Plan Review Details - Permit 18100109
Plan Review Stops For Permit 18100109
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2018-10-26 Cont ID  
Sent By skennedy Date 2018-10-26 Time 14:50 Rev Time 0.00
Received By skennedy Date 2018-10-26 Time 14:50 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2018-10-26 Cont ID  
Sent By skennedy Date 2018-10-26 Time 14:50 Rev Time 0.00
Received By skennedy Date 2018-10-26 Time 14:50 Sent To  
Notes
2018-10-26 14:56:59DISCUSSED WITH CHIEF LEDUC SEE REVIEWS UNDER 17021235.

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2018-10-09 Cont ID  
Sent By scaldero Date 2018-10-09 Time 12:11 Rev Time 0.00
Received By scaldero Date 2018-10-09 Time 12:03 Sent To B
Notes
2018-10-09 12:11:16PERMIT # 18100109
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 1) PLEASE PROVIDE DETAILS SHOWING COMPLIANCE WITH THE
 FOLLOWING REQUIREMENT(S):
  
 13.3.2.6* EXTERIOR ROOFS, CANOPIES, PORTE-COCHERES,
 BALCONIES, DECKS, OR SIMILAR PROJECTIONS. IN BUILDINGS
 PROTECTED THROUGHOUT BY AUTOMATIC SPRINKLERS IN
 ACCORDANCE WITH NFPA 13, AUTOMATIC SPRINKLER PROTECTION
 SHALL BE PROVIDED FOR THE EXTERIOR SPACES IN ACCORDANCE
 WITH 13.3.2.6.
 13.3.2.6.1 UNLESS THE REQUIREMENTS OF 13.3.2.6.2,
 13.3.2.6.3, OR 13.3.2.6.4 ARE MET, SPRINKLERS SHALL BE
 INSTALLED UNDER EXTERIOR PROJECTIONS EXCEEDING 4 FT IN
 WIDTH. [13:8.15.7.1]
 13.3.2.6.2* SPRINKLERS SHALL BE PERMITTED TO BE OMITTED
 WHERE THE EXTERIOR PROJECTIONS ARE CONSTRUCTED WITH
 MATERIALS THAT ARE NONCOMBUSTIBLE, LIMITED-COMBUSTIBLE,
 OR FIRE RETARDANT.TREATED WOOD AS DEFINED IN NFPA 703,
 STANDARD FOR FIRE RETARDANT? TREATED WOOD AND
 FIRE-RETARDANT COATINGS FOR BUILDING MATERIALS.
 [13:8.15.7.2]
 13.3.2.6.3 SPRINKLERS SHALL BE PERMITTED TO BE OMITTED
 FROM BELOW THE EXTERIOR PROJECTIONS OF COMBUSTIBLE
 CONSTRUCTION, PROVIDED THE EXPOSED FINISH MATERIAL ON
 THE EXTERIOR PROJECTIONS ARE NONCOMBUSTIBLE,
 LIMITED-COMBUSTIBLE, OR FIRE RETARDANT.TREATED WOOD AS
 DEFINED IN NFPA 703, STANDARD FOR FIRE RETARDANT?
 TREATED WOOD AND FIRE-RETARDANT COATINGS FOR BUILDING
 MATERIALS, AND THE EXTERIOR PROJECTIONS CONTAIN ONLY
 SPRINKLERED CONCEALED SPACES OR ANY OF THE FOLLOWING
 UNSPRINKLERED COMBUSTIBLE CONCEALED SPACES:
 (1) COMBUSTIBLE CONCEALED SPACES FILLED ENTIRELY WITH
 NONCOMBUSTIBLE INSULATION
 (2) LIGHT OR ORDINARY HAZARD OCCUPANCIES WHERE
 NONCOMBUSTIBLE OR LIMITED-COMBUSTIBLE CEILINGS ARE
 DIRECTLY ATTACHED TO THE BOTTOM OF SOLID WOOD JOISTS SO
 AS TO CREATE ENCLOSED JOIST SPACES 160 FT3 OR LESS IN
 VOLUME, INCLUDING SPACE BELOW INSULATION THAT IS LAID
 DIRECTLY ON TOP OR WITHIN THE CEILING JOISTS IN AN
 OTHERWISE SPRINKLERED ATTIC [SEE 11.2.3.1.4(4)(D) OF
 NFPA 13]
 (3) CONCEALED SPACES OVER ISOLATED SMALL EXTERIOR
 PROJECTIONS NOT EXCEEDING 55 FT2 IN AREA [13:8.15.7.3]
 13.3.2.6.4 SPRINKLERS SHALL BE PERMITTED TO BE OMITTED
 FROM EXTERIOR EXIT CORRIDORS WHEN THE EXTERIOR WALLS OF
 THE CORRIDOR ARE AT LEAST 50 PERCENT OPEN AND WHEN THE
 CORRIDOR IS ENTIRELY OF NONCOMBUSTIBLE CONSTRUCTION.
 [13:8.15.7.4]
 13.3.2.6.5* SPRINKLERS SHALL BE INSTALLED UNDER
 EXTERIOR PROJECTIONS GREATER THAN 2 FT WIDE OVER AREAS
 WHERE COMBUSTIBLES ARE STORED. [13:8.15.7.5]
 13.3.2.6.5.1 THE REQUIREMENT OF 13.3.2.6.5 MAY BE
 OMITTED IF THE SEPARATION OF ROOFS, CANOPIES,
 PORTE-COCHERES, BALCONIES, DECKS, OR SIMILAR
 PROJECTIONS ARE A MINIMUM OF 5 FT FROM THE SPRINKLERED
 BUILDING. THIS PROVISION IS EFFECTIVE FOR NEW
 CONSTRUCTION PROJECTS ONLY.
  
  
 SUE ELLEN CALDERON
 ASSISTANT FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2018-10-26 Cont ID  
Sent By skennedy Date 2018-10-26 Time 15:58 Rev Time 0.00
Received By skennedy Date 2018-10-18 Time 13:07 Sent To  
Notes
2018-10-22 13:07:32RESUB ROUTED TO ZONING INBOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-10-19 Cont ID  
Sent By shill Date 2018-10-19 Time 14:36 Rev Time 0.00
Received By shill Date 2018-10-02 Time 10:46 Sent To  
Notes
2018-10-19 14:38:5010/19 CONTRACTOR PULLED FROM REVIEW AS THE PLANS
 SUBMITTED SHOW WORK WHICH WAS ALREADY DONE UNDER
 ANOTHER PERMIT; HAS NEW PLANS TO SUBMIT WHICH CLARIFY
 SCOPE OF WORK. WE CALLED THE ARCHITECT; I RECOMMENDED
 THAT THEY PROVIDE A RESPONSE LETTER. ARCHITECT CAN SEND
 TO ME VIA EMAIL BY END OF DAY TODAY AND I'LL PUT WITH
 THE PACKAGE (IF IT COMES LATER, I WON'T BE ABLE TO PUT
 WITH THE PACKAGE AS IT WILL NO LONGER BE IN BUILDING
 DIVISION
  
  
2018-10-12 08:27:3410/12 TO BLDG MISC 2 BOX
  
2018-10-04 10:46:25ROUTED TO ZONING INBOX

Review Stop Z ZONING
Rev No 2 Status P Date 2018-10-26 Cont ID  
Sent By eschneid Date 2018-10-26 Time 15:42 Rev Time 0.25
Received By eschneid Date 2018-10-26 Time 15:35 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2018-10-05 Cont ID  
Sent By eschneid Date 2018-10-05 Time 10:47 Rev Time 0.75
Received By eschneid Date 2018-10-05 Time 08:08 Sent To FIRE
Notes
2018-10-05 10:47:00FAILED
  
 1) THE PLANS STATE "FUTURE FABRIC CANOPY". THE PLANS
 NEED TO BE UPDATED TO REFLECT THAT THIS IS PERMIT IS
 FOR THE CANOPY STRUCTURE.
  
 2) IT SEEMS THAT THERE ARE EXTRA PLAN SHEETS THAT HAVE
 BEEN SUBMITTED THAT DO NOT APPLY TO THIS PERMIT. FOR
 EXAMPLE, THE DEMOLITION PLAN. THIS NO LONGER APPLIES
 SINCE THE EXTERIOR DECK PERMIT, WHICH INCLUDED THE
 DEMOLITION OF THE PREVIOUS PORTE COCHERE, PASSED FINAL
 INSPECTION ON 9/12/18. REMOVE ANY SHEETS THAT DO NOT
 APPLY TO THE SCOPE OF WORK FOR THIS PERMIT.
  
 3) PROVIDE DETAILS OF THE CANOPY MATERIAL.
  
 CONTACT ERIC SCHNEIDER @ 9561) 822-1446
 [email protected]