Plan Review Details - Permit 18100068
Plan Review Stops For Permit 18100068
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2018-12-21 Cont ID  
Sent By pvalenti Date 2018-12-21 Time 14:39 Rev Time 0.00
Received By pvalenti Date 2018-12-21 Time 14:39 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2018-11-13 Cont ID  
Sent By jwitmer Date 2018-11-13 Time 10:56 Rev Time 0.00
Received By jwitmer Date   Time   Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2018-12-21 Cont ID  
Sent By jleahy Date 2018-12-21 Time 13:14 Rev Time 0.00
Received By jleahy Date 2018-12-21 Time 13:14 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2018-10-18 Cont ID  
Sent By jpearson Date 2018-10-18 Time 15:21 Rev Time 0.00
Received By jpearson Date 2018-10-18 Time 12:35 Sent To  
Notes
2018-10-18 15:20:58CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. SHEET E9-20, NOTE 1 CALLS FOR A 60KW DIESEL GENSET
 WHICH CORRESPONDS WITH SPEC SHEET PROVIDED FOR
 GENERATOR. SHEET E9-30 AND E9-40 CALL FOR A 50KW
 GENSET. CORRECT DISCREPANCY. WPB FBC 107.2.1
 2. THE ADDRESS ON PLANS NEEDS TO BE CLARIFIED. THIS
 PERMIT APPLICATION IS FOR 101 EXECUTIVE CENTER DR.,
 WHILE PERMIT APPLICATION 18100064 IS FOR 111 EXECUTIVE
 CENTER DR.. EITHER PROVIDE BOTH ADDRESSES ON PLAN SET,
 OR SUBMIT SEPARATE PLAN FOR EACH ADDRESS. WPB FBC
 107.2.1
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD
 SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2018-12-10 Cont ID  
Sent By pleduc Date 2018-12-10 Time   Rev Time 0.00
Received By pleduc Date 2018-12-10 Time 15:13 Sent To  
Notes
2018-12-10 15:29:15THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 PLEASE CONSIDER THE FOLLOWING AS PROVISO:
  
 THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED
 AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE
 PROVISO COMMENTS WILL RESULT IN A FAILED FIRE
 INSPECTION.
  
  
  
 1) THE INSTALLATION OF THE GENERATOR SHALL COMPLY WITH
 THE REQUIRMENTS OF NFPA 37.
  
 PER NFPA 1, CHAPTER 11, BUILDING SERVICES
  
 11.7 STATIONARY GENERATORS AND STANDBY POWER SYSTEMS
 11.7.1 11.7.1 STATIONARY COMBUSTION ENGINES AND GAS
 TURBINES
 INSTALLATION. STATIONARY GENERATOR SETS SHALL BE
 INSTALLED IN
 ACCORDANCE WITH NFPA 37, STANDARD FOR THE INSTALLATION
 AND USE
 OF STATIONARY COMBUSTION ENGINES AND GAS TURBINES, AND
 NFPA 70.
  
  
  
 2) ANY PROPOSED TIE IN TO THE FIRE ALARM AND/OR FIRE
 SPRINKLER SYSTEM SHALL BE DONE UNDER SEPARATE SHOP
 DRAWINGS UNDER APPLICABLE NFPA CODES.
  
  
 3) TIE IN TO ANY LIFE SAFETY SYSTEMS OR AS PER
 APPLICABLE LAW SHALL BE UNDER NFPA 110
  
 11.7.3 EMERGENCY AND LEGALLY REQUIRED STANDBY POWER
 SYSTEMS.
 11.7.3.1 GENERAL. NEW STATIONARY GENERATORS FOR
 EMERGENCY USE
 OR FOR LEGALLY REQUIRED STANDBY POWER REQUIRED BY THIS
 CODE, THE
 BUILDING CODE, OR OTHER CODES AND STANDARDS SHALL BE
 INSTALLED IN
 ACCORDANCE WITH NFPA 110, STANDARD FOR EMERGENCY AND
 STANDBY
 POWER SYSTEMS.
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2018-10-10 Cont ID  
Sent By pleduc Date 2018-10-10 Time   Rev Time 0.00
Received By pleduc Date 2018-10-10 Time 14:21 Sent To  
Notes
2018-10-10 14:22:08THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 PLEASE CONSIDER THE FOLLOWING AS PROVISO:
  
 THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED
 AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE
 PROVISO COMMENTS WILL RESULT IN A FAILED FIRE
 INSPECTION.
  
  
  
 1) THE INSTALLATION OF THE GENERATOR SHALL COMPLY WITH
 THE REQUIRMENTS OF NFPA 37.
  
 PER NFPA 1, CHAPTER 11, BUILDING SERVICES
  
 11.7 STATIONARY GENERATORS AND STANDBY POWER SYSTEMS
 11.7.1 11.7.1 STATIONARY COMBUSTION ENGINES AND GAS
 TURBINES
 INSTALLATION. STATIONARY GENERATOR SETS SHALL BE
 INSTALLED IN
 ACCORDANCE WITH NFPA 37, STANDARD FOR THE INSTALLATION
 AND USE
 OF STATIONARY COMBUSTION ENGINES AND GAS TURBINES, AND
 NFPA 70.
  
  
  
 2) ANY PROPOSED TIE IN TO THE FIRE ALARM AND/OR FIRE
 SPRINKLER SYSTEM SHALL BE DONE UNDER SEPARATE SHOP
 DRAWINGS UNDER APPLICABLE NFPA CODES.
  
  
 3) TIE IN TO ANY LIFE SAFETY SYSTEMS OR AS PER
 APPLICABLE LAW SHALL BE UNDER NFPA 110
  
 11.7.3 EMERGENCY AND LEGALLY REQUIRED STANDBY POWER
 SYSTEMS.
 11.7.3.1 GENERAL. NEW STATIONARY GENERATORS FOR
 EMERGENCY USE
 OR FOR LEGALLY REQUIRED STANDBY POWER REQUIRED BY THIS
 CODE, THE
 BUILDING CODE, OR OTHER CODES AND STANDARDS SHALL BE
 INSTALLED IN
 ACCORDANCE WITH NFPA 110, STANDARD FOR EMERGENCY AND
 STANDBY
 POWER SYSTEMS.
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2018-12-21 Cont ID  
Sent By pvalenti Date 2018-12-21 Time 14:39 Rev Time 0.00
Received By pvalenti Date 2018-12-05 Time 10:31 Sent To  
Notes
2018-12-07 10:32:02B12
 **TRAVELLING TOGETHER 18100064 & 18100068**

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-12-07 Cont ID  
Sent By lmarchan Date 2018-12-07 Time 10:31 Rev Time 0.00
Received By lmarchan Date 2018-10-02 Time 10:33 Sent To  
Notes
2018-10-04 10:33:55B12
 **TRAVELLING TOGETHER 18100064 & 18100068**

Review Stop Z ZONING
Rev No 3 Status P Date 2019-02-01 Cont ID  
Sent By awooten Date 2019-02-01 Time   Rev Time 0.00
Received By awooten Date 2019-02-01 Time   Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status F Date 2018-12-21 Cont ID  
Sent By awooten Date 2018-12-21 Time   Rev Time 0.00
Received By awooten Date 2018-12-21 Time   Sent To  
Notes
2018-12-21 11:56:48*************************ZONING REVIEW
 FAILED*****************************
  
 PROVIDE A TREE ALTERATION APPLICATION FOR THE TREES
 BEING RELOCATED ON SHEET C9-20, AND A SEPARATE
 LANDSCAPE PERMIT FOR THE HEDGE SCREENING. PLEASE
 CONTACT RAY CARANCI WITH ANY QUESTIONS (561-822-1462).
  
 ALANA WOOTEN
 ASSOCIATE PLANNER
 561-822-1449
 [email protected]

Review Stop Z ZONING
Rev No 1 Status F Date 2018-10-17 Cont ID  
Sent By awooten Date 2018-10-17 Time   Rev Time  
Received By awooten Date 2018-10-17 Time   Sent To  
Notes
2018-10-17 14:33:18****************************************ZONING REVIEW
 FAILED********************************************
  
 PROVIDE THE SETBACKS FOR THE GENERATOR (MINIMUM OF 4
 FEET INTO THE REQUIRED SETBACK).
  
 ARE ANY TREES BEING MOVED/RELOCATED?
  
 WHAT SCREENING IS BEING PROVIDED?
  
 ALANA WOOTEN
 ASSOCIATE PLANNER
 PLANNING DIVISION
 561-822-1449
 [email protected]