| 2018-09-18 19:28:39 | 09/18/2018 1ST GAS REVIEW**DENIED** WITH COMMENTS |
| | |
| | NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS |
| | TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE |
| | GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS. |
| | |
| | 1. SUBMIT MANUFACTURER?S SPECIFICATIONS FOR THE |
| | PRESSURE REGULATORS. REGULATORS INSTALLED ON THE |
| | EXTERIOR OF THE BUILDING SHALL BE APPROVED FOR OUTDOOR |
| | INSTALLATION, 2017 FBC FUEL GAS RES. SEC. G2421.1. |
| | |
| | 2. GAS APPLIANCES SHALL BE LISTED AND LABELED, THE |
| | (FIRE PIT AND COOKTOP). THE INSTALLATION MANUALS FOR |
| | ALL GAS APPLIANCES/EQUIPMENT SHALL BE ONSITE AT THE |
| | TIME OF INSPECTION, 2017 FBC FUEL GAS RES. SEC. G2413.2 |
| | AND G2404.3. |
| | |
| | 3. SUBMIT CALCULATIONS FOR COMBUSTION AIR PER THE 2017 |
| | FBC FUEL GAS SEC. 304.1, 614.5 (COOKTOP) OR 2017 FBC |
| | FUEL GAS RES. SEC. G2407.1 AND G2439.4. |
| | |
| | 4. A GAS GRILL IS LABELED FOR OUTSIDE USE AND IT SEEMS |
| | TO BE IN A COVERED PATIO, IF SO PLEASE PROVIDE |
| | MANUFACTURES RECOMMENDATION FOR A VENTILATION HOOD, |
| | 2017 FBC FG SEC.G2408.1. |
| | |
| | 5. ON THE TWO COPIES SUBMITTED OF PLANS PLEASE SHOW THE |
| | DISTANCE OF THE TANKLESS WATER HEATER FROM EACH DOOR OR |
| | WINDOW THAT THE TABLE FOR INSTALLATION CLEARANCES OF |
| | THE RINNAI INSTALLATION MANUAL PROVIDES. THE MANUAL |
| | REQUIRES A CLEARANCE OF EITHER 4 FEET OR 12 INCHES FROM |
| | ANY OPERABLE WINDOWS OR DOORS PLEASE DRAW IT IN. WPB |
| | AMENDMENTS TO THE FBC SEC. 107.2.1. INFORMATION ON |
| | CONSTRUCTION DOCUMENTS. |
| | |
| | 6. THERE ARE TWO TANKLESS WATER HEATERS, ONE IS 199 |
| | BTU?S AND THERE WAS ONE RINNAI MANUAL SUBMITTED WHICH |
| | ONLY SHOW DOWN TO 150 BTU?S, IF THERE IS A DIFFERENT |
| | TANKLESS OF 120 BTU?S PLEASE SUBMIT AND LABEL ON PLANS |
| | OF WHICH LOCATION IS EACH IN. WPB AMENDMENTS TO THE FBC |
| | SEC. 107.2.1. INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | |
| | 7. PLEASE SUBMIT MANUFACTURERS SPECIFICATIONS FOR POOL |
| | HEATER AND THE MANUFACTURER'S SPECIFICATIONS FOR THE |
| | POOL HEATER SHALL BE ONSITE FOR FINAL GAS INSPECTION. |
| | WPB AMENDMENTS TO THE FBC SEC. 107.2.1. INFORMATION ON |
| | CONSTRUCTION DOCUMENTS. |
| | |
| | 8. PLEASE SUBMIT MANUFACTURERS SPECIFICATIONS FOR |
| | GENERATOR AND THE MANUFACTURER'S SPECIFICATIONS FOR THE |
| | GENERATOR SHALL BE ONSITE FOR FINAL GAS INSPECTION. THE |
| | GENERATOR SHALL BE LISTED AND APPROVED. NFPA 58 SEC. |
| | 5.20.1. THE GENERATOR SHALL MEET THE REQUIREMENTS OF UL |
| | 2200. WPB AMENDMENTS TO THE FBC SEC. 107.2.1. |
| | INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | |
| | 9. THE GENERATOR SHALL BE ONE FOOT SIX INCHES (1?-6?) |
| | FROM THE HOUSE, FIVE (5?-0?) FROM THE PROPERTY LINE, |
| | EXHAUST SHALL BE TEN (10?-0?) FROM ANY OPENING UNLESS |
| | OTHERWISE STATED IN THE MANUFACTURES SPECIFICATION |
| | INSTRUCTIONS. WPB AMENDMENTS TO THE FBC SEC. 107.2.1. |
| | INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & |
| | REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION, MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |