Plan Review Details - Permit 18090868
| Plan Review Stops For Permit 18090868 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
7 |
Status |
P |
Date |
2019-10-01 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2019-10-01 |
Time |
16:57 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2019-09-27 |
Time |
12:13 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
6 |
Status |
F |
Date |
2019-09-10 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2019-09-10 |
Time |
10:02 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2019-09-10 |
Time |
10:02 |
Sent To |
|
|
| Notes |
| 2019-09-10 10:03:53 | BUILDING PLAN REVIEW | | | 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST | | | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, | | | CHAPTER 1 ADMINISTRATION | | | | | | CHRISTOPHER S. THROOP, C.B.O. | | | BUILDING PLANS EXAMINER, PX3169 | | | 1&2 FAMILY PLANS EXAMINER, SFP306 | | | CONSTRUCTION SERVICES DIVISION | | | TEL: 561-805-6726 | | | FAX: 561-805-6676 | | | E-MAIL: [email protected] | | | | | | 6TH REVIEW | | | RESULTS: DENIED | | | YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED | | | BELOW. | | | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT | | | | | | REPEAT COMMENTS | | | | | | 1. PROVIDE PRODUCT APPROVALS FOR WINDOW MULLIONS FOR | | | WINDOWS 4 & 5. | | | FBC 107.3.4 ? PROVIDE PRODUCT APPROVALS FOR THOSE | | | PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED | | | AND APPROVED IN WRITING BY THE DESIGNER OF RECORD. | | | SPECIFICALLY, PROVIDE WINDOW MULLION SUBMITTALS. | | | | | | NOTICE: | | | | | | 4X FEES | | | | | | F.S. 553.80 (2) (B) | | | (B)?WITH RESPECT TO EVALUATION OF DESIGN PROFESSIONALS? | | | DOCUMENTS, IF A LOCAL GOVERNMENT FINDS IT NECESSARY, IN | | | ORDER TO ENFORCE COMPLIANCE WITH THE FLORIDA BUILDING | | | CODE AND ISSUE A PERMIT, TO REJECT DESIGN DOCUMENTS | | | REQUIRED BY THE CODE THREE OR MORE TIMES FOR FAILURE TO | | | CORRECT A CODE VIOLATION SPECIFICALLY AND CONTINUOUSLY | | | NOTED IN EACH REJECTION, INCLUDING, BUT NOT LIMITED TO, | | | EGRESS, FIRE PROTECTION, STRUCTURAL STABILITY, ENERGY, | | | ACCESSIBILITY, LIGHTING, VENTILATION, ELECTRICAL, | | | MECHANICAL, PLUMBING, AND GAS SYSTEMS, OR OTHER | | | REQUIREMENTS IDENTIFIED BY RULE OF THE FLORIDA BUILDING | | | COMMISSION ADOPTED PURSUANT TO CHAPTER 120, THE LOCAL | | | GOVERNMENT SHALL IMPOSE, EACH TIME AFTER THE THIRD SUCH | | | REVIEW THE PLANS ARE REJECTED FOR THAT CODE VIOLATION, | | | A FEE OF FOUR TIMES THE AMOUNT OF THE PROPORTION OF THE | | | PERMIT FEE ATTRIBUTED TO PLANS REVIEW. | | | | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
5 |
Status |
F |
Date |
2019-07-25 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2019-07-25 |
Time |
14:55 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2019-07-24 |
Time |
17:22 |
Sent To |
Z |
|
| Notes |
| 2019-07-25 14:58:00 | BUILDING PLAN REVIEW | | | 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST | | | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, | | | CHAPTER 1 ADMINISTRATION | | | | | | CHRISTOPHER S. THROOP, C.B.O. | | | BUILDING PLANS EXAMINER, PX3169 | | | 1&2 FAMILY PLANS EXAMINER, SFP306 | | | CONSTRUCTION SERVICES DIVISION | | | TEL: 561-805-6726 | | | FAX: 561-805-6676 | | | E-MAIL: [email protected] | | | | | | 5TH REVIEW | | | RESULTS: DENIED | | | YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED | | | BELOW. | | | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT | | | | | | REPEAT COMMENTS | | | | | | 1. PROVIDE PRODUCT APPROVALS FOR WINDOW MULLIONS FOR | | | WINDOWS 4 & 5. | | | FBC 107.3.4 ? PROVIDE PRODUCT APPROVALS FOR THOSE | | | PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED | | | AND APPROVED IN WRITING BY THE DESIGNER OF RECORD. | | | SPECIFICALLY, PROVIDE WINDOW MULLION SUBMITTALS. | | | | | | NOTICE: | | | | | | 4X FEES | | | | | | F.S. 553.80 (2) (B) | | | (B)?WITH RESPECT TO EVALUATION OF DESIGN PROFESSIONALS? | | | DOCUMENTS, IF A LOCAL GOVERNMENT FINDS IT NECESSARY, IN | | | ORDER TO ENFORCE COMPLIANCE WITH THE FLORIDA BUILDING | | | CODE AND ISSUE A PERMIT, TO REJECT DESIGN DOCUMENTS | | | REQUIRED BY THE CODE THREE OR MORE TIMES FOR FAILURE TO | | | CORRECT A CODE VIOLATION SPECIFICALLY AND CONTINUOUSLY | | | NOTED IN EACH REJECTION, INCLUDING, BUT NOT LIMITED TO, | | | EGRESS, FIRE PROTECTION, STRUCTURAL STABILITY, ENERGY, | | | ACCESSIBILITY, LIGHTING, VENTILATION, ELECTRICAL, | | | MECHANICAL, PLUMBING, AND GAS SYSTEMS, OR OTHER | | | REQUIREMENTS IDENTIFIED BY RULE OF THE FLORIDA BUILDING | | | COMMISSION ADOPTED PURSUANT TO CHAPTER 120, THE LOCAL | | | GOVERNMENT SHALL IMPOSE, EACH TIME AFTER THE THIRD SUCH | | | REVIEW THE PLANS ARE REJECTED FOR THAT CODE VIOLATION, | | | A FEE OF FOUR TIMES THE AMOUNT OF THE PROPORTION OF THE | | | PERMIT FEE ATTRIBUTED TO PLANS REVIEW. | | | | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
4 |
Status |
F |
Date |
2019-06-24 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2019-06-24 |
Time |
10:24 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2019-06-24 |
Time |
10:06 |
Sent To |
|
|
| Notes |
| 2019-06-24 10:26:52 | BUILDING PLAN REVIEW | | | 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST | | | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, | | | CHAPTER 1 ADMINISTRATION | | | | | | CHRISTOPHER S. THROOP, C.B.O. | | | BUILDING PLANS EXAMINER, PX3169 | | | 1&2 FAMILY PLANS EXAMINER, SFP306 | | | CONSTRUCTION SERVICES DIVISION | | | TEL: 561-805-6726 | | | FAX: 561-805-6676 | | | E-MAIL: [email protected] | | | | | | 4TH REVIEW | | | RESULTS: DENIED | | | YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED | | | BELOW. | | | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT | | | | | | 1. PROVIDE PRODUCT APPROVALS FOR WINDOW MULLIONS FOR | | | WINDOWS 4 & 5. | | | FBC 107.3.4 ? PROVIDE PRODUCT APPROVALS FOR THOSE | | | PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED | | | AND APPROVED IN WRITING BY THE DESIGNER OF RECORD. | | | SPECIFICALLY, PROVIDE WINDOW MULLION SUBMITTALS. | | | | | | | | | | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
F |
Date |
2019-05-24 |
|
|
Cont ID |
|
| Sent By |
jduprey |
Date |
2019-05-24 |
Time |
07:56 |
Rev Time |
0.00 |
| Received By |
jduprey |
Date |
2019-05-23 |
Time |
10:25 |
Sent To |
|
|
| Notes |
| 2019-05-24 07:56:39 | BUILDING PLAN REVIEW | | | 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST | | | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, | | | CHAPTER 1 ADMINISTRATION | | | | | | JOSEAN A. DUPREY | | | BUILDING PLANS EXAMINER | | | CONSTRUCTION SERVICES DIVISION | | | TEL: 561-805-6716 | | | FAX: 561-805-6676 | | | E-MAIL: [email protected] | | | | | | | | | 3RD REVIEW | | | RESULTS: DENIED | | | YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED | | | BELOW. | | | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT | | | | | | PREVIOUS COMMENTS THAT HAVE BEEN ADDRESSED | | | SATISFACTORILY ARE MARKED AS CORRECTED. PREVIOUS | | | COMMENTS THAT HAVE NOT BEEN ADDRESSED SATISFACTORILY | | | HAVE ADDITIONAL COMMENTS IN PARENTHESES. ANY NEW | | | COMMENT WILL BE LISTED AFTER PREVIOUS COMMENTS | | | | | | ***REPEAT COMMENTS*** | | | 1. PROVIDE PRODUCT APPROVALS FOR PROPOSED EXT. DOORS. ( | | | STILL OPEN ) | | | | | | 2. REF. WINDOW SCH. PLAN PAGE A-1. ROUGH OPENING FOR | | | PROPOSED WINDOW B IS 60 INCHES WIDE. PRODUCT APPROVAL | | | FL19715 FO9R V1 SERIES 70 SH WINDOWS IS LIMITED TO 52 | | | INCHES WIDE. PROVIDE PRODUCT APPROVAL FOR PROPOSED | | | WINDOW B. | | | FBC 107.3.4 PROVIDE PRODUCT APPROVALS FOR THOSE | | | PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED | | | AND APPROVED IN WRITING BY THE DESIGNER OF RECORD. | | | SPECIFICALLY, PROVIDE WINDOW AND DOOR SUBMITTALS. | | | CORRECTED - PLAN PAGE A-1 REPLACED - WINDOW SCHEDULE | | | NOW ON PAGE A-2 | | | | | | 3. IF PROPOSED WOOD FLOOR SYSTEM IS FOR THE ENTIRE | | | HOUSE, VALUE MUST BE ADJUSTED SUBSTANTIALLY. (SCOPPE OF | | | WORK APPEARS TO HAVE EXPANDED - PROVIDE CONTRACT SIGNED | | | BY OWNER/CONTRACTOR | | | CITY OF WPB CHPT. 1 VALUE 109.3 BUILDING PERMIT | | | VALUATIONS. IF, IN THE OPINION OF THE BUILDING | | | OFFICIAL, THE CLAIMED VALUATION OF BUILDING, | | | ALTERATION, STRUCTURE, ELECTRICAL, GAS, MECHANICAL OR | | | PLUMBING SYSTEMS APPEARS TO BE UNDERESTIMATED ON THE | | | APPLICATION, THE PERMIT SHALL BE DENIED, UNLESS THE | | | APPLICANT CAN SHOW DETAILED, QUANTITY ESTIMATES, AND/OR | | | BONA FIDE SIGNED CONTRACTS (EXCLUDING LAND VALUE) TO | | | MEET THE APPROVAL OF THE BUILDING OFFICIAL. FOR | | | PERMITTING PURPOSES, VALUATION OF BUILDINGS AND SYSTEMS | | | SHALL BE TOTAL REPLACEMENT VALUE TO INCLUDE STRUCTURAL, | | | ELECTRIC, PLUMBING, MECHANICAL, INTERIOR FINISH, | | | RELATIVE SITE WORK, ARCHITECTURAL AND DESIGN FEES, | | | MARKETING COSTS, OVERHEAD AND PROFIT; EXCLUDING ONLY | | | LAND VALUE. VALUATION REFERENCES MAY INCLUDE THE LATEST | | | PUBLISHED DATA OF NATIONAL CONSTRUCTION COST ANALYSIS | | | SERVICES (MARSHALL-SWIFT, MEANS, ETC.), AS PUBLISHED BY | | | INTERNATIONAL CODE CONGRESS. | | | FINAL BUILDING PERMIT VALUATION SHALL BE SET BY THE | | | BUILDING OFFICIAL. | | | | | | 4. TWO EXTRA PLAN PAGE A-1 INCLUDED IN SUBMITTAL. | | | REMOVE ANY EXCESSIVE DOCUMENTS FROM SUBMITTAL. | | | | | | 5. NOTE ON PLAN PAGE A-1 STATES " TO THE BEST OF THE | | | ARCHITECTS KNOWLEDGE". IS THERE AN ARCHITECT INVOLVED | | | WITH THIS PROJECT PLEASE IDENTIFY. | | | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT | | | CORRECTED PAGES INTO SUBMITTAL AND LEAVE THE PREVIOUSLY | | | REVIEWED SHEETS DETACHED. | | | | | | | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2019-04-24 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2019-04-24 |
Time |
06:54 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2019-04-19 |
Time |
16:26 |
Sent To |
|
|
| Notes |
| 2019-04-24 07:08:56 | BUILDING PLAN REVIEW | | | 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST | | | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, | | | CHAPTER 1 ADMINISTRATION | | | | | | CHRISTOPHER S. THROOP, C.B.O. | | | PLANS EXAMINER, PX3169 | | | CONSTRUCTION SERVICES DIVISION | | | TEL: 561-805-6726 | | | FAX: 561-805-6676 | | | E-MAIL: [email protected] | | | | | | 2ND REVIEW | | | RESULTS: DENIED | | | YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED | | | BELOW. | | | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT | | | | | | PREVIOUS COMMENTS THAT HAVE BEEN ADDRESSED | | | SATISFACTORILY ARE MARKED AS CORRECTED. PREVIOUS | | | COMMENTS THAT HAVE NOT BEEN ADDRESSED SATISFACTORILY | | | HAVE ADDITIONAL COMMENTS IN PARENTHESES. ANY NEW | | | COMMENT WILL BE LISTED AFTER PREVIOUS COMMENTS | | | | | | 1. PROVIDE PRODUCT APPROVALS FOR PROPOSED EXT. DOORS. ( | | | STILL OPEN ) | | | 2. REF. WINDOW SCH. PLAN PAGE A-1. ROUGH OPENING FOR | | | PROPOSED WINDOW B IS 60 INCHES WIDE. PRODUCT APPROVAL | | | FL19715 FO9R V1 SERIES 70 SH WINDOWS IS LIMITED TO 52 | | | INCHES WIDE. PROVIDE PRODUCT APPROVAL FOR PROPOSED | | | WINDOW B. | | | FBC 107.3.4 ? PROVIDE PRODUCT APPROVALS FOR THOSE | | | PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED | | | AND APPROVED IN WRITING BY THE DESIGNER OF RECORD. | | | SPECIFICALLY, PROVIDE WINDOW AND DOOR SUBMITTALS. | | | CORRECTED - PLAN PAGE A-1 REPLACED - WINDOW SCHEDULE | | | NOW ON PAGE A-2 | | | | | | 3. PLAN PAGES S-1 AND S-2 SHOW WOOD FLOOR SYSTEM.THERE | | | IS NO LOCATION IDENTIFIED ON PROPOSED FLOOR PLAN FOR | | | THIS FLOOR SYSTEM. CORRECTED - PAGES S-1 AND S-2 | | | REMOVED FROM PLANS | | | 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. | | | CONSTRUCTION DOCUMENTS SHALL BE | | | DIMENSIONED AND DRAWN UPON SUITABLE MATERIAL. | | | CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT CLARITY | | | TO INDICATE THE LOCATION, NATURE AND EXTENT OF THE WORK | | | PROPOSED AND SHOW IN DETAIL THAT IT WILL CONFORM TO THE | | | PROVISIONS OF THIS CODE AND RELEVANT LAWS, ORDINANCES, | | | RULES AND REGULATIONS, AS DETERMINED BY THE BUILDING | | | OFFICIAL. | | | | | | 4. IF PROPOSED WOOD FLOOR SYSTEM IS FOR THE ENTIRE | | | HOUSE, VALUE MUST BE ADJUSTED SUBSTANTIALLY. (SCOPPE OF | | | WORK APPEARS TO HAVE EXPANDED - PROVIDE CONTRACT SIGNED | | | BY OWNER/CONTRACTOR | | | CITY OF WPB CHPT. 1 ? VALUE | | | 109.3 BUILDING PERMIT VALUATIONS. IF, IN THE OPINION OF | | | THE BUILDING OFFICIAL, THE CLAIMED VALUATION OF | | | BUILDING, ALTERATION, STRUCTURE, ELECTRICAL, GAS, | | | MECHANICAL OR PLUMBING SYSTEMS APPEARS TO BE | | | UNDERESTIMATED ON THE APPLICATION, THE PERMIT SHALL BE | | | DENIED, UNLESS THE APPLICANT CAN SHOW DETAILED, | | | QUANTITY ESTIMATES, AND/OR BONA FIDE SIGNED CONTRACTS | | | (EXCLUDING LAND VALUE) TO MEET THE APPROVAL OF THE | | | BUILDING OFFICIAL. FOR PERMITTING PURPOSES, VALUATION | | | OF BUILDINGS AND SYSTEMS SHALL BE TOTAL REPLACEMENT | | | VALUE TO INCLUDE STRUCTURAL, ELECTRIC, PLUMBING, | | | MECHANICAL, INTERIOR FINISH, RELATIVE SITE WORK, | | | ARCHITECTURAL AND DESIGN FEES, MARKETING COSTS, | | | OVERHEAD AND PROFIT; EXCLUDING ONLY LAND VALUE. | | | VALUATION REFERENCES MAY INCLUDE THE LATEST PUBLISHED | | | DATA OF NATIONAL CONSTRUCTION | | | COST ANALYSIS SERVICES (MARSHALL-SWIFT, MEANS, ETC.), | | | AS PUBLISHED BY INTERNATIONAL CODE CONGRESS. | | | FINAL BUILDING PERMIT VALUATION SHALL BE SET BY THE | | | BUILDING OFFICIAL. | | | | | | 5. PROVIDE EXISTING FLOOR PLAN. IDENTIFY ANY | | | DEMOLITION. CORRECTED - APPEARS WHOLE INTERIOR WILL BE | | | DEMOLISHED | | | | | | NEW COMMENTS | | | | | | 6. TWO EXTRA PLAN PAGE A-1 INCLUDED IN SUBMITTAL. | | | REMOVE ANY EXCESSIVE DOCUMENTS FROM SUBMITTAL. | | | | | | 7. NOTE ON PLAN PAGE A-1 STATES " TO THE BEST OF THE | | | ARCHITECTS KNOWLEDGE". IS THERE AN ARCHITECT INVOLVED | | | WITH THIS PROJECT? PLEASE IDENTIFY. | | | | | | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT | | | CORRECTED PAGES INTO SUBMITTAL AND LEAVE THE PREVIOUSLY | | | REVIEWED SHEETS DETACHED. | | | | | | | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2018-11-06 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2018-11-06 |
Time |
14:45 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2018-11-03 |
Time |
12:17 |
Sent To |
|
|
| Notes |
| 2018-11-06 15:00:06 | BUILDING PLAN REVIEW | | | 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST | | | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, | | | CHAPTER 1 ADMINISTRATION | | | | | | CHRISTOPHER S. THROOP, C.B.O. | | | PLANS EXAMINER, PX3169 | | | CONSTRUCTION SERVICES DIVISION | | | TEL: 561-805-6726 | | | FAX: 561-805-6676 | | | E-MAIL: [email protected] | | | | | | 1ST REVIEW | | | RESULTS: DENIED | | | YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED | | | BELOW. | | | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT | | | | | | 1. PROVIDE PRODUCT APPROVALS FOR PROPOSED EXT. DOORS. | | | 2. REF. WINDOW SCH. PLAN PAGE A-1. ROUGH OPENING FOR | | | PROPOSED WINDOW B IS 60 INCHES WIDE. PRODUCT APPROVAL | | | FL19715 FO9R V1 SERIES 70 SH WINDOWS IS LIMITED TO 52 | | | INCHES WIDE. PROVIDE PRODUCT APPROVAL FOR PROPOSED | | | WINDOW B. | | | FBC 107.3.4 ? PROVIDE PRODUCT APPROVALS FOR THOSE | | | PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED | | | AND APPROVED IN WRITING BY THE DESIGNER OF RECORD. | | | SPECIFICALLY, PROVIDE WINDOW AND DOOR SUBMITTALS. | | | | | | 3. PLAN PAGES S-1 AND S-2 SHOW WOOD FLOOR SYSTEM.THERE | | | IS NO LOCATION IDENTIFIED ON PROPOSED FLOOR PLAN FOR | | | THIS FLOOR SYSTEM. | | | 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. | | | CONSTRUCTION DOCUMENTS SHALL BE | | | DIMENSIONED AND DRAWN UPON SUITABLE MATERIAL. | | | CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT CLARITY | | | TO INDICATE THE LOCATION, NATURE AND EXTENT OF THE WORK | | | PROPOSED AND SHOW IN DETAIL THAT IT WILL CONFORM TO THE | | | PROVISIONS OF THIS CODE AND RELEVANT LAWS, ORDINANCES, | | | RULES AND REGULATIONS, AS DETERMINED BY THE BUILDING | | | OFFICIAL. | | | | | | 4. IF PROPOSED WOOD FLOOR SYSTEM IS FOR THE ENTIRE | | | HOUSE, VALUE MUST BE ADJUSTED SUBSTANTIALLY. | | | CITY OF WPB CHPT. 1 ? VALUE | | | 109.3 BUILDING PERMIT VALUATIONS. IF, IN THE OPINION OF | | | THE BUILDING OFFICIAL, THE CLAIMED VALUATION OF | | | BUILDING, ALTERATION, STRUCTURE, ELECTRICAL, GAS, | | | MECHANICAL OR PLUMBING SYSTEMS APPEARS TO BE | | | UNDERESTIMATED ON THE APPLICATION, THE PERMIT SHALL BE | | | DENIED, UNLESS THE APPLICANT CAN SHOW DETAILED, | | | QUANTITY ESTIMATES, AND/OR BONA FIDE SIGNED CONTRACTS | | | (EXCLUDING LAND VALUE) TO MEET THE APPROVAL OF THE | | | BUILDING OFFICIAL. FOR PERMITTING PURPOSES, VALUATION | | | OF BUILDINGS AND SYSTEMS SHALL BE TOTAL REPLACEMENT | | | VALUE TO INCLUDE STRUCTURAL, ELECTRIC, PLUMBING, | | | MECHANICAL, INTERIOR FINISH, RELATIVE SITE WORK, | | | ARCHITECTURAL AND DESIGN FEES, MARKETING COSTS, | | | OVERHEAD AND PROFIT; EXCLUDING ONLY LAND VALUE. | | | VALUATION REFERENCES MAY INCLUDE THE LATEST PUBLISHED | | | DATA OF NATIONAL CONSTRUCTION | | | COST ANALYSIS SERVICES (MARSHALL-SWIFT, MEANS, ETC.), | | | AS PUBLISHED BY INTERNATIONAL CODE CONGRESS. | | | FINAL BUILDING PERMIT VALUATION SHALL BE SET BY THE | | | BUILDING OFFICIAL. | | | | | | 5. PROVIDE EXISTING FLOOR PLAN. IDENTIFY ANY | | | DEMOLITION. | | | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT | | | CORRECTED PAGES INTO SUBMITTAL AND LEAVE THE PREVIOUSLY | | | REVIEWED SHEETS DETACHED. | | | | | | | | | | | | | | | | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
7 |
Status |
P |
Date |
2019-10-01 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2019-10-01 |
Time |
16:57 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2019-09-27 |
Time |
12:13 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
6 |
Status |
F |
Date |
2019-08-26 |
|
|
Cont ID |
|
| Sent By |
jpearson |
Date |
2019-08-26 |
Time |
13:51 |
Rev Time |
0.00 |
| Received By |
jpearson |
Date |
2019-08-26 |
Time |
09:20 |
Sent To |
|
|
| Notes |
| 2019-08-26 13:51:37 | CODES IN EFFECT: | | | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION | | | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 | | | 6TH ED, CHAPTER 1. | | | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 | | | 6TH EDITION | | | FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017 | | | 6TH EDITION | | | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION | | | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE | | | FS = FLORIDA STATUTES | | | FAC = FLORIDA ADMINISTRATIVE CODE | | | | | | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | | | PREVIOUS COMMENTS THAT HAVE BEEN ADDRESSED | | | SATISFACTORILY ARE MARKED AS CORRECTED. PREVIOUS | | | COMMENTS THAT HAVE NOT BEEN ADDRESSED SATISFACTORILY | | | HAVE ADDITIONAL COMMENTS IN PARENTHESES. ANY NEW | | | COMMENTS WILL BE LISTED AFTER PREVIOUS COMMENTS. | | | | | | 1. CORRECTED. | | | 2. CORRECTED. | | | 3. CORRECTED. | | | 4. CORRECTED. | | | 5. VALUE FOR WORK STATED ON PERMIT APPLICATION APPEARS | | | LOW. PROVIDE COPY OF SIGNED CONTRACT WITH SCOPE AND | | | VALUE OF WORK, TO INCLUDE ALL MATERIALS AND LABOR. THIS | | | IS FOR TOTAL PROJECT, NOT JUST ELECTRICAL. WPB FBC | | | 109.3 (NOT PROVIDED.) | | | 6. CORRECTED. | | | 7. CORRECTED. | | | 8. CORRECTED. | | | 9. CORRECTED. | | | 10. IF THIS IS A NEW PANEL AND SERVICE AS THE PLAN | | | SEEMS TO INDICATE, THEN PROVIDE AVAILABLE SHORT CIRCUIT | | | CALCULATION FOR SERVICE INCLUDING INFORMATION FROM THE | | | POWER COMPANY STATING WHAT THE AVAILABLE SHORT CIRCUIT | | | CURRENT IS FOR THE SERVICE. INDICATE ON PLAN THE AIC | | | RATING OF THE SERVICE EQUIPMENT TO CONFIRM IT IS | | | ADEQUATE. NEC 110.9, 110.10; FBC RE E3606.3 (FPL LETTER | | | PROVIDED STATES THAT THE AVAILABLE AIC IS 21110. RISER | | | DIAGRAM SHOWS THE MAIN DISCONNECT AND PANEL RATED FOR | | | ONLY 10000 AIC. PROVIDE CORRECTION.) | | | 11. CORRECTED. | | | 12. CORRECTED. | | | 13. CORRECTED. | | | 14. CORRECTED. | | | 15. CORRECTED. | | | | | | END OF COMMENTS. | | | | | | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN | | | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES | | | INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY | | | REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED | | | SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED ?OLD | | | SHEETS?. | | | | | | SINCERELY, | | | | | | JOHN PEARSON | | | ELECTRICAL PLANS EXAMINER | | | 561-805-6746 | | | [email protected] | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
5 |
Status |
F |
Date |
2019-07-22 |
|
|
Cont ID |
|
| Sent By |
jpearson |
Date |
2019-07-22 |
Time |
09:04 |
Rev Time |
0.00 |
| Received By |
jpearson |
Date |
2019-07-22 |
Time |
06:49 |
Sent To |
|
|
| Notes |
| 2019-07-22 09:04:24 | CODES IN EFFECT: | | | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION | | | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 | | | 6TH ED, CHAPTER 1. | | | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 | | | 6TH EDITION | | | FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017 | | | 6TH EDITION | | | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION | | | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE | | | FS = FLORIDA STATUTES | | | FAC = FLORIDA ADMINISTRATIVE CODE | | | | | | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | | | PREVIOUS COMMENTS THAT HAVE BEEN ADDRESSED | | | SATISFACTORILY ARE MARKED AS CORRECTED. PREVIOUS | | | COMMENTS THAT HAVE NOT BEEN ADDRESSED SATISFACTORILY | | | HAVE ADDITIONAL COMMENTS IN PARENTHESES. ANY NEW | | | COMMENTS WILL BE LISTED AFTER PREVIOUS COMMENTS. | | | | | | 1. CORRECTED. | | | 2. CORRECTED. | | | 3. CORRECTED. | | | 4. CORRECTED. | | | 5. VALUE FOR WORK STATED ON PERMIT APPLICATION APPEARS | | | LOW. PROVIDE COPY OF SIGNED CONTRACT WITH SCOPE AND | | | VALUE OF WORK, TO INCLUDE ALL MATERIALS AND LABOR. THIS | | | IS FOR TOTAL PROJECT, NOT JUST ELECTRICAL. WPB FBC | | | 109.3 (NOT PROVIDED.) | | | 6. PROVIDE GFCI PROTECTION FOR DISHWASHER. NEC | | | 210.8(D); FBC RE E3902.10 (NOT PROVIDED.) | | | 7. LIGHTING IN BATHTUB OR SHOWER AREAS SHALL BE | | | SUITABLE FOR DAMP LOCATIONS. THIS IS NOT IDENTIFIED ON | | | PLAN. PROVIDE CORRECTION. NEC 410.10(D); FBC RE | | | E4003.11 (NOT CORRECTED.) | | | 8. CORRECTED. | | | 9. CORRECTED. | | | 10. IF THIS IS A NEW PANEL AND SERVICE AS THE PLAN | | | SEEMS TO INDICATE, THEN PROVIDE AVAILABLE SHORT CIRCUIT | | | CALCULATION FOR SERVICE INCLUDING INFORMATION FROM THE | | | POWER COMPANY STATING WHAT THE AVAILABLE SHORT CIRCUIT | | | CURRENT IS FOR THE SERVICE. INDICATE ON PLAN THE AIC | | | RATING OF THE SERVICE EQUIPMENT TO CONFIRM IT IS | | | ADEQUATE. NEC 110.9, 110.10; FBC RE E3606.3 (NOT | | | PROVIDED OR ADDRESSED.) | | | 11. 4 TIMES FEE ADDED FOR PLAN REVIEW. THIS WILL BE | | | ADJUSTED TO MATCH CORRECT CONTRACT VALUE WHEN CONTRACT | | | IS SUPPLIED. | | | 12. RISER DIAGRAM SHOWS THREE # 2 COPPER CONDUCTORS TO | | | INTERIOR PANEL. THIS CONDUIT MUST CONTAIN AN EQUIPMENT | | | GROUNDING CONDUCOTR, SIZED PER CODE. PROVIDE | | | CORRECTION. NEC 250.122; FBC RE E3704.6, 3607.3.1 (NOT | | | CORRECTED.) | | | 13. BATH 1 AND BATH 2 SHOW A 15 AMP CIRCUIT FOR THE | | | BATHROOM INCLUDING THE RECEPTACLE OUTLETS. A MINIMUM OF | | | ONE 20 AMPERE BRANCH CIRCUIT SHALL BE PROVIDED TO | | | SUPPLY BATHROOM RECEPTACLE OUTLET(S). PROVIDE | | | CORRECTION. NEC 210.11(C)(3) , FBC RE E3703.4 (NOT | | | CORRECTED.) | | | 14. DINING ROOM RECEPTACLE OUTLETS ARE REQUIRED TO BE | | | ON A 20 AMP CIRCUIT. PROVIDE CORRECTION. NEC | | | 210.52(B)(2); FBC RE E3703.2 (NOT CORRECTED.) | | | | | | NEW COMMENT: | | | | | | 15. PER FAC 61G15-23.001 SIGNATURE, DATE AND SEAL SHALL | | | BE AFFIXED. A PROFESSIONAL ENGINEER SHALL SIGN, DATE | | | AND SEAL ALL FINAL PLANS, PRINTS, SPECIFICATIONS, | | | REPORTS, OR OTHER DOCUMENTS PREPARED OR ISSUED BY THE | | | LICENSEE AND BEING FILED FOR PUBLIC RECORD. THE DATE IS | | | MISSING FROM THE ELECTRICAL PLAN. PROVIDE CORRECTION. | | | WPB FBC 107.1; FAC 61G15-23.001 | | | | | | END OF COMMENTS. | | | | | | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN | | | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES | | | INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY | | | REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED | | | SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED ?OLD | | | SHEETS?. | | | | | | SINCERELY, | | | | | | JOHN PEARSON | | | ELECTRICAL PLANS EXAMINER | | | 561-805-6746 | | | [email protected] | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
4 |
Status |
F |
Date |
2019-06-26 |
|
|
Cont ID |
|
| Sent By |
jpearson |
Date |
2019-06-26 |
Time |
11:12 |
Rev Time |
0.00 |
| Received By |
jpearson |
Date |
2019-06-26 |
Time |
10:37 |
Sent To |
I |
|
| Notes |
| 2019-06-26 10:51:23 | CODES IN EFFECT: | | | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION | | | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 | | | 6TH ED, CHAPTER 1. | | | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 | | | 6TH EDITION | | | FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017 | | | 6TH EDITION | | | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION | | | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE | | | FS = FLORIDA STATUTES | | | | | | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | | | PREVIOUS COMMENTS THAT HAVE BEEN ADDRESSED | | | SATISFACTORILY ARE MARKED AS CORRECTED. PREVIOUS | | | COMMENTS THAT HAVE NOT BEEN ADDRESSED SATISFACTORILY | | | HAVE ADDITIONAL COMMENTS IN PARENTHESES. ANY NEW | | | COMMENTS WILL BE LISTED AFTER PREVIOUS COMMENTS. | | | | | | 1. CORRECTED. | | | 2. CORRECTED. | | | 3. CORRECTED. | | | 4. CORRECTED. | | | 5. VALUE FOR WORK STATED ON PERMIT APPLICATION APPEARS | | | LOW. PROVIDE COPY OF SIGNED CONTRACT WITH SCOPE AND | | | VALUE OF WORK, TO INCLUDE ALL MATERIALS AND LABOR. THIS | | | IS FOR TOTAL PROJECT, NOT JUST ELECTRICAL. WPB FBC | | | 109.3 (NOT PROVIDED.) | | | 6. PROVIDE GFCI PROTECTION FOR DISHWASHER. NEC | | | 210.8(D); FBC RE E3902.10 (NOT PROVIDED.) | | | 7. LIGHTING IN BATHTUB OR SHOWER AREAS SHALL BE | | | SUITABLE FOR DAMP LOCATIONS. THIS IS NOT IDENTIFIED ON | | | PLAN. PROVIDE CORRECTION. NEC 410.10(D); FBC RE | | | E4003.11 (NOT CORRECTED.) | | | 8. CORRECTED. | | | 9. CORRECTED. | | | 10. IF THIS IS A NEW PANEL AND SERVICE AS THE PLAN | | | SEEMS TO INDICATE, THEN PROVIDE AVAILABLE SHORT CIRCUIT | | | CALCULATION FOR SERVICE INCLUDING INFORMATION FROM THE | | | POWER COMPANY STATING WHAT THE AVAILABLE SHORT CIRCUIT | | | CURRENT IS FOR THE SERVICE. INDICATE ON PLAN THE AIC | | | RATING OF THE SERVICE EQUIPMENT TO CONFIRM IT IS | | | ADEQUATE. NEC 110.9, 110.10; FBC RE E3606.3 (NOT | | | PROVIDED.) | | | 11. PLEASE BE ADVISED THAT SOME OF THESE COMMENTS HAVE | | | NOT BEEN ADDRESSED FOR TWO REVIEWS. IF UPON THE NEXT | | | REVIEW, IF IT IS NECESSARY TO REJECT THE SUBMITTED PLAN | | | AGAIN FOR THE SAME REASONS, AN ADDITIONAL PLAN REVIEW | | | IS REQUIRED. FLORIDA STATUTES STATE: WITH RESPECT TO | | | EVALUATION OF DESIGN PROFESSIONALS DOCUMENTS, IF A | | | LOCAL GOVERNMENT FINDS IT NECESSARY, IN ORDER TO | | | ENFORCE COMPLIANCE WITH THE FLORIDA BUILDING CODE AND | | | ISSUE A PERMIT, TO REJECT DESIGN DOCUMENTS REQUIRED BY | | | THE CODE THREE OR MORE TIMES FOR FAILURE TO CORRECT A | | | CODE VIOLATION SPECIFICALLY AND CONTINUOUSLY NOTED IN | | | EACH REJECTION, INCLUDING, BUT NOT LIMITED TO, EGRESS, | | | FIRE PROTECTION, STRUCTURAL STABILITY, ENERGY, | | | ACCESSIBILITY, LIGHTING, VENTILATION, ELECTRICAL, | | | MECHANICAL, PLUMBING, AND GAS SYSTEMS, OR OTHER | | | REQUIREMENTS IDENTIFIED BY RULE OF THE FLORIDA BUILDING | | | COMMISSION ADOPTED PURSUANT TO CHAPTER 120, THE LOCAL | | | GOVERNMENT SHALL IMPOSE, EACH TIME AFTER THE THIRD SUCH | | | REVIEW THE PLANS ARE REJECTED FOR THAT CODE VIOLATION, | | | A FEE OF FOUR TIMES THE AMOUNT OF THE PROPORTION OF THE | | | PERMIT FEE ATTRIBUTED TO PLANS REVIEW. FS 553.80(2)(B) | | | THE ADDITIONAL FEE FOR THIS PROJECT WOULD BE $440.00, | | | BASED ON CURRENT VALUE OF PROJECT. | | | | | | NEW COMMENTS: | | | | | | 12. RISER DIAGRAM SHOWS THREE # 2 COPPER CONDUCTORS TO | | | INTERIOR PANEL. THIS CONDUIT MUST CONTAIN AN EQUIPMENT | | | GROUNDING CONDUCOTR, SIZED PER CODE. PROVIDE | | | CORRECTION. NEC 250.122; FBC RE E3704.6, 3607.3.1 | | | 13. BATH 1 AND BATH 2 SHOW A 15 AMP CIRCUIT FOR THE | | | BATHROOM INCLUDING THE RECEPTACLE OUTLETS. A MINIMUM OF | | | ONE 20 AMPERE BRANCH CIRCUIT SHALL BE PROVIDED TO | | | SUPPLY BATHROOM RECEPTACLE OUTLET(S). PROVIDE | | | CORRECTION. NEC 210.11(C)(3) , FBC RE E3703.4 | | | 14. DINING ROOM RECEPTACLE OUTLETS ARE REQUIRED TO BE | | | ON A 20 AMP CIRCUIT. PROVIDE CORRECTION. NEC | | | 210.52(B)(2); FBC RE E3703.2 | | | | | | END OF COMMENTS. | | | | | | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN | | | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES | | | INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY | | | REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED | | | SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED ?OLD | | | SHEETS?. | | | | | | SINCERELY, | | | | | | JOHN PEARSON | | | ELECTRICAL PLANS EXAMINER | | | 561-805-6746 | | | [email protected] | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
F |
Date |
2019-05-29 |
|
|
Cont ID |
|
| Sent By |
jpearson |
Date |
2019-05-29 |
Time |
11:30 |
Rev Time |
0.00 |
| Received By |
jpearson |
Date |
2019-05-29 |
Time |
08:01 |
Sent To |
I |
|
| Notes |
| 2019-05-29 10:37:16 | CODES IN EFFECT: | | | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION | | | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 | | | 6TH ED, CHAPTER 1. | | | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 | | | 6TH EDITION | | | FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017 | | | 6TH EDITION | | | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION | | | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE | | | FS = FLORIDA STATUTES | | | | | | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | | | PREVIOUS COMMENTS THAT HAVE BEEN ADDRESSED | | | SATISFACTORILY ARE MARKED AS CORRECTED. PREVIOUS | | | COMMENTS THAT HAVE NOT BEEN ADDRESSED SATISFACTORILY | | | HAVE ADDITIONAL COMMENTS IN PARENTHESES. ANY NEW | | | COMMENTS WILL BE LISTED AFTER PREVIOUS COMMENTS. | | | | | | 1. AFCI PROTECTION SHOWN IN NOT CODE COMPLIANT. ALL | | | BRANCH CIRCUITS THAT SUPPLY 120-VOLT, SINGLE-PHASE, 15- | | | AND 20-AMPERE OUTLETS INSTALLED IN KITCHENS, FAMILY | | | ROOMS, DINING ROOMS, LIVING ROOMS, PARLORS, LIBRARIES, | | | DENS, BEDROOMS, SUN-ROOMS, RECREATIONS ROOMS, CLOSETS, | | | HALLWAYS, LAUNDRY AREAS AND SIMILAR ROOMS OR AREAS | | | SHALL BE AFCI PROTECTED. THIS INCLUDES LIGHTING AND | | | POWER OUTLETS AND RECEPTACLES. SOME AREAS REQUIRE BOTH | | | AFCI AND GFCI PROTECTION. PROVIDE CORRECTION. NEC | | | 210.8, 210.12; FBC RE E3902 (NOT PROVIDED.) | | | 2. CORRECTED. | | | 3. PROVIDE RISER DIAGRAM, SHOWING ALL DETAILS OF | | | SERVICE EQUIPMENT, UNDERGROUND OR OVERHEAD SERVICE, | | | WIRE AND BREAKER SIZES FOR SERVICE AND FEED TO ANY | | | SUB-PANEL(S). SHOW GEC SIZE AND SYSTEM, SHOW | | | INTERSYSTEM BONDING TERMINATION POINT. NEC 215.5, 230, | | | 250.50, 250.94, 408.30; FBC RE E3706.1, E3608.1, | | | E3609.3; WPB FBC 107.2.1 (NOT PROVIDED.) | | | 4. PROVIDE LOCATION OF METER AND MAIN. (NOT PROVIDED.) | | | 5. VALUE FOR WORK STATED ON PERMIT APPLICATION APPEARS | | | LOW. PROVIDE COPY OF SIGNED CONTRACT WITH SCOPE AND | | | VALUE OF WORK, TO INCLUDE ALL MATERIALS AND LABOR. THIS | | | IS FOR TOTAL PROJECT, NOT JUST ELECTRICAL. WPB FBC | | | 109.3 (NOT PROVIDED.) | | | | | | NEW COMMENTS: | | | | | | 6. PROVIDE GFCI PROTECTION FOR DISHWASHER. NEC | | | 210.8(D); FBC RE E3902.10 | | | 7. LIGHTING IN BATHTUB OR SHOWER AREAS SHALL BE | | | SUITABLE FOR DAMP LOCATIONS. THIS IS NOT IDENTIFIED ON | | | PLAN. PROVIDE CORRECTION. NEC 410.10(D); FBC RE | | | E4003.11 | | | 8. PROVIDE COMPLIANCE WITH FBC RE R314.3.1. | | | 9. LOAD CALCULATION STATES THAT A 125 AMP SERVICE WILL | | | BE INSTALLED. THE PANEL SCHEDULE SHOWS A PANEL RATED | | | FOR 100 AMPS. PROVIDE CORRECTION. NEC 408.30, 408.36; | | | FBC RE E3706.3 | | | 10. IF THIS IS A NEW PANEL AND SERVICE AS THE PLAN | | | SEEMS TO INDICATE, THEN PROVIDE AVAILABLE SHORT CIRCUIT | | | CALCULATION FOR SERVICE INCLUDING INFORMATION FROM THE | | | POWER COMPANY STATING WHAT THE AVAILABLE SHORT CIRCUIT | | | CURRENT IS FOR THE SERVICE. INDICATE ON PLAN THE AIC | | | RATING OF THE SERVICE EQUIPMENT TO CONFIRM IT IS | | | ADEQUATE. NEC 110.9, 110.10; FBC RE E3606.3 | | | 11. PLEASE BE ADVISED THAT SOME OF THESE COMMENTS HAVE | | | NOT BEEN ADDRESSED FOR TWO REVIEWS. IF UPON THE NEXT | | | REVIEW, IF IT IS NECESSARY TO REJECT THE SUBMITTED PLAN | | | AGAIN FOR THE SAME REASONS, AN ADDITIONAL PLAN REVIEW | | | IS REQUIRED. FLORIDA STATUTES STATE: WITH RESPECT TO | | | EVALUATION OF DESIGN PROFESSIONALS DOCUMENTS, IF A | | | LOCAL GOVERNMENT FINDS IT NECESSARY, IN ORDER TO | | | ENFORCE COMPLIANCE WITH THE FLORIDA BUILDING CODE AND | | | ISSUE A PERMIT, TO REJECT DESIGN DOCUMENTS REQUIRED BY | | | THE CODE THREE OR MORE TIMES FOR FAILURE TO CORRECT A | | | CODE VIOLATION SPECIFICALLY AND CONTINUOUSLY NOTED IN | | | EACH REJECTION, INCLUDING, BUT NOT LIMITED TO, EGRESS, | | | FIRE PROTECTION, STRUCTURAL STABILITY, ENERGY, | | | ACCESSIBILITY, LIGHTING, VENTILATION, ELECTRICAL, | | | MECHANICAL, PLUMBING, AND GAS SYSTEMS, OR OTHER | | | REQUIREMENTS IDENTIFIED BY RULE OF THE FLORIDA BUILDING | | | COMMISSION ADOPTED PURSUANT TO CHAPTER 120, THE LOCAL | | | GOVERNMENT SHALL IMPOSE, EACH TIME AFTER THE THIRD SUCH | | | REVIEW THE PLANS ARE REJECTED FOR THAT CODE VIOLATION, | | | A FEE OF FOUR TIMES THE AMOUNT OF THE PROPORTION OF THE | | | PERMIT FEE ATTRIBUTED TO PLANS REVIEW. FS 553.80(2)(B) | | | THE ADDITIONAL FEE FOR THIS PROJECT WOULD BE $440.00, | | | BASED ON CURRENT VALUE OF PROJECT. | | | | | | END OF COMMENTS. | | | | | | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN | | | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES | | | INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY | | | REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED | | | SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED ?OLD | | | SHEETS?. | | | | | | SINCERELY, | | | | | | JOHN PEARSON | | | ELECTRICAL PLANS EXAMINER | | | 561-805-6746 | | | [email protected] | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
F |
Date |
2019-04-08 |
|
|
Cont ID |
|
| Sent By |
ppetty |
Date |
2019-04-08 |
Time |
10:21 |
Rev Time |
0.00 |
| Received By |
ppetty |
Date |
2019-04-08 |
Time |
10:21 |
Sent To |
|
|
| Notes |
| 2019-04-08 10:21:27 | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | | | 1.AFCI PROTECTION SHOWN IN NOT CODE COMPLIANT. ALL | | | BRANCH CIRCUITS THAT SUPPLY 120-VOLT, SINGLE-PHASE, 15- | | | AND 20-AMPERE OUTLETS INSTALLED IN KITCHENS, FAMILY | | | ROOMS, DINING ROOMS, LIVING ROOMS, PARLORS, LIBRARIES, | | | DENS, BEDROOMS, SUN-ROOMS, RECREATIONS ROOMS, CLOSETS, | | | HALLWAYS, LAUNDRY AREAS AND SIMILAR ROOMS OR AREAS | | | SHALL BE AFCI PROTECTED. THIS INCLUDES LIGHTING AND | | | POWER OUTLETS AND RECEPTACLES. SOME AREAS REQUIRE BOTH | | | AFCI AND GFCI PROTECTION. PROVIDE CORRECTION. NEC | | | 210.8, 210.12; FBC RE E3902 | | | 2.PROVIDE LOAD CALCULATION FOR SERVICE, INCLUDE | | | EXISTING AND NEW LOADS TO CONFIRM CAPACITY OF SERVICE | | | IS ADEQUATE. NEC 215.2, 220, 408.30; FBC RE E3602.2 | | | 3.PROVIDE RISER DIAGRAM, SHOWING ALL DETAILS OF SERVICE | | | EQUIPMENT, UNDERGROUND OR OVERHEAD SERVICE, WIRE AND | | | BREAKER SIZES FOR SERVICE AND FEED TO ANY SUB-PANEL(S). | | | SHOW GEC SIZE AND SYSTEM, SHOW INTERSYSTEM BONDING | | | TERMINATION POINT. NEC 215.5, 230, 250.50, 250.94, | | | 408.30; FBC RE E3706.1, E3608.1, E3609.3; WPB FBC | | | 107.2.1 | | | 4.PROVIDE LOCATION OF METER AND MAIN. | | | END OF COMMENTS. | | | | | | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN | | | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES | | | INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY | | | REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED | | | SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED ?OLD | | | SHEETS?. | | | | | | SINCERELY, | | | | | | PHIL PETTY | | | ELECTRICAL PLANS EXAMINER/CHIEF ELECTRICAL INSPECTOR | | | 561-805-6742 | | | [email protected] | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2018-10-05 |
|
|
Cont ID |
|
| Sent By |
jpearson |
Date |
2018-10-05 |
Time |
09:09 |
Rev Time |
0.00 |
| Received By |
jpearson |
Date |
2018-10-05 |
Time |
08:20 |
Sent To |
|
|
| Notes |
| 2018-10-05 09:04:57 | CODES IN EFFECT: | | | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION | | | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 | | | 6TH ED, CHAPTER 1. | | | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 | | | 6TH EDITION | | | FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017 | | | 6TH EDITION | | | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION | | | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE | | | FS = FLORIDA STATUTES | | | | | | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | | | 1. VALUE FOR WORK STATED ON PERMIT APPLICATION APPEARS | | | LOW. PROVIDE COPY OF SIGNED CONTRACT WITH SCOPE AND | | | VALUE OF WORK, TO INCLUDE ALL MATERIALS AND LABOR. THIS | | | IS FOR TOTAL PROJECT, NOT JUST ELECTRICAL. FBC 109.3 | | | 2. PROVIDE ELECTRICAL PLAN FOR REVIEW, SIGNED AND | | | SEALED BY THE PERSON RESPONSIBLE FOR THE DESIGN. WPB | | | FBC 107.2.1, 107.3.5; FS 471 481 | | | 3. PROVIDE RISER DIAGRAM, SHOWING ALL DETAILS OF | | | SERVICE EQUIPMENT, UNDERGROUND OR OVERHEAD SERVICE, | | | WIRE AND BREAKER SIZES FOR SERVICE AND FEED TO ANY | | | SUB-PANEL(S). SHOW GEC SIZE AND SYSTEM, SHOW | | | INTERSYSTEM BONDING TERMINATION POINT. NEC 215.5, 230, | | | 250.50, 250.94, 408.30; FBC RE E3706.1, E3608.1, | | | E3609.3; WPB FBC 107.2.1 | | | 4. PROVIDE PANEL SCHEDULE INDICATING ANY NEW OR ALTERED | | | CIRCUITS, THE WIRE AND BREAKER SIZE FOR THESE CIRCUITS, | | | AND AFCI OR GFCI PROTECTION WHERE APPLICABLE TO COMPLY | | | WITH CODE. NEC 210.8, 210.12, 210.19, 210.20, 215.5, | | | 408.4; WPB FBC 107.3.5; FBC RE E3706.2, E3902 | | | 5. PROVIDE LOAD CALCULATION FOR SERVICE, INCLUDE | | | EXISTING AND NEW LOADS TO CONFIRM CAPACITY OF SERVICE | | | IS ADEQUATE. NEC 215.2, 220, 408.30; FBC RE E3602.2 | | | | | | END OF COMMENTS. | | | | | | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN | | | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES | | | INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY | | | REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED | | | SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD | | | SHEETS. | | | | | | SINCERELY, | | | | | | JOHN PEARSON | | | ELECTRICAL PLANS EXAMINER | | | 561-805-6746 | | | [email protected] | | | |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
7 |
Status |
N |
Date |
2019-10-02 |
|
|
Cont ID |
|
| Sent By |
cpuell |
Date |
2019-10-02 |
Time |
09:42 |
Rev Time |
0.00 |
| Received By |
cpuell |
Date |
2019-09-19 |
Time |
13:43 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
6 |
Status |
N |
Date |
2019-09-10 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2019-09-10 |
Time |
10:03 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2019-08-12 |
Time |
14:12 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
5 |
Status |
N |
Date |
2019-07-30 |
|
|
Cont ID |
|
| Sent By |
cpuell |
Date |
2019-07-30 |
Time |
10:19 |
Rev Time |
0.00 |
| Received By |
cpuell |
Date |
2019-07-01 |
Time |
15:12 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
4 |
Status |
N |
Date |
|
|
|
Cont ID |
|
| Sent By |
|
Date |
2019-06-26 |
Time |
|
Rev Time |
0.00 |
| Received By |
lmarchan |
Date |
2019-06-03 |
Time |
15:53 |
Sent To |
|
|
| Notes |
| 2019-06-11 10:13:15 | PER JESMITH | | | RETURNED PLANS TO BIN R06 | | | 4TH PLBG REVIEW OBSERVED THAT NONE OF THE PREVIOUS | | | COMMENTS FOR PLUMBING REVIEW 2 AND 3 HAVE BEEN | | | ADDRESSED. | | | CONTACTED GC; BUILD PRO CONSTRUCTION, INC., DAVIAN | | | RODRIGUEZ PH: 786-740-2549 AND ADVISED. I WILL HOLD OFF | | | REVIEW TO GIVE HIM AN OPPORTUNITY TO GET CORRECTED | | | PLANS INSERTED INTO THE PRESENT SUBMITTAL. | | | | | 2019-06-04 15:53:43 | R06 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
|
|
|
Cont ID |
|
| Sent By |
|
Date |
2019-05-29 |
Time |
|
Rev Time |
0.00 |
| Received By |
lmarchan |
Date |
2019-05-15 |
Time |
15:05 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2019-04-24 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2019-04-24 |
Time |
07:44 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2019-03-28 |
Time |
12:59 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2018-11-06 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2018-11-06 |
Time |
15:00 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2018-09-20 |
Time |
13:07 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
IMPACT |
COUNTY IMPACT FEES |
| Rev No |
1 |
Status |
N |
Date |
2018-11-06 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2018-11-06 |
Time |
14:45 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2018-11-03 |
Time |
12:17 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
4 |
Status |
N |
Date |
2019-06-17 |
|
|
Cont ID |
|
| Sent By |
cmontell |
Date |
2019-06-17 |
Time |
14:40 |
Rev Time |
0.00 |
| Received By |
cmontell |
Date |
2019-06-17 |
Time |
14:40 |
Sent To |
|
|
| Notes |
| 2019-06-17 14:46:15 | NO MECHANICAL WORK TO BE DONE ON THIS PERMIT PER OWNER | | | | | | PERMIT FOR AC REPLACEMENT ONLY NO DUCTWORK 18071057 | | | | | | CHRIS MONTELLO | | | 805-6733 |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
3 |
Status |
N |
Date |
2019-05-28 |
|
|
Cont ID |
|
| Sent By |
cmontell |
Date |
2019-05-28 |
Time |
13:25 |
Rev Time |
0.00 |
| Received By |
cmontell |
Date |
2019-05-28 |
Time |
14:14 |
Sent To |
|
|
| Notes |
| 2019-05-28 13:25:38 | NO MECHANICAL WORK TO BE DONE ON THIS PERMIT PER OWNER | | | | | | PERMIT FOR AC REPLACEMENT ONLY NO DUCTWORK 18071057 | | | | | | CHRIS MONTELLO | | | 805-6733 |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
F |
Date |
2019-04-24 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2019-04-24 |
Time |
07:39 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2019-04-19 |
Time |
16:26 |
Sent To |
|
|
| Notes |
| 2019-04-24 07:43:53 | MECHANICAL PLAN REVIEW | | | 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST | | | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, | | | CHAPTER 1 ADMINISTRATION | | | | | | CHRISTOPHER S. THROOP, C.B.O. | | | BUILDING PLANS EXAMINER, PX3169 | | | 1&2 FAMILY PLANS EXAMINER, SFP306 | | | CONSTRUCTION SERVICES DIVISION | | | TEL: 561-805-6726 | | | FAX: 561-805-6676 | | | E-MAIL: [email protected] | | | | | | 2ND REVIEW | | | RESULTS: DENIED | | | YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED | | | BELOW. | | | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT | | | | | | 1. SECOND REQUEST - PROVIDE MECHANICAL PLAN. | | | | | | 2. PROVIDE A WHOLE HOUSE ENERGY CALCULATION. | | | FBCE-R101.5.1.1 BUILDING THERMAL ENVELOPE ALTERNATIVE. | | | AN ACCURATELY COMPLETED RESIDENTIAL BUILDING FORM R402 | | | SHALL BE SUBMITTED TO THE BUILDING OFFICIAL TO | | | DEMONSTRATE CODE COMPLIANCE BY THIS METHOD. | | | | | | FBCE-101.5.1.1.2 SIMULATED PERFORMANCE ALTERNATIVE. | | | AN ACCURATELY COMPLETED RESIDENTIAL BUILDING FORM R405 | | | (GENERATED BY COMMISSION APPROVED SOFTWARE) SHALL BE | | | SUBMITTED TO THE BUILDING OFFICIAL TO DEMONSTRATE CODE | | | COMPLIANCE BY SECTION 405. | | | | | | 3. PROVIDE EQUIPMENT SIZING CALCULATIONS. | | | FBC E R403.7.1EQUIPMENT SIZING. | | | HEATING AND COOLING EQUIPMENT SHALL BE SIZED IN | | | ACCORDANCE WITH ACCA MANUAL S BASED ON THE EQUIPMENT | | | LOADS CALCULATED IN ACCORDANCE WITH ACCA MANUAL J OR | | | OTHER APPROVED HEATING AND COOLING CALCULATION | | | METHODOLOGIES, BASED ON BUILDING LOADS FOR THE | | | DIRECTIONAL ORIENTATION OF THE BUILDING. THE | | | MANUFACTURER AND MODEL NUMBER OF THE OUTDOOR AND INDOOR | | | UNITS (IF SPLIT SYSTEM) SHALL BE SUBMITTED ALONG WITH | | | THE SENSIBLE AND TOTAL COOLING CAPACITIES AT THE DESIGN | | | CONDITIONS DESCRIBED IN SECTION R302.1. THIS CODE DOES | | | NOT ALLOW DESIGNER SAFETY FACTORS, PROVISIONS FOR | | | FUTURE EXPANSION OR OTHER FACTORS THAT AFFECT EQUIPMENT | | | SIZING. SYSTEM SIZING CALCULATIONS SHALL NOT INCLUDE | | | LOADS CREATED BY LOCAL INTERMITTENT MECHANICAL | | | VENTILATION SUCH AS STANDARD KITCHEN AND BATHROOM | | | EXHAUST SYSTEMS. NEW OR REPLACEMENT HEATING AND COOLING | | | EQUIPMENT SHALL HAVE AN EFFICIENCY RATING EQUAL TO OR | | | GREATER THAN THE MINIMUM REQUIRED BY FEDERAL LAW FOR | | | THE GEOGRAPHIC LOCATION WHERE THE EQUIPMENT IS | | | INSTALLED. | | | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT | | | CORRECTED PAGES INTO SUBMITTAL AND LEAVE THE PREVIOUSLY | | | REVIEWED SHEETS DETACHED. | | | | | | | | | | | | | | | |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2018-10-15 |
|
|
Cont ID |
|
| Sent By |
cmontell |
Date |
2018-10-15 |
Time |
14:02 |
Rev Time |
0.00 |
| Received By |
cmontell |
Date |
2018-10-15 |
Time |
14:01 |
Sent To |
|
|
| Notes |
| 2018-10-15 14:02:44 | MECHANICAL PLAN REVIEW FAIL | | | | | | 1 - NEED MECHANICAL PLAN PER FBC. SEC 107.1 GENERAL |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
5 |
Status |
P |
Date |
2019-07-11 |
|
|
Cont ID |
|
| Sent By |
gjohnson |
Date |
2019-07-11 |
Time |
18:02 |
Rev Time |
0.00 |
| Received By |
gjohnson |
Date |
2019-07-11 |
Time |
08:55 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
4 |
Status |
F |
Date |
2019-06-11 |
|
|
Cont ID |
|
| Sent By |
thunt |
Date |
2019-06-11 |
Time |
16:03 |
Rev Time |
0.00 |
| Received By |
thunt |
Date |
2019-06-11 |
Time |
12:39 |
Sent To |
|
|
| Notes |
| 2019-06-12 12:16:30 | P.E (MARTHA MCNICHOLAS) CALLEDL TODAY 6/12/19 ASKING | | | FOR COMMENTS AS SHE HAS NOT SEEN ANY COMMENTS FROM THE | | | 2-4 REVIEW.EMAILED TO HER @ 12:15 A COPY OF THE 4TH | | | REVIEW COMMENTS. | | 2019-06-11 16:08:54 | PLUMBING 4TH REVIEW**DENIED**A 4X PLAN REVIEW FEE HAS | | | BEEN ADDED AS COMMENTS HAVE NOT BEEN ADDRESSED AND PLAN | | | CHANGES EACH SUBMITTAL WILL CONTINUE TO CAUSE NEW | | | COMMENTS PER F.S 553.80 (2) (B). PLEASE HAVE THE DESIGN | | | PROFESSIONAL COME IN FOR A MEETING BEFORE RESUBMITTING. | | | ERIC FROM BUILD PRO WAS CONTACTED AND ADVISED OF ISSUES | | | AND ACKNOWLEDGE OF LAST PLAN REVIEWERS COMMENTS | | | REQUESTING A MEETING BUT DUE TO DESIGN PROFESSIONALS | | | SCHEDULE SHE WAS NOT ABLE TO COME IN. HE ADVISED HE | | | WOULD HAVE DESIGN PROFESSIONAL CALL ME DIRECTLY WHICH | | | AS OF 4:03 PM SHE HAS NOT NOR ANSWERED MY PHONE CALL. | | | | | | 1) 4TH REQUEST. PROVIDE A CODE COMPLYING SANITARY | | | ISOMETRIC DRAWING. (A) THE WATER CLOSET FIXTURE DRAIN | | | NEEDS TO BE SIZED, SHOW A HORIZONTAL TO VERTICAL | | | DISCHARGE PIPE WITH NO P-TRAP. (B) KITCHEN DRAIN SHALL | | | NOT CONNECT INTO THE BATHROOM GROUP. KITCHEN LINE SHALL | | | CONNECT DOWNSTREAM OF THE BATHROOM GROUP WET VENT. | | | FBC-R P3108.1(C) CLOTHS WASHER FIXTURE DRAIN SHALL BE | | | VENTED. FBC-R P 3101.2 | | | | | | 2) 3RD REQUEST. PROVIDE HAMMER ARRESTORS FOR THE CLOTHS | | | WASHER. FBC-R P 2903.5 | | | | | | 3) 3RD REQUEST. IS THE CLOTHS WASHER OUTSIDE? SHOW THAT | | | IT IS PROTECTED FROM THE ELEMENTS OR PROVIDE | | | DOCUMENTATION THAT IT IS SUITABLE FOR OUTDOOR USE. FBC | | | 107.2.1 | | | | | | 4) PROVIDE WATER HEATER INSTALLATION MANUAL AS THE | | | HEATER IS NOW SHOWING STORAGE TYPE. PROVIDE WATER | | | PIPING DETAIL SHOWING DISCHARGE OF RELIEF LINE INTO THE | | | ROOM IT SERVES AND PAN DRAIN LINE SHOWING IT DISCHARGES | | | TO THE OUTSIDE. FBC-R P 2108.1, 2804 | | | | | | NEW COMMENTS: | | | 5)PLUMBING PERMIT CALL OUT 2 BATHROOMS BOTH PLAN IS | | | CURRENTLY ONLY SHOWING 1. PLEASE CLARIFY AND CHANGE | | | SCOPE OF WORK ON PERMIT APPLICATION. FBC 107.2.1 | | | | | | 6)PER ERIC (GC) IT IS YOUR INTENTION TO 100% COMPLY | | | WITH 2017 FLORIDA ACCESSIBILITY. IT SO PLEASE ADDRESS | | | THE FOLLOWING COMMENTS OTHERWISE REMOVE ALL ADA ITEMS | | | FROM PLAN AS I WILL NOT PUT MY SIGNATURE ON A PLAN THAT | | | DOES NOT SHOW CODE COMPLIANT ACCESSIBILITY. | | | 1. SHOW ON ALL SHEETS THE MIN SIZE PERMITTED FOR THE | | | SHOWER ALT ROLL IN AS 36? X 60. SHT A-1 DETAIL SHOWS 2? | | | 9? SEE FBC-ACC 608.2.3 | | | 2. GRAB BARS SHALL BE 33?-36? TO THE TOP OF THE | | | GRIPPING SURFACE AND NOT THE CENTER OF THE BAR. FBC-ACC | | | 608.4 | | | 3. SHOW WASHING MACHINE AS COMPLYING WITH FBC-ACC 611. | | | CLEAR FLOOR SPACE, OPERABLE PARTS HEIGHT, ETC | | | 4. PROVIDE CLEAR FLOOR SPACE FOR THE ALT ROLL IN | | | SHOWER. FBC-ACC 608.2.2.1 | | | 5. PROVIDE KITCHEN DETAIL TO INCLUDE CLEAR FLOOR SPACE, | | | COUNTER TOP HEIGHT, AND TUNING SPACE. FBC-ACC 606.2, | | | 606.3 | | | 6. MIRROR SHALL BE MAX 40? TO THE BOTTOM OF THE | | | REFLECTIVE SURFACE. YOU CALL OUT 3? 6? (42?) ON DETAIL | | | #6 SHT. A-2. FBC-ACC 603.3 | | | 7. LIST 2017 FLORIDA ACCESSIBILITY CODE AS APPLICABLE | | | CODE ON SHT. A-1 | | | | | | 7) VALUE APPEARS LOW AND HAS BEEN ADDRESSED BY OTHER | | | PLAN REVIEWERS BUT NO SUPPORTING DOCUMENTATION HAS BEEN | | | PROVIDE. PROVIDE A SIGNED BONA FIDE CONTRACT FOR THE | | | ENTIRE JOB. WPB AMEND 109.3 | | | | | | | | | | | | TIM HUNT | | | PLUMBING PLANS EXAMINER/ PLUMBING INSPECTOR | | | BUILDING DIVISION | | | CITY OF WEST PALM BEACH | | | 401 CLEMATIS STREET, 1ST FLOOR | | | |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
3 |
Status |
F |
Date |
2019-05-17 |
|
|
Cont ID |
|
| Sent By |
gjohnson |
Date |
2019-05-17 |
Time |
09:48 |
Rev Time |
0.00 |
| Received By |
gjohnson |
Date |
2019-05-17 |
Time |
09:03 |
Sent To |
|
|
| Notes |
| 2019-05-17 09:55:26 | CODES IN EFFECT: | | | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION | | | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 | | | 6TH ED, CHAPTER 1. | | | WPB CCC = WEST PALM BEACH CROSS CONNECTION CONTROL | | | MANUAL | | | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 | | | 6TH EDITION | | | FBC RES = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION | | | FBC ACC = FLORIDA ACCESSIBILITY CODE 2017 6TH EDITION | | | FBC EX = FLORIDA EXISTING BUILDING CODE 2017 6TH | | | EDITION | | | FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION | | | FBC FG = FLORIDA FUEL GAS CODE 2017 6TH EDITION | | | FAC= FLORIDA ADMINISTRATIVE CODE | | | FS = FLORIDA STATUTES | | | | | | | | | 3RD REVIEW: | | | PLUMBING COMMENTS: DENIED! IT DOES NOT APPEAR THAT ANY | | | OF THE PLUMBING COMMENTS WERE ADDRESSED. I SUGGEST A | | | MEETING IN ORDER TO EXPEDITE APPROVAL OF THIS PERMIT, | | | PLEASE CONTACT ME TO SET UP A TIME SEE CONTACT INFO | | | BELOW. | | | | | | 1. P-1 SANITARY RISER DIAGRAM | | | A. PER WPB FBC 107.2.1, IDENTIFY THE TWO BATHROOM | | | FIXTURES DOWNSTREAM OF BATHROOM SINK (LAVATORY) AND | | | IDENTIFY BATHROOM SINK AS LAVATORY. | | | B. PER WPB FBC 107.2.1, SIZE WATER CLOSET FIXTURE DRAIN | | | AND REPLACE P-TRAP WITH A VERTICAL TO HORIZONTAL | | | DISCHARGE PIPE. | | | C. PER FBC RES P3108.1, KITCHEN SINK SHALL NOT CONNECT | | | TO THE BATHROOM GROUP. | | | D. PER FBC RES P3101.2, CLOTHES WASHER FIXTURE DRAIN | | | SHALL BE VENTED. | | | E. THE T&P DISCHARGE FROM THE WATER HEATER SHALL COMPLY | | | WITH THE REQUIREMENTS OF FBC RES P2804.6.1 WHICH | | | INCLUDES BUT IS NOT LIMITED TO DISCHARGING THROUGH AN | | | AIR GAP IN THE SAME ROOM. | | | 2.P-1 WATER RISER DIAGRAM | | | A. PER FBC RES P2903.5, PROVIDE WATER HAMMER ARRESTORS | | | FOR CLOTHES WASHER. | | | 3. WATER HEATER INSTALLATION SHALL COMPLY WITH | | | REQUIREMENTS OF FBC RES P2108.1 AND P2804 | | | 4. IS CLOTHES WASHER OUTSIDE? PER WPB FBC 107.2.1, SHOW | | | THAT IT IS PROTECTED FROM THE ELEMENTS OR PROVIDE | | | DOCUMENTATION THAT IT IS SUITABLE FOR OUTDOOR USE. | | | | | | END OF COMMENTS | | | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN | | | RESUBMITTING, AA TRANSMITTAL LETTER LISTING THE | | | ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF | | | THE REVISION MADE, IDENTIFYING THE SHEET OR | | | SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND WILL | | | HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR | | | ANTICIPATED COOPERATION. | | | | | | | | | GEORGE JOHNSON | | | PLUMBING PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | 561-805-6711 | | | [email protected] | | | |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
F |
Date |
2019-04-09 |
|
|
Cont ID |
|
| Sent By |
jesmith |
Date |
2019-04-09 |
Time |
15:11 |
Rev Time |
0.00 |
| Received By |
jesmith |
Date |
2019-04-09 |
Time |
07:52 |
Sent To |
|
|
| Notes |
| 2019-04-09 15:11:26 | CODES IN EFFECT: | | | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION | | | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 | | | 6TH ED, CHAPTER 1. | | | WPB CCC = WEST PALM BEACH CROSS CONNECTION CONTROL | | | MANUAL | | | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 | | | 6TH EDITION | | | FBC RES = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION | | | FBC ACC = FLORIDA ACCESSIBILITY CODE 2017 6TH EDITION | | | FBC EX = FLORIDA EXISTING BUILDING CODE 2017 6TH | | | EDITION | | | FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION | | | FBC FG = FLORIDA FUEL GAS CODE 2017 6TH EDITION | | | FAC= FLORIDA ADMINISTRATIVE CODE | | | FS = FLORIDA STATUTES | | | | | | | | | 2ND REVIEW: | | | PLUMBING COMMENTS: DENIED | | | | | | 1. P-1 SANITARY RISER DIAGRAM | | | A. PER WPB FBC 107.2.1, IDENTIFY THE TWO BATHROOM | | | FIXTURES DOWNSTREAM OF BATHROOM SINK (LAVATORY) AND | | | IDENTIFY BATHROOM SINK AS LAVATORY. | | | B. PER WPB FBC 107.2.1, SIZE WATER CLOSET FIXTURE DRAIN | | | AND REPLACE P-TRAP WITH A VERTICAL TO HORIZONTAL | | | DISCHARGE PIPE. | | | C. PER FBC RES P3108.1, KITCHEN SINK SHALL NOT CONNECT | | | TO THE BATHROOM GROUP. | | | D. PER FBC RES P3101.2, CLOTHES WASHER FIXTURE DRAIN | | | SHALL BE VENTED. | | | E. THE T&P DISCHARGE FROM THE WATER HEATER SHALL COMPLY | | | WITH THE REQIREMENTS OF FBC RES P2804.6.1 WHICH | | | INCLUDES BUT IS NOT LIMITED TO DISCHARGING THROUGH AN | | | AIR GAP IN THE SAME ROOM. | | | 2.P-1 WATER RISER DIAGRAM | | | A. PER FBC RES P2903.5, PROVIDE WATER HAMMER ARRESTORS | | | FOR CLOTHES WASHER. | | | 3. WATER HEATER INSTALLATION SHALL COMPLY WITH | | | REQUIREMENTS OF FBC RES P2108.1 AND P2804 | | | 4. IS CLOTHES WASHER OUTSIDE? PER WPB FBC 107.2.1, SHOW | | | THAT IT IS PROTECTED FROM THE ELEMENTS OR PROVIDE | | | DOCUMENTATION THAT IT IS SUITABLE FOR OUTDOOR USE. | | | | | | END OF COMMENTS | | | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN | | | RESUBMITTING, AA TRANSMITTAL LETTER LISTING THE | | | ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF | | | THE REVISION MADE, IDENTIFYING THE SHEET OR | | | SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND WILL | | | HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR | | | ANTICIPATED COOPERATION. | | | | | | JERALD SMITH | | | PLUMBING PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | EMAIL [email protected] | | | PHONE 561-805-6715 |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2018-10-18 |
|
|
Cont ID |
|
| Sent By |
jesmith |
Date |
2018-10-18 |
Time |
08:23 |
Rev Time |
0.00 |
| Received By |
jesmith |
Date |
2018-10-18 |
Time |
08:26 |
Sent To |
|
|
| Notes |
| 2018-10-18 08:23:22 | CODES IN EFFECT: | | | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION | | | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 | | | 6TH ED, CHAPTER 1. | | | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 | | | 6TH EDITION | | | FBC RES = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION | | | FBC ACC = FLORIDA ACCESSIBILITY CODE 2017 6TH EDITION | | | FBC EX = FLORIDA EXISTING BUILDING CODE 2017 6TH | | | EDITION | | | FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION | | | FAC= FLORIDA ADMINISTRATIVE CODE | | | FS = FLORIDA STATUTES | | | | | | 1ST REVIEW: | | | PLUMBING COMMENTS: DENIED | | | | | | 1. PROVIDE SANITARY RISER DIAGRAM PER WPB FBC | | | 107.3.5.3(13) | | | 2. HAND HELD SHOWER REQUIRES AN ATMOSPHERIC VACUUM | | | BREAKER AT SHOWER ARM OUTLET PER FBC RES P2708.5. | | | PLEASE NOTE ON PLAN. | | | | | | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN | | | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES | | | (STAMPED/SEALED AND SIGNED BY DESIGNER OF RECORD IN | | | ACCORDANCE WITH FS 471 FAC 61G15) INTO THE ORIGINAL | | | SUBMITTAL AND REMOVE THE PREVIOUSLY REVIEWED SHEETS. | | | ONE COPY OF THE PREVIOUSLY REVIEWED SHEETS SHOULD | | | REMAIN IN PACKAGE AND BE MARKED "VOID". | | | | | | | | | JERALD SMITH | | | PLUMBING PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | EMAIL [email protected] | | | PHONE 561-805-6715 |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
6 |
Status |
P |
Date |
|
|
|
Cont ID |
|
| Sent By |
|
Date |
2019-10-02 |
Time |
|
Rev Time |
0.00 |
| Received By |
pgreilic |
Date |
2019-10-03 |
Time |
09:44 |
Sent To |
|
|
| Notes |
| 2019-10-02 08:57:51 | | | | 1.) A LANDSCAPE PERMIT IS REQUIRED | | | | | | PAUL GREILICH, SENIOR PLANNER | | | 561-822-1443 | | | [email protected] |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
5 |
Status |
F |
Date |
|
|
|
Cont ID |
|
| Sent By |
|
Date |
2019-08-19 |
Time |
|
Rev Time |
0.00 |
| Received By |
pgreilic |
Date |
2019-08-19 |
Time |
15:16 |
Sent To |
|
|
| Notes |
| 2019-08-19 15:27:16 | 1.) PROVIDE A LEGIBLE SITE PLAN INDICATING PROPOSED | | | SETBACKS FOR ANY/ALL PROPOSED BUILDINGS OR EXPANSIONS, | | | INCLUDING SETBACKS FOR ANY PROPOSED RAMPS | | | 2.) PROVIDE ARCHITECTURAL ELEVATIONS WITH HEIGHTS FOR | | | ANY NEW CONSTRUCTION | | | 2.) A LANDSCAPE PERMIT IS REQUIRED | | | | | | PAUL GREILICH, SENIOR PLANNER | | | 561-822-1443 | | | [email protected] |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
4 |
Status |
F |
Date |
|
|
|
Cont ID |
|
| Sent By |
|
Date |
2019-07-29 |
Time |
|
Rev Time |
0.00 |
| Received By |
pgreilic |
Date |
2019-07-29 |
Time |
14:47 |
Sent To |
|
|
| Notes |
| 2019-07-29 14:49:30 | 1.) PROVIDE A LEGIBLE SITE PLAN INDICATING PROPOSED | | | SETBACKS FOR ANY/ALL PROPOSED BUILDINGS OR EXPANSIONS, | | | INCLUDING SETBACKS FOR ANY PROPOSED RAMPS | | | 2.) A LANDSCAPE PERMIT IS REQUIRED | | | | | | PAUL GREILICH, SENIOR PLANNER | | | 561-822-1443 | | | [email protected] |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
3 |
Status |
F |
Date |
|
|
|
Cont ID |
|
| Sent By |
|
Date |
2019-06-13 |
Time |
|
Rev Time |
0.00 |
| Received By |
pgreilic |
Date |
2019-06-13 |
Time |
12:09 |
Sent To |
|
|
| Notes |
| 2019-06-13 12:13:48 | 1.) PLEASE PROVIDE AN UPDATED SITE PLAN THAT SHOWS THE | | | PROPOSED ADA RAMP AND LABEL THE SETBACK ACCORDINGLY | | | 2.) LANDSCAPE PERMIT REQUIRED | | | | | | PAUL GREILICH, AICP, SENIOR PLANNER | | | 561-822-1443 | | | [email protected] |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
P |
Date |
|
|
|
Cont ID |
|
| Sent By |
|
Date |
2019-04-15 |
Time |
|
Rev Time |
0.00 |
| Received By |
pgreilic |
Date |
2019-04-15 |
Time |
10:42 |
Sent To |
|
|
| Notes |
| 2019-04-15 10:43:07 | 1.) LANDSCAPE PERMIT REQUIRED | | | | | | PAUL GREILICH, AICP, SENIOR PLANNER | | | 561-822-1443 | | | [email protected] |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
P |
Date |
|
|
|
Cont ID |
|
| Sent By |
pgreilic |
Date |
2018-10-04 |
Time |
|
Rev Time |
0.00 |
| Received By |
pgreilic |
Date |
2018-10-02 |
Time |
16:43 |
Sent To |
|
|
| Notes |
| 2018-10-04 12:56:31 | 1.) LANDSCAPE PERMIT REQUIRED | | | | | | PAUL GREILICH, AICP, SENIOR PLANNER | | | 561-822-1443 | | | [email protected] |
|
|
|