Plan Review Details - Permit 18091300
Plan Review Stops For Permit 18091300
Review Stop E ELECTRICAL
Rev No 1 Status P Date 2018-10-03 Cont ID  
Sent By fgiaquin Date 2018-10-03 Time 07:10 Rev Time 0.00
Received By fgiaquin Date 2018-10-03 Time 06:50 Sent To I
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2018-10-02 Cont ID  
Sent By fgiaquin Date 2018-10-03 Time 07:11 Rev Time 0.00
Received By pleduc Date 2018-10-02 Time 10:43 Sent To E
Notes
2018-10-02 10:49:24THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 PLEASE CONSIDER THE FOLLOWING AS PROVISO:
  
 THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED
 AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE
 PROVISO COMMENTS WILL RESULT IN A FAILED FIRE
 INSPECTION.
  
  
 1) THIS INSTALL & FUNCTION OF TURNSTILES SHALL COMPLY
 WITH THE APPLICABLE REQUIRMENTS OF NFPA 101, CHAPTER 7,
 MEANS OF EGRESS.
  
 7.2.1.11 TURNSTILES AND SIMILAR DEVICES.
 7.2.1.11.1 TURNSTILES OR SIMILAR DEVICES THAT RESTRICT
 TRAVEL TO ONE
 DIRECTION OR ARE USED TO COLLECT FARES OR ADMISSION
 CHARGES SHALL
 NOT BE PLACED SO AS TO OBSTRUCT ANY REQUIRED MEANS OF
 EGRESS,
 UNLESS OTHERWISE SPECIFIED IN 7.2.1.11.1.1,
 7.2.1.11.1.2, AND
 7.2.1.11.1.3.
  
 7.2.1.11.1.2 WHERE TURNSTILES ARE APPROVED BY THE
 AUTHORITY HAVING
 JURISDICTION AND PERMITTED IN CHAPTERS 11 THROUGH 43,
 EACH
 TURNSTILE SHALL BE CREDITED FOR A CAPACITY OF 50
 PERSONS, PROVIDED
 THAT SUCH TURNSTILES MEET ALL OF THE FOLLOWING
 CRITERIA:
 (1) THEY FREEWHEEL IN THE EGRESS DIRECTION WHEN PRIMARY
 POWER IS
 LOST, AND FREEWHEEL IN THE DIRECTION OF EGRESS TRAVEL
 UPON
 MANUAL RELEASE BY AN EMPLOYEE ASSIGNED IN THE AREA.
 (2) THEY ARE NOT GIVEN CREDIT FOR MORE THAN 50 PERCENT
 OF THE
 REQUIRED EGRESS WIDTH.
 (3) THEY ARE NOT IN EXCESS OF 39 IN. (990 MM) IN HEIGHT
 AND HAVE
 A CLEAR WIDTH OF NOT LESS THAN 16? IN. (420 MM).
 7.2.1.11.1.3* SECURITY ACCESS TURNSTILES THAT IMPEDE
 TRAVEL IN THE
 DIRECTION OF EGRESS UTILIZING A PHYSICAL BARRIER SHALL
 BE PERMITTED
 TO BE CONSIDERED AS A COMPONENT OF THE MEANS OF EGRESS,
 WHERE
 PERMITTED IN CHAPTERS 11 THROUGH 43, PROVIDED THAT ALL
 THE
 FOLLOWING CRITERIA ARE MET:
 (1) THE BUILDING IS PROTECTED THROUGHOUT BY AN
 APPROVED,
 SUPERVISED AUTOMATIC SPRINKLER SYSTEM IN ACCORDANCE
 WITH
 SECTION 9.7.
 (2) EACH SECURITY ACCESS TURNSTILE LANE CONFIGURATION
 HAS A
 MINIMUM CLEAR PASSAGE WIDTH OF 22 IN. (560 MM).
 (3) ANY SECURITY ACCESS TURNSTILE LANE CONFIGURATION
 PROVIDING A
 CLEAR PASSAGE WIDTH OF LESS THAN 32 IN. (810 MM) SHALL
 BE
 GIVEN AN EGRESS CAPACITY OF 50 PERSONS.
 (4) ANY SECURITY ACCESS TURNSTILE LANE CONFIGURATION
 PROVIDING A
 CLEAR PASSAGE WIDTH OF 32 IN. (810 MM) OR MORE SHALL BE
 GIVEN AN EGRESS CAPACITY AS CALCULATED IN ACCORDANCE
 WITH
 SECTION 7.3.
 (5) EACH SECURED PHYSICAL BARRIER SHALL AUTOMATICALLY
 RETRACT OR
 SWING TO AN UNOBSTRUCTED OPEN POSITION IN THE DIRECTION
 OF
 EGRESS, UNDER EACH OF THE FOLLOWING CONDITIONS:
 (A) UPON LOSS OF POWER TO THE TURNSTILE OR ANY PART OF
 THE
 ACCESS CONTROL SYSTEM THAT SECURES THE PHYSICAL BARRIER
 (B) UPON ACTUATION OF A READILY ACCESSIBLE AND CLEARLY
 IDENTIFIED MANUAL RELEASE DEVICE THAT RESULTS IN DIRECT
 INTERRUPTION OF POWER TO EACH SECURED PHYSICAL BARRIER,
 REMAINS IN THE OPEN POSITION FOR NOT LESS THAN 30
 SECONDS, AND IS POSITIONED AT ONE OF THE FOLLOWING
 LOCATIONS:
 I. THE MANUAL RELEASE DEVICE IS LOCATED ON THE EGRESS
 SIDE OF EACH SECURITY ACCESS TURNSTILE LANE.
 II. THE MANUAL RELEASE DEVICE IS LOCATED AT AN
 APPROVED LOCATION WHERE IT CAN BE ACTUATED BY AN
 EMPLOYEE ASSIGNED TO THE AREA.
 (C) UPON ACTUATION OF THE BUILDING FIRE-PROTECTIVE
 SIGNALING
 SYSTEM, IF PROVIDED, AND FOR WHICH THE FOLLOWING APPLY:
 I. THE PHYSICAL BARRIER REMAINS IN THE OPEN POSITION
 UNTIL THE FIRE-PROTECTIVE SIGNALING SYSTEM IS
 MANUALLY RESET.
 II. THE ACTUATION OF MANUAL FIRE ALARM BOXES THAT
 ACTUATE THE BUILDING FIRE-PROTECTIVE SIGNALING
 SYSTEM IS NOT REQUIRED TO MEET THE REQUIREMENTS
 SPECIFIED IN 7.2.1.11.1.3(5) (C)I.
 (D) UPON ACTUATION OF THE BUILDING AUTOMATIC SPRINKLER
 OR
 FIRE DETECTION SYSTEM, AND FOR WHICH THE PHYSICAL
 BARRIER
 REMAINS IN THE OPEN POSITION UNTIL THE FIRE-PROTECTIVE
 SIGNALING SYSTEM IS MANUALLY RESET
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-10-03 Cont ID  
Sent By fgiaquin Date 2018-10-03 Time 07:11 Rev Time 0.00
Received By fgiaquin Date 2018-09-28 Time 12:13 Sent To FIRE
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2018-10-03 Cont ID  
Sent By fgiaquin Date 2018-10-03 Time 07:10 Rev Time  
Received By fgiaquin Date   Time   Sent To  
Notes
***NONE***