Plan Review Details - Permit 18100116
Plan Review Stops For Permit 18100116
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2018-11-13 Cont ID  
Sent By jwitmer Date 2018-11-13 Time 07:56 Rev Time 0.00
Received By jwitmer Date 2018-11-13 Time 07:34 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date   Cont ID  
Sent By   Date 2019-05-01 Time   Rev Time 0.00
Received By skennedy Date 2019-05-01 Time 11:36 Sent To  
Notes
2019-05-01 11:37:14ELECTRICAL CONTRACTOR OF RECORD TO PROVIDE PANEL
 SCHEDULE TO ELECTRICAL INSPECTOR AT ROUGH ELECTRICAL
 INSPECTION.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2018-10-17 Cont ID  
Sent By jpearson Date 2018-10-17 Time 07:37 Rev Time 0.00
Received By jpearson Date 2018-10-17 Time 06:54 Sent To  
Notes
2018-10-17 07:37:19CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. PROVIDE ELECTRICAL PLAN FOR REVIEW, SIGNED AND
 SEALED BY A LICENSED DESIGN PROFESSIONAL OR SIGNED BY
 THE ELECTRICAL CONTRACTOR QUALIFIER. FS 471.003(2)(H);
 471.025; WPB FBC 107.2.1, 107.3.5
 2. PROVIDE PANEL SCHEDULE INDICATING ANY NEW OR ALTERED
 CIRCUITS, THE WIRE AND BREAKER SIZE FOR THESE CIRCUITS,
 AND AFCI OR GFCI PROTECTION WHERE APPLICABLE TO COMPLY
 WITH CODE. NEC 210.8, 210.12, 210.19, 210.20, 215.5,
 408.4
 3. IF ANY LOAD IS BEING ADDED, PROVIDE LOAD CALCULATION
 FOR SERVICE, INCLUDE EXISTING AND NEW LOADS TO CONFIRM
 CAPACITY OF SERVICE IS ADEQUATE. NEC 215.2, 220, 408.30
 4. PROVIDE GFCI AND AFCI PROTECTION PER CODE. NEC
 210.8, 210.12; FBC EX 607.1.1 OR 801.1, 801.2, OR 901.2
 AS APPLICABLE.
 5. PROVIDE TAMPER RESISTANT RECEPTACLES PER CODE. A
 NOTE WILL SUFFICE. NEC 406.12
 6. VALUE FOR WORK STATED ON PERMIT APPLICATION APPEARS
 LOW. PROVIDE COPY OF SIGNED CONTRACT WITH SCOPE AND
 VALUE OF WORK, TO INCLUDE ALL MATERIALS AND LABOR. THIS
 IS FOR TOTAL PROJECT, NOT JUST ELECTRICAL. FBC 109.3
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD
 SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2018-10-09 Cont ID  
Sent By scaldero Date 2018-10-09 Time 10:58 Rev Time 0.00
Received By scaldero Date 2018-10-09 Time 10:58 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-11-13 Cont ID  
Sent By cpuell Date 2018-11-13 Time 10:43 Rev Time 0.00
Received By cpuell Date 2018-10-02 Time 10:16 Sent To  
Notes
2018-10-04 10:16:42B07

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status N Date 2018-11-13 Cont ID  
Sent By jwitmer Date 2018-11-13 Time 07:56 Rev Time  
Received By jwitmer Date   Time   Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2018-10-24 Cont ID  
Sent By ccole Date 2018-10-24 Time 07:39 Rev Time 0.00
Received By ccole Date 2018-10-24 Time 07:07 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2018-10-31 Cont ID  
Sent By gjohnson Date 2018-10-31 Time 17:38 Rev Time 0.00
Received By gjohnson Date 2018-10-31 Time 17:33 Sent To  
Notes
***NONE***