| 2018-10-01 12:42:52 | PERMIT # 18091026 |
| | REVIEW COMMENTS - FIRE DEPARTMENT |
| | |
| | APPROVED PROVISO: |
| | |
| | 1) THE DINING TENTS, SPECIFICALLY THE 40 X100 TENT |
| | SHALL HAVE THE SEATING ARRANGED IN A MANNER THAT |
| | COMPLIES WITH THE AISLE AND AISLEWAY REQUIREMENTS AS |
| | LISTED UNDER NFPA 101: 12.2.5 (ARRANGEMENT OF MEANS OF |
| | EGRESS). |
| | |
| | 2) THE OCCUPANT LOAD FOR THE 40 X 100 TENT SHALL COMPLY |
| | WITH THE OCCUPANT LOAD FACTOR AS LISTED UNDER NFPA 101: |
| | CHAPTER 7, TABLE 7.3.1.2. MORE SPECIFICALLY, ASSEMBLY |
| | USE: LESS CONCENTRATED USE, WITHOUT FIXED SEATING - 15 |
| | SQ FT/PERSON. |
| | |
| | 3) PROVIDE PORTABLE FIRE EXTINGUISHERS. EXTINGUISHERS |
| | SHALL HAVE A MINIMUM RATING OF 2A:10BC AND SHALL BE |
| | TAGGED BY A LICENSED FIRE EXTINGUISHER COMPANY. TRAVEL |
| | DISTANCE TO EXTINGUISHERS SHALL NOT EXCEED 75 FEET. |
| | PROVIDE TYPE K EXTINGUISHERS WHEN COOKING WITH GREASE |
| | OR WHEN PRODUCING SMOKE OR GREASE-LADEN VAPORS. |
| | |
| | 4) TENTS SHALL BE LOCATED AT LEAST 10 FEET AWAY FROM |
| | BUILDING STRUCTURES. |
| | |
| | 5) TENT SHALL BE OF THE OPEN AREA/NO SIDEWALL TYPE, |
| | OTHERWISE EMERGENCY LIGHTING AND ILLUMINATED EXIT SIGNS |
| | ARE REQUIRED FOR TENTS EXCEEDING 1,200 SQUARE FEET. |
| | |
| | 6) POST WEATHERPROOF NO SMOKING SIGNS IN CONSPICUOUS |
| | LOCATIONS. |
| | |
| | 7) GENERATORS AND OTHER INTERNAL COMBUSTION POWER |
| | SOURCES SHALL BE SEPARATED FROM TENTS BY A MINIMUM OF 5 |
| | FEET AND SHALL BE PROTECTED FROM CONTACT BY FENCING OR |
| | ENCLOSURE. |
| | |
| | 8) A FIRE INSPECTION CAN AND MAY BE CONDUCTED AFTER |
| | SET-UP OF THE VENUE. |
| | |
| | |
| | SUE ELLEN CALDERON |
| | ASSISTANT FIRE MARSHAL |
| | WEST PALM BEACH FIRE RESCUE |
| | [email protected] |
| | |