| 2018-12-05 11:17:27 | 1ST REVIEW FBC-2017 MECHANICAL |
| | PERMIT #18100072 |
| | 12/5/18 |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| | 2017 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | FGI GUIDELINES FOR DESIGN AND CONSTRUCTION OF HEALTH |
| | CARE FACILITIES |
| | ASHRAE 170-2008 |
| | |
| | PLAN REVIEW RESULTS: DENIED: |
| | |
| | 1) SUBMIT AC COOLING AND HEATING CALCULATIONS FOR THE |
| | NEW SYSTEMS IN COMPLIANCE WITH SECTION C403.2.1 FBC EC. |
| | |
| | 2) COMMISSIONING OF THE NEW MECHANICAL SYSTEMS IS |
| | REQUIRED PER SECTION C408.2 FBC EC. SUBMIT A |
| | COMMISSIONING PLAN AS OUTLINED IN SECTION C408.2.1 AND |
| | DESCRIBED IN SECTIONS C408.2.2- C408.2.3.3. PLEASE NOTE |
| | THAT COPIES OF THE COMMISSIONING REPORT SHALL BE |
| | SUBMITTED TO THE BUILDING OWNER AND TO THE WPB BUILDING |
| | DEPARTMENT FOR FINAL APPROVAL AND CO OF THE BUILDING. |
| | |
| | 3) SHEET M0.1: PLEASE REVIEW SECTIONS 8.5 AND 8.6 |
| | ASHRAE 170-2014 AND PLACE NOTES ON THE PLAN |
| | ACCORDINGLY. IN ADDITION PLEASE PROVIDE ON THE PLAN A |
| | SUMMARY OF ALL REQUIRED SYSTEM TESTING AND |
| | DOCUMENTATION REQUIRED FOR FINAL MECHANICAL APPROVAL |
| | INCLUDING: |
| | |
| | A) COMMISSIONING AND TESTING AND BALANCING REPORT. |
| | |
| | B) ACCEPTANCE TESTING REPORT. |
| | |
| | C) DUCT CLEANLINESS REPORT. |
| | |
| | D) BLOWER TESTS REPORTS FOR EACH OPERATING ROOM. |
| | |
| | E) FAN SHUTDOWN AND FIRE ALARM TEST. |
| | |
| | 4) SHEET IC1.0: IT APPEARS THAT THE PLAN IS INDICATING |
| | ICRA CLASS II BECAUSE THAT BOX IS EMBOLDENED. WOULD |
| | THIS BE THE CLASS FOR A MAJOR DEMOLITION? THERE ARE NO |
| | REQUIREMENTS LISTED IN THAT CLASS FOR NEGATIVE AIR |
| | PRESSURE AND HEPA EQUIPPED AIR FILTRATION UNITS. PLEASE |
| | CLARIFY HOW AIRBORNE DUST WILL BE CONTROLLED AND DUCT |
| | SYSTEM CONTAMINATION BE PREVENTED. |
| | |
| | 5) M4.0: PROVIDE WIND LOAD ENGINEERING DESIGN CRITERIA |
| | FOR INSTALLATION OF THE CHILLER- SECTION 301.15 |
| | |
| | 6) M4.0: INDICATE HOW THE CHILLER PIPING WILL BE |
| | SUPPORTED INSIDE THE SOFFIT- PROVIDE A DETAIL |
| | |
| | 7) M4.0: PROVIDE CHILLER PIPING AND INSULATION |
| | SPECIFICATIONS. |
| | |
| | 8) M4.3, M4.4, & LS1.1: THE FOLLOWING COMMENTS (A-F) |
| | PERTAIN TO THE ROOMS THAT ARE DESIGNATED AS "HAZARDOUS" |
| | ON SHEET LS.1.1. THE ARCHITECT MUST REVIEW SECTIONS 307 |
| | AND 414 FBC B AND PROVIDE MORE SPECIFIC INFORMATION |
| | ABOUT THE USE OF THESE ROOMS AND WHAT IF ANY HAZARDOUS |
| | MATERIALS WILL BE STORED, AND THERIR WQUANTITES. PLEASE |
| | SEE SECTION 414.1.3 AND PROVIDE A REPORT. |
| | |
| | A) M4.3, LS1.1: FIRE DAMPERS APPEAR TO BE MISSING FOR |
| | DUCTS THAT ARE PENETRATING THE 1-HR. FIRE-RATED WALLS |
| | ENCLOSING STORAGE- 2003, CLEANUTILTY- 2034, AND SOILED |
| | UTILITY- 2049- SEE SECTION 607.5.2 FBC M. |
| | |
| | B) M4.3, LS1.1: THE STORAGE ROOM BETWEEN BAY #7 & 8 |
| | REQUIRES NEGATIVE PRESSURE AND ALL AIR TO BE EXHAUSTED |
| | TO THE OUTDOORS PER TABLE 701 ASHRAE 170-2014. IN |
| | ADDITION MINIMUM OF 2 O/A CHANGES AND 10 TOTAL AIR |
| | CHANGES ARE REQUIRED- PLEASE CORRECT THE PLANS. |
| | |
| | C) M4.4, LS1.1: EQUIPMENT STORAGE ROOMS 2090, 2097, |
| | 2101 REQUIRES NEGATIVE PRESSURE, ALL AIR TO BE |
| | EXHAUSTED TO THE OUTDOORS, A MINIMUM OF 2 O/A CHANGES |
| | AND 10 TOTAL AIR CHANGES- TABLE 7-1. PLEASE PROVIDE |
| | EQUIPMENT LAYOUT PLANS AND EQUIPMENT SCHEDULES FOR EACH |
| | ROOM- SECTION 107.2.1 WPB. |
| | |
| | D) M4.4, LS1.1: THE CENTRAL STERILE ROOM 2083 REQUIRES |
| | NEGATIVE PRESSURE, ALL AIR TO BE EXHAUSTED TO THE |
| | OUTDOORS, AND A MINIMUM OF 10 TOTAL ACH- TABLE 7-1. |
| | INDICATE IF A STEAM STERILIZER WILL BE INSTALLED IN THE |
| | ROOM AND PROVIDE AN EXHAUST HOOD IF APPLICABLE- SEE |
| | SECTIONS 7.4.2 ASHRAE 170-2014, AND ALSO SECTION |
| | 3.1-8.2.2.9 OF THE GUIDELINES WHICH HAS ADDITIONAL |
| | REQUIREMENTS FOR ETHYLENE OXIDE (ETO) STERILIZATION |
| | EQUIPMENT. PLEASE PROVIDE AN EQUIPMENT LAYOUT AND |
| | EQUIPMENTR SCHEDULE FOR THE ROOM. |
| | |
| | E) M4.4, LS1.1: THE ANESTHESIA WORK ROOM 2109 REQUIRES |
| | NEGATIVE PRESSURE, ALL AIR TO BE EXHAUSTED TO THE |
| | OUTDOORS, AND A MINIMUM OF 8 TOTAL ACH- TABLE 7-1. |
| | |
| | F) M4.4, LS1.1: THE JANITOR'S ROOM REQUIRES NEGATIVE |
| | PRESSURE, ALL AIR TO BE EXHAUSTED TO THE OUTDOORS, AND |
| | A MINIMUM OF 10 TOTAL ACH- TABLE 7-1. |
| | |
| | 9) M4.5: PLEASE SHOW THE LOCATION OF THE REQUIRED DUCT |
| | SMOKE DETECTOR FOR THE NEW AHU-1- SECTION 606.2.1 FBC |
| | M. |
| | |
| | 10) M4.5: VERIFY THE REQUIRED CLEARANCES FOR THE O/A |
| | INTAKE TO AHU-1 IN ACCORDANCE WITH SECTION 6.3.1 ASHRAE |
| | 170-2014- MINIMUM 25' FROM ALL EXHAUST AND VENT |
| | DISCHARGES, AND AT 6' ABOVE GRADE. A) SUBMIT |
| | MANUFACTURER'S SPECIFICATIONS AND THE MIAMI-DADE NOA |
| | FOR THE O/A LOUVER PER SECTION 6.3.1, AND SECTION 401.5 |
| | FBC M. |
| | |
| | 11) M4.5: IDENTIFY THE NEW FAN COIL UNIT SHOWN IN MECH |
| | ROOM M002, INCLUDE IT IN THE EQUIPMENT SCHEDULES, AND |
| | SUBMIT AC COOLING AND HEATING CALCULATIONS FOR SIZING |
| | OF THE UNIT. |
| | |
| | 12) M4.5: PER NOTES #11 & 12, PLEASE SHOW THE RETURN |
| | DUCT CONTINUATIONS ON THE FIRST FLOOR- SECTION 603.1 |
| | FBC M. |
| | |
| | 13) M4.6 & M.7: PROVIDE AN ABBREVIATIONS TABLE THAT |
| | INCLUDES MPS, BOP, AND CR. |
| | |
| | 14) M5.1: REFER TO TABLE C403.2.3(7) FBC EC AND VERIFY |
| | THAT THE NEW CHILLER MEETS THE EFFICIENCY REQUIRMENTS |
| | IN ACCORDANCE WITH THE AHRI 550/590 TEST REQUIREMENTS. |
| | |
| | 15) M5.3 & M5.4: TABLE 7-1 SHOWS 2 O/A ACH FOR SOILED |
| | WORKROOM AND SOILED HOLDING, HOWEVER NO O/A ACH IS |
| | SHOWN IN THE AIRFLOW SUMMARY TABLE- PLEASE CORRECT. |
| | |
| | 16) FILTRATION BANKS ARE REQUIRED IN ACCORDANCE WITH |
| | SECTIONS 6.4 AND TABLE 6-1 ASHRAE 170-2014. |
| | |
| | 17) REQUIRED PRODUCT SUBMITTALS TO BE APPROVED BY THE |
| | ENGINEER OF RECORD: |
| | |
| | A) SUPPLY AND EXHAUST DUCTWORK. |
| | B) OR AND PROCEDURE ROOM DIFFUSERS AND GRILLES. |
| | C) DIFFERENTIAL PRESSURE SENSORS |
| | D) CHILLED WATER AND STEAM PIPING. |
| | E) PIPING INSULATION |
| | F) FILTER BANKS |
| | G) DUCT SMOKE DETECTORS |
| | H) FIRE AND FIRE/SMOKE DAMPERS |
| | |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE |
| | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND |
| | KEEP THEM WITH THE SUBMITTALS. |
| | |
| | IF YOU HAVE ANY QUESTIONS ABOUT THE REVIEW COMMENTS |
| | PLEASE CONTACT ME. |
| | |
| | CHRISTOPHER L. COLE |
| | MECHANICAL PLANS EXAMINER |
| | 401 CLEMATIS STREET |
| | WEST PALM BEACH FL 33401 |
| | 561-805-6719 |
| | [email protected] |
| | |