Plan Review Details - Permit 18090784
Plan Review Stops For Permit 18090784
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2018-10-12 Cont ID  
Sent By dbattles Date 2018-10-12 Time 14:45 Rev Time 0.00
Received By dbattles Date 2018-10-12 Time 14:45 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2018-09-27 Cont ID  
Sent By pleduc Date 2018-09-27 Time   Rev Time 0.00
Received By pleduc Date 2018-09-27 Time 12:29 Sent To B
Notes
2018-09-27 12:38:32THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 PLEASE CONSIDER THE FOLLOWING AS PROVISO:
  
 THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED
 AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE
 PROVISO COMMENTS WILL RESULT IN A FAILED FIRE
 INSPECTION.
  
  
 1) FOR FIRE DEPARTMENT VEHICLE ACCESS 20' GATE OPENINGS
 ARE REQUIRED.
  
 PER NFPA 1, CHAPTER 18, FIRE DEPARTMENT ACCESS AND
 WATER SUPPLY
  
 18.2.1 FIRE DEPARTMENT ACCESS AND FIRE DEPARTMENT
 ACCESS ROADS SHALL
 BE PROVIDED AND MAINTAINED IN ACCORDANCE WITH SECTION
 18.2.
 18.2.3.2 ACCESS TO BUILDING.
  
 18.2.3.2.1 A FIRE DEPARTMENT ACCESS ROAD SHALL EXTEND
 TO WITHIN 50 FT
 (15 M) OF AT LEAST ONE EXTERIOR DOOR THAT CAN BE OPENED
 FROM THE
 OUTSIDE AND THAT PROVIDES ACCESS TO THE INTERIOR OF THE
 BUILDING.
  
 18.2.3.2.1.2 WHEN REQUIRED BY THE AUTHORITY HAVING
 JURISDICTION,
 ROAD(S) OR PARKING LOTS PROVIDING ACCESS TO THE MAIN
 ENTRANCE DOOR(S)
 SHALL BE CONSIDERED ACCESS ROADS AND SHALL COMPLY WITH
 THE
 REQUIREMENTS OF 18.2.3.4.1.1 AND 18.2.3.4.1.2.
  
 18.2.3.4 SPECIFICATIONS.
  
 18.2.3.4.1 DIMENSIONS.
  
 18.2.3.4.1.1 FIRE DEPARTMENT ACCESS ROADS SHALL HAVE AN
 UNOBSTRUCTED
 WIDTH OF NOT LESS THAN 20 FT (6.1 M).
 18.2.3.4.1.2 FIRE DEPARTMENT ACCESS ROADS SHALL HAVE AN
 UNOBSTRUCTED
 VERTICAL CLEARANCE OF NOT LESS THAN 13 FT 6 IN. (4.1
 M).
  
 PLEASE PROVIDE THE REQUIRED ACCESS WIDTH.
  
  
  
 2) KNOX PADLOCKS ARE RECCOMENDED AT EACH GATE TO ASSIST
 WITH AFTERHOURS RAPIID ENTRY AND SITE SECURITY. IN THE
 EVENT OF AN EMERGENCY, WITHOUT A KNOX PADLOCK THE CHAIN
 OR LOCK WILL BE CUT AND LEFT UNSECURED.
  
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-10-12 Cont ID  
Sent By dbattles Date 2018-10-12 Time 14:46 Rev Time 0.00
Received By dbattles Date 2018-09-18 Time 13:17 Sent To  
Notes
2018-09-26 14:32:55TO LMARCHAN
2018-09-19 13:17:25ROUTED TO ZONING INBOX

Review Stop Z ZONING
Rev No 1 Status P Date 2018-09-26 Cont ID  
Sent By aaponte Date 2018-09-26 Time 14:31 Rev Time 0.00
Received By aaponte Date 2018-09-26 Time 14:31 Sent To FIRE
Notes
2018-09-26 14:32:45PROVISO: SIGN NOT INCLUDED IN THIS PERMIT.