Plan Review Details - Permit 18100035
Plan Review Stops For Permit 18100035
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2018-11-19 Cont ID  
Sent By pvalenti Date 2018-11-19 Time 17:05 Rev Time 0.00
Received By pvalenti Date 2018-11-19 Time 17:05 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2018-12-11 Cont ID  
Sent By jleahy Date 2018-12-11 Time 18:17 Rev Time 0.00
Received By jleahy Date 2018-12-11 Time 18:17 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2018-10-12 Cont ID  
Sent By jleahy Date 2018-10-12 Time 14:52 Rev Time 0.00
Received By jleahy Date 2018-10-12 Time 14:52 Sent To  
Notes
2018-10-12 15:01:03FLORIDA BUILDING CODE 2017 6TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED
 NFPA 70 2014 EDITION
  
 JAKE LEAHY
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 PLANS NEED TO BE SIGNED BY THE OWNER.
  
  

Review Stop G GAS REVIEW
Rev No 2 Status P Date 2018-12-10 Cont ID  
Sent By lcrespo Date 2018-12-10 Time 14:20 Rev Time 0.00
Received By lcrespo Date 2018-12-10 Time 14:20 Sent To  
Notes
2018-12-10 14:21:3012/10/18 REVIEWED FOR CODE COMPLIANCE (GAS)
  
 BY REVIEWING THE PLANS / SPECIFICATIONS FOR CODE
 COMPLIANCE DOES NOT RELIEVE THE OWNER, DESIGN
 PROFESSIONAL, CONTRACTORS OR THEIR REPRESENTATIVES FROM
 THE RESPONSIBILITY TO COMPLY WITH ALL LOCAL, STATE AND
 NATIONAL CODES AND STANDARDS IN EFFECT AT THE TIME OF
 PERMIT ISSUANCE. OUR REVIEW IS NOT A CHECK OF EVERY
 ITEM AND DOES NOT PREVENT THIS DEPARTMENT FROM
 REQUIRING CORRECTIONS DURING CONSTRUCTION. ANY CHANGES
 / ALTERATIONS TO APPROVE PLANS SHALL BE APPROVED TO
 AVOID VOIDING OF THE PERMIT.
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER
  

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2018-10-15 Cont ID  
Sent By lcrespo Date 2018-10-15 Time 17:23 Rev Time 0.00
Received By lcrespo Date 2018-10-15 Time 17:23 Sent To  
Notes
2018-10-15 17:24:5910/15/2018 1ST GAS REVIEW**DENIED** WITH COMMENTS
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
 1. THE PLANS INDICATE AN EXISTING GAS METER. THE BTU
 LOAD OF THE EXISTING GAS SYSTEM MUST BE ADDED INTO THE
 TOTAL BTU LOAD ON THE SYSTEM TO ENSURE THE EXISTING
 SYSTEM IS PROPERLY SIZED. IF UNDERSIZED, THE EXISTING
 SYSTEM MUST BE REDONE TO ENSURE A SAFE OPERATING
 SYSTEM. SUBMIT A GAS PIPING RISER DIAGRAM THAT SHOWS
 THE EACH TYPE OF EXISTING APPLIANCE, THE BTU LOAD OF
 EACH APPLIANCE, THE PIPE SIZE AND TYPE OF PIPE TO EACH
 APPLIANCE, AND THE DISTANCE OF THE LONGEST LENGTH OF
 PIPING FROM THE POINT OF DELIVERY TO THE MOST REMOTE
 OUTLET AND THE LOAD OF THE SECTION. NOTE: IF THE
 EXISTING SYSTEM IS LESS THAN A 2 PSI SYSTEM AND THE
 SYSTEM PRESSURE IS INCREASED TO 2 PSI, A LINE PRESSURE
 REGULATOR IS REQUIRED AT ALL THE EXISTING APPLIANCES,
 2017 FBC FUEL GAS RES. SECS.G2412.4, G2412.8, G2413.1,
 G2413.2, G2413.3.
  
 2. LIST THE BTU LOAD OF EACH APPLIANCE AND THE TOTAL
 BTU LOAD ON THE SYSTEM. REFER TO THE 2017 FBC FUEL GAS
 RES. SEC. G2413.
  
 3. THE SPECIFICATION FOR GENERAC SAYS 320 BTU AT FULL
 LOAD AND YOU HAVE 240 BTU ON LABELED ON YOU ISOMETRIC,
 PLEASE CORRECT AND CLARIFY. WPB AMENDMENTS TO THE FBC
 SEC. 107.2.1. INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 4. SUBMIT MANUFACTURER?S SPECIFICATIONS FOR THE
 PRESSURE REGULATORS. REGULATORS INSTALLED ON THE
 EXTERIOR OF THE BUILDING SHALL BE APPROVED FOR OUTDOOR
 INSTALLATION, 2017 FBC FUEL GAS RES. SEC. G2421.1.
  
 5. A SEPARATE GAS SUB PERMIT REQUIRED, 2017 FBC WPB A
 105.1.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION, MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 LUIS A. CRESPO
 PLUMBING INSPECTOR /
 PLUMBING PLAN REVIEW
 AVAILABLE FROM 1:00 PM TO 4:00 PM
 [email protected]
 561-805-6720
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2018-12-11 Cont ID  
Sent By jleahy Date 2018-12-11 Time 18:17 Rev Time 0.00
Received By jleahy Date 2018-12-06 Time 14:35 Sent To  
Notes
2018-12-07 14:35:31RESUB ROUTED TO LCRESPO

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-11-19 Cont ID  
Sent By pvalenti Date 2018-11-19 Time 17:07 Rev Time 0.00
Received By pvalenti Date 2018-10-01 Time 16:04 Sent To I
Notes
2018-10-03 16:04:52ROUTED TO ZONING
 **TRAVELLING TOGETHER - 18100035 & 18100036**

Review Stop Z ZONING
Rev No 1 Status P Date 2018-10-09 Cont ID  
Sent By mcruz Date 2018-10-09 Time 16:33 Rev Time 0.00
Received By mcruz Date 2018-10-09 Time 16:31 Sent To  
Notes
***NONE***