00 |
| Received By |
jroach |
Date |
2019-02-05 |
Time |
14:14 |
Sent To |
|
|
| Notes |
| 2019-02-05 14:23:41 | ZONING PLAN REVIEW | | | ___________________________________________ | | | | | | DATE OF REVIEW: 02.05.2019 | | | PERMIT NO.: 15111020 (REVISION #18100146) | | | ___________________________________________ | | | | | | REVIEW STATUS: FAILED | | | ___________________________________________ | | | | | | PLEASE PROVIDE A WRITTEN RESPONSE TO THE FOLLOWING PLAN | | | REVIEW COMMENTS (NO RESPONSE WAS PROVIDED FOR COMMENTS | | | ISSUED ON 11/9/2018): | | | | | | 1. THE NARRATIVE INDICATES THAT SEVERAL ITEMS WERE | | | ADDED TO THE MATERIALS SCHEDULE ON SHEET L4.01, BUT | | | THESE DO NOT APPEAR ON THE REVISED SHEET SUBMITTED. | | | PLEASE CLARIFY. - MATERIALS WITH DETAIL #S F-06, G-14, | | | DP-P-01, DP-01, DP-02, DP-03, DP-04, AND DP-05 ARE NOT | | | SHOWN ON SHEET L4.01, AS SPECIFIED IN THE NARRATIVE OF | | | CHANGES, AND YOUR RESPONSE. PLEASE NOTE THAT SHEET | | | L4.01 HAS A LATEST REVISION DATE OF 8.10.2016. | | | ___________________________________________ | | | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | | ___________________________________________ | | | | | | QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING: | | | | | | JOHN P. ROACH, AICP, PRINCIPAL PLANNER | | | CITY OF WEST PALM BEACH | | | DEVELOPMENT SERVICES DEPARTMENT ? PLANNING DIVISION | | | 401 CLEMATIS STREET - P.O. BOX 3147 | | | WEST PALM BEACH, FLORIDA 33402 | | | | | | P: 561.822.1448 | | | F: 561.822.1460 | | | | | | E: [email protected] | | | | | | W: WPB.ORG | | | |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
F |
Date |
2018-12-31 |
|
|
Cont ID |
|
| Sent By |
jroach |
Date |
2018-12-31 |
Time |
08:51 |
Rev Time |
0.00 |
| Received By |
jroach |
Date |
2018-12-31 |
Time |
08:51 |
Sent To |
|
|
| Notes |
| 2018-12-31 08:51:59 | ZONING PLAN REVIEW | | | ___________________________________________ | | | | | | DATE OF REVIEW: 12.31.2018 | | | PERMIT NO.: 15111020 (REVISION #18100146) | | | ___________________________________________ | | | | | | REVIEW STATUS: FAILED | | | ___________________________________________ | | | | | | PLEASE PROVIDE A WRITTEN RESPONSE TO THE FOLLOWING PLAN | | | REVIEW COMMENTS (NO RESPONSE WAS PROVIDED FOR COMMENTS | | | ISSUED ON 11/9/2018): | | | | | | 1. THE NARRATIVE INDICATES THAT SEVERAL ITEMS WERE | | | ADDED TO THE MATERIALS SCHEDULE ON SHEET L4.01, BUT | | | THESE DO NOT APPEAR ON THE REVISED SHEET SUBMITTED. | | | PLEASE CLARIFY. | | | 3. MANUFACTURER?S SPECIFICATIONS SHALL BE PROVIDED FOR | | | THE DOG PARK ARTIFICIAL TURF, AND SHALL INDICATE | | | COMPLIANCE WITH ALL OF THE REQUIREMENTS OF SECTION | | | 94-451(E) AND (F) OF THE CITY?S ZONING AND LAND | | | DEVELOPMENT REGULATIONS. | | | 4. ALL LANDSCAPE REVISIONS SHALL BE SUBMITTED AS A | | | REVISION TO THE LANDSCAPE PERMIT. | | | ___________________________________________ | | | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | | ___________________________________________ | | | | | | QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING: | | | | | | JOHN P. ROACH, AICP, PRINCIPAL PLANNER | | | CITY OF WEST PALM BEACH | | | DEVELOPMENT SERVICES DEPARTMENT ? PLANNING DIVISION | | | 401 CLEMATIS STREET - P.O. BOX 3147 | | | WEST PALM BEACH, FLORIDA 33402 | | | | | | P: 561.822.1448 | | | F: 561.822.1460 | | | | | | E: [email protected] | | | | | | W: WPB.ORG | | | |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
F |
Date |
2018-11-09 |
|
|
Cont ID |
|
| Sent By |
jroach |
Date |
2018-11-09 |
Time |
09:47 |
Rev Time |
0.00 |
| Received By |
jroach |
Date |
2018-11-09 |
Time |
09:43 |
Sent To |
|
|
| Notes |
| 2018-11-09 09:47:59 | ZONING PLAN REVIEW | | | ___________________________________________ | | | | | | DATE OF REVIEW: 11.09.2018 | | | PERMIT NO.: 15111020 (REVISION #18100146) | | | ___________________________________________ | | | | | | REVIEW STATUS: FAILED | | | ___________________________________________ | | | | | | PLEASE PROVIDE A WRITTEN RESPONSE TO THE FOLLOWING PLAN | | | REVIEW COMMENTS: | | | | | | 1. THE NARRATIVE INDICATES THAT SEVERAL ITEMS WERE | | | ADDED TO THE MATERIALS SCHEDULE ON SHEET L4.01, BUT | | | THESE DO NOT APPEAR ON THE REVISED SHEET SUBMITTED. | | | PLEASE CLARIFY. | | | 2. THE NARRATIVE INDICATES THAT REVISIONS ARE BEING | | | MADE TO SHEET L4.52, BUT THIS SHEET DOES NOT APPEAR IN | | | THE SHEETS SUBMITTED. | | | 3. MANUFACTURER?S SPECIFICATIONS SHALL BE PROVIDED FOR | | | THE DOG PARK ARTIFICIAL TURF, AND SHALL INDICATE | | | COMPLIANCE WITH ALL OF THE REQUIREMENTS OF SECTION | | | 94-451(E) AND (F) OF THE CITY?S ZONING AND LAND | | | DEVELOPMENT REGULATIONS. | | | 4. ALL LANDSCAPE REVISIONS SHALL BE SUBMITTED AS A | | | REVISION TO THE LANDSCAPE PERMIT. | | | ___________________________________________ | | | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | | ___________________________________________ | | | | | | QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING: | | | | | | JOHN P. ROACH, AICP, PRINCIPAL PLANNER | | | CITY OF WEST PALM BEACH | | | DEVELOPMENT SERVICES DEPARTMENT ? PLANNING DIVISION | | | 401 CLEMATIS STREET - P.O. BOX 3147 | | | WEST PALM BEACH, FLORIDA 33402 | | | | | | P: 561.822.1448 | | | F: 561.822.1460 | | | | | | E: [email protected] | | | | | | W: WPB.ORG | | | |
|
|