Plan Review Details - Permit 18090994
Plan Review Stops For Permit 18090994
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2018-12-08 Cont ID  
Sent By shill Date 2018-12-08 Time 18:26 Rev Time 0.00
Received By shill Date 2018-12-08 Time 18:26 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2018-10-30 Cont ID  
Sent By jwitmer Date 2018-10-30 Time 14:17 Rev Time 0.00
Received By jwitmer Date 2018-10-30 Time 14:00 Sent To  
Notes
2018-10-30 14:14:402017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 18090994
 ADD: 2465 MERCER AVE., SUITE:A-205
 CONT: SEARCH CONSTRUCTION
 TEL: 561-346-8191
 E-MAIL: [email protected]
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: TUES. OCT. 30/ 2018
 ACTION: DENIED
  
 1) ADDITIONAL INFORMATION IS REQUIRED MISSING FROM THE
 FLOOR/ LIFE SAFETY PLAN. 107.3.5 MINIMUM PLAN REVIEW
 CRITERIA FOR BUILDINGS. THE EXAMINATION OF THE
 DOCUMENTS BY THE BUILDING OFFICIAL SHALL INCLUDE THE
 FOLLOWING MINIMUM CRITERIA AND DOCUMENTS:
 1A) THE MINIMUM BUILDING TYPE? 2017 FBC-B TABLE 504.3 &
 504.4.
 1B) STORIES THIS BUILDING HAS? 2017 FBC-B TABLE 504.3 &
 504.4
 1C) THE ACTUAL SQUARE FOOTAGE FOR EACH STORY? 2017
 FBC-B TABLE 504.3 & 504.4
 1D) IS THE BUILDING FIRE SPRINKLERED? 2017 FBC-B TABLE
 504.3 & 504.4
 1E) SQUARE FOOTAGE OF THE TENANT SPACE? 2017 FBC-B
 TABLE 504.3 & 504.4
  
 2) THE PLANS DOES NOT INDICATE IF THE LOCATION OF THE
 WATER CLOSET IS A NEW LOCATION REQUIRING A NEW FLOOR
 PENETRATION AND FIRE RATED FLOOR ASSEMBLIES PER 2017
 FBC-B 714.4 HORIZONTAL ASSEMBLIES. PENETRATIONS OF A
 FIRE-RESISTANCE-RATED FLOOR, FLOOR/CEILING ASSEMBLY OR
 THE CEILING MEMBRANE OF A ROOF/CEILING ASSEMBLY NOT
 REQUIRED TO BE ENCLOSED IN A SHAFT BY SECTION 712.1
 SHALL BE PROTECTED IN ACCORDANCE WITH SECTIONS 714.4.1
 THROUGH 714.4.4.
  
 3) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2018-12-07 Cont ID  
Sent By jpearson Date 2018-12-07 Time 14:53 Rev Time 0.00
Received By jpearson Date 2018-12-07 Time 14:10 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2018-10-05 Cont ID  
Sent By jpearson Date 2018-10-05 Time 12:10 Rev Time 0.00
Received By jpearson Date 2018-10-05 Time 11:51 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2018-11-28 Cont ID  
Sent By scaldero Date 2018-11-28 Time 10:51 Rev Time 0.00
Received By scaldero Date 2018-11-28 Time 10:51 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2018-09-26 Cont ID  
Sent By scaldero Date 2018-09-26 Time 10:57 Rev Time 0.00
Received By scaldero Date 2018-09-26 Time 10:57 Sent To  
Notes
2018-09-26 10:57:56PERMIT # 18090994
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 APPROVED PROVISO:
  
 1) UPDATE THE CODE LIST TO REFERENCE THE 6TH EDITION OF
 THE FLORIDA FIRE PREVENTION CODE WHICH CONTAINS THE
 2015 EDITION OF BOTH NFPA 1 AND NFPA 101 WITH FLORIDA
 AMENDMENTS.
  
 2) SEPARATE PLANS AND PERMITS ARE REQUIRED FOR THE
 INSTALLATION OR MODIFICATION OF THE FIRE SPRINKLER
 SYSTEM AND/OR FIRE ALARM SYSTEM.
  
  
 SUE ELLEN CALDERON
 ASSISTANT FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date   Cont ID  
Sent By   Date 2019-01-11 Time   Rev Time 0.00
Received By lmarchan Date 2019-01-07 Time 11:38 Sent To  
Notes
2019-01-08 11:38:38RESUB ROUTED TO CCOLE

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2019-01-03 Cont ID  
Sent By jesmith Date 2019-01-03 Time 16:06 Rev Time 0.00
Received By jesmith Date 2018-11-20 Time 10:03 Sent To  
Notes
2018-11-21 10:03:27B32

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-10-30 Cont ID  
Sent By cpuell Date 2018-10-30 Time 16:29 Rev Time 0.00
Received By cpuell Date 2018-09-21 Time 11:27 Sent To  
Notes
2018-09-25 11:27:14B13

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2018-10-30 Time 14:17 Rev Time  
Received By   Date 2018-10-30 Time 14:00 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2019-01-11 Cont ID  
Sent By ccole Date 2019-01-11 Time 11:05 Rev Time 0.00
Received By ccole Date 2019-01-11 Time 11:05 Sent To I
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2018-12-13 Cont ID  
Sent By ccole Date 2018-12-13 Time 15:46 Rev Time 0.00
Received By ccole Date 2018-12-13 Time 15:38 Sent To  
Notes
2018-12-13 15:48:492ND REVIEW FBC-2017 MECHANICAL
 PERMIT #18090994
 12/13/2018
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 COMMENT #2 FROM THE 1ST REVIEW (PRINTED BELOW) STILL
 EXISTS- PLEASE COMPLY.
  
 2) THE PERSON WHO PREPARED THE ENERGY/GAUGE CALCULATION
 FORM AND THE BUILDING'S OWNER SHALL EACH SIGN AND DATE
 THE FORM ON THE CERTIFICATIONS PAGE- SECTION C103.1.1.2
 FBC EC
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2018-10-12 Cont ID  
Sent By ccole Date 2018-10-12 Time 15:32 Rev Time 0.00
Received By ccole Date 2018-10-12 Time 15:31 Sent To  
Notes
2018-10-12 15:55:381ST REVIEW FBC-2017 MECHANICAL
 PERMIT #18090994
 10/12/2018
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PROVIDE COOLING AND HEATING CALCULATIONS FOR THE NEW
 AC SYSTEM- SECTION C403.2.1 FBC-17 EC.
  
 2) THE PERSON WHO PREPARED THE ENERGY/GAUGE CALCULATION
 FORM AND THE BUILDING'S OWNER SHALL EACH SIGN AND DATE
 THE FORM ON THE CERTIFICATIONS PAGE- SECTION C103.1.1.2
 FBC EC
  
 3) SHEET A-3: PROVIDE MINIMUM VENTILATION CALCULATIONS
 FOR ALL ROOMS AND SPACES PER TABLE 403.3.1 FBC-17
 MECHANICAL. PROVIDE A SCHEDULE THAT INDICATES THE
 REQUIRED AND PROVIDED CFMS OF OUTDOOR AIR. PLEASE NOTE
 THAT THE AC EQUIPMENT SCHEDULE IS INDICATING 440 CFMS
 OF OUTSIDE AIR IS BEING PROVIDED WHICH SEEMS TO BE
 EXCESSIVE FOR THIS 1066 SF. OFFICE SPACE.
  
 4) A-3: THE AC EQUIPMENT SCHEDULE INDICATES COOLING AND
 HEATING CAPCITIES FOR THE SYSTEM THAT DON'T MATCH THE
 COMPLIANCE DATA IN THE ENERGY/GAUGE FORM. THE SCHEDULE
 INDICATES COOLING AT 30,136 BTUH HOWEVER THE ENERGY
 CALCS INDICATE 34,000 BTUH.
  
 5) THE AC EQUIPMENT SCHEDULE INDICATES THE TOTAL SUPPLY
 AIR FOR THE SYSTEM IS 671 CFMS, HOWEVER THE PLAN
 INDICATES 950 CFMS- PLEASE CORRECT.
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2019-01-03 Cont ID  
Sent By jesmith Date 2019-01-03 Time 16:05 Rev Time 0.00
Received By jesmith Date 2019-01-03 Time 16:01 Sent To  
Notes
2019-01-03 16:05:12APPROVED
 PLUMBING PROVISO
 1. ALL WORK PER CITY CODES SUBJECT TO FIELD INSPECTOR'S
 APPROVAL

Review Stop P PLUMBING
Rev No 1 Status F Date 2018-10-18 Cont ID  
Sent By jesmith Date 2018-10-18 Time 10:29 Rev Time 0.00
Received By jesmith Date 2018-10-18 Time 08:50 Sent To  
Notes
2018-10-18 09:37:17CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RES = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 FBC ACC = FLORIDA ACCESSIBILITY CODE 2017 6TH EDITION
 FBC EX = FLORIDA EXISTING BUILDING CODE 2017 6TH
 EDITION
 FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION
 FBC FG = FLORIDA FUEL GAS CODE 2017 6TH EDITION
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
 1ST REVIEW: DENIED
 PLUMBING COMMENTS:
  
 1. RE: A-3; HOT WATER REQUIRED PER FBC PL 607.1.
 PROVIDE TEMPERED WATER TO LAVATORY IN ACCORDANCE WITH
 FBC PL 416.5, 607.1.1 AND 607.1.2.
 A. SHOW LOCATION OF WATER HEATER ON PLAN. PROVIDE WATER
 HEATER SCHEDULE PER WPB FPC 107.3.5.1.3 (5). IF A
 STORAGE TYPE WATER HEATER IS SPECIFIED THEN INCLUDE
 THERMAL EXPANSION CONTROL DEVICE, T&P DISCHARGE(
 INCLUDING TERMINATION) AND WATER HEATER PAN AND DRAIN
 (INCLUDING TERMINATION)PER WPB FPC 107.2.1; COMPLY WITH
 FBC PL 607.3, 503.1, 504.1, 504.4, 504.4.1, 504.5,
 504.6, 504.7, 504.7.1 AND 504.7.2.
 B. PROVIDE SPEC FOR APPROVED WATER-TEMPERATURE LIMITING
 DEVICE THAT CONFORMS TO ASSE 1070 OR CSA B125.3 FOR
 LAVATORY.
 2. RE: A-3; PLUMBING RISER. SHOW CONNECTION TO SANITARY
 STACK AT WET COLUMN.
 3. RE: A-3; PLUMBING LAYOUT. SHOW CONNECTION TO
 SANITARY STACK AND LABEL AT WET COLUMN; ELIMINATE
 CONNECTION OR REFERENCE TO BUILDING SEWER.
 4. RE: A-3; PLUMBING NOTE 16. THE NOTE ALLUDES TO GAS
 PIPING. THERE IS NO PLAN SHOWING GAS PIPING AND NO
 REVIEW HAS BEEN MADE. IF THERE IS GAS PIPING, AN
 APPLICATION FOR GAS PERMIT MUST BE SUBMITTED ALONG WITH
 PLANS COMPLYING WITH FBC FG. IF THERE IS NO GAS PIPING
 THEN PLEASE REMOVE THE NOTE PER WPB FBC 107.2.1.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 (STAMPED/SEALED AND SIGNED BY DESIGNER OF RECORD IN
 ACCORDANCE WITH FS 471 FAC 61G15) INTO THE ORIGINAL
 SUBMITTAL AND REMOVE THE PREVIOUSLY REVIEWED SHEETS.
 ONE COPY OF THE PREVIOUSLY REVIEWED SHEETS SHOULD
 REMAIN IN PACKAGE AND BE MARKED "VOID".
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 PHONE 561-805-6715