Plan Review Details - Permit 18091195
Plan Review Stops For Permit 18091195
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2019-01-15 Cont ID  
Sent By dbattles Date 2019-01-15 Time 11:03 Rev Time 0.00
Received By dbattles Date 2019-01-15 Time 08:20 Sent To  
Notes
2019-01-15 11:05:05PROVISOS:
 -PRE-FAB ALUMINUM TRELLIS, STAIRS AND GUARD RAIL
 ENGINEERING WILL BE A DEFFERED SUBMITTAL AS STATED ON
 SHEET A-1.
 -WINDOWS AND DOORS WILL BE A DEFFERED SUBMITTAL AS
 STATED ON SHEET A-1.
 -TRUSS SHOP DRAWINGS TO THE BUILDING INSPECTOR PRIOR TO
 INSTALLATION.
 -PROVIDE PRODUCT APPROVALS FOR ROOFING WITH SUB-PERMIT
 APPLICATION.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2018-11-19 Cont ID  
Sent By dbattles Date 2018-11-19 Time 08:11 Rev Time 0.00
Received By dbattles Date 2018-11-15 Time 15:22 Sent To  
Notes
2018-11-19 08:11:29****CORRECTIONS****
 W.P.B. PERMIT: 18091195
 REVIEWED: NOVEMBER 16, 2018
  
 DYLAN BATTLES
 BUILDING PLANS EXAMINER I
 [email protected]
 561-805-6718
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC AMENDED = FLORIDA BUILDING CODE,6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC ENERGY = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 1. [FBC 107.5][FBC 110.9][FBC R401.3][PROVIDE SITE
 DRAINAGE PLAN.
 SURFACE DRAINAGE SHALL BE DIVERTED TO A STORM SEWER
 CONVEYANCE OR OTHER APPROVED POINT OF COLLECTION THAT
 DOES NOT CREATE A HAZARD. LOTS SHALL BE GRADED TO DRAIN
 SURFACE WATER AWAY FROM FOUNDATION WALLS. THE GRADE
 SHALL FALL A MINIMUM OF 6 INCHES (152 MM) WITHIN THE
 FIRST 10 FEET (3048 MM).
 EXCEPTION: WHERE LOT LINES, WALLS, SLOPES OR OTHER
 PHYSICAL BARRIERS PROHIBIT 6 INCHES (152 MM) OF FALL
 WITHIN 10 FEET (3048 MM), DRAINS OR SWALES SHALL BE
 CONSTRUCTED TO ENSURE DRAINAGE AWAY FROM THE STRUCTURE.
 IMPERVIOUS SURFACES WITHIN 10 FEET (3048 MM) OF THE
 BUILDING FOUNDATION SHALL BE SLOPED A MINIMUM OF 2
 PERCENT AWAY FROM THE BUILDING.
  
 2. [FBC 107.3.5.3]PROVIDE SEDIMENT CONTROL PLAN TO KEEP
 CONSTRUCTION DEBRIS FROM ENTERING ADJACENT PROPERTIES
 AND STORM DRAINS DURING CONSTRUCTION. YOU CAN FIND
 ENGINEERING STANDARD DETAILS FROM WPB WEBSITE-POLLUTION
 CONTROL
 HTTP://WWW.WPB.ORG/DEPARTMENTS/ENGINEERING-PUBLIC-WORKS
 /FORMS,-PERMITS-APPLICATIONS
  
 3. [FBC R302.10]PROVIDE CUT SHEET FOR ICYNENE(ICC-ES
 REPORT OR EQUAL) WITH THE TYPE SELECTED TO ESTABLISH
 THICKNESS NEEDED TO MEET REQUIRED R-VALUE, FLAME SPREAD
 INDEX AND SMOKE DEVELOPED INDEX.
 [FBC R302.10]SHEET A-21 STATES R-19 SPRAY INSULATION
 AND POINTS TO A FURRED CEILING. PROVIDE DETAIL OF HOW
 THE REQUIRED AMOUNT OF INSULATION WILL FIT WITHIN THE
 THERMAL ENVELOPE.
  
 4. [FBC ENERGY 103.1.1.2]CODE COMPLIANCE CERTIFICATION.
 THE BUILDING?S OWNER, THE OWNER?S ARCHITECT OR OTHER
 AUTHORIZED AGENT LEGALLY DESIGNATED BY THE OWNER SHALL
 CERTIFY THAT THE BUILDING IS IN COMPLIANCE WITH THE
 CODE, AS PER SECTION 553.907, FLORIDA STATUTES, PRIOR
 TO RECEIVING THE PERMIT TO BEGIN CONSTRUCTION OR
 RENOVATION.
 -PLEASE HAVE OWNER OR OWNERS AGENT SIGN THE ENERGY
 CALCULATION IN ADDITION TO THE PREPARER WHO SIGNED.
  
 PROVISOS:
 -PRE-FAB ALUMINUM TRELLIS, STAIRS AND GUARD RAIL
 ENGINEERING WILL BE A DEFFERED SUBMITTAL AS STATED ON
 SHEET A-1.
 -WINDOWS AND DOORS WILL BE A DEFFERED SUBMITTAL AS
 STATED ON SHEET A-1.
 -TRUSS SHOP DRAWINGS TO THE BUILDING INSPECTOR PRIOR TO
 INSTALLATION.
 -PROVIDE PRODUCT APPROVALS FOR ROOFING WITH SUB-PERMIT
 APPLICATION.
 -SEPARATE PERMIT WILL BE NEEDED FOR
 DRIVEWAY(ENGINEERING DEPT.), POOL AND FENCING.
  
 NOTE:
 -PLEASE PROVIDE COMMENT RESPONSE SHEET TO EXPLAIN HOW
 EACH COMMENT IS BEING ADDRESSED.
 -ADDITIONAL COMMENTS MAY BE FORTHCOMING PENDING REVIEW
 OF MATERIALS REQUESTED.
 -WHEN RESUBMITTING, PROVIDE TWO IDENTICAL COLLATED SETS
 OF DOCUMENTS FOR ISSUANCE. OLD SHEETS (BOTH SETS)
 SHOULD BE RETAINED IN THE PACKAGE; PLEASE DO NOT
 DISCARD ANY DOCUMENTS. THEY SHOULD BE BOUND TOGETHER
 SEPARATELY FROM THE TWO ISSUANCE SETS AND MARKED "VOID"
 OR "OLD SHEETS". PLEASE DO NOT STAMP THE PLANS VOID AS
 APPLICANTS ARE INADVERTENTLY STAMPING SHEETS THAT WE
 NEED "VOID", RENDERING THEM NOT USABLE.
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2019-01-26 Cont ID  
Sent By fgiaquin Date 2019-01-26 Time 11:00 Rev Time 0.00
Received By fgiaquin Date 2019-01-26 Time 10:00 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date   Cont ID  
Sent By   Date 2018-10-29 Time   Rev Time 0.00
Received By ppetty Date 2018-10-25 Time 12:40 Sent To  
Notes
2018-10-25 14:34:04CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1.PROVIDE AVAILABLE SHORT CIRCUIT CALCULATION FOR EACH
 PANEL INCLUDING INFORMATION FROM THE POWER COMPANY
 STATING WHAT THE AVAILABLE SHORT CIRCUIT CURRENT IS FOR
 THE SERVICE TO CONFIRM THE STATED AIC RATING OF THE
 SERVICE EQUIPMENT AND DOWNSTREAM PANELS IS ADEQUATE.
 NEC 110.9, 110.10; FBC RE E3404.2
  
 2.PROVIDE INTERSYSTEM BONDING TERMINATION POINT AT
 SERVICE. SHOW ON PLAN. NEC 250.94; FBC RE E3609.3
 3.A GROUNDING ELECTRODE SYSTEM IS REQUIRED TO BE
 ESTABLISHED AT EACH SEPARATE BUILDING OR STRUCTURE AND
 CONNECTED TOGETHER. PROVIDE DETAILS ON PLAN OF
 GROUNDING ELECTRODE SYSTEM AND WIRING. NEC 250.32; FBC
 RE E3607.3
 4.FEED TO INTERIOR PANEL IS REQUIRED TO HAVE AN
 EQUIPMENT GROUNDING CONDUCTOR, SIZED PER CODE. PROVIDE
 CORRECTION. NEC 250.122; FBC RE E3704.6, 3607.3.1
 5.PROVIDE SMOKE/CO ALARMS IN EACH LOCATION REQUIRED PER
 CODE. FBC RE R314.3, R315.1; WPB FBC 107.2.1.
 6.THE WALL SPACING REQUIREMENTS FOR KITCHEN COUNTER
 SPACE STATE THAT RECEPTACLE OUTLETS SHALL BE INSTALLED
 SO THAT NO POINT ALONG THE WALL LINE IS MORE THAN 24
 INCHES MEASURED HORIZONTALLY FROM A RECEPTACLE OUTLET
 IN THAT SPACE. THE PLAN PROVIDED DOES NOT MEET THIS
 CODE IN SOME AREAS. PROVIDE CORRECTION. NEC
 210.52(C)(1); FBC RE E3901.4
 7.PROVIDE GFCI PROTECTION FOR DISHWASHER. NEC 210.8(D);
 FBC RE E3902.10
 8.GEC TOO SMALL 250.66
 9.OCP TO COTTAGE TOO LARGE
  
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED ?OLD
 SHEETS?.
  
 SINCERELY,
  
 PHIL PETTY
 ELECTRICAL PLANS EXAMINER CHIEF ELECTRICAL INSPECTOR
 561-805-6742
 [email protected]
  

Review Stop HIST HISTORICAL
Rev No 2 Status P Date 2019-01-28 Cont ID  
Sent By fmittner Date 2019-01-28 Time 08:56 Rev Time 0.00
Received By fmittner Date 2019-01-28 Time 08:56 Sent To  
Notes
***NONE***

Review Stop HIST HISTORICAL
Rev No 1 Status P Date 2018-12-20 Cont ID  
Sent By fmittner Date 2018-12-20 Time 09:29 Rev Time 0.00
Received By fmittner Date 2018-12-20 Time 09:29 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2019-01-28 Cont ID  
Sent By lmarchan Date 2019-01-28 Time 09:05 Rev Time 0.00
Received By lmarchan Date 2019-01-10 Time 08:30 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-12-21 Cont ID  
Sent By shill Date 2018-12-21 Time 17:16 Rev Time 0.00
Received By shill Date 2018-10-08 Time 11:15 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status P Date 2019-02-01 Cont ID  
Sent By lmarchan Date 2019-02-01 Time 10:58 Rev Time 0.00
Received By lmarchan Date 2019-01-28 Time 09:05 Sent To  
Notes
2019-02-01 10:58:49RECEIPT - MU2019-0130-75 - $10,253.16
2019-01-28 09:05:451/28/19 IMPACT FEE OFFICE NOTIFIED FOR REVIEW. LEM

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2018-11-19 Cont ID  
Sent By dbattles Date 2018-11-19 Time 08:12 Rev Time 0.00
Received By dbattles Date 2018-11-19 Time 08:12 Sent To  
Notes
2018-11-19 08:12:26DYLAN BATTLES
 BUILDING PLANS EXAMINER I
 [email protected]
 561-805-6718
  
 [FBC AMENDED 109]PLANS WILL BE REVIEWED BY THE PBC
 IMPACT FEE OFFICE DIGITALLY VIA PROJECTDOX UPON
 NOTIFICATION BY THIS OFFICE. NOTIFICATION MAY OCCUR
 WHEN PLANS ARE NEAREST FINAL FORM. YOU MAY COORDINATE
 WITH THE IMPACT FEE OFFICE AT (561) 233-5025 OR SIMPLY
 UPLOAD THE MUNICIPAL IMPACT FEE QUESTIONNAIRE FORM TO
 YOUR PROJECT AND NAME THE FILE MUNICIPAL IMPACT FEE
 QUESTIONNAIRE. THE FORM CAN BE FOUND AT: HTTP://DISCOVE
 R.PBCGOV.ORG/PZB/ADMINISTRATION/PDF/IMPACTFEES/FORMS/QU
 ESTIONNAIRE.PDF UPON APPROVAL AND FEE PAYMENT, PLEASE
 UPLOAD THE RECEIPT TO YOUR PROJECT OR EMAIL IT TO
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2018-10-27 Cont ID  
Sent By cmontell Date 2018-10-27 Time 07:28 Rev Time 0.00
Received By cmontell Date 2018-10-27 Time 07:27 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2018-12-11 Cont ID  
Sent By gjohnson Date 2018-12-11 Time 17:34 Rev Time 0.00
Received By gjohnson Date 2018-12-11 Time 17:34 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status N Date 2019-01-15 Cont ID  
Sent By dbattles Date 2019-01-15 Time 11:47 Rev Time 0.00
Received By dbattles Date 2019-01-15 Time 11:47 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2019-01-15 Cont ID  
Sent By dbattles Date 2019-01-15 Time 11:02 Rev Time 0.00
Received By dbattles Date 2019-01-15 Time 11:02 Sent To  
Notes
2019-01-15 11:03:06ALL SHEETS GOOD FOR SECOND REVIEW.

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2018-11-19 Cont ID  
Sent By dbattles Date 2018-11-19 Time 08:17 Rev Time 0.00
Received By dbattles Date 2018-11-19 Time 08:16 Sent To  
Notes
2018-11-19 08:18:11VERSION 1 SHEETS-OK.
 ALL RE SUBMITTAL SHEETS WILL NEED TO BE CHECKED.
  
 DYLAN BATTLES
 BUILDING PLANS EXAMINER I
 [email protected]
 561-805-6718
  

Review Stop Z ZONING
Rev No 2 Status P Date 2019-01-28 Cont ID  
Sent By fmittner Date 2019-01-28 Time 08:56 Rev Time 0.00
Received By fmittner Date 2019-01-28 Time 08:56 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2018-12-20 Cont ID  
Sent By fmittner Date 2018-12-20 Time 09:30 Rev Time 0.00
Received By fmittner Date 2018-12-20 Time 09:29 Sent To  
Notes
2018-12-20 09:30:27REQUIRES A SEPARATE LANDSCAPE PERMIT