Review Stop G GAS REVIEW
Rev No 2 Status P Date 2018-10-09 Cont ID  
Sent By lcrespo Date 2018-10-09 Time 07:23 Rev Time 0.00
Received By lcrespo Date 2018-10-09 Time 07:23 Sent To  
Notes
2018-10-09 07:24:2010/09/18 REVIEWED FOR CODE COMPLIANCE (GAS)
  
 BY REVIEWING THE PLANS / SPECIFICATIONS FOR CODE
 COMPLIANCE DOES NOT RELIEVE THE OWNER, DESIGN
 PROFESSIONAL, CONTRACTORS OR THEIR REPRESENTATIVES FROM
 THE RESPONSIBILITY TO COMPLY WITH ALL LOCAL, STATE AND
 NATIONAL CODES AND STANDARDS IN EFFECT AT THE TIME OF
 PERMIT ISSUANCE. OUR REVIEW IS NOT A CHECK OF EVERY
 ITEM AND DOES NOT PREVENT THIS DEPARTMENT FROM
 REQUIRING CORRECTIONS DURING CONSTRUCTION. ANY CHANGES
 / ALTERATIONS TO APPROVE PLANS SHALL BE APPROVED TO
 AVOID VOIDING OF THE PERMIT.
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER
  

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2018-09-18 Cont ID  
Sent By lcrespo Date 2018-09-18 Time 17:23 Rev Time 0.00
Received By lcrespo Date 2018-09-18 Time 17:23 Sent To  
Notes
2018-09-18 18:15:5909/18/2018 1ST GAS REVIEW**DENIED** WITH COMMENTS
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
 1. THE PLANS INDICATE AN EXISTING COOK TOP ON A 2017
 PERMIT (1710299) BUT NO GAS PERMIT WAS PULLED OR
 APPLICATION ON FILE SO THIS WILL REQUIRE A FULL REVIEW
 OF ALL APPLIANCES AND INSPECTION OF SYSTEM IN HOLE. WPB
 AMENDMENTS TO THE FBC SEC. 107.1 GENERAL PLANS AND
 APPLICATION.
  
 2. TYPE OF GAS NEEDS TO BE PUT ON ISOMETRIC AND LABEL.
 WPB AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS.
  
 3. SUBMIT MANUFACTURER?S SPECIFICATION
 SHEETS/INSTALLATION MANUAL FOR ALL GAS EQUIPMENT (STOVE
 AND DRYER) TO VERIFY COMPLIANCE WITH 2017 FBC FUEL GAS
 RES. SEC. G2408.1
 .
 4. A LISTED SHUTOFF VALVE SHALL BE INSTALLED
 IMMEDIATELY AHEAD OF EACH REGULATOR ON ISOMETRIC ON THE
 TANKLESS. 2017 FBC FG RES. SEC. G2420.4.
  
 5. REGULATORS INSTALLED ON THE EXTERIOR OF THE BUILDING
 SHALL BE APPROVED FOR OUTDOOR INSTALLATION. 2017 FBC
 FUEL GAS RES. SEC. G2421.1.
  
 6. GAS APPLIANCES SHALL BE LISTED AND LABELED. THE
 INSTALLATION MANUALS FOR ALL GAS APPLIANCES/EQUIPMENT
 SHALL BE ONSITE AT THE TIME OF INSPECTION 2017 FBC FUEL
 GAS SEC. 402.2 AND 301.3 OR 2017 FBC FUEL GAS RES. SEC.
 G2413.2 AND G2404.3.
  
 7. SUBMIT CALCULATIONS FOR COMBUSTION AIR PER THE 2017
 FBC FUEL GAS SEC. 304.1, 614.5 (RANGE) OR 2017 FBC FUEL
 GAS RES. SEC. G2407.1 AND G2439.4 (CLOTHES DRYERS).
  
 8. SUBMIT TWO COPIES OF THE APPLICABLE SIZING TABLES
 USED TO SIZE THE GAS SYSTEM OR PLACE A NOTE ON THE
 PLANS/DRAWINGS SPECIFYING WHICH SIZING TABLE(S) FROM
 THE GAS CODE OR ANOTHER STANDARD THAT WAS USED IN THE
 DESIGN OF THIS GAS SYSTEM. REFER TO THE 2017 FBC FUEL
 GAS RES. SEC. G2412.4, G2412.8, G2413.1, G2413.2, &
 G2413.3.
  
 9. SUBMIT A DETAIL SHOWING THE TYPE, LOCATION, SIZE,
 TERMINATION POINT, HEIGHT ABOVE THE ROOF AND ANCHORING
 DETAILS OF THE GAS VENT(S) PER 2017 FBC FUEL GAS RES.
 SECS. G2426 THRU G2429.1.
  
 10. SUBMIT TWO COPIES OF THE APPLICABLE SIZING TABLES
 USED TO SIZE THE GAS SYSTEM OR PLACE A NOTE ON THE
 PLANS/DRAWINGS SPECIFYING WHICH SIZING TABLE(S) FROM
 THE GAS CODE OR ANOTHER STANDARD THAT WAS USED IN THE
 DESIGN OF THIS GAS SYSTEM. REFER TO THE 2017 FBC FUEL
 GAS RES. SEC. G2412.4, G2412.8, G2413.1, G2413.2, &
 G2413.3.
  
 11. SUBMIT TWO COPIES OF A HOUSE PLAN SHOWING THE
 LOCATION OF THE TANKLESS WATER HEATER AND THE LOCATION
 AND DISTANCE OF ANY OPERABLE DOORS OR WINDOWS IN
 RELATION TO THE WATER HEATER. THE LOCATION OF THE WATER
 HEATER SHALL COMPLY WITH THE MANUFACTURER'S
 INSTALLATION INSTRUCTIONS. THE HOUSE PLAN CAN BE HAND
 DRAWN. WPB AMENDMENTS TO THE FBC SEC. 107.2.1.
 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 12. A SUB ELECTRICAL PERMIT MAY BE REQUIRED FOR THE
 SOURCE OF IGNITION, WPB AMENDMENTS TO THE FBC SEC 105.1
  
 13. A SUB PLUMBING PERMIT MAY BE REQUIRED FOR THE
 INSTALATION OF TANKLESS, WPB AMENDMENTS TO THE FBC SEC
 105.1
  
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION, MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 LUIS A. CRESPO
 PLUMBING INSPECTOR /
 PLUMBING PLAN REVIEW
 AVAILABLE FROM 1:00 PM TO 4:00 PM
 [email protected]
 561-805-6720
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2018-10-09 Cont ID  
Sent By lcrespo Date 2018-10-09 Time 07:24 Rev Time 0.00
Received By lcrespo Date 2018-10-03 Time 09:34 Sent To  
Notes
2018-10-05 09:34:22RESUB ROUTED TO LCRESPO

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-09-18 Cont ID  
Sent By lcrespo Date 2018-09-18 Time 18:14 Rev Time 0.00
Received By lcrespo Date 2018-09-17 Time 11:11 Sent To  
Notes
2018-09-18 11:11:54PLUMB <5K