Plan Review Details - Permit 18100146
Plan Review Stops For Permit 18100146
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2018-12-04 Cont ID  
Sent By dbattles Date 2018-12-04 Time 14:27 Rev Time 0.00
Received By dbattles Date 2018-12-04 Time 14:27 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2018-11-16 Cont ID  
Sent By jwitmer Date 2018-11-16 Time 15:00 Rev Time 0.00
Received By dbattles Date 2018-11-15 Time 14:15 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2018-12-07 Cont ID  
Sent By jleahy Date 2018-12-07 Time 08:32 Rev Time 0.00
Received By jleahy Date 2018-12-07 Time 08:32 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2018-10-22 Cont ID  
Sent By jleahy Date 2018-10-22 Time 17:38 Rev Time 0.00
Received By jleahy Date 2018-10-11 Time 12:09 Sent To  
Notes
2018-10-22 17:46:34FLORIDA BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH ED
 NFPA 70 2011 EDITION
  
 JAKE LEAHY
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 PAGE E1.01L
  
 PLEASE PROVIDE CUT SHEETS FOR WATER FEATURE LIGHTS
  
 PAGE E2.27
  
 SYMBOL FOR OUTLETS SHOWN ON ROOF NOT IN LEGEND
  
 CIRCUIT LRN 33, 35 NOT SHOWN ON PANEL SCHEDULE.ON PAGE
 E6.13
  
 CIRCUITS LRN 33, 35 TO BE GFCI PROTECTED
  
 PAGE E5.01
  
 PH 24 RISER MSN-4 SIZE OF MAIN TO A1N NOT SHOWN
 ATS-N, AND ATS-S SIZES NOT SHOWN
 B1N, AND B1S SIZE NOT SHOWN
 LRN4 AND LRS4 SIZE NOT SHOWN
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2018-10-10 Cont ID  
Sent By pleduc Date 2018-10-10 Time   Rev Time 0.00
Received By pleduc Date 2018-10-05 Time 15:42 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date   Cont ID  
Sent By   Date 2019-02-22 Time   Rev Time 0.00
Received By lmarchan Date 2019-02-19 Time 11:47 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date   Cont ID  
Sent By   Date 2019-02-19 Time   Rev Time 0.00
Received By lmarchan Date 2019-02-08 Time 13:49 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2019-02-05 Cont ID  
Sent By lmarchan Date 2019-02-05 Time 14:26 Rev Time 0.00
Received By lmarchan Date 2019-01-11 Time 14:14 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2018-12-31 Cont ID  
Sent By cpuell Date 2018-12-31 Time 09:53 Rev Time 0.00
Received By cpuell Date 2018-11-28 Time 08:19 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-11-16 Cont ID  
Sent By dbattles Date 2018-11-16 Time 15:00 Rev Time 0.00
Received By dbattles Date 2018-10-03 Time 13:14 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 5 Status P Date 2019-02-22 Cont ID  
Sent By ccole Date 2019-02-22 Time 17:25 Rev Time 0.00
Received By ccole Date 2019-02-22 Time 17:25 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 4 Status F Date 2019-02-19 Cont ID  
Sent By ccole Date 2019-02-19 Time 08:58 Rev Time 0.00
Received By ccole Date 2019-02-13 Time 17:16 Sent To  
Notes
2019-02-19 09:02:252ND REVIEW FBC-2010 MECHANICAL
 PERMIT #18100146
 2/19/19
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THE LETTER FROM DAVE LUCAS OF CARRIER ENTERPRISE
 LISTS CARRIER SYSTEM MODELS THAT THAT DO NOT MATCH THE
 MODEL NUMBERS OF THE CARRIER SYSTEMS TO BE INSTALLED IN
 THE GARAGE ( SEE REVISED SHEET M-603 SIGNED AND SEALED
 9/26/18).
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
  
  

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2019-01-30 Cont ID  
Sent By ccole Date 2019-01-30 Time 14:27 Rev Time 0.00
Received By ccole Date 2019-01-29 Time 16:58 Sent To  
Notes
2019-01-30 14:32:362ND REVIEW FBC-2010 MECHANICAL
 REVISION #18100146
 MASTER #15111020
 1/30/2019
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE- 2010
 FBC M- FLORIDA MECHANICAL CODE- 2010
 FBC EC- FLORIDA ENERGY CONSERVATION CODE- 2010
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THE LETTER FROM DAVE LUCAS- REGIONAL DIRECTOR OF
 CARRIER ENTERPRISE CERIFYING THE INSTALLATION OF THE
 AC/P1-1 AND P1-2 OUTDOOR CONDENSERS IN THE PARKING
 GARAGE IS NOT ACCEPTED BECAUSE THE LETTER IS NOT
 ADDRESSING THE ACTUAL INSTALLATION LOCATIONS IN THE
 ENCLOSED PARKING GARAGE. MR.LUCAS'S LETTER IS
 ADDRESSING CONDENSERS IN "OUTDOOR ENVIRONMENTS AND
 WITHIN OPEN VENTILATED COVERED AREAS WHERE AIR FLOW
 CLEARANCES MEET WITH THE MINIMAL REQUIREMENTS AS SET
 FORTH IN THE PRODUCT INSTALLATION INSTRUCTIONS." THE
 INTERIOR OF THE WALL OF THE ENCLOSED PARKING GARAGE IS
 NOT CONSIDERED AN OUTDOOR, OR OPEN VENTILATED COVERED
 AREA, PROVIDE A REVISED LETTER THAN PROVIDES MORE
 INFORMATION AND EVIDENCE OF COMPLIANCE, OR RELOCATE THE
 CONDENSERS TO THE OUTDOORS.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2018-12-19 Cont ID  
Sent By ccole Date 2018-12-19 Time 11:13 Rev Time 0.00
Received By ccole Date 2018-12-19 Time 08:30 Sent To  
Notes
2018-12-19 11:28:212ND REVIEW FBC-2010 MECHANICAL
 REVISION #18100146
 MASTER #15111020
 12/18/18
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE- 2010
 FBC M- FLORIDA MECHANICAL CODE- 2010
 FBC EC- FLORIDA ENERGY CONSERVATION CODE- 2010
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 THE COMMENTS LISTED BELOW ARE REMAINING FROM THE 1ST
 REVIEW. PLEASE ADDRESS THEM COMPLETELY
  
 1) SHEET M2.0P1: THE EXTERIOR CONDENSER FOR THE NEW
 CARRIER SPLIT SYSTEM CANNOT BE INSTALLED ON THE
 INTERIOR OF THE BUILDING BECAUSE IT HAS TO BE INSTALLED
 IN ACCORDANCE WITH THE CONDITIONS OF THE LISTING AND
 MANUFACTURER'S INSTRUCTIONS- SECTION 304.1 FBC M.
 PLEASE RELOCATE THE CONDENSER TO THE OUTDOORS.
  
 2)) M2.24: A) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR
 THE EXHAUST HOOD. C) INDICATE WHAT COOKING APPLIANCES
 WILL BE EXHAUSTED BY THE HOOD- MAKES AND MODELS, TYPE
 OF FUEL, AND SUBMIT SPECS. D) PROVIDE A SEQUENCE OF
 OPERATION FOR THE SYSTEM. F) PROVIDE SECTION VIEWS
 SHOWING THE DUCT CONNECTIONS TO THE HOOD. E) NEW
 COMMENT- REFERENCE IS MADE TO ARCHITECTURAL PLANS AND
 DETAILS THAT CONTAIN CUSTOM SUPPLY AIR DEVICES. PLEASE
 PROVIDE THE PLANS AND DETAILS OR INDICATE WHICH PLAN
 SHEET THEY CAN BE FOUND ON.
  
 3) M2.26: PROVIDE WIND LOAD ENGINEERING FOR
 INSTALLATION OF THE NEW ROOFTOP FANS AND DUCTWORK-
 SECTION 301.15.
  
 4) M2.24: THE FIRE DAMPERS IN THE KITCHEN EXHAUST AND
 MAKEUP AIR DUCTS ARE NOT REQUIRED PER SECTION 607.5.5
 (5). PLEASE REMOVE THE DAMPERS AND PROVIDE PROTECTION
 FOR THE BOTTOM OF THE SHAFT ENCLOSURE IN COMPLIANCE
 WITH SECTION 607.5.5.1 FBC M, AND 713.1.1 FBC B.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2018-11-05 Cont ID  
Sent By ccole Date 2018-11-05 Time 16:39 Rev Time 0.00
Received By ccole Date 2018-11-05 Time 16:39 Sent To  
Notes
2018-11-05 17:23:121ST REVIEW FBC-2010 MECHANICAL
 REVISION #18100146
 MASTER #15111020
 11/5/18
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE- 2010
 FBC M- FLORIDA MECHANICAL CODE- 2010
 FBC EC- FLORIDA ENERGY CONSERVATION CODE- 2010
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET M2.0P1: THE EXTERIOR CONDENSER FOR THE NEW
 CARRIER SPLIT SYSTEM CANNOT BE INSTALLED ON THE
 INTERIOR OF THE BUILDING BECAUSE IT HAS TO BE INSTALLED
 IN ACCORDANCE WITH THE CONDITIONS OF THE LISTING AND
 MANUFACTURER'S INSTRUCTIONS- SECTION 304.1 FBC M.
 PLEASE RELOCATE THE CONDENSER.TO THE OUTDOORS.
  
 2) M2.0P2: RELOCATED PSGF-1A NOT SHOWN.
  
 3) M2.24: A) PROVIDE AN EQUIPMENT SCHEDULE FOR THE
 EXHAUST HOOD LISTING MAKE AND MODEL AND DIMENSIONS, AND
 SUBMIT MANIFACTURER'S SPECIFICATIONS. B) INDICATE THE
 TYPE AND GAGE OF EXHAUST AND MAKEUP AIR DUCT. C)
 INDICATE WHAT COOKING APPLIANCE(S) WILL BE EXHAUSTED BY
 THE HOOD- MAKE(S) AND MODEL(S), TYPE OF FUEL, AND
 SUBMIT SPECS. D) PROVIDE A SEQUENCE OF OPERATION FOR
 THE SYSTEM. E) CLARIFY IF A FIRE SUPPRESSION SYSTEM
 WILL BE INSTALLED F) PROVIDE SECTION VIEWS SHOWING THE
 DUCT CONNECTIONS TO THE HOOD. PLEASE NOTE THAT SEPARATE
 PERMITS ARE REQUIRED FOR COMMERCIAL COOKING HOODS AND
 FIRE SUPPRESSION SYSTEMS- SECTION 107.2.1 WPB.
  
 4) M2.24: WHAT IS THE PURPOSE OF THE FD'S IN THE DUCTS?
 HOW WILL THEY FUNCTION? ARE THEY BEING USED FOR
 TRANSITIONING TO THE FLAMEBAR DUCTWORK?
  
 5) M2.26: PROVIDE WIND LOAD ENGINEERING FOR
 INSTALLATION OF THE NEW ROOFTOP FANS AND DUCTWORK-
 SECTION 301.15.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status P Date 2018-11-05 Cont ID  
Sent By gjohnson Date 2018-11-05 Time 07:19 Rev Time 0.00
Received By gjohnson Date 2018-11-05 Time 07:19 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2019-02-19 Cont ID  
Sent By ccole Date 2019-02-19 Time 09:02 Rev Time 0.00
Received By ccole Date 2019-02-19 Time 09:02 Sent To  
Notes
2019-01-30 14:57:07THE REVISED M2.24 PLAN SHEET IS NOT ELECTRONICALLY
 SIGNED AND SEALED.

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2018-11-02 Cont ID  
Sent By shill Date 2018-11-02 Time 22:11 Rev Time 0.00
Received By shill Date 2018-11-02 Time 22:11 Sent To  
Notes
2018-11-02 22:12:10DIGITAL SIGNATURES ARE OK, ALL TRADES
 NEW SHEETS SUBMITTED NEXT REVIEW NEED VERIFICATION
 [email protected]
  

Review Stop Z ZONING
Rev No 4 Status P Date 2019-02-06 Cont ID  
Sent By jroach Date 2019-02-06 Time 10:53 Rev Time 0.00
Received By jroach Date 2019-02-06 Time 10:53 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 3 Status F Date 2019-02-05 Cont ID  
Sent By jroach Date 2019-02-05 Time 14:14 Rev Time 0.00
Received By jroach Date 2019-02-05 Time 14:14 Sent To  
Notes
2019-02-05 14:23:41ZONING PLAN REVIEW
 ___________________________________________
  
 DATE OF REVIEW: 02.05.2019
 PERMIT NO.: 15111020 (REVISION #18100146)
 ___________________________________________
  
 REVIEW STATUS: FAILED
 ___________________________________________
  
 PLEASE PROVIDE A WRITTEN RESPONSE TO THE FOLLOWING PLAN
 REVIEW COMMENTS (NO RESPONSE WAS PROVIDED FOR COMMENTS
 ISSUED ON 11/9/2018):
  
 1. THE NARRATIVE INDICATES THAT SEVERAL ITEMS WERE
 ADDED TO THE MATERIALS SCHEDULE ON SHEET L4.01, BUT
 THESE DO NOT APPEAR ON THE REVISED SHEET SUBMITTED.
 PLEASE CLARIFY. - MATERIALS WITH DETAIL #S F-06, G-14,
 DP-P-01, DP-01, DP-02, DP-03, DP-04, AND DP-05 ARE NOT
 SHOWN ON SHEET L4.01, AS SPECIFIED IN THE NARRATIVE OF
 CHANGES, AND YOUR RESPONSE. PLEASE NOTE THAT SHEET
 L4.01 HAS A LATEST REVISION DATE OF 8.10.2016.
 ___________________________________________
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 ___________________________________________
  
 QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING:
  
 JOHN P. ROACH, AICP, PRINCIPAL PLANNER
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES DEPARTMENT ? PLANNING DIVISION
 401 CLEMATIS STREET - P.O. BOX 3147
 WEST PALM BEACH, FLORIDA 33402
  
 P: 561.822.1448
 F: 561.822.1460
  
 E: [email protected]
  
 W: WPB.ORG
  

Review Stop Z ZONING
Rev No 2 Status F Date 2018-12-31 Cont ID  
Sent By jroach Date 2018-12-31 Time 08:51 Rev Time 0.00
Received By jroach Date 2018-12-31 Time 08:51 Sent To  
Notes
2018-12-31 08:51:59ZONING PLAN REVIEW
 ___________________________________________
  
 DATE OF REVIEW: 12.31.2018
 PERMIT NO.: 15111020 (REVISION #18100146)
 ___________________________________________
  
 REVIEW STATUS: FAILED
 ___________________________________________
  
 PLEASE PROVIDE A WRITTEN RESPONSE TO THE FOLLOWING PLAN
 REVIEW COMMENTS (NO RESPONSE WAS PROVIDED FOR COMMENTS
 ISSUED ON 11/9/2018):
  
 1. THE NARRATIVE INDICATES THAT SEVERAL ITEMS WERE
 ADDED TO THE MATERIALS SCHEDULE ON SHEET L4.01, BUT
 THESE DO NOT APPEAR ON THE REVISED SHEET SUBMITTED.
 PLEASE CLARIFY.
 3. MANUFACTURER?S SPECIFICATIONS SHALL BE PROVIDED FOR
 THE DOG PARK ARTIFICIAL TURF, AND SHALL INDICATE
 COMPLIANCE WITH ALL OF THE REQUIREMENTS OF SECTION
 94-451(E) AND (F) OF THE CITY?S ZONING AND LAND
 DEVELOPMENT REGULATIONS.
 4. ALL LANDSCAPE REVISIONS SHALL BE SUBMITTED AS A
 REVISION TO THE LANDSCAPE PERMIT.
 ___________________________________________
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 ___________________________________________
  
 QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING:
  
 JOHN P. ROACH, AICP, PRINCIPAL PLANNER
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES DEPARTMENT ? PLANNING DIVISION
 401 CLEMATIS STREET - P.O. BOX 3147
 WEST PALM BEACH, FLORIDA 33402
  
 P: 561.822.1448
 F: 561.822.1460
  
 E: [email protected]
  
 W: WPB.ORG
  

Review Stop Z ZONING
Rev No 1 Status F Date 2018-11-09 Cont ID  
Sent By jroach Date 2018-11-09 Time 09:47 Rev Time 0.00
Received By jroach Date 2018-11-09 Time 09:43 Sent To  
Notes
2018-11-09 09:47:59ZONING PLAN REVIEW
 ___________________________________________
  
 DATE OF REVIEW: 11.09.2018
 PERMIT NO.: 15111020 (REVISION #18100146)
 ___________________________________________
  
 REVIEW STATUS: FAILED
 ___________________________________________
  
 PLEASE PROVIDE A WRITTEN RESPONSE TO THE FOLLOWING PLAN
 REVIEW COMMENTS:
  
 1. THE NARRATIVE INDICATES THAT SEVERAL ITEMS WERE
 ADDED TO THE MATERIALS SCHEDULE ON SHEET L4.01, BUT
 THESE DO NOT APPEAR ON THE REVISED SHEET SUBMITTED.
 PLEASE CLARIFY.
 2. THE NARRATIVE INDICATES THAT REVISIONS ARE BEING
 MADE TO SHEET L4.52, BUT THIS SHEET DOES NOT APPEAR IN
 THE SHEETS SUBMITTED.
 3. MANUFACTURER?S SPECIFICATIONS SHALL BE PROVIDED FOR
 THE DOG PARK ARTIFICIAL TURF, AND SHALL INDICATE
 COMPLIANCE WITH ALL OF THE REQUIREMENTS OF SECTION
 94-451(E) AND (F) OF THE CITY?S ZONING AND LAND
 DEVELOPMENT REGULATIONS.
 4. ALL LANDSCAPE REVISIONS SHALL BE SUBMITTED AS A
 REVISION TO THE LANDSCAPE PERMIT.
 ___________________________________________
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 ___________________________________________
  
 QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING:
  
 JOHN P. ROACH, AICP, PRINCIPAL PLANNER
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES DEPARTMENT ? PLANNING DIVISION
 401 CLEMATIS STREET - P.O. BOX 3147
 WEST PALM BEACH, FLORIDA 33402
  
 P: 561.822.1448
 F: 561.822.1460
  
 E: [email protected]
  
 W: WPB.ORG
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved