Plan Review Details - Permit 18090904
Plan Review Stops For Permit 18090904
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2018-12-03 Cont ID  
Sent By pvalenti Date 2018-12-03 Time 17:19 Rev Time 0.00
Received By pvalenti Date 2018-12-03 Time 17:19 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2018-11-19 Cont ID  
Sent By pvalenti Date 2018-11-19 Time 12:38 Rev Time 0.00
Received By pvalenti Date 2018-11-19 Time 12:38 Sent To  
Notes
2018-11-19 12:46:59****CORRECTIONS****
  
 PETER E VALENTI
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6673
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 FBC 107. PLEASE PROVIDE MORE INFORMATION:
  
 1. FOR CLARITY, PLEASE RESPOND TO THE LAST BUILDING
 PLAN REVIEW NOTES ITEM BY ITEM.
 NOTE:
 THE PLANS THAT WERE SUBMITTED ARE MISSING THE
 ENGINEER'S SIGNATURE/SEAL, ALSO THE ADDRESS ON PLANS
 SHOULD MATCH THE ADDRESS ON THE RESUBMITTAL FORM
 INCLUDING THE SUITE NUMBER.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2018-10-29 Cont ID  
Sent By jwitmer Date 2018-10-29 Time 11:56 Rev Time 0.00
Received By jwitmer Date 2018-10-29 Time 10:51 Sent To  
Notes
2018-10-29 11:56:502017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 18090904
 ADD: 3202 CARIBBEAN BLVD. BLDG. 32/ UNIT 2
 CONT: BEST BUILDING CONCEPTS/ CRC1328815
 TEL: 561-294-8255
 E-MAIL: [email protected]
  
 2017 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: MON. OCT. 29/ 2018
 ACTION: DENIED
  
 1) THE SCOPE OF WORK INDICATED UNDER THIS PERMIT IS
 BEYOND THE SCOPE OF YOUR LICENSE (CRC1328815). PLEASE
 REVIEW 2018 FLORIDA STATUTE 489.105 ( C ). ?RESIDENTIAL
 CONTRACTOR? MEANS A CONTRACTOR WHOSE SERVICES ARE
 LIMITED TO CONSTRUCTION, REMODELING, REPAIR, OR
 IMPROVEMENT OF ONE-FAMILY, TWO-FAMILY, OR THREE-FAMILY
 RESIDENCES NOT EXCEEDING TWO HABITABLE STORIES ABOVE NO
 MORE THAN ONE UNINHABITABLE STORY AND ACCESSORY USE
 STRUCTURES IN CONNECTION THEREWITH.
  
 2) MISSING INFORMATION. 107.3.5 MINIMUM PLAN REVIEW
 CRITERIA FOR COMMERCIAL BUILDINGS.
 107.3.5.1.FLOOR PLANS.
 107.3.5.1.8 WIND REQUIREMENTS.
 2017 FBC-B 1603.1.4 WIND DESIGN DATA.
 THE FOLLOWING INFORMATION RELATED TO WIND LOADS SHALL
 BE SHOWN, REGARDLESS OF WHETHER WIND LOADS GOVERN THE
 DESIGN OF THE LATERAL FORCE-RESISTING SYSTEM OF THE
 STRUCTURE:
  
 1. ULTIMATE DESIGN WIND SPEED, VULT, (3-SECOND GUST),
 MILES PER HOUR (KM/HR) AND NOMINAL DESIGN WIND SPEED,
 VASD, AS DETERMINED IN ACCORDANCE WITH SECTION
 1609.3.1.
  
 2. RISK CATEGORY.
  
 3. WIND EXPOSURE. APPLICABLE WIND DIRECTION IF MORE
 THAN ONE WIND EXPOSURE IS UTILIZED. TABLE 1609.7.2.
 HEIGHT AND EXPOSURE.
  
 4. APPLICABLE INTERNAL PRESSURE COEFFICIENT.
  
 5. DESIGN WIND PRESSURES TO BE USED FOR EXTERIOR
 COMPONENTS AND CLADDING MATERIALS NOT SPECIFICALLY
 DESIGNED BY THE REGISTERED DESIGN PROFESSIONAL
 RESPONSIBLE FOR THE DESIGN OF THE STRUCTURE, PSF.
  
 TABLE 1609.7(2) ADJUSTMENT FACTORS FOR HEIGHT &
 EXPOSURE. PROVIDE THE MEAN ROOF HEIGHT FOR THE
 BUILDING.
  
 1609.3.1 WIND SPEED CONVERSION VULT TO VASD.
 3) PRODUCT APPROVALS CAN NOT BE REVIEWED UNTIL THE WIND
 DESIGN CRITERIA IS GIVEN. 107.2.1.3. ADDITIONAL
 INFORMATION IS REQUIRED.
  
 4) THE PLANS DOES NOT STATE IF THIS IS A 1ST STORY UNIT
 OR 2ND STORY UNIT. IF A 2ND STORY UNIT THEN SHOW
 COMPLIANCE WITH: BLDG TYPE: TYPE I/ TYPE II FLOOR
 INSULATION (FBC-B 2017)
 FOR TILE, STONE, MARBLE, VINYL AND WOOD FLOORING ALL
 NEED TO HAVE HAD THE SOUND UNDERLAYMENT TESTED FLOOR
 ASSEMBLIES TO THE FOLLOWING STANDARDS AND MEET THE
 QUALIFICATIONS LISTED UNDER EACH OF THE STANDARDS FOR A
 6 INCH CONCRETE FLOOR ASSEMBLY/ NO DROPPED CEILING:
 PLEASE PROVIDE TEST REPORTS SHOWING COMPLIANCE WITH:
  
 4A) FBC-B 2017 1207.3 STRUCTURE-BORNE SOUND.
 FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR
 BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA
 WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION
 CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD
 TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 492.
  
 4B) FBC-B 2017 1207.2 AIR-BORNE SOUND.
 WALLS, PARTITIONS AND FLOOR/CEILING ASSEMBLIES
 SEPARATING DWELLING UNITS FROM EACH OTHER OR FROM
 PUBLIC OR SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION
 CLASS (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED)
 FOR AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM
 E 90.
  
 4C) FLAME SPREAD- FBC-B 2014 603.1. EXCEPTION 2.
 INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID
 DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED
 TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200.
  
 FLAME SPREAD INDEX. A COMPARATIVE MEASURE, EXPRESSED AS
 A DIMENSIONLESS NUMBER, DERIVED FROM VISUAL
 MEASUREMENTS OF THE SPREAD OF FLAME VERSUS TIME FOR A
 MATERIAL TESTED IN ACCORDANCE WITH ASTM E 84 OR UL 723.
  
 TYPE III-TYPE V CONSTRUCTION:
 FBC-B-2014 720.2 CONCEALED INSTALLATION. INSULATING
 MATERIALS, WHERE CONCEALED AS INSTALLED IN BUILDINGS OF
 ANY TYPE OF CONSTRUCTION, SHALL HAVE A FLAME SPREAD
 INDEX OF NOT MORE THAN 25 AND A SMOKE-DEVELOPED INDEX
 OF NOT MORE THAN 450.
  
 5) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 A THOROUGH REVIEW OF THE PLANS COULD NOT HAPPEN SINCE
 THERE WAS A GREAT DEFICIENCY IN PLANS AND REQUIRED
 DOCUMENTATION. WITH THE NEXT PLAN REVIEW CYCLE THERE
 MAYBE ADDITIONAL REVIEW COMMENTS BECAUSE OF NEW PLANS
 AND INFORMATION LACKING UNDER THE PRIOR REVIEW.
  
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT/
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2018-10-03 Cont ID  
Sent By jpearson Date 2018-10-03 Time 15:44 Rev Time 0.00
Received By jpearson Date 2018-10-03 Time 15:44 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2018-12-03 Cont ID  
Sent By pvalenti Date 2018-12-03 Time 17:19 Rev Time 0.00
Received By pvalenti Date 2018-11-27 Time 12:36 Sent To  
Notes
2018-11-29 12:36:15RESUB ROUTED TO CCOLE

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2018-11-19 Cont ID  
Sent By pvalenti Date 2018-11-19 Time 12:47 Rev Time 0.00
Received By pvalenti Date 2018-11-08 Time 13:09 Sent To I
Notes
2018-11-19 08:56:3311/19 TO PV DESK
  
2018-11-09 13:10:07RESUB ROUTED TO CCOLE

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-10-29 Cont ID  
Sent By cpuell Date 2018-10-29 Time 14:04 Rev Time 0.00
Received By cpuell Date 2018-09-20 Time 13:04 Sent To  
Notes
2018-09-21 13:02:50B30

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2018-12-03 Cont ID  
Sent By ccole Date 2018-12-03 Time 16:28 Rev Time 0.00
Received By ccole Date 2018-12-03 Time 16:28 Sent To B
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2018-11-19 Cont ID  
Sent By ccole Date 2018-11-19 Time 08:26 Rev Time 0.00
Received By ccole Date 2018-11-19 Time 08:21 Sent To B
Notes
2018-11-19 08:30:422ND REVIEW FBC-2017 MECHANICAL
 PERMIT #18090904
 11/19/18
  
 1) COMMENTS FROM THE 1ST REVIEW HAVE NOT BEEN
 ADDRESSED. SEE COMMENTS BELOW AND PLEASE COMPLY
  
  
 1ST REVIEW FBC-2017 MECHANICAL
 PERMIT #18090904
 10/12/18
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SIGNATURE OF THE PERSON RESPONSIBLE FOR THE DESIGN
 (CONTRACTOR, QUALIFIER, OR DESIGN PROFESSIONAL) SHALL
 BE ON THE PLAN- SECTION 107.2.1 WPB.
  
 2) SUBMIT AN AHRI CETIFICATE FOR THE REPLACED AC
 SYSTEM- SECTION C501.7 FBC EC.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2018-10-12 Cont ID  
Sent By ccole Date 2018-10-12 Time 10:14 Rev Time 0.00
Received By ccole Date 2018-10-12 Time 10:14 Sent To  
Notes
2018-10-12 10:21:421ST REVIEW FBC-2017 MECHANICAL
 PERMIT #18090904
 10/12/18
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SIGNATURE OF THE PERSON RESPONSIBLE FOR THE DESIGN
 (CONTRACTOR, QUALIFIER, OR DESIGN PROFESSIONAL) SHALL
 BE ON THE PLAN- SECTION 107.2.1 WPB.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  