Plan Review Details - Permit 18090868
Plan Review Stops For Permit 18090868
Review Stop B BUILDING (STRUCTURAL)
Rev No 7 Status P Date 2019-10-01 Cont ID  
Sent By cthroop Date 2019-10-01 Time 16:57 Rev Time 0.00
Received By cthroop Date 2019-09-27 Time 12:13 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 6 Status F Date 2019-09-10 Cont ID  
Sent By cthroop Date 2019-09-10 Time 10:02 Rev Time 0.00
Received By cthroop Date 2019-09-10 Time 10:02 Sent To  
Notes
2019-09-10 10:03:53BUILDING PLAN REVIEW
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 BUILDING PLANS EXAMINER, PX3169
 1&2 FAMILY PLANS EXAMINER, SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 6TH REVIEW
 RESULTS: DENIED
 YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED
 BELOW.
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 REPEAT COMMENTS
  
 1. PROVIDE PRODUCT APPROVALS FOR WINDOW MULLIONS FOR
 WINDOWS 4 & 5.
 FBC 107.3.4 ? PROVIDE PRODUCT APPROVALS FOR THOSE
 PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED
 AND APPROVED IN WRITING BY THE DESIGNER OF RECORD.
 SPECIFICALLY, PROVIDE WINDOW MULLION SUBMITTALS.
  
 NOTICE:
  
 4X FEES
  
 F.S. 553.80 (2) (B)
 (B)?WITH RESPECT TO EVALUATION OF DESIGN PROFESSIONALS?
 DOCUMENTS, IF A LOCAL GOVERNMENT FINDS IT NECESSARY, IN
 ORDER TO ENFORCE COMPLIANCE WITH THE FLORIDA BUILDING
 CODE AND ISSUE A PERMIT, TO REJECT DESIGN DOCUMENTS
 REQUIRED BY THE CODE THREE OR MORE TIMES FOR FAILURE TO
 CORRECT A CODE VIOLATION SPECIFICALLY AND CONTINUOUSLY
 NOTED IN EACH REJECTION, INCLUDING, BUT NOT LIMITED TO,
 EGRESS, FIRE PROTECTION, STRUCTURAL STABILITY, ENERGY,
 ACCESSIBILITY, LIGHTING, VENTILATION, ELECTRICAL,
 MECHANICAL, PLUMBING, AND GAS SYSTEMS, OR OTHER
 REQUIREMENTS IDENTIFIED BY RULE OF THE FLORIDA BUILDING
 COMMISSION ADOPTED PURSUANT TO CHAPTER 120, THE LOCAL
 GOVERNMENT SHALL IMPOSE, EACH TIME AFTER THE THIRD SUCH
 REVIEW THE PLANS ARE REJECTED FOR THAT CODE VIOLATION,
 A FEE OF FOUR TIMES THE AMOUNT OF THE PROPORTION OF THE
 PERMIT FEE ATTRIBUTED TO PLANS REVIEW.
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status F Date 2019-07-25 Cont ID  
Sent By cthroop Date 2019-07-25 Time 14:55 Rev Time 0.00
Received By cthroop Date 2019-07-24 Time 17:22 Sent To Z
Notes
2019-07-25 14:58:00BUILDING PLAN REVIEW
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 BUILDING PLANS EXAMINER, PX3169
 1&2 FAMILY PLANS EXAMINER, SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 5TH REVIEW
 RESULTS: DENIED
 YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED
 BELOW.
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 REPEAT COMMENTS
  
 1. PROVIDE PRODUCT APPROVALS FOR WINDOW MULLIONS FOR
 WINDOWS 4 & 5.
 FBC 107.3.4 ? PROVIDE PRODUCT APPROVALS FOR THOSE
 PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED
 AND APPROVED IN WRITING BY THE DESIGNER OF RECORD.
 SPECIFICALLY, PROVIDE WINDOW MULLION SUBMITTALS.
  
 NOTICE:
  
 4X FEES
  
 F.S. 553.80 (2) (B)
 (B)?WITH RESPECT TO EVALUATION OF DESIGN PROFESSIONALS?
 DOCUMENTS, IF A LOCAL GOVERNMENT FINDS IT NECESSARY, IN
 ORDER TO ENFORCE COMPLIANCE WITH THE FLORIDA BUILDING
 CODE AND ISSUE A PERMIT, TO REJECT DESIGN DOCUMENTS
 REQUIRED BY THE CODE THREE OR MORE TIMES FOR FAILURE TO
 CORRECT A CODE VIOLATION SPECIFICALLY AND CONTINUOUSLY
 NOTED IN EACH REJECTION, INCLUDING, BUT NOT LIMITED TO,
 EGRESS, FIRE PROTECTION, STRUCTURAL STABILITY, ENERGY,
 ACCESSIBILITY, LIGHTING, VENTILATION, ELECTRICAL,
 MECHANICAL, PLUMBING, AND GAS SYSTEMS, OR OTHER
 REQUIREMENTS IDENTIFIED BY RULE OF THE FLORIDA BUILDING
 COMMISSION ADOPTED PURSUANT TO CHAPTER 120, THE LOCAL
 GOVERNMENT SHALL IMPOSE, EACH TIME AFTER THE THIRD SUCH
 REVIEW THE PLANS ARE REJECTED FOR THAT CODE VIOLATION,
 A FEE OF FOUR TIMES THE AMOUNT OF THE PROPORTION OF THE
 PERMIT FEE ATTRIBUTED TO PLANS REVIEW.
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2019-06-24 Cont ID  
Sent By cthroop Date 2019-06-24 Time 10:24 Rev Time 0.00
Received By cthroop Date 2019-06-24 Time 10:06 Sent To  
Notes
2019-06-24 10:26:52BUILDING PLAN REVIEW
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 BUILDING PLANS EXAMINER, PX3169
 1&2 FAMILY PLANS EXAMINER, SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 4TH REVIEW
 RESULTS: DENIED
 YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED
 BELOW.
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. PROVIDE PRODUCT APPROVALS FOR WINDOW MULLIONS FOR
 WINDOWS 4 & 5.
 FBC 107.3.4 ? PROVIDE PRODUCT APPROVALS FOR THOSE
 PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED
 AND APPROVED IN WRITING BY THE DESIGNER OF RECORD.
 SPECIFICALLY, PROVIDE WINDOW MULLION SUBMITTALS.
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2019-05-24 Cont ID  
Sent By jduprey Date 2019-05-24 Time 07:56 Rev Time 0.00
Received By jduprey Date 2019-05-23 Time 10:25 Sent To  
Notes
2019-05-24 07:56:39BUILDING PLAN REVIEW
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 JOSEAN A. DUPREY
 BUILDING PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6716
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
 3RD REVIEW
 RESULTS: DENIED
 YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED
 BELOW.
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 PREVIOUS COMMENTS THAT HAVE BEEN ADDRESSED
 SATISFACTORILY ARE MARKED AS CORRECTED. PREVIOUS
 COMMENTS THAT HAVE NOT BEEN ADDRESSED SATISFACTORILY
 HAVE ADDITIONAL COMMENTS IN PARENTHESES. ANY NEW
 COMMENT WILL BE LISTED AFTER PREVIOUS COMMENTS
  
 ***REPEAT COMMENTS***
 1. PROVIDE PRODUCT APPROVALS FOR PROPOSED EXT. DOORS. (
 STILL OPEN )
  
 2. REF. WINDOW SCH. PLAN PAGE A-1. ROUGH OPENING FOR
 PROPOSED WINDOW B IS 60 INCHES WIDE. PRODUCT APPROVAL
 FL19715 FO9R V1 SERIES 70 SH WINDOWS IS LIMITED TO 52
 INCHES WIDE. PROVIDE PRODUCT APPROVAL FOR PROPOSED
 WINDOW B.
 FBC 107.3.4 PROVIDE PRODUCT APPROVALS FOR THOSE
 PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED
 AND APPROVED IN WRITING BY THE DESIGNER OF RECORD.
 SPECIFICALLY, PROVIDE WINDOW AND DOOR SUBMITTALS.
 CORRECTED - PLAN PAGE A-1 REPLACED - WINDOW SCHEDULE
 NOW ON PAGE A-2
  
 3. IF PROPOSED WOOD FLOOR SYSTEM IS FOR THE ENTIRE
 HOUSE, VALUE MUST BE ADJUSTED SUBSTANTIALLY. (SCOPPE OF
 WORK APPEARS TO HAVE EXPANDED - PROVIDE CONTRACT SIGNED
 BY OWNER/CONTRACTOR
 CITY OF WPB CHPT. 1 VALUE 109.3 BUILDING PERMIT
 VALUATIONS. IF, IN THE OPINION OF THE BUILDING
 OFFICIAL, THE CLAIMED VALUATION OF BUILDING,
 ALTERATION, STRUCTURE, ELECTRICAL, GAS, MECHANICAL OR
 PLUMBING SYSTEMS APPEARS TO BE UNDERESTIMATED ON THE
 APPLICATION, THE PERMIT SHALL BE DENIED, UNLESS THE
 APPLICANT CAN SHOW DETAILED, QUANTITY ESTIMATES, AND/OR
 BONA FIDE SIGNED CONTRACTS (EXCLUDING LAND VALUE) TO
 MEET THE APPROVAL OF THE BUILDING OFFICIAL. FOR
 PERMITTING PURPOSES, VALUATION OF BUILDINGS AND SYSTEMS
 SHALL BE TOTAL REPLACEMENT VALUE TO INCLUDE STRUCTURAL,
 ELECTRIC, PLUMBING, MECHANICAL, INTERIOR FINISH,
 RELATIVE SITE WORK, ARCHITECTURAL AND DESIGN FEES,
 MARKETING COSTS, OVERHEAD AND PROFIT; EXCLUDING ONLY
 LAND VALUE. VALUATION REFERENCES MAY INCLUDE THE LATEST
 PUBLISHED DATA OF NATIONAL CONSTRUCTION COST ANALYSIS
 SERVICES (MARSHALL-SWIFT, MEANS, ETC.), AS PUBLISHED BY
 INTERNATIONAL CODE CONGRESS.
 FINAL BUILDING PERMIT VALUATION SHALL BE SET BY THE
 BUILDING OFFICIAL.
  
 4. TWO EXTRA PLAN PAGE A-1 INCLUDED IN SUBMITTAL.
 REMOVE ANY EXCESSIVE DOCUMENTS FROM SUBMITTAL.
  
 5. NOTE ON PLAN PAGE A-1 STATES " TO THE BEST OF THE
 ARCHITECTS KNOWLEDGE". IS THERE AN ARCHITECT INVOLVED
 WITH THIS PROJECT PLEASE IDENTIFY.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO SUBMITTAL AND LEAVE THE PREVIOUSLY
 REVIEWED SHEETS DETACHED.
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2019-04-24 Cont ID  
Sent By cthroop Date 2019-04-24 Time 06:54 Rev Time 0.00
Received By cthroop Date 2019-04-19 Time 16:26 Sent To  
Notes
2019-04-24 07:08:56BUILDING PLAN REVIEW
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER, PX3169
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 2ND REVIEW
 RESULTS: DENIED
 YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED
 BELOW.
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 PREVIOUS COMMENTS THAT HAVE BEEN ADDRESSED
 SATISFACTORILY ARE MARKED AS CORRECTED. PREVIOUS
 COMMENTS THAT HAVE NOT BEEN ADDRESSED SATISFACTORILY
 HAVE ADDITIONAL COMMENTS IN PARENTHESES. ANY NEW
 COMMENT WILL BE LISTED AFTER PREVIOUS COMMENTS
  
 1. PROVIDE PRODUCT APPROVALS FOR PROPOSED EXT. DOORS. (
 STILL OPEN )
 2. REF. WINDOW SCH. PLAN PAGE A-1. ROUGH OPENING FOR
 PROPOSED WINDOW B IS 60 INCHES WIDE. PRODUCT APPROVAL
 FL19715 FO9R V1 SERIES 70 SH WINDOWS IS LIMITED TO 52
 INCHES WIDE. PROVIDE PRODUCT APPROVAL FOR PROPOSED
 WINDOW B.
 FBC 107.3.4 ? PROVIDE PRODUCT APPROVALS FOR THOSE
 PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED
 AND APPROVED IN WRITING BY THE DESIGNER OF RECORD.
 SPECIFICALLY, PROVIDE WINDOW AND DOOR SUBMITTALS.
 CORRECTED - PLAN PAGE A-1 REPLACED - WINDOW SCHEDULE
 NOW ON PAGE A-2
  
 3. PLAN PAGES S-1 AND S-2 SHOW WOOD FLOOR SYSTEM.THERE
 IS NO LOCATION IDENTIFIED ON PROPOSED FLOOR PLAN FOR
 THIS FLOOR SYSTEM. CORRECTED - PAGES S-1 AND S-2
 REMOVED FROM PLANS
 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
 CONSTRUCTION DOCUMENTS SHALL BE
 DIMENSIONED AND DRAWN UPON SUITABLE MATERIAL.
 CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT CLARITY
 TO INDICATE THE LOCATION, NATURE AND EXTENT OF THE WORK
 PROPOSED AND SHOW IN DETAIL THAT IT WILL CONFORM TO THE
 PROVISIONS OF THIS CODE AND RELEVANT LAWS, ORDINANCES,
 RULES AND REGULATIONS, AS DETERMINED BY THE BUILDING
 OFFICIAL.
  
 4. IF PROPOSED WOOD FLOOR SYSTEM IS FOR THE ENTIRE
 HOUSE, VALUE MUST BE ADJUSTED SUBSTANTIALLY. (SCOPPE OF
 WORK APPEARS TO HAVE EXPANDED - PROVIDE CONTRACT SIGNED
 BY OWNER/CONTRACTOR
 CITY OF WPB CHPT. 1 ? VALUE
 109.3 BUILDING PERMIT VALUATIONS. IF, IN THE OPINION OF
 THE BUILDING OFFICIAL, THE CLAIMED VALUATION OF
 BUILDING, ALTERATION, STRUCTURE, ELECTRICAL, GAS,
 MECHANICAL OR PLUMBING SYSTEMS APPEARS TO BE
 UNDERESTIMATED ON THE APPLICATION, THE PERMIT SHALL BE
 DENIED, UNLESS THE APPLICANT CAN SHOW DETAILED,
 QUANTITY ESTIMATES, AND/OR BONA FIDE SIGNED CONTRACTS
 (EXCLUDING LAND VALUE) TO MEET THE APPROVAL OF THE
 BUILDING OFFICIAL. FOR PERMITTING PURPOSES, VALUATION
 OF BUILDINGS AND SYSTEMS SHALL BE TOTAL REPLACEMENT
 VALUE TO INCLUDE STRUCTURAL, ELECTRIC, PLUMBING,
 MECHANICAL, INTERIOR FINISH, RELATIVE SITE WORK,
 ARCHITECTURAL AND DESIGN FEES, MARKETING COSTS,
 OVERHEAD AND PROFIT; EXCLUDING ONLY LAND VALUE.
 VALUATION REFERENCES MAY INCLUDE THE LATEST PUBLISHED
 DATA OF NATIONAL CONSTRUCTION
 COST ANALYSIS SERVICES (MARSHALL-SWIFT, MEANS, ETC.),
 AS PUBLISHED BY INTERNATIONAL CODE CONGRESS.
 FINAL BUILDING PERMIT VALUATION SHALL BE SET BY THE
 BUILDING OFFICIAL.
  
 5. PROVIDE EXISTING FLOOR PLAN. IDENTIFY ANY
 DEMOLITION. CORRECTED - APPEARS WHOLE INTERIOR WILL BE
 DEMOLISHED
  
 NEW COMMENTS
  
 6. TWO EXTRA PLAN PAGE A-1 INCLUDED IN SUBMITTAL.
 REMOVE ANY EXCESSIVE DOCUMENTS FROM SUBMITTAL.
  
 7. NOTE ON PLAN PAGE A-1 STATES " TO THE BEST OF THE
 ARCHITECTS KNOWLEDGE". IS THERE AN ARCHITECT INVOLVED
 WITH THIS PROJECT? PLEASE IDENTIFY.
  
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO SUBMITTAL AND LEAVE THE PREVIOUSLY
 REVIEWED SHEETS DETACHED.
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2018-11-06 Cont ID  
Sent By cthroop Date 2018-11-06 Time 14:45 Rev Time 0.00
Received By cthroop Date 2018-11-03 Time 12:17 Sent To  
Notes
2018-11-06 15:00:06BUILDING PLAN REVIEW
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER, PX3169
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 1ST REVIEW
 RESULTS: DENIED
 YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED
 BELOW.
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. PROVIDE PRODUCT APPROVALS FOR PROPOSED EXT. DOORS.
 2. REF. WINDOW SCH. PLAN PAGE A-1. ROUGH OPENING FOR
 PROPOSED WINDOW B IS 60 INCHES WIDE. PRODUCT APPROVAL
 FL19715 FO9R V1 SERIES 70 SH WINDOWS IS LIMITED TO 52
 INCHES WIDE. PROVIDE PRODUCT APPROVAL FOR PROPOSED
 WINDOW B.
 FBC 107.3.4 ? PROVIDE PRODUCT APPROVALS FOR THOSE
 PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED
 AND APPROVED IN WRITING BY THE DESIGNER OF RECORD.
 SPECIFICALLY, PROVIDE WINDOW AND DOOR SUBMITTALS.
  
 3. PLAN PAGES S-1 AND S-2 SHOW WOOD FLOOR SYSTEM.THERE
 IS NO LOCATION IDENTIFIED ON PROPOSED FLOOR PLAN FOR
 THIS FLOOR SYSTEM.
 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
 CONSTRUCTION DOCUMENTS SHALL BE
 DIMENSIONED AND DRAWN UPON SUITABLE MATERIAL.
 CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT CLARITY
 TO INDICATE THE LOCATION, NATURE AND EXTENT OF THE WORK
 PROPOSED AND SHOW IN DETAIL THAT IT WILL CONFORM TO THE
 PROVISIONS OF THIS CODE AND RELEVANT LAWS, ORDINANCES,
 RULES AND REGULATIONS, AS DETERMINED BY THE BUILDING
 OFFICIAL.
  
 4. IF PROPOSED WOOD FLOOR SYSTEM IS FOR THE ENTIRE
 HOUSE, VALUE MUST BE ADJUSTED SUBSTANTIALLY.
 CITY OF WPB CHPT. 1 ? VALUE
 109.3 BUILDING PERMIT VALUATIONS. IF, IN THE OPINION OF
 THE BUILDING OFFICIAL, THE CLAIMED VALUATION OF
 BUILDING, ALTERATION, STRUCTURE, ELECTRICAL, GAS,
 MECHANICAL OR PLUMBING SYSTEMS APPEARS TO BE
 UNDERESTIMATED ON THE APPLICATION, THE PERMIT SHALL BE
 DENIED, UNLESS THE APPLICANT CAN SHOW DETAILED,
 QUANTITY ESTIMATES, AND/OR BONA FIDE SIGNED CONTRACTS
 (EXCLUDING LAND VALUE) TO MEET THE APPROVAL OF THE
 BUILDING OFFICIAL. FOR PERMITTING PURPOSES, VALUATION
 OF BUILDINGS AND SYSTEMS SHALL BE TOTAL REPLACEMENT
 VALUE TO INCLUDE STRUCTURAL, ELECTRIC, PLUMBING,
 MECHANICAL, INTERIOR FINISH, RELATIVE SITE WORK,
 ARCHITECTURAL AND DESIGN FEES, MARKETING COSTS,
 OVERHEAD AND PROFIT; EXCLUDING ONLY LAND VALUE.
 VALUATION REFERENCES MAY INCLUDE THE LATEST PUBLISHED
 DATA OF NATIONAL CONSTRUCTION
 COST ANALYSIS SERVICES (MARSHALL-SWIFT, MEANS, ETC.),
 AS PUBLISHED BY INTERNATIONAL CODE CONGRESS.
 FINAL BUILDING PERMIT VALUATION SHALL BE SET BY THE
 BUILDING OFFICIAL.
  
 5. PROVIDE EXISTING FLOOR PLAN. IDENTIFY ANY
 DEMOLITION.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO SUBMITTAL AND LEAVE THE PREVIOUSLY
 REVIEWED SHEETS DETACHED.
  
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 7 Status P Date 2019-10-01 Cont ID  
Sent By cthroop Date 2019-10-01 Time 16:57 Rev Time 0.00
Received By cthroop Date 2019-09-27 Time 12:13 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 6 Status F Date 2019-08-26 Cont ID  
Sent By jpearson Date 2019-08-26 Time 13:51 Rev Time 0.00
Received By jpearson Date 2019-08-26 Time 09:20 Sent To  
Notes
2019-08-26 13:51:37CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
 FAC = FLORIDA ADMINISTRATIVE CODE
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 PREVIOUS COMMENTS THAT HAVE BEEN ADDRESSED
 SATISFACTORILY ARE MARKED AS CORRECTED. PREVIOUS
 COMMENTS THAT HAVE NOT BEEN ADDRESSED SATISFACTORILY
 HAVE ADDITIONAL COMMENTS IN PARENTHESES. ANY NEW
 COMMENTS WILL BE LISTED AFTER PREVIOUS COMMENTS.
  
 1. CORRECTED.
 2. CORRECTED.
 3. CORRECTED.
 4. CORRECTED.
 5. VALUE FOR WORK STATED ON PERMIT APPLICATION APPEARS
 LOW. PROVIDE COPY OF SIGNED CONTRACT WITH SCOPE AND
 VALUE OF WORK, TO INCLUDE ALL MATERIALS AND LABOR. THIS
 IS FOR TOTAL PROJECT, NOT JUST ELECTRICAL. WPB FBC
 109.3 (NOT PROVIDED.)
 6. CORRECTED.
 7. CORRECTED.
 8. CORRECTED.
 9. CORRECTED.
 10. IF THIS IS A NEW PANEL AND SERVICE AS THE PLAN
 SEEMS TO INDICATE, THEN PROVIDE AVAILABLE SHORT CIRCUIT
 CALCULATION FOR SERVICE INCLUDING INFORMATION FROM THE
 POWER COMPANY STATING WHAT THE AVAILABLE SHORT CIRCUIT
 CURRENT IS FOR THE SERVICE. INDICATE ON PLAN THE AIC
 RATING OF THE SERVICE EQUIPMENT TO CONFIRM IT IS
 ADEQUATE. NEC 110.9, 110.10; FBC RE E3606.3 (FPL LETTER
 PROVIDED STATES THAT THE AVAILABLE AIC IS 21110. RISER
 DIAGRAM SHOWS THE MAIN DISCONNECT AND PANEL RATED FOR
 ONLY 10000 AIC. PROVIDE CORRECTION.)
 11. CORRECTED.
 12. CORRECTED.
 13. CORRECTED.
 14. CORRECTED.
 15. CORRECTED.
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED ?OLD
 SHEETS?.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 5 Status F Date 2019-07-22 Cont ID  
Sent By jpearson Date 2019-07-22 Time 09:04 Rev Time 0.00
Received By jpearson Date 2019-07-22 Time 06:49 Sent To  
Notes
2019-07-22 09:04:24CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
 FAC = FLORIDA ADMINISTRATIVE CODE
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 PREVIOUS COMMENTS THAT HAVE BEEN ADDRESSED
 SATISFACTORILY ARE MARKED AS CORRECTED. PREVIOUS
 COMMENTS THAT HAVE NOT BEEN ADDRESSED SATISFACTORILY
 HAVE ADDITIONAL COMMENTS IN PARENTHESES. ANY NEW
 COMMENTS WILL BE LISTED AFTER PREVIOUS COMMENTS.
  
 1. CORRECTED.
 2. CORRECTED.
 3. CORRECTED.
 4. CORRECTED.
 5. VALUE FOR WORK STATED ON PERMIT APPLICATION APPEARS
 LOW. PROVIDE COPY OF SIGNED CONTRACT WITH SCOPE AND
 VALUE OF WORK, TO INCLUDE ALL MATERIALS AND LABOR. THIS
 IS FOR TOTAL PROJECT, NOT JUST ELECTRICAL. WPB FBC
 109.3 (NOT PROVIDED.)
 6. PROVIDE GFCI PROTECTION FOR DISHWASHER. NEC
 210.8(D); FBC RE E3902.10 (NOT PROVIDED.)
 7. LIGHTING IN BATHTUB OR SHOWER AREAS SHALL BE
 SUITABLE FOR DAMP LOCATIONS. THIS IS NOT IDENTIFIED ON
 PLAN. PROVIDE CORRECTION. NEC 410.10(D); FBC RE
 E4003.11 (NOT CORRECTED.)
 8. CORRECTED.
 9. CORRECTED.
 10. IF THIS IS A NEW PANEL AND SERVICE AS THE PLAN
 SEEMS TO INDICATE, THEN PROVIDE AVAILABLE SHORT CIRCUIT
 CALCULATION FOR SERVICE INCLUDING INFORMATION FROM THE
 POWER COMPANY STATING WHAT THE AVAILABLE SHORT CIRCUIT
 CURRENT IS FOR THE SERVICE. INDICATE ON PLAN THE AIC
 RATING OF THE SERVICE EQUIPMENT TO CONFIRM IT IS
 ADEQUATE. NEC 110.9, 110.10; FBC RE E3606.3 (NOT
 PROVIDED OR ADDRESSED.)
 11. 4 TIMES FEE ADDED FOR PLAN REVIEW. THIS WILL BE
 ADJUSTED TO MATCH CORRECT CONTRACT VALUE WHEN CONTRACT
 IS SUPPLIED.
 12. RISER DIAGRAM SHOWS THREE # 2 COPPER CONDUCTORS TO
 INTERIOR PANEL. THIS CONDUIT MUST CONTAIN AN EQUIPMENT
 GROUNDING CONDUCOTR, SIZED PER CODE. PROVIDE
 CORRECTION. NEC 250.122; FBC RE E3704.6, 3607.3.1 (NOT
 CORRECTED.)
 13. BATH 1 AND BATH 2 SHOW A 15 AMP CIRCUIT FOR THE
 BATHROOM INCLUDING THE RECEPTACLE OUTLETS. A MINIMUM OF
 ONE 20 AMPERE BRANCH CIRCUIT SHALL BE PROVIDED TO
 SUPPLY BATHROOM RECEPTACLE OUTLET(S). PROVIDE
 CORRECTION. NEC 210.11(C)(3) , FBC RE E3703.4 (NOT
 CORRECTED.)
 14. DINING ROOM RECEPTACLE OUTLETS ARE REQUIRED TO BE
 ON A 20 AMP CIRCUIT. PROVIDE CORRECTION. NEC
 210.52(B)(2); FBC RE E3703.2 (NOT CORRECTED.)
  
 NEW COMMENT:
  
 15. PER FAC 61G15-23.001 SIGNATURE, DATE AND SEAL SHALL
 BE AFFIXED. A PROFESSIONAL ENGINEER SHALL SIGN, DATE
 AND SEAL ALL FINAL PLANS, PRINTS, SPECIFICATIONS,
 REPORTS, OR OTHER DOCUMENTS PREPARED OR ISSUED BY THE
 LICENSEE AND BEING FILED FOR PUBLIC RECORD. THE DATE IS
 MISSING FROM THE ELECTRICAL PLAN. PROVIDE CORRECTION.
 WPB FBC 107.1; FAC 61G15-23.001
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED ?OLD
 SHEETS?.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 4 Status F Date 2019-06-26 Cont ID  
Sent By jpearson Date 2019-06-26 Time 11:12 Rev Time 0.00
Received By jpearson Date 2019-06-26 Time 10:37 Sent To I
Notes
2019-06-26 10:51:23CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 PREVIOUS COMMENTS THAT HAVE BEEN ADDRESSED
 SATISFACTORILY ARE MARKED AS CORRECTED. PREVIOUS
 COMMENTS THAT HAVE NOT BEEN ADDRESSED SATISFACTORILY
 HAVE ADDITIONAL COMMENTS IN PARENTHESES. ANY NEW
 COMMENTS WILL BE LISTED AFTER PREVIOUS COMMENTS.
  
 1. CORRECTED.
 2. CORRECTED.
 3. CORRECTED.
 4. CORRECTED.
 5. VALUE FOR WORK STATED ON PERMIT APPLICATION APPEARS
 LOW. PROVIDE COPY OF SIGNED CONTRACT WITH SCOPE AND
 VALUE OF WORK, TO INCLUDE ALL MATERIALS AND LABOR. THIS
 IS FOR TOTAL PROJECT, NOT JUST ELECTRICAL. WPB FBC
 109.3 (NOT PROVIDED.)
 6. PROVIDE GFCI PROTECTION FOR DISHWASHER. NEC
 210.8(D); FBC RE E3902.10 (NOT PROVIDED.)
 7. LIGHTING IN BATHTUB OR SHOWER AREAS SHALL BE
 SUITABLE FOR DAMP LOCATIONS. THIS IS NOT IDENTIFIED ON
 PLAN. PROVIDE CORRECTION. NEC 410.10(D); FBC RE
 E4003.11 (NOT CORRECTED.)
 8. CORRECTED.
 9. CORRECTED.
 10. IF THIS IS A NEW PANEL AND SERVICE AS THE PLAN
 SEEMS TO INDICATE, THEN PROVIDE AVAILABLE SHORT CIRCUIT
 CALCULATION FOR SERVICE INCLUDING INFORMATION FROM THE
 POWER COMPANY STATING WHAT THE AVAILABLE SHORT CIRCUIT
 CURRENT IS FOR THE SERVICE. INDICATE ON PLAN THE AIC
 RATING OF THE SERVICE EQUIPMENT TO CONFIRM IT IS
 ADEQUATE. NEC 110.9, 110.10; FBC RE E3606.3 (NOT
 PROVIDED.)
 11. PLEASE BE ADVISED THAT SOME OF THESE COMMENTS HAVE
 NOT BEEN ADDRESSED FOR TWO REVIEWS. IF UPON THE NEXT
 REVIEW, IF IT IS NECESSARY TO REJECT THE SUBMITTED PLAN
 AGAIN FOR THE SAME REASONS, AN ADDITIONAL PLAN REVIEW
 IS REQUIRED. FLORIDA STATUTES STATE: WITH RESPECT TO
 EVALUATION OF DESIGN PROFESSIONALS DOCUMENTS, IF A
 LOCAL GOVERNMENT FINDS IT NECESSARY, IN ORDER TO
 ENFORCE COMPLIANCE WITH THE FLORIDA BUILDING CODE AND
 ISSUE A PERMIT, TO REJECT DESIGN DOCUMENTS REQUIRED BY
 THE CODE THREE OR MORE TIMES FOR FAILURE TO CORRECT A
 CODE VIOLATION SPECIFICALLY AND CONTINUOUSLY NOTED IN
 EACH REJECTION, INCLUDING, BUT NOT LIMITED TO, EGRESS,
 FIRE PROTECTION, STRUCTURAL STABILITY, ENERGY,
 ACCESSIBILITY, LIGHTING, VENTILATION, ELECTRICAL,
 MECHANICAL, PLUMBING, AND GAS SYSTEMS, OR OTHER
 REQUIREMENTS IDENTIFIED BY RULE OF THE FLORIDA BUILDING
 COMMISSION ADOPTED PURSUANT TO CHAPTER 120, THE LOCAL
 GOVERNMENT SHALL IMPOSE, EACH TIME AFTER THE THIRD SUCH
 REVIEW THE PLANS ARE REJECTED FOR THAT CODE VIOLATION,
 A FEE OF FOUR TIMES THE AMOUNT OF THE PROPORTION OF THE
 PERMIT FEE ATTRIBUTED TO PLANS REVIEW. FS 553.80(2)(B)
 THE ADDITIONAL FEE FOR THIS PROJECT WOULD BE $440.00,
 BASED ON CURRENT VALUE OF PROJECT.
  
 NEW COMMENTS:
  
 12. RISER DIAGRAM SHOWS THREE # 2 COPPER CONDUCTORS TO
 INTERIOR PANEL. THIS CONDUIT MUST CONTAIN AN EQUIPMENT
 GROUNDING CONDUCOTR, SIZED PER CODE. PROVIDE
 CORRECTION. NEC 250.122; FBC RE E3704.6, 3607.3.1
 13. BATH 1 AND BATH 2 SHOW A 15 AMP CIRCUIT FOR THE
 BATHROOM INCLUDING THE RECEPTACLE OUTLETS. A MINIMUM OF
 ONE 20 AMPERE BRANCH CIRCUIT SHALL BE PROVIDED TO
 SUPPLY BATHROOM RECEPTACLE OUTLET(S). PROVIDE
 CORRECTION. NEC 210.11(C)(3) , FBC RE E3703.4
 14. DINING ROOM RECEPTACLE OUTLETS ARE REQUIRED TO BE
 ON A 20 AMP CIRCUIT. PROVIDE CORRECTION. NEC
 210.52(B)(2); FBC RE E3703.2
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED ?OLD
 SHEETS?.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2019-05-29 Cont ID  
Sent By jpearson Date 2019-05-29 Time 11:30 Rev Time 0.00
Received By jpearson Date 2019-05-29 Time 08:01 Sent To I
Notes
2019-05-29 10:37:16CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 PREVIOUS COMMENTS THAT HAVE BEEN ADDRESSED
 SATISFACTORILY ARE MARKED AS CORRECTED. PREVIOUS
 COMMENTS THAT HAVE NOT BEEN ADDRESSED SATISFACTORILY
 HAVE ADDITIONAL COMMENTS IN PARENTHESES. ANY NEW
 COMMENTS WILL BE LISTED AFTER PREVIOUS COMMENTS.
  
 1. AFCI PROTECTION SHOWN IN NOT CODE COMPLIANT. ALL
 BRANCH CIRCUITS THAT SUPPLY 120-VOLT, SINGLE-PHASE, 15-
 AND 20-AMPERE OUTLETS INSTALLED IN KITCHENS, FAMILY
 ROOMS, DINING ROOMS, LIVING ROOMS, PARLORS, LIBRARIES,
 DENS, BEDROOMS, SUN-ROOMS, RECREATIONS ROOMS, CLOSETS,
 HALLWAYS, LAUNDRY AREAS AND SIMILAR ROOMS OR AREAS
 SHALL BE AFCI PROTECTED. THIS INCLUDES LIGHTING AND
 POWER OUTLETS AND RECEPTACLES. SOME AREAS REQUIRE BOTH
 AFCI AND GFCI PROTECTION. PROVIDE CORRECTION. NEC
 210.8, 210.12; FBC RE E3902 (NOT PROVIDED.)
 2. CORRECTED.
 3. PROVIDE RISER DIAGRAM, SHOWING ALL DETAILS OF
 SERVICE EQUIPMENT, UNDERGROUND OR OVERHEAD SERVICE,
 WIRE AND BREAKER SIZES FOR SERVICE AND FEED TO ANY
 SUB-PANEL(S). SHOW GEC SIZE AND SYSTEM, SHOW
 INTERSYSTEM BONDING TERMINATION POINT. NEC 215.5, 230,
 250.50, 250.94, 408.30; FBC RE E3706.1, E3608.1,
 E3609.3; WPB FBC 107.2.1 (NOT PROVIDED.)
 4. PROVIDE LOCATION OF METER AND MAIN. (NOT PROVIDED.)
 5. VALUE FOR WORK STATED ON PERMIT APPLICATION APPEARS
 LOW. PROVIDE COPY OF SIGNED CONTRACT WITH SCOPE AND
 VALUE OF WORK, TO INCLUDE ALL MATERIALS AND LABOR. THIS
 IS FOR TOTAL PROJECT, NOT JUST ELECTRICAL. WPB FBC
 109.3 (NOT PROVIDED.)
  
 NEW COMMENTS:
  
 6. PROVIDE GFCI PROTECTION FOR DISHWASHER. NEC
 210.8(D); FBC RE E3902.10
 7. LIGHTING IN BATHTUB OR SHOWER AREAS SHALL BE
 SUITABLE FOR DAMP LOCATIONS. THIS IS NOT IDENTIFIED ON
 PLAN. PROVIDE CORRECTION. NEC 410.10(D); FBC RE
 E4003.11
 8. PROVIDE COMPLIANCE WITH FBC RE R314.3.1.
 9. LOAD CALCULATION STATES THAT A 125 AMP SERVICE WILL
 BE INSTALLED. THE PANEL SCHEDULE SHOWS A PANEL RATED
 FOR 100 AMPS. PROVIDE CORRECTION. NEC 408.30, 408.36;
 FBC RE E3706.3
 10. IF THIS IS A NEW PANEL AND SERVICE AS THE PLAN
 SEEMS TO INDICATE, THEN PROVIDE AVAILABLE SHORT CIRCUIT
 CALCULATION FOR SERVICE INCLUDING INFORMATION FROM THE
 POWER COMPANY STATING WHAT THE AVAILABLE SHORT CIRCUIT
 CURRENT IS FOR THE SERVICE. INDICATE ON PLAN THE AIC
 RATING OF THE SERVICE EQUIPMENT TO CONFIRM IT IS
 ADEQUATE. NEC 110.9, 110.10; FBC RE E3606.3
 11. PLEASE BE ADVISED THAT SOME OF THESE COMMENTS HAVE
 NOT BEEN ADDRESSED FOR TWO REVIEWS. IF UPON THE NEXT
 REVIEW, IF IT IS NECESSARY TO REJECT THE SUBMITTED PLAN
 AGAIN FOR THE SAME REASONS, AN ADDITIONAL PLAN REVIEW
 IS REQUIRED. FLORIDA STATUTES STATE: WITH RESPECT TO
 EVALUATION OF DESIGN PROFESSIONALS DOCUMENTS, IF A
 LOCAL GOVERNMENT FINDS IT NECESSARY, IN ORDER TO
 ENFORCE COMPLIANCE WITH THE FLORIDA BUILDING CODE AND
 ISSUE A PERMIT, TO REJECT DESIGN DOCUMENTS REQUIRED BY
 THE CODE THREE OR MORE TIMES FOR FAILURE TO CORRECT A
 CODE VIOLATION SPECIFICALLY AND CONTINUOUSLY NOTED IN
 EACH REJECTION, INCLUDING, BUT NOT LIMITED TO, EGRESS,
 FIRE PROTECTION, STRUCTURAL STABILITY, ENERGY,
 ACCESSIBILITY, LIGHTING, VENTILATION, ELECTRICAL,
 MECHANICAL, PLUMBING, AND GAS SYSTEMS, OR OTHER
 REQUIREMENTS IDENTIFIED BY RULE OF THE FLORIDA BUILDING
 COMMISSION ADOPTED PURSUANT TO CHAPTER 120, THE LOCAL
 GOVERNMENT SHALL IMPOSE, EACH TIME AFTER THE THIRD SUCH
 REVIEW THE PLANS ARE REJECTED FOR THAT CODE VIOLATION,
 A FEE OF FOUR TIMES THE AMOUNT OF THE PROPORTION OF THE
 PERMIT FEE ATTRIBUTED TO PLANS REVIEW. FS 553.80(2)(B)
 THE ADDITIONAL FEE FOR THIS PROJECT WOULD BE $440.00,
 BASED ON CURRENT VALUE OF PROJECT.
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED ?OLD
 SHEETS?.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2019-04-08 Cont ID  
Sent By ppetty Date 2019-04-08 Time 10:21 Rev Time 0.00
Received By ppetty Date 2019-04-08 Time 10:21 Sent To  
Notes
2019-04-08 10:21:27ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1.AFCI PROTECTION SHOWN IN NOT CODE COMPLIANT. ALL
 BRANCH CIRCUITS THAT SUPPLY 120-VOLT, SINGLE-PHASE, 15-
 AND 20-AMPERE OUTLETS INSTALLED IN KITCHENS, FAMILY
 ROOMS, DINING ROOMS, LIVING ROOMS, PARLORS, LIBRARIES,
 DENS, BEDROOMS, SUN-ROOMS, RECREATIONS ROOMS, CLOSETS,
 HALLWAYS, LAUNDRY AREAS AND SIMILAR ROOMS OR AREAS
 SHALL BE AFCI PROTECTED. THIS INCLUDES LIGHTING AND
 POWER OUTLETS AND RECEPTACLES. SOME AREAS REQUIRE BOTH
 AFCI AND GFCI PROTECTION. PROVIDE CORRECTION. NEC
 210.8, 210.12; FBC RE E3902
 2.PROVIDE LOAD CALCULATION FOR SERVICE, INCLUDE
 EXISTING AND NEW LOADS TO CONFIRM CAPACITY OF SERVICE
 IS ADEQUATE. NEC 215.2, 220, 408.30; FBC RE E3602.2
 3.PROVIDE RISER DIAGRAM, SHOWING ALL DETAILS OF SERVICE
 EQUIPMENT, UNDERGROUND OR OVERHEAD SERVICE, WIRE AND
 BREAKER SIZES FOR SERVICE AND FEED TO ANY SUB-PANEL(S).
 SHOW GEC SIZE AND SYSTEM, SHOW INTERSYSTEM BONDING
 TERMINATION POINT. NEC 215.5, 230, 250.50, 250.94,
 408.30; FBC RE E3706.1, E3608.1, E3609.3; WPB FBC
 107.2.1
 4.PROVIDE LOCATION OF METER AND MAIN.
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED ?OLD
 SHEETS?.
  
 SINCERELY,
  
 PHIL PETTY
 ELECTRICAL PLANS EXAMINER/CHIEF ELECTRICAL INSPECTOR
 561-805-6742
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2018-10-05 Cont ID  
Sent By jpearson Date 2018-10-05 Time 09:09 Rev Time 0.00
Received By jpearson Date 2018-10-05 Time 08:20 Sent To  
Notes
2018-10-05 09:04:57CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. VALUE FOR WORK STATED ON PERMIT APPLICATION APPEARS
 LOW. PROVIDE COPY OF SIGNED CONTRACT WITH SCOPE AND
 VALUE OF WORK, TO INCLUDE ALL MATERIALS AND LABOR. THIS
 IS FOR TOTAL PROJECT, NOT JUST ELECTRICAL. FBC 109.3
 2. PROVIDE ELECTRICAL PLAN FOR REVIEW, SIGNED AND
 SEALED BY THE PERSON RESPONSIBLE FOR THE DESIGN. WPB
 FBC 107.2.1, 107.3.5; FS 471 481
 3. PROVIDE RISER DIAGRAM, SHOWING ALL DETAILS OF
 SERVICE EQUIPMENT, UNDERGROUND OR OVERHEAD SERVICE,
 WIRE AND BREAKER SIZES FOR SERVICE AND FEED TO ANY
 SUB-PANEL(S). SHOW GEC SIZE AND SYSTEM, SHOW
 INTERSYSTEM BONDING TERMINATION POINT. NEC 215.5, 230,
 250.50, 250.94, 408.30; FBC RE E3706.1, E3608.1,
 E3609.3; WPB FBC 107.2.1
 4. PROVIDE PANEL SCHEDULE INDICATING ANY NEW OR ALTERED
 CIRCUITS, THE WIRE AND BREAKER SIZE FOR THESE CIRCUITS,
 AND AFCI OR GFCI PROTECTION WHERE APPLICABLE TO COMPLY
 WITH CODE. NEC 210.8, 210.12, 210.19, 210.20, 215.5,
 408.4; WPB FBC 107.3.5; FBC RE E3706.2, E3902
 5. PROVIDE LOAD CALCULATION FOR SERVICE, INCLUDE
 EXISTING AND NEW LOADS TO CONFIRM CAPACITY OF SERVICE
 IS ADEQUATE. NEC 215.2, 220, 408.30; FBC RE E3602.2
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD
 SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2019-10-02 Cont ID  
Sent By cpuell Date 2019-10-02 Time 09:42 Rev Time 0.00
Received By cpuell Date 2019-09-19 Time 13:43 Sent To  
Notes
2019-09-20 13:43:36R38

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2019-09-10 Cont ID  
Sent By cthroop Date 2019-09-10 Time 10:03 Rev Time 0.00
Received By cthroop Date 2019-08-12 Time 14:12 Sent To  
Notes
2019-08-13 14:13:08R38

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2019-07-30 Cont ID  
Sent By cpuell Date 2019-07-30 Time 10:19 Rev Time 0.00
Received By cpuell Date 2019-07-01 Time 15:12 Sent To  
Notes
2019-07-02 15:12:10R06

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date   Cont ID  
Sent By   Date 2019-06-26 Time   Rev Time 0.00
Received By lmarchan Date 2019-06-03 Time 15:53 Sent To  
Notes
2019-06-11 10:13:15PER JESMITH
 RETURNED PLANS TO BIN R06
 4TH PLBG REVIEW OBSERVED THAT NONE OF THE PREVIOUS
 COMMENTS FOR PLUMBING REVIEW 2 AND 3 HAVE BEEN
 ADDRESSED.
 CONTACTED GC; BUILD PRO CONSTRUCTION, INC., DAVIAN
 RODRIGUEZ PH: 786-740-2549 AND ADVISED. I WILL HOLD OFF
 REVIEW TO GIVE HIM AN OPPORTUNITY TO GET CORRECTED
 PLANS INSERTED INTO THE PRESENT SUBMITTAL.
  
2019-06-04 15:53:43R06

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date   Cont ID  
Sent By   Date 2019-05-29 Time   Rev Time 0.00
Received By lmarchan Date 2019-05-15 Time 15:05 Sent To  
Notes
2019-05-16 15:05:29R18

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2019-04-24 Cont ID  
Sent By cthroop Date 2019-04-24 Time 07:44 Rev Time 0.00
Received By cthroop Date 2019-03-28 Time 12:59 Sent To  
Notes
2019-03-29 12:59:11R14

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-11-06 Cont ID  
Sent By cthroop Date 2018-11-06 Time 15:00 Rev Time 0.00
Received By cthroop Date 2018-09-20 Time 13:07 Sent To  
Notes
2018-09-21 13:07:58R10

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status N Date 2018-11-06 Cont ID  
Sent By cthroop Date 2018-11-06 Time 14:45 Rev Time 0.00
Received By cthroop Date 2018-11-03 Time 12:17 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 4 Status N Date 2019-06-17 Cont ID  
Sent By cmontell Date 2019-06-17 Time 14:40 Rev Time 0.00
Received By cmontell Date 2019-06-17 Time 14:40 Sent To  
Notes
2019-06-17 14:46:15NO MECHANICAL WORK TO BE DONE ON THIS PERMIT PER OWNER
  
 PERMIT FOR AC REPLACEMENT ONLY NO DUCTWORK 18071057
  
 CHRIS MONTELLO
 805-6733

Review Stop M MECHANICAL (A/C)
Rev No 3 Status N Date 2019-05-28 Cont ID  
Sent By cmontell Date 2019-05-28 Time 13:25 Rev Time 0.00
Received By cmontell Date 2019-05-28 Time 14:14 Sent To  
Notes
2019-05-28 13:25:38NO MECHANICAL WORK TO BE DONE ON THIS PERMIT PER OWNER
  
 PERMIT FOR AC REPLACEMENT ONLY NO DUCTWORK 18071057
  
 CHRIS MONTELLO
 805-6733

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2019-04-24 Cont ID  
Sent By cthroop Date 2019-04-24 Time 07:39 Rev Time 0.00
Received By cthroop Date 2019-04-19 Time 16:26 Sent To  
Notes
2019-04-24 07:43:53MECHANICAL PLAN REVIEW
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 BUILDING PLANS EXAMINER, PX3169
 1&2 FAMILY PLANS EXAMINER, SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 2ND REVIEW
 RESULTS: DENIED
 YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED
 BELOW.
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. SECOND REQUEST - PROVIDE MECHANICAL PLAN.
  
 2. PROVIDE A WHOLE HOUSE ENERGY CALCULATION.
 FBCE-R101.5.1.1 BUILDING THERMAL ENVELOPE ALTERNATIVE.
 AN ACCURATELY COMPLETED RESIDENTIAL BUILDING FORM R402
 SHALL BE SUBMITTED TO THE BUILDING OFFICIAL TO
 DEMONSTRATE CODE COMPLIANCE BY THIS METHOD.
  
 FBCE-101.5.1.1.2 SIMULATED PERFORMANCE ALTERNATIVE.
 AN ACCURATELY COMPLETED RESIDENTIAL BUILDING FORM R405
 (GENERATED BY COMMISSION APPROVED SOFTWARE) SHALL BE
 SUBMITTED TO THE BUILDING OFFICIAL TO DEMONSTRATE CODE
 COMPLIANCE BY SECTION 405.
  
 3. PROVIDE EQUIPMENT SIZING CALCULATIONS.
 FBC E R403.7.1EQUIPMENT SIZING.
 HEATING AND COOLING EQUIPMENT SHALL BE SIZED IN
 ACCORDANCE WITH ACCA MANUAL S BASED ON THE EQUIPMENT
 LOADS CALCULATED IN ACCORDANCE WITH ACCA MANUAL J OR
 OTHER APPROVED HEATING AND COOLING CALCULATION
 METHODOLOGIES, BASED ON BUILDING LOADS FOR THE
 DIRECTIONAL ORIENTATION OF THE BUILDING. THE
 MANUFACTURER AND MODEL NUMBER OF THE OUTDOOR AND INDOOR
 UNITS (IF SPLIT SYSTEM) SHALL BE SUBMITTED ALONG WITH
 THE SENSIBLE AND TOTAL COOLING CAPACITIES AT THE DESIGN
 CONDITIONS DESCRIBED IN SECTION R302.1. THIS CODE DOES
 NOT ALLOW DESIGNER SAFETY FACTORS, PROVISIONS FOR
 FUTURE EXPANSION OR OTHER FACTORS THAT AFFECT EQUIPMENT
 SIZING. SYSTEM SIZING CALCULATIONS SHALL NOT INCLUDE
 LOADS CREATED BY LOCAL INTERMITTENT MECHANICAL
 VENTILATION SUCH AS STANDARD KITCHEN AND BATHROOM
 EXHAUST SYSTEMS. NEW OR REPLACEMENT HEATING AND COOLING
 EQUIPMENT SHALL HAVE AN EFFICIENCY RATING EQUAL TO OR
 GREATER THAN THE MINIMUM REQUIRED BY FEDERAL LAW FOR
 THE GEOGRAPHIC LOCATION WHERE THE EQUIPMENT IS
 INSTALLED.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO SUBMITTAL AND LEAVE THE PREVIOUSLY
 REVIEWED SHEETS DETACHED.
  
  
  
  
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2018-10-15 Cont ID  
Sent By cmontell Date 2018-10-15 Time 14:02 Rev Time 0.00
Received By cmontell Date 2018-10-15 Time 14:01 Sent To  
Notes
2018-10-15 14:02:44MECHANICAL PLAN REVIEW FAIL
  
 1 - NEED MECHANICAL PLAN PER FBC. SEC 107.1 GENERAL

Review Stop P PLUMBING
Rev No 5 Status P Date 2019-07-11 Cont ID  
Sent By gjohnson Date 2019-07-11 Time 18:02 Rev Time 0.00
Received By gjohnson Date 2019-07-11 Time 08:55 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 4 Status F Date 2019-06-11 Cont ID  
Sent By thunt Date 2019-06-11 Time 16:03 Rev Time 0.00
Received By thunt Date 2019-06-11 Time 12:39 Sent To  
Notes
2019-06-12 12:16:30P.E (MARTHA MCNICHOLAS) CALLEDL TODAY 6/12/19 ASKING
 FOR COMMENTS AS SHE HAS NOT SEEN ANY COMMENTS FROM THE
 2-4 REVIEW.EMAILED TO HER @ 12:15 A COPY OF THE 4TH
 REVIEW COMMENTS.
2019-06-11 16:08:54PLUMBING 4TH REVIEW**DENIED**A 4X PLAN REVIEW FEE HAS
 BEEN ADDED AS COMMENTS HAVE NOT BEEN ADDRESSED AND PLAN
 CHANGES EACH SUBMITTAL WILL CONTINUE TO CAUSE NEW
 COMMENTS PER F.S 553.80 (2) (B). PLEASE HAVE THE DESIGN
 PROFESSIONAL COME IN FOR A MEETING BEFORE RESUBMITTING.
 ERIC FROM BUILD PRO WAS CONTACTED AND ADVISED OF ISSUES
 AND ACKNOWLEDGE OF LAST PLAN REVIEWERS COMMENTS
 REQUESTING A MEETING BUT DUE TO DESIGN PROFESSIONALS
 SCHEDULE SHE WAS NOT ABLE TO COME IN. HE ADVISED HE
 WOULD HAVE DESIGN PROFESSIONAL CALL ME DIRECTLY WHICH
 AS OF 4:03 PM SHE HAS NOT NOR ANSWERED MY PHONE CALL.
  
 1) 4TH REQUEST. PROVIDE A CODE COMPLYING SANITARY
 ISOMETRIC DRAWING. (A) THE WATER CLOSET FIXTURE DRAIN
 NEEDS TO BE SIZED, SHOW A HORIZONTAL TO VERTICAL
 DISCHARGE PIPE WITH NO P-TRAP. (B) KITCHEN DRAIN SHALL
 NOT CONNECT INTO THE BATHROOM GROUP. KITCHEN LINE SHALL
 CONNECT DOWNSTREAM OF THE BATHROOM GROUP WET VENT.
 FBC-R P3108.1(C) CLOTHS WASHER FIXTURE DRAIN SHALL BE
 VENTED. FBC-R P 3101.2
  
 2) 3RD REQUEST. PROVIDE HAMMER ARRESTORS FOR THE CLOTHS
 WASHER. FBC-R P 2903.5
  
 3) 3RD REQUEST. IS THE CLOTHS WASHER OUTSIDE? SHOW THAT
 IT IS PROTECTED FROM THE ELEMENTS OR PROVIDE
 DOCUMENTATION THAT IT IS SUITABLE FOR OUTDOOR USE. FBC
 107.2.1
  
 4) PROVIDE WATER HEATER INSTALLATION MANUAL AS THE
 HEATER IS NOW SHOWING STORAGE TYPE. PROVIDE WATER
 PIPING DETAIL SHOWING DISCHARGE OF RELIEF LINE INTO THE
 ROOM IT SERVES AND PAN DRAIN LINE SHOWING IT DISCHARGES
 TO THE OUTSIDE. FBC-R P 2108.1, 2804
  
 NEW COMMENTS:
 5)PLUMBING PERMIT CALL OUT 2 BATHROOMS BOTH PLAN IS
 CURRENTLY ONLY SHOWING 1. PLEASE CLARIFY AND CHANGE
 SCOPE OF WORK ON PERMIT APPLICATION. FBC 107.2.1
  
 6)PER ERIC (GC) IT IS YOUR INTENTION TO 100% COMPLY
 WITH 2017 FLORIDA ACCESSIBILITY. IT SO PLEASE ADDRESS
 THE FOLLOWING COMMENTS OTHERWISE REMOVE ALL ADA ITEMS
 FROM PLAN AS I WILL NOT PUT MY SIGNATURE ON A PLAN THAT
 DOES NOT SHOW CODE COMPLIANT ACCESSIBILITY.
 1. SHOW ON ALL SHEETS THE MIN SIZE PERMITTED FOR THE
 SHOWER ALT ROLL IN AS 36? X 60. SHT A-1 DETAIL SHOWS 2?
 9? SEE FBC-ACC 608.2.3
 2. GRAB BARS SHALL BE 33?-36? TO THE TOP OF THE
 GRIPPING SURFACE AND NOT THE CENTER OF THE BAR. FBC-ACC
 608.4
 3. SHOW WASHING MACHINE AS COMPLYING WITH FBC-ACC 611.
 CLEAR FLOOR SPACE, OPERABLE PARTS HEIGHT, ETC
 4. PROVIDE CLEAR FLOOR SPACE FOR THE ALT ROLL IN
 SHOWER. FBC-ACC 608.2.2.1
 5. PROVIDE KITCHEN DETAIL TO INCLUDE CLEAR FLOOR SPACE,
 COUNTER TOP HEIGHT, AND TUNING SPACE. FBC-ACC 606.2,
 606.3
 6. MIRROR SHALL BE MAX 40? TO THE BOTTOM OF THE
 REFLECTIVE SURFACE. YOU CALL OUT 3? 6? (42?) ON DETAIL
 #6 SHT. A-2. FBC-ACC 603.3
 7. LIST 2017 FLORIDA ACCESSIBILITY CODE AS APPLICABLE
 CODE ON SHT. A-1
  
 7) VALUE APPEARS LOW AND HAS BEEN ADDRESSED BY OTHER
 PLAN REVIEWERS BUT NO SUPPORTING DOCUMENTATION HAS BEEN
 PROVIDE. PROVIDE A SIGNED BONA FIDE CONTRACT FOR THE
 ENTIRE JOB. WPB AMEND 109.3
  
  
  
 TIM HUNT
 PLUMBING PLANS EXAMINER/ PLUMBING INSPECTOR
 BUILDING DIVISION
 CITY OF WEST PALM BEACH
 401 CLEMATIS STREET, 1ST FLOOR
  

Review Stop P PLUMBING
Rev No 3 Status F Date 2019-05-17 Cont ID  
Sent By gjohnson Date 2019-05-17 Time 09:48 Rev Time 0.00
Received By gjohnson Date 2019-05-17 Time 09:03 Sent To  
Notes
2019-05-17 09:55:26CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 WPB CCC = WEST PALM BEACH CROSS CONNECTION CONTROL
 MANUAL
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RES = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 FBC ACC = FLORIDA ACCESSIBILITY CODE 2017 6TH EDITION
 FBC EX = FLORIDA EXISTING BUILDING CODE 2017 6TH
 EDITION
 FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION
 FBC FG = FLORIDA FUEL GAS CODE 2017 6TH EDITION
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
  
 3RD REVIEW:
 PLUMBING COMMENTS: DENIED! IT DOES NOT APPEAR THAT ANY
 OF THE PLUMBING COMMENTS WERE ADDRESSED. I SUGGEST A
 MEETING IN ORDER TO EXPEDITE APPROVAL OF THIS PERMIT,
 PLEASE CONTACT ME TO SET UP A TIME SEE CONTACT INFO
 BELOW.
  
 1. P-1 SANITARY RISER DIAGRAM
 A. PER WPB FBC 107.2.1, IDENTIFY THE TWO BATHROOM
 FIXTURES DOWNSTREAM OF BATHROOM SINK (LAVATORY) AND
 IDENTIFY BATHROOM SINK AS LAVATORY.
 B. PER WPB FBC 107.2.1, SIZE WATER CLOSET FIXTURE DRAIN
 AND REPLACE P-TRAP WITH A VERTICAL TO HORIZONTAL
 DISCHARGE PIPE.
 C. PER FBC RES P3108.1, KITCHEN SINK SHALL NOT CONNECT
 TO THE BATHROOM GROUP.
 D. PER FBC RES P3101.2, CLOTHES WASHER FIXTURE DRAIN
 SHALL BE VENTED.
 E. THE T&P DISCHARGE FROM THE WATER HEATER SHALL COMPLY
 WITH THE REQUIREMENTS OF FBC RES P2804.6.1 WHICH
 INCLUDES BUT IS NOT LIMITED TO DISCHARGING THROUGH AN
 AIR GAP IN THE SAME ROOM.
 2.P-1 WATER RISER DIAGRAM
 A. PER FBC RES P2903.5, PROVIDE WATER HAMMER ARRESTORS
 FOR CLOTHES WASHER.
 3. WATER HEATER INSTALLATION SHALL COMPLY WITH
 REQUIREMENTS OF FBC RES P2108.1 AND P2804
 4. IS CLOTHES WASHER OUTSIDE? PER WPB FBC 107.2.1, SHOW
 THAT IT IS PROTECTED FROM THE ELEMENTS OR PROVIDE
 DOCUMENTATION THAT IT IS SUITABLE FOR OUTDOOR USE.
  
 END OF COMMENTS
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, AA TRANSMITTAL LETTER LISTING THE
 ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF
 THE REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND WILL
 HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR
 ANTICIPATED COOPERATION.
  
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  

Review Stop P PLUMBING
Rev No 2 Status F Date 2019-04-09 Cont ID  
Sent By jesmith Date 2019-04-09 Time 15:11 Rev Time 0.00
Received By jesmith Date 2019-04-09 Time 07:52 Sent To  
Notes
2019-04-09 15:11:26CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 WPB CCC = WEST PALM BEACH CROSS CONNECTION CONTROL
 MANUAL
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RES = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 FBC ACC = FLORIDA ACCESSIBILITY CODE 2017 6TH EDITION
 FBC EX = FLORIDA EXISTING BUILDING CODE 2017 6TH
 EDITION
 FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION
 FBC FG = FLORIDA FUEL GAS CODE 2017 6TH EDITION
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
  
 2ND REVIEW:
 PLUMBING COMMENTS: DENIED
  
 1. P-1 SANITARY RISER DIAGRAM
 A. PER WPB FBC 107.2.1, IDENTIFY THE TWO BATHROOM
 FIXTURES DOWNSTREAM OF BATHROOM SINK (LAVATORY) AND
 IDENTIFY BATHROOM SINK AS LAVATORY.
 B. PER WPB FBC 107.2.1, SIZE WATER CLOSET FIXTURE DRAIN
 AND REPLACE P-TRAP WITH A VERTICAL TO HORIZONTAL
 DISCHARGE PIPE.
 C. PER FBC RES P3108.1, KITCHEN SINK SHALL NOT CONNECT
 TO THE BATHROOM GROUP.
 D. PER FBC RES P3101.2, CLOTHES WASHER FIXTURE DRAIN
 SHALL BE VENTED.
 E. THE T&P DISCHARGE FROM THE WATER HEATER SHALL COMPLY
 WITH THE REQIREMENTS OF FBC RES P2804.6.1 WHICH
 INCLUDES BUT IS NOT LIMITED TO DISCHARGING THROUGH AN
 AIR GAP IN THE SAME ROOM.
 2.P-1 WATER RISER DIAGRAM
 A. PER FBC RES P2903.5, PROVIDE WATER HAMMER ARRESTORS
 FOR CLOTHES WASHER.
 3. WATER HEATER INSTALLATION SHALL COMPLY WITH
 REQUIREMENTS OF FBC RES P2108.1 AND P2804
 4. IS CLOTHES WASHER OUTSIDE? PER WPB FBC 107.2.1, SHOW
 THAT IT IS PROTECTED FROM THE ELEMENTS OR PROVIDE
 DOCUMENTATION THAT IT IS SUITABLE FOR OUTDOOR USE.
  
 END OF COMMENTS
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, AA TRANSMITTAL LETTER LISTING THE
 ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF
 THE REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND WILL
 HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR
 ANTICIPATED COOPERATION.
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 PHONE 561-805-6715

Review Stop P PLUMBING
Rev No 1 Status F Date 2018-10-18 Cont ID  
Sent By jesmith Date 2018-10-18 Time 08:23 Rev Time 0.00
Received By jesmith Date 2018-10-18 Time 08:26 Sent To  
Notes
2018-10-18 08:23:22CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RES = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 FBC ACC = FLORIDA ACCESSIBILITY CODE 2017 6TH EDITION
 FBC EX = FLORIDA EXISTING BUILDING CODE 2017 6TH
 EDITION
 FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
 1ST REVIEW:
 PLUMBING COMMENTS: DENIED
  
 1. PROVIDE SANITARY RISER DIAGRAM PER WPB FBC
 107.3.5.3(13)
 2. HAND HELD SHOWER REQUIRES AN ATMOSPHERIC VACUUM
 BREAKER AT SHOWER ARM OUTLET PER FBC RES P2708.5.
 PLEASE NOTE ON PLAN.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 (STAMPED/SEALED AND SIGNED BY DESIGNER OF RECORD IN
 ACCORDANCE WITH FS 471 FAC 61G15) INTO THE ORIGINAL
 SUBMITTAL AND REMOVE THE PREVIOUSLY REVIEWED SHEETS.
 ONE COPY OF THE PREVIOUSLY REVIEWED SHEETS SHOULD
 REMAIN IN PACKAGE AND BE MARKED "VOID".
  
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 PHONE 561-805-6715

Review Stop Z ZONING
Rev No 6 Status P Date   Cont ID  
Sent By   Date 2019-10-02 Time   Rev Time 0.00
Received By pgreilic Date 2019-10-03 Time 09:44 Sent To  
Notes
2019-10-02 08:57:51 
 1.) A LANDSCAPE PERMIT IS REQUIRED
  
 PAUL GREILICH, SENIOR PLANNER
 561-822-1443
 [email protected]

Review Stop Z ZONING
Rev No 5 Status F Date   Cont ID  
Sent By   Date 2019-08-19 Time   Rev Time 0.00
Received By pgreilic Date 2019-08-19 Time 15:16 Sent To  
Notes
2019-08-19 15:27:161.) PROVIDE A LEGIBLE SITE PLAN INDICATING PROPOSED
 SETBACKS FOR ANY/ALL PROPOSED BUILDINGS OR EXPANSIONS,
 INCLUDING SETBACKS FOR ANY PROPOSED RAMPS
 2.) PROVIDE ARCHITECTURAL ELEVATIONS WITH HEIGHTS FOR
 ANY NEW CONSTRUCTION
 2.) A LANDSCAPE PERMIT IS REQUIRED
  
 PAUL GREILICH, SENIOR PLANNER
 561-822-1443
 [email protected]

Review Stop Z ZONING
Rev No 4 Status F Date   Cont ID  
Sent By   Date 2019-07-29 Time   Rev Time 0.00
Received By pgreilic Date 2019-07-29 Time 14:47 Sent To  
Notes
2019-07-29 14:49:301.) PROVIDE A LEGIBLE SITE PLAN INDICATING PROPOSED
 SETBACKS FOR ANY/ALL PROPOSED BUILDINGS OR EXPANSIONS,
 INCLUDING SETBACKS FOR ANY PROPOSED RAMPS
 2.) A LANDSCAPE PERMIT IS REQUIRED
  
 PAUL GREILICH, SENIOR PLANNER
 561-822-1443
 [email protected]

Review Stop Z ZONING
Rev No 3 Status F Date   Cont ID  
Sent By   Date 2019-06-13 Time   Rev Time 0.00
Received By pgreilic Date 2019-06-13 Time 12:09 Sent To  
Notes
2019-06-13 12:13:481.) PLEASE PROVIDE AN UPDATED SITE PLAN THAT SHOWS THE
 PROPOSED ADA RAMP AND LABEL THE SETBACK ACCORDINGLY
 2.) LANDSCAPE PERMIT REQUIRED
  
 PAUL GREILICH, AICP, SENIOR PLANNER
 561-822-1443
 [email protected]

Review Stop Z ZONING
Rev No 2 Status P Date   Cont ID  
Sent By   Date 2019-04-15 Time   Rev Time 0.00
Received By pgreilic Date 2019-04-15 Time 10:42 Sent To  
Notes
2019-04-15 10:43:071.) LANDSCAPE PERMIT REQUIRED
  
 PAUL GREILICH, AICP, SENIOR PLANNER
 561-822-1443
 [email protected]

Review Stop Z ZONING
Rev No 1 Status P Date   Cont ID  
Sent By pgreilic Date 2018-10-04 Time   Rev Time 0.00
Received By pgreilic Date 2018-10-02 Time 16:43 Sent To  
Notes
2018-10-04 12:56:311.) LANDSCAPE PERMIT REQUIRED
  
 PAUL GREILICH, AICP, SENIOR PLANNER
 561-822-1443
 [email protected]


Account Summary | Usage Policy | Privacy Policy