| 2018-10-05 14:39:26 | 1ST REVIEW FBC-2017 MECHANICAL |
| | REVISION #18091057 |
| | PERMIT #18030167 |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FBC R- FLORIDA RESIDENTIAL CODE SIXTH EDITION 2017 |
| | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| | 2017 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) SHEET MEP-1: LABEL THE DIFFUSERS AND RETURNS USING |
| | THE DEVICES SHOWN IN THE AIR DISTRIBUTION SCHEDULE, AND |
| | PROVIDE THE SUPPLY AND RETURN CFMS AT EACH LOCATION- |
| | SECTION 603.1 FBC M. |
| | |
| | 2) MEP-1: PROVIDE AN INSTALLATION DETAIL FOR THE NEW |
| | FIRE DAMPER IN THE RETURN AND INDICATE HOW ACCESS WILL |
| | BE PROVIDED- SECTIONS 607.4 & 607.5.2 FBC M. A) SUBMIT |
| | SPECS FOR THE DAMPER- SECTION 607.2 FBC M. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE |
| | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND |
| | KEEP THEM WITH THE SUBMITTALS |
| | |