Plan Review Details - Permit 18091122
Plan Review Stops For Permit 18091122
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2019-04-26 Cont ID  
Sent By dbattles Date 2019-04-26 Time 15:59 Rev Time 0.00
Received By dbattles Date 2019-04-26 Time 15:59 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2019-02-08 Cont ID  
Sent By dbattles Date 2019-02-08 Time 09:28 Rev Time 0.00
Received By dbattles Date 2019-02-08 Time 08:20 Sent To  
Notes
2019-02-08 09:27:38FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC AMENDED = FLORIDA BUILDING CODE,6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC ENERGY = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 2ND REVIEW 2/8/2019
  
 1. OK
  
 2. OK
  
 3. NO RESPONSE SHEET WAS PROVIDED, SO I DO NOT KNOW HOW
 YOUR COMPLYING WITH ENERGY CODE.
 PLEASE PROVIDE DOCUMENTATION TO SHOW COMPLIANCE WITH
 ENERGY CODE.
 503.3 FBC[CE] BUILDING ENVELOPE. NEW BUILDING ENVELOPE
 ASSEMBLIES THAT ARE PART OF THE ALTERATION SHALL COMPLY
 WITH SECTIONS C402.1 THROUGH C402.5.
  (SEE SECTIONS C402.1 THROUGH C402.5)
  
 4. NO RESPONSE TO FLOORING UNDERLAYMENT. ONLY THE UNIT
 ON SECOND FLOOR EAST SIDE THAT HAS UNIT BELOW NEEDS
 UNDERLAYMENT.
 PLEASE PROVIDE FLOORING SUBMITTAL, OR INDICATE THAT IT
 WILL BE DEFERRED.
  
 PLEASE ADVISE, WHAT FLOORING AND UNDERLAYMENT ARE
 PROPOSED? PLEASE ADVISE VIA EMAIL. IF THE UNDERLAYMENT
 PRODUCT PROPOSED IS NOT ONE FOR WHICH WE HAVE TEST
 REPORTS ON FILE, THE FOLLOWING REPORTS ARE REQUIRED:
  
 MANUFACTURER SPEC SHEETS ARE NOT ACCEPTABLE DUE TO
 DISCREPANCIES BETWEEN SPEC SHEETS/BROCHURES AND TEST
 REPORTS FOR SOME MANUFACTURERS (NOT NECESSARILY THE
 MANUFACTURER SELECTED; THIS IS A GENERAL COMMENT)
  
 A. FBC 1207.2, FLOOR/CEILING ASSEMBLIES SEPARATING
 DWELLING UNITS FROM EACH OTHER OR FROM PUBLIC OR
 SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS
 (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) FOR AIR
 BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM E 90.
 THE TEST REPORT CANNOT INCLUDE A DROPPED GYPSUM
 CEILING. PROVIDE A COPY OF THE TEST REPORT.
  
 B. FBC 1207.3, FLOOR/CEILING ASSEMBLIES BETWEEN
 DWELLING UNITS OR BETWEEN A DWELLING UNIT AND A PUBLIC
 OR SERVICE AREA WITHIN THE STRUCTURE SHALL HAVE AN
 IMPACT INSULATION CLASS (IIC) RATING OF NOT LESS THAN
 50 (45 IF FIELD TESTED) WHEN TESTED IN ACCORDANCE WITH
 ASTM E 492. THE TEST REPORT CANNOT INCLUDE A DROPPED
 GYPSUM CEILING. PROVIDE A COPY OF THE TEST REPORT.
  
 C. FBC 603.1, ALLOWABLE MATERIALS IN NON COMBUSTIBLE
 BUILDINGS, SEE ITEM 2, EXCEPTION 2, ACOUSTICAL
 INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID
 DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED
 TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200. SEE
 803.1.1, PROVIDE TEST DATA IN ACCORDANCE WITH ASTM E 84
 OR UL 723.
  
 NOTE:
 -PLEASE PROVIDE COMMENT RESPONSE SHEET TO EXPLAIN HOW
 EACH COMMENT IS BEING ADDRESSED.
 -ADDITIONAL COMMENTS MAY BE FORTHCOMING PENDING REVIEW
 OF MATERIALS REQUESTED.
 -WHEN RESUBMITTING, PROVIDE TWO IDENTICAL COLLATED SETS
 OF DOCUMENTS FOR ISSUANCE. OLD SHEETS (BOTH SETS)
 SHOULD BE RETAINED IN THE PACKAGE; PLEASE DO NOT
 DISCARD ANY DOCUMENTS. THEY SHOULD BE BOUND TOGETHER
 SEPARATELY FROM THE TWO ISSUANCE SETS AND MARKED "VOID"
 OR "OLD SHEETS". PLEASE DO NOT STAMP THE PLANS VOID AS
 APPLICANTS ARE INADVERTENTLY STAMPING SHEETS THAT WE
 NEED "VOID", RENDERING THEM NOT USABLE.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2018-11-07 Cont ID  
Sent By dbattles Date 2018-11-07 Time 08:19 Rev Time 0.00
Received By dbattles Date 2018-11-06 Time 15:30 Sent To  
Notes
2018-11-07 08:20:17****CORRECTIONS****
 W.P.B. PERMIT: 18091122
 REVIEWED: NOVEMBER 7, 2018
  
 DYLAN BATTLES
 BUILDING PLANS EXAMINER I
 [email protected]
 561-805-6718
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC AMENDED = FLORIDA BUILDING CODE,6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC ENERGY = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 1. [FBC 107.3.5.3]MINIMUM DRAWING REQUIREMENTS
 A FULL REVIEW CANNOT BE DONE WITH THE DRAWINGS
 PROVIDED. PLEASE PROVIDE DRAWINGS TO SHOW ALL TRADES
 AND ALL WORK BEING PERFORMED.
 DEMO PLAN TO SHOW WHAT IS EXISTING AND WHAT IS
 PROPOSED.
 LABLE ROOM UNDER THE STAIRS AND NEXT TO GARAGE. IS THAT
 PART OF FIRST FLOOR UNIT?
 WHAT IS GOING IN THE KITCHENS?
 HOW ARE THE SPACES COOLED (SEE COMMENT #3)
 CURRENT CODES: LIST THE CODES APPLICABLE TO THE WORK
 BEING PERFORMED.
 PROJECT DATA:
 OCCUPANCY =
 LEVEL OF ALTERATION =
 TYPE OF CONSTRUCTION =
 AREA TABULATIONS =
 WHAT ARE THE CURRENT SEPARATIONS BETWEEN UNITS AND WHAT
 WILL THEY BE TO MEET CURRENT CODES FOR UNIT SEPARATION?
  
 2. [R302.6]GARAGE CEILING TO HAVE TYPE NOT LESS THAT
 5/8? TYPE X OR EQUIVELANT DRYWALL WHEN HABITABLE SPACE
 IS PROVIDED ABOVE.
  
 3. [FBC ENERGY R401.2]PROVIDE ENERGY CALCULATIONS TO
 MEET REQUIREMENTS IN R401.2 RESIDENTIAL ENERGY CODE.
 CHOOSE METHOD IN R401.2 AND SUPPLY DOCUMENTATION.
  
 4. PLEASE ADVISE, WHAT FLOORING AND UNDERLAYMENT ARE
 PROPOSED? PLEASE ADVISE VIA EMAIL. IF THE UNDERLAYMENT
 PRODUCT PROPOSED IS NOT ONE FOR WHICH WE HAVE TEST
 REPORTS ON FILE, THE FOLLOWING REPORTS ARE REQUIRED:
  
 MANUFACTURER SPEC SHEETS ARE NOT ACCEPTABLE DUE TO
 DISCREPANCIES BETWEEN SPEC SHEETS/BROCHURES AND TEST
 REPORTS FOR SOME MANUFACTURERS (NOT NECESSARILY THE
 MANUFACTURER SELECTED; THIS IS A GENERAL COMMENT)
  
 A. FBC 1207.2, FLOOR/CEILING ASSEMBLIES SEPARATING
 DWELLING UNITS FROM EACH OTHER OR FROM PUBLIC OR
 SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS
 (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) FOR AIR
 BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM E 90.
 THE TEST REPORT CANNOT INCLUDE A DROPPED GYPSUM
 CEILING. PROVIDE A COPY OF THE TEST REPORT.
  
 B. FBC 1207.3, FLOOR/CEILING ASSEMBLIES BETWEEN
 DWELLING UNITS OR BETWEEN A DWELLING UNIT AND A PUBLIC
 OR SERVICE AREA WITHIN THE STRUCTURE SHALL HAVE AN
 IMPACT INSULATION CLASS (IIC) RATING OF NOT LESS THAN
 50 (45 IF FIELD TESTED) WHEN TESTED IN ACCORDANCE WITH
 ASTM E 492. THE TEST REPORT CANNOT INCLUDE A DROPPED
 GYPSUM CEILING. PROVIDE A COPY OF THE TEST REPORT.
  
 C. FBC 603.1, ALLOWABLE MATERIALS IN NON COMBUSTIBLE
 BUILDINGS, SEE ITEM 2, EXCEPTION 2, ACOUSTICAL
 INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID
 DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED
 TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200. SEE
 803.1.1, PROVIDE TEST DATA IN ACCORDANCE WITH ASTM E 84
 OR UL 723.
  
 NOTE:
 -PLEASE PROVIDE COMMENT RESPONSE SHEET TO EXPLAIN HOW
 EACH COMMENT IS BEING ADDRESSED.
 -ADDITIONAL COMMENTS MAY BE FORTHCOMING PENDING REVIEW
 OF MATERIALS REQUESTED.
 -WHEN RESUBMITTING, PROVIDE TWO IDENTICAL COLLATED SETS
 OF DOCUMENTS FOR ISSUANCE. OLD SHEETS (BOTH SETS)
 SHOULD BE RETAINED IN THE PACKAGE; PLEASE DO NOT
 DISCARD ANY DOCUMENTS. THEY SHOULD BE BOUND TOGETHER
 SEPARATELY FROM THE TWO ISSUANCE SETS AND MARKED "VOID"
 OR "OLD SHEETS". PLEASE DO NOT STAMP THE PLANS VOID AS
 APPLICANTS ARE INADVERTENTLY STAMPING SHEETS THAT WE
 NEED "VOID", RENDERING THEM NOT USABLE.
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2019-04-30 Cont ID  
Sent By jpearson Date 2019-04-30 Time 15:56 Rev Time 0.00
Received By jpearson Date 2019-04-30 Time 15:56 Sent To I
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2019-02-25 Cont ID  
Sent By jpearson Date 2019-02-25 Time 15:45 Rev Time 0.00
Received By jpearson Date 2019-02-25 Time 12:12 Sent To  
Notes
2019-02-25 15:45:50CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 PREVIOUS COMMENTS THAT HAVE BEEN ADDRESSED
 SATISFACTORILY ARE MARKED AS CORRECTED. PREVIOUS
 COMMENTS THAT HAVE NOT BEEN ADDRESSED SATISFACTORILY
 HAVE ADDITIONAL COMMENTS IN PARENTHESES. ANY NEW
 COMMENTS WILL BE LISTED AFTER PREVIOUS COMMENTS.
  
 1. CORRECTED.
 2. PROVIDE COPY OF SIGNED CONTRACT WITH SCOPE AND VALUE
 OF WORK, TO INCLUDE ALL MATERIALS AND LABOR. THIS IS
 FOR TOTAL PROJECT, NOT JUST ELECTRICAL. FBC 109.3 (NOT
 PROVIDED.)
  
 NEW COMMENTS:
  
 3. AFCI PROTECTION DESCRIBED IN NOTE 1 IS NOT CODE
 COMPLIANT. ALL BRANCH CIRCUITS THAT SUPPLY 120-VOLT,
 SINGLE-PHASE, 15- AND 20-AMPERE OUTLETS INSTALLED IN
 KITCHENS, FAMILY ROOMS, DINING ROOMS, LIVING ROOMS,
 PARLORS, LIBRARIES, DENS, BEDROOMS, SUN-ROOMS,
 RECREATIONS ROOMS, CLOSETS, HALLWAYS, LAUNDRY AREAS AND
 SIMILAR ROOMS OR AREAS SHALL BE AFCI PROTECTED. THIS
 INCLUDES LIGHTING AND POWER OUTLETS AND RECEPTACLES.
 SOME AREAS REQUIRE BOTH AFCI AND GFCI PROTECTION.
 PROVIDE CORRECTION. NEC 210.8, 210.12; FBC RE E3902;
 FBC EX 607.1.1 OR 801.1, 801.2, OR 901.2 AS APPLICABLE.
 4. NOTE 13 STATES THAT LIGHTING IN CLOTHES CLOSETS
 SHALL COMPLY WITH NEC 4/10.16, WHICH DOESN?T EXIST.
 PROVIDE CORRECTION. NEC 410.16; FBC RE E4003.12
 5. SHEET E2.1, NOTE 3 CALLS FOR WIRING PER 2011 NEC,
 WHICH IS NOT THE CURRENT CODE. PROVIDE CORRECTION. FBC
 PREFACE.
 6. PROVIDE CARBON MONOXIDE ALARMS WITHIN 10 FEET OF
 EACH ROOM USED FOR SLEEPING PURPOSES. FBC RE R315.1
  
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD
 SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2018-10-07 Cont ID  
Sent By jpearson Date 2018-10-07 Time 17:45 Rev Time 0.00
Received By jpearson Date 2018-10-07 Time 17:45 Sent To  
Notes
2018-10-07 17:45:13CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. PROVIDE ELECTRICAL PLAN FOR REVIEW, SIGNED AND
 SEALED BY THE PERSON RESPONSIBLE FOR THE DESIGN. WPB
 FBC 107.2.1, 107.3.5; FS 471 481
 2. PROVIDE COPY OF SIGNED CONTRACT WITH SCOPE AND VALUE
 OF WORK, TO INCLUDE ALL MATERIALS AND LABOR. THIS IS
 FOR TOTAL PROJECT, NOT JUST ELECTRICAL. FBC 109.3
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD
 SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop HIST HISTORICAL
Rev No 3 Status N Date 2019-04-25 Cont ID  
Sent By aborngra Date 2019-04-25 Time 11:50 Rev Time 0.00
Received By aborngra Date 2019-04-25 Time 11:49 Sent To PC
Notes
***NONE***

Review Stop HIST HISTORICAL
Rev No 2 Status N Date 2019-02-20 Cont ID  
Sent By fmittner Date 2019-02-20 Time 09:33 Rev Time 0.00
Received By fmittner Date 2019-02-20 Time 09:33 Sent To  
Notes
***NONE***

Review Stop HIST HISTORICAL
Rev No 1 Status N Date 2018-11-19 Cont ID  
Sent By fmittner Date 2018-11-19 Time 16:32 Rev Time 0.00
Received By fmittner Date 2018-11-19 Time 16:32 Sent To Z
Notes
2018-11-19 16:32:57ALL INTERIOR WORK NO HISTORIC PRESERVATION JURISDICTION
 DESPITE CONCERN ABOUT LOS OF PLASTER AND FLOORING.
 SEDNIGN TO ZONING TO CONFIRM IF 3 APARTMENTS ARE
 PERMITTED.

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2019-05-31 Cont ID  
Sent By thunt Date 2019-05-31 Time 13:34 Rev Time 0.00
Received By thunt Date 2019-05-21 Time 14:20 Sent To  
Notes
2019-05-22 14:21:04RESUB ROUTED TO CCOLE

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2019-05-14 Cont ID  
Sent By thunt Date 2019-05-14 Time 16:48 Rev Time 0.00
Received By thunt Date 2019-05-09 Time 13:24 Sent To  
Notes
2019-05-09 13:24:30RESUB ROUTED TO CCOLE

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date   Cont ID  
Sent By   Date 2019-04-30 Time   Rev Time 0.00
Received By lmarchan Date 2019-04-16 Time 14:14 Sent To  
Notes
2019-04-17 14:14:48B32

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2019-02-26 Cont ID  
Sent By jesmith Date 2019-02-26 Time 11:12 Rev Time 0.00
Received By jesmith Date 2019-02-26 Time 11:12 Sent To  
Notes
2019-02-07 14:47:46B10

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-12-04 Cont ID  
Sent By cpuell Date 2018-12-04 Time 13:14 Rev Time 0.00
Received By cpuell Date 2018-09-25 Time 11:02 Sent To  
Notes
2018-09-27 11:02:31R31

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2019-05-30 Cont ID  
Sent By ccole Date 2019-05-30 Time 11:08 Rev Time 0.00
Received By ccole Date 2019-05-30 Time 11:08 Sent To P
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2019-05-14 Cont ID  
Sent By ccole Date 2019-05-14 Time 14:53 Rev Time 0.00
Received By ccole Date 2019-05-14 Time 14:53 Sent To P
Notes
2019-05-14 15:20:542ND REVIEW FBC-2017 MECHANICAL
 PERMIT #18091122
 4/29/19
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THE 1ST REVIEW COMMENT #3 PRINTED BELOW STILL EXIST-
 PLEASE COMPLY.
  
 3) M1: INDICATE HOW THE APARTMENTS ARE TO BE
 VENTILATED- NATURALLY OR MECHANICALLY -AND PROVIDE
 CALCULATIONS- SEE SECTIONS 401.2, 402.1, AND 403.1 FBC
 M. (REFER TO SECTION 403.3.2 FBC M FOR ADDITIONAL
 REQUIREMENTS). PLEASE READ EXPLALNATORY NOTES AND CODE
 COMPLIANCE REQUIRMENTS BELOW- A & B.
  
 A) NATURAL VENTILATION IS ALLOWED FOR BATHROOMS IN
 SINGLE FAMILY HOMES ONLY, HOWEVER THE PROPOSED PROJECT
 IS A B (BUSINESS) AND R2 (APARTMENTS) OCCUPANCY WHICH
 REQUIRES MECHANICAL VENTILATION FOR THE BATHROOMS- SEE
 SECTION 1203.4.2.1 FBC B. MECHANICAL VENTILATION MOST
 COMMONLY WOULD BE ACCOMPLISHED USING EXHAUST FANS AND
 EXHAUST DUCTS IN THE BATHROOMS
  
 B) AS PREVIOUSLY REQUESTED PROVIDE CALCULATIONS FOR
 NATURAL VENTILATION OF THE LIVING SPACES, EXCLUDING THE
 BATHROOMS- SEE SECTION 402.2 FBC M.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2019-04-29 Cont ID  
Sent By ccole Date 2019-04-29 Time 14:47 Rev Time 0.00
Received By ccole Date 2019-04-29 Time 13:25 Sent To  
Notes
2019-04-29 15:03:472ND REVIEW FBC-2017 MECHANICAL
 PERMIT #18091122
 4/29/19
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) M1: THE 14 SEER 2-TON AC SYSTEMS DON'T MATCH WITH
 THE ENERGY CALCULATIONS WHICH INDICATE THE SYSTEMS
 ARE16 SEER. THE SCHEDULE ALSO DOES NOT PROVIDE A SEER
 FOR THE MINI SPLIT WHICH IS LISTED AS 18 SEER IN THE
 ENERGY CALCS.
  
 2) M1 & A4: THE LOUVERD AC CLOSET DOORS SHALL BE OF
 NON-COMBUSTIBLE CONSTUCTION MATERIALS PER SECTION 602.1
 FBC M. THE DOOR SCHEDULE IS INDICATING WOOD.
  
 3) THE 1ST REVIEW COMMENTS #3, 5, 7, 8 PRINTED BELOW
 STILL EXIST- PLEASE COMPLY.
  
 3) M1: INDICATE HOW THE APARTMENTS ARE TO BE
 VENTILATED- NATURALLY OR MECHANICALLY -AND PROVIDE
 CALCULATIONS- SEE SECTIONS 401.2, 402.1, AND 403.1 FBC
 M. (REFER TO SECTION 403.3.2 FBC M FOR ADDITIONAL
 REQUIREMENTS).
 .
 5) M1: SHOW HOW LOCAL EXHAUST SYSTEMS ARE BEING
 PROVIDED FOR THE BATH AND KITCHEN- SECTION 403.3.2.3
 FBC M.
  
 7) M2: SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE
 VENTLESS DRYER, AND THE COOKING APPLIANCES- SECTIONS
 304.1 AND 504.1 FBC M.
  
 8) M2: CLARIFY IF NEW EXHAUST HOODS FOR THE COOKING
 APPLIANCES ARE TO BE INSTALLED AND PROVIDE DETAILS AND
 SPECIFICATIONS- SECTION 505.1 FBC M.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2019-02-20 Cont ID  
Sent By ccole Date 2019-02-20 Time 10:54 Rev Time 0.00
Received By ccole Date 2019-02-20 Time 09:57 Sent To  
Notes
2019-02-20 11:30:101ST REVIEW FBC-2017 MECHANICAL
 PERMIT #18091122
 2/20/19
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PROVIDE AC COOLING AND HEATING CALCULATIONS FOR THE
 NEW SYSTEMS IN ACCORDANCE WITH SECTION R403.7.1 FBC EC.
  
 2) THE PROPOSED PROJECT IS CLASSIFIED AS A RENOVATION
 IN ACCORDANCE WITH SECTION 202 FBC EC. SUBMIT AN ENERGY
 COMPLIANCE REPORT AS REQUIRED BY SECTION R505.1.1, AND
 R101.5.1.1 FBC EC
  
 3) INDICATE HOW THE APARTMENTS ARE TO BE VENTILATED-
 NATURALLY OR MECHANICALLY -AND PROVIDE CALCULATIONS-
 SEE SECTIONS 401.2, 402.1, AND 403.1 FBC M.
  
 4) THE MODEL NUMBERS ON THE SUBMITTED CUT SHEET FOR THE
 MINI-SPLIT SYSTEM DO NOT MATCH THE MODEL NUMBERS ON
 SHEET M1.
  
 5) M-1: SHOW HOW LOCAL EXHAUST SYSTEMS ARE BEING
 PROVIDED FOR THE BATH AND KITCHEN- SECTION 403.3.2.3
 FBC M.
  
 6) M-1: INDICATE WHAT APPLIANCE IS LOCATED IN THE
 CLOSET BY THE STAIRS.
  
 7) M-2: SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE
 VENTLESS DRYER, AND THE COOKING APPLIANCES- SECTIONS
 304.1 AND 504.1 FBC M.
  
 8) M-2: CLARIFY IF NEW EXHAUST HOODS FOR THE COOKING
 APPLIANCES ARE TO BE INSTALLED AND PROVIDE DETAILS AND
 SPECIFICATIONS- SECTION 505.1 FBC M.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 5 Status P Date 2019-05-31 Cont ID  
Sent By thunt Date 2019-05-31 Time 13:34 Rev Time 0.00
Received By thunt Date 2019-05-31 Time 13:34 Sent To  
Notes
2019-05-31 13:34:40PROVISIO APPROVAL ON 5/14/19

Review Stop P PLUMBING
Rev No 4 Status P Date 2019-05-14 Cont ID  
Sent By thunt Date 2019-05-14 Time 16:46 Rev Time 0.00
Received By thunt Date 2019-05-14 Time 16:46 Sent To  
Notes
2019-05-14 16:46:56PLUMBING PROVISO WAS AGREED BY MR. DRAGO VIA PHONE
 CONVERSATION ON 5/14/19 4:30 P.M
  
 1) A CODE COMPLIANT SANITARY ISOMETRIC DRAWING SHALL BE
 PROVIDE AS A REVISION TO THE BUILDING DEPARTMENT AND
 APPROVED BY THE 2ND ROUGH/ TOP OUT INSPECTION. THE
 WASHING MACHINE SHALL NOT DISCHARGE INTO THE BATHROOM
 GROUP WET VENT. FBC R-P3108.1, P3108.2.1.
  
 2) ANY EXISTING PIPING THAT IS REPLACE SHALL BE INSTALL
 PER THE 2017 6TH ED FBC AND TREATED AS NEW WORK.
  

Review Stop P PLUMBING
Rev No 3 Status F Date 2019-04-18 Cont ID  
Sent By jesmith Date 2019-04-18 Time 15:05 Rev Time 0.00
Received By jesmith Date 2019-04-18 Time 14:57 Sent To  
Notes
2019-04-18 15:04:49CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION
 WPB CCC = WEST PALM BEACH CROSS CONNECTION CONTROL
 MANUAL
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RES = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 FBC ACC = FLORIDA ACCESSIBILITY CODE 2017 6TH EDITION
 FBC EX = FLORIDA EXISTING BUILDING CODE 2017 6TH
 EDITION
 FBC FG = FLORIDA FUEL GAS CODE 2017 6TH EDITION
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
 3RD REVIEW
 PLUMBING COMMENTS: DENIED
 1. RE: A-6 PLUMBING PLAN; UNIT #1 & #2 SANITARY RISER.
 A. GROUND FLOOR; KITCHEN SINK SHALL DISCHARGE TO
 HORIZONTAL BRANCH DOWNSTREAM OF BATHROOM GROUP PER FBC
 PL 912.1 AND SHALL BE VENTED PER FBC PL 910.1.
 B. 2ND FLOOR; NEW CLOTHES WASHER SHALL CONNECT TO
 VERTICAL STACK BELOW THE SHOWER FIXTURE DRAIN
 CONNECTION PER FBC PL 912.1.1 AND SHALL BE VENTED PER
 FBC PL 910.1.
 C. 2ND FLOOR; KITCHEN SINK AND DISPOSAL SHALL CONNECT
 TO VERTICAL STACK BELOW THE BATHROOM FIXTURE DRAIN
 CONNECTIONS PER FBC PL 912.1.1 AND SHALL BE VENTED PER
 FBC PL 910.1. WATER CLOSET AND BATHTUB FIXTURE DRAINS
 SHALL CONNECT INDEPENDENTLY TO THE VERTICAL WET VENT.
 THE BATHTUB FIXTURE DRAIN SHALL CONNECT ABOVE OR AT THE
 SAME ELEVATION AS THE WATER CLOSET FIXTURE DRAIN. THE
 DRY-VENT CONNECTION TO THE VERTICAL WET VENT SHALL BE
 AN INDIVIDUAL OR COMMON VENT SERVING ONE OR TWO
 FIXTURES.
 2.WPB FBC 107.3.5.1.3 REQUIRES A CODE COMPLIANT WATER
 RISER DIAGRAM.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED "VOID".
  
  
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 PHONE 561-805-6715
  
 18091122 230 ARGYLE RD
  
 NOTE: EXISTING GAS TANKLESS WATER HEATER INSTALLED
 UNDER PERMIT #16060022
  
  

Review Stop P PLUMBING
Rev No 2 Status F Date 2019-02-26 Cont ID  
Sent By jesmith Date 2019-02-26 Time 11:11 Rev Time 0.00
Received By jesmith Date 2019-02-26 Time 11:10 Sent To  
Notes
2019-02-26 11:11:26CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RES = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 FBC ACC = FLORIDA ACCESSIBILITY CODE 2017 6TH EDITION
 FBC EX = FLORIDA EXISTING BUILDING CODE 2017 6TH
 EDITION
 FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION
 FBC FG = FLORIDA FUEL GAS CODE 2017 6TH EDITION
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
 2ND REVIEW: DENIED
 PLUMBING COMMENTS:
 ORIGINAL SUBMITTAL WAS ONE (1) PLAN SHEET A101, DATED
 9/18/2018. PLUMBING SCOPE WAS LIMITED TO REMOVING AND
 REPLACING EXISTING BATHROOM AND KITCHEN FIXTURES. NEW
 SUBMITTED PLANS DATED 2/4/2019 SHOW RECONFIGURATION OF
 BATHROOMS AND KITCHENS AS WELL AS ADDED PLUMBING
 FIXTURES.
 PER WPB FBC 107.2.1 AND WPB FBC 107.3.5.3 (12), PROVIDE
 A CODE COMPLIANT SANITARY PLUMBING RISER DIAGRAM
 INTEGRATING EXISTING AND NEW PIPING
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 (STAMPED/SEALED AND SIGNED BY DESIGNER OF RECORD IN
 ACCORDANCE WITH FS 471 FAC 61G15) INTO THE ORIGINAL
 SUBMITTAL AND REMOVE THE PREVIOUSLY REVIEWED SHEETS.
 ONE COPY OF THE PREVIOUSLY REVIEWED SHEETS SHOULD
 REMAIN IN PACKAGE AND BE MARKED "VOID".
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 PHONE 561-805-6715

Review Stop P PLUMBING
Rev No 1 Status F Date 2018-10-23 Cont ID  
Sent By jesmith Date 2018-10-23 Time 11:08 Rev Time 0.00
Received By jesmith Date 2018-10-23 Time 11:08 Sent To  
Notes
2018-10-23 11:08:47CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RES = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 FBC ACC = FLORIDA ACCESSIBILITY CODE 2017 6TH EDITION
 FBC EX = FLORIDA EXISTING BUILDING CODE 2017 6TH
 EDITION
 FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION
 FBC FG = FLORIDA FUEL GAS CODE 2017 6TH EDITION
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
 1ST REVIEW:
 PLUMBING COMMENTS: DENIED
  
 1. REFERENCED THE THE PLANS SUBMITTED FOR CITY OF WEST
 PALM BEACH PERMIT #17040402. THE BUILDING IN QUESTION
 APPEARS TO BE THE ONE LOCATED ON THE SOUTH SIDE OF THE
 PROPERTY. PLEASE PROVIDE THE BOUNDARY SURVEY AND
 CONFIRM THE BUILDING THAT THE WORK IS TO BE PERFORMED
 IN. WPB FBC 107.2.1
 2. REVISE PLAN TO PROVIDE OCCUPANCY CLASSIFICATION. WPB
 FBC 107.2.1
 3. SHOW EXISTING COMMON CLOTHES WASHER FACILITIES FOR
 RESIDENTS AS REQUIRED BY FBC PL TABLE 403.1. WPB FBC
 107.2.12.
 4. SHOW LOCATION(S) AND TYPE/CAPACITY OF EXISTING WATER
 HEATER(S) COMPLYING WITH THE PROVISIONS OF FBC PL
 CHAPTER 5 AND 607.3, PROVIDING HOT WATER TO FIXTURES AS
 REQUIRED BY FBC PL 607.1. WPB FBC 107.2.1
 5. PROVIDE WATER HAMMER ARRESTORS AT WATER SUPPLIES TO
 ICE LINE, DISHWASHER AND CLOTHES WASHER PER FPC PL
 604.9; INDICATE SAME ON THE PLANS PER WPB FPC 107.2.1
 6. TUB/SHOWER CONTROL VALVE(S) SHALL BE PRESSURE
 BALANCED PB,THERMOSTATIC MIXING (TM) OR COMBINATION
 PB/TM VALVE TYPES WITH HIGH TEMPERATURE LIMITING STOP
 IN ACCORDANCE WITH FBC PL 424.3
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 (STAMPED/SEALED AND SIGNED BY DESIGNER OF RECORD IN
 ACCORDANCE WITH FS 471 FAC 61G15) INTO THE ORIGINAL
 SUBMITTAL AND REMOVE THE PREVIOUSLY REVIEWED SHEETS.
 ONE COPY OF THE PREVIOUSLY REVIEWED SHEETS SHOULD
 REMAIN IN PACKAGE AND BE MARKED "VOID".
  
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 PHONE 561-805-6715

Review Stop Z ZONING
Rev No 3 Status P Date 2019-04-25 Cont ID  
Sent By aborngra Date 2019-04-25 Time 11:49 Rev Time 0.00
Received By aborngra Date 2019-04-25 Time 11:49 Sent To PC
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date 2019-02-20 Cont ID  
Sent By fmittner Date 2019-02-20 Time 09:32 Rev Time 0.00
Received By fmittner Date 2019-02-20 Time 09:32 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2018-11-20 Cont ID  
Sent By fmittner Date 2018-11-20 Time 16:12 Rev Time 0.00
Received By fmittner Date 2018-11-20 Time 16:12 Sent To  
Notes
***NONE***