Plan Review Details - Permit 18091017
Plan Review Stops For Permit 18091017
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2019-03-07 Cont ID  
Sent By shill Date 2019-03-07 Time 12:12 Rev Time 0.00
Received By shill Date 2019-03-07 Time 12:12 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2019-02-16 Cont ID  
Sent By shill Date 2019-02-16 Time 11:48 Rev Time 0.00
Received By shill Date 2019-02-16 Time 11:48 Sent To  
Notes
2019-02-16 11:51:40****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 5TH EDITION (2014)
 FBC B = FBC BUILDING
 FBC R = FBC RESIDENTIAL
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
  
 2. FROM PREVIOUS REVIEWS: AS THE PROPOSED FOUNTAIN
 APPEARS TO BE DIRECTLY AGAINST THE BUILDING, ARCHITECT
 AND ENGINEER ARE TO VERIFY THAT THIS LOCATION HAS NO
 CONFLICTS, FBC B CHAPTER 16.
  
 3RD REVIEW, NOT ADDRESSED. HAVE ARCHITECT OR ENGINEER
 PROVIDE A LETTER OR SHOP DRAWING REVIEW STAMP TO SHOW
 THAT THEY HAVE VERIFIED THAT YOUR PLAN IS ACCEPTABLE TO
 THEM. THIS MAY BE SENT TO ME VIA EMAIL.
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2018-12-08 Cont ID  
Sent By shill Date 2018-12-08 Time 17:46 Rev Time 0.00
Received By shill Date 2018-12-08 Time 17:44 Sent To  
Notes
2018-12-08 17:47:36****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 5TH EDITION (2014)
 FBC B = FBC BUILDING
 FBC R = FBC RESIDENTIAL
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
  
 IT IS NOT CLEAR HOW COMMENTS WERE ADDRESSED. NO
 RESPONSE LETTER PROVIDED.
  
 1. OK
  
 2. AS THE PROPOSED FOUNTAIN APPEARS TO BE DIRECTLY
 AGAINST THE BUILDING, ARCHITECT AND ENGINEER ARE TO
 VERIFY THAT THIS LOCATION HAS NO CONFLICTS, FBC B
 CHAPTER 16.
  
 3. FBC 107, THERE ARE REFERENCES TO "ARCHITECTURAL
 PLANS". IT IS NOT CLEAR WHAT YOU ARE REFERRING TO; IF
 THIS IS REFERRING TO AN ISSUED PERMIT, REVISE PLAN TO
 STATE THIS. IF REFERRING TO ARCHITECTURAL PAGES WITHIN
 THE SUBMITTAL, REVISE TO INCLUDE THE PAGE.
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2018-10-30 Cont ID  
Sent By gjohnson Date 2018-10-30 Time 10:31 Rev Time 0.00
Received By shill Date 2018-10-30 Time 10:31 Sent To  
Notes
2018-10-30 10:36:59****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 5TH EDITION (2014)
 FBC B = FBC BUILDING
 FBC R = FBC RESIDENTIAL
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
  
 1. FBC 107, PLANS ARE NOT CLEARLY LEGIBLE.
  
 2. AS THE PROPOSED FOUNTAIN APPEARS TO BE DIRECTLY
 AGAINST THE BUILDING, ARCHITECT AND ENGINEER ARE TO
 VERIFY THAT THIS LOCATION HAS NO CONFLICTS, FBC B
 CHAPTER 16.
  
 3. FBC 107, THERE ARE REFERENCES TO "ARCHITECTURAL
 PLANS". IT IS NOT CLEAR WHAT YOU ARE REFERRING TO; IF
 THIS IS REFERRING TO AN ISSUED PERMIT, REVISE PLAN TO
 STATE THIS. IF REFERRING TO ARCHITECTURAL PAGES WITHIN
 THE SUBMITTAL, REVISE TO INCLUDE THE PAGE.
2018-10-30 10:24:32 
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2019-02-13 Cont ID  
Sent By jpearson Date 2019-02-13 Time 09:33 Rev Time 0.00
Received By jpearson Date 2019-02-13 Time 09:33 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2018-11-14 Cont ID  
Sent By jpearson Date 2018-11-14 Time 11:14 Rev Time 0.00
Received By jpearson Date 2018-11-14 Time 11:14 Sent To  
Notes
2018-11-14 11:14:21CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. SHOW LOCATION ON PLAN OF SR SMITH ILLUMINATORS,
 WHICH ACCORDING TO MANUFACTURERS DIRECTIOINS SHOULD BE
 MOUNTED AT LEAST 5 FEET FROM WATER. NEC 110.3; WPB FBC
 107.2.1
 2. PROVIDE EXTERIOR LIGHTING CONTROLS FOR LIGHTS. FBC
 EC C05.2.5
 3. PROVIDE PANEL SCHEDULE SHOWING WIRE AND BREAKER
 SIZE, AND GFCI PROTECITON WHERE REQUIRED. NEC 210.8,
 210.19, 210.20, 215.5, 408.4
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD
 SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2018-10-08 Cont ID  
Sent By jpearson Date 2018-10-08 Time 09:25 Rev Time 0.00
Received By jpearson Date 2018-10-08 Time 09:25 Sent To  
Notes
2018-10-08 09:25:26CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. A REVIEW IS NOT POSSIBLE AT THIS TIME DUE TO THE
 QUALITY OF THE PLAN PROVIDED. MUCH OF THE INFORMATION
 IS CORRUPTED AND ILLEGIBLE. PER WPB FBC 107.2.1:
 INFORMATION ON CONSTRUCTION DOCUMENTS. CONSTRUCTION
 DOCUMENTS SHALL BE DIMENSIONED AND DRAWN UPON SUITABLE
 MATERIAL. ELECTRONIC MEDIA DOCUMENTS SHALL BE SUBMITTED
 WHEN APPROVED BY THE BUILDING OFFICIAL. CONSTRUCTION
 DOCUMENTS SHALL BE OF SUFFICIENT CLARITY TO INDICATE
 THE LOCATION, NATURE AND EXTENT OF THE WORK PROPOSED
 AND SHOW IN DETAIL THAT IT WILL CONFORM TO THE
 PROVISIONS OF THIS CODE AND RELEVANT LAWS, ORDINANCES,
 RULES AND REGULATIONS, AS DETERMINED BY THE BUILDING
 OFFICIAL. SUCH DRAWINGS AND SPECIFICATIONS SHALL
 CONTAIN INFORMATION, IN THE FORM OF NOTES OR OTHERWISE,
 AS TO THE QUALITY OF MATERIALS, WHERE QUALITY IS
 ESSENTIAL TO CONFORMITY WITH THE TECHNICAL CODES. SUCH
 INFORMATION SHALL BE SPECIFIC, AND THE TECHNICAL CODES
 SHALL NOT BE CITED AS A WHOLE OR IN PART, NOR SHALL THE
 TERM "LEGAL" OR ITS EQUIVALENT BE USED AS A SUBSTITUTE
 FOR SPECIFIC INFORMATION. ALL INFORMATION, DRAWINGS,
 SPECIFICATIONS AND ACCOMPANYING DATA SHALL BEAR THE
 NAME AND SIGNATURE OF THE PERSON RESPONSIBLE FOR THE
 DESIGN. PROVIDE CORRECTION.
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD
 SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2019-03-11 Cont ID  
Sent By rmcdouga Date 2019-03-11 Time 08:20 Rev Time 0.00
Received By rmcdouga Date 2019-03-07 Time 14:03 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2019-02-21 Cont ID  
Sent By shill Date 2019-02-21 Time 13:28 Rev Time 0.00
Received By shill Date 2019-01-24 Time 11:00 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2018-12-13 Cont ID  
Sent By lmarchan Date 2018-12-13 Time 08:09 Rev Time 0.00
Received By lmarchan Date 2018-11-02 Time 10:04 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-11-02 Cont ID  
Sent By lmarchan Date 2018-11-02 Time 15:35 Rev Time 0.00
Received By lmarchan Date 2018-09-26 Time 10:57 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status P Date 2019-03-11 Cont ID  
Sent By rmcdouga Date 2019-03-11 Time 08:20 Rev Time 0.00
Received By rmcdouga Date 2019-03-11 Time 07:39 Sent To I
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2018-12-12 Cont ID  
Sent By gjohnson Date 2018-12-12 Time 16:24 Rev Time 0.00
Received By gjohnson Date 2018-12-12 Time 16:24 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2018-10-30 Cont ID  
Sent By gjohnson Date 2018-10-30 Time 10:25 Rev Time 0.00
Received By gjohnson Date 2018-10-30 Time 10:25 Sent To  
Notes
2018-10-30 10:25:331ST REVIEW:
 2017 FLORIDA BUILDING CODE 6TH EDITION
 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH
 EDITION
  
 PLUMBING COMMENTS:
  
  
 1. A REVIEW IS NOT POSSIBLE AT THIS TIME DUE TO THE
 QUALITY OF THE PLAN PROVIDED. MUCH OF THE INFORMATION
 IS CORRUPTED AND ILLEGIBLE. PER WPB FBC 107.2.1:
 INFORMATION ON CONSTRUCTION DOCUMENTS. CONSTRUCTION
 DOCUMENTS SHALL BE DIMENSIONED AND DRAWN UPON SUITABLE
 MATERIAL. ELECTRONIC MEDIA DOCUMENTS SHALL BE SUBMITTED
 WHEN APPROVED BY THE BUILDING OFFICIAL. CONSTRUCTION
 DOCUMENTS SHALL BE OF SUFFICIENT CLARITY TO INDICATE
 THE LOCATION, NATURE AND EXTENT OF THE WORK PROPOSED
 AND SHOW IN DETAIL THAT IT WILL CONFORM TO THE
 PROVISIONS OF THIS CODE AND RELEVANT LAWS, ORDINANCES,
 RULES AND REGULATIONS, AS DETERMINED BY THE BUILDING
 OFFICIAL. SUCH DRAWINGS AND SPECIFICATIONS SHALL
 CONTAIN INFORMATION, IN THE FORM OF NOTES OR OTHERWISE,
 AS TO THE QUALITY OF MATERIALS, WHERE QUALITY IS
 ESSENTIAL TO CONFORMITY WITH THE TECHNICAL CODES. SUCH
 INFORMATION SHALL BE SPECIFIC, AND THE TECHNICAL CODES
 SHALL NOT BE CITED AS A WHOLE OR IN PART, NOR SHALL THE
 TERM "LEGAL" OR ITS EQUIVALENT BE USED AS A SUBSTITUTE
 FOR SPECIFIC INFORMATION. ALL INFORMATION, DRAWINGS,
 SPECIFICATIONS AND ACCOMPANYING DATA SHALL BEAR THE
 NAME AND SIGNATURE OF THE PERSON RESPONSIBLE FOR THE
 DESIGN. PROVIDE CORRECTION.
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD
 SHEETS.
  
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2019-02-13 Cont ID  
Sent By jpearson Date 2019-02-13 Time 09:34 Rev Time 0.00
Received By jpearson Date 2019-02-13 Time 09:34 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status F Date 2018-12-08 Cont ID  
Sent By shill Date 2018-12-08 Time 17:48 Rev Time 0.00
Received By shill Date 2018-12-08 Time 17:48 Sent To  
Notes
2018-12-08 17:48:56SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 DIGITAL SIGNATURES ARE OK, ALL TRADES
 NEW SHEETS SUBMITTED NEXT REVIEW CYCLE NEED
 VERIFICATION

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2018-10-08 Cont ID  
Sent By jpearson Date 2018-10-08 Time 08:24 Rev Time 0.00
Received By jpearson Date 2018-10-08 Time 08:24 Sent To  
Notes
2018-10-08 08:24:10PLAN IS REQUIRED TO BE SIGNED AND SEALED BY THE PERSON
 RESPONSIBLE FOR THE DESIGN. A DIGITAL PLAN REQUIRES A
 DIGITAL SIGNATURE. PROVIDE CORRECTION. WPB FBC 107.1;
 FS 471/481

Review Stop Z ZONING
Rev No 3 Status P Date 2019-02-19 Cont ID  
Sent By aaponte Date 2019-02-19 Time 14:50 Rev Time 0.00
Received By aaponte Date 2019-02-19 Time 14:50 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date 2018-12-06 Cont ID  
Sent By aaponte Date 2018-12-06 Time 09:33 Rev Time 0.00
Received By aaponte Date 2018-12-06 Time 09:33 Sent To  
Notes
2018-12-06 09:33:38PROVISO: FOUNTAIN LOCATION SHALL MATCH APPROVED MASTER
 SITE PLAN.

Review Stop Z ZONING
Rev No 1 Status P Date 2018-11-02 Cont ID  
Sent By aaponte Date 2018-11-02 Time 13:51 Rev Time 0.00
Received By aaponte Date 2018-11-02 Time 13:51 Sent To  
Notes
2018-11-02 13:52:04PROVISO: FOUNDATIN LOCATION SHALL MATCH APPROVED MASTER
 SITE PLAN PERMIT.