Plan Review Details - Permit 18090922
Plan Review Stops For Permit 18090922
Review Stop B BUILDING (STRUCTURAL)
Rev No 7 Status P Date 2019-03-25 Cont ID  
Sent By jgomez Date 2019-03-25 Time 12:28 Rev Time 0.00
Received By jgomez Date 2019-03-25 Time 10:25 Sent To  
Notes
2019-03-25 12:17:5503/19/19 ROBERT BROWN (BUILDING OFFICIAL) AGREED TO
 EXCEPTION #4 OF SEC. 213.2 FBC-ACCESSIBILITY APPLIED BY
 PLUMBING. JG.

Review Stop B BUILDING (STRUCTURAL)
Rev No 6 Status F Date 2019-03-20 Cont ID  
Sent By jgomez Date 2019-03-20 Time 15:14 Rev Time 0.00
Received By jgomez Date 2019-03-20 Time 15:14 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status F Date 2019-03-19 Cont ID  
Sent By jgomez Date 2019-03-19 Time 11:30 Rev Time 0.00
Received By jgomez Date 2019-03-19 Time 11:22 Sent To E
Notes
2019-03-19 11:54:252017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 18090922
 ADD: 6803 S. DIXIE HWY.
 CONT: ATLANTIC GENERAL CONTRACTING INC.
 TEL: 561-434-4171
 E-MAIL: [email protected]
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 4TH REVIEW
 DATE: TUESDAY MARCH 19/2019
 ACTION: DENIED
  
 ORIGINAL COMMENT:
 1) PLEASE NOTE THE PRIME PERMIT 18090922 IS FOR THE
 REMOVAL OF AN EXISTING INTERIOR CLOSET AND REPLACE
 DRYWALL. THE SUBMITTED PLANS ARE FOR A NEWLY
 RECONFIGURATION RESTROOM. PLEASE EXPLAIN IF THERE IS A
 CHANGE IN THE SCOPE OF WORK, IF SO PLEASE CHANGE THE
 SCOPE OF WORK ON THE PERMIT APPLICATION AS
 WELL.107.2.1.2 ADDITIONAL INFORMATION IS REQUIRED.
  
 RESPONSE:
 REPEAT COMMENT. SCOPE OF WORK WAS NOT REVISED ON THE
 PERMIT APPLICATION. THE SCOPE OF WORK IS FOR A NEWLY
 RECONFIGURATION OF EXISTING RESTROOM. AND BASED ON THE
 PLANS SUBMITTED, THE SCOPE OF WORK NEEDS TO INCLUDE THE
 WORK DONE IN THE KITCHEN. PLANS SUBMITTED SHOW THAT
 SIZE OF EXISTING RESTROOM WAS REDUCED BUT THERE IS NO
 INFORMATION ON PLANS FOR WORK DONE IN THE INCREASED
 KITCHEN. CONTRACTOR TO REVISE SCOPE OF WORK ON THE
 PERMIT APPLICATION AND ARCHITECT TO REVISE PLANS
 SHOWING THE SCOPE OF WORK DONE IN THE KITCHEN. SEC.
 107.2.1 CITY AMENDMENTS.
  
 2) OK. ROBERT BROWN (BUILDING OFFICIAL) AGREED WITH TIM
 LARGE (CHIEF INSPECTOR, PLUMBING) THAT ALTERED RESTROOM
 IS OK AS SHOWN BECAUSE THE TWO RESTROOMS ARE CLUSTERED
 IN A CLOSE PROXIMITY. BOTH RESTROOMS ARE SHOWN AS
 UNISEX AND ONE OF THEM IS A COMPLIANT UNISEX RESTROOM.
  
  
 3) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2019-03-15 Cont ID  
Sent By jgomez Date 2019-03-13 Time 18:38 Rev Time 0.00
Received By jgomez Date 2019-03-13 Time 16:03 Sent To P
Notes
2019-03-13 18:40:55 
  
 3/15/19 REVIEW IN PROGRESS. NEED TO TALK TO ROBERT
 BROWN (BUILDING OFFICIAL) REGARDING ALTERATION TO THE
 RESTROOM AND FULL ACCESSIBILITY REQUIREMENTS. PLANS ON
 JULIO'S DESK. JG.

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2019-02-22 Cont ID  
Sent By jgomez Date 2019-02-22 Time 12:33 Rev Time 0.00
Received By jgomez Date 2019-02-21 Time 18:15 Sent To  
Notes
2019-02-22 12:33:372017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 18090922
 ADD: 6803 S. DIXIE HWY.
 CONT: ATLANTIC GENERAL CONTRACTING INC.
 TEL: 561-434-4171
 E-MAIL: [email protected]
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 3RD REVIEW
 DATE: FRIDAY FEB. 22/2019
 ACTION: DENIED
  
 ORIGINAL COMMENT:
 1) PLEASE NOTE THE PRIME PERMIT 18090922 IS FOR THE
 REMOVAL OF AN EXISTING INTERIOR CLOSET AND REPLACE
 DRYWALL. THE SUBMITTED PLANS ARE FOR A NEWLY
 RECONFIGURATION RESTROOM. PLEASE EXPLAIN IF THERE IS A
 CHANGE IN THE SCOPE OF WORK, IF SO PLEASE CHANGE THE
 SCOPE OF WORK ON THE PERMIT APPLICATION AS
 WELL.107.2.1.2 ADDITIONAL INFORMATION IS REQUIRED.
  
 RESPONSE:
 REPEAT COMMENT. SCOPE OF WORK WAS NOT REVISED ON THE
 PERMIT APPLICATION.
  
 ORIGINAL COMMENT:
 2) THERE IS A CLOSED PERMIT 18010296 FOR THE CONVERSION
 OF A RESTROOM TO BE A HANDICAPPED RESTROOM.
 ON THAT PERMIT AND ON THIS PROPOSED PERMIT NEITHER
 STATE HOW MANY RESTROOMS THERE ARE IN THIS RESTAURANT,
 NOR HOW MANY ARE ACCESSIBLE RESTROOMS, NOR IF THEY ARE
 UNISEX RESTROOMS WITH THE APPROPRIATE SIGNAGE?
 2017 FBC-B TABLE 2902.1 MINIMUM NUMBER OF REQUIRED
 PLUMBING FIXTURES (FOOTNOTE A) (SEE SECTIONS 2902.1.1
 AND 2902.2)
 2017 FBC-ACCESSIBILITY CODE SECTION 213.1. WHERE TOILET
 FACILITIES AND BATHING FACILITIES ARE PROVIDED, THEY
 SHALL COMPLY WITH 213.
  
 RESPONSE:
 PLAN SUBMITTED STATES 80 PEOPLE AS THE RESTAURANT
 OCCUPANT LOAD. THIS SEEMS TO BE INCORRECT. ACCORDING TO
 CITY RECORDS, THE LIFE SAFETY PLANS ON PERMIT #13060084
 SHOWS 128 PEOPLE INSIDE AND ANOTHER 128 PEOPLE OUTSIDE.
 THE NUMBER OF PLUMBING FIXTURES MAY NOT BE ADEQUATE.
 REVISE AS REQUIRED AND SHOW COMPLIANCE WITH 2017
 FBC-ACCESSIBILITY CODE SECTION 213.1. WHERE TOILET
 FACILITIES AND BATHING FACILITIES ARE PROVIDED, THEY
 SHALL COMPLY WITH 213.
  
 3) PLEASE NOTE THERE JOBSITE PICTURES THAT ALL DRYWALL
 ON THE WALLS WAS REMOVED. PLEASE SHOW COMPLIANCE WITH:
 3A) OK. TO BE VERIFIED IN FIELD.
  
 3A)(1) OK. TO BE VERIFIED IN FIELD.
  
 3A)(2) OK. TO BE VERIFIED IN FIELD.
  
 4) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2019-01-09 Cont ID  
Sent By jwitmer Date 2019-01-09 Time 10:29 Rev Time 0.00
Received By jwitmer Date 2019-01-09 Time 08:57 Sent To  
Notes
2019-01-09 10:29:302017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 18090922
 ADD: 6803 S. DIXIE HWY.
 CONT: ATLANTIC GENERAL CONTRACTING INC.
 TEL: 561-434-4171
 E-MAIL: [email protected]
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 2ND REVIEW
 DATE: WED. JAN. 09/2019
 ACTION: DENIED
  
 1) PLEASE NOTE THE PRIME PERMIT 19090922 IS FOR THE
 REMOVAL OF AN EXISTING INTERIOR CLOSET AND REPLACE
 DRYWALL. THE SUBMITTED PLANS ARE FOR A NEWLY
 RECONFIGURATION RESTROOM. PLEASE EXPLAIN IF THERE IS A
 CHANGE IN THE SCOPE OF WORK, IF SO PLEASE CHANGE THE
 SCOPE OF WORK ON THE PERMIT APPLICATION AS
 WELL.107.2.1.2 ADDITIONAL INFORMATION IS REQUIRED.
  
 2) THERE IS A CLOSED PERMIT 18010296 FOR THE CONVERSION
 OF A RESTROOM TO BE A HANDICAPPED RESTROOM.
 ON THAT PERMIT AND ON THIS PROPOSED PERMIT NEITHER
 STATE HOW MANY RESTROOMS THERE ARE IN THIS RESTAURANT,
 NOR HOW MANY ARE ACCESSIBLE RESTROOMS, NOR IF THEY ARE
 UNISEX RESTROOMS WITH THE APPROPRIATE SIGNAGE?
 2017 FBC-B TABLE 2902.1 MINIMUM NUMBER OF REQUIRED
 PLUMBING FIXTURES (FOOTNOTE A) (SEE SECTIONS 2902.1.1
 AND 2902.2)
 2017 FBC-ACCESSIBILITY CODE SECTION 213.1. WHERE TOILET
 FACILITIES AND BATHING FACILITIES ARE PROVIDED, THEY
 SHALL COMPLY WITH 213.
  
 3) PLEASE NOTE THERE JOBSITE PICTURES THAT ALL DRYWALL
 ON THE WALLS WAS REMOVED. PLEASE SHOW COMPLIANCE WITH:
 3A) 2017 FBC-B SECTION 2509.1 WET AREAS. PUBLIC TOILET
 WALLS SHALL CONFORM TO SECTION 1210.2.
  
 3A)(1) FBC-B 1210.2.1 FLOORS AND WALL BASES. IN OTHER
 THAN DWELLING UNITS, TOILET, BATHING AND SHOWER ROOM
 FLOOR FINISH MATERIALS SHALL HAVE A SMOOTH, HARD,
 NONABSORBENT SURFACE. THE INTERSECTIONS OF SUCH FLOORS
 WITH WALLS SHALL HAVE A SMOOTH, HARD, NONABSORBENT
 VERTICAL BASE THAT EXTENDS UPWARD ONTO THE WALLS NOT
 LESS THAN 4 INCHES.
  
 3A)(2) FBC-B 1210.2.2 WALLS AND PARTITIONS. WALLS AND
 PARTITIONS WITHIN 2 FEET OF SERVICE SINKS, URINALS AND
 WATER CLOSETS SHALL HAVE A SMOOTH, HARD, NONABSORBENT
 SURFACE, TO A HEIGHT OF NOT LESS THAN 4 FEET ABOVE THE
 FLOOR, AND EXCEPT FOR STRUCTURAL ELEMENTS, THE
 MATERIALS USED IN SUCH WALLS SHALL BE OF A TYPE THAT IS
 NOT ADVERSELY AFFECTED BY MOISTURE.
  
 4) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2018-10-30 Cont ID  
Sent By jwitmer Date 2018-10-30 Time 16:16 Rev Time 0.00
Received By jwitmer Date 2018-10-30 Time 16:00 Sent To  
Notes
2018-10-30 16:16:272017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 18090922
 ADD: 6803 S. DIXIE, HAVANA RESTAURANT
 CONT: ATLANTIC GENERAL CONTRACTING INC.
 TEL: 561-434-4171
 E-MAIL: [email protected]
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: TUES. OCT. 30/ 2018
 ACTION: DENIED
  
 1) THE SCOPE OF WORK DESCRIBED IN THE PERMIT
 APPLICATION (REMOVE EXISTING INTERIOR CLOSET & REPLACE
 DRYWALL). THE PERMIT IS NOT ISSUED, AND THE SCOPE OF
 WORK EXCEEDED, JOBSITE VISIT BY INSPECTOR AND PICTURES
 TAKEN AT THE TIME OF VISIT EXCEEDS THE SCOPE OF WORK
 DECLARED.
  
 2017 WEST PALM BEACH ADMINISTRATIVE CODE SECTION
 105.6.1 MISREPRESENTATION OF APPLICATION. THE BUILDING
 OFFICIAL MAY SUSPEND OR REVOKE A PERMIT OR APPROVAL,
 ISSUED UNDER THE PROVISIONS OF THIS CODE, IN CASE THERE
 HAS BEEN ANY FALSE STATEMENT OR MISREPRESENTATION AS TO
 THE MATERIAL FACT IN THE APPLICATION OR PLANS ON WHICH
 THE PERMIT OR APPROVAL WAS BASED.
  
 2) 107.3.5 MINIMUM PLAN REVIEW CRITERIA FOR BUILDINGS.
 THE EXAMINATION OF THE DOCUMENTS BY THE BUILDING
 OFFICIAL SHALL INCLUDE THE FOLLOWING MINIMUM CRITERIA
 AND DOCUMENTS: A FLOOR PLAN;
 107.3.5.1 COMMERCIAL BUILDINGS: 107.3.5.1.1 BUILDING.
 PLANS WILL NEED TO SHOW WHAT APPEARS TO BE A NEW
 ACCESSIBLE RESTROOM. TOILET AND BATHING FACILITIES.
 INTERIOR REQUIREMENTS SHALL INCLUDE THE FOLLOWING:
 INTERIOR FINISHES (FLAME SPREAD/SMOKE DEVELOPMENT)
 LIGHT AND VENTILATION
 SANITATION.
  
 3) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  

Review Stop E ELECTRICAL
Rev No 5 Status P Date 2019-04-02 Cont ID  
Sent By jpearson Date 2019-04-02 Time 16:23 Rev Time 0.00
Received By jpearson Date 2019-04-02 Time 16:20 Sent To  
Notes
2019-04-02 15:40:23NEW PLAN SUBMITTED. JG.

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2019-03-19 Cont ID  
Sent By jpearson Date 2019-03-19 Time 12:10 Rev Time 0.00
Received By jpearson Date 2019-03-19 Time 12:10 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2019-02-21 Cont ID  
Sent By jpearson Date 2019-02-21 Time 13:11 Rev Time 0.00
Received By jpearson Date 2019-02-21 Time 10:31 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2019-01-08 Cont ID  
Sent By jpearson Date 2019-01-08 Time 13:38 Rev Time 0.00
Received By jpearson Date 2019-01-08 Time 13:38 Sent To  
Notes
2019-01-08 13:38:21NO CHANGES TO PREVIOUSLY APPROVED PLANS.

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2018-10-02 Cont ID  
Sent By fgiaquin Date 2018-10-02 Time 13:02 Rev Time 0.00
Received By fgiaquin Date 2018-10-02 Time 11:21 Sent To  
Notes
2018-10-02 13:02:49PASSED PROVVISIONALLY:
  
 PROVIDE SUBMITTAL FOR PRODUCT APPROVAL OF NEW HAND
 DRYER TO BE INSTALLED BEFORE FINAL. FBC 107.2.1, NEC
 110.3B

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status P Date 2019-03-28 Cont ID  
Sent By pleduc Date 2019-03-28 Time   Rev Time 0.00
Received By pleduc Date 2019-03-28 Time 14:01 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2019-02-06 Cont ID  
Sent By scaldero Date 2019-02-06 Time 10:23 Rev Time 0.00
Received By scaldero Date 2019-02-06 Time 10:19 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2019-01-03 Cont ID  
Sent By scaldero Date 2019-01-03 Time 11:52 Rev Time 0.00
Received By scaldero Date 2019-01-03 Time 11:49 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2018-09-26 Cont ID  
Sent By scaldero Date 2018-09-26 Time 09:51 Rev Time 0.00
Received By scaldero Date 2018-09-26 Time 09:50 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2019-04-03 Cont ID  
Sent By tklarge Date 2019-04-03 Time 11:56 Rev Time 0.00
Received By tklarge Date 2019-03-21 Time 15:29 Sent To  
Notes
2019-03-22 15:25:00B17
2019-03-21 15:29:4703/21/19 MET W/ MARIA. SHE RE-SUBMITTED PLANS FOR
 REVIEW. JG.
  
  

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2019-03-15 Cont ID  
Sent By tklarge Date 2019-03-15 Time 08:30 Rev Time 0.00
Received By tklarge Date 2019-03-11 Time 15:39 Sent To  
Notes
2019-03-13 15:40:3803/11/19 MARIA RE-SUBMITTED NEW PLANS. JG.
 03/14/19 PLANS SENT TO TIM LARGE FOR PLUMBING REVIEW.
 JG.

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2019-02-22 Cont ID  
Sent By jgomez Date 2019-02-22 Time 12:33 Rev Time 0.00
Received By jgomez Date 2019-02-01 Time 14:35 Sent To I
Notes
2019-02-01 14:35:32B21

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2019-01-10 Cont ID  
Sent By cpuell Date 2019-01-10 Time 12:57 Rev Time 0.00
Received By cpuell Date 2018-12-28 Time 16:14 Sent To  
Notes
2018-12-28 16:14:38B31

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-11-01 Cont ID  
Sent By tklarge Date 2018-11-01 Time 16:23 Rev Time 0.00
Received By tklarge Date 2018-09-20 Time 11:21 Sent To  
Notes
2018-09-21 11:21:59B10

Review Stop M MECHANICAL (A/C)
Rev No 3 Status N Date 2019-04-02 Cont ID  
Sent By ccole Date 2019-04-02 Time 17:06 Rev Time 0.00
Received By ccole Date 2019-04-02 Time 17:06 Sent To  
Notes
2019-04-02 15:40:45NEW PLAN SUBMITTED. JG.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2019-02-19 Cont ID  
Sent By ccole Date 2019-02-19 Time 16:15 Rev Time 0.00
Received By ccole Date 2019-02-19 Time 16:15 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2019-01-15 Cont ID  
Sent By ccole Date 2019-01-15 Time 14:44 Rev Time 0.00
Received By ccole Date 2019-01-15 Time 14:44 Sent To I
Notes
2019-01-15 15:00:161ST REVIEW FBC-2017 MECHANICAL
 PERMIT #18090922
 1/15/19
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PROVIDE A SCOPE OF WORK FOR MECHANICAL, AND CLARIFY
 IF THE EXHAUST FAN SHOWN ON THE DRAWINGS IS NEW OR
 EXISTING. IT APPEARS A NEW EXHAUST FAN WAS INSTALLED.
 PLEASE PROVIDE AN EQUIPMENT SCHEDULE FOR THE FAN AND
 SHOW THE EXHAUST DUCT RUN AND TERMINATION LOCATION.
  
 2) PLEASE NOTE THAT ALL PLANS SHALL BE DRAWN BY A FL.
 LICENSED ARCHITECT OR ENGINEER IN ACCORDANCE WITH
 SECTION 107.1 WPB. CONTRACTOR DRAWN PLANS MUST BEAR THE
 SIGNATURE OF THE CONTRACTOR- SECTION 107.2.1 WPB. THE
 SUBMITTED PLANS DRAWN BY ON TARGET HOME DESIGNS ARE NOT
 ACCEPTABLE.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 5 Status P Date 2019-04-03 Cont ID  
Sent By tklarge Date 2019-04-03 Time 11:56 Rev Time 0.00
Received By tklarge Date 2019-04-03 Time 11:28 Sent To I
Notes
2019-04-02 15:40:55NEW PLAN SUBMITTED. JG.

Review Stop P PLUMBING
Rev No 4 Status P Date 2019-03-15 Cont ID  
Sent By jgomez Date 2019-03-15 Time 09:02 Rev Time 0.00
Received By tklarge Date 2019-03-15 Time 06:42 Sent To I
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status F Date 2019-02-19 Cont ID  
Sent By jesmith Date 2019-02-19 Time 09:31 Rev Time 0.00
Received By jesmith Date 2019-02-19 Time 09:03 Sent To  
Notes
2019-02-19 09:31:37CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RES = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 FBC ACC = FLORIDA ACCESSIBILITY CODE 2017 6TH EDITION
 FBC EX = FLORIDA EXISTING BUILDING CODE 2017 6TH
 EDITION
 FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION
 FBC FG = FLORIDA FUEL GAS CODE 2017 6TH EDITION
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
 3RD REVIEW: DENIED
  
 1) SUBMIT A WATER RISER DIAGRAM FOR THE PLUMBING WORK
 THAT HAS BEEN DONE PER WPB FBC 107.3.5.1.3. THIS IS THE
 3RD REQUEST. INDICATE SIZED HOT AND COLD WATER LINES AS
 WELL AS TEMPERATURE LIMITING DEVICE (SEE FBC PL 416.5)
 FOR LAVATORY PER WPB FBC 107.3.5.1.3 AND 107.2.1. .
 A. PLEASE NOTE PREVIOUS COMMENT HISTORY.
 01/03/2019 SUBMIT A WATER RISER DIAGRAM FOR THE
 PLUMBING WORK THAT HAS BEEN DONE. WPB AMEND. TO 2017
 FBC SEC. 107.3.5.1.3. 2ND REQUEST.
 11/01/2018 SUBMIT A WATER AND SANITERY RISER DIAGRAM
 FOR THE PLUMBING WORK THAT HAS BEEN DONE. WPB AMEND. TO
 2017 FBC SEC. 107.3.5.1.3.
  
 SUBMITTAL OF ADDITIONAL AND/OR REVISED MATERIALS,
 ESPECIALLY AS A RESULT OF RESPONSE TO BUILDING REVIEW
 COMMENTS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED "VOID".
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 PHONE 561-805-6715
  

Review Stop P PLUMBING
Rev No 2 Status F Date 2019-01-03 Cont ID  
Sent By tklarge Date 2019-01-03 Time 10:45 Rev Time 0.00
Received By tklarge Date 2019-01-03 Time 09:01 Sent To  
Notes
2019-01-03 10:45:021) SUBMIT A WATER RISER DIAGRAM FOR THE PLUMBING WORK
 THAT HAS BEEN DONE. WPB AMEND. TO 2017 FBC SEC.
 107.3.5.1.3. 2ND REQUEST.
 2) IS THIS TOILET ROOM HANDICAP ACCESSIBLE? IF SO,
 SUBMIT DETAILS FOR THE WATER CLOSET, LAVATORY, HAND
 DRYER, GRAB BARS, TOILET PAPER DISPENSER, ETC. WPB
 AMEND. TO FBC SEC. 107.2.1. 2ND REQUEST.
 3) INDICATE THE WALL AND FLOOR FINISHES OF THE TOILET
 ROOM ON THE PLANS. WALLS WITHIN TWO FEET OF WATER
 CLOSETS SHALL HAVE A SMOOTH, HARD, NONABSORBANT
 SURFACE, TO A HEIGHT OF NOT LESS THAN 4 FEET ABOVE THE
 FLOOR PER 2017 FBC SEC. 1210.2.2. THE FLOOR FINISH
 MATERIAL SHALL HAVE A SMOOTH, HARD NONABSORBANT SURFACE
 AND THE INTERSECTIONS OF SUCH FLOORS WITH WALLS SHALL
 COMPLY WITH 2017 FBC SEC.1210.2.1. 2ND REQUEST.
 4) THE SUBMITTED PLAN SHOWS THE REMOVAL OF A MOP SINK
 AND A URINAL. THE MOP SINK IS A REQUIRED FIXTURE PER
 TABLE 403.1 OF THE PLUMBING CODE AND REMOVING THIS
 FIXTURE MAY BE CREATING A PLUMBING CODE VIOLATION. IS
 THERE ANOTHER MOP SINK IN THE BUILDING? THE URINAL MAY
 ALSO BE REQUIRED. SUBMIT THE TOTAL OCCUPANT LOAD FOR
 THIS RESTAURANT AND THE TOTAL NUMBER OF EXISTING WATER
 CLOSETS AND LAVATORIES FOR THE MALES AND THE TOTAL
 NUMBER OF WATER CLOSETS AND LAVATORIES FOR THE FEMALES.
 5) IF THIS TOILET ROOM IS HANDICAP ACCESSIBLE, SHOW THE
 REQUIRED CLEAR FLOOR SPACE FOR THE WATER CLOSET AND THE
 LAVATORY ON THE FLOOR PLAN. 2017 FBC-ACCESS. SEC.604.3
 (WATER CLOSETS) AND SEC. 606.2 (LAVATORIES).
 6) IS THIS TOILET ROOM SERVING THE MALE OR FEMALE
 GENDER? INDICATE SUCH ON THE PLAN.
 7) THE SANITARY RISER DOES NOT CORRELATE WITH THE FLOOR
 PLAN AND THE PLUMBING CANNOT BE INSTALLED AS DRAWN.
 8) TEMPERED WATER IS REQUIRED AT THE LAVATORY AND HOT
 WATER WILL BE REQUIRED AT THE MOP SINK. 2017 FBC-
 PLUMBING SEC.607.1, 416.5.
  
  
 NOTE: ANY NEW PLUMBING WORK THAT HAS BEEN COVERED BY
 DRYWALL OR CONCRETE SHALL BE EXPOSED FOR INSPECTION.
 WPB AMEND. TO FBC SEC. 110.6.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2018-11-01 Cont ID  
Sent By tklarge Date 2018-11-01 Time 16:23 Rev Time 0.00
Received By tklarge Date 2018-11-01 Time 15:50 Sent To I
Notes
2018-11-01 15:56:571) THE SCOPE OF WORK NOTED ON THE APPLICATION AND ALSO
 IN THE LETTER FROM SPEEDY ROOTER DOES NOT CORRELATE
 WITH THE PHOTOS TAKEN BY THE FIELD INSPECTOR. THIS
 APPEARS TO BE A COMPLETE ALTERATION OF AN EXISTING
 STORAGE ROOM INTO A TOILET ROOM. SUBMIT A COPY OF THE
 EXISTING FLOOR PLAN AND OF THE PROPOSED FLOOR PLAN. WPB
 AMEND. TO 2017 FBC SEC. 107.3.5.1.3.
 2) SUBMIT A WATER AND SANITERY RISER DIAGRAM FOR THE
 PLUMBING WORK THAT HAS BEEN DONE. WPB AMEND. TO 2017
 FBC SEC. 107.3.5.1.3.
 3) SHOW THE DIMENSIONS OF THE TOILET ROOM ON THE PLANS
 (L X W ).
 4) IS THIS TOILET ROOM HANDICAP ACCESSIBLE? IF SO,
 SUBMIT DETAILS FOR THE WATER CLOSET, LAVATORY, HAND
 DRYER, GRAB BARS, TOILET PAPER DISPENSER, ETC.
 5) SUBMIT TWO COPIES OF PROFESSIONALLY DRAWN PLANS THAT
 BEAR THE NAME AND SIGNATURE OF THE PERSON RESPONSIBLE
 FOR THE DESIGN.
 6) INDICATE THE WALL FINISHES OF THE TOILET ROOM ON THE
 PLANS. WALLS WITHIN TWO FEET OF WATER CLOSETS SHALL
 HAVE A SMOOTH, HARD, NONABSORBANT SSURFACE, TO A HEIGHT
 OF NOT LESS THAN 4 FEET ABOVE THE FLOOR PER 2017 FBC
 SEC. 1210.2.2.
  
 NOTE: ANY NEW PLUMBING WORK THAT HAS BEEN COVERED BY
 DRYWALL OR CONCRETE SHALL BE EXPOSED FOR INSPECTION.
 WPB AMEND. TO FBC SEC. 110.6.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  