| 2018-09-28 10:06:09 | 1ST REVIEW: |
| | 2017 FLORIDA BUILDING CODE 6TH EDITION |
| | 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION |
| | 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH |
| | EDITION |
| | 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION |
| | 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION |
| | 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH |
| | EDITION |
| | 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH |
| | EDITION |
| | |
| | PLUMBING COMMENTS: |
| | |
| | 1. THE 2" VENT TERMINAL EXTENDING THROUGH THE WALL |
| | SHALL TERMINATE AT A POINT NOT LESS THAN 10 FEET FROM A |
| | LOT LINE AND NOT LESS THAN 10 FEET ABOVE AVERAGE GROUND |
| | LEVEL. VENT TERMINALS SHALL NOT TERMINATE UNDER THE |
| | OVERHANG OF A STRUCTURE WITH SOFFIT VENTS. SIDE WALL |
| | VENT TERMINALS SHALL BE PROTECTED TO PREVENT BIRDS OR |
| | RODENTS FROM ENTERING OR BLOCKING THE VENT OPENING. PER |
| | FBC PL 903.6 |
| | |
| | 2. BEING THAT THIS BUILDING IS OVER 4 FLOORS IN ORDER |
| | TO USE AIR ADMITTANCE VALVES MORE THAN FOUR BRANCH |
| | INTERVALS FROM THE TOP OF THE STACK, THE HORIZONTAL |
| | BRANCH SHALL BE PROVIDED WITH A RELIEF VENT THAT SHALL |
| | CONNECT TO A VENT STACK OR STACK VENT, OR EXTEND |
| | OUTDOORS TO THE OPEN AIR. PER FBC PL 918.3.1 |
| | |
| | 3. THE FLOOR DRAINS REQUIRE A DRY VENT CONNECTION PER |
| | FBC PL 915.2.3 |
| | |
| | 4. THE SERVICE SINK IS NOT VENTED PROPERLY PER FBC PL |
| | 901.2.1 |
| | |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| | THE PREVIOUSLY REVIEWED SHEETS. |
| | |
| | |
| | |