Plan Review Details - Permit 18091187
Plan Review Stops For Permit 18091187
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2018-10-02 Cont ID  
Sent By dbattles Date 2018-10-02 Time 11:34 Rev Time 0.00
Received By dbattles Date 2018-10-02 Time 11:34 Sent To  
Notes
2018-10-02 11:35:46CUSTOMER COME IN TO ON-CALL AND HE PROVIDED ADDITIONAL
 INFO TO ADDRESS COMMENTS.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2018-09-28 Cont ID  
Sent By pvalenti Date 2018-09-28 Time 11:17 Rev Time  
Received By pvalenti Date   Time   Sent To  
Notes
2018-09-28 11:21:43****CORRECTIONS****
  
 PETER E VALENTI
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6673
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 1. FBC R 301, COMPLETE THE "SCHEDULE FOR INSTALLATION
 OF OPENING PROTECTIVE DEVICES" OR PROVIDE ALL
 INFORMATION REQUIRED IN ANOTHER FORMAT (SUCH AS EXCEL
 SPREADSHEET):
  
 HTTP://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/B
 UILDING-PERMIT-FORMS?PAGE=2
  
 2. WHEN COMPLETING THE INSTALLATION SCHEDULE, PLEASE
 NOTE FACTORS THAT APPLY DEPENDING ON SUBSTRATE, EDGE
 DISTANCE AND FASTENER. FOR FASTENER, IF USING TAPCON,
 BE SPECIFIC AS TO WHICH TAPCON (TAPCON W/ADVANCED
 THREADFORM TECHNOLOGY REQUIRES A .9 FACTOR).
  
 PLEASE CONTACT ME IF YOU NEED ASSISTANCE.
  
 3. REVISE PLAN TO SHOW MEANS OF ESCAPE REQUIRED BY FBC
 R 310.4; INCLUDE ROOM DESIGNATION.
  
  
  
 NOTE: PLEASE UPDATE AND SUBMIT THE INSURANCE/WORKERS
 COMP.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-09-28 Cont ID  
Sent By pvalenti Date 2018-09-28 Time 11:22 Rev Time 0.00
Received By pvalenti Date 2018-09-26 Time 14:37 Sent To I
Notes
2018-09-27 14:37:33BLDG <5K