Plan Review Details - Permit 18100122
Plan Review Stops For Permit 18100122
Review Stop E ELECTRICAL
Rev No 1 Status P Date 2018-10-18 Cont ID  
Sent By jleahy Date 2018-10-18 Time 10:20 Rev Time 0.00
Received By jleahy Date 2018-10-18 Time 10:20 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2018-10-05 Cont ID  
Sent By pleduc Date 2018-10-05 Time   Rev Time 0.00
Received By pleduc Date 2018-10-05 Time 11:38 Sent To E
Notes
2018-10-05 11:43:25THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 PLEASE CONSIDER THE FOLLOWING AS PROVISO:
  
 THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED
 AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE
 PROVISO COMMENTS WILL RESULT IN A FAILED FIRE
 INSPECTION
  
  
 1) THE INDICATED CODE REFERENCE, 7.2.1.5 DOES NOT
 APPEAR TO BE ACCURATE.
  
 PER NFPA 101, CHAPTER 7 MEANS OF EGRESS
  
 7.2.1.5.6 ELECTRICALLY CONTROLLED EGRESS DOOR
 ASSEMBLIES. DOOR
 ASSEMBLIES IN THE MEANS OF EGRESS SHALL BE PERMITTED TO
 BE
 ELECTRICALLY LOCKED IF EQUIPPED WITH APPROVED, LISTED
 HARDWARE,
 PROVIDED THAT ALL OF THE FOLLOWING CONDITIONS ARE MET:
 (1) THE HARDWARE FOR OCCUPANT RELEASE OF THE LOCK IS
 AFFIXED TO
 THE DOOR LEAF.
 (2) THE HARDWARE HAS AN OBVIOUS METHOD OF OPERATION
 THAT IS
 READILY OPERATED IN THE DIRECTION OF EGRESS.
 (3) THE HARDWARE IS CAPABLE OF BEING OPERATED WITH ONE
 HAND IN
 THE DIRECTION OF EGRESS.
 (4) OPERATION OF THE HARDWARE INTERRUPTS THE POWER
 SUPPLY
 DIRECTLY TO THE ELECTRIC LOCK AND UNLOCKS THE DOOR
 ASSEMBLY IN
 THE DIRECTION OF EGRESS.
 (5) *LOSS OF POWER TO THE LISTED RELEASING HARDWARE
 AUTOMATICALLY UNLOCKS THE DOOR ASSEMBLY IN THE
 DIRECTION OF
 EGRESS.
 (6) HARDWARE FOR NEW INSTALLATIONS IS LISTED IN
 ACCORDANCE WITH
 ANSI/UL 294, STANDARD FOR ACCESS CONTROL SYSTEM UNITS.
  
  
 PLEASE ENSURE COMPLIANCE
  
  
  
 2) UPDATE YOUR CODE REFERENCES ON FUURE SUBMITTALS.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  
  
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-10-18 Cont ID  
Sent By jleahy Date 2018-10-18 Time 10:20 Rev Time 0.00
Received By jleahy Date 2018-10-02 Time 15:37 Sent To  
Notes
2018-10-03 15:37:22ROUTED TO FIRE INBOX