Plan Review Details - Permit 18100072
Plan Review Stops For Permit 18100072
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2019-03-21 Cont ID  
Sent By dbattles Date 2019-03-21 Time 13:18 Rev Time 0.00
Received By dbattles Date 2019-03-21 Time 13:18 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2019-02-02 Cont ID  
Sent By dbattles Date 2019-02-02 Time 08:42 Rev Time 0.00
Received By dbattles Date 2019-02-01 Time 13:02 Sent To  
Notes
2019-02-02 08:43:25PROVIDO:
 -THIS PROJECT WILL NEED TO FULFILL REQUIREMENTS FOR
 AIPP.
 -PROVIDE PRODUCT APPROVALS FOR DOORS AT CHILLER YARD.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2018-12-20 Cont ID  
Sent By dbattles Date 2018-12-20 Time 11:15 Rev Time 0.00
Received By dbattles Date 2018-12-13 Time 15:45 Sent To  
Notes
2018-12-20 11:15:31****CORRECTIONS****
 W.P.B. PERMIT: 18100072
 REVIEWED: DECEMBER 17, 2018
  
 DYLAN BATTLES
 BUILDING PLANS EXAMINER I
 [email protected]
 561-805-6718
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC AMENDED = FLORIDA BUILDING CODE,6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC ENERGY = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 1. ART IN PUBLIC PLACES
 THE CITY OF WEST PALM BEACH ART IN PUBLIC PLACES
 ORDINANCE REQUIREMENT THAT APPLIES TO ANY REMODEL OR
 NEW CONSTRUCTION PROJECT FOR WHICH THE PERMIT
 APPLICATION WAS SUBMITTED AFTER 6/29/14, AND THE TOTAL
 PROJECT CONSTRUCTION COSTS ARE EQUAL TO OR GREATER THAN
 $750,000 WILL NEED TO COMPLY WITH THIS ORDINANCE.
 PER CITY OF WEST PALM BEACH ORDINANCE NO. 4504-14, AND
 CITY OF WEST PALM BEACH CODE OF ORDINANCES, ARTICLE V,
 ART IN PUBLIC PLACES, SECTION 78-123(A) AND SECTION
 78-126(A), THE ART ASSESSMENT IS 1% OF THE TOTAL
 PROJECT CONSTRUCTION COST.
 PER CITY OF WEST PALM BEACH CODE OF ORDINANCES, ARTICLE
 V, ART IN PUBLIC PLACES, SECTION 78-122, RENOVATION AND
 NEW CONSTRUCTION PROJECTS ARE ASSESSED CUMULATIVELY, SO
 THE ART ASSESSMENT WILL BE APPLICABLE TO ALL FUTURE
 PROJECTS.
 SEC. 78-129. - PUBLIC ART ASSESSMENT FOR PRIVATE
 DEVELOPMENT.
 (A) APPLICABILITY. THE PROVISIONS OF THIS ARTICLE AND
 THE PUBLIC ART ASSESSMENT SECTION SHALL APPLY TO ALL
 PRIVATE DEVELOPMENT PROJECTS, INCLUDING NEW
 CONSTRUCTION, OR THE RENOVATION OR IMPROVEMENT OF AN
 EXISTING BUILDING, WHERE TOTAL CONSTRUCTION COSTS ARE
 EQUAL TO OR GREATER THAN $750,000.00. ALL BUILDINGS
 WITHIN NEW PLANNED DEVELOPMENTS SHALL BE ASSESSED
 CUMULATIVELY TOWARDS THIS ART IN PUBLIC PLACES
 REQUIREMENT, EVEN IF THE BUILDINGS ARE PERMITTED
 SEPARATELY OR DEVELOPED IN PHASES. THE PROVISIONS OF
 THIS SECTION APPLY TO NEW DEVELOPMENT OR NEW
 CONSTRUCTION WITHIN EXISTING PLANNED DEVELOPMENTS.
 FOR CONTACT INFORMATION PLEASE CONTACT:
 MS. SYBILLE WELTER ART IN PUBLIC PLACES COORDINATOR
 822-1515 E-MAIL: [email protected]
  
 2. [FBC 107.3.5]PROVIDE SITE PLAN TO SHOW PROPERTY
 BOUNDARIES AND DISTANCES FROM PROPERTY LINE.
  
 3. [FBC EXISTING 501]SHEET A0.0-IN BUILDING DATA, STATE
 THE LEVEL OF ALTERATION FOR WORK BEING PERFORMED. THIS
 WOULD APPEAR TO BE A LEVEL 2 ALTERATION.
  
 4. [FBC 107.3.5]SHEET LS1.1
 A) IN EGRESS CALCULATIONS 2ND FLOOR. WHERE COLUMN D
 ADDS UP AREAS 2A AND 2B, THE TOTAL BELOW SAYS 12,233.
 PLEASE CHECK HOW COLUMN ABOVE ADDS UP BECAUSE IT SHOULD
 BE 21,233 (LOOKS LIKE FIRST TWO DIGITS GOT REVERSED)
 B) UPDATE CODE SECTIONS IN ALLOWABLE TRAVEL DISTANCES.
 TABLE 1017.2 FOR TRAVEL DISTANCES AND 1020.4 FOR DEAD
 END CORRODORS.
 C) WHAT IS BEING STORED IN STORAGE 2003, 2090 & 2101
 THAT IS LABLED HAZARDOUS AREA AND WHAT TYPES/AMOUNTS OF
 HAZARDOUS MATERIALS ARE STORED?
 D) WHAT IS BEING STORED IN STORAGE ROOM NEXT TO EXAM
 RM#14 T2022?
 THERE IS NO ROOM DESIGNATION FOR THIS STORAGE ROOM.
 E) ARE MEDGAS CONTAINERS STORED ON THIS FLOOR AND WHERE
 DO MEDGAS LINES ORIGINATE?
  
 5. [FBC 451.3.4.1]NO DOORS SHALL SWING INTO THE
 CORRIDOR EXCEPT
 THOSE TO SMALL CLOSETS OR SMALL MECHANICAL OR
 ELECTRICAL
 ROOMS THAT CANNOT BE USEFULLY OCCUPIED WITH THE DOORS
 IN THE CLOSED POSITION.
 DOOR T2026 1.3-1.N SHOULD BE REVIEWED FOR CODE
 COMPLIANCE WITH 451.3.4.1.
  
 6. [FBC 107.3.5]SHEET A1.1
 A) KEYNOTE #1 REFERS TO SEE SHEET A0.2. IS THIS
 SUPPOSED TO BE SHEET A0.3 FOR UL DETAILS?
 B) THERE IS A SMOKE BARRIER WITH NOTES TO INSTALL RATED
 WALL. CAN A CALL OUT BE ADDED TO SHOW DETAIL OF HOW
 THIS WALL COMPLIES WITH 709.4 CONTINUITY.
 C) CHECK THAT ALL NEW WALLS HAVE WALL TYPE ACCOCIATED
 WITH IT.
  
 7. [FBC TABLE 716.5]DEMO PLAN SHOWS DOORS BEING
 REMOVED. SHEET A7.1 HAS DOOR SCHEDULE, BUT LITTLE
 INFORMATION PROVIDED.
 PLEASE PROVIDE DOOR TYPES TO INCLUDE DOOR RATINGS AT
 RATED WALLS AND SMOKE BARRIER.
  
 8. [FBC 803.4]BENCHES. A BENCH COMPLYING WITH 903 SHALL
 BE PROVIDED WITHIN THE ROOM.
 CHECK BOTH LOCKER ROOMS FOR COMPLIANCE WITH FBC
 ACCESSIBILITY WHERE NEW WORK IS OCCURING.
  
 9. [FBC A404.2.4]MANEUVERING CLEARANCES.
 A) ACCESSIBLE BATHROOMS STALLS IN LOCKER ROOMS ARE
 GOOD, BUT THE TWO DOORS LEADING INTO LOCKER ROOMS
 SHOULD BE REVIEWED FOR COMPLIANCE WITH MANEUVERING
 CLEARANCE. WHILE I UNDERSTAND THAT SOME WORK IS
 EXISTING TO REMAIN, THIS AREA IS BEING SUBSTANTIALLY
 REWORKED AND THE NEW STALLS SHOULD BE FULLY ACCESSIBLE.
 B) PLEASE UPDATE DOOR SCHEDULE TO STATE DOOR TYPES AND
 IF DOOR CLOSERS ARE PROVIDED.
 C) CHECK THAT MANEUVERING CLEARANCES WORK AT EACH NEW
 WORK AREA WITH THE DOOR SCHEDULE.
  
 NOTE:
 -PLEASE PROVIDE COMMENT RESPONSE SHEET TO EXPLAIN HOW
 EACH COMMENT IS BEING ADDRESSED.
 -ADDITIONAL COMMENTS MAY BE FORTHCOMING PENDING REVIEW
 OF MATERIALS REQUESTED.
 -WHEN RESUBMITTING, PROVIDE TWO IDENTICAL COLLATED SETS
 OF DOCUMENTS FOR ISSUANCE. OLD SHEETS (BOTH SETS)
 SHOULD BE RETAINED IN THE PACKAGE; PLEASE DO NOT
 DISCARD ANY DOCUMENTS. THEY SHOULD BE BOUND TOGETHER
 SEPARATELY FROM THE TWO ISSUANCE SETS AND MARKED "VOID"
 OR "OLD SHEETS". PLEASE DO NOT STAMP THE PLANS VOID AS
 APPLICANTS ARE INADVERTENTLY STAMPING SHEETS THAT WE
 NEED "VOID", RENDERING THEM NOT USABLE.
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2019-02-26 Cont ID  
Sent By jpearson Date 2019-02-26 Time 14:55 Rev Time 0.00
Received By jpearson Date 2019-02-26 Time 14:55 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2018-11-20 Cont ID  
Sent By jpearson Date 2018-11-20 Time 15:51 Rev Time 0.00
Received By jpearson Date 2018-11-20 Time 10:44 Sent To  
Notes
2018-11-20 15:51:06CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. PROVIDE PANEL BOARD BONDING PER NEC 517.14
 2. PROVIDE A MINIMUM OF 36 RECEPTACLES IN THE OPERATING
 ROOMS PER CODE. NEC 517.19(C)(1)
 3. SHEET E7.1 IS ILLEGIBLE. PROVIDE LEGIBLE SHEET. WPB
 FBC 107.2.1
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD
 SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop E-LOWVOLT ELECTRICAL LOW VOLTAGE
Rev No 1 Status P Date 2018-11-20 Cont ID  
Sent By jpearson Date 2018-11-20 Time 15:18 Rev Time 0.00
Received By jpearson Date 2018-11-20 Time 15:18 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2019-03-18 Cont ID  
Sent By scaldero Date 2019-03-18 Time 14:33 Rev Time 0.00
Received By scaldero Date 2019-03-18 Time 14:33 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2018-10-18 Cont ID  
Sent By scaldero Date 2018-10-18 Time 10:34 Rev Time 0.00
Received By scaldero Date 2018-10-18 Time 08:36 Sent To  
Notes
2018-10-18 10:41:09PERMIT # 1810072
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 1) SEPARATE PLANS AND PERMITS ARE REQUIRED FOR THE
 INSTALLATION OR MODIFICATION OF THE FIRE SPRINKLER
 SYSTEM AND/OR FIRE ALARM SYSTEM.
  
  
 SUE ELLEN CALDERON
 ASSISTANT FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2019-04-02 Cont ID  
Sent By gjohnson Date 2019-04-02 Time 10:23 Rev Time 0.00
Received By gjohnson Date 2019-03-29 Time 16:08 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date   Cont ID  
Sent By   Date 2019-03-26 Time   Rev Time 0.00
Received By lmarchan Date 2019-03-15 Time 09:38 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2019-03-06 Cont ID  
Sent By lmarchan Date 2019-03-06 Time 08:09 Rev Time 0.00
Received By lmarchan Date 2019-01-30 Time 07:29 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2019-01-08 Cont ID  
Sent By gjohnson Date 2019-01-08 Time 09:49 Rev Time 0.00
Received By gjohnson Date 2018-10-16 Time 16:32 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 3 Status P Date 2019-02-25 Cont ID  
Sent By lmarchan Date 2019-02-25 Time 14:27 Rev Time 0.00
Received By lmarchan Date 2019-02-07 Time 11:10 Sent To  
Notes
2019-02-25 14:27:20PER IMPACT FEE OFFICE, NO MONEY OWED, NO MU NUMBER
 CREATED (SEE ATTACHEMENT)
2019-02-07 11:10:552/7/19 EMAILED IMPACT FEE OFFICE FOR REVIEW. LEM

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status F Date 2019-02-02 Cont ID  
Sent By dbattles Date 2019-02-02 Time 09:16 Rev Time 0.00
Received By dbattles Date 2019-02-02 Time 09:16 Sent To  
Notes
2019-02-02 09:18:00PLEASE PROVIDE PALM BEACH COUNTY IMPACT REVIEW, OR
 CONTACT ME TO DISCUSS.
  
 DYLAN BATTLES
 BUILDING PLANS EXAMINER I
 [email protected]
 561-805-6718
  
  

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2018-12-14 Cont ID  
Sent By dbattles Date 2018-12-14 Time 10:02 Rev Time 0.00
Received By dbattles Date 2018-12-13 Time 16:37 Sent To  
Notes
2018-12-14 10:03:35[FBC AMENDED 109]PLANS WILL BE REVIEWED BY THE PBC
 IMPACT FEE OFFICE DIGITALLY VIA PROJECTDOX UPON
 NOTIFICATION BY THIS OFFICE. NOTIFICATION MAY OCCUR
 WHEN PLANS ARE NEAREST FINAL FORM. YOU MAY COORDINATE
 WITH THE IMPACT FEE OFFICE AT (561) 233-5025 OR SIMPLY
 UPLOAD THE MUNICIPAL IMPACT FEE QUESTIONNAIRE FORM TO
 YOUR PROJECT AND NAME THE FILE MUNICIPAL IMPACT FEE
 QUESTIONNAIRE. THE FORM CAN BE FOUND AT: HTTP://DISCOVE
 R.PBCGOV.ORG/PZB/ADMINISTRATION/PDF/IMPACTFEES/FORMS/QU
 ESTIONNAIRE.PDF UPON APPROVAL AND FEE PAYMENT, PLEASE
 UPLOAD THE RECEIPT TO YOUR PROJECT OR EMAIL IT TO
 [email protected]
  
 DYLAN BATTLES
 BUILDING PLANS EXAMINER I
 [email protected]
 561-805-6718
  

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2019-04-01 Cont ID  
Sent By ccole Date 2019-04-01 Time 13:19 Rev Time 0.00
Received By ccole Date 2019-04-01 Time 13:19 Sent To  
Notes
2019-04-01 13:22:47MECHANICAL PROVISOS:
  
 1) DEFERRED SUBMITTALS
 A) SUPPLY AND EXHAUST DUCTWORK.
 B) OR AND PROCEDURE ROOM DIFFUSERS AND GRILLES.
 C) DIFFERENTIAL PRESSURE SENSORS
 D) CHILLED WATER AND STEAM PIPING.
 E) PIPING INSULATION
 F) FILTER BANKS
 G) DUCT SMOKE DETECTORS
 H) FIRE AND FIRE/SMOKE DAMPERS
  
 2) PARKING GARAGE SMOKE TEST REQUIRED.
  
 3) COMMISSIONING REPORT DUE AT FINAL INSPECTION

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2019-03-26 Cont ID  
Sent By ccole Date 2019-03-26 Time 14:34 Rev Time 0.00
Received By ccole Date 2019-03-25 Time 09:55 Sent To  
Notes
2019-03-26 14:38:061ST REVIEW FBC-2017 MECHANICAL
 PERMIT #18100072
 3/26/19
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
 FGI GUIDELINES FOR DESIGN AND CONSTRUCTION OF HEALTH
 CARE FACILITIES
 ASHRAE 170-2008
  
 PLAN REVIEW RESULTS: DENIED:
  
 1) THE ENGINEER'S RESPONSES TO COMMENT'S #4 & 5 FROM
 THE PREVIOUS REVIEW (PRINTED BELOW) MUST BE PUT INTO A
 SINGED AND ESA;LED LETTER FOR FINAL APPROVAL.
  
 4) NEW PLAN SHEET M4.0: A) THE FIRE DAMPER IN THE MED
 GAS EXHAUST DUCT IS PROHIBITED- SECTION 510.7.1 FBC M.
 B) THE EXHAUST DUCT PENETRATING THE FIRE-RATED MED GAS
 ROOM WALL SHALL BE ENCLOSED IN FIRE-RATED CONSTRUCTION
 FROM THE POINT OF PENETRATION TO THE OUTLET TERMINAL-
 SECTION 510.7.3 FBC M. C) THE EXHAUST OUTLET FROM THE
 MED GAS ROOM SHALL HAVE A MINIMUM 10' CLEARANCE TO THE
 DOOR OPENING- SECTION 501.3.1 (2) FBC M.
  
 5) SHEET M4.3 & M4.4: THE EXHAUST SYSTEM FOR THE
 ANESTHESIA ROOM SHALL BE INDEPENDENT OF THE OTHER
 ENVIRONMENTAL EXHAUST SYSTEMS- SEE SECTION 501.2 FBC M.
  
 7) DEFERRED SUBMITTALS
  
 A) SUPPLY AND EXHAUST DUCTWORK.
 B) OR AND PROCEDURE ROOM DIFFUSERS AND GRILLES.
 C) DIFFERENTIAL PRESSURE SENSORS
 D) CHILLED WATER AND STEAM PIPING.
 E) PIPING INSULATION
 F) FILTER BANKS
 G) DUCT SMOKE DETECTORS
 H) FIRE AND FIRE/SMOKE DAMPERS
  
 PLEASE NOTE ALL SUBMITTALS MAY BE DEFERRED IN
 ACCORDANCE WITH SECTION 107.3.4.1 WPB. PROVIDE A LIST
 ON THE PLANS.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS.
  
 IF YOU HAVE ANY QUESTIONS ABOUT THE REVIEW COMMENTS
 PLEASE CONTACT ME.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2019-03-06 Cont ID  
Sent By ccole Date 2019-03-06 Time 07:44 Rev Time 0.00
Received By ccole Date 2019-03-05 Time 11:22 Sent To  
Notes
2019-03-06 08:32:381ST REVIEW FBC-2017 MECHANICAL
 PERMIT #18100072
 3/6/19
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
 FGI GUIDELINES FOR DESIGN AND CONSTRUCTION OF HEALTH
 CARE FACILITIES
 ASHRAE 170-2008
  
 PLAN REVIEW RESULTS: DENIED:
  
 1) THE AC CALCULATIONS REQUIRE ELECTRONIC SEALS AND
 SIGNATURES PER SECTION 61G15-23.005 FAC.
  
 2) IN REFERENCE TO 1ST REVIEW COMMENT'S #8A, B, C, D,
 IT APPEARS THAT THE LS1.1 PLAN HAS NOT BEEN UPDATED TO
 REMOVE THE HAZARDOUS ROOM IDENTIFICATIONS- SEE COLOR
 LEGEND THAT DESIGNATES HATCHED AREAS AS "HAZARDOUS
 STORAGE".
  
 3) IN REFERENCE TO 1ST REVIEW COMMENT #8D, THE LS1.1
 PLAN IS STILL INDICATING ROOM 2083 AS "STERILE SUPPLY"
 HOWEVER THE NARRATIVE RESPONSE INDICATES THIS ROOM HAS
 BEEN CHANGED TO "CLEAN SUPPLY".
  
 4) NEW PLAN SHEET M4.0: A) THE FIRE DAMPER IN THE MED
 GAS EXHAUST DUCT IS PROHIBITED- SECTION 510.7.1 FBC M.
 B) THE EXHAUST DUCT PENETRATING THE FIRE-RATED MED GAS
 ROOM WALL SHALL BE ENCLOSED IN FIRE-RATED CONSTRUCTION
 FROM THE POINT OF PENETRATION TO THE OUTLET TERMINAL-
 SECTION 510.7.3 FBC M. C) THE EXHAUST OUTLET FROM THE
 MED GAS ROOM SHALL HAVE A MINIMUM 10' CLEARANCE TO THE
 DOOR OPENING- SECTION 501.3.1 (2) FBC M.
  
 5) SHEET M4.3 & M4.4: THE EXHAUST SYSTEM FOR THE
 ANESTHESIA ROOM SHALL BE INDEPENDENT OF THE OTHER
 ENVIRONMENTAL EXHAUST SYSTEMS- SEE SECTION 501.2 FBC M.
  
 6) M4.5: IN REFERENCE TO 1ST REVIEW COMMENT #9 PLEASE
 SHOW THE LOCATION OF THE REQUIRED DUCT SMOKE DETECTOR
 FOR THE NEW AHU-1- SECTION 606.2.1 FBC M.
  
 7) REQUIRED PRODUCT SUBMITTALS TO BE APPROVED BY THE
 ENGINEER OF RECORD:
  
 A) SUPPLY AND EXHAUST DUCTWORK.
 B) OR AND PROCEDURE ROOM DIFFUSERS AND GRILLES.
 C) DIFFERENTIAL PRESSURE SENSORS
 D) CHILLED WATER AND STEAM PIPING.
 E) PIPING INSULATION
 F) FILTER BANKS
 G) DUCT SMOKE DETECTORS
 H) FIRE AND FIRE/SMOKE DAMPERS
  
 PLEASE NOTE ALL SUBMITTALS MAY BE DEFERRED IN
 ACCORDANCE WITH SECTION 107.3.4.1 WPB. PROVIDE A LIST
 ON THE PLANS.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS.
  
 IF YOU HAVE ANY QUESTIONS ABOUT THE REVIEW COMMENTS
 PLEASE CONTACT ME.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2018-12-05 Cont ID  
Sent By ccole Date 2018-12-05 Time 11:13 Rev Time 0.00
Received By ccole Date 2018-12-03 Time 16:59 Sent To  
Notes
2018-12-05 11:17:271ST REVIEW FBC-2017 MECHANICAL
 PERMIT #18100072
 12/5/18
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
 FGI GUIDELINES FOR DESIGN AND CONSTRUCTION OF HEALTH
 CARE FACILITIES
 ASHRAE 170-2008
  
 PLAN REVIEW RESULTS: DENIED:
  
 1) SUBMIT AC COOLING AND HEATING CALCULATIONS FOR THE
 NEW SYSTEMS IN COMPLIANCE WITH SECTION C403.2.1 FBC EC.
  
 2) COMMISSIONING OF THE NEW MECHANICAL SYSTEMS IS
 REQUIRED PER SECTION C408.2 FBC EC. SUBMIT A
 COMMISSIONING PLAN AS OUTLINED IN SECTION C408.2.1 AND
 DESCRIBED IN SECTIONS C408.2.2- C408.2.3.3. PLEASE NOTE
 THAT COPIES OF THE COMMISSIONING REPORT SHALL BE
 SUBMITTED TO THE BUILDING OWNER AND TO THE WPB BUILDING
 DEPARTMENT FOR FINAL APPROVAL AND CO OF THE BUILDING.
  
 3) SHEET M0.1: PLEASE REVIEW SECTIONS 8.5 AND 8.6
 ASHRAE 170-2014 AND PLACE NOTES ON THE PLAN
 ACCORDINGLY. IN ADDITION PLEASE PROVIDE ON THE PLAN A
 SUMMARY OF ALL REQUIRED SYSTEM TESTING AND
 DOCUMENTATION REQUIRED FOR FINAL MECHANICAL APPROVAL
 INCLUDING:
  
 A) COMMISSIONING AND TESTING AND BALANCING REPORT.
  
 B) ACCEPTANCE TESTING REPORT.
  
 C) DUCT CLEANLINESS REPORT.
  
 D) BLOWER TESTS REPORTS FOR EACH OPERATING ROOM.
  
 E) FAN SHUTDOWN AND FIRE ALARM TEST.
  
 4) SHEET IC1.0: IT APPEARS THAT THE PLAN IS INDICATING
 ICRA CLASS II BECAUSE THAT BOX IS EMBOLDENED. WOULD
 THIS BE THE CLASS FOR A MAJOR DEMOLITION? THERE ARE NO
 REQUIREMENTS LISTED IN THAT CLASS FOR NEGATIVE AIR
 PRESSURE AND HEPA EQUIPPED AIR FILTRATION UNITS. PLEASE
 CLARIFY HOW AIRBORNE DUST WILL BE CONTROLLED AND DUCT
 SYSTEM CONTAMINATION BE PREVENTED.
  
 5) M4.0: PROVIDE WIND LOAD ENGINEERING DESIGN CRITERIA
 FOR INSTALLATION OF THE CHILLER- SECTION 301.15
  
 6) M4.0: INDICATE HOW THE CHILLER PIPING WILL BE
 SUPPORTED INSIDE THE SOFFIT- PROVIDE A DETAIL
  
 7) M4.0: PROVIDE CHILLER PIPING AND INSULATION
 SPECIFICATIONS.
  
 8) M4.3, M4.4, & LS1.1: THE FOLLOWING COMMENTS (A-F)
 PERTAIN TO THE ROOMS THAT ARE DESIGNATED AS "HAZARDOUS"
 ON SHEET LS.1.1. THE ARCHITECT MUST REVIEW SECTIONS 307
 AND 414 FBC B AND PROVIDE MORE SPECIFIC INFORMATION
 ABOUT THE USE OF THESE ROOMS AND WHAT IF ANY HAZARDOUS
 MATERIALS WILL BE STORED, AND THERIR WQUANTITES. PLEASE
 SEE SECTION 414.1.3 AND PROVIDE A REPORT.
  
 A) M4.3, LS1.1: FIRE DAMPERS APPEAR TO BE MISSING FOR
 DUCTS THAT ARE PENETRATING THE 1-HR. FIRE-RATED WALLS
 ENCLOSING STORAGE- 2003, CLEANUTILTY- 2034, AND SOILED
 UTILITY- 2049- SEE SECTION 607.5.2 FBC M.
  
 B) M4.3, LS1.1: THE STORAGE ROOM BETWEEN BAY #7 & 8
 REQUIRES NEGATIVE PRESSURE AND ALL AIR TO BE EXHAUSTED
 TO THE OUTDOORS PER TABLE 701 ASHRAE 170-2014. IN
 ADDITION MINIMUM OF 2 O/A CHANGES AND 10 TOTAL AIR
 CHANGES ARE REQUIRED- PLEASE CORRECT THE PLANS.
  
 C) M4.4, LS1.1: EQUIPMENT STORAGE ROOMS 2090, 2097,
 2101 REQUIRES NEGATIVE PRESSURE, ALL AIR TO BE
 EXHAUSTED TO THE OUTDOORS, A MINIMUM OF 2 O/A CHANGES
 AND 10 TOTAL AIR CHANGES- TABLE 7-1. PLEASE PROVIDE
 EQUIPMENT LAYOUT PLANS AND EQUIPMENT SCHEDULES FOR EACH
 ROOM- SECTION 107.2.1 WPB.
  
 D) M4.4, LS1.1: THE CENTRAL STERILE ROOM 2083 REQUIRES
 NEGATIVE PRESSURE, ALL AIR TO BE EXHAUSTED TO THE
 OUTDOORS, AND A MINIMUM OF 10 TOTAL ACH- TABLE 7-1.
 INDICATE IF A STEAM STERILIZER WILL BE INSTALLED IN THE
 ROOM AND PROVIDE AN EXHAUST HOOD IF APPLICABLE- SEE
 SECTIONS 7.4.2 ASHRAE 170-2014, AND ALSO SECTION
 3.1-8.2.2.9 OF THE GUIDELINES WHICH HAS ADDITIONAL
 REQUIREMENTS FOR ETHYLENE OXIDE (ETO) STERILIZATION
 EQUIPMENT. PLEASE PROVIDE AN EQUIPMENT LAYOUT AND
 EQUIPMENTR SCHEDULE FOR THE ROOM.
  
 E) M4.4, LS1.1: THE ANESTHESIA WORK ROOM 2109 REQUIRES
 NEGATIVE PRESSURE, ALL AIR TO BE EXHAUSTED TO THE
 OUTDOORS, AND A MINIMUM OF 8 TOTAL ACH- TABLE 7-1.
  
 F) M4.4, LS1.1: THE JANITOR'S ROOM REQUIRES NEGATIVE
 PRESSURE, ALL AIR TO BE EXHAUSTED TO THE OUTDOORS, AND
 A MINIMUM OF 10 TOTAL ACH- TABLE 7-1.
  
 9) M4.5: PLEASE SHOW THE LOCATION OF THE REQUIRED DUCT
 SMOKE DETECTOR FOR THE NEW AHU-1- SECTION 606.2.1 FBC
 M.
  
 10) M4.5: VERIFY THE REQUIRED CLEARANCES FOR THE O/A
 INTAKE TO AHU-1 IN ACCORDANCE WITH SECTION 6.3.1 ASHRAE
 170-2014- MINIMUM 25' FROM ALL EXHAUST AND VENT
 DISCHARGES, AND AT 6' ABOVE GRADE. A) SUBMIT
 MANUFACTURER'S SPECIFICATIONS AND THE MIAMI-DADE NOA
 FOR THE O/A LOUVER PER SECTION 6.3.1, AND SECTION 401.5
 FBC M.
  
 11) M4.5: IDENTIFY THE NEW FAN COIL UNIT SHOWN IN MECH
 ROOM M002, INCLUDE IT IN THE EQUIPMENT SCHEDULES, AND
 SUBMIT AC COOLING AND HEATING CALCULATIONS FOR SIZING
 OF THE UNIT.
  
 12) M4.5: PER NOTES #11 & 12, PLEASE SHOW THE RETURN
 DUCT CONTINUATIONS ON THE FIRST FLOOR- SECTION 603.1
 FBC M.
  
 13) M4.6 & M.7: PROVIDE AN ABBREVIATIONS TABLE THAT
 INCLUDES MPS, BOP, AND CR.
  
 14) M5.1: REFER TO TABLE C403.2.3(7) FBC EC AND VERIFY
 THAT THE NEW CHILLER MEETS THE EFFICIENCY REQUIRMENTS
 IN ACCORDANCE WITH THE AHRI 550/590 TEST REQUIREMENTS.
  
 15) M5.3 & M5.4: TABLE 7-1 SHOWS 2 O/A ACH FOR SOILED
 WORKROOM AND SOILED HOLDING, HOWEVER NO O/A ACH IS
 SHOWN IN THE AIRFLOW SUMMARY TABLE- PLEASE CORRECT.
  
 16) FILTRATION BANKS ARE REQUIRED IN ACCORDANCE WITH
 SECTIONS 6.4 AND TABLE 6-1 ASHRAE 170-2014.
  
 17) REQUIRED PRODUCT SUBMITTALS TO BE APPROVED BY THE
 ENGINEER OF RECORD:
  
 A) SUPPLY AND EXHAUST DUCTWORK.
 B) OR AND PROCEDURE ROOM DIFFUSERS AND GRILLES.
 C) DIFFERENTIAL PRESSURE SENSORS
 D) CHILLED WATER AND STEAM PIPING.
 E) PIPING INSULATION
 F) FILTER BANKS
 G) DUCT SMOKE DETECTORS
 H) FIRE AND FIRE/SMOKE DAMPERS
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS.
  
 IF YOU HAVE ANY QUESTIONS ABOUT THE REVIEW COMMENTS
 PLEASE CONTACT ME.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop MEDGAS MEDICAL GAS
Rev No 3 Status P Date 2019-04-02 Cont ID  
Sent By gjohnson Date 2019-04-02 Time 10:23 Rev Time 0.00
Received By gjohnson Date 2019-04-02 Time 10:23 Sent To  
Notes
***NONE***

Review Stop MEDGAS MEDICAL GAS
Rev No 2 Status P Date 2019-03-01 Cont ID  
Sent By gjohnson Date 2019-03-01 Time 15:49 Rev Time 0.00
Received By gjohnson Date   Time   Sent To  
Notes
***NONE***

Review Stop MEDGAS MEDICAL GAS
Rev No 1 Status F Date 2019-01-08 Cont ID  
Sent By gjohnson Date 2019-01-08 Time 09:30 Rev Time 0.00
Received By gjohnson Date 2019-01-08 Time 09:30 Sent To  
Notes
2019-01-08 09:49:301ST REVIEW:
 2017 FLORIDA BUILDING CODE 6TH EDITION
 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH
 EDITION
  
 MED GAS COMMENTS:
  
 1. SHT. P1.2 IT IS UNCLEAR WHAT PIPING IS BEING REMOVED
 AND WHICH IS REMAINING IS SERVICE PLEASE CLARIFY. PER
 WPB AMEND TO FBC 107.2.1
  
 2. PLEASE PLACE NOTE ON PLAN THE CONTRACTOR AND ANYONE
 INSTALLING MED GAS PIPING SHALL BE MED GAS CERTIFIED.
 INSTALLERS SHALL PROVIDE FOR INSPECTORS ON JOBSITE AND
 COPY'S PROVIDED FOR PERMIT ISSUE. PER FAC 61G4-15.031
  
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
2019-01-07 09:22:18 
  

Review Stop P PLUMBING
Rev No 3 Status P Date 2019-04-02 Cont ID  
Sent By gjohnson Date 2019-04-02 Time 10:22 Rev Time 0.00
Received By gjohnson Date 2019-04-02 Time 10:22 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2019-03-01 Cont ID  
Sent By gjohnson Date 2019-03-01 Time 15:48 Rev Time 0.00
Received By gjohnson Date   Time   Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2019-01-04 Cont ID  
Sent By gjohnson Date 2019-01-04 Time 11:26 Rev Time 0.00
Received By gjohnson Date 2018-12-21 Time 10:56 Sent To  
Notes
2019-01-08 09:30:071ST REVIEW:
 2017 FLORIDA BUILDING CODE 6TH EDITION
 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH
 EDITION
  
 PLUMBING COMMENTS:
 1. SHT. A9.2 DETAIL #8 THE CLEAR FLOOR SPACE FOR THE
 TOILET SHOWS THE SHOWER ENCROACHING INTO SPACE THE
 SHOWER IS NOT PERMITTED TO ENCROACH THE SHOWER STALL
 SHALL BE OUTSIDE OF THE CLEAR FLOOR SPACE. PER FBC ACC
 604.3.2
 2. SHT. A9.2 DETAIL #8 THE TRANSFER TYPE SHOWER SHALL
 HAVE WALLS ON THREE SIDES, ONE SIDE WALL WITH A SEAT, A
 BACK WALL WITH GRAB BARS AND ANOTHER SIDE WALL WITH
 CONTROLS. PER FBC ACC 608.2.1, FIGURE 608.2.1, 608.3.1,
 608.4
 3. PLEASE PROVIDE A DETAIL SHOWING COMPLIANCE WITH FBC
 ACC 608.5.1
 4. GRAB BARS SHALL BE INSTALLED 33 INCHES MINIMUM AND
 36 INCHES MAXIMUM ABOVE THE FINISH FLOOR MEASURED TO
 THE TOP OF THE GRIPPING SURFACE. PER FBC ACC 909.4
 5. SHT P2.1 THE SHOWER IN THE MEN?S LOCKER ROOM
 BATHROOM #2111 IS SHOWN ENCROACHING INTO THE CLEAR
 FLOOR SPACE OF THE TOILET AND DOES NOT MATCH THE LAYOUT
 OF THE ARCHITECTURAL PLANS PLEASE CLARIFY. PER WPB
 AMEND TO FBC 107.2.1
 6. SHT. A1.1 SHOWS A CLINICAL SINK IN ROOM T2049 SHT
 P2.1 DOES NOT SHOW A CLINICAL SINK AND THE DEMO NOTES
 IT BEING REMOVED PLEASE CLARIFY. PER WPB AMEND TO FBC
 107.2.1
 7. SHT. A1.1 ROOM T2002 DOES NOT SHOW THE MOP SINK THAT
 IS SHOWN ON SHT P2.1 PLEASE CLARIFY. PER WPB AMEND TO
 FBC 107.2.1
 8. SHT. P2.1 THE (X)1 ??DHW FOR THE MEN?S LOCKER ROOM
 BATHROOM SHALL BE RECONNECTED TO THE (X) ?? DHR AS IT
 WAS REMOVED ON THE DEMO SHEET P1.1. PER FBC PL 607.2
 9. PLEASE PROVIDE A SANITARY FLOOR PLAN SHOWING NEW AND
 EXISTING PIPING AND LABEL THE STACK TO MATCH LABELS ON
 THE ISOMETRIC DRAWINGS . PER WPB AMEND TO FBC 107.2.1
 10. SHT. P3.1 THE ISOMETRIC ON STACK B-1 WITH THE NURSE
 STATION 2002 SHOWS A S1 I COULD NOT LOCATE ON THE FLOOR
 PLAN PLEASE CLARIFY. PER WPB AMEND TO FBC 107.2.1
 11. SHT. P3.1 THE ISOMETRIC ON STACK B-1 WITH THE NURSE
 STATION 2002 IS SHOWING A FIXTURE LABEL W3 PLEASE
 IDENTIFY THIS FIXTURE PROVIDE A FIXTURE SCHEDULE. . PER
 WPB AMEND TO FBC 107.2.1
 12. SHT. P3.1 I COULD NOT LOCATE THE NEW PIPING FOR THE
 MOP SINK IN JANITORS ROOM T2002 PLEASE CLARIFY. . PER
 WPB AMEND TO FBC 107.2.1
 13. SHT. P3.2 PLEASE LABEL ALL HOT AND COLD PIPING. .
 PER WPB AMEND TO FBC 107.2.1
 14. SHT. P3.2 THE NEW LINE NPSW FROM THE WATER SOFTNER
 DOES NOT MATCH THE LAY OUT FROM THE FLOOR PLAN SHT.
 P2.1 PLEASE CLARIFY. . PER WPB AMEND TO FBC 107.2.1
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2019-03-21 Cont ID  
Sent By dbattles Date 2019-03-21 Time 13:23 Rev Time 0.00
Received By dbattles Date 2019-03-21 Time 13:23 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2019-02-02 Cont ID  
Sent By dbattles Date 2019-02-02 Time 08:20 Rev Time 0.00
Received By dbattles Date 2019-02-02 Time 08:13 Sent To  
Notes
2019-02-02 08:20:51ALL SHEETS OK FOR SECOND REVIEW.
 ANY ADDITIONAL SHEETS FOR THIRD REVIEW WILL NEED TO BE
 DIGITALLY SIGNED.

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2018-12-14 Cont ID  
Sent By dbattles Date 2018-12-14 Time 10:00 Rev Time 0.00
Received By dbattles Date 2018-12-13 Time 16:37 Sent To  
Notes
2018-12-14 10:01:281ST REVIEW ALL SHEETS-OK
 ANY ADDITIONAL SHEETS FOR 2ND REVIEW WILL NEED TO BE
 LOOKED AT FOR DIGITAL SIGNATURE.
2018-11-20 10:44:53ELECTRICAL SHEETS OK.

Review Stop Z ZONING
Rev No 2 Status P Date   Cont ID  
Sent By   Date 2019-02-21 Time   Rev Time 0.00
Received By pgreilic Date 2019-02-21 Time 15:43 Sent To  
Notes
2019-02-21 15:44:09PAUL GREILICH, SENIOR PLANNER
 561-822-1443
 [email protected]

Review Stop Z ZONING
Rev No 1 Status F Date   Cont ID  
Sent By   Date 2018-10-26 Time   Rev Time 0.00
Received By pgreilic Date 2018-10-26 Time 10:19 Sent To  
Notes
2018-10-26 10:20:261.) PLEASE INDICATE IF BUILDING FOOTPRINT IS BEING
 ALTERED. IF IT IS PROVIDE AN OVERALL SITE PLAN WITH
 DIMENSIONS, SETBACKS ETC.
  
 PAUL GREILICH, SENIOR PLANNER
 561-822-1443
 [email protected]


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved