Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2018-12-20 Cont ID  
Sent By dbattles Date 2018-12-20 Time 11:27 Rev Time 0.00
Received By dbattles Date 2018-12-20 Time 11:27 Sent To  
Notes
2018-12-20 11:28:39PROVISOS:
 1. PROVIDE ENGINEERING FOR GUARDRAILS
 2. PROVIDE PRODUCT APPROVAL FOR THREE DOORS ON THE
 PLANS
 3. HAVE PROPERTY OWNER SIGN THE ENERGY CALCULATIONS

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2018-12-14 Cont ID  
Sent By dbattles Date 2018-12-14 Time 08:10 Rev Time 0.00
Received By dbattles Date 2018-12-14 Time 08:10 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2018-11-28 Cont ID  
Sent By dbattles Date 2018-11-28 Time 09:37 Rev Time 0.00
Received By dbattles Date 2018-11-28 Time 09:37 Sent To  
Notes
2018-11-28 10:02:05THE LABELS OF NORTH AND SOUTH ELEVATIONS DID NEED TO BE
 SWITCHED.
 ZONING COMMENTED THAT THE ELEVATIONS DIDN'T MATCH THE
 FLOOR PLAN BECAUSE OF THIS.
 I DID REDLINE THE CHANGE SO THAT I COULD STAMP DRAWING
 APPROVED.
 IF THE PLAN IS REPLACED MAKE SURE IT IS ROUTED BACK TO
 BUILDING FOR RE-STAMP.
2018-11-28 09:53:48PROVISOS:
 1. PROVIDE ENGINEERING FOR GUARDRAILS
 2. PROVIDE PRODUCT APPROVAL FOR THREE DOORS ON THE
 PLANS
 3. HAVE PROPERTY OWNER SIGN THE ENERGY CALCULATIONS

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2018-10-30 Cont ID  
Sent By dbattles Date 2018-10-30 Time 09:16 Rev Time 0.00
Received By dbattles Date 2018-10-29 Time 13:04 Sent To  
Notes
2018-10-30 09:17:19****CORRECTIONS****
 W.P.B. PERMIT: 18090702
 REVIEWED: OCTOBER 29, 2018
  
 DYLAN BATTLES
 BUILDING PLANS EXAMINER I
 [email protected]
 561-805-6718
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC AMENDED = FLORIDA BUILDING CODE,6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC ENERGY = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 1. [FBC 107.5][FBC 110.9][FBC R401.3][PROVIDE SITE
 DRAINAGE PLAN.
 SURFACE DRAINAGE SHALL BE DIVERTED TO A STORM SEWER
 CONVEYANCE OR OTHER APPROVED POINT OF COLLECTION THAT
 DOES NOT CREATE A HAZARD. LOTS SHALL BE GRADED TO DRAIN
 SURFACE WATER AWAY FROM FOUNDATION WALLS. THE GRADE
 SHALL FALL A MINIMUM OF 6 INCHES (152 MM) WITHIN THE
 FIRST 10 FEET (3048 MM).
 EXCEPTION: WHERE LOT LINES, WALLS, SLOPES OR OTHER
 PHYSICAL BARRIERS PROHIBIT 6 INCHES (152 MM) OF FALL
 WITHIN 10 FEET (3048 MM), DRAINS OR SWALES SHALL BE
 CONSTRUCTED TO ENSURE DRAINAGE AWAY FROM THE STRUCTURE.
 IMPERVIOUS SURFACES WITHIN 10 FEET (3048 MM) OF THE
 BUILDING FOUNDATION SHALL BE SLOPED A MINIMUM OF 2
 PERCENT AWAY FROM THE BUILDING.
  
 2. [FBC R403.1.7.3] FOUNDATION ELEVATION.
 ON GRADED SITES, THE TOP OF ANY EXTERIOR FOUNDATION
 SHALL EXTEND ABOVE THE ELEVATION OF THE STREET GUTTER
 AT POINT OF DISCHARGE OR THE INLET OF AN APPROVED
 DRAINAGE DEVICE A MINIMUM OF 12 INCHES (305 MM) PLUS 2
 PERCENT. ALTERNATE ELEVATIONS ARE PERMITTED SUBJECT TO
 THE APPROVAL OF THE BUILDING OFFICIAL, PROVIDED IT CAN
 BE DEMONSTRATED THAT REQUIRED DRAINAGE TO THE POINT OF
 DISCHARGE AND AWAY FROM THE STRUCTURE IS PROVIDED AT
 ALL LOCATIONS ON THE SITE.
  
 3. SHEET A-1 WEST ELEVATION SHOULD BE LABLES EAST
 ELEVATION AND THE DRAWING NEEDS TO BE MIRRORED TO MATCH
 FLOOR PLAN.
  
 4. SHEET A-1 EAST FLOOR PLAN SHOULD BE LABLED WEST
 ELEVATION AND MIRRORED AS WELL. ALSO, THE
  
 5. SHEET A-1 NORTH ELEVATION JUST NEEDS TO BE MIRRORED
 AND CHECK THE SECOND STORY WINDOWS. PLAN SHOWS ONE
 WINDOW AND ELEVATION SHOWS THREE.
  
 6. SHEET A-1 SOUTH ELEVATION JUST NEEDS TO BE MIRRORED.
  
 7. [FBC R301.4]DEAD LOAD [FBC R301.5]LIVE LOAD
 WHAT ARE THE LOADS ON ROOF AND ON FLOORS?
 WHAT ARE THE POINT LOADS ON THE STEEL PLATES?
 THE STEM FOOTER SAYS 24? WIDE, BUT THE DASHED LINE
 SCALES AT 18?. PLEASE LOOK AT THE POINT LOADS AND
 FOUNDATION PLAN AS IT SEEMS THAT A 24 IN. WIDE FOOTER
 ISN?T CARRYING EVEN LOAD. IT SEEMS THAT THERE ARE POINT
 LOADS THAT MAY REQUIRE LARGER FOOTER WHILE INBETWEEN
 MAY NOT.
  
 8. [FBC R403.4] EXTERIOR FOOTINGS SHALL BE PLACED NOT
 LESS THAN 12 INCHES (305 MM) BELOW THE UNDISTURBED
 GROUND SURFACE.
 SECTIONS AND ELEVATIONS DEPICT GRADE DIFFERENLTY. SOME
 LOOK LIKE THE SLAB BOTTOM IS AT GRADE AND SOME SHOW
 GRADE ABOUT HALF WAY UP THE SLAB AND FOOTER SCHEDULE
 SAYS -6 FOR STEM FOOTING.
 PLEASE CLARIFY GRADE, TOP OF STEM FOOTER AND FINISHED
 FLOOR. THE DRAINAGE PLAN WILL START FROM GRADE AT HOUSE
 AND THEN SHOW HOW DRAINAGE IS MAINTAINED WITHIN
 PROPERTY.
 9.
 SHEET S-1 SHOWS THREE P-1 TYPE CONCRETE PADS IN THE
 CENTER AREA WHERE CONTAINERS MEET IN THE MIDDLE. IS
 THIS WHERE THE CONTAINERS CONECT AT BOTTOM, AND WOULD
 THE PAD BE -10 INCHES? THAT WOULD BE 4 INCHES LOWER
 THAN THE STEM FOOTING.
 PLEASE SHOW WHAT THESE THREE PADS ARE FOR AND WHAT
 CONNECTS TO THEM.
  
 10. [FBC R408.1]UNDER FLOOR VENTILATION
 PROVIDE HOW UNDER FLOOR SPACE IS BEING HANDLED. VENTED
 OR UNVENTED. FOLLOW SECTION R408 FOR THE OPTION
 PROVIDED.
  
 11. [FBC R302.10]PROVIDE CUT SHEET FOR ICYNENE(ICC-ES
 REPORT OR EQUAL) WITH THE TYPE SELECTED TO ESTABLISH
 THICKNESS NEEDED TO MEET REQUIRED R-VALUE, FLAME SPREAD
 INDEX AND SMOKE DEVELOPED INDEX.
 ALSO, COVER SHEET GENERAL CONSTRUCTION NOTES #6 STATES
 MINIMUM R-VALUES FOR ASSEMBLIES. THE ENERGY
 CALCULATIONS HAVE DIFFERENT VALUES AND THE STRUCTURE
 PASSES WITH THE LOWER VALUES SPECIFIED IN ENERGY CALCS.
 PLEASE WRITE SEE ENERGY CALCULATION IN NOTE #6 SO ALL
 R-VALUES ARE CONSISTANT.
  
 12. [FBC ENERGY 103.1.1.2]CODE COMPLIANCE
 CERTIFICATION.
 THE BUILDING?S OWNER, THE OWNER?S ARCHITECT OR OTHER
 AUTHORIZED AGENT LEGALLY DESIGNATED BY THE OWNER SHALL
 CERTIFY THAT THE BUILDING IS IN COMPLIANCE WITH THE
 CODE, AS PER SECTION 553.907, FLORIDA STATUTES, PRIOR
 TO RECEIVING THE PERMIT TO BEGIN CONSTRUCTION OR
 RENOVATION.
 PLEASE HAVE THE ENERGY CALCULATIONS SIGNED ON PAGE 1 AT
 OWNER.AGENT SIGNATURE SPACE.
  
 13. [FBC AMENDED 107.2.1.2]PROVIDE PRODUCT APPROVAL FOR
 THREE DOORS ON THE PLANS.
  
 14. [FBC ENERGY R401.2]ENERGY CALCULATIONS SHOW R-11 AT
 RAISED FLOOR. ADD NOTE TO STATE INSULATION IN FLOOR PER
 ENERGY CALCULATIONS.
  
 15. [FBC AMENDED 107.2.1.2]PROVIDE ENGINEERING FOR
 GUARDRAILS, OR INDICATE THAT IT WILL BE A DEFERRED
 SUBMITTAL.
  
 16. [FBC 107.2.1]INDICATE THE CEMENT ROOF TILE
 ATTACHMENT AND SUBMIT THE PRODUCT APPROVAL FOR IT.
  
 17. [FBC R905.11]PROVIDE THE MAXIMUM DESIGN PRESSURE
 AND INDICATE WHICH SYSTEM IS BEING USED FROM NOA
 17-1003.04 TO MEET IT.
  
 NOTE:
 -PLEASE PROVIDE COMMENT RESPONSE SHEET TO EXPLAIN HOW
 EACH COMMENT IS BEING ADDRESSED.
 -ADDITIONAL COMMENTS MAY BE FORTHCOMING PENDING REVIEW
 OF MATERIALS REQUESTED.
 -WHEN RESUBMITTING, PROVIDE TWO IDENTICAL COLLATED SETS
 OF DOCUMENTS FOR ISSUANCE. OLD SHEETS (BOTH SETS)
 SHOULD BE RETAINED IN THE PACKAGE; PLEASE DO NOT
 DISCARD ANY DOCUMENTS. THEY SHOULD BE BOUND TOGETHER
 SEPARATELY FROM THE TWO ISSUANCE SETS AND MARKED "VOID"
 OR "OLD SHEETS". PLEASE DO NOT STAMP THE PLANS VOID AS
 APPLICANTS ARE INADVERTENTLY STAMPING SHEETS THAT WE
 NEED "VOID", RENDERING THEM NOT USABLE.
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2018-12-14 Cont ID  
Sent By jpearson Date 2018-12-14 Time 10:45 Rev Time 0.00
Received By jpearson Date 2018-12-14 Time 10:45 Sent To I
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2018-11-26 Cont ID  
Sent By jpearson Date 2018-11-26 Time 08:20 Rev Time 0.00
Received By jpearson Date 2018-11-26 Time 08:20 Sent To B
Notes
2018-11-26 08:20:33CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 PREVIOUS COMMENTS THAT HAVE BEEN ADDRESSED
 SATISFACTORILY ARE MARKED AS CORRECTED. PREVIOUS
 COMMENTS THAT HAVE NOT BEEN ADDRESSED SATISFACTORILY
 HAVE ADDITIONAL COMMENTS IN PARENTHESES. ANY NEW
 COMMENTS WILL BE LISTED AFTER PREVIOUS COMMENTS.
  
 1. VALUE FOR WORK STATED ON PERMIT APPLICATION APPEARS
 LOW. PROVIDE COPY OF SIGNED CONTRACT WITH SCOPE AND
 VALUE OF WORK, TO INCLUDE ALL MATERIALS AND LABOR. THIS
 IS FOR TOTAL PROJECT, NOT JUST ELECTRICAL. FBC 109.3
 (NOT PROVIDED.)
 2. CORRECTED.
 3. PROVIDE AVAILABLE SHORT CIRCUIT CALCULATION FOR EACH
 PANEL INCLUDING INFORMATION FROM THE POWER COMPANY
 STATING WHAT THE AVAILABLE SHORT CIRCUIT CURRENT IS FOR
 THE SERVICE TO CONFIRM THE STATED AIC RATING OF THE
 SERVICE EQUIPMENT AND DOWNSTREAM PANELS IS ADEQUATE.
 NEC 110.9, 110.10; FBC RE E3606.3 (NOT PROVIDED. IF
 THIS IS TO BE A DEFERRED SUBMITTAL DUE TO DELAYS FROM
 FPL, PROVIDE NOTE ON PLAN THAT THIS INFORMATION WILL BE
 PROVIDED PRIOR TO POWER RELEASE INSPECTION.)
 4. WIRE SIZE SHOWN FROM METER MAIN TO INTERIOR PANEL IS
 NOT RATED FOR 200 AMPS. PROVIDE CORRECTION. NEC
 310.15(B)(16); FBC RE E3603.1, E3705.1 (NOT CORRECTED
 STILL SHOWS THE OPTION OF USING #1 WIRE TO INTERIOR
 PANEL. THIS WIRE IS NOT RATED FOR 200 AMPS. PROVIDE
 CORRECTION.)
 5. CORRECTED.
 6. CORRECTED.
 7. CORRECTED.
 8. CORRECTED.
 9. CORRECTED.
 10. CORRECTED.
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD
 SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2018-10-02 Cont ID  
Sent By jpearson Date 2018-10-02 Time 15:13 Rev Time 0.00
Received By jpearson Date 2018-10-02 Time 12:01 Sent To  
Notes
2018-10-02 15:13:29CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. VALUE FOR WORK STATED ON PERMIT APPLICATION APPEARS
 LOW. PROVIDE COPY OF SIGNED CONTRACT WITH SCOPE AND
 VALUE OF WORK, TO INCLUDE ALL MATERIALS AND LABOR. THIS
 IS FOR TOTAL PROJECT, NOT JUST ELECTRICAL. FBC 109.3
 2. AFCI PROTECTION SHOWN IN NOTE 29 AND NOTE BELOW
 RISER DIAGRAM IS NOT CODE COMPLIANT. ALL BRANCH
 CIRCUITS THAT SUPPLY 120-VOLT, SINGLE-PHASE, 15- AND
 20-AMPERE OUTLETS INSTALLED IN KITCHENS, FAMILY ROOMS,
 DINING ROOMS, LIVING ROOMS, PARLORS, LIBRARIES, DENS,
 BEDROOMS, SUN-ROOMS, RECREATIONS ROOMS, CLOSETS,
 HALLWAYS, LAUNDRY AREAS AND SIMILAR ROOMS OR AREAS
 SHALL BE AFCI PROTECTED. THIS INCLUDES LIGHTING AND
 POWER OUTLETS AND RECEPTACLES. SOME AREAS REQUIRE BOTH
 AFCI AND GFCI PROTECTION. PROVIDE CORRECTION. NEC
 210.8, 210.12; FBC RE E3902
 3. PROVIDE AVAILABLE SHORT CIRCUIT CALCULATION FOR EACH
 PANEL INCLUDING INFORMATION FROM THE POWER COMPANY
 STATING WHAT THE AVAILABLE SHORT CIRCUIT CURRENT IS FOR
 THE SERVICE TO CONFIRM THE STATED AIC RATING OF THE
 SERVICE EQUIPMENT AND DOWNSTREAM PANELS IS ADEQUATE.
 NEC 110.9, 110.10; FBC RE E3606.3
 4. WIRE SIZE SHOWN FROM METER MAIN TO INTERIOR PANEL IS
 NOT RATED FOR 200 AMPS. PROVIDE CORRECTION. NEC
 310.15(B)(16); FBC RE E3603.1, E3705.1
 5. PROVIDE GFCI PROTECTION FOR DISHWASHER. NEC
 210.8(D); FBC RE E3902.10
 6. PROVIDE LOCATION OF SERVICE AND ELECTRICAL PANELS ON
 PLAN. WPB FBC 107.2.1
 7. RISER DIAGRAM SHOWS A SINGLE GROUND ROD AS A
 SUPPLEMENTAL GROUNDING ELECTRODE. THIS SUPPLEMENTAL
 GROUNDING ELECTRODE NEEDS TO BE AUGMENTED BY AN
 ADDITIONAL ELECTRODE AT LEAST 6 FEET AWAY OR PROVIDE
 EVIDENCE OF RESISTANCE TO GROUND OF 25 OHMS OR LESS.
 NEC 250.53(A)(2); FBC RE E3608.4
 8. FOR A ONE FAMILY DWELLING AND EACH UNIT OF A
 TWO-FAMILY DWELLING THAT IS AT GRADE LEVEL, AT LEAST
 ONE RECEPTACLE OUTLET READILY ACCESSIBLE FROM GRADE AND
 NOT MORE THAN 2.0 M (6.5 FT) ABOVE GRADE LEVEL SHALL BE
 INSTALLED AT THE FRONT AND BACK OF THE DWELLING.
 PROVIDE CORRECTION. NEC 210.52(E)(1) FBC RE E3901.7
 9. PNEL SCHEDULE DOES NOT SHOW THE TWO SMALL APPLIANCE
 CIRCUIT FOR KITCHEN RECEPTACLE OUTLETS. A MINIMUM OF
 TWO 20 AMPERE BRANCH CIRCUIT SHALL BE PROVIDED TO
 SUPPLY KITCHEN COUNTERTOP RECEPTACLE OUTLET(S). PROVIDE
 CORRECTION. NEC 210.11(C)(1) , FBC RE E3703.2
 10. PROVIDE WEATHER PROOF GFCI PROTECTED RECEPTACLE
 OUTLET FOR EACH BALCONY ACCESSIBLE FROM THE DWELLING
 UNIT. NEC 210.52(E)(3); FBC RE E3901.7
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD
 SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2018-12-20 Cont ID  
Sent By dbattles Date 2018-12-20 Time 11:29 Rev Time 0.00
Received By dbattles Date 2018-12-17 Time 14:46 Sent To  
Notes
2018-12-18 14:46:31RESUB ROUTED TO ZONING INBOX

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date   Cont ID  
Sent By   Date 2018-12-14 Time   Rev Time 0.00
Received By lmarchan Date 2018-12-03 Time 15:51 Sent To  
Notes
2018-12-04 15:51:25R10

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2018-11-28 Cont ID  
Sent By gjohnson Date 2018-11-28 Time 16:48 Rev Time 0.00
Received By gjohnson Date 2018-11-14 Time 14:58 Sent To  
Notes
2018-11-21 10:14:06SENT TO ELEC
2018-11-15 14:58:11LIBRARY

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-10-30 Cont ID  
Sent By dbattles Date 2018-10-30 Time 09:17 Rev Time 0.00
Received By dbattles Date 2018-09-17 Time 13:45 Sent To  
Notes
2018-09-18 13:45:59R40

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status P Date 2019-01-03 Cont ID  
Sent By dbattles Date 2019-01-03 Time 13:00 Rev Time 0.00
Received By dbattles Date 2019-01-03 Time 13:00 Sent To  
Notes
2019-01-03 13:01:31STAMP ON PLANS - OK
 MU#-2019-000169-0000

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2018-10-30 Cont ID  
Sent By dbattles Date 2018-10-30 Time 09:17 Rev Time 0.00
Received By dbattles Date 2018-10-30 Time 09:17 Sent To  
Notes
2018-10-30 09:18:24[FBC AMENDED 109]PLANS REQUIRE REVIEW BY THE PBC IMPACT
 FEE OFFICE. CALL (561) 233-5025. UPON APPROVAL, YOU MAY
 CHECK OUT ONE PLAN SET AND TAKE TO THAT OFFICE FOR
 REVIEW. PLEASE RETURNED STAMPED AND WITH A COPY OF THE
 RECEIPT AS APPLICABLE. PLEASE PROVIDE THE MUNICIPAL
 IMPACT FEE QUESTIONNAIRE FORM TO THE PBC IMPACT FEE
 OFFICE. THE FORM CAN BE FOUND AT: HTTP://DISCOVER.PBCGO
 V.ORG/PZB/ADMINISTRATION/PDF/IMPACTFEES/FORMS/QUESTIONN
 AIRE.PDF

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2018-10-15 Cont ID  
Sent By cmontell Date 2018-10-15 Time 13:41 Rev Time 0.00
Received By cmontell Date 2018-10-15 Time 13:32 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2018-11-28 Cont ID  
Sent By gjohnson Date 2018-11-28 Time 16:47 Rev Time 0.00
Received By gjohnson Date 2018-11-28 Time 16:47 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2018-10-16 Cont ID  
Sent By gjohnson Date 2018-10-16 Time 10:40 Rev Time 0.00
Received By gjohnson Date 2018-10-16 Time 07:25 Sent To  
Notes
2018-10-16 11:24:441ST REVIEW:
 2017 FLORIDA BUILDING CODE 6TH EDITION
 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH
 EDITION
  
 PLUMBING COMMENTS:
  
 1. SHT. E-1 THE SANITARY ISOMETRIC HAS THE FOLLOWING
 CODE VIOLATIONS PLEASE CORRECT AND RESUBMIT.
 A) THE TOILET ON THE FIRST FLOOR IS NOT VENTED THE
 TOILET, SHOWER AND LAVATORY SHOULD CONNECT TO A SINGLE
 BUILDING BRANCH DRAIN VENTED BY THE LAVATORY AS A WET
 VENT SYSTEM. PER FBC RES P3801.1
 B) THE LAUNDRY IS SHOWN ON THE END OF THE BUILDING
 DRAIN THE PLAN SHOWS IT IN THE MIDDLE OF THE BUILDING
 IT SHOULD BE SHOWN NEXT TO THE BATHROOM AND THE KITCHEN
 SHOWN ON THE END PLEASE CLARIFY. PER WPB AMEND TO FBC
 107.2.1
 C) THERE SHALL BE A MIN OF 21" CLEARANCE BETWEEN THE
 TOILET AND LAVATORY OR VANITY. PER FBC RES P2705.1 (5)
  
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status P Date 2019-02-04 Cont ID  
Sent By pvalenti Date 2019-02-04 Time 10:14 Rev Time 0.00
Received By pvalenti Date 2019-02-04 Time 10:13 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status N Date 2018-11-28 Cont ID  
Sent By dbattles Date 2018-11-28 Time 09:54 Rev Time 0.00
Received By dbattles Date 2018-11-28 Time 09:54 Sent To  
Notes
2018-11-28 09:59:44PRODUCT APPROVALS PROVIDED FOR TILE, UNDERLAYMENT AND
 SEALER FOR TILE ROOF - OK
 PROVISO-SUPPLY PRODUCT APPROVAL FOR TILE ATTACHMENT
 WITH SUB-PERMIT APPLICATION
  
 PRODUCT APPROVAL FOR FLAT ROOF SUBMITTED - OK
 PROVISO-SUPPLY ENHNACED ROOF NAILING AS REQUIRED BY
 LIMITATION #7, SUPPLY MAXIMUM DESIGN PRESSURE AND
 SELECT WHICH SYSTEM IS BEING INSTALLED FROM PRODUCT
 APPROVAL.

Review Stop Z ZONING
Rev No 4 Status P Date 2018-12-19 Cont ID  
Sent By llouie Date 2018-12-19 Time   Rev Time 0.00
Received By llouie Date 2018-12-19 Time   Sent To B
Notes
2018-12-19 10:44:50SEPARATE PERMITS REQUIRED FOR: LANDSCAPING, DRIVEWAY
 AND WALKWAY.

Review Stop Z ZONING
Rev No 3 Status F Date 2018-12-07 Cont ID  
Sent By llouie Date 2018-12-07 Time   Rev Time 0.00
Received By llouie Date 2018-12-07 Time   Sent To  
Notes
2018-12-07 16:48:03** FAILED **
  
 PLEASE ADDRESS THE FOLLOWING COMMENTS. RESPOND TO THE
 COMMENTS IN WRITING AND/OR ON THE PLANS WHERE
 APPLICABLE:
  
 1.) WILL THERE BE A WALKWAY LEADING TO THE FRONT
 ENTRANCE OF THE PROPOSED RESIDENCE? IF SO, IT MUST BE
 ILLUSTRATED IN THE SITE PLAN. PLEASE NOTE THAT THE
 CALCULATIONS FOR THE REQUIRED FRONT YARD LANDSCAPING IS
 EXACTLY 1,000 SQ. FT. THIS REQUIRED MINIMUM FOR
 LANDSCAPING SHALL BE MAINTAINED WITHIN THE FRONT YARD
 OF THE PROPERTY (INCLUDING ANY DRIVEWAYS AND WALKWAYS).
  
  
  
 NOTES:
  
 * SEPARATE PERMITS REQUIRED FOR: LANDSCAPING, NEW
 DRIVEWAY/WALKWAYS.
  
 * REVISIONS MAY RESULT IN ADDITIONAL COMMENTS.
  
 * ZONE: SF7
  
 * CONTACT LINDA LOUIE @ (561) 822-1458 IF THERE ARE
 QUESTIONS.
  

Review Stop Z ZONING
Rev No 2 Status F Date 2018-11-20 Cont ID  
Sent By llouie Date 2018-11-20 Time   Rev Time 0.00
Received By llouie Date 2018-11-20 Time   Sent To E
Notes
2018-11-20 11:14:13** FAILED **
  
 PLEASE ADDRESS THE FOLLOWING COMMENTS. RESPOND TO THE
 COMMENTS IN WRITING AND/OR ON THE PLANS WHERE
 APPLICABLE:
  
 1.) NORTH ARCHITECTURAL ELEVATION DOES NOT SEEM TO
 MATCH THE FLOOR PLAN. PLEASE CORRECT.
  
 2.) PROPOSED DRIVEWAY SHALL BE SETBACK AT LEAST 3 FT.
 FROM THE SIDE PROPERTY LINE. SITE PLAN SHOWS A 2 FT.
 SETBACK. PLEASE CORRECT. [ZLDR S.94-482]
  
 3.) PLEASE PROVIDE FRONT YARD LANDSCAPE CALCULATIONS SO
 THAT STAFF CAN ENSURE THE MINIMUM FRONT YARD
 LANDSCAPING REQUIREMENT (1,000 FT. OF LANDSCAPED AREA
 WITHIN THE FIRST 25 FT. OF THE PROPERTY) HAS BEEN
 ADDRESS. THERE ARE NO CALCULATIONS PROVIDED IN THE
 PLANS.
  
  
 NOTES:
  
 * SEPARATE PERMITS REQUIRED FOR: LANDSCAPING, NEW
 DRIVEWAY/WALKWAYS.
  
 * REVISIONS MAY RESULT IN ADDITIONAL COMMENTS.
  
 * ZONE: SF7
  
 * CONTACT LINDA LOUIE @ (561) 822-1458 IF THERE ARE
 QUESTIONS.
  

Review Stop Z ZONING
Rev No 1 Status F Date 2018-10-01 Cont ID  
Sent By llouie Date 2018-10-01 Time   Rev Time  
Received By llouie Date 2018-10-01 Time   Sent To  
Notes
2018-10-01 13:42:48** FAILED **
  
 PLEASE ADDRESS THE FOLLOWING COMMENTS. RESPOND TO THE
 COMMENTS IN WRITING AND/OR ON THE PLANS WHERE
 APPLICABLE:
  
 1.) THERE SEEMS TO BE OVERHEAD WIRES RUNNING THROUGH
 THE PROPERTY, WHICH IS A GOOD INDICATION THAT THERE ARE
 UTILITY EASEMENTS RUNNING THROUGH THE PROPERTY;
 HOWEVER, THE SURVEY PRESENTED HAS NOT BEEN REVIEWED FOR
 EASEMENTS ON THE PROPERTY. ANY EXISTING UTILITY
 EASEMENTS MUST BE CLEARLY SHOWN ON THE SURVEY, AS IT
 MAY IMPACT THE PROPOSED DEVELOPMENT.
  
 2.) ARCHITECTURAL ELEVATIONS SHALL INCLUDE THE OVERALL
 HEIGHT DIMENSION FOR THE PROPOSED STRUCTURE (INCLUDING
 ANY ARCHITECTURAL FEATURES/PARAPETS, ETC.). THE MAXIMUM
 HEIGHT OF THE STRUCTURE CANNOT EXCEED 30 FT. [ZLDR
 S.94-72(A)(3)]
  
 3.) ELEVATIONS DO NOT MATCH FLOOR PLANS. PLEASE ADDRESS
 FOR CONSISTENCY.
  
 4.) MASTER SITE PLAN NOTES A FENCE; HOWEVER, THE FENCE
 NEEDS TO BE ILLUSTRATED IN THE PLAN. IS THIS FENCE
 EXISTING OR IS IT PROPOSED? INFORMATION ON THE HEIGHT
 OF THE FENCE IS REQUIRED. [ZLDR S.94-302]
  
 5.) THE PROPOSED COVERED PATIO CANNOT PROJECT MORE THAN
 3 FT. INTO ANY SETBACK (PLAN SHOWS A 5 FT. PROJECTION
 FROM THE STRUCTURE). PLEASE CORRECT. [ZLDR
 S.94-305(B)(2)]
  
 6.) SITE PLAN MUST ILLUSTRATE THE LOCATION AND SETBACK
 DISTANCE OF THE PROPOSED A/C UNIT PAD TO THE PROPERTY
 LINES. PLEASE NOTE THAT THE PAD CANNOT PROJECT MORE
 THAN 4 FT. INTO A SETBACK. SHOW DIMENSIONS TO
 DEMONSTRATE COMPLIANCE. [ZLDR S.94-305(B)(4)]
  
 7.) PROVIDE DIMENSIONS AND SETBACK DISTANCES (TO THE
 PROPERTY LINE) FOR THE PROPOSED DRIVEWAY. THE DRIVEWAY
 SHALL COMPLY WITH THE REGULATIONS OF S.94-312 AND
 S.94-482 OF THE ZONING AND LAND DEVELOPMENT REGULATIONS
 (ZLDRS).
  
 8.) 1,000 SQ. FT. OF REQUIRED FRONT YARD (THE AREA
 WITHIN THE FIRST 25 FT. OF THE PROPERTY FROM PINEWOOD
 AVENUE), SHALL BE LANDSCAPED WITHIN LIVING PLANT
 MATERIAL. PLEASE DEMONSTRATE COMPLIANCE BY PROVIDING
 THE FRONT YARD CALCULATIONS FOR OPEN SPACE. [ZLDR
 S.94-482(A)]
  
 9.) PARKING FOR TWO (2) VEHICLES SHALL BE PROVIDED ON
 SITE. PLEASE DEMONSTRATE THAT THERE IS SUFFICIENT
 DRIVEWAY TO ACCOMMODATE A MINIMUM OF TWO VEHICLES.
 [ZLDR S.94-486]
  
  
 NOTES:
  
 * REVISION MAY RESULT IN ADDITIONAL COMMENTS.
  
 * SEPARATE PERMITS REQUIRED FOR: LANDSCAPING, NEW
 DRIVEWAY/WALKWAYS AND FENCE.
  
 * ZONE: SF7
  
 * CONTACT LINDA LOUIE @ (561) 822-1458 IF THERE ARE
 QUESTIONS.
  