Plan Review Details - Permit 18091119
Plan Review Stops For Permit 18091119
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2018-11-21 Cont ID  
Sent By pvalenti Date 2018-11-21 Time 13:38 Rev Time 0.00
Received By pvalenti Date 2018-11-21 Time 13:37 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2018-11-05 Cont ID  
Sent By jwitmer Date 2018-11-05 Time 10:56 Rev Time  
Received By jwitmer Date 2018-11-05 Time 07:16 Sent To  
Notes
2018-11-05 10:55:512017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 18091119
 ADD: 851 VILLAGE BLVD. SUITE: 602A
 CONT: MASTER PLAN INC.
 TEL: 561-683-9972
 E-MAIL: [email protected]
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: MON. NOV. 5/ 2018
 ACTION: DENIED
  
 1) PLEASE SUBMIT AN ORIGINAL PERMIT APPLICATION BEFORE
 THE PERMIT CAN BE ISSUED.
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION SECTION 105.1 REQUIRED SIGNATURES,
 ORIGINAL SIGNATURE NOT COPIES.
 2) SHEET A-1:
 2A) HEADING APPLICABLE CODES AND STANDARDS INDICATES
 THE SUBMITTED PLANS WERE DESIGNED UNDER THE 2014 5TH
 EDITION OF THE FLORIDA FAMILY OF CODES. PLEASE UPDATE
 THE PLANS, DEC. 31/ 2017 STATEWIDE THE 2017 6TH EDITION
 OF THE FLORIDA FAMILY OF CODES WAS ADOPTED STATEWIDE.
 2B) UNDER THE HEADING BUILDING BASICS THE OCCUPANCY
 CLASSIFICATION IS A A-2 SMALL ASSEMBLY. PLEASE SEE 2017
 FBC-B SECTION 303.1.2 FOR SMALL ASSEMBLY, THE SMALL
 ASSEMBLY HAS TO BE AN ACCESSORY OCCUPANCY TO THE MAIN
 OCCUPANCY TYPE, AND A ROOM OR SPACE LESS THAN 750 SQ.
 FT. AND AN OCCUPANT LOAD OF LESS THAN 50. THIS TENANT
 SPACE IS AN A-2 OCCUPANCY RESTAURANT WITH A DECLARED
 OCCUPANT LOAD OF 92 OCCUPANTS, PLEASE UPDATE PLANS.
 3C) UNDER THE HEADING BUILDING BASICS THE MINIMUM
 BUILDING TYPE IS LABELED A TYPE III CONSTRUCTION.
 PLEASE IDENTIFY THE BUILDING TYPE AS EITHER TYPE IIIA
 OR IIIB? SEE 2017 FBC-B 504.4 & TABLE 506.2.
 3D) THE PLANS DOES NOT INDICATE IF THE BUILDING IS FIRE
 SPRINKLERED OR NOT, COMPLIANCE WITH 2017 FBC-B TABLE
 508.4 REQUIRING 1 OR 2 HOUR FIRE SEPARATION FROM OTHER
 OCCUPANCIES WALL TYPES AND RATINGS CANNOT BE
 DETERMINED?
 3E) THE COVERSHEET INDICATES THERE IS 84 SEATS FOR THIS
 ASSEMBLY OCCUPANCY, 84X0.05%= 4.2 OR 5 REQUIRED
 ACCESSIBLE SEATS ARE REQUIRED TO BE SHOWN ON THE PLANS
 TO SHOW COMPLIANCE WITH 2017 FBC-ACCESSIBILITY CODE
 SECTION 226.1 WHERE DINING SURFACES ARE PROVIDED FOR
 THE CONSUMPTION OF FOOD OR DRINK, AT LEAST 5 PERCENT OF
 THE SEATING SPACES AND STANDING SPACES AT THE DINING
 SURFACES SHALL COMPLY WITH 902.
  
 3E)(1) 226.2 DISPERSION. DINING SURFACES AND WORK
 SURFACES REQUIRED TO COMPLY WITH 902 SHALL BE DISPERSED
 THROUGHOUT THE SPACE OR FACILITY CONTAINING DINING
 SURFACES AND WORK SURFACES.
  
 3E)(2) 206.2.5 206.2.5 RESTAURANTS AND CAFETERIAS. IN
 RESTAURANTS AND CAFETERIAS, AN ACCESSIBLE ROUTE SHALL
 BE PROVIDED TO ALL DINING AREAS, INCLUDING RAISED OR
 SUNKEN DINING AREAS, AND OUTDOOR DINING AREAS.
  
 3F) 902.1 .DINING SURFACES AND WORK SURFACES SHALL
 COMPLY WITH 902.2 AND 902.3. ADVISORY 902.1 GENERAL.
 DINING SURFACES INCLUDE, BUT ARE NOT LIMITED TO, BARS,
 TABLES, LUNCH COUNTERS, AND BOOTHS. EXAMPLES OF WORK
 SURFACES INCLUDE WRITING SURFACES, STUDY CARRELS,
 STUDENT LABORATORY STATIONS, BABY CHANGING AND OTHER
 TABLES OR FIXTURES FOR PERSONAL GROOMING, COUPON
 COUNTERS, AND WHERE COVERED BY THE ABA SCOPING
 PROVISIONS, EMPLOYEE WORK STATIONS.
  
 3F)(1) 902.2 CLEAR FLOOR OR GROUND SPACE. A CLEAR FLOOR
 SPACE COMPLYING WITH 305 POSITIONED FOR A FORWARD
 APPROACH SHALL BE PROVIDED. KNEE AND TOE CLEARANCE
 COMPLYING WITH 306 SHALL BE PROVIDED.
  
 3F)(2) 902.3 HEIGHT. THE TOPS OF DINING SURFACES AND
 WORK SURFACES SHALL BE 28 INCHES MINIMUM AND 34 INCHES
 MAXIMUM ABOVE THE FINISH FLOOR OR GROUND.
  
 3G) THE P. O. S. (POINT OF SALE) DOES NOT PROVIDE ANY
 ELEVATION VIEW OR CUT SECTION THROUGH THIS ELEMENT
 SHOWING COMPLIANCE WITH THE 2017 FBC-ACCESSIBILITY CODE
 SECTION CHECK WRITING SURFACES. 2017 ACCESS. CODE
 904.3.3 CHECK WRITING SURFACES.
 ? WHERE PROVIDED, CHECK WRITING SURFACES SHALL COMPLY
 WITH 902.3. 902.3HEIGHT.
 THE TOPS OF WORK SURFACES SHALL BE 28 INCHES (710 MM)
 MINIMUM AND 34 INCHES (865 MM) MAXIMUM ABOVE THE FINISH
 FLOOR OR GROUND.
  
 904.4 SALES AND SERVICE COUNTERS. SALES COUNTERS AND
 SERVICE COUNTERS SHALL COMPLY WITH 904.4.1 OR 904.4.2.
 THE ACCESSIBLE PORTION OF THE COUNTER TOP SHALL EXTEND
 THE SAME DEPTH AS THE SALES OR SERVICE COUNTER TOP.
  
 4) ZONING HOLD ON PERMIT, NEW ROOF TOP MECHANICAL
 EQUIPMENT MUST BE SCREENED. SHOW COMPLIANCE WITH
 2017 FBC-B 1509.6 MECHANICAL EQUIPMENT SCREENS.
 MECHANICAL EQUIPMENT SCREENS SHALL BE CONSTRUCTED OF
 THE MATERIALS SPECIFIED FOR THE EXTERIOR WALLS IN
 ACCORDANCE WITH THE TYPE OF CONSTRUCTION OF THE
 BUILDING. WHERE THE FIRE SEPARATION DISTANCE IS GREATER
 THAN 5 FEET (1524 MM), MECHANICAL EQUIPMENT SCREENS
 SHALL NOT BE REQUIRED TO COMPLY WITH THE
 FIRE-RESISTANCE RATING REQUIREMENTS.
  
  1509.6.1 HEIGHT LIMITATIONS. MECHANICAL EQUIPMENT
 SCREENS SHALL NOT EXCEED 18 FEET (5486 MM) IN HEIGHT
 ABOVE THE ROOF DECK, AS MEASURED TO THE HIGHEST POINT
 ON THE MECHANICAL EQUIPMENT SCREEN. EXCEPTION: WHERE
 LOCATED ON BUILDINGS OF TYPE IA CONSTRUCTION, THE
 HEIGHT OF MECHANICAL EQUIPMENT SCREENS SHALL NOT BE
 LIMITED.
  
  1509.6.4 EQUIPMENT AND APPLIANCES ON ROOFS OR ELEVATED
 STRUCTURES.
 WHERE EQUIPMENT AND APPLIANCES REQUIRING ACCESS ARE
 INSTALLED ON ROOFS OR ELEVATED STRUCTURES AT A HEIGHT
 EXCEEDING 16 FEET (4877 MM), SUCH ACCESS SHALL BE
 PROVIDED BY A PERMANENT APPROVED MEANS OF ACCESS, THE
 EXTENT OF WHICH SHALL BE FROM GRADE OR FLOOR LEVEL TO
 THE EQUIPMENT AND APPLIANCES? LEVEL SERVICE SPACE. SUCH
 ACCESS SHALL NOT REQUIRE CLIMBING OVER OBSTRUCTIONS
 GREATER THAN 30 INCHES HIGH OR WALKING ON ROOFS HAVING
 A SLOPE GREATER THAN 4 UNITS VERTICAL IN 12 UNITS
 HORIZONTAL (33-PERCENT SLOPE).
 PERMANENT LADDERS INSTALLED TO PROVIDE THE REQUIRED
 ACCESS
  
 5) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 A THOROUGH REVIEW OF THE PLANS COULD NOT HAPPEN SINCE
 THERE WAS A GREAT DEFICIENCY IN PLANS AND REQUIRED
 DOCUMENTATION. WITH THE NEXT PLAN REVIEW CYCLE THERE
 MAYBE ADDITIONAL REVIEW COMMENTS BECAUSE OF NEW PLANS
 AND INFORMATION LACKING UNDER THE PRIOR REVIEW.
  
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717 / FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2018-11-19 Cont ID  
Sent By pvalenti Date 2018-11-21 Time 13:39 Rev Time 0.00
Received By jpearson Date 2018-11-19 Time 15:51 Sent To B
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2018-10-07 Cont ID  
Sent By jpearson Date 2018-10-07 Time 16:06 Rev Time 0.00
Received By jpearson Date 2018-10-07 Time 16:06 Sent To  
Notes
2018-10-07 16:06:43CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. THE NEC AND FBC SPECIFIED FOR DESIGN IS NOT THE
 CURRENT CODE. PROVIDE CORRECTION. FBC PREFACE (ALSO SEE
 CURRENT CODES ABOVE)
 2. ALL RECEPTACLE OUTLETS IN KITCHEN/FOOD PREP AREAS
 SHALL BE GFCI PROTECTED. PROVIDE CORRECTION. NEC
 210.8(B)(2)
 3. VALUE FOR WORK STATED ON PERMIT APPLICATION APPEARS
 LOW. PROVIDE COPY OF SIGNED CONTRACT WITH SCOPE AND
 VALUE OF WORK, TO INCLUDE ALL MATERIALS AND LABOR. THIS
 IS FOR TOTAL PROJECT, NOT JUST ELECTRICAL. FBC 109.3
 4. ADDRESS ON PLAN IS DIFFERENT THAN ADDRES ON PERMIT
 APPLICAITON. CORRECT DISCREPANCY USING CORRECT ADDRESS.
 WPB FBC 107.2.1
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD
 SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2018-09-28 Cont ID  
Sent By pleduc Date 2018-09-28 Time   Rev Time 0.00
Received By pleduc Date 2018-09-28 Time 11:57 Sent To I
Notes
2018-09-28 12:06:19THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 PLEASE CONSIDER THE FOLLOWING AS PROVISO:
  
 THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED
 AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE
 PROVISO COMMENTS WILL RESULT IN A FAILED FIRE
 INSPECTION.
  
  
 1) THE SPACE BETWEEN THE NEW HOSTESS STAND AND THE NEW
 BOOTH DOES NOT HAVE ADIMENSION INDICATED. THIS AREA IS
 AN EGRESS TRAVEL PATH.
  
 THIS DIMENSION SHALL NOT BE LESS THAN 36" PER NFPA 101,
 CHAPTER 7, MEANS OF EGRESS.
  
 7.3.4 MINIMUM WIDTH.
 7.3.4.1 THE WIDTH OF ANY MEANS OF EGRESS, UNLESS
 OTHERWISE
 PROVIDED IN 7.3.4.1.1 THROUGH 7.3.4.1.3, SHALL BE AS
 FOLLOWS:
 (1) NOT LESS THAN THAT REQUIRED FOR A GIVEN EGRESS
 COMPONENT IN
 THIS CHAPTER OR CHAPTERS 11 THROUGH 43
 (2) NOT LESS THAN 36 IN. (915 MM) WHERE ANOTHER PART OF
 THIS
 CHAPTER AND CHAPTERS 11 THROUGH 43 DO NOT SPECIFY A
 MINIMUM WIDTH
  
  
  
 2) THERE IS AN INCORRECT REFERENCE TO THE CURRENT
 FLORIDA FIRE PREVENTION CODE; 2014 5TH EDITION.
  
 THE PROPOSED PROJECT SHALL COMPLY WITH CURRENT FFPC ;
 2017, 6TH EDITION.
  
 PLEASE ENSURE COMPLAINCE AND UPDATE YOUR REFERENCES
 ACCORDINGLY.
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2018-11-21 Cont ID  
Sent By pvalenti Date 2018-11-21 Time 13:39 Rev Time 0.00
Received By pvalenti Date 2018-11-16 Time 13:57 Sent To I
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-11-05 Cont ID  
Sent By ccole Date 2018-11-05 Time 11:07 Rev Time 0.00
Received By ccole Date 2018-09-25 Time 10:04 Sent To  
Notes
2018-09-27 10:04:18B19

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status N Date 2018-11-05 Cont ID  
Sent By jwitmer Date 2018-11-05 Time 10:56 Rev Time 0.00
Received By jwitmer Date 2018-11-05 Time 10:56 Sent To  
Notes
2018-11-05 10:57:14NOT REQUIRED, I SPOKE WITH MICHELE OVER AT PBC IMPACT
 FEE OFFICE.
 JW

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2018-11-05 Cont ID  
Sent By ccole Date 2018-11-05 Time 11:06 Rev Time 0.00
Received By ccole Date 2018-11-05 Time 11:06 Sent To I
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2018-10-17 Cont ID  
Sent By tklarge Date 2018-10-17 Time 06:29 Rev Time 0.00
Received By tklarge Date 2018-10-17 Time 06:10 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2018-10-30 Cont ID  
Sent By eschneid Date 2018-10-30 Time 14:24 Rev Time 0.25
Received By eschneid Date 2018-10-30 Time 14:24 Sent To  
Notes
***NONE***