Plan Review Details - Permit 18091136
Plan Review Stops For Permit 18091136
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2019-01-14 Cont ID  
Sent By shill Date 2019-01-14 Time 17:03 Rev Time 0.00
Received By shill Date 2019-01-14 Time 17:03 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2018-11-07 Cont ID  
Sent By shill Date 2018-11-07 Time 16:03 Rev Time 0.00
Received By shill Date 2018-11-07 Time 14:16 Sent To  
Notes
2018-11-07 16:03:15SEE 18091132
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2019-01-29 Cont ID  
Sent By jpearson Date 2019-01-29 Time 15:44 Rev Time 0.00
Received By jpearson Date 2019-01-29 Time 15:44 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2018-12-26 Cont ID  
Sent By jpearson Date 2018-12-26 Time 08:09 Rev Time 0.00
Received By jpearson Date 2018-12-26 Time 08:09 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2018-10-09 Cont ID  
Sent By jpearson Date 2018-10-09 Time 15:38 Rev Time 0.00
Received By jpearson Date 2018-10-09 Time 15:38 Sent To  
Notes
2018-10-09 15:38:54CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. SHEET E-6.00, METER CENTER MC 1A1 IS SHOWN WITH A
 1200 AMP MAIN LUG ONLY CONFIGURATION. A MAIN BREAKER IS
 REQUIRED. MAINS SHOULD BE LABLELED. PROVIDE CORRECTION.
 NEC 230.2(E), 230.70, 230.71, 230.72
 2. SHEET E-6.02, METER CENTER MC 1B1 IS SHOWN WITH A
 1000 AMP MAIN LUG ONLY CONFIGURATION. A MAIN BREAKER IS
 REQUIRED. MAINS SHOULD BE LABLELED. PROVIDE CORRECTION.
 NEC 230.2(E), 230.70, 230.71, 230.72
 3. PROVIDE ARC ENERGY REDUCTION FOR THE BREAKERS IN
 COMMENT 1 AND 2. NEC 240.87
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD
 SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2018-10-12 Cont ID  
Sent By pleduc Date 2018-10-12 Time   Rev Time 0.00
Received By pleduc Date 2018-10-12 Time 14:46 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2019-02-07 Cont ID  
Sent By lmarchan Date 2019-02-07 Time 14:14 Rev Time 0.00
Received By lmarchan Date 2019-01-17 Time 09:01 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2019-01-14 Cont ID  
Sent By shill Date 2019-01-14 Time 17:03 Rev Time 0.00
Received By shill Date 2018-12-14 Time 11:35 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-11-07 Cont ID  
Sent By shill Date 2018-11-07 Time 16:03 Rev Time 0.00
Received By shill Date 2018-09-27 Time 15:18 Sent To  
Notes
2018-10-02 11:49:51**PLANS THE SAME FOR 18091132, 18091134, 18091135, &
 18091136**

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2018-10-22 Cont ID  
Sent By ccole Date 2018-10-22 Time 16:43 Rev Time 0.00
Received By ccole Date 2018-10-22 Time 16:38 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2019-01-11 Cont ID  
Sent By gjohnson Date 2019-01-11 Time 16:04 Rev Time 0.00
Received By gjohnson Date 2019-01-11 Time 16:04 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2018-10-31 Cont ID  
Sent By gjohnson Date 2018-10-31 Time 14:48 Rev Time 0.00
Received By gjohnson Date 2018-10-31 Time 14:48 Sent To  
Notes
2018-10-31 14:48:331ST REVIEW:
 2017 FLORIDA BUILDING CODE 6TH EDITION
 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH
 EDITION
  
 PLUMBING COMMENTS:
  
 1. SHT. P-300 HAS A RED LINE NOTE AT THE LOCATION OF
 THE SUB METER ASKING IS THE SUB METER HERE ? IT APPEARS
 IT IS POSSIBLE THAT THE WRONG VERSION OF SHT. P-300 WAS
 UPLOADED BECAUSE SHT P-301 IS CORRECT. IF YOU CAN
 UPLOAD THE CURRENT VERSION OF SHT P-300 I CAN APPROVE
 THIS REVISION PLEASE CONTACT ME.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2019-01-29 Cont ID  
Sent By jpearson Date 2019-01-29 Time 15:44 Rev Time 0.00
Received By jpearson Date 2019-01-29 Time 15:44 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status F Date 2018-12-26 Cont ID  
Sent By jpearson Date 2018-12-26 Time 07:54 Rev Time 0.00
Received By jpearson Date 2018-12-26 Time 07:54 Sent To  
Notes
2018-12-26 07:54:24CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. PLAN IS REQUIRED TO BE SIGNED AND SEALED BY THE
 PERSON RESPONSIBLE FOR THE DESIGN. A DIGITAL PLAN
 REQUIRES A DIGITAL SIGNATURE. SHEET E-2.05A IS MISSING
 THIS. PROVIDE CORRECTION. WPB FBC 107.1; FS 471/481
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD
 SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2018-10-09 Cont ID  
Sent By jpearson Date 2018-10-09 Time 15:38 Rev Time 0.00
Received By jpearson Date 2018-10-09 Time 15:38 Sent To  
Notes
2018-10-09 15:38:23CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. PLAN IS REQUIRED TO BE SIGNED AND SEALED BY THE
 PERSON RESPONSIBLE FOR THE DESIGN. A DIGITAL PLAN
 REQUIRES A DIGITAL SIGNATURE. SHEETS PD-1, A-6.15, AND
 A-10.03 ARE NOT SIGNED/SEALED. PROVIDE CORRECTION. WPB
 FBC 107.1; FS 471/481
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD
 SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop Z ZONING
Rev No 3 Status P Date 2019-02-07 Cont ID  
Sent By jroach Date 2019-02-07 Time 14:09 Rev Time 0.00
Received By jroach Date 2019-02-07 Time 14:09 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status F Date 2019-01-04 Cont ID  
Sent By jroach Date 2019-01-04 Time 14:39 Rev Time 0.00
Received By jroach Date 2019-01-04 Time 14:39 Sent To  
Notes
2019-01-04 14:39:24REVIEW STATUS: FAILED
 ___________________________________________
  
 PLEASE PROVIDE A WRITTEN RESPONSE TO THE FOLLOWING PLAN
 REVIEW COMMENTS:
  
 1. THE REVISED LANDSCAPE PLANS SHOULD NOT BE INCLUDED
 IN THE REVISION TO THE BUILDING PERMIT; THEY SHOULD BE
 REMOVED AND RE-SUBMITTED AS A REVISION TO THE LANDSCAPE
 PERMIT. PLEASE NOTE THAT THE LANDSCAPE PLANS THAT WERE
 INCLUDED DO NOT MATCH THE SITE PLAN, NOR THE MOST
 RECENT APPROVED PLANS FOR THE DUNBAR VILLAGE
 RESIDENTIAL PLANNED DEVELOPMENT (RPD).
  
 2. THE DUMPSTER DETAIL ON SHEET A-1.01A (DETAIL #1)
 INDICATES A 42-INCH-HIGH KNEE WALL AT A SECTION OF THE
 ENCLOSURE. THIS OPENING SHALL HAVE A GATE/DOOR/ETC. TO
 BLOCK VISIBILITY INTO THE DUMPSTER ENCLOSURE.
 ___________________________________________
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 ___________________________________________
  
 QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING:
  
 JOHN P. ROACH, AICP, PRINCIPAL PLANNER
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES DEPARTMENT ? PLANNING DIVISION
 401 CLEMATIS STREET - P.O. BOX 3147
 WEST PALM BEACH, FLORIDA 33402
  
 P: 561.822.1448
 F: 561.822.1460
  
 E: [email protected]
  
 W: WPB.ORG
  

Review Stop Z ZONING
Rev No 1 Status F Date 2018-10-11 Cont ID  
Sent By jroach Date 2018-10-11 Time 16:23 Rev Time 0.00
Received By jroach Date 2018-10-11 Time 16:23 Sent To  
Notes
2018-10-11 16:23:46REVIEW STATUS: FAILED
 ___________________________________________
  
 PLEASE PROVIDE A WRITTEN RESPONSE TO THE FOLLOWING PLAN
 REVIEW COMMENTS:
  
 1. THE REVISED LANDSCAPE PLANS SHOULD NOT BE INCLUDED
 IN THE REVISION TO THE BUILDING PERMIT; THEY SHOULD BE
 REMOVED AND RE-SUBMITTED AS A REVISION TO THE LANDSCAPE
 PERMIT. PLEASE NOTE THAT THE LANDSCAPE PLANS THAT WERE
 INCLUDED DO NOT MATCH THE SITE PLAN, NOR THE MOST
 RECENT APPROVED PLANS FOR THE DUNBAR VILLAGE
 RESIDENTIAL PLANNED DEVELOPMENT (RPD).
  
 2. THE ARCHITECTURAL NARRATIVE INDICATES THAT A FLAG
 POLE IS BEING ADDED ON SHEET A-1.00; SUCH SHEET DOES
 NOT APPEAR TO INDICATE SUCH ADDITION. THE LOCATION OF
 THE POLE SHALL BE IDENTIFIED, AND DETAILS SHALL BE
 PROVIDED (INCLUDING HEIGHT), OR THE POLE MAY BE
 SUBMITTED UNDER A SEPARATE PERMIT APPLICATION.
  
 3. THE DUMPSTER DETAIL ON SHEET A-1.01A (DETAIL #1)
 INDICATES A 42-INCH-HIGH KNEE WALL AT A SECTION OF THE
 ENCLOSURE; PLEASE CLARIFY.
 ___________________________________________
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 ___________________________________________
  
 QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING:
  
 JOHN P. ROACH, AICP, PRINCIPAL PLANNER
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES DEPARTMENT ? PLANNING DIVISION
 401 CLEMATIS STREET - P.O. BOX 3147
 WEST PALM BEACH, FLORIDA 33402
  
 P: 561.822.1448
 F: 561.822.1460
  
 E: [email protected]
  
 W: WPB.ORG
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved