| 2018-09-28 15:57:37 | PERMIT # 18091206 |
| | |
| | REVIEW COMMENTS - CONDITIONALLY APPROVED - COMPLY VIA |
| | INSPECTION ON 10/01/18 |
| | |
| | 1) A THOROUGH AND COMPLETE PLAN REVIEW CANNOT BE |
| | COMPLETED AT THIS TIME DUE TO LACK OF INFORMATION |
| | SUBMITTED ON THE PLANS. ADDITIONAL PLAN REVIEW COMMENTS |
| | MAY BE GENERATED DURING PLAN RESUBMISSION. |
| | |
| | 2) PROVIDE PORTABLE FIRE EXTINGUISHERS AND NOTE ON THE |
| | SITE PLAN WHERE THESE EXTINGUISHERS WILL BE LOCATED. |
| | EXTINGUISHERS SHALL HAVE A MINIMUM RATING OF 2A:10BC |
| | AND SHALL BE TAGGED BY A LICENSED FIRE EXTINGUISHER |
| | COMPANY. TRAVEL DISTANCE TO EXTINGUISHERS SHALL NOT |
| | EXCEED 75 FEET. PROVIDE TYPE K EXTINGUISHERS WHEN |
| | COOKING WITH GREASE OR WHEN PRODUCING SMOKE OR |
| | GREASE-LADEN VAPORS. |
| | |
| | 3) TENTS SHALL BE LOCATED AT LEAST 10 FEET AWAY FROM |
| | BUILDING STRUCTURES. PROVIDE DISTANCE OF TENT FROM |
| | NEAREST STRUCTURES. |
| | |
| | 4) TENT SHALL BE OF THE OPEN AREA/NO SIDEWALL TYPE, |
| | OTHERWISE EMERGENCY LIGHTING AND ILLUMINATED EXIT SIGNS |
| | ARE REQUIRED FOR TENTS EXCEEDING 1,200 SQUARE FEET. |
| | THIS TENT IS 3,200 SQUARE FEET AND, ALTHOUGH NOT |
| | SPECIFICALLY MENTIONED ON DOCUMENTS PROVIDED, APPEARS |
| | TO BE ENCLOSED WITH SIDEWALLS. EMERGENCY LIGHTING AND |
| | ILLUMINATED EXIT SIGNS ARE REQUIRED. |
| | |
| | 5) PLAN DOES NOT INDICATE WHERE THE DESIGNATED MEANS OF |
| | EGRESS IS. PLEASE NOTE THAT 2 MEANS OF EGRESS IS NEEDED |
| | AND SHALL BE IDENTIFIED BY AN ILLUMINATED EXIT SIGN. |
| | EGRESS SHALL ALSO COMPLY WITH ALL RELEVANT REQUIREMENTS |
| | OF NFPA 101: CHAPTER 7 (MEANS OF EGRESS). |
| | |
| | 6) POST WEATHERPROOF NO SMOKING SIGNS IN CONSPICUOUS |
| | LOCATIONS. |
| | |
| | 7) GENERATORS AND OTHER INTERNAL COMBUSTION POWER |
| | SOURCES SHALL BE SEPARATED FROM TENTS BY A MINIMUM OF 5 |
| | FEET AND SHALL BE PROTECTED FROM CONTACT BY FENCING OR |
| | ENCLOSURE. THIS TENT APPEARS TO HAVE A/C UNITS |
| | ATTACHED, HOWEVER THE POWER SOURCE FOR THESE UNITS IS |
| | NOT PROVIDED. PLEASE PROVIDE THESE DETAILS AND, IF |
| | APPLICABLE, SHOW THE LOCATION OF THE GENERATOR AND/OR |
| | POWER SOURCE. |
| | |
| | 8) MEANS OF EGRESS ACCESS, AISLE ACCESSWAYS, AND AISLES |
| | SERVING SEATING AT TABLES SHALL COMPLY WITH NFPA 101: |
| | 12.2.5. PLEASE PROVIDE A MORE DETAILED SITE PLAN THAT |
| | CLEARLY SHOWS THE AISLE WIDTHS AND TRAVEL DISTANCES. |
| | |
| | 9) THE TENT IS 3,200 SQ FT AND FOR THIS PARTICULAR USE |
| | MUST COMPLY WITH THE OCCUPANT LOAD FACTORS FOR ASSEMBLY |
| | OCCUPANCIES, AS LISTED UNDER NFPA 101: CHAPTER 7, TABLE |
| | 7.3.1.2. IT APPEARS THAT SEATING IS BEING PROVIDED FOR |
| | 280 PERSONS, HOWEVER, KEEPING THE LOAD FACTORS AND |
| | REQUIREMENTS FOR AISLES/AISLE ACCESSWAYS, IT APPEARS |
| | THAT THIS MAY BE PRESENTING A SITUATION OF |
| | OVERCROWDING. PLEASE REVIEW AND PROVIDE THE OCCUPANT |
| | LOAD AND OCCUPANT LOAD LAYOUT THAT PROPERLY COMPLIES |
| | WITH ALL CODE REQUIREMENTS. |
| | |
| | 10) PLEASE PROVIDE THE SET DATE. A FIRE INSPECTION MAY |
| | BE CONDUCTED AFTER SET-UP TO ENSURE COMPLIANCE WITH ALL |
| | RELEVANT FIRE CODES. |
| | |
| | CONDITIONALLY APPROVED - COMPLY VIA INSPECTION ON |
| | 10/01/18 |
| | |
| | BY STEVEN KENNEDY PER DISCUSSION WITH PETER LEDUC FIRE |
| | MARSHAL |
| | WEST PALM BEACH FIRE RESCUE |
| | |
| | |