| Plan Review Stops For Permit 18090753 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2018-09-18 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2018-09-18 |
Time |
11:59 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2018-09-18 |
Time |
11:59 |
Sent To |
|
|
| Notes |
| 2018-09-18 12:01:59 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6724 | | | | | | FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) | | | FBC B = FBC BUILDING | | | FBC EB = FBC EXISTING BUILDING | | | FBC A = FBC ACCESSIBILITY | | | FBC EC = FBC ENERGY CONSERVATION | | | FBC R = FBC RESIDENTIAL | | | | | | 1. THE UNDERLAYMENT WAS TESTED ON AN 8" SLAB. THE | | | THICKNESS OF THE SLAB AT THIS UNIT IS NOT KNOWN TO ME | | | AT THIS TIME. | | | | | | HAVE THE ARCHITECT REVISE THE LETTER TO INCLUDE SLAB | | | THICKNESS. PROFLEX WILL BE CONTACTED TO CONFIRM THAT | | | THE TEST REPORT "PROFLEX 90" IS THE SAME PRODUCT | | | PROPOSED, "PROFLEX MSC90". | | | | | | |
|
|