Plan Review Details - Permit 18090843
Plan Review Stops For Permit 18090843
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2018-10-22 Cont ID  
Sent By shill Date 2018-10-22 Time 16:09 Rev Time 0.00
Received By shill Date 2018-10-22 Time 16:09 Sent To  
Notes
2018-10-22 16:10:41PROVISO: AN ANALYSIS OF THE BUILDING SHOWING COMPLIANCE
 WITH FBC B 2017 IS REQUIRED
 PER DISCUSSIONS W/JON WAINRIGHT, TIM SLIGER
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2018-10-17 Cont ID  
Sent By shill Date 2018-10-17 Time 17:59 Rev Time 0.00
Received By shill Date 2018-10-16 Time 08:03 Sent To  
Notes
2018-10-17 17:49:49****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 COMMENT FROM PREVIOUS LIST:
  
 1. FBC EB 701.2, PROVIDE ADDITIONAL INFORMATION TO
 JUSTIFY REMOVAL OF FIRE RATED DOORS. IT APPEARS THAT
 THIS IS A CORRIDOR OR ELEVATOR LOBBY. ARE THE ELEVATORS
 PRESSURIZED?
  
 PLEASE CONTACT ME IF YOU WISH TO DISCUSS.
  
 2ND REVIEW:
  
 SEE BELOW FOR THE EMAIL WHICH I RECEIVED. IF APPLIANT
 WOULD LIKE TO USE THE REQUIREMENTS FOR NEW CONSTRUCTION
 (0 RATING FOR THE CORRIDORS), YOU CAN PROVIDE AN
 ANALYSIS OF THE ENTIRE BUILDING TO SHOW THAT THE ENTIRE
 BUILDING COMPLIES WITH FBC 2017, BUILDING.
  
 THE COMMENTARY FOR THE EXISTING BUILDING CODE, SECTION
 804.1.1 STATES THE SPRINKLER SYSTEM ALSO NEEDS TO
 INCLUDE THE EXIT STAIRWAY(S).
  
 PLEASE CONTACT ME IF YOU WISH TO DISCUSS.
  
 ***************************************************
 FROM: ANDY SHANAHAN
 SENT: WEDNESDAY, SEPTEMBER 26, 2018 5:06 PM
 TO: TIM SLIGER
 CC: DAVID BROWN
 SUBJECT: RE: NORTHBRIDGE CENTRE MASTER PERMIT# 17080045
  
 TIM,
  
 SECTION 804.1.1 IS A SUBSECTION TO 804.1, WHICH STATES
 THE REQUIREMENTS OF THIS SECTION ARE LIMITED TO THE
 WORK AREA. SECTION 804.1.1 THEN PROVIDES A CAVEAT. YOU
 NEED TO SPRINKLER OUTSIDE YOUR WORK AREA IF YOU WANT TO
 TAKE ADVANTAGE OF THE CORRIDOR RATING REDUCTION. YOU
 ALREADY EXCEED THIS REQUIREMENT ALREADY AS YOUR
 BUILDING IS FULLY-SPRINKLERED.
  
 I HAVE COME ACROSS STUFF LIKE THIS BEFORE. THE INTENT
 OF THIS SECTION IS TO BE APPLIED TO A NON-SPRINKLERED
 OR PARTIALLY-SPRINKLERED BUILDING. IN A NON-SPRINKLERED
 (OR PARTIALLY-SPRINKLERED) BUILDING YOU COULD INSTALL A
 SPRINKLER SYSTEM AS DESCRIBED AND REDUCE THE CORRIDOR
 RATING EVEN THOUGH YOUR BUILDING ISN?T COMPLETELY
 SPRINKLERED (NEW CONSTRUCTION REQUIRES THE BUILDING TO
 BE COMPLETELY SPRINKLERED TO ELIMINATE THE CORRIDOR
 RATINGS. SEE SECTION 1020.1).
  
 YOUR BUILDING IS COMPLETELY SPRINKLERED. IN A
 COMPLETELY SPRINKLERED BUILDING, YOU DO NOT NEED TO
 SPRINKLER THE LANDINGS AS DESCRIBED. PUTTING IT
 DIFFERENTLY, THE CODE OFFICIAL WOULD CLEARLY RATHER
 SOMEONE SPRINKLER THE ENTIRE BUILDING IN COMPLIANCE
 WITH NFPA 13 (WITHOUT SPRINKLERS AT THE LANDINGS) THAN
 WHAT IS PERMITTED BY THAT SECTION.
  
 THIS CODE IS SPECIFICALLY WRITTEN TO BE LESS
 RESTRICTIVE THAN THE CODE FOR NEW CONSTRUCTION. IF THIS
 SECTION WERE APPLIED TO YOUR BUILDING, IT WOULD BE IN
 EXCESS OF THE REQUIREMENTS FOR NEW CONSTRUCTION.
 [A]101.3INTENT.
 THE INTENT OF THIS CODE IS TO PROVIDE FLEXIBILITY TO
 PERMIT THE USE OF ALTERNATIVE APPROACHES TO ACHIEVE
 COMPLIANCE WITH MINIMUM REQUIREMENTS TO SAFEGUARD THE
 PUBLIC HEALTH, SAFETY AND WELFARE INSOFAR AS THEY ARE
 AFFECTED BY THE REPAIR, ALTERATION, CHANGE OF
 OCCUPANCY, ADDITION AND RELOCATION OF EXISTING
 BUILDINGS.
  
 SINCERELY,
  
 ANDREW SHANAHAN, P.E.
 PROJECT DIRECTOR
 HOWE ENGINEERS, INC.
 PHONE: 781.878.3500
 EMAIL: [email protected]
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2018-09-22 Cont ID  
Sent By shill Date 2018-09-22 Time 13:59 Rev Time 0.00
Received By shill Date 2018-09-22 Time 13:59 Sent To  
Notes
2018-09-22 14:03:09****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 1. FBC EB 701.2, PROVIDE ADDITIONAL INFORMATION TO
 JUSTIFY REMOVAL OF FIRE RATED DOORS. IT APPEARS THAT
 THIS IS A CORRIDOR OR ELEVATOR LOBBY. ARE THE ELEVATORS
 PRESSURIZED?
  
 PLEASE CONTACT ME IF YOU WISH TO DISCUSS.
  
  
  
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2018-09-28 Cont ID  
Sent By pleduc Date 2018-09-28 Time   Rev Time 0.00
Received By pleduc Date 2018-09-28 Time 11:21 Sent To B
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2018-09-24 Cont ID  
Sent By pleduc Date 2018-09-24 Time   Rev Time 0.00
Received By pleduc Date 2018-09-24 Time 15:23 Sent To I
Notes
2018-09-24 15:23:21THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
  
  
 1) THERE INSUFFICIENT INFORMATION PROVIDED TO DETERMINE
 IF THIS DOOR IS REQUIRED TO BE RATED OR NOT.
  
 IF THIS DOOR IS A CORRIDOR DOOR, IT IMAY REQUIRED TO BE
 RATED PER THE ORIGINAL EOR LIFE SAFETY SYSTEM.
  
 PER NFPA 101,
  
 11.8 HIGH-RISE BUILDINGS.
 11.8.1 GENERAL.
 11.8.1.1 THE PROVISIONS OF SECTION 11.8 SHALL APPLY TO
 THE
 FOLLOWING:
 (1) NEW HIGH-RISE BUILDINGS, AS DEFINED IN 3.3.36.7
 (2) EXISTING HIGH-RISE BUILDINGS AS REQUIRED BY
 CHAPTERS 13, 15,
 17, 19, 21, 23, 26, 29, 31, 33, 37, 39, 40, 42, OR 43
  
 PER THE APPLICABLE CHAPTER THE CORRIDAOR IS REQUIRED TO
 BE RATED.
  
 PLEASE REVIEW ANC CORRECT OR PROVIDE A DETAIL
 JUSTIFICATION WITH SPECIFIC CODE REFERENCES AND OR
 APPLICABLE BUILDING RECORDS.
  
  
 2) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
 3) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2018-10-17 Cont ID  
Sent By shill Date 2018-10-17 Time 17:59 Rev Time 0.00
Received By shill Date 2018-09-26 Time 10:34 Sent To  
Notes
2018-09-28 10:34:46RESUB ROUTED TO FIRE INBOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-09-24 Cont ID  
Sent By cpuell Date 2018-09-24 Time 15:54 Rev Time 0.00
Received By cpuell Date 2018-09-19 Time 15:44 Sent To  
Notes
2018-09-22 14:03:319/22 TO FIRE BOX
  
2018-09-20 15:44:42REVISION ROUTED TO SHILL