Plan Review Details - Permit 18091264
Plan Review Stops For Permit 18091264
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2018-10-18 Cont ID  
Sent By rmcdouga Date 2018-10-18 Time 11:20 Rev Time 0.00
Received By rmcdouga Date 2018-10-18 Time 11:20 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status N Date 2018-10-17 Cont ID  
Sent By jpearson Date 2018-10-08 Time 10:16 Rev Time 0.00
Received By jpearson Date 2018-10-08 Time 10:16 Sent To  
Notes
2018-10-17 09:50:52SEPARATE ELECTRICAL PERMIT PULLED, SEE PERMIT 18100696.
 CHANGED STATUS TO N.
  
  
2018-10-08 10:16:10CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. VALUE FOR WORK STATED ON PERMIT APPLICATION APPEARS
 LOW. PROVIDE COPY OF SIGNED CONTRACT WITH SCOPE AND
 VALUE OF WORK, TO INCLUDE ALL MATERIALS AND LABOR. THIS
 IS FOR TOTAL PROJECT, NOT JUST ELECTRICAL. FBC 109.3
 2. PROVIDE ELECTRICAL PLAN FOR REVIEW, SIGNED AND
 SEALED BY A LICENSED DESIGN PROFESSIONAL OR SIGNED BY
 THE ELECTRICAL CONTRACTOR QUALIFIER. FS 471.003(2)(H);
 471.025; WPB FBC 107.2.1, 107.3.5
 3. PROVIDE RISER DIAGRAM, SHOWING ALL DETAILS OF
 SERVICE EQUIPMENT, UNDERGROUND OR OVERHEAD SERVICE,
 WIRE AND BREAKER SIZES FOR SERVICE AND FEED TO ANY
 SUB-PANEL(S). SHOW GEC SIZE AND SYSTEM, SHOW
 INTERSYSTEM BONDING TERMINATION POINT. NEC 215.5, 230,
 250.50, 250.94, 408.30; FBC RE E3706.1, E3608.1,
 E3609.3; WPB FBC 107.2.1
 4. PROVIDE ACCURATE LOAD CALCULATION INCLUDING ALL
 LOADS. NEC 220; FBC RE E3602.2
 5. PROVIDE PANEL SCHEDULE INDICATING ANY NEW OR ALTERED
 CIRCUITS, THE WIRE AND BREAKER SIZE FOR THESE CIRCUITS,
 AND AFCI OR GFCI PROTECTION WHERE APPLICABLE TO COMPLY
 WITH CODE. NEC 210.8, 210.12, 210.19, 210.20, 215.5,
 408.4; WPB FBC 107.3.5; FBC RE E3706.2, E3902
  
 DUE TO LACK OF INFORMATION ON PLAN, THIS LIST IS NOT
 ALL INCLUSIVE. FURTHER COMMENTS ARE POSSIBLE.
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD
 SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-10-25 Cont ID  
Sent By cmontell Date 2018-10-25 Time 13:58 Rev Time 0.00
Received By cmontell Date 2018-10-25 Time 13:58 Sent To  
Notes
2018-09-28 15:41:46R05

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2018-10-25 Cont ID  
Sent By cmontell Date 2018-10-25 Time 13:58 Rev Time 0.00
Received By cmontell Date 2018-10-25 Time 13:58 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2018-10-23 Cont ID  
Sent By jesmith Date 2018-10-23 Time 13:01 Rev Time 0.00
Received By jesmith Date 2018-10-23 Time 13:01 Sent To  
Notes
2018-10-23 13:01:391ST REVIEW:
 PLUMBING COMMENTS: APPROVED
  
 PLUMBING PROVISO
 1. TUB/SHOWER CONTROL VALVE(S) SHALL BE ANTI-SCALD TYPE
 WITH HIGH TEMPERATURE LIMITING STOP. FBC RES P2708.4
 2. PROVIDE WATER HAMMER ARRESTORS AT WATER SUPPLIES TO
 ICE LINE AND DISHWASHER. FBC RES P2903.5
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 PHONE 561-805-6715