| Plan Review Stops For Permit 18091017 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
4 |
Status |
P |
Date |
2019-03-07 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2019-03-07 |
Time |
12:12 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2019-03-07 |
Time |
12:12 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
F |
Date |
2019-02-16 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2019-02-16 |
Time |
11:48 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2019-02-16 |
Time |
11:48 |
Sent To |
|
|
| Notes |
| 2019-02-16 11:51:40 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6724 | | | | | | FBC = FLORIDA BUILDING CODE, 5TH EDITION (2014) | | | FBC B = FBC BUILDING | | | FBC R = FBC RESIDENTIAL | | | FBC EB = FBC EXISTING BUILDING | | | FBC A = FBC ACCESSIBILITY | | | FBC EC = FBC ENERGY CONSERVATION | | | | | | 2. FROM PREVIOUS REVIEWS: AS THE PROPOSED FOUNTAIN | | | APPEARS TO BE DIRECTLY AGAINST THE BUILDING, ARCHITECT | | | AND ENGINEER ARE TO VERIFY THAT THIS LOCATION HAS NO | | | CONFLICTS, FBC B CHAPTER 16. | | | | | | 3RD REVIEW, NOT ADDRESSED. HAVE ARCHITECT OR ENGINEER | | | PROVIDE A LETTER OR SHOP DRAWING REVIEW STAMP TO SHOW | | | THAT THEY HAVE VERIFIED THAT YOUR PLAN IS ACCEPTABLE TO | | | THEM. THIS MAY BE SENT TO ME VIA EMAIL. | | | | | | | | | | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2018-12-08 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2018-12-08 |
Time |
17:46 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2018-12-08 |
Time |
17:44 |
Sent To |
|
|
| Notes |
| 2018-12-08 17:47:36 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6724 | | | | | | FBC = FLORIDA BUILDING CODE, 5TH EDITION (2014) | | | FBC B = FBC BUILDING | | | FBC R = FBC RESIDENTIAL | | | FBC EB = FBC EXISTING BUILDING | | | FBC A = FBC ACCESSIBILITY | | | FBC EC = FBC ENERGY CONSERVATION | | | | | | IT IS NOT CLEAR HOW COMMENTS WERE ADDRESSED. NO | | | RESPONSE LETTER PROVIDED. | | | | | | 1. OK | | | | | | 2. AS THE PROPOSED FOUNTAIN APPEARS TO BE DIRECTLY | | | AGAINST THE BUILDING, ARCHITECT AND ENGINEER ARE TO | | | VERIFY THAT THIS LOCATION HAS NO CONFLICTS, FBC B | | | CHAPTER 16. | | | | | | 3. FBC 107, THERE ARE REFERENCES TO "ARCHITECTURAL | | | PLANS". IT IS NOT CLEAR WHAT YOU ARE REFERRING TO; IF | | | THIS IS REFERRING TO AN ISSUED PERMIT, REVISE PLAN TO | | | STATE THIS. IF REFERRING TO ARCHITECTURAL PAGES WITHIN | | | THE SUBMITTAL, REVISE TO INCLUDE THE PAGE. | | | | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2018-10-30 |
|
|
Cont ID |
|
| Sent By |
gjohnson |
Date |
2018-10-30 |
Time |
10:31 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2018-10-30 |
Time |
10:31 |
Sent To |
|
|
| Notes |
| 2018-10-30 10:36:59 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6724 | | | | | | FBC = FLORIDA BUILDING CODE, 5TH EDITION (2014) | | | FBC B = FBC BUILDING | | | FBC R = FBC RESIDENTIAL | | | FBC EB = FBC EXISTING BUILDING | | | FBC A = FBC ACCESSIBILITY | | | FBC EC = FBC ENERGY CONSERVATION | | | | | | 1. FBC 107, PLANS ARE NOT CLEARLY LEGIBLE. | | | | | | 2. AS THE PROPOSED FOUNTAIN APPEARS TO BE DIRECTLY | | | AGAINST THE BUILDING, ARCHITECT AND ENGINEER ARE TO | | | VERIFY THAT THIS LOCATION HAS NO CONFLICTS, FBC B | | | CHAPTER 16. | | | | | | 3. FBC 107, THERE ARE REFERENCES TO "ARCHITECTURAL | | | PLANS". IT IS NOT CLEAR WHAT YOU ARE REFERRING TO; IF | | | THIS IS REFERRING TO AN ISSUED PERMIT, REVISE PLAN TO | | | STATE THIS. IF REFERRING TO ARCHITECTURAL PAGES WITHIN | | | THE SUBMITTAL, REVISE TO INCLUDE THE PAGE. | | 2018-10-30 10:24:32 | | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
P |
Date |
2019-02-13 |
|
|
Cont ID |
|
| Sent By |
jpearson |
Date |
2019-02-13 |
Time |
09:33 |
Rev Time |
0.00 |
| Received By |
jpearson |
Date |
2019-02-13 |
Time |
09:33 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
F |
Date |
2018-11-14 |
|
|
Cont ID |
|
| Sent By |
jpearson |
Date |
2018-11-14 |
Time |
11:14 |
Rev Time |
0.00 |
| Received By |
jpearson |
Date |
2018-11-14 |
Time |
11:14 |
Sent To |
|
|
| Notes |
| 2018-11-14 11:14:21 | CODES IN EFFECT: | | | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION | | | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 | | | 6TH ED, CHAPTER 1. | | | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 | | | 6TH EDITION | | | FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017 | | | 6TH EDITION | | | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION | | | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE | | | FS = FLORIDA STATUTES | | | | | | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | | | 1. SHOW LOCATION ON PLAN OF SR SMITH ILLUMINATORS, | | | WHICH ACCORDING TO MANUFACTURERS DIRECTIOINS SHOULD BE | | | MOUNTED AT LEAST 5 FEET FROM WATER. NEC 110.3; WPB FBC | | | 107.2.1 | | | 2. PROVIDE EXTERIOR LIGHTING CONTROLS FOR LIGHTS. FBC | | | EC C05.2.5 | | | 3. PROVIDE PANEL SCHEDULE SHOWING WIRE AND BREAKER | | | SIZE, AND GFCI PROTECITON WHERE REQUIRED. NEC 210.8, | | | 210.19, 210.20, 215.5, 408.4 | | | | | | END OF COMMENTS. | | | | | | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN | | | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES | | | INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY | | | REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED | | | SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD | | | SHEETS. | | | | | | SINCERELY, | | | | | | JOHN PEARSON | | | ELECTRICAL PLANS EXAMINER | | | 561-805-6746 | | | [email protected] | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2018-10-08 |
|
|
Cont ID |
|
| Sent By |
jpearson |
Date |
2018-10-08 |
Time |
09:25 |
Rev Time |
0.00 |
| Received By |
jpearson |
Date |
2018-10-08 |
Time |
09:25 |
Sent To |
|
|
| Notes |
| 2018-10-08 09:25:26 | CODES IN EFFECT: | | | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION | | | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 | | | 6TH ED, CHAPTER 1. | | | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 | | | 6TH EDITION | | | FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017 | | | 6TH EDITION | | | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION | | | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE | | | FS = FLORIDA STATUTES | | | | | | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | | | 1. A REVIEW IS NOT POSSIBLE AT THIS TIME DUE TO THE | | | QUALITY OF THE PLAN PROVIDED. MUCH OF THE INFORMATION | | | IS CORRUPTED AND ILLEGIBLE. PER WPB FBC 107.2.1: | | | INFORMATION ON CONSTRUCTION DOCUMENTS. CONSTRUCTION | | | DOCUMENTS SHALL BE DIMENSIONED AND DRAWN UPON SUITABLE | | | MATERIAL. ELECTRONIC MEDIA DOCUMENTS SHALL BE SUBMITTED | | | WHEN APPROVED BY THE BUILDING OFFICIAL. CONSTRUCTION | | | DOCUMENTS SHALL BE OF SUFFICIENT CLARITY TO INDICATE | | | THE LOCATION, NATURE AND EXTENT OF THE WORK PROPOSED | | | AND SHOW IN DETAIL THAT IT WILL CONFORM TO THE | | | PROVISIONS OF THIS CODE AND RELEVANT LAWS, ORDINANCES, | | | RULES AND REGULATIONS, AS DETERMINED BY THE BUILDING | | | OFFICIAL. SUCH DRAWINGS AND SPECIFICATIONS SHALL | | | CONTAIN INFORMATION, IN THE FORM OF NOTES OR OTHERWISE, | | | AS TO THE QUALITY OF MATERIALS, WHERE QUALITY IS | | | ESSENTIAL TO CONFORMITY WITH THE TECHNICAL CODES. SUCH | | | INFORMATION SHALL BE SPECIFIC, AND THE TECHNICAL CODES | | | SHALL NOT BE CITED AS A WHOLE OR IN PART, NOR SHALL THE | | | TERM "LEGAL" OR ITS EQUIVALENT BE USED AS A SUBSTITUTE | | | FOR SPECIFIC INFORMATION. ALL INFORMATION, DRAWINGS, | | | SPECIFICATIONS AND ACCOMPANYING DATA SHALL BEAR THE | | | NAME AND SIGNATURE OF THE PERSON RESPONSIBLE FOR THE | | | DESIGN. PROVIDE CORRECTION. | | | | | | END OF COMMENTS. | | | | | | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN | | | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES | | | INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY | | | REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED | | | SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD | | | SHEETS. | | | | | | SINCERELY, | | | | | | JOHN PEARSON | | | ELECTRICAL PLANS EXAMINER | | | 561-805-6746 | | | [email protected] | | | |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
4 |
Status |
N |
Date |
2019-03-11 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2019-03-11 |
Time |
08:20 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2019-03-07 |
Time |
14:03 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2019-02-21 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2019-02-21 |
Time |
13:28 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2019-01-24 |
Time |
11:00 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2018-12-13 |
|
|
Cont ID |
|
| Sent By |
lmarchan |
Date |
2018-12-13 |
Time |
08:09 |
Rev Time |
0.00 |
| Received By |
lmarchan |
Date |
2018-11-02 |
Time |
10:04 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2018-11-02 |
|
|
Cont ID |
|
| Sent By |
lmarchan |
Date |
2018-11-02 |
Time |
15:35 |
Rev Time |
0.00 |
| Received By |
lmarchan |
Date |
2018-09-26 |
Time |
10:57 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
3 |
Status |
P |
Date |
2019-03-11 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2019-03-11 |
Time |
08:20 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2019-03-11 |
Time |
07:39 |
Sent To |
I |
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
P |
Date |
2018-12-12 |
|
|
Cont ID |
|
| Sent By |
gjohnson |
Date |
2018-12-12 |
Time |
16:24 |
Rev Time |
0.00 |
| Received By |
gjohnson |
Date |
2018-12-12 |
Time |
16:24 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2018-10-30 |
|
|
Cont ID |
|
| Sent By |
gjohnson |
Date |
2018-10-30 |
Time |
10:25 |
Rev Time |
0.00 |
| Received By |
gjohnson |
Date |
2018-10-30 |
Time |
10:25 |
Sent To |
|
|
| Notes |
| 2018-10-30 10:25:33 | 1ST REVIEW: | | | 2017 FLORIDA BUILDING CODE 6TH EDITION | | | 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION | | | 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH | | | EDITION | | | 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION | | | 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION | | | 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH | | | EDITION | | | 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH | | | EDITION | | | | | | PLUMBING COMMENTS: | | | | | | | | | 1. A REVIEW IS NOT POSSIBLE AT THIS TIME DUE TO THE | | | QUALITY OF THE PLAN PROVIDED. MUCH OF THE INFORMATION | | | IS CORRUPTED AND ILLEGIBLE. PER WPB FBC 107.2.1: | | | INFORMATION ON CONSTRUCTION DOCUMENTS. CONSTRUCTION | | | DOCUMENTS SHALL BE DIMENSIONED AND DRAWN UPON SUITABLE | | | MATERIAL. ELECTRONIC MEDIA DOCUMENTS SHALL BE SUBMITTED | | | WHEN APPROVED BY THE BUILDING OFFICIAL. CONSTRUCTION | | | DOCUMENTS SHALL BE OF SUFFICIENT CLARITY TO INDICATE | | | THE LOCATION, NATURE AND EXTENT OF THE WORK PROPOSED | | | AND SHOW IN DETAIL THAT IT WILL CONFORM TO THE | | | PROVISIONS OF THIS CODE AND RELEVANT LAWS, ORDINANCES, | | | RULES AND REGULATIONS, AS DETERMINED BY THE BUILDING | | | OFFICIAL. SUCH DRAWINGS AND SPECIFICATIONS SHALL | | | CONTAIN INFORMATION, IN THE FORM OF NOTES OR OTHERWISE, | | | AS TO THE QUALITY OF MATERIALS, WHERE QUALITY IS | | | ESSENTIAL TO CONFORMITY WITH THE TECHNICAL CODES. SUCH | | | INFORMATION SHALL BE SPECIFIC, AND THE TECHNICAL CODES | | | SHALL NOT BE CITED AS A WHOLE OR IN PART, NOR SHALL THE | | | TERM "LEGAL" OR ITS EQUIVALENT BE USED AS A SUBSTITUTE | | | FOR SPECIFIC INFORMATION. ALL INFORMATION, DRAWINGS, | | | SPECIFICATIONS AND ACCOMPANYING DATA SHALL BEAR THE | | | NAME AND SIGNATURE OF THE PERSON RESPONSIBLE FOR THE | | | DESIGN. PROVIDE CORRECTION. | | | | | | END OF COMMENTS. | | | | | | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN | | | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES | | | INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY | | | REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED | | | SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD | | | SHEETS. | | | | | | | | | GEORGE JOHNSON | | | PLUMBING PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | 561-805-6711 | | | [email protected] | | | |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
3 |
Status |
P |
Date |
2019-02-13 |
|
|
Cont ID |
|
| Sent By |
jpearson |
Date |
2019-02-13 |
Time |
09:34 |
Rev Time |
0.00 |
| Received By |
jpearson |
Date |
2019-02-13 |
Time |
09:34 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
2 |
Status |
F |
Date |
2018-12-08 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2018-12-08 |
Time |
17:48 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2018-12-08 |
Time |
17:48 |
Sent To |
|
|
| Notes |
| 2018-12-08 17:48:56 | SAMANTHA HILL | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6724 | | | | | | DIGITAL SIGNATURES ARE OK, ALL TRADES | | | NEW SHEETS SUBMITTED NEXT REVIEW CYCLE NEED | | | VERIFICATION |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
1 |
Status |
F |
Date |
2018-10-08 |
|
|
Cont ID |
|
| Sent By |
jpearson |
Date |
2018-10-08 |
Time |
08:24 |
Rev Time |
0.00 |
| Received By |
jpearson |
Date |
2018-10-08 |
Time |
08:24 |
Sent To |
|
|
| Notes |
| 2018-10-08 08:24:10 | PLAN IS REQUIRED TO BE SIGNED AND SEALED BY THE PERSON | | | RESPONSIBLE FOR THE DESIGN. A DIGITAL PLAN REQUIRES A | | | DIGITAL SIGNATURE. PROVIDE CORRECTION. WPB FBC 107.1; | | | FS 471/481 |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
3 |
Status |
P |
Date |
2019-02-19 |
|
|
Cont ID |
|
| Sent By |
aaponte |
Date |
2019-02-19 |
Time |
14:50 |
Rev Time |
0.00 |
| Received By |
aaponte |
Date |
2019-02-19 |
Time |
14:50 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
P |
Date |
2018-12-06 |
|
|
Cont ID |
|
| Sent By |
aaponte |
Date |
2018-12-06 |
Time |
09:33 |
Rev Time |
0.00 |
| Received By |
aaponte |
Date |
2018-12-06 |
Time |
09:33 |
Sent To |
|
|
| Notes |
| 2018-12-06 09:33:38 | PROVISO: FOUNTAIN LOCATION SHALL MATCH APPROVED MASTER | | | SITE PLAN. |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
P |
Date |
2018-11-02 |
|
|
Cont ID |
|
| Sent By |
aaponte |
Date |
2018-11-02 |
Time |
13:51 |
Rev Time |
0.00 |
| Received By |
aaponte |
Date |
2018-11-02 |
Time |
13:51 |
Sent To |
|
|
| Notes |
| 2018-11-02 13:52:04 | PROVISO: FOUNDATIN LOCATION SHALL MATCH APPROVED MASTER | | | SITE PLAN PERMIT. |
|
|