Plan Review Details - Permit 18090940
Plan Review Stops For Permit 18090940
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2018-10-30 Cont ID  
Sent By skennedy Date 2018-10-30 Time 11:23 Rev Time 0.00
Received By skennedy Date 2018-10-30 Time 11:23 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2018-10-30 Cont ID  
Sent By jleahy Date 2018-10-30 Time 14:03 Rev Time 0.00
Received By jleahy Date 2018-10-30 Time 14:02 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2018-10-02 Cont ID  
Sent By fgiaquin Date 2018-10-02 Time 13:52 Rev Time 0.00
Received By fgiaquin Date 2018-10-02 Time 13:11 Sent To  
Notes
2018-10-02 13:51:16ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. PROVIDE PANEL SCHEDULE INDICATING ANY NEW OR ALTERED
 CIRCUITS, THE WIRE AND BREAKER SIZE FOR THESE CIRCUITS,
 AND AFCI OR GFCI PROTECTION WHERE APPLICABLE TO COMPLY
 WITH CODE. NEC 210.8, 210.12, 215.5, 408.4; WPB FBC
 107.3.5; FBC RE E3706.2, E3902
  
 2. ALL BRANCH CIRCUITS THAT SUPPLY 120-VOLT,
 SINGLE-PHASE, 15- AND 20-AMPERE OUTLETS INSTALLED IN
 KITCHENS, FAMILY ROOMS, DINING ROOMS, LIVING ROOMS,
 PARLORS, LIBRARIES, DENS, BEDROOMS, SUN-ROOMS,
 RECREATIONS ROOMS, CLOSETS, HALLWAYS, LAUNDRY AREAS AND
 SIMILAR ROOMS OR AREAS SHALL BE AFCI PROTECTED. PROVIDE
 CORRECTION. NEC 210.12; FBC RE E3902.16
  
 3. RECEPTACLES IN KITCHEN REQUIRE GFCI PROTECTION.
 PROVIDE CORRECTION. NEC 210.8; FBC RE E3902.6
  
 4. RECEPTACLE OUTLETS INSTALLED IN LAUNDRY AREAS SHALL
 HAVE GFCI PROTECTION. PROVIDE CORRECTION. NEC
 210.8(A)(9); FBC RE E3902.9
  
 5. PROVIDE GFCI PROTECTION FOR DISHWASHER. NEC
 210.8(D); FBC RE E3902.10
  
 6. PROVIDE LOCATION OF PANEL ON PLAN. FBC 107.2.1
  
 7. FOR DWELLING UNITS, ATTACHED GARAGES, AND DETACHED
 GARAGES WITH ELECTRIC POWER, AT LEAST ONE WALL
 SWITCH-CONTROLLED LIGHTING OUTLET SHALL BE INSTALLED ON
 THE EXTERIOR SIDE OF OUTDOOR ENTRANCES/EXITS WITH GRADE
 LEVEL ACCESS. PROVIDE CORRECTION. NEC 210.70(A)(2)(B),
 FBC RE E3903.3
  
 8. PROVIDE TAMPER RESISTANT RECEPTACLES PER CODE. A
 NOTE WILL SUFFICE. NEC 406.12; FBC RE E4002.14
  
 9. NO DISCONNECT FOR W/H 422.30 NEC PROVIDE CORRECTION.
  
 10. NO TANKLESS WATER HEATER IN LOAD CALC, PROVIDE
 ACCURATE LOAD CALCULATION INCLUDING ALL LOADS. NEC 220;
 FBC RE E3602.2
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
 CODES IN EFFECT:
  
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2017 6TH ED.
 FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 V/R,
  
 FRANK GIAQUINTO III
 ELECTRICAL INSPECTOR
 ELECTRICAL PLANS EXAMINER
 CITY OF WPB
 [email protected]
 CELL: 561-657-1653
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2018-10-30 Cont ID  
Sent By jleahy Date 2018-10-30 Time 14:03 Rev Time 0.00
Received By jleahy Date 2018-10-30 Time 11:24 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-10-30 Cont ID  
Sent By skennedy Date 2018-10-30 Time 11:23 Rev Time 0.00
Received By skennedy Date 2018-09-21 Time 13:38 Sent To  
Notes
2018-09-25 13:38:55R09

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2018-10-23 Cont ID  
Sent By cmontell Date 2018-10-23 Time 09:24 Rev Time 0.00
Received By cmontell Date 2018-10-23 Time 09:48 Sent To  
Notes
2018-10-23 09:24:09MECHANICAL PLAN REVIEW
  
 1 - AC CHANGEOUT ONLY PERMIT PULLED
  
 CHRIS MONTELLO
 561-805-6733

Review Stop P PLUMBING
Rev No 2 Status P Date 2018-10-30 Cont ID  
Sent By jesmith Date 2018-10-30 Time 13:48 Rev Time 0.00
Received By jesmith Date 2018-10-30 Time 13:48 Sent To  
Notes
2018-10-30 13:48:28PLUMBING COMMENTS: APPROVED
  
 ALL WORK PER CITY CODES SUBJECT TO FIELD INSPECTOR'S
 APPROVAL.
  
  
  
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 PHONE 561-805-6715

Review Stop P PLUMBING
Rev No 1 Status F Date 2018-10-18 Cont ID  
Sent By jesmith Date 2018-10-18 Time 14:35 Rev Time 0.00
Received By jesmith Date 2018-10-18 Time 14:34 Sent To  
Notes
2018-10-18 14:35:09CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RES = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 FBC ACC = FLORIDA ACCESSIBILITY CODE 2017 6TH EDITION
 FBC EX = FLORIDA EXISTING BUILDING CODE 2017 6TH
 EDITION
 FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION
 FBC FG = FLORIDA FUEL GAS CODE 2017 6TH EDITION
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
 1ST REVIEW:
 PLUMBING COMMENTS: DENIED
  
 1. WPB FBC 107.2.1: PROVIDE LEGIBLE PLAN SHOWING SCOPE
 OF WORK.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 (STAMPED/SEALED AND SIGNED BY DESIGNER OF RECORD IN
 ACCORDANCE WITH FS 471 FAC 61G15) INTO THE ORIGINAL
 SUBMITTAL AND REMOVE THE PREVIOUSLY REVIEWED SHEETS.
 ONE COPY OF THE PREVIOUSLY REVIEWED SHEETS SHOULD
 REMAIN IN PACKAGE AND BE MARKED "VOID".
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 PHONE 561-805-6715
  