Plan Review Details - Permit 18091037
Plan Review Stops For Permit 18091037
Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2018-11-29 Cont ID  
Sent By tklarge Date 2018-11-29 Time 06:53 Rev Time 0.00
Received By tklarge Date 2018-11-29 Time 06:53 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-09-28 Cont ID  
Sent By gjohnson Date 2018-09-28 Time 10:27 Rev Time 0.00
Received By gjohnson Date 2018-09-24 Time 13:40 Sent To  
Notes
2018-09-26 13:40:14REVISION ROUTED TO GJOHNSON

Review Stop P PLUMBING
Rev No 2 Status P Date 2018-11-29 Cont ID  
Sent By tklarge Date 2018-11-29 Time 06:53 Rev Time 0.00
Received By tklarge Date 2018-11-29 Time 06:53 Sent To I
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2018-09-28 Cont ID  
Sent By gjohnson Date 2018-09-28 Time 10:02 Rev Time 0.00
Received By gjohnson Date 2018-09-28 Time 10:02 Sent To  
Notes
2018-09-28 10:06:091ST REVIEW:
 2017 FLORIDA BUILDING CODE 6TH EDITION
 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH
 EDITION
  
 PLUMBING COMMENTS:
  
 1. THE 2" VENT TERMINAL EXTENDING THROUGH THE WALL
 SHALL TERMINATE AT A POINT NOT LESS THAN 10 FEET FROM A
 LOT LINE AND NOT LESS THAN 10 FEET ABOVE AVERAGE GROUND
 LEVEL. VENT TERMINALS SHALL NOT TERMINATE UNDER THE
 OVERHANG OF A STRUCTURE WITH SOFFIT VENTS. SIDE WALL
 VENT TERMINALS SHALL BE PROTECTED TO PREVENT BIRDS OR
 RODENTS FROM ENTERING OR BLOCKING THE VENT OPENING. PER
 FBC PL 903.6
  
 2. BEING THAT THIS BUILDING IS OVER 4 FLOORS IN ORDER
 TO USE AIR ADMITTANCE VALVES MORE THAN FOUR BRANCH
 INTERVALS FROM THE TOP OF THE STACK, THE HORIZONTAL
 BRANCH SHALL BE PROVIDED WITH A RELIEF VENT THAT SHALL
 CONNECT TO A VENT STACK OR STACK VENT, OR EXTEND
 OUTDOORS TO THE OPEN AIR. PER FBC PL 918.3.1
  
 3. THE FLOOR DRAINS REQUIRE A DRY VENT CONNECTION PER
 FBC PL 915.2.3
  
 4. THE SERVICE SINK IS NOT VENTED PROPERLY PER FBC PL
 901.2.1
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
  
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  