| 2018-10-05 14:06:34 | 1ST REVIEW FBC-2017 MECHANICAL |
| | REVISION #18090893 |
| | 10/5/18 |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| | 2017 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE NEW |
| | CLOTHES DRYERS INCLUDING INSTALLATION INSTRUCTIONS FOR |
| | THE DRYER EXHAUST- SEE SECTIONS 504.1 AND 504.8.4.2 FBC |
| | M. |
| | |
| | 2) SHEET M2.1: PROVIDE DRYER EXHAUST DUCT DIAGRAMS |
| | INDICATING THE TOTAL RUN LENGTHS OF THE DUCTS FROM THE |
| | EXHAUST OUTLETS TO THE TERMINATION LOCATIONS. |
| | |
| | 3) M2.1: INDICATE HOW MAKE UP AIR IS BEING PROVIDED FOR |
| | THE DRYERS AND PROVIDE AN AIR BALANCE CALCULATION FOR |
| | THE ROOM. |
| | |
| | 4) M2.1: PLEASE LABEL THE O/A INTAKE AND EXHAUST OUTLET |
| | FOR THE ERV AND VERIFY COMPLIANCE WITH REQUIRED |
| | CLEARANCE DISTANCES AS REQUIRED BY SECTION 401.4(1-4) |
| | AND 501.3.1(3) FBC M |
| | |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE |
| | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND |
| | KEEP THEM WITH THE SUBMITTALS |
| | |