| 2018-10-10 15:57:12 | ****CORRECTIONS**** |
| | W.P.B. PERMIT: 18091331 |
| | REVIEWED: OCTOBER 10, 2018 |
| | |
| | DYLAN BATTLES |
| | BUILDING PLANS EXAMINER I |
| | [email protected] |
| | 561-805-6718 |
| | |
| | FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) |
| | FBC AMENDED = FLORIDA BUILDING CODE,6TH EDITION (2017) |
| | FBC B = FBC BUILDING |
| | FBC EB = FBC EXISTING BUILDING |
| | FBC A = FBC ACCESSIBILITY |
| | FBC ENERGY = FBC ENERGY CONSERVATION |
| | |
| | 1. [FBC AMENDED 107.2.5] PROVIDE PLAN AND ELEVATION |
| | VIEW TO SHOW LOCATION AND SIZE OF EXISTING STOREFRONT |
| | AND NEW STOREFRONT. |
| | |
| | 2. [FBC AMENDED 107.2.5] IS THIS DOOR FIRE RATED? |
| | EGRESS? WHAT IS THE EXISTING HARDWARE AND WHAT IS THE |
| | NEW? |
| | |
| | 3. [FBC ENERGY C401.2] WHERE SOME OR ALL OF AN EXISTING |
| | FENESTRATION UNIT IS REPLACED WITH A NEW FENESTRATION |
| | PRODUCT, INCLUDING SASH AND GLAZING, THE REPLACEMENT |
| | FENESTRATION UNIT SHALL MEET THE APPLICABLE |
| | REQUIREMENTS FOR U-FACTOR AND SHGC IN TABLE C402.4 |
| | (SEE C401.2.1 FOR EXCEPTION FOR COMBINING AREA WEIGHTED |
| | AVERAGE) |
| | WHAT ARE THE SHGC AND U-FACTOR OF REPLACEMENT GLAZING? |
| | |
| | 4. [FBC 1609.1.1]PROVIDE DESIGN DATA TO MEET WIND |
| | REQUIREMENTS. |
| | OCCUPANCY = ___ |
| | TYPE OF WALL CONSTRUCTION = _________(ARE THE WALLS |
| | MASONRY, CONCRETE OR WOOD FRAMED?) |
| | METHOD OF DESIGN = (ASCE 7-10?) |
| | RISK CATEGORY = ___(II?) |
| | EXPOSURE CATEGORY = ___(B,C OR D?) |
| | BUILDING CLASSIFICATION = __________(ENCLOSED?) |
| | MEAN BLDG. HGT. = ___FT. ___IN. |
| | WIND SPEED V ULT = _____(170?) |
| | WIND SPEED V ASD = _____(132?) |
| | ZONE OF OPENING = (4 OR 5?) |
| | DESIGN PRESSURE = +___ & -___ |
| | |
| | 5. [FBC 1609.1.2]PROTECTION OF OPENINGS |
| | PLEASE PROVIDE PRODUCT APPROVAL FOR IMPACT PROTECTION. |
| | |
| | NOTE: |
| | -PLEASE PROVIDE COMMENT RESPONSE SHEET TO EXPLAIN HOW |
| | EACH COMMENT IS BEING ADDRESSED. |
| | -ADDITIONAL COMMENTS MAY BE FORTHCOMING PENDING REVIEW |
| | OF MATERIALS REQUESTED. |
| | -WHEN RESUBMITTING, PROVIDE TWO IDENTICAL COLLATED SETS |
| | OF DOCUMENTS FOR ISSUANCE. OLD SHEETS (BOTH SETS) |
| | SHOULD BE RETAINED IN THE PACKAGE; PLEASE DO NOT |
| | DISCARD ANY DOCUMENTS. THEY SHOULD BE BOUND TOGETHER |
| | SEPARATELY FROM THE TWO ISSUANCE SETS AND MARKED "VOID" |
| | OR "OLD SHEETS". PLEASE DO NOT STAMP THE PLANS VOID AS |
| | APPLICANTS ARE INADVERTENTLY STAMPING SHEETS THAT WE |
| | NEED "VOID", RENDERING THEM NOT USABLE. |
| | |