Plan Review Details - Permit 18100142
Plan Review Stops For Permit 18100142
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2019-03-20 Cont ID  
Sent By skennedy Date 2019-03-20 Time 08:46 Rev Time 0.00
Received By skennedy Date 2019-03-20 Time 08:46 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2019-03-13 Cont ID  
Sent By shill Date 2019-03-13 Time 17:53 Rev Time 0.00
Received By shill Date 2019-03-13 Time 17:53 Sent To  
Notes
2019-03-13 17:54:06PROVISO: SEPARATE ROOF PERMIT REQUIRED
 ONLY ONE SET OF PLANS IN PACKAGE; 2ND SET REQUIRED TO
 BE SUBMITTED PRIOR TO ISSUANCE
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2018-10-17 Cont ID  
Sent By shill Date 2018-10-17 Time 16:41 Rev Time 0.00
Received By shill Date 2018-10-17 Time 16:41 Sent To  
Notes
2018-10-17 16:57:23****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 1. FBC 107, PROVIDE A PLAN WHICH SHOWS PROPOSED WORK.
 APPLICATION INDICATES "DOORS & ROOF TILE REPLACEMENT".
 THE PLAN SHOULD SHOW LOCATION OF DOORS PROPOSED TO BE
 REPLACED. IT SHOULD ALSO INDICATE LOCATION AND SCOPE OF
 ROOF TILES TO BE REPLACED. NOTE THAT NOT MORE THAN 25%
 OF THE ROOF CAN BE REPAIRED; OTHERWISE A REROOF IS
 REQUIRED, FBC EB 706.1.1.
  
 YOU CAN MARK UP A FLOOR PLAN TO SHOW THIS INFORMATION.
 EXISTING PLANS FOR THE ENTIRE BUILDING ARE NOT REQUIRED
 FOR THIS MINOR SCOPE OF WORK.
  
 2. PROVIDE PRODUCT APPROVAL FOR THE DOORS, FBC B 1609.
  
 3. ON THE TILE PRODUCT APPROVAL, INDICATE METHOD OF
 ATTACHMENT. UPON REQUEST THIS CAN BE SUBMITTED WITH THE
 ROOF SUB PERMIT APPLICATION.
  
 PLEASE CONTACT ME IF YOU NEED ASSISTANCE.
  
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 3 Status N Date 2019-03-19 Cont ID  
Sent By skennedy Date 2019-03-19 Time 10:50 Rev Time 0.00
Received By skennedy Date 2019-03-19 Time 10:49 Sent To  
Notes
2019-03-19 10:53:37ELECTRICAL DESIGN TO BE SUBMITTED AS A REVISION.

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2019-03-04 Cont ID  
Sent By jpearson Date 2019-03-04 Time 12:04 Rev Time 0.00
Received By jpearson Date 2019-03-04 Time 10:48 Sent To  
Notes
2019-03-04 12:04:30CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 PREVIOUS COMMENTS HAVE NOT BEEN ADDRESSED
 SATISFACTORILY. SEE BELOW.
  
 1. PER THE WPB AMENDMENTS TO THE FBC, PLAN (EACH SHEET
 OF BOTH COPIES) IS REQUIRED TO BEAR THE NAME AND BE
 SIGNED AND SEALED BY THE PERSON RESPONSIBLE FOR THE
 DESIGN. PROVIDE CORRECTION. WPB FBC 107.1, 107.2; FS
 471, 481
 2. PROVIDE ELECTRICAL PLAN FOR REVIEW DETAILING THE
 PROPOSED WORK. PLAN PROVIDED STATES THAT IT IS AN
 AS-BUILT FROM 2000 AND NO PROPOSED WORK IS SHOWN. WPB
 FBC 107.2.1, 107.3.5
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD
 SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2018-10-18 Cont ID  
Sent By jpearson Date 2018-10-18 Time 08:19 Rev Time 0.00
Received By jpearson Date 2018-10-18 Time 08:19 Sent To  
Notes
2018-10-18 08:19:44CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. PER THE WPB AMENDMENTS TO THE FBC, PLAN (EACH SHEET
 OF BOTH COPIES) IS REQUIRED TO BEAR THE NAME AND BE
 SIGNED AND SEALED BY THE PERSON RESPONSIBLE FOR THE
 DESIGN. PROVIDE CORRECTION. WPB FBC 107.1, 107.2; FS
 471, 481
 2. PROVIDE ELECTRICAL PLAN FOR REVIEW DETAILING THE
 PROPOSED WORK. PLAN PROVIDED STATES THAT IT IS AN
 AS-BUILT FROM 2000 AND NO PROPOSED WORK IS SHOWN. WPB
 FBC 107.2.1, 107.3.5
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD
 SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2018-10-11 Cont ID  
Sent By pleduc Date 2018-10-10 Time   Rev Time 0.00
Received By pleduc Date 2018-10-10 Time 14:34 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2019-03-13 Cont ID  
Sent By shill Date 2019-03-13 Time 17:54 Rev Time 0.00
Received By shill Date 2019-02-14 Time 10:31 Sent To  
Notes
2019-03-11 11:41:333/7 ON D.HARVEY DESK
  
  
2019-02-15 10:32:00B20

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-10-18 Cont ID  
Sent By gjohnson Date 2018-10-18 Time 14:43 Rev Time 0.00
Received By gjohnson Date 2018-10-03 Time 10:40 Sent To  
Notes
2018-10-17 16:59:2110/17 TO JP DESK
  
2018-10-05 10:40:48B28

Review Stop P PLUMBING
Rev No 2 Status P Date 2019-02-27 Cont ID  
Sent By gjohnson Date 2019-02-27 Time 15:54 Rev Time 0.00
Received By gjohnson Date 2019-02-27 Time 15:54 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2018-10-18 Cont ID  
Sent By gjohnson Date 2018-10-18 Time 14:27 Rev Time 0.00
Received By gjohnson Date 2018-10-18 Time 14:26 Sent To  
Notes
2018-10-18 14:43:151ST REVIEW:
 2017 FLORIDA BUILDING CODE 6TH EDITION
 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH
 EDITION
  
 PLUMBING COMMENTS:
  
 1. TEMPERED WATER SHALL BE DELIVERED FROM LAVATORIES
 AND GROUP WASH FIXTURES LOCATED IN PUBLIC TOILET
 FACILITIES PROVIDED FOR CUSTOMERS, PATRONS AND
 VISITORS. TEMPERED WATER SHALL BE DELIVERED THROUGH AN
 APPROVED WATER-TEMPERATURE LIMITING DEVICE THAT
 CONFORMS TO ASSE 1070 OR CSA B125.3. PER FBC PL 416.5
  
 2. THE SIDE WALL GRAB BAR SHALL BE 42 INCHES (1065 MM)
 LONG MINIMUM, LOCATED 12 INCHES (305 MM) MAXIMUM FROM
 THE REAR WALL AND EXTENDING 54 INCHES (1370 MM) MINIMUM
 FROM THE REAR WALL. PER FBC ACC 604.5.1
  
 3. TOILET PAPER DISPENSERS SHALL COMPLY WITH 309.4 AND
 SHALL BE 7 INCHES MINIMUM AND 9 INCHES MAXIMUM IN FRONT
 OF THE WATER CLOSET MEASURED TO THE CENTERLINE OF THE
 DISPENSER. THE OUTLET OF THE DISPENSER SHALL BE 15
 INCHES MINIMUM AND 48 INCHES MAXIMUM ABOVE THE FINISH
 FLOOR. PER FBC ACC 604.7
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status P Date 2019-03-13 Cont ID  
Sent By shill Date 2019-03-13 Time 18:01 Rev Time 0.00
Received By shill Date 2019-03-13 Time 18:01 Sent To  
Notes
2019-03-13 18:03:25BARCELONA 900 CONCRETE ROOF TILE NOA 16-0711.01
 ICP ADHESIVE FL 6332